TrueAlarm Sensors

Features 4098-9733 Heat Sensor


Sealed against rear air flow entry TrueAlarm heat sensors are self-restoring and provide rate
Interchangeable mounting compensated, fixed temperature sensing, selectable with
EMI/RFI shielded electronics or without rate-of-rise temperature sensing. Due to its
small thermal mass, the sensor accurately and quickly
Heat sensors:
measures the local temperature for analysis at the fire
 Selectable rate compensated, fixed temperature alarm control panel.
sensing with or without rate-of-rise operation
 Rated spacing distance between sensors: Rate-of-rise temperature detection is selectable at the
control panel for either 15° F (8.3° C) or 20° F (11.1° C)
Fixed Temp. UL & ULC FM Spacing, Either Fixed per minute. Fixed temperature sensing is independent of
Setting Spacing Temperature Setting
rate-of-rise sensing and programmable to operate at
135° F 60 ft x 60 ft 20 ft x 20 ft (6.1 m) for fixed
temperature only; RTI = Quick
135° F (57.2° C) or 155° F (68° C). In a slow developing
(57.2° C) (18.3 m)
50 ft x 50 ft (15.2 m) for fixed
fire, the temperature may not increase rapidly enough to
155° F 40 ft x 40 ft temperature with either rate-of-rise operate the rate-of-rise feature. However, an alarm will be
(68° C) (12.2 m) selection; RTI = Ultra Fast initiated when the temperature reaches its rated fixed
temperature setting.
Smoke Sensors:
 Photoelectric technology sensing TrueAlarm heat sensors can be programmed as a utility
 360° smoke entry for optimum response device to monitor for temperature extremes in the range
from 32° F to 155° F (0° C to 68° C). This feature can
 Built-in insect screens provide freeze warnings or alert to HVAC system
problems. Refer to specific panels for availability.
4098-9714 Photoelectric Sensor
4-7/8" (124 mm)
TrueAlarm photoelectric sensors use a stable, pulsed
infrared LED light source and a silicon photodiode LED status indicator
receiver to provide consistent and accurate low power 2-3/8"
smoke sensing. Seven levels of sensitivity are available (60 mm)
for each individual sensor, ranging from 0.2% to 3.7% per
foot of smoke obscuration. Sensitivities of 0.2%, 0.5%,
and 1% are for special applications in clean areas.
Standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and
3.7%. Application type and sensitivity are selected and 4098-9733 Heat Sensor with Base
then monitored at the fire alarm control panel.*
The sensor head design provides 360° smoke entry for WARNING: In most fires, hazardous levels of smoke
optimum response to smoke from any direction. Due to its and toxic gas can build up before a heat detection
photoelectric operation, air velocity is not normally a device would initiate an alarm. In cases where Life
factor, except for impact on area smoke flow. Safety is a factor, the use of smoke detection is highly
recommended.

4-7/8" (124 mm)

LED status indicator Application Reference


2-1/8"
(54 mm) Sensor locations should be determined only after careful
consideration of the physical layout and contents of the
area to be protected. Refer to NFPA 72, the National Fire
Alarm and Signaling Code. On smooth ceilings, smoke
sensor spacing of 30 ft (9.1 m) may be used as a guide.*
4098-9714 Photoelectric Sensor with Base
* For detailed application information including sensitivity
selection, refer to Installation Instructions 574-709.

