Firmware version for InteliGen ,
NT
InteliSys controller
SW version 4.4.0
1 General information 3
2 Changes in the version 4.4.0 4
3 Changes in the version 4.3.3 5
4 Changes in the version 4.3.2 6
5 Changes in the version 4.3.1 7
6 Changes in the version 4.3.0 8
7 Changes in the version 4.2.0 9
8 Changes in the version 4.1.2 10
9 Changes in the version 4.1.1 11
10 Changes in the version 4.1.0 12
11 Changes in the version 4.0.1 14
12 Changes in the version 4.0.0 15
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
2.2 Repairs
CAN1 communication improvements for InteliField Gateway
CAN1 communication between controller and the InteliField Gateway, has been improved.
Missing Run hours value in GeCon-MINT archive
Missing Run hours value in GeCon-MINT archive, has been fixed.
Screen template missing error
Screen template missing error in default MINT MARINE archive, has been fixed.
Force block behavior with BOC protections
Force block behavior, has been fixed.
3.2 Repairs
4.2 Repairs
System start/stop timer freezing
System start/stop freezes at 1s, when setpoint #SysAMFstopDel = 0 has been fixed.
SlowStopLoad
Setpoint group Pwr management Related FW SW version: 4.2.0
Range [units] UNLOAD / LDSHARING [-]
Description
This setpoint defines behavior of a genset with active Slow stop protection:
UNLOAD – Genset is unloaded as much as possible (other gensets are not overloaded). The
unloading is limited to 20 % of its Nomin power rating to avoid reverse power issue. Genset load
can be lower than 20%, if system load is low and all gensets are forced to operate with such a low
load level.
LDSHARING – Genset is not unloaded, load sharing with other gensets is done until a backup
genset is started and loaded.
Service time 5
Setpoint group Engine protect Related FW SW version: 4.1.0
Range [DD/MM/YYYY] or [MM-DD-YYYY]*
Default value 01/01/2000 Force value NO
Step 1 day
Comm object 16391 Related applications All
Config level Standard
Setpoint
Always
visibility
Description
Use this setpoint to set a date at which is issued the WrnServiceT5 alarm (the alarm is issued at 12
a.m). Set the setpoint to 01/01/2000 or 01-01-2000 to disable the protection.
10.2 Repairs
InteliMains NT synchronisation
InteliMains NT could not synchronise genset with mains when LocalBaseload function was used. It
worked only with Process control: LocalBaseload set to OFF. It has been fixed.
Imaginary ECU alarms
Controller could display imaginary ECU alarms because of incorrect DM1 frames handling. It has been
fixed.
SUS sequence related history record
Controller in some cases made SUSseq break-3 history record, when in fact SUS sequence was not
interrupted. It has been fixed.
Emergency manual SRO jump
Speed Regulator Output (SRO) level jumped up when the LBI: Emerg. manual was deactivated and
genset was running loaded. Size of the jump depended on Sync/Load ctrl:LS gain setting and actual
genset load level. It has been fixed.
SMS sending via IB-NT
Alarm SMS sending did not work with IB-NT connected to controller via RS232. It has been fixed.
New LBI:GenProtBlock
GenProtBlock is intended to block protections, which prevents operation with no generator voltages
(voltage regulator is switched off). It enables to use controller with applications, which require
temporary operation without excited generator.
GenProtBlock provides this functionality:
Voltage and frequency related regulations are switched off
Under/overfrequency and under/overvoltage protections are inactive! It means that protections
associated with these parameters are deactivated:
Gener protect: Gen >V BOC, Gen <V BOC, Gen >f, Gen <f
Sd Overvoltage protection is still active. Parameter Gener protect: Gen >V Sd is used to set
protection threshold of the Sd Overvoltage protection.
IMPORTANT: Be aware that frequency/voltage protections switching off is potentially
dangerous and could result with equipment damage! Pay close attention to Gen >V Sd
setup when GenProtBlock is used!
12.2 Repairs
Slow stop protection fix
Genset with active Slow stop protection started to unload, but it was still part of load sharing. It caused
bus frequency drop, which could result with underfrequency tripping.
