DETERMINATION OF PERMEABILITY IN
OVERBURDEN : CONSTANT HEAD METHOD
The Constant head method is used when the permeability of the
strata being tested is very high.
In this method a hole is drilled or bored up to the level at which
the test is to be performed. The casing is simultaneously driven as the
drilling or boring of the hole is in progress. After the required lovel is
reached the hole is to bo cleaned by means of scooping spoons and
bailer. In case of drilling below ground water level, the hole is cleaned
by passing air under pressure by air jetting method,
SATURATED MATERIAL, UNSATURATED MATERIAL
Flow i
ay fe oe |
vorkin [ON Penvioussrmaron 5
ae =|
ow.
Vee. =
Aller the hole is cleaned the test is started by allowing clear water
through a metering system to maintain gravity flow at constant head. The
observations of the water level at 5 minutes intervals is to be noted, When
threo consecutive readings show constant values, further observations
may be stopped and the constant reading should be taken to the depth
of water level
Co-efficient of permeability ‘K’ is given by
K=C,xQH
Coefficient of permeability in cm/sec
Constant, varies with the size of casing and rods, the values are
given in the table below
Discharge in Vm
Head in Meter = H, (Gravity Head) -H, (Head loss due to friction)
10 ele
fa eet eer a eo eer ee
DISCHARGE Littmin
Head Loss Due to Pipe Friction Per 3m Length of Drill Rod Versus Discharge