Professional Documents
Culture Documents
To provide an even more comprehensive transformer monitoring solution, the HYDROCAL 1001+
analyses additionally the content of moisture (H2O) in the transformer oil.
The integration of 6 relevant key gases into a total weighted gas concentration and the measurement
of moisture in oil, enables the HYDROCAL 1001+ to react to most transformer faults and makes the
unit to a compact and cost effective tool used in particular for early transformer fault detection and
preventative maintenance.
The HYDROCAL 1001+ is equipped with 2 analog 0/4 ... 20 mA outputs for the dissolved composite
gas-in-oil and moisture in oil analysis results and 4 digital relay outputs (Gas high alarm, gas high-
high alarm, moisture alarm and function alarm)
Key advantages:
Composite measurement of hydrogen (H2), carbon monoxide (CO), methane (CH4), acetylene
(C2H2), ethylene (C2H4) and ethane (C2H6) and dissolved moisture (H2O) in the transformer oil
Relay outputs with light indicators showing potential alarms
Easy and fast installation without any operational interruption of the transformer
It provides communication interfaces ETHERNET 10/100Mbit/s (copper-wired or fibre-optical) and
RS485 to support proprietary communication protocols and to be prepared for sub-station com-
munication protocols MODBUS®TCP and MODBUS® serial RTU/ASCII
The construction has been significantly simplified and size has been reduced compared to other
products in the market period.
Note: On the installation position a good and continuous oil circulation must be present.
Never use or stock chemicals with hydrocarbon contents near the meas-
uring sensor.
Never clean the HYDROCAL unit with solvents, because its gases will strongly
impair the measurement accuracy and the sensitivity of the sensors.
Never operate the HYDROCAL unit on a valve that is closed for a long
period of time. Remove the unit if this cannot be avoided. Please refer to
the de-installation instructions.
Never install the HYDROCAL unit on the suction side of the cooling
pump!!
Attention!!!
Faulty or inappropriate handling of the connection unit, like malfunction
by negative pressure, paint or solvent liquids make the warranty invalid.
Note: The thread depth of the threaded flange or the connection adapter should be at least 25 mm.
2.3.1.2. Fitting with union nut
We recommend installing the HYDROCAL unit with a fitting with union nut (flat sealing) to the trans-
former gate / valve. This fitting consists of a threaded flange, a flat sealing union end and a union nut.
In this case the union nut must be rotated to fix the HYDROCAL unit and a gasket is used to seal the
connection. An additional thread sealing with thread seal tape or thread sealant is not or rarely nec-
essary in this case.
Note: Ball valves with union nut are also available (pump ball valve).
Attention !!!
If you use Teflon tape for sealing the connection thread,
nothing can be adjusted after wards.
!!!! Risk of leakage !!!!
Attention !!!
Please follow the instructions of the manufacturer!!!
Note: In case there are strong vibrations on the connection valve, the valve should be relieved by a
support.
A good oil flux should exist on the installation position. If necessary, use a reduction piece (adapter).
In order to have a sufficient oil flux on the membrane, the diameter of the valve should be not less
than 25 mm. For optimal working conditions, the valve diameter should not be more than 76 mm. The
valve must be on earth potential.
Attention!!!
The distance between the oil main stream and the backplate unit shall not
be more than 6 times the length of valve diameter.
(Distance 150 mm at Valve- 25 mm / Distance 228 mm at Valve- 38 mm /
Distance 300mm at Valve- 50 mm / Distance 450mm at Valve- 76 mm).
The connection thread can be sealed and fixed using either a thread seal tape or a thread sealant.
Attention!!!
Always open the aeration screw first!!!
Attention!!!
Only remove the protection cap (slowly while turning) when to aeration
screw is open and you are ready to mount the HYDROCAL unit!
Then mount the unit according to the following steps (sequence description with Teflon tape):
Clean the inside of the threaded flange with a dry cleaning rag or paper towel.
Clean the outer thread of the connection unit with a dry cleaning rag or paper towel. Remove
any remaining of thread sealing tape completely from the threads. For persistent remaining
you can use the brass brush or use white spirit (pure alcohol). White spirit must dry out com-
pletely before proceeding.
Wrap 3 to 15 layers of Teflon tape (depending on the tolerance of the two threads) clockwise
(rear view) tightly around the connection thread of HYDROCAL unit. The first thread should
remain free.
Place the HYDROCAL unit horizontally to the threaded flange. Make sure that the unit is lev-
eled.
Turn in the HYDROCAL unit 2 to 3 turns clockwise by hand to the threaded flange.
Now turn in the HYDROCAL unit for another 5 to 6 turns clockwise using a tin spanner M55 or
adjustable tin spanner 1 ½“ and stop when the aeration screw is at about 9 o`clock.
Note: If the turn in was possible without major effort, too less Teflon tape was used. Turn out the
unit, remove Teflon tape completely and perform the installation again.
HYDROCAL 1001+ Installation and operation manual Page 11/76
Now align the unit clockwise until the position of the aeration screw is at 12 o`clock. Make
sure that the unit is tight in this position.
Note: The alignment of the unit must be only clockwise. Once the unit is turned counterclockwise
during the alignment, the installation procedure must be performed once again! Risk of oil leak-
age!
Attention !!!
Do not exceed 12 o`clock position!
Otherwise you have to remove the HYDROCAL unit, completely remove
the Teflon tape from the connection thread and perform the installation
procedure again!
Attention !!!
The following steps must be done according to the company procedures.
Work carefully in order to prevent air entering into the transformer. Use a
bucket to catch the leaking oil
Slowly open the transformer valve until oil runs out of the provided hole. Collect the leaking oil
with a bucket.
Close the aeration screw as soon as no air bubbles sort the provided hole.
Now open the transformer valve completely.
Remove thoroughly the oil residues with a dry cleaning rag or paper towel from the unit.
Attention !!!
Do not use solvents for cleaning!
Attention!!!
Always open the aeration screw first!!!
Attention!!!
Only remove the protection cap (slowly while turning) when to aeration
screw is open and you are ready to mount the HYDROCAL unit!
Clean the inside of the union nut with a dry cleaning rag or paper towel.
Clean the outer thread of the connection unit with a dry cleaning rag or paper towel. Remove
any remaining of thread sealing tape completely from the threads. For persistent remaining
you can use the brass brush or use white spirit (pure alcohol). White spirit must dry out com-
pletely before proceeding.
Place the HYDROCAL unit horizontally to the fitting. Make sure that the unit is leveled and the
gasket inserted.
Attention !!!
Make sure that the gasket is inserted
between HYDROCAL unit and fitting.
Turn in the union nut by hand to the external thread of the connection unit.
Now align the unit until the position of the aeration screw is at 12 o`clock.
Attention !!!
Do not use solvents for cleaning!
Check after 30 minutes if the threaded connection is tight (no leakage).
For feed through, following cable gland must be used for all cables:
1x M20 SKINTOP® cable gland (Clamping range 7,0 ... 13,0 mm)
1x M25 SKINTOP® cable gland (Clamping range 9,0 ... 17,0 mm)
Attention !!!
For cables with a smaller diameter please use reducing seal inserts to
provide clamping and sealing!
Note: The unit comes with 2 SKINTOP® cable glands (M20 and M25) from the factory!
Copper wire:
Recommendation for Ethernet communication cable (copper):
Cable type: Ethernet cable Cat. 5e with RJ45 connector
Cable diameter : 6,3 mm
Fibre optical:
Recommendation for Ethernet communication cable (fibre optical):
®
Cable type: HITRONIC HQN 1000 Multimode G4 62,5/125 with SC Duplex connector
Cable diameter : 6,5 mm
Bending radius: min. 15 x Ø
RS485 interface:
Recommendation for RS485 interface communication cable:
Cable type: UNITRONIC® BUS LD FD P cable 1x2x0.25 mm2, shielded, purple
Cable diameter : 6,2 mm
Note: To check the correct regulation of the back plate heating use Hydrosoft - Online Sensors - and
check the back plate temperature T2.
DC Version
Plus conductor: +
Protection earth: PE
Minus conductor: –
Note 1):
120 V 120 V -20% = 96 Vmin 120 V +15% = 138 Vmax
230 V 230 V -20% = 184 Vmin 230 V +15% = 264 Vmax
[13] Jumper J1 – Function relay contact (when system is okay, relay is switched on )
The function relay output can operate as a closing or opening contact. The configuration is
selected by the jumper J1, which is located near the connection terminal X2:8:
J1:1-2 Pos. 1 Contact is open, when relay is switched on (Normally Closed)
J1:2-3 Pos. 2 Contact is closed, when relay is switched on (Normally Open)
Icon Description
The solid-state relay varies between supply voltage type (AC and DC):
For AC supply voltages the solid-state relay crydom D2410 AC 10 A is used (left).
For DC supply voltages the solid-state relay crydom D5D07 DC 7 A is used (right).
The wiring for the heating resistors varies between supply voltage value (120 V and 230 V):
Wiring heating resistors for 230 VAC / 230 VDC (3.5.1)
Wiring heating resistors for 120 VAC / 120 VDC (3.5.2)
Note: The solid-sate relay must correspond to the supply voltage type (AC or DC)!!!
Note: The solid-sate relay must correspond to the supply voltage type (AC or DC)!!!
The HYDROCAL 1001+ does not have a graphical display but is equipped with two user interfaces:
External user interface (4.2)
Internal user interface (4.3)
Note: The signification of the LED status you can find in the following tables of the external user in-
terface LED.
The multicolor function LED illustrates the status of the internal system monitoring as follow:
Description
System monitoring not active
System monitoring active - system okay - relay switched on
- not defined -
System monitoring active - system has monitored an error - relay switched off
As the alarms for gas concentration (absolute, daily- and weekly trend) can be present in parallel the
individual status of the gas LED is illustrated as following patterns:
Note: In order to simplify the illustration in the pattern table the level 1 (High) alarm is named as 1
and level 2 (High-High) alarm as 2. No alarm active is named as 0.
weekly
trend
trend
daily
0 0 0 -
1 0 0 -
2 0 0 -
0 1 0
0 2 0
1 1 0
1 2 0
2 1 0
2 2 0
0 0 1
0 0 2
1 0 1
1 0 2
2 0 1
2 0 2
0 1 1
0 1 2
0 2 1
0 2 2
1 1 1
1 1 2
1 2 1
1 2 2
2 1 1
2 1 2
2 2 1
2 2 2
Note: The standard settings for gas concentration daily trend alarm (High-High) are:
Level 1: 50 Level 2: 100
Delay 1 [s]: 43200 or 12:00:00 Delay 2 [s]: 86400 or 1-0:00:00
Action 1: Output,Hold Action 2: Output,Hold
Note: The standard settings for gas concentration weekly trend alarm (High-High) are:
Level 1: 100 Level 2: 200
Delay 1 [s]: 86400 or 1-0:00:00 Delay 2 [s]: 172800 or 2-0:00:00
Action 1: Output,Hold Action 2: Output,Hold
Note: The standard settings for moisture concentration alarm (High) are:
Level 1: 10
Delay 1 [s]: 7200 or 2:00:00
Action 1: Output,Hold
These settings can be modified in Hydrosoft -> Alarm setup.
During special operations the LEDs are used in another manner to reflect the status or progress of
the related task.
The icons of the single color LEDs (green or red) have the following signification:
Icon Description Color sequence
Green LED permanently off -
Green color permanently on -
Note: The signification of the LED status you can find in the following tables of the internal user inter-
face. The speed of the toggling or flashing LEDs varies and is defined with e.g. (~1 s on / ~1 s off).
The Ethernet communication interface is represented by a red- and a green single color LED.
The LEDs illustrates the status of the Ethernet communication interface as follow:
Description
Ethernet interface not active
Ethernet interface active
Ethernet interface deactivated - MAC address not configured
red flashing on - on receive; green shortly off - on transmit
red flashing (~½ s on / ~½ s off) - no cable connected
green and red flashing (~½ s on / ~½ s off) - Request IP-address via DHCP
- not defined -
The RS485 communication interface is also represented by a red- and a green single color LED.
The LEDs illustrates the status of the RS485 communication interface as follow:
Description
No transmission
Green shortly flashing on transmit
Red shortly flashing on receive
- not defined -
The status and the actual value of the analog output are represented by a red- and a green single
color LED.
The LEDs illustrates the status and the actual value of the analog output as follow:
Description
The HYDROCAL unit contains an additional LED bar level monitoring to give the user a rough over-
view of the absolute gas concentration, gas concentration daily trend and gas concentration weekly
trend. It is completely independent form the alarm level monitoring and is visualized with 1 green-
and 3 red single color LEDs. The gas concentration absolute, gas concentration daily trend and gas
concentration weekly trend have each 3 configurable levels (level 1 ... 3) but their status will be illus-
trated with the same 4 LEDs.
The LEDs illustrates the status of the gas concentration absolute as follow:
Description
As the levels for gas concentration (absolute, daily- and weekly trend) can be reached in parallel the
individual status of the LEDs is illustrated as following color sequences:
Note: To keep it as simple as possible the levels of the gas concentrations (absolute, daily- and
weekly trend) are specified as follow in the color sequence tables:
0 < Level 1 (Level 1 not reached)
1 < Level 2 (Level 1 reached)
2 < Level 3 (Level 2 reached)
3 ≥ Level 3 (Level 3 reached)
weekly
trend
trend
daily
0 0 0
1 0 0
2 0 0
3 0 0
0 1 0
0 2 0
0 3 0
weekly
trend
trend
daily
0 0 1
0 0 2
0 0 3
0 1 1
0 1 2
0 1 3
weekly
trend
trend
daily
0 2 1
0 2 2
0 2 3
0 3 1
0 3 2
0 3 3
weekly
trend
trend
daily
1 1 0
1 2 0
1 3 0
2 1 0
2 2 0
2 3 0
weekly
trend
trend
daily
3 1 0
3 2 0
3 3 0
1 0 1
1 0 2
1 0 3
weekly
trend
trend
daily
2 0 1
2 0 2
2 0 3
3 0 1
3 0 2
3 0 3
weekly
trend
trend
daily
1 1 1
1 1 2
1 1 3
1 2 1
1 2 2
1 2 3
weekly
trend
trend
daily
1 3 1
1 3 2
1 3 3
2 1 1
2 1 2
2 1 3
weekly
trend
trend
daily
2 2 1
2 2 2
2 2 3
2 3 1
2 3 2
2 3 3
weekly
trend
trend
daily
3 1 1
3 1 2
3 1 3
3 2 1
3 2 2
3 2 3
weekly
trend
trend
daily
3 3 1
3 3 2
3 3 3
Note: The standard settings for LED bar level gas concentration absolute are:
Level 1: 100 Level 2: 500 Level 3: 1000
Note: The standard settings for LED bar level gas concentration daily trend are:
Level 1: 10 Level 2: 50 Level 3: 100
Note: The standard settings for LED bar level gas concentration weekly trend are:
Level 1: 10 Level 2: 50 Level 3: 100
These settings can be modified in Hydrosoft -> Settings -> LED Bar Levels.
The HYDROCAL unit contains an additional LED bar level monitoring to give the user a rough over-
view of the moisture concentration. It is completely independent form the alarm level monitoring and
is visualized with 1 green- and 2 red single color LEDs. The moisture concentration has 2 configura-
ble levels (level 1 ... 2) and their status will be illustrated with the 3 LEDs.
The LED bar levels for moisture concentration are illustrated as follow:
Description
Moisture sensor not active - measurement function stopped
Moisture concentration < Level 1
Moisture concentration < Level 2
Moisture concentration ≥ Level 2
Moisture sensor active - error
Note: The standard settings for LED bar levels moisture concentration are:
Level 1: 10 Level 2: 20
These settings can be modified in Hydrosoft -> settings -> LED Bar Levels.
Supply voltage on
a
a b
b
a
a
A firmware download operation being in progress is indicated by the following special LED pattern (3
red LED are turned on and 1 green LED is circulating clockwise):
a
a
a
a b
b c
c
To invoke the functional test press and hold the reset button until 1+5 beeps have occurred (the 1st
short beep is committing the pressed button, pause, then 4 short beeps and the last beep is longer to
inform of commitment).
Start a
a b
b c
c d
h’ i
h’’ i
i j
j k
k l
l m
m End
Note: After this sequence all present alarms will be automatically acknowledged.
To invoke the test mode press and hold the test button until 1+5 beeps have occurred (the 1st short
beep is committing the pressed button, pause, then 4 short beeps and the last beep is longer to in-
form of commitment).
Note: After invoking the test mode the first test cycle (Test gas concentration - Start) is automatically
entered.
The active test mode is illustrated with the following special LED pattern on the LED bar level – Gas:
LED bar level – Gas
a b
b a
Current
Step Description
[mA]
Current
Step Description
[mA]
Description Relay-
Step
Jumper J1 on Pos. 1 (J1:1-2) contact
Description Relay-
Step
Jumper J1 on Pos. 1 (J1:2-3) contact
Relay-
Step Description
contact
d
IV - Test Gas high-high alarm
Relay-
Step Description
contact
e
V - Test Moisture alarm
Relay-
Step Description
contact
End
VI - Return to normal operation
Note: The test mode is also terminated automatically 15 minutes after the last button operation. To
terminate the test mode prior press and hold both buttons until 1+3 beeps have occurred.
PRESS & HOLD RELEASE
To invoke the communication interface reset press and hold the reset button until 1+5 beeps have
occurred (the 1st short beep is committing the pressed button, pause, then 4 short beeps and the last
beep is longer to inform of commitment). Immediately after the long commitment beep press and hold
the test button until 1+5 beeps have occurred (the 1st short beep is committing the pressed button,
pause, then 4 short beeps and the last beep is longer and oscillating to inform of commitment).
Note: The setup is only changed temporarily. In order to make permanent changes to the communi-
cation interface setup, a connection has to be established and the requested setup has to be sent to
the unit. To return to normal operation a reset of the unit is required.
Ethernet
DHCP activated (DHCP Client)
Port: 49152
IP: (192.168.1.32)
Mask: (255.255.255.0)
Gateway: (192.168.1.1)
Note: The TCP/IP settings (in brackets) are not used as the DHCP mode is activated.
PC
IP address: 192.168.0.2
Network mask: 255.255.255.0
Port number: - only needed in Hydrosoft -
Other settings can be used but a working configuration must obey the following rules:
The network mask must be identical on PC / HYDROCAL (e.g. 255.255.255.0)
The IP address must be identical in the first 3 dot-separated numbers (e.g. 192.168.0)
The 4th number of the IP address must be different (e.g. 1 and 2)
The port number must not be 0, 80 (HTTP) or 502 (MODBUS® TCP) (e.g. 49152)
Note: Other settings are also valid but are not in the scope of this description.
When a point-to-point connection is required a manual tuning of the network adapter is needed. Us-
ing the configuration dialogs offered by the Windows Control Panel the settings of the network adapt-
er must be edited.
Note: The screen shots are taken form a PC running under an English (US) Windows 7 operating
system. The paths to open the described dialogs are one way - alternate ways exist but are not de-
scribed here. The older systems (Windows Vista and XP) also have the related dialogs - the path to
get there is different, but the settings at the detail dialog level are the same - a good way to start for
the network dialog search is always the control panel that exist in all windows versions.
The list of available network adapters appears. Depending on the configuration of the PC one or
more items may be present. The network adapter used to connect to the HYDROCAL must be se-
lected.
HYDROCAL 1001+ Installation and operation manual Page 60/76
4.5.2.2. Changing the Network Adapter Properties
Do a right-click on the network adapter to bring up the context menu and choose the bottom level
entry (Properties). The properties page for the network adapter is coming up.
Click into the list in the middle of the dialog and highlight the entry for Internet Protocol Version 4
(TCP/IPv4). Next click the Properties button.
In the up-coming dialog activate the Alternate Configuration tab - (leave the General tab settings un-
changed).
IP Address: 192.169.0.1
TCP Port: 49152
Note: The Access via field must remain empty
(only used in dial-up networks).
The IPv4 Address and Subnet Mask must show the values of the alternate setup (4.5.2.2).
Under some circumstances it may take some time until the PC changes to the alternate setup. If a 2-
3 minutes time of waiting does not change the status a reboot of the PC may be helpful.
To invoke PING open the start menu und type cmd into the edit field at the bottom (a greyed text
Search programs and files is shown in the field on entry). Start the command interpreter cmd (also
called DOS window) by pressing enter.
In the command interpreter type the following and execute by pressing enter.
ping 192.168.0.1
The screen shot shows a successful PING - the unit answers. If the unit does not answer and the PC
settings are correct try a reboot of the HYDROCAL device. Optionally execute the Communication
Interface Reset (4.3.3) again.
4.6.1.1. Point-to-Point
The point-to-point setup is used for a communication between PC to one HYDROCAL unit. Please
perform following configuration:
Note: The proprietary HYDROCAL protocol allows only configuration of the baud rate. The settings
of the Data Bits, Parity and Stop Bits are fixed to 8-N-1.
Note: As soon the address is unequal 0, the bus node is activated automatically. The proprietary
HYDROCAL protocol allows only configuration of the baud rate. The settings of the Data Bits, Parity
and Stop Bits are fixed to 8-N-1.
Note: A unique address (1...247) has to be entered for each unit in the RS485 bus. Actually up to 32
units can be present in the same RS485 bus. Change of the transmission mode does not set the cod-
ing format parameters to the default values for the selected mode (RTU: 19200-8-E-1; ASCII: 19200-
7-E-1). The right configuration has to be performed manually.
Note: A unique address (1...247) has to be entered for each unit in the RS485 bus. Actually up to 32
units can be present in the same RS485 bus. Change of the transmission mode does not set the cod-
ing format parameters to the default values for the selected mode (RTU: 19200-8-E-1; ASCII: 19200-
7-E-1). The right configuration has to be performed manually.
4.6.2.1. Static IP
The network settings can be obtained from your corresponding system administrator!
IP Address
Mask (The setting 255.255.255.0 can be used in general)
Gateway (Normally the automatic assigned setting can be used)
TCP Port Number The TCP port number should be determined by the system administrator as
well. The free range for TCP port numbers is: 49152 ... 65535. Theoretically the
unit allows the following settings: 1 ... 65535. However several TCP port num-
bers are reserved for other applications for example HTTP, FTP, Mail, etc.
By using this setting, the unit obtains the network settings from the DHCP server which is responsible
for the network administration. In this case only the port number can be entered. The network admin-
istrator must allow the automatic TCP/IP address assignment for HYDROCAL in the network
The data in the tree structure which is newly created or modified has to be stored with the
button then. It appears a star right to the symbol which indicates us that a
change was performed and that the data still has to be transferred to the unit. In this moment the
data is unequal and will be aligned with the HYDROCAL unit on the next connection (see Hydrosoft
manual).
Note: Function, Register and Address Mapping is also valid for MODBUS serial.
Safety CE certified
Isolation protection: IEC 61010-1:2002
Degree of protection: IP-55
Measurements
Gas-in-oil measurement
Measuring quantity Range Accuracy 2) 3) TDCG-Contribution
TDCG 0 ... 5.000 ppm ± 15 % ± 20 ppm
Hydrogen H2 ± 10 % ± 15 ppm approx. 20 %
Carbon Monoxide CO ± 20 % ± 25 ppm approx. 30 %
Methane CH4 ± 20 % ± 25 ppm <5%
Acetylene C2H2 ± 20 % ± 25 ppm 100 %
Ethylene C2H4 ± 20 % ± 25 ppm approx. 32 %
Ethane C2H6 ± 20 % ± 25 ppm <5%
Moisture H2O 0 ... 100 ppm ±3% ± 3 ppm
Measurement cycle 20 min
Analog and digital outputs
2 x Analog DC output
Type Control range Default function
(free assignment)
1 x Current DC 4 ... 20 mADC TDCG -Concentration
1 x Current DC 4 ... 20 mADC Moisture in oil concentra-
tion
4 x Digital outputs
Type Control voltage Max. switching capacity
4)
4 x Relay 12 VDC 220 VDC/VAC / 2 A / 60 W