It has been fixed, genset with active Slow stop protection is not part of load sharing and its unloading
does not affect bus frequency.
The voltage regulation is activated all the time in the controller with the lowest CAN2 address (this is
unchanged behavior from previous versions).
IMPORTANT: This firmware is not to be used with other firmware that has standard
VArsharing behavior. If this firmware is mixed with other types of firmware it may cause slight
unbalance in the VArsharing.
13.2 Repairs
Speed regulator output drop after GCB closing (MINT configuration)
Speed Regulator Output (valueSRO) value dropped after GCB closing. Magnitude of the drop
depended on setting of parameters LS gain and RampStartLevel. It has been fixed.
14.2 Repairs
The alarm BOC NCB fail is no more issued while the LBI Emerg. Manual is active.
15.2 Repairs
History Record SUS seq blck.
When the settings of the controller does not match the conditions for the SUS start sequence the Alarm
SUS seq blck iss issued and the message SUS seq blck is written to history (replaced the wrong
message SUS Start Block). Fixed.
Non-functional Horn Reset in case of sensor fail.
When any protection set as „Sensor Fail“ it is not possible to deactivate the horn using the Horn Reset
button. Fixed.
Missing AirGate ID (value Info:AirgGate ID) when controller language set to Chinese. Fixed
Swapped alarms messages G ph+L neg and G ph opposed. Fixed.
Soft unload of the gen-set during the warming procedure not working. Fixed.
Controller issues the NCB fail although the LBI Emergency Manual is active. Fixed.
This input forces devices (PC, - IB-NT connected via CAN2 with adr #3 (ETH access,
WebSuperVisor, AirGate, display with ModBus TCP)
AcsLockCAN2(3)
terminal adr #3) connected to CAN2 with - I-LB+ connected via CAN2 with adr #1 - connected via
address #3 into monitoring mode. MODEM to user
This input forces devices (PC, - IB-NT connected via CAN2 with adr #4 (ETH access,
WebSuperVisor, AirGate, display with ModBus TCP)
AcsLockCAN2(4)
terminal adr #4) connected to CAN2 with - I-LB+ connected via CAN2 with adr #2 - connected via
address #4 into monitoring mode. MODEM to user
IMPORTANT: In worst case, every 300ms one data package is ignored from DIASYS. It is
necessary to be careful with sampling rates bigger than 300ms during creation of a recording
file.
Low load - the gen-sets in power management system are loaded for less than their 5% of their
nominal power.
When gen-sets in power management (without active Local Baseload function) are loaded for less
than 5% of their nominal power, then gen-set with the highest CAN address (from gen-sets with set
Local Baseload) is temporary switched from holding Local Baseload level and start loadshare with
gen-sets from power management. If this gen-set and other gen-sets in power management are still
loaded less than 5% of their nominal power then next gen-set with local Baseload (from gen-sets with
set Local Baseload) is switched from Local Baseload function to the loadsharing).
High load - all gen-sets running in power management system are loaded on their nominal power
or more
When the load is increased and running gen-sets in power management (Local Baseload = OFF)
achieved their nominal power, then the gen-set with the highest CAN address (from gen-sets with set
Local Baseload) takes power what is more then nominal power of gen-sets in power management
system. The result is that gen-sets in power management run on their nominal power and the gen-set
with the highest CAN address (from gen-sets with set Local Baseload) is loaded by power higher than
what is set by its Local Baseload setpoint.
This feature is determined for Gas engines or slow-speed gen-sets.
Note:
When the Local Baseload function is activated (Local Baseload ≥ 0 kW) then the setpoint Power
management [Enabled/Disabled] has no influence for the function of the gen-set.
Currently we have not implemented the cooperation of the Local Baseload function and power management
NT
system in InteliMains controller. It causes that calculation of the load reserve will not be correct.
But it doesn’t have influence for the function of the gen-sets because each gen-set calculates itself conditions
for start and stop.
19.2 Repairs
Bus MeasError protection has not beeing working. The bug was fixed.
Problem with External values inserting via modbus was resolved.