3 S4098-0019-20 1/2015
TrueAlarm Analog Sensing Product Selection Chart
TrueAlarm Sensor Bases (for use with Sensors 4098-9714 and 4098-9733)
(Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information)
Model Description Compatibility Mounting Requirements
4” octagonal or 4” square box, 1-1/2” min.
4098-9792 Standard Sensor Base No options
depth; or single gang box, 2” min. depth
Sensor Base with connections for
2098-9808 Remote Alarm Indicator or
4098-9789 Remote LED Alarm Indicator or
4098-9822 Unsupervised Relay 4” octagonal or 4” square box
Unsupervised Relay
4-Wire Sensor Supervised Relay 2098-9737 Supervised Remote Relay Note: Box depth requirements depend on
4098-9791** Base with connections for LED total wire count and wire size, refer to
2098-9808 Remote Alarm Indicator or
Indicator or Unsupervised Relay accessories list below for reference.
4098-9822 Unsupervised Relay
2-Wire Sensor Supervised Relay 4098-9860 Supervised Remote Relay ** NOTE: 4098-9791 and 4098-9780 are NOT
4098-9780** Base with connections for LED compatible with the 2120 CDT
2098-9808 Remote Alarm Indicator or
Indicator or Unsupervised Relay 4098-9822 Unsupervised Relay
TrueAlarm Sensors
Model Description Compatibility Mounting Requirements
4098-9714 Photoelectric Smoke Sensor Bases 4098-9792, 4098-9789,
Refer to base requirements
4098-9733 Heat Sensor 4098-9791, and 4098-9780

TrueAlarm Sensor/Base Accessories


Model Description Compatibility Mounting Requirements
Supervised Relay, mounts remote or in base Remote Mounting requires 4” octagonal
2098-9737 For use with 4098-9791 base
electrical box or 4” square box, 1-1/2” minimum depth
Supervised Relay, mounts remote or in base Base Mounting requires 4” octagonal
4098-9860 For use with 4098-9780 base box, 2-1/8” deep with 1-1/2” extension ring
electrical box
Remote Red LED Alarm Indicator on single Bases 4098-9789, 4098-9791,
2098-9808 Single gang box, 1-1/2” minimum depth
gang stainless steel plate and 4098-9780
Unsupervised Relay, tracks base LED status; Bases 4098-9789, 4098-9791, 4” octagonal box, 2-1/8” deep with 1-1/2”
4098-9822
Note: Mounts only in base electrical box and 4098-9780 extension ring
Required for surface or semi-flush
Bases 4098-9792, 4098-9789,
4098-9832 Adapter Plate mounted 4” square box and for surface
4098-9791, and 4098-9780
mounted 4” octagonal box

Specifications
General Operating Specifications
Communications and Sensor Supervisory Power IDNet or MAPNET II communications, auto-selected, 1 address per base
2 2
Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm to 2.08 mm )
Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current
2
Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm )
UL Listed Operating Temperature Range 32° to 100° F (0° to 38° C)
Operating Temperature with 4098-9733 Heat Sensor 32° to 122° F (0° to 50° C)
Range with 4098-9714 Smoke Sensor 15° to 122° F (-9° to 50° C)
Storage Temperature Range 0° F to 140° F (-18° C to 60° C)
Humidity Range 10 to 95% RH
4098-9714 Smoke Sensor Air Velocity Rating 0-4000 ft/min (0-1220 m/min)
Housing Color Frost White
4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current 270 A, from 24 VDC supply
Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply
4098-9780 Base With Supervised Remote Relay 4098-9860 (see page 2 for contact ratings)
Power Supplied from communications
4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789. 4098-9791, and 4098-9780 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current Supplied from communications
Alarm Current 13 mA from separate 24 VDC supply

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4098-0019-20 1/2015


www.simplex-fire.com
© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
6/9/2019 HEAT-AUTOMATIC FIRE DETECTORS | UL Product iQ

UQGS.S844 - HEAT-AUTOMATIC FIRE DETECTORS

Heat-automatic Fire Detectors


See General Information for Heat-automatic Fire Detectors

SIMPLEX TIME RECORDER CO S844


50 TECHNOLOGY DR
WESTMINSTER, MA 01441 USA
Heat Sensor, Model(s) 4098-9778

Spacing (Ft)
Model Compatibility Contact Temp Smooth to Wall or
No. Type Restrictions Arrangement Range (°F) Ceiling Partition

4098-5201 FT, FT/ROR D2 - 135/200 50 25

4098-5202 (1), 4098-5203 (1)

FT D2 - 135 50 25

4098-5253 FT/ROR D2 - - - -

4098-9401 (screw terminals)

FT, RC D2 - 135 60 30

4098-9402 (screw terminals)

FT/ROR D2 - 135 70 35

4098-9403 (screw terminals)

