[Meaning] [Condition]
Checks errors.
1. SYS1 LED(green) on DOC-1XX lights up or off
(Normal if it flickers)
2. When a Watchdog error occurs
- it is transferred to 74HC4538 chip and recognized by speed
[Explanation]
control section
Tasks are monitored within the software(S/W) regularly. - running control program registers a S/W watchdog error in the
If a task has errors three successive times, S/W Watchdog error occurs. table and reset running control program automatically.
DI-1 elevator operation control program is composed of 12 tasks. These tasks are
inspected for their any possible errors as shown below.(Initial Error_Counter value
is set to 0(Zero)).
[Countermeasures]
- This error has no relation to the outside connection.
- Check the voltage(5V) on output of SMPS,
If no, replace SMPS.
Task에 error in
Error occurs 발생task? - If the same error continues to happen, replace DOC-1XX.
Yes
No
Error_Counter를
Increase 1
1 증가시킨다.
Error_Counter
Error_Counter == 3
Yes
시스템에서
Create 사용할
memory pool
메모리for풀(pool)
system생성
Memory
메모리 pool
풀(pool) 생성
실패failed
creating ? ?
No
Yes
Memory
메모리 assigning
풀(pool)에서 for task &
타스크(Task)나
인터럽트 interrupt handlerhandler),
핸들러(Interrupt &
큐(Queue)queue
등에서 in pool.메모리 할당
사용할
No
Memory assigning
메모리 할당 실패 ?
failed ?
프로그램 다음
Perform 단계
Next Yes
stage수행
of P/G
Memory assigning
메모리 할당 Error 발생
error generated?
시스템에서
Create 사용할
memory pool
메모리for풀(pool)
system생성
Task
타스크creating
생성 혹은or
No interrupt
인터럽트 registering
등록 실패 ?
failed?
Yes
프로그램 다음
Perform 단계
next
stage수행
of P/G
Task creating error
타스크 생성 Error 발생
generated
엘리베이터 운전 제어
Initialize elevator 프로그램
operation
시스템
control 초기화
P/G system
Semaphore
Create 생성
semaphore
Semaphore creating
No Semaphore 생성 실패 ?
failed?
Yes
Perform next stage of
프로그램 다음 단계 수행
P/G
Semaphore생성
Semaphore creating
Error
error
Watchdog Timer not only carries out tasks periodically just as several
other tasks do, but also supervises all other tasks. So its period is the
shortest(30m sec) and it has top priority.
Create memory
시스템에서 사용할pool
메모리 풀(pool) 생성
for system
Create
Watchdogwatchdog
Timer 생성
timer
Yes
Watchdog timer
Watchdog Timer
생성 실패
creating ?
failed?
Watchdog
Watchdog timer
Timer 생성 No
creatingError
error발생generated
Assign
메모리 memory타스크(Task)나
풀(pool)에서 for task &
인터럽트interrupt handler
핸들러(Interrupt in
handler)에서
사용할 메모리
memory pool할당
Task
타스크creating
생성 혹은or
No interrupt
인터럽트 등록 실패 ?
registering
Yes
Perform
프로그램 다음next
단계
수행
stage of P/G
Task creating
타스크 생성 Error 발생
error generated
[Reference]
The number of interrupt vector can be checked by ‘A42E’.
(Trace information)
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 15/103
○ Operation CPU
TCD 16 Speed CPU H/W WDT trouble occurred Detection Application Si210
○ Speed CPU
[Detection] In case that H/W Watchdog error of DSP maintain over 3 cycle of
detection(Min. 60~ Max. 90ms), detect the trouble and output
the signal of DSP reset.
This trouble can not be detective in case of over 48 volts.
(Voltage drop/ failure)
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 16/103
○ Operation CPU
TCD 17 Speed CPU Retry failure Detection Application Si210
○ Speed CPU
[Meaning] DSP H/W Watchdog has been detective and DSP can not be operable [Countermeasures]
even if operation CPU perform retry of DSP more than 4 times.
- Check if the communication connector(64P) between
DOC-1XX and DPC-11X is connected well, If connector is
abnormal, replace.
[Explanation] If retry signal of operation CPU keeps up more than 4 times, - Check the voltage(5V) on output of SMPS,
the error is detected and make the elevator being inoperable. If no, replace SMPS.
- Twist the cables of the communication connector(64P)
- Check if ground condition is correct.
- Replace DPC-11X.
[Meaning] When communicating DPRAM between operation side & speed side, [Countermeasures]
a error detected if transmitted data is different with feed back data for
- Check if the communication connector(64P) between
4 cycles(120ms) in series.
DOC-1XX and DPC-11X is connected well, If connector is
abnormal, replace.
[Explanation] 1. When transmitting data by DPRAM, feed back data - Check the voltage(5V) on output of SMPS,
If no, replace SMPS.
Transmitted data Feed back data - Twist the cables of the communication connector(64P)
- Check if ground condition is correct.
Coil[RS_SUPPRESS_ON]: 0x91C3 Coil[SV_INV_SUPPRESS_FB]: 0x9208 - Replace DOC-1XX
- Replace DPC-11X.
SWD_O[VO_C1ST]: 0x8081 Coil[SV_INV_C1ST_FB]: 0x920A
[Meaning] When current in the electric motor exceeds limit value(If over current [Countermeasures]
occurs,stop switching in order to prevent damages on motor and 1. Check VB connector on DPC-1XX PCB.
inverter devices).
2. Verify that HCT cable is properly connected to U and V of HCT.
3. Check a proper connection HCT direction (Normal if HCT ‘arrow’
[Explanation] points
downwards).
INV U-V-W stack
4. Verify that voltage of HCT connectors are +15V and -15V.
5. Check J5H jumper on DPC-1XX and number of HCT turns, on the
HCT basis of the below table.
U
V +15V
W HCT J5H
J5Hjumper
SHORT pin Motor max. Capa.
MOTOR최대용량
R10 R9 R11 R12 IGBT 용량
IGBT, IPM HCT turns
J5H TURN수 PIN 삽입위치
position (check(명판확인
the nameplate)
)
1 2
3 4 R78 75A 2 1-2 4.5kW ~ 7.5kW
+5V
100A 2 3-4 9.5kW ~ 11kW
R18
10 OCT
VB - 03
- 13 150A 1 1-2 13kW ~ 15kW
11 + U6HD U4GA
VB - 07
R44 C88 200A 1 3-4 18.5kW ~ 22kW
DPC-1XX 6. Check if ground conditions of building & control panel are good.
7. Check followings:
- Resistance R9, 10, 11, 12 and 78 (marked on the left diagram) are properly
To DPC-1XX VB connector
fitted.(R9: 10K, R10: 1.5K, R11: 5K, R12: 12K, R78: 1M)
HCT
HCT 커넥터
- When a short pin is inserted into 1-2 on J5H, the potential of pin 10 on U6H
1 2 3 4 5 6
connector
+15V -15V IAS GND IBS GND is 6.26 ±0.31V
1 6
HCT - When a short pin is inserted into 3-4 on J5H, the potential of pin 10 on U6H
A B
is 8.89 ±0.44V.
HCT
HCT의 ‘arrow’
방향이 should
아래로
8. Replace HCT.
U-phase point 향해야 정상임
downwards 9. Replace DPC-1XX PCB.
U상 V상
V-phase
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 19/103
○ Operation CPU
TCD 31 DC Link Over voltage Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
When DC link voltage is 770V or more is detected (Stop switching to prevent condenser, IPM
and IGBT from damages). 1. Turn the power OFF and examine the followings:
- VG connector on DPC-1XX PCB
- GA connector on DPP-1XX PCB
[Diagram]
- GW, GP and GX connectors on DPP-1XX PCB
Over voltage
과전압 detection
검출회로 circuit 2. Check if the voltage of DC link is 770V±60V.
3. Check if reference voltage is within 7.9 ±0.5V.
VDC(+)
GW - 03 DPP-1XX Check point (DPC-111: R31, DPC-131: TE40, TE100)
15V (GDC) 정상시 LOW(0V)
Normal if Low(0V)
이상시 HIGH(15V)
VDC(-)
D23
Abnormal if High(15V) 4. If item 2, 3 are OK, check the connection between INV STACK
GP - 09 OV
R101 R36
R31
& DPP-1XX, replace DPP-1XX.
15V
R102 R37 C10D29 PC7 D30
VG - 13
5. Check if regenerative IGBT operates normally. (Refer to TCD35:
R103 -9V R47
R38
R30 DPC-1XX In case of regenerative IGBT trouble, this error may be occurred.
4
R39
- 2 R21 C5 (INV)
R104
5
+
VG - 14 6. Check if input power of control panel is correct.
LED1 R98 C4 IC1
7. If TCD 31 is detected while the car is not running, check followings:
-9V - VG connector on DPC-1XX.
- VA, GA connector on DPP-1XX. (Check if #13,14 pin of VA, GA is
connected - short check is normal)
8. After power off, check regenerative resistors is OK.
VDC(+) VDC(-) (Before this job, the voltage of DC link is 0V)
Motor PCB
connector connector
11kW below DPP-13X GP-01 GP-02 *Caution : To prevent the hazard of electric shock on DC link end,
even though the power is OFF, make sure that LED1(CHG)
13~15kW DPP-12X GP-01 GP-03
on DPP-10X PCB lights OFF.
[Countermeasures]
[Meaning] Motor capacity 11kW below : In case that one of upper IGBT & one of
1. Turn the power off and check if the condition of VG connector of DPC-
lower IGBT in IPM are switching on together or regenerative IGBT in IPM
is short failure, the trouble occurs. 1XX PCB and GA & VA connector of DPP-1XX PCB are OK.
Motor capacity 13kW~15kW: In case that one of upper IGBT & one of 2. In case of DPP-111, check if the condition of GXU, GXL, GU connector
lower IGBT in IPM are switching on together, the trouble occurs. and GW-03 pin are OK, and the connection between GU, GW & IGBT
Motor capacity 18kW~22kW: In case that +IGBT & -IGBT of U phase on INV. Stack.
are switching on together, the trouble occurs. 3. In case of DPP-131, check if the condition of GU, GV, GW & GX pin
And incase that the connection of INV STACK is incorrect or drive
connector are OK, and the connection between IPM and INV. Stack.
power of IGBT is incorrect or inverter output(U,V,W) are shortened
together. 4. After removing cables from DPP-1XX and IPM, check output of gate
SMPS
[Explanation] (GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
Motor 11kW below: Motor 13kW~15kW:
R.IGBT inside IPM R.IGBT outside IPM
Motor 18kW~22kW: GX-03,02: -9V)
IGBT
5. Check if the condition of HCT cable and HCT is OK.
6. Check the direction of HCT
CONVERTER
DIODE Reactor is applied - Normal if HCT ‘arrow’ points to the bottom of CP
IPM in case of 13kW
and above
- Check wiring directions and refer to INV. over current.
3Φ 380V 7. Check for proper connections of the followings:
HCT - VB connector to DPC-100 PCB
U
V
W
IM - U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
8. Turn the power ON and check the followings:
- Power supply to TP3 and TP6 on DPP-1XX PCB
- Voltage of GATE terminal
9. If TDC 32 is detected while the car is not running, check followings:
- VG connector on DPC-1XX.
GP - 01
GP - 03
GU - 01
1Φ 110V GU - 02
VB - 07
VB - 03
GV - 01 - VA connector on DPP-1XX.
GATE GV - 02
SMPS
GW - 01
GW - 02 DPP-1XX DPC-1XX 10. If the voltage of pin 6 of RA1(coordinates: 81) on DPC-1XX is +15V,
GX - 01 (GDC) VA VG (INV) examine the connection between pin 21 on DPC-1XX VG connector,
GX - 02
GX - 03
and pin 21 on DPP-1XX VA connector.
It is normal if they are connected.
In case of IGBT,
Use GATE TRANS 11. Examine and replace IGBT, IPM.
12. Replace DPP-1XX PCB.
13. Replace DPC-1XX PCB.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 21/103
[Countermeasures]
[Meaning] Motor capacity 13kW~15kW: In case that one of upper IGBT & one of
1. Turn the power off and check if the condition of VG connector of DPC-
lower IGBT in IPM are switching on together, the trouble occurs.
Motor capacity 18kW~22kW: In case that +IGBT & -IGBT of V phase 1XX PCB and GA & VA connector of DPP-1XX PCB are OK.
are switching on together, the trouble occurs. 2. In case of DPP-111, check if the condition of GXV, GXL, GV connector
And incase that the connection of INV STACK is incorrect or drive and GW-03 pin are OK, and the connection between GV, GW & IGBT
power of IGBT is incorrect or inverter output(U,V,W) are shortened on INV. Stack.
together. 3. In case of DPP-131, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
4. After removing cables from DPP-1XX and IPM, check output of gate
[Explanation]
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
DIODE GX-03,02: -9V)
CONVERTER Reactor applied for
리액터는
V-phase IGBT
V상 IGBT 모터용량 5. Check if the condition of HCT cable and HCT is OK.
Reactormotor
appliedcapa.
for15kW
motor cap.
13KW
15kW or이상에만
or only
more more 채용only
6. Check the direction of HCT
3-phase 380V
3상 380V - Normal if HCT ‘arrow’ points to the bottom of CP
HCT
U - Check wiring directions and refer to INV. over current.
V IM
W
7. Check for proper connections of the followings:
- VB connector to DPC-1XX PCB.
- U-phase HCT signal wire to VB-03.
- V-phase HCT signal wire to VB-07.
8. Turn the power ON and check the followings:
- Power supply to TP2 and TP5 on DPP-1XX PCB.
GW - 03
VB - 03
GV - 04
GV - 01
GV - 05
GV - 07
VB - 07
[Countermeasures]
[Meaning] Motor capacity 13kW~15kW: In case that one of upper IGBT & one of
1. Turn the power off and check if the condition of VG connector of DPC-
lower IGBT in IPM are switching on together, the trouble occurs.
Motor capacity 18kW~22kW: In case that +IGBT & -IGBT of W phase 1XX PCB and GA & VA connector of DPP-1XX PCB are OK.
are switching on together, the trouble occurs. 2. In case of DPP-111, check if condition of GXW, GXL, GW connector
And incase that the connection of INV STACK is incorrect or drive and GW-03 pin are OK, and the connection between GW & IGBT
power of IGBT is incorrect or inverter output(U,V,W) are shortened on INV. Stack.
together. 3. In case of DPP-131, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
4. After removing cables from DPP-1XX and IPM, check output of gate
[Explanation]
SMPS.
DIODE
CONVERTER (GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
W-phase IGBT
W상 IGBT Reactor
*리액터는applied on GX-03,02: -9V)
motors
모터용량
Reactor 13KW
15kW
applied and
for motor cap.
이상에만
15kW 채용
above
or more only 5. Check if the condition of HCT cable and HCT is OK.
3상
AC 380V
380V
HCT 6. Check the direction of HCT
U
V IM - Normal if HCT ‘arrow’ points to the bottom of CP
W
- Check wiring directions and refer to INV. over current.
7. Check for proper connections of the followings:
- VB connector to DPC-1XX PCB
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
8. Turn the power ON and check the followings:
GW - 05
GW - 01
GW - 06
GW - 09
GW - 03
VB - 03
GXW - 02 VB - 07
단상110V
AC 110V
GXW - 05 - Power supply to TP1 and TP4 on DPP-1XX PCB
GXL - 06
GATE
GXL - 07
DPC-1XX
- Voltage of GATE terminal (-8V±1V in stop)
DPP-1XX VA VG
TRANS
(GDC) (INV) 9. If TDC 34 is detected while the car is not running, check followings:
- VG connector on DPC-1XX.
- VA connector on DPP-1XX.
10. If the voltage of D20 (coordinates 5C) is 0 and the voltage of pin 8
of RA1(Coordinates 81) on DPC-1XX is +15V, then, examine the
connection between pin 25, on DPC-1XX VG connector, and pin 25
on DPP-1XX VA connector. It is normal if they are connected.
11. Examine and replace IGBT, IPM.
12. Replace DPP-1XX PCB.
13. Replace DPC-1XX PCB.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 23/103
○ Operation CPU
TCD 35 Regenerative IGBT trouble Detection Application Si210
○ Speed CPU
[Meaning] DPP-111: In case that On failure of regenerative IGBT occurs or driving [Countermeasures]
power of regeneration is failure or the connection of INV STACK is bad,
the trouble occurs. 1. Turn the power OFF and examine the followings:
- VG connector on DPC-1XX
[Diagram] - VA connector on DPP-111
- GP and GXL connectors on DPP-1XX
- Connection between GP on DPP-111 and IGBT on INV STACK
Regenerative - Check that variable resistor(BR) on DPP-111 PCB is set to a black
회생resistor
저항
DIODE mark.
CONVERTER 리액터는
Reactor applied for
Regenerative
회생 IGBT IGBT 모터용량
motors 15kW
capa. 13KW
2. If TCD 35 is detected while the car is not running, check followings:
or more 채용
이상에만 only - VG connector on DPC-1XX
AC 380V
3상 380V - VA connector on DPP-111
HCT
U If the voltage of pin 5 of RA1(Coordinate 81) on DPC-1XX is +15V,
V IM
W then, examine the connection between pin 19 on DPC-1XX VG
connector and pin 19 on DPP-111 VA connector.
It is normal if they are connected.
3. Examine IGBT.
4. Replace DPP-111 PCB.
5. Replace DPC-1XX PCB.
GP - 03
GP - 05
GP - 09
VB - 07
VB - 03
단상
AC 110V
110V
GATE DPC-1XX
DPP-111 VA VG
TRANS
(GDC) (INV)
GXL - 09
GXL - 17
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 24/103
○ Operation CPU
TCD 36 Inverter Hall CT trouble Detection Application Si210
○ Speed CPU
[Meaning] When current controlling HCT and VB connector on DPC-1XX PCB [Countermeasures]
are not connected.
1. Examine VB connector and cable on DPC-1XX PCB
(Connector checking jumper should be connected as in the left diagram)
[Diagram] 2. Examine connector and cable of HCT.
2. If TCD 36 is detected, while the connector is tightly inserted,
replace VB connector cable.
[Meaning] When the thermal switch on radiating plate activates in order to prevent [Countermeasures]
IGBT from being damaged by overheating. ( 85 ℃ or more, b contact)
1. Examine the followings:
- GP and GXL connectors on DPP-1XX
[Diagram] - VA, GA connector on DPP-1XX and VG connector on DPC-1XX
- Check for a proper connection between GP Pin 6, Pin 7 and terminal
INV. STACK
Detect circuit for Overheating Normal LOW(0V)
ends of thermal guard.
THERMAL GUARD DIODE Abnormal HIGH(15V)
CONV.
THERMAL1
2. Check the fan on the stack
THERMAL2
- Running status of the fan
15V
PC
VG - 17 - Power supply to the fan
R. IGBT DPC-1XX - Status of relay.
VG - 18
(INV)
IPM -9V
3. If the ambient temperature in the machine room is over 40°C, check
U IGBT
V IGBT the air-conditioning runs.
W IGBT DPP-1XX
( GDC) 4. Turn the power ON and check the stack overheats after sufficiently
cooling down the radiating plate and properly connecting GP connector
FAN
to DPP-1XX.
5. If TCD 37 is detected, check the followings:
PCB THERMAL1 THERMAL2
DPP-121 GB-05
- VG connector on DPC-1XX
GB-04
TH-01
- VA connector on DPP-111, GA connector on DPP-131
DPP-131 TH-02
[Meaning] When a current command, which is over 150% of the rated motor [Countermeasures]
current, is detected due to failure in the motor, unstable input power
supply & drop of voltage.
1. Examine the number of turns of HCT
This is detected when the current command value is over 150% of the rated motor current,
while the motor are running at the rated speed, going through starting and acceleration zone.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 27/103
○ Operation CPU
TCD 48 DC Link Under Voltage Detection Application Si210
○ Speed CPU
GP - 09
VDC(-)
D23
(1: +15V, 2: -9, 4: GND)
R62
R101 R36
4. If the voltage of pin 3 of RA1(Coordinates 81) on DPC-1XX is +15V,
R63
R102 R37
15V
C13 D36 PC9 D37
then, examine the connection between pin 15 on DPC-1XX VG
VG - 15
-9V R49
connector and pin 15 or DPP-1XX VA connector.
R103 R38
R35 DPC-1XX
9 (Normal if they are connected)
R104 R39 + 14 R23 C9 (INV)
8 VG - 16
- 5. This indicates that the voltage has not charged.
LED1 R98 C4 IC1
Check regenerative IGBT ON failure and MAIN IGBT ON failure.
-9V 6. Check the condenser and replace it, if necessary.
7. Replace DPP-1XX PCB and DPC-1XX PCB.
8. Check RCR resistor and wiring.
9. Check input power.
VDC(+) VDC(-)
PCB
Connector Connector 10. In case that the trouble occurs in the beginning of acceleration,
DPP-12X GP-01 GP-03 check if the door switches is off.
DPP-13X GP-01 GP-02
[Meaning] When the actual direction of the motor is opposite to the command. [Countermeasures]
1. Check the connection between the encoder fitted to the motor shaft
and the control panel.
[Explanation]
2. Examine that U and V-phase on the STACK pass through those of the
This TCD is to be detected when the actual running direction of the motor is opposite to the HCT in order.
command at a speed of 16 m/min. or more after starting. The detection is carried out at the 3. Check the number of turns of HCT(Refer to the INV over current table).
interval of 10m SEC only on the running of the motor. 4. Check for proper connections of the followings:
- U, V and W-phase INV STACK wires to motor terminals in order
- VG connector on DPC-1XX and VA, GA connector on DPP-1XX
- GU, GV, GW & GX connectors on DPP-131 PCB and IPM
- GXU, GXV & GXW connectors on DPP-111 PCB and IGBT
5. Check the following
- IGBT and IPM on INV STACK turns ON/OFF normally
(U-phase+, U-phase-, V-phase+, V-phase-, W-phase+ and W-phase-)
and U, V and W-phase currents are sine waves with 120 degree
phase difference. (When measuring check pin 3, 4 and 5 with a
oscilloscope, examine that U, V and W-phase currents are sine
waves without any distortion) If abnormal, STACK needs replacing.
6. Replace DPC-1XX PCB
7. Replace DPP-1XX PCB
8. Check if the positioning of traction machine is reverse or normal
9. Check if the cable of Rotary Encoder is disconnected
10. Check the condition of Rotary Encoder wiring
11. Replace HCT.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 29/103
○ Operation CPU
TCD 53 Inverter Charging Trouble Detection Application Si210
○ Speed CPU
[Meaning] When a failure occurs in the charging circuit which protects the [Countermeasures]
condensers and power devices by damping surge current on a initial
charging of DC link end. 1. Refer to DC LINK under voltage trouble.
2. Check for the connection status of the followings:
[Diagram] - VC connector on DPC-1XX and GW and GP connector on DPP-1XX
C1VD
Option - Wiring of VC connector on DPC-1XX PCB (C1VD)
DIODE
RCRR CONVERTER
MCCB
- Wiring of RCRR, RCRS and RCRT resistor
3Φ380V
RCRS
3. Turn the power OFF and check short-circuited DC-link ends.
NOISE (The examination should be carried out after the voltage at DC link has
FILTER RCRT
been completely discharged and LED1 on DPP-1XX PCB extinguishes.)
GW - 03
GP - 09
4. Replace DPP-1XX PCB
VC - 01
DPC-1XX DPP-1XX
VG VA
VC - 02 (INV) (GDC) 5. Replace DPC-1XX PCB
In case C1VD is applied: DC link voltage is charged through charging resistor RCRR, RCRS
and RCRT when C1VD is picked up in 3 seconds after the power turns on. If DC link voltage is
inspected to be low(below 330V) in 8 seconds after the C1VD contactor is picked up, drop out
C1VD contactor and then pick it up again. If DC link voltage is not charged in 8 seconds, it will
be dropped out and be in unable condition. This time, refer to DC link low voltage failure.
In case C1VD is not applied: DC link voltage will be charged through RCRR, RCRS within 3
seconds after power on, and 8 seconds later, DC link voltage will be inspected whether the
voltage is under 330V or not.
And TCD53 will be appeared even if the voltage is still under 330V after inspecting DC link
voltage 8 seconds later.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 30/103
○ Operation CPU
TCD 54 Inverter Overload Detection Detection Application Si210
○ Speed CPU
[Meaning] When the current detected on motor exceeds general motor capacity [Countermeasures]
continuously.
1. Check the No. of HCT TURN (Refer to INV over current table)
2. Verify that SPEC such as motor capacity, control panel capacity, etc..
[Diagram] are correct.
3. Check VB connector on DPC-1XX PCB and HCT connection
4. Check the condition of traction M/C gear and brake.
5. Verify that there’s no jam in car and CWT rail
2
DPC-1XX
6. Replace E PROM in DPC-1XX
(INV) 7. Replace DPC-1XX
U - Phase Currency
U상전류
8. Replace HCT
LOW Overload 9. Check if the positioning of traction machine is reverse or normal
V - Phase Currency A/D - Detected
V상전류 A/D변환 PASS + 과부하 검출
CONVERSION 10. Check if the cable of Rotary Encoder is disconnected
FILTER -
W - Phase Currency
W상전류 (Refer to TCD 92)
150% of Rated
전동기 정격전류
Motor Current
의 150%
This error is detected when the motor’s U, V, and W-phase values that have been radio-
rectified, converted into A/D values, and then gone through LOW PASS FILTER exceed
150% of rated
motor current. Error is detected when the rated value is exceeded for over 1 second.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 31/103
○ Operation CPU
TCD 55 Inverter Under Speed Detection Detection Application Si210
○ Speed CPU
[Meaning] When actual motor speed does not reach the value commanded. [Countermeasures]
1. Check the connection between control panel and the Rotary Encoder
fitted to motor shaft.
2. Verify that U and V-phase on inverter stack side are passing through U
[Explanation] Detection starts 100msec after motor start-up. An error is detected and V-phase of HALL-CT respectively.
when motor speed is detected to be below 4m/min for 100 m/sec while 3. Check the No. of HALL-CT turn (Refer to INV over current table)
speed command value is 6 m/min or more.
4. Check the connection sequence of U, V, and W-phase from inverter
stack to motor terminal.
5. Check the connection between VG connector in DPC-1XX PCB and
VA & GA connector of DPP-1XX.
6. Check the connection between IGBT and GU, GV, and GW connector
in DPP-111.
7. Verify that inverter stack IGBT(U-phase+, U-phase-, V-phase+, V-
phase-, W-phase+, W-phase-) turn ON and OFF normally and U, V,
and W-phase currents are sine waves with 120 phase difference.
(Verify that U, V, and W-phase currency are sine waves without
deformation by measuring check pin(CHK) 3, 4, and 5 on DPC-1XX
with scope)
If any error is found, replace the stack.
8. Replace DOC-1XX PCB.
9. Replace DPC-1XX PCB.
10. Replace DPP-1XX PCB.
11. Replace HCT
12. Check if the positioning of traction machine is reverse or normal.
13. Check if the cable of Rotary Encoder is disconnected.
(Refer to TCD 92)
14. Check if the electric power goes to motor terminal.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 32/103
○ Operation CPU
TCD 56 Inverter Over speed Detection Detection Application Si210
○ Speed CPU
[Meaning] When the actual number of rotations of motor is higher than the normal [Countermeasures]
abnormally.
1. Check the connection between the encoder fitted to the motor shaft
and the control panel.
2. Examine that U and V-phase on the STACK pass through those of the
[Explanation]
HCT in order.
This error is detected when the motor’s turn number detected exceeds 16 m/min 3. Check the number of turns of HCT(Refer to the INV over current table).
and, in case of high speed operation, is over 110% of the rated speed. In case of 4. Check for proper connections of the followings:
slow speed, the error is detected when the number is over 120% of the commanded - U, V and W-phase INV STACK wires to motor terminals in order
value for speed.
- VG connector on DPC-1XX and VA, GA connector on DPP-1XX
- GU, GV, GW & GX connectors on DPP-131 PCB and IPM
- GXU, GXV & GXW connectors on DPP-111 PCB and IGBT
5. Check the following
- IGBT on INV STACK turns ON/OFF normally. (U-phase+, U-phase-,
V-phase+, V-phase-, W-phase+ and W-phase-) and U, V and W-
phase currents are sine waves with 120 degree phase difference.
(When measuring check pin 3, 4 and 5 with a oscilloscope, examine
that U, V and W-phase currents are sine waves without any distortion)
If abnormal, STACK needs replacing.
6. Replace DOC-1XX PCB.
7. Replace DPC-1XX PCB.
8. Replace DPP-1XX PCB.
9. Replace Rotary Encoder and check the line.
10. Replace Hall CT.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 33/103
○ Operation CPU
TCD 57 Brake Over Current Trouble Detection Application Si210
○ Speed CPU
[Meaning] When the current of Brake coil exceeds the normal, the trouble occurs [Countermeasures]
[Meaning] When the input power of Brake coil is unstable or low, and the power is [Countermeasures]
cut at Fuse or somewhere, the trouble occurs.
1. Check the connection of VJ connector between DPC-1XX & DPB-1XX.
2. Check the red LED. If it is off, check the power supply line(DC 110V).
3. Check if #4, 6 pin of the connector on DPB-1XX is DC 100V.
[Explanation] In case that the current is broken or applied abnormally,
the trouble occurs. 4. Check if #3, 5 pin of the connector UB on DOP-1XX is DC 100V.
5. Check the condition of Fuse FS1, FS2.
6. Check if C1ST, C1BR operate well.
7. When C1BR, C1ST are activated, check if #2, 6 of VK connector on
DPB-1XX have DC110V.
5. Check if the line of Brake is broken.
6. Replace DPB-1XX PCB.
7. Replace DPC-1XX PCB.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 35/103
○ Operation CPU
TCD 59 Inverter Inoperable for 24 seconds Detection Application Si210
○ Speed CPU
[Meaning] When a momentary power failure is detected in DSP on DPC-1XX PCB. [Countermeasures]
[Meaning] When the failure of DC110V or the under voltage of Brake PCB is detected. [Countermeasures]
[Meaning] This is the method that detects any possible lost phase of E/L three-phase [Countermeasures]
input power. The decision is carried out by checking the DC rectifying
voltage(DC 48V) in the controlling power three-phase AC37V. 1) Verify that D48 FUSE LED(LED3.LED4) in DOP-100 PCB
lights on.
[Explanation] If IALM(red) LED and P.F(red) LED flashes within DOC-1XX, 2) Check the fuse(FS3, FS4) when the above LED lights off. If it
operation will be unable.
is
disconnected, replace it with a rated fuse(250V/3A).
V48_Down_10sec_Count >= 0x0A TCD 70
3) If any error are not found at the above items, verify that the
0x48106
voltage
AC 37V± 10% among pin 1, 9 and 12 of PB connector in
Left picture below show DC 48V at a normal power and the right picture shows DOP-100P PCB BOARD.
wave form when a phase was lost.
4) Verify that the voltage between AB-10 pin in DOC-100 PCB
Lost phase detecting circuit in DOC-1XX lights ARM LED when it detects a wave
form which falls down 35V or less. If it detects such wave for 300msec, it makes and F.G
Error 70. is DC48V± 10% .
[ Wave form & voltage on normal ] [ Wave form & voltage on abnormal ]
[Meaning] When input power(3 phases) drops to its 85% or below, [Countermeasures]
the trouble occurs.
1. There is a special countermeasure.
Check the power source from the building.
2. Refer to countermeasures of TCD70.
[Explanation] In case 85% of voltage drop continues for 90 msec, the trouble is
detected.
It is detected by the voltage(DC48V) rectified from AC37V that is
3 phases power for control.
+1 under_85p_count
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 42/103
○ Operation CPU
TCD 74 Operation SPEC DATA Trouble Detection Application Si210
○ Speed CPU
If data of each BIT is 1, the SPEC DATA of set BIT is the reason of the trouble.
15 14 13 12 11 10 9 8
Service Shelter
- - - - - -
floor plate
7 6 5 4 3 2 1 0
H.CT Rotary
IGBT Motor - Speed TM Gear
TURN Encoder
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 43/103
○ Operation CPU
TCD 76 EEPROM Write Trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
When different values are found over 100 times while writing data on
EEPROM and reading data from the same address.
1. Verify if SW2 switch in DOC-1XX is switched to “WE” side.
2. Verify if EEPROM is properly inserted into DOC-1XX.
[Explanation] This error means that the SPEC DATA is not written properly when
3. Check EEPROM.
letting SPEC DATA written in EEPROM.
( 28C64-xxPC: xx should be below 15 )
4. Replace SPEC ROM.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 44/103
○ Operation CPU
TCD 77 EEPROM Read Trouble Detection Application Si210
○ Speed CPU
[Meaning] Different data are found over 4 consecutive times while reading data [Countermeasures]
from the same address on EEPROM. 1. Check EEPROM.
( 28C64-xxPC: xx should be below 15)
2. Verify that EEPROM is properly inserted into DOC-1XX
[Explanation] While reading the SPEC DATA of EEPROM,
when different data is found over 4 times consecutively though BOARD.
reading SPEC DATA on the same address. 3. Replace SPEC ROM.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 45/103
○ Operation CPU
TCD 78 Floor Height measuring Table SUM trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
NVRAM floor height table error
1. When the sum obtained by adding each floor height table value saved in
NVRAM(Backup RAM) and the floor height sum data saved in
RAM(Backup RAM) does not match.
2. When the floor height sum data in NVRAM is 0(Zero).
3. When the floor height of the lowest floor of floor height table in NVRAM is
not the lowest floor height(150000).
[Symptom]
1. Low speed return operation to the lowest level with buzzer ringing and display
ACD = 0B.
[Meaning] R5SC ON condition lasts for over 500ms after R5SC OFF was commanded. [Countermeasures]
SWD_I[VI_R5SC]
4. The LED(red) of R5SC relay will light on while driving.
SWD_O[VO_R5SC] check_out
Verify if contacts are connected during LED lights on and
0x8001 0x8082
disconnected during LED lights off.
SWD_I[VI_R5SC] SWD_O[VO_R5SC] Coil[SV_INV_SW_FAIL] 0x923D 5. Check contacts when relay turns on.
6. Replace R5SC relay(contactor type).
0x8001 0x8082 0x9210 Coil[SW_SS_DSP_WD]
check_out
TMC_Start(R5SC_
ERROR_DETECT_T)
TMC_Check(R5SC_ERROR_
DETECT_T, FINISH_STATE) SWD_I[VI_R5SC]
TCD 84
0x8001
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 48/103
○ Operation CPU
TCD 85 R5SC Relay off trouble Detection Application Si210
○ Speed CPU
[Meaning] R5SC OFF condition lasts for over 500ms after R5SC ON was commanded [Countermeasures]
1. Verify if the voltage of AB-01 is 48V .
2. Verify if the voltage of AA-01 is 48V when NORMAL/STOP
switch is positioned to NORMAL.
[Explanation]
3. Verify if R5SC relay is properly inserted.
SWD_I[VI_R5SC] 4. The LED(red) of R5SC relay will light on while driving.
SWD_O[VO_R5SC] check_out
Verify if contacts are connected during LED lights on and
0x8001 0x8082
disconnected during LED lights off.
SWD_I[VI_R5SC] SWD_O[VO_R5SC] Coil[SV_INV_SW_FAIL] 0x923D 5. Replace R5SC relay(contactor type).
check_out
TMC_Start(R5SC_
ERROR_DETECT_T)
TMC_Check(R5SC_ERROR_
DETECT_T, FINISH_STATE) SWD_I[VI_R5SC]
TCD 85
0x8001
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 49/103
○ Operation CPU
TCD 86 C1BR CTT. on trouble Detection Application Si210
○ Speed CPU
[Meaning] Even after 500ms away from C1BR off command, C1BR on is maintained. [Countermeasures]
P48
0x8082 0x9210
1. Check voltage of AA-08 of DOC-1XX from above circuit.
0x8001 Coil[SW_SS_DSP_WD]
• When C1BR driving section is ON : DC 48 V
check_out
• When C1BR driving section is OFF : 0 V
TMC_Start(R5SC_
ERROR_DETECT_T) 2. Check the state of input state indicating row(row 3)
TMC_Check(R5SC_ERROR_ column 10 on LCD of DOA-100.
DETECT_T, FINISH_STATE) SWD_I[VI_R5SC]
TCD 85
• When C1BR driving section is ON : 1
0x8001 • When C1BR driving section is OFF : 0
3. Check C1BR contact point of contactor.
• Even after 500ms away from OFF command of C1BR output, C1BR contact
does not turns OFF, and C1BR contact point input is ON is detected(driving
section ON failure).
• Even with C1BR contact off, C1BR contact point input on is detected, because
of contact point not being off(contact point melted and adhered).
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 50/103
○ Operation CPU
TCD 87 C1BR CTT. off trouble Detection Application Si210
○ Speed CPU
• Even after 500ms away from ON command of C1BR output, C1BR contact
does not become ON, and C1BR contact point input is OFF is detected(driving
section OFF failure).
• Even with C1BR contact on, C1BR contact point input off is detected, because
of contact point not being on(failure of contact point off).
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 51/103
○ Operation CPU
TCD 88 C1ST CTT. on trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
Even after 500ms away from C1ST off command, C1ST on is maintained.
P48
• Even after 540ms away from OFF command of C1ST output, C1ST contact
does not become OFF, and C1ST contact point input is ON is detected.
• Even with C1ST contact off, C1ST contact point input on is detected, because
of contact point not being off.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 52/103
○ Operation CPU
TCD 89 C1ST CTT. off trouble Detection Application Si210
○ Speed CPU
[Meaning] Even after 500ms away from C1ST on command, C1ST off is maintained. [Countermeasures]
P48
[Meaning] Even after 360ms away from driving OFF command from operation side [Countermeasures]
to speed side,ON feedback is maintained.
•1. Check flickering condition of WDT LED(green) of DPC-1XX.
•2. Check connection condition of communication cable(64P)
[Explanation] between operation and speed.
Coil[SV_INV_
Coil[RS_SUPPRESS_ON] RUN_STOP_FB] SWD_I[VI_C1ST] • Check flickering condition of SYS2 LED(green) of DOC-1XX.
0x91C3 0x9207
0x802A
Coil[SV_INV_
Coil[RS_SUPPRESS_ON] RUN_STOP_FB]
0x9207
0x91C3
check_out
TMC_Start(SUPRS_
ON_OFF_DETECT_T)
TMC_Check(SUPRS_ON_OFF_
DETECT_T, FINISH_STATE) Coil[RS_SUPPRESS_ON]
TCD 90
0x91C3
Even suppress OFF command of operation control side is maintained for 360ms,
the suppress command which is a feedback from speed control side does not
become OFF, and maintain continuously ON.
[Symptom]
[Meaning] Even after 360ms away from driving ON command from operation side [Countermeasures]
to speed side,OFF feedback is maintained.
•1. Check flickering condition of WDT LED(green) of DPC-1XX.
•2. Check connection condition of communication cable(64P)
[Explanation] between operation and speed.
Coil[SV_INV_ • Check flickering condition of SYS2 LED(green) of DOC-1XX.
Coil[RS_SUPPRESS_ON] RUN_STOP_FB] SWD_I[VI_C1ST]
0x91C3 0x9207
0x48082
Coil[SV_INV_
Coil[RS_SUPPRESS_ON] RUN_STOP_FB]
0x91C3 0x9207
check_out
TMC_Start(SUPRS_
ON_OFF_DETECT_T)
TMC_Check(SUPRS_ON_OFF_
DETECT_T, FINISH_STATE) Coil[RS_SUPPRESS_ON]
TCD 91
0x91C3
[Explanation]
ALM LED (Red color) on DOC-1XX is turned on: Operation unable condition
With speed command is more than 1m/min and C1ST & C1BR is on [Countermeasures]
1. In rope compensation operation, if the pulse of R/E doesn’t change for 4.86 seconds,
the trouble occurs.
1. Voltage check of AD connector in DOC-1XX in stop.
2. In other operation (not rope compensation), if the pulse of R/E doesn’t change for
• PIN 1 : 15 V ± 5% (power supply of R/E)
1.62 seconds, the trouble occurs.
• PIN 2 : 0 V ± 0.5 V (GND)
• PIN 3 : 0 V ± 0.5 V or 15 V ± 5%
Coil[RS_RUNNING] SWD_O[VO_C1BR] SWD_I[VI_C1BR] SWD_I[VI_C1ST] • PIN 4 : 0 V ± 0.5 V or 15 V ± 5%
0x91C3 0x9207 0x9207 0x48082 2. Check voltage of AD connector in DOC-1XX during running.
TCD 92
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 56/103
○ Operation CPU
TCD 93 R.E pulse counter read trouble Detection Application Si210
○ Speed CPU
[Meaning] The difference is more than 1mm in reading the value of R.E twice. [Symptom]
[Explanation]
In case the difference that is more than 1mm in reading the value of R.E twice, occurs
more than 10 times, TCD 92 is detected.
[Countermeasures]
[Meaning] In case that the case of changed value between R.E counter value read [Countermeasures]
in current cycle and in the previous cycle exceeds 3 times, and
1. Check SPEC data from address 0100H ~ 0112H of control
this exceeded value is continued for 150ms, the trouble is detected.
SPEC. (Refer to map of TCD 60)
2. Check if R.E is out of function. (Refer to TCD 92)
[Explanation]
[Meaning] [Countermeasures]
Off detected from hoist way and safety circuit.
1. Enter A21E in KEYPAD of DOA-100, to check address 8011
and verify the data if it is x01.
[Meaning] [Countermeasures]
In case of high speed signal and ON_CAR signal having input concurrent
time, or no signal of operation being inputted at the same time. DCL-241
P48V
[Explanation] $82AD
0x82AE
0x82AD P48V [ In case of applying IN CAR Switch ] DCL-241
CND_F_Op[CN_ON_CAR]
[Meaning] When CDS is inputted after DOLS operation, the trouble is detected. [Countermeasures]
SWD_O
[VO_R2OP] SWD_I[VI_LDS]
check_out
0x8083 0x802C
SWD_I[VI_DOLS] SWD_I[VI_CDS]
0x802D
TMC_Check(R2CD_R2LD_ 0x802B
ERROR_DETECT_T,RUN_STATE)
check_out
990 msec TMC_Start(R2CD_R2LD_
ERROR_DETECT_T)
TMC_Check(R2CD_R2LD_
ERROR_DETECT_T,
FINISH_STATE) Coil[DC_DOLS] SWD_I[VI_CDS] TCD 97
0x90A6 0x802B
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 61/103
○ Operation CPU
TCD 98 LDS trouble Detection Application Si210
○ Speed CPU
[Meaning] When LDS is inputted after DOLS operation, the trouble is detected. [Countermeasures]
SWD_O
[VO_R2OP] SWD_I[VI_LDS]
check_out
0x8083 0x802C
SWD_I[VI_DOLS] SWD_I[VI_CDS]
0x802D
TMC_Check(R2CD_R2LD_ 0x802B
ERROR_DETECT_T,RUN_STATE)
check_out
990 msec TMC_Start(R2CD_R2LD_
ERROR_DETECT_T)
TMC_Check(R2CD_R2LD_
ERROR_DETECT_T,
FINISH_STATE) Coil[DC_DOLS] SWD_I[VI_LDS] TCD 98
0x90A6 0x802C
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 62/103
○ Operation CPU
TCD 99 Dual input signal trouble Detection Application Si210
○ Speed CPU
[Meaning] Different contact states of the same inputs between operation CPU and [Countermeasures]
speed CPU exceeds for 300ms. 1. Check trace data of TCD 99 by means of ‘A42E’ trace mode.
2. The meaning of each bit is as left table, in case that ‘1’ is set
at one of bit, meaning of the bit is the reason of trouble.
[Explanation]
err_count ++
b7 b6 b5 b4 b3 b2 b1 b0
[Meaning] [Countermeasures]
SD1D does not operate from bottom floor.
1. Check the value of address 8023 from MEMORY READ
MODE, when car is not in bottom floor. If it is x00, it is normal. If
it is x01, check voltage of LSD-05, LSD-06 and HA-02. They
[Explanation] must have DC 48V.
DC48V is normal, if not, check wiring and connection.
It is detected when SD1D input does not enter when car is in bottom floor.
2. Check the value of address 8023 from MEMORY READ
TCD 77 TCD 78 TCD 114 ERD_Digi_Fl_Err MODE when car is in bottom floor. If it is x01, it is normal. If it is
x01, check voltage of LSD-06 and HA-02, and They must have
DC 0V.
Coil[SV_ Coil[SW_SS_48V_ Coil[AC_OP_ Coil[AC_OP_FHM_
FORCE_DECEL] DOWN_HOLD] FHM_MODE] START_MODE] 3. Check if SD switches works normally.
0x921D 0x923C 0x9031 0x9032
4. Check assembly condition of SD
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Bottom SWD_I[VI_SD1D]
TCD 100
0x8023
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 64/103
○ Operation CPU
TCD 101 SD2D ON trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
SD2D does not operate from bottom floor.
1. Check the value of address 8024 from MEMORY READ
MODE, when car is not in bottom floor. If it is x00, it is normal. If
it is x01, check voltage of LSD-07, LSD-08 and HA-03. They
[Explanation] must have DC 48V.
DC48V is normal, if not, check wiring and connection.
Detected only when the rated speed is 90m/min or more.
Detected when SD2D input does not enter when car is on the bottom floor. 2. Check the value of address 8024 from MEMORY READ
MODE when car is in bottom floor. If it is x01, it is normal. If it is
x01, check voltage of LSD-08 and HA-03, and They must have
TCD 77 ERD_Digi_Fl_Err
DC 0V.
TCD 78 TCD 114
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Bottom SWD_I[VI_SD2D] TCD 101
SPD_Control_Spec. 0x8024
Contract_Velocity >= 90
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 65/103
○ Operation CPU
TCD 107 SD1U ON trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
SD1U does not operate from bottom floor.
1. Check the value of address 8021 from MEMORY READ MODE,
when car is not in top floor. If it is x00, it is normal. If it is x01,
check voltage of LSU-05, LSU-06 and HA-06. They must have DC
[Explanation] 48V.
DC48V is normal, if not, check wiring and connection.
It is detected when SD1U input does not enter when car is in top floor.
2. Check the value of address 8023 from MEMORY READ MODE
when car is in top floor. If it is x01, it is normal. If it is x01, check
TCD 77 TCD 78 TCD 114 ERD_Digi_Fl_Err
voltage of LSU-06 and HA-06, and They must have DC 0V.
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Top SWD_I[VI_SD1U]
TCD 107
0x8021
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 66/103
○ Operation CPU
TCD 108 SD2U ON trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
SD2U does not operate from bottom floor.
1. Check the value of address 8022 from MEMORY READ
MODE, when car is not in bottom floor. If it is x00, it is normal. If
it is x01, check voltage of LSU-07, LSU-08 and HA-07. They
[Explanation] must have DC 48V.
DC48V is normal, if not, check wiring and connection.
Detected only when the rated speed is 90m/min or more.
Detected when SD2U input does not enter when car is on the top floor. 2. Check the value of address 8022 from MEMORY READ
MODE when car is in bottom floor. If it is x01, it is normal. If it is
x01, check voltage of LSU-08 and HA-07, and They must have
TCD 77 TCD 78 TCD 114 ERD_Digi_Fl_Err DC 0V.
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Top SWD_I[VI_SD2U]
TCD 108
SPD_Control_Spec. 0x8022
Contract_Velocity >= 90
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 67/103
○ Operation CPU
TCD 114 POSI ON trouble (LDC) Detection Application Si210
○ Speed CPU
[Explanation] 2. Check at door zone, if the value of 3rd row and 5th column of
Coil[RS_RUNNING] Coil[SW_FS_MAINT] SWD_I[VI_LDC] DOA-100 is ‘1’.
0x91B0 0x929A 0x8025
3. Check at no door zone, if the value of 3rd row and 5th column
Coil[SW_GS_LDC]
of DOA-100 is ‘0’.
0x9251
4. Check the voltage between Y1-05 of DOM-100 and CA-10 of
Coil[SW_GS_OPEN_ZONE] Coil[IS_CUR_V_10]
check_out DOC-1XX. (with door zone, 0V is normal and without door zone,
0x9256 0x91EB 48V is normal)
check_out 2070 msec
TMC_Start(POSI_
OFF_ERR_T)
5. Check if POSI is defective.
TMC_Check(POSI_OFF_
ERR_T,FINISH_STATE)
TCD 114
POSI off error
TMC_Start(POSI_ON_
OFF_DETECT_T)
TMC_Check(POSI_ON_OFF_
DETECT_T,FINISH_STATE) TCD 114
POSI on error
SWD_I[VI_LDC]
old_LDC_state
0x8025
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 68/103
○ Operation CPU
TCD 116 POSI ON trouble (LDU) Detection Application Si210
○ Speed CPU
[Explanation]
[Countermeasures]
When LDU trouble is detected, rope compensation function would be cut.
1. The trouble will be detected, when SPEC data in address 0016
SPD_Function. TMC_Check(POWER_ Coil{AC_OP_ SPD_I[SP_ is set, even if rope compensation is not applied.
Rope_Compen READY_T,FINISH_STATE) MAINT_MODE] FAC_INSPECT]
[Explanation]
[Countermeasures]
When LDD trouble is detected, rope compensation function would be cut.
1. The trouble will be detected, when SPEC data in address 0016
SPD_Function. TMC_Check(POWER_ Coil{AC_OP_ SPD_I[SP_
Rope_Compen READY_T,FINISH_STATE) MAINT_MODE] FAC_INSPECT]
is set, even if rope compensation is not applied.
ldc_off_event
0x91AF
SWD_I[VI_LDC]
old_ldc
0x8025
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 70/103
○ Operation CPU
TCD 119 SLOW DOWN S/W trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
When speed command is more than 10m/min but real speed is 8m/min
or less, and this continues more than 3 sec. The trouble will be detected.
1. Refer to TCD 86.
2. Check assembly condition of Brake if it works normally.
3. Check the disconnection of Rotary Encoder.
[Explanation]
See TCD 92.
SWD_I[VI_C1BR] Coil[IS_CMD_V_10] Coil[IS_CUR_V_8] Coil[AC_OP_ALP_MODE]
Coil[RS_ROPE_
Coil[RS_DECELERATION] COMPEN_REQUEST]
0x91BE 0x91A8
Coil[RS_ROPE_COMPEN_RUN]
0x91B5 0x92A8
Coil[A_ALP_RUN_PERMIT] Coil[SW_ALP_DIR_DECISION]
check_out
0x9062 0x92BC
check_out
3060 msec TMC_Start(BREAK_
OFF_DETECT_T)
TMC_Check(BREAK_OFF_
DETECT_T,FINISH_STATE)
TCD125
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 72/103
○ Operation CPU
TCD 130 Load detector input trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
It will be detected in Input trouble of Load detector
Potential meter (PTM)
1. Perform ‘No Load Point Setting’ (A61E) and ‘Full Load Point
Setting’ (A62E).
- ‘No Load Point Setting’ is priority.
[Explanation]
Detected load by load detector exceeds 135% or is under -25%, and either 2. Check if channel value of each PTM shows on 3rd row normally.
condition continues for 2 sec. and more. - Car load mode (A86E)
[Condition]
Make high speed operation unable with door opening.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 73/103
○ Operation CPU
TCD 132 Door open lock detection Detection Application Si210
○ Speed CPU
[Meaning] DOLS signal does not go in within 10 sec. after open command
Door open lock detected
and if this condition repeats 3 times, the trouble will be detected.
[Countermeasures]
1. Check door operating. In case that door can’t operate due to a
[Explanation]
Coil[SW_SS_48V_
foreign substance on sill, remove it.
Coil[RS_
RUNNING] Coil[DC_DOLS] Coil[DC_DCO] DOWN_HOLD] 2. Check if DMC CUT of DOR-131 & apparatus box is placed on
NORMAL.
0x91B0 0x90A6 0x9082 0x923C 3. Check open command signal.
If data of 2nd row & 13th column of annunciator is ‘1’, open
Coil[A_AUTO_ Coil[SW_GS_ command is energizing.
DOOR_CLOSE] OPEN_ZONE] SWD_O[VO_R2OP] Check if the volt of CA-01 is 0.7V±0.1V.
check_out
Check the connection & wiring, if the data is ‘0’ and the volt of
0x9050 0x9256 0x8083
ERD_Door_Err CA-07 is 0V±0.1V.
4. If LED of R2LD relay isn’t off. Check the volt of AB-15 (LDS) &
TMC_Check(OPEN_LOCK_DETECT_T,FINISH_STATE) CA-08 (CDS).
check_out
(OPEN_LOCK_DETECT
When door is opened, the volt of AB-15 & CA-08 should be 0V
_T).Spec = 4000 level.
0x8083
5. When door is opened completely, check if data of 3rd row &
15th column of annunciator is ‘1’. ‘1’ is normal.
6. If the volt of CA-07 is 48V±10%, check the condition of DOLS
(OPEN_LOCK_DETECT
_T).Spec = 10000 contactor. When door is opened, check LD5 (OLS/CLS) of DCD
PCB is turned on. (LED is on in normal)
TMC_Start(OPEN_ 7. Check if RDZ relay operates normally.
LOCK_DETECT_T)
TMC_Check(OPEN_LOCK_ LED of the relay should be turned on with door zone and off
Open_Trouble_Count < 3
DETECT_T,FINISH_STATE) without door zone.
TMC_Start(OPEN_
LOCK_DETECT_T)
Open_Trouble_Count++
TMC_Reset(OPEN_
LOCK_DETECT_T)
Open_Trouble_Count >= 3
TCD 132
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 74/103
○ Operation CPU
TCD 133 Open_Lock repeated trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
TCD132 occurs 3 times in series
Refer to TCD132.
[Explanation]
If TCD132 occurs, it tries to open door of another floor after moving to another
floor. But if TCD132 occurs 3 times in series, ‘Open Lock repeated trouble’ will
occurs.
The elevator keeps hall/car call unable and stops operation.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 75/103
○ Operation CPU
TCD 134 Door close lock detection Detection Application Si210
○ Speed CPU
[Meaning] Door does not close within 10 sec. after close command,
Door close lock detected
the trouble will be detected.
[Countermeasures]
1. Check door operating. In case that door can’t operate due to a
[Explanation]
foreign substance on sill, remove it.
Coil[A_AUTO_ Coil[SW_GS_
DOOR_CLOSE] DOOR_ZONE] Coil[IS_ZERO_V] Coil[DC_DCO] ERD_Door_Err 2. Check if DMC CUT switch of DOR-131 & apparatus box is
placed on NORMAL.
0x9050 0x9250 0x91F2 0x9082 3. Check close command signal.
If data of 2nd row & 14th column of annunciator is ‘1’, close
SWD_I[VI_CDS] command is energizing.
SWD_O[VO_R2CL] check_out Check if the volt of CA-02 is 0.7V±0.1V.
0x8684 0x802B 4. If LED of R2LD relay isn’t off. Check the volt of AB-15 (LDS) &
Coil[DC_F_CLS] Coil[SW_SV_2ND_FIRE] CA-08 (CDS).
When door is closed, the volt of AB-15 & CA-08 should be 48V
0x90B5 0x9275 level.
SWD_I[VI_LDS] 5. When door is closed, check if data of 3rd row & 12th (LDS) &
13th (CDS) column of annunciator is ‘1’. ‘1’ is normal.
0x802C
TMC_Check(CLOSE_LOCK_ 6. If 12th (LDS) is ‘0’, check the volt of AB-15 and condition of
DETECT_T,FINISH_STATE) TCD 135 landing door.
If 13th (CDS) is ‘0’, check the volt of CA-08 and condition of
Coil[SW_GS_ car door.
Coil[DC_DOLS] OPEN_ZONE]
7. Check if data of 3rd row & 14th column of annunciator is ‘1’.
TMC_Check(FORCE_ 0x90A6 0x9256 ‘1’ is normal.
OPEN_T,FINISH_STATE) 8. Check the condition of DCLS contactor. When door is closed,
check_out
With NUGING : 20 sec check LD5 (OLS/CLS) of DCD PCB is turned on.
Without NUGING : 10 sec TMC_Start (CLOSE_ (LED is on in normal)
LOCK_DETECT_T)
9. Check if RDZ relay operates normally.
TMC_Check(CLOSE_LOCK_
DETECT_T,FINISH_STATE) LED of the relay should be turned on with door zone and off
close_lock_count ++
without door zone.
close_lock_count >= 2
TCD 134
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 76/103
○ Operation CPU
TCD 135 Close_Lock repeated trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
TCD134 occurs 12 times (can be changed by SPEC) in series
Refer to TCD134.
[Explanation]
[Meaning] [Countermeasures]
When ALP control panel is out of order.
1. Check if the condition of ALP is normal by annunciator of ALP.
In case of power failure, elevator must go to door zone by the power of ALP,
but elevator isn’t operable due to abnormal condition.
Abnormal condition
1. Operation unable due to R5SC off.
2. Operation unable due to floor error.
3. Operation unable due to abnormal signal from DSP.
4. In case that the speed exceeds designated speed.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 78/103
○ Operation CPU
TCD 140 Discharging voltage of Backup Battery under reference Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
NVRAM is abnormal
1. Check if Backup Battery is normal.
This trouble doesn’t hinder elevator operating. It will be returned to normal after
rescue operation to bottom floor.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 79/103
○ Operation CPU
TCD 141 Clock chip trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
When RTC chip doesn’t operate well, the trouble occurs.
1. Perform ‘RTC set’ by ‘A69E’.
In case that RTC chip is abnormal, the trouble occurs. 3. Replace DOC-1XX.
This trouble doesn’t hinder elevator operating.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 80/103
○ Operation CPU
TCD 145 INV. Door CPU WDT trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
In case that the connection between apparatus box & DCL-24X is
abnormal.
1. Check if the connection between TERM-01 and DRIN-01 is
disconnected.
[Explanation]
[Meaning] [Countermeasures]
Float switch is still activated even after drain operation for 1 min.
1. Check the float switch.
[Explanation]
1. This trouble doesn’t hinder elevator operating even if the trouble occurs.
[Meaning] [Condition]
The signal of LDC keep off for 20~45 sec. at on position during high
speed operation. (Detecting time is depend on floor height)
This is hold type, so cut safety line and keep elevator inoperable.
[Explanation]
TMC_Start(OBS_
LDC_ON_DETECT_T)
TMC_Check(OBS_LDC_ON_
DETECT_T,FINISH_STATE)
TCD147
SWD_I[VI_LDC] old_LDC_state
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 83/103
○ Operation CPU
TCD 150 SD1D Over Speed detection Detection Application Si210
○ Speed CPU
[Meaning] Over speed is detected at SD1D zone and emergency stop. [Countermeasures]
1. When SD1D is activated, check the volt of HA-02.
Normal: 48V → 0V.
2. When SD1D is activated, check address 0x8023 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD1D.
>> The speed is 15m/min higher than the command at where SD1D is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the speed is less than 30 m/min, No trouble is detected.
2. In case that the condition of forced deceleration is not detected.
Speed 60 m/min 90 m/min 105 m/min
( Coil[SV_FORCE_DECEL] = OFF )
1) 60m/min Distance 1000 mm 1400 mm 1800 mm
>> If the speed is higher than limit speed below according to regular speed at
where SD1D is activated, the trouble will be detected. * Above distance is from ‘0’ level of bottom floor to the center of
switch roller.
2) 90m/min and higher
>> If the speed is higher than limit speed below according to regular speed at
where SD1D is activated and this condition keeps for 150 msec. and more,
the trouble will be detected.
[Meaning] Over speed is detected at SD2D zone and emergency stop. [Countermeasures]
1. When SD2D is activated, check the volt of HA-03.
Normal: 48V → 0V.
2. When SD2D is activated, check address 0x8024 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD2D.
>> The speed is 15m/min higher than the command at where SD2D is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the speed is less than 30 m/min, No trouble is detected. Speed 90 m/min 105 m/min
2. In case that the condition of forced deceleration is not detected.
( Coil[SV_FORCE_DECEL] = OFF ) Distance 2000 mm 2700 mm
>> If the speed is higher than limit speed below according to regular speed at
where SD2D is activated and this condition keeps for 150 msec. and more, * Above distance is from ‘0’ level of bottom floor to the center of
the trouble will be detected. switch roller.
[Meaning] Over speed is detected at SD1D zone and emergency stop. [Countermeasures]
1. When SD1U is activated, check the volt of HA-06.
Normal: 48V → 0V.
2. When SD1U is activated, check address 0x8021 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD1U.
>> The speed is 15m/min higher than the command at where SD1U is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the speed is less than 30 m/min, No trouble is detected.
Speed 60 m/min 90 m/min 105 m/min
2. In case that the condition of forced deceleration is not detected.
( Coil[SV_FORCE_DECEL] = OFF ) Distance 1000 mm 1400 mm 1800 mm
1) 60m/min
>> If the speed is higher than limit speed below according to regular speed at * Above distance is from ‘0’ level of top floor to the center of
where SD1U is activated, the trouble will be detected. switch roller.
2) 90m/min and higher
>> If the speed is higher than limit speed below according to regular speed at
where SD1U is activated and this condition keeps for 150 msec. and more,
the trouble will be detected.
[Meaning] Over speed is detected at SD2U zone and emergency stop. [Countermeasures]
1. When SD2U is activated, check the volt of HA-07.
Normal: 48V → 0V.
2. When SD2U is activated, check address 0x8022 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD2U.
>> The speed is 15m/min higher than the command at where SD2U is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the speed is less than 30 m/min, No trouble is detected. Speed 90 m/min 105 m/min
2. In case that the condition of forced deceleration is not detected.
( Coil[SV_FORCE_DECEL] = OFF ) Distance 2000 mm 2700 mm
>> If the speed is higher than limit speed below according to regular speed at
where SD2U is activated and this condition keeps for 150 msec. and more, * Above distance is from ‘0’ level of top floor to the center of
the trouble will be detected. switch roller.
[Meaning] Emergency stop detected, elevator is suddenly stopped during run with [Countermeasures]
more than 10m/min speed by the trouble in relation to R/E.
1. Check whether MAINT(Inspection) switch has been operated
during driving.
2. Verify whether switch and connectors in PCB have had
[Explanation] bad contacts.
3. Check if R/E is disconnected.
run_stop Coil[RS_RUNNING] Coil[IS_CUR_V_10] 4. Check if LDS &CDS operate normally.
TCD 164
5. Check the state of R5SC relay.
0x91EE
0x91B0 6. Check the state of ALARM LED.
TCD 92 7. Check the flickering state of SYS1 LED inside DOC-1XX.
8. Check the flickering state of SYS2 LED inside DOC-1XX.
9. Check if safety switches are activated. (Man-hole, pit, SCS)
TCD 93
* In case of emergency stop with 10m/min speed and more
The reason can be analyzed by ERROR LOG Table (A42E)
TCD 94
- Trace monitor
0x91B0
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 88/103
○ Operation CPU
TCD 168 Speed difference (real speed detection) Detection Application Si210
○ Speed CPU
[Meaning] When the speed difference between command & real is more than [Countermeasures]
30m/min, the trouble is detected.
1. Refer to TCD 60 and check if SPEC is correct in accordance
with the field.
2. Check if brake open & close as its function.
[Explanation] 3. Check disconnection of Rotary Encoder (AD Connect).
Refer to TCD 92.
Coil[IS_CUR_V_15] Coil[IS_CMD_V_15] SWD_O[VO_C1BR] Coil[SV_DDLP_CMD] 4. Check balancing rate between car & C.WT.
(It must be within 0.45 ~ 0.55)
0x91EC 0x91E4 0x8080 0x9206
Coil[RS_FAST_
SWD_I[VI_C1BR] SWD_I[VI_LDS] SWD_I[VI_CDS] RUN_COMMAND] check_out
abs(SVD_Cmd_V - SVD_Cur_V)
check_out >= 30 speed_err_count ++ speed_err_count
SVD_Cmd_V <
speed_err_count > 3
SVD_Cur_V TCD 168
speed_err_count > 12
TCD 168
check_out
=0 speed_err_count
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 89/103
○ Operation CPU
TCD 170 Operation direction trouble Detection Application Si210
○ Speed CPU
[Explanation]
[Countermeasures]
Coil[IS_CUR_V_8] Coil[RS_RUNNING] 1. Check if DIR LED is on.
check_out
2. If DIR LED is on, change the position of DIR jumper in
0x91EA 0x91B0 DOC-1XX.
3. Switch to MAINT(Inspection) operation, and perform
UP/DOWN operation for a little while, to check right/reverse
540 msec matter in operating direction.
check_out Coil[RS_UP_RUN] enco_diff < 0 In reverse, change DIR jumper in DOC-1XX.
TMC_Start(DIR_ 4. When rerunning, make sure to reset.
0x91AE ERROR_DETECT_T) 5. Verify if BIT 8 of SPEC1 is OFF.
6. Still no effect, change 2-phases of MOTOR output line.
0x91AF
TMC_Reset(DIR_
ERROR_DETECT_T)
TMC_Check((DIR_ERROR_
SWD_Emergency_Call DETECT_T, FINISH_STATE)
TCD170
ICC_Set_Sys_Output_Port
(RE_DIR_ERROR, ON)
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 90/103
○ Operation CPU
TCD 171 Synchronous position trouble Detection Application Si210
○ Speed CPU
15 .. 7 6 5 4 3 2 1 0
[Meaning] It is detected that the failures of high speed running prohibited have [Countermeasures]
occurred 12 times within 10 min
1. Check Error Log Table by A42E, find out the trouble occurred
frequently and perform trouble shooting.
[Explanation]
Coil[EM_EO_ Coil[AC_OP_
old_fast_run_cut FAST_RUN_CUT] MAINT_MODE] +1 E_Stop_Count[9]
0x90F4 0x9030
+1 E_Stop_10M_Count
E_Stop_10M_Count >= 12
TCD 177
Coil[EM_EO_FAST_RUN_CUT] old_fast_run_cut
0x90F4
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 92/103
○ Operation CPU
TCD 178 Safety drive occurred frequently Detection Application Si210
○ Speed CPU
[Meaning] Detected that rescue running have occurred more than 6 times [Countermeasures]
within 10 min.
1. Door Zone 외에 정지하는 원인을 찾는다.
2. 주행 중에 비상 정지하는 경우는 Error Log Table 참조한다.
3. 착상 시 Door Zone에 못 미치거나 지나쳐서 정지하는 경우는
[Explanation]
SPEC의 착상 제어용 파라메터 설정이 바르게 되어 있는지
It is hold type, prohibit operation by R5SCafter opening door at door zone 확인 한다. ( Pgc_Gain → ADDR:0x0212 )
1. Search the reason for stopping out of door zone.
2. If stopping during running, refer to the error log table,
Coil[SW_FS_SAFETY_DRIVE_DETECT] tmp 3. When below-stopping or over-stopping during leveling occurs
verify whether parameter setting for the control of leveling is
0x92A8 light. (Pgc_Gain → ADDR:0x0212)
0x9030
+1 S_Drv_10M_Count
tmp old_safety_drive
Coil[SW_GS_IS_STOP] SWD_I[VI_LDC]
TCD 178
Stop at door zone with door opened for 10 min., and return
normal operation automatically.
[Explanation]
[Condition]
Stand by 10 min. after door open at door zone.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 94/103
○ Operation CPU
TCD 184 SDS forced deceleration occurred frequently Detection Application Si210
○ Speed CPU
Coil[AC_OP_ Coil[SW_SV_
FIREMAN_MODE] 2ND_FIRE]
TMC_Check(OLS_ERROR_
DETECT_T,FINISH_STATE) Coil[SW_GS_DOOR_ZONE]
TCD 188
0x9250
0x802B 0x802D
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 96/103
○ Operation CPU
TCD 192 Door position trouble Detection Application Si210
○ Speed CPU
[Explanation]
In case of the trouble of door thermal, under voltage, over voltage & current,
TCD192 occurs.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 97/103
○ Operation CPU
TCD 200 CNET LON communication trouble Detection Application Si210
○ Speed CPU
[Meaning] DPRAM communication between Main LON and i186 does not operate [Countermeasures]
1. If the trouble isn’t disappeared after system reset is done on
DOC-1XX, Check if ROM(OS ROM) of DOC-1XX & ROM Main
LON are mounted correctly.
[Explanation] 2. If the trouble isn’t disappeared after performing 1 item above,
Replace ROM(OS ROM) of DOC-1XX & ROM Main LON.
3. Replace DOC-1XX even if nothing is improved after performing
I186EC_Port3_Input & 0x20
Coil[VALID_186_TOKEN] item 2 above.
0x9300
err_count > 5
TCD 200
[Condition]
LON LED on DOC-1XX will light off.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 98/103
○ Operation CPU
TCD 202 Car communication trouble Detection Application Si210
○ Speed CPU
[Condition]
LON LED of DOC-1XX or LED of DCL-24X is flickering with 1.2 sec. cycle
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 99/103
○ Operation CPU
TCD 211 Other elevator trouble Detection Application Si210
○ Speed CPU
[Meaning] Communication error with other car is detected in duplex operation. [Countermeasures]
HJP SH
HJP SH
SH SL SL SH
DHG-16X
DHG-16X
DHG-16X
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 100/103
○ Operation CPU
TCD 217 Hall button jam detection Detection Application Si210
○ Speed CPU
[Meaning] When hall button is being pushed continuously, the trouble is detected. [Countermeasures]
Button_Jam_Detect[0][UP_INDX]
TCD 217
Button_Jam_Detect[0][DN_INDX]
Address Floor
0x9954 1st floor ~ 8th floor UP Button
0x9955 9th floor ~ 16th floor UP Button
0x9956 17th floor ~ 24th floor UP Button
0x9957 25th floor ~ 32nd floor UP Button
0x9958 1st floor ~ 8th floor DOWN Button
0x9959 9th floor ~ 16th floor DOWN Button
0x995A 17th floor ~ 24th floor DOWN Button
0x995B 25th floor ~ 32nd floor DOWN Button
[Meaning] Communication error with all floor in hall line is detected [Countermeasures]
H_Data_Receive_Wait_Counter == 0
[Condition]
When TCD224 occurs, operation mode would be ACD26 and perform backup
operation.
Revision: 0
MMR Elevator_SI / Trouble Shooting Page: 103/103