20.2 Repairs
Problem in Automatic priority swapping (for Power management) system was repaired
Problem in Automatic priority swapping (for Power management) system was repaired
When the LDS option is selected and a controller is adjusted to the Master role, the controller does not
initiate its master functions and therefore other controllers will not accept its priority changing
messages.
Bug in SPTM application was repaired
During transformation from island operation to parallel with Mains (after Mains returns) the GCB was
cyclically opened and closed
21.2 Repairs
Non-valid issuing of the alarm SUS Min power during the SUS start even when all conditions of the
available powerof the system are fulfilled. The bug has been fixed.
Watchdog of the controller recalled by changing of modes on InteliGen NT GC hardware. The bug has
been fixed.
24.2 Repairs
Problem with DISTBIN timeout in combination with I-CR-R resolved
Problem with DISTBIN timeout in combination with I-CR-R resolved
PLC block Delay in pulse mode no longer shortens pulses by 100ms
CANNegotiation warning (Wrn AddrErr) is no longer displayed when synchronized setpoint is changed
while CANNegotiation function is active
Power and current is now written in history correctly after Emergency manual deactivation
InteliVision terminals no longer stop communication if 100% of history memory columns in the controller is
used
The false alarm is no longer indicated when controller and IGS-PTM module are power on at the same
time
Logical binary output Horn flashing is no longer delayed by 2s against logical binary output Horn
Regulation of Base PF in parallel to mains wrong calculated when power format set to 0,01MW MVAr
MVA MX kV or 0,01MW MVAr MVA MX V. The bug has been fixed.
Not valid BOC EarthFaultCurr issued after the restart of the controller. The bug has been fixed.
Statistic of pulse counter on Inteli AIN8 gets latched. Bug has been fixed.
Behavior of LBO Horn in case of Analog or Binary protection unified.
Pressing of Stop button during running of pre-lubricate function and consequent pressing of Start button
caused the interruption of pre-lubricate function. The bug has been fixed.
The problem of simultaneous activation of LBI ECU StoppedEng and Rem Star/Stop fixed.
Archive (*.ant)
NT
NT NT
For InteliSys BaseBox and
For InteliGen GC For InteliGen BaseBox NTC
InteliSys BaseBox
IG-BB-MINT4.4.0-.ant
IG-GC-MINT-4.4.0.ant IS-MINT-4.4.0.ant
IG-BB-MINT-BC-4.4.0.ant
IG-GC-MINT-BC-4.4.0.ant IS-MINT-BC-4.4.0.ant
IG-BB-Combi-4.4.0.ant
IG-GC-Combi-4.4.0.ant IS-Combi-4.4.0.ant
IG-BB-SPTM-4.4.0.ant
IG-GC-SPTM-4.4.0.ant IS-SPTM-4.4.0.ant
IG-BB-SPI-4.4.0.ant
IG-GC-SPI-4.4.0.ant IS-SPI-4.4.0.ant
IG-BB-GeCon-SPTM-4.4.0.ant
IG-GC-GeCon-SPTM-4.4.0.ant IS-GeCon-SPTM-4.4.0.ant
IG-BB-GeCon-SPI-4.4.0.ant
IG-GC-GeCon-SPI-4.4.0.ant IS-GeCon-SPI-4.4.0.ant
IG-BB-GeCon-MINT-BC-
IG-GC-GeCon-MINT-BC-4.4.0.ant IS-GeCon-MINT-BC-4.4.0.ant
4.4.0.ant
IG-GC-GeCon-MINT-4.4.0.ant IS-GeCon-MINT-4.4.0.ant
IG-BB-GeCon-MINT-4.4.0.ant
IG-GC-GeCon-Combi-4.4.0.ant IS-GeCon-Combi-4.4.0.ant
IG-BB-GeCon-Combi-4.4.0.ant
NT
Table 16.3 Available hardware for InteliGen
NT NTC
InteliSys BaseBox InteliSys BaseBox
Binary Inputs 16 16
Binary Outputs 16 16
Analog Inputs 4 4
Analog Outputs 1 1
Communications RS232, RS485, USB RS232, RS485, USB, Ethernet
NT
Table 16.4 Available hardware for InteliSys