FT, RC D2 - 200 60 30

4098-9404 (screw terminals)

FT, RC D2 - 200 70 35

4098-9612 FT, RC D2 - 135 70 30

4098-9612C FT None - - - -

4098-9613, JTW-ZOF-CN4098-9613

FT/ROR None - 135 70 35

4098-9613C FT/ROR None - - - -

4098-9614 FT, RC D2 - 200 70 30

4098-9614C FT None - - - -

https://iq.ulprospector.com/en/profile?e=153069 1/3
6/9/2019 HEAT-AUTOMATIC FIRE DETECTORS | UL Product iQ

4098-9614E FT, RC D2 - 200 70 30

4098-9615 FT/ROR D2 - 200 70 30

4098-9615C FT/ROR None - - - -

4098-9615E FT/ROR D2 - 200 70 30

4098-9733C FT/ROR None - - - -

4098-9734 FT/ROR None - - - -

4098-9734, GSA4098-9734, 4098-9734E

FT/ROR D2 - 135 60 30

155 40 20

190 60 30

601H-F-UL FT D2 - 135 70 25

601H-RF-UL FT/ROR D2 - 135 70 25

612H FT/ROR D2 - 135 50 25

622H FT D2 - 135 50 25

631H-F-UL FT D2 - 200 70 25

632H FT D2 - 200 50 25

912H FT/ROR D2 - 135 50 25

200 50 25

GSA4098-9612, 4098-9612E

FT, RC None - 135 70 30

GSA4098-9613, 4098-9613E

FT/ROR None - 135 70 35

GSA4098-9733, 4098-9733, 4098-9733E, JTW-ZOM-CN4098-9733

FT, RC None - 155 40 20

135 60 30

Control Unit
Base Compatibility
Model Related Detector Restrictions

4098- 4098-5201, 4098-5202, 4098-5203 B2


5209

4098- 4098-5253, 4098-5251, 4098-5254 B2


5260

https://iq.ulprospector.com/en/profile?e=153069 2/3
6/9/2019 HEAT-AUTOMATIC FIRE DETECTORS | UL Product iQ

4098- 4098-5253, 4098-5251, 4098-5254 B2


5261

4098-9682, 4098-9683, 4098-9684, 4098-9788:

4098-9612, GSA4098-9612, 4098-9613, GSA4098-9613, CN4098-9613, 4098- B2


9614, 4098-9615

4098-9682E, 4098-9683E, 4098-9684E, 4098-9788E

4098-9612E, 4098-9613E,4098-9614E, 4098-9615E, 4098-9733E, 4098-9734E B2

4098-9780, GSA4098-9780, 4098-9789, GSA4089-9789, 4098-9791, 4098-9792, GSA4098-9792, CN4098-


9792,4098-9793, GSA4098-9793, 4098-9794, GSA4098-9794, 4098-9795, GSA4098-9795, 4098-9796, GSA4098-
9796, 4098-9770, 4098-9771

4098-9733, GSA4098-9733, CN40908-9733, 4098-9734, GSA4098-9734 B2

4098-9780E, 4098-9789E, 4098-9791E, 4098-9792E, 4098-9793E, 4098-9794E

4098-9733E, 4098-9734E. B2

4B, 6B 612H, 622H, 632H, 912H B2

4B-UL 601H-RF-UL, 601H-F-UL, 631H-F-UL B7

6B 4098-5202, 4098-5203 B2

B2 - For connection to Listed control units with which compatibility was determined by test or a review of circuit parameters. Interconnection and
compatible models indicated on installation wiring diagram for detector (base) and/or control unit.

B7 - Determined by head.

D2 - For connection to Listed control units with which compatibility was determined by test or a review of circuit parameters. Interconnection and
compatible models indicated on installation wiring diagram for detector (base) and/or control unit.

FT - Fixed temperature

FT/ROR - Fixed temperature/rate of rise combination

RC - Rate compensation

(1) - Complementary Listed under Smoke-Automatic Fire Detectors (UROX).

Last Updated on 2017-03-28

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2019 UL LLC"

https://iq.ulprospector.com/en/profile?e=153069 3/3

You might also like