PROCESO
DATOS:
Altura de piso a techo 2.40 m
Altura de tablero de distribución 1.80 m
METRADO DE CONDUCTOR ELECTRICO DE ILUMINARIA PARA UN CIRCUITO DE 2 VIAS
DUCTO:
0.60+0.50+2.5+0.05=3.65m de ducto
CONDUCTOR:
0.5+0.12+3.65+0.12+0.15=4.54m de conductor
Centro de luz = 20.5+4.54=25.04
25.04*25%=31.3m*2=62.6m
1.60m

1.50m 1.50m

1.80m

1.60m
2m
PROCESO

DATOS:
Altura de piso a interruptor 1.20m
Altura de piso al techo 2.40m
METRADO DE LOS INTERRUPTORES
CