Professional Documents
Culture Documents
Cired2005 0383
Cired2005 0383
Summary Introduction
SF6 insulated RMUs are designed and tested for operation Gas-insulated medium-voltage switchgear is a long-life
in severe environmental conditions and have proven its capital good and an integral part of modern power
reliability on thousands of units in service since 1983. distribution systems.
International standards give only limited recommendations
This type of switchgear is an environmentally compatible
of how to test switchgears for special and severe
product in comparison with conventional switchgear,
environmental conditions and which risks have to be
mainly because of
considered for an expected life time of more than 30 years.
- small switchgear design,
To accumulate field experience, tests are carried out on - no maintenance is required,
switchgears which were operated up to 20 years in different - long life time and
regions in the world. Such tests include e.g. dielectric tests, - minimal requirements for the installation room.
mechanical tests or dew point measurements inside the SF6
RMUs [1] came into the market in 1983 and have been in
compartments.
service under severe environmental conditions in many
One of the examined 24kV-RMU was in service countries e.g. in Indonesia, the Middle East or in Norway
continuously from 1985 to 2000 on the south west coast of since then.
Norway with salty atmosphere and has been used since
RMUs for long time operation in severe environmental
2000 also in sandy and traffic atmosphere after moving in a
conditions have to be specially designed and tested.
substation for temporary installation.
International standards give only limited recommendations
The investigations were performed in July/August 2004 in of how to test the switchgear for special and severe
the Testing Laboratory Medium Voltage Frankfurt am environmental conditions and which risk have to be
Main, Germany. considered.
In detail, the following tests were carried out: Therefore it is necessary
- to have a proper design with less inherent risks,
- Checking the condition of the gas.
- to use excellent and proven materials and manufacturing
- Checking the condition of the electrical contacts. techniques, even though it is partly more expensive,
- to perform additional tests to verify the long time
- Dielectric tests including partial discharge measurement.
behaviour of switchgear and to compare the results with
- Mechanical tests. field experience,
- to control and improve the design and manufacturing
- Visual inspection on the SF6-vessel and mechanical as a continuous process.
parts, e.g. for corrosion.
The examination showed a good condition of the primary Some of the additional tests are:
circuit, the SF6-tank and the other materials. The insulating- - Measurement of permeation of water vapour through
gas itself has got minimal humidity with a dew point of less insulating and tightening materials.
than -30°C. - Dew point measurements at switchgears after years of
operation in severe environmental conditions.
Out of this examination we can derive a conclusion that the - Temperature cycle test on bushings and other insulating
RMU will have an expected life time which is much longer parts for investigation of internal mechanical stresses.
than 30 years. It also shows that the chosen design and the - Ageing tests according to IEC 60932 [6] for complete
intensive aging tests, e.g. according to IEC 60932 are switchgear panels.
suitable to prove the long time behaviour for switchgear in - Intensified temperature/humidity cycle tests for corrosion
severe environmental conditions. investigation on mechanical parts.
CIRED2005
Session No 1
CIRED 18th International Conference on Electricity Distribution Turin, 6th to 9th June 2005
Classification of environmental conditions and Risks of operation for medium voltage switchgear
environmental tests in the standards in severe environmental conditions
CIRED2005
Session No 1
CIRED 18th International Conference on Electricity Distribution Turin, 6th to 9th June 2005
Basic design
Fig. 1 shows the sectional view of a typical 8DJ RMU with
the main components.
The heart of the switchgear is the gas-filled “sealed-for-
life” compartment with the switching devices, bars,
electrical and mechanical bushings. To avoid any tightness
problems, the vessel is made of stainless-steel and
completely welded without any sealed openings. Fig. 1 Sectional view of a 8DJ RMU
Metal bellows are used as mechanical bushings for 1 Upper bushing for the HV HRC fuse assembly
operating the three-position switch as well as the SF6 2 Connecting bars in the switchgear vessel
ready-for-service indicator, which is moved by a magnetic 3 Three-position switch disconnector with
system at both sides of the vessel wall. The electrical make proof earthing function
bushings for cable connections are made of epoxy cast 4 Switchgear vessel, hermetically welded
resin and completely welded into the vessel. and filled with SF6 gas
6 Transport lug
The pressure relief device is also welded into the vessel.
7 HV HRC Fuse box
Even the pipe for evacuating and filling the gas
8 Grip at sealing cover for handling the
compartment with SF6 is welded after the tightness test and
HV HRC fuse box
the filling procedure.
9 Cover of HV HRC fuse assembly
Securing the insulation properties 10 Operating mechanism for the three-position
switch disconnector
Besides securing the tightness of the gas compartment and 11 Control board
avoiding of inadmissible permeation of water vapour into 12 Detachable lever mechanism
it, one important task is to minimize internal mechanical 13 Bushing for cable connector
stresses within the components of the gasinsulated 14 Cable plugs
enclosure. If internal mechanical stresses are superimposed 15 Cable connection compartment
with normal service stresses and ageing, cracks can occur 16 Cable compartment cover
in the insulating components, partly after years. 17 Cable brackets
Consequently, partial discharges, break downs and leakage
may occur.
CIRED2005
Session No 1
CIRED 18th International Conference on Electricity Distribution Turin, 6th to 9th June 2005
Therefore the gas compartment is made of tough stainless materials and surfaces for mechanical parts.
steel with bushings containing a minimum of cast resin. On the other hand, the transfer of test results of high duty
The selected special composition of cast resin, the short time corrosion tests to the long time behaviour of the
automatic mixing process and several routine tests after switchgear cannot be made easily because of special
manufacturing ensure that components have very low conditions at the different switchgear locations.
internal mechanical stresses.
RMUs which came back to the factory after years of
Some of the routine tests are service at tropical and coastal areas, in substations with
- X-ray test for cracks and shrinking holes, water in the cable duct or in open air installation were
- partial discharge measurement, investigated with regard to corrosion effects.
- temperature cycle test from – 40°C up to + 80°C
The results were compared to the above mentioned
on a certain amount of bushings.
corrosion tests showing that the most severe climatic duty
Partial discharge measurements results from frequent dewing in the switchgear at high
ambient temperatures. A common rule of chemistry says
Partial discharges within polymeric materials and on
that an increase of temperature of about 10K makes the
surfaces can cause electrical treeing and deterioration of
corrosion speed double.
insulating properties (electrical ageing).
The current knowledge about the effects of partial Derived from experience, there has been defined an
discharges is not sufficient for standardizing common intensified temperature/humidity cycle test similar to IEC
technical limits. 60068 series for further improving of the switchgear with
- temperature cycle from - 5°C up to + 80°C,
Therefore there has been set up an own standard with the
- at a relative humidity of 93%,
basic requirement that during normal service no partial
- 12 cycles with a cycle time of 24 hours.
discharge should occur.
This test was carried out on “normal” and “improved”
Limits for partial discharge rates: driving mechanisms with test results as follows:
Components Complete
switchgear - Corrosion effects as known from the practical experience
at 1.1 Ur ≤ 5pC ≤ 20pC of operation in very severe environmental conditions
at 1.1 Ur/√3 partial discharge free appear after 3 to 5 temperature/humidity cycles.
(lower than the ground level) - After having performed about 12 cycles the corrosion is
much stronger than known from real switchgear
The test procedure is in accordance with IEC 62271-200. observation.
The experience of more than 20 years of gas-insulated MV- - The improved type of driving mechanism at which all
switchgear in service confirms that these limits are well parts are zinc-coated and have a special surface treatment
chosen from the practical point of view. Compared with do not show any significant corrosion effects after 12
standards of other high voltage equipment, e.g. power cycles.
transformers or instrument transformers, this standard is
very demanding. - After the temperature/humidity cycle test all investigated
improved drives operate without any objections from the
Ageing test according to IEC 60932 test engineers.
The RMUs have passed this ageing test and are classified
as ”design class 2”, applicable for severe climatic Securing the tightness of the gas compartment
conditions. At the driving mechanisms of the switching minimizing the permeation of water vapour
devices no significant corrosion occurred. The moving Especially the concept of the “hermetically sealed
characteristics of the mechanisms were not changed. enclosure” with the completely welded stainless-steel
vessels prevents inadmissible diffusion of insulating gas to
Securing the reliability of the driving mechanism the outside and ingress of water vapour to the inside.
Since the relevant switchgear standards give no To ensure the high quality, the following tests are used:
requirements concerning the long time behaviour in severe
environmental conditions, these capabilities are verified by - 100% leakage test with helium of all components before
welded in with a permissible leakage rate of 10-7mbarl/s
- condensation tests according to DIN 50017,
- Integral leakage measurement with 1 bar helium of the
- condensation tests with SO2 acc. to DIN EN ISO 6988, complete gas compartments with a permissible leakage rate
- salt fog test according to DIN 50021, of 10-6mbarl/s; this means a pressure reduction of the
insulating gas is far less than 0.1 % per year.
- intensified temperature/humidity cycle tests similar
to IEC 60068-2-30. - To ensure the stability of the gas vessel due to the daily
pressure fluctuations, pressure changing tests with 10 000
The purpose of these tests is to find out the most suitable load cycles have been carried out on typical arrangements
CIRED2005
Session No 1
CIRED 18th International Conference on Electricity Distribution Turin, 6th to 9th June 2005
with a leakage test at the end of the tests. in service continuously from 1985 to 2000 on the south
west coast of Norway with salty atmosphere and has been
- Measurements of permeation rates were made with
used since 2000 also in a sandy and traffic atmosphere after
components, e.g. bushings. In order to accelerate the
moving in a substation for temporary installation.
permeation velocity, the test objects were stored in a
climatic chamber at a temperature of 80°C and a relative The substation was installed in a normal distribution
humidity of 85%. This corresponds to a partial pressure of network. During its lifetime the three-position switch of the
water vapour of about 400 mbar. The permeation 8DJ10 was operated only a few times.The ring-main
coefficient was determined by measuring the pressure rise feeders normally will be operated after faults in the
in the small compartments of the test objects. By means of network, e.g. for selection of earth faults. The trans-former
these test results, the water vapour permeation for e.g. feeder will be operated for maintenance of the transformer
tropical climate can be calculated. or for works on the LV compartment of the substation.
- Dew point measurements were carried out on several The switchgear was manufactured at the Switchgear
panels of 8DJ load break switchgear which came back to Factory in Frankfurt am Main, the Siemens Centre of
the switchgear factory after years of operation. The Competence for gas-insulated medium-voltage switchgears.
measured dew points were all below -30°C. The
Test results
measurements confirm the above mentioned test and
calculation results of water vapour permeation. The investigations were carried out in July/August 2004 in
the Testing Laboratory Medium Voltage Frankfurt am
Main, Germany which is independent and has been
Examination of a RMU after 19 years of service in accredited by DATech (German Accreditation Body
Norway Technology) and PEHLA according to the standard
Transformer Substation with RMU ISO/IEC 17025.
A typical substation used in Norway in 1985 is shown in Dielectric tests including partial discharge measurement
Fig. 2, which also was used for the examined RMU.
High-voltage tests were performed with the uncleaned
RMU according to DIN EN 60271-200 [3] with 80% of the
test voltages for factory new switchgears:
- Power frequency voltage test 50 Hz, 40 kV / 1 min.
between phases and to earth and across the contact gap
CIRED2005
Session No 1
CIRED 18th International Conference on Electricity Distribution Turin, 6th to 9th June 2005
Conclusion
As a result of this examination we can derive the
conclusion that the RMU from Siemens will have an
expected life time which is much longer than 30 years. It
also shows that the chosen design and the intensive ageing
tests, e.g. according to IEC 60932 are suitable to prove the
long time behaviour for switchgear in severe environmental
conditions.
The know-how obtained from the accumulated field
experience and the tests described in this paper are an
integral part of the continuous improvement of the product
development process and the life cycle management for
medium-voltage switchgear.
Fig. 3: Driving mechanism of a ring-main feeder
References
Checking the condition of the insulating gas
[1] www.siemens/medium-voltage-switchgear
The gas pressure was 0,5 bar (gauge), which corresponds to [2] IEC 60694 Common clauses for high-voltages
rated filling pressure of a new switchgear panel. The dew- switchgear and controlgear standards
point of the gas was less than – 30 °C, comparable to a new [3] IEC 62271-200 AC metal-enclosed switchgear and
switchgear. controlgear for rated voltages above 1 kV and up to and
including 52 kV
Checking the conditions of the electrical contacts [4] IEC 60721 Series Classification of environmental
The electrical contacts were inspected visually and showed conditions
no sign of erosion. The three-position switch-disconnectors [5] IEC 60068 Basic environmental testing procedures
and the connecting bars showed no ageing; see fig. 4. [6] IEC 60932 (Report) Additional requirements for
enclosed switchgear and controlgear from 1 kV
Inspection of the SF6-vessel and mechanical parts to 72.5 kV to be used in severe climatic conditions
The visual inspection showed traces of corrosion on the
external part of the vessel in the welding area. This is only
superficial corrosion. The corrosion is completely
removable by polishing the surface.
CIRED2005
Session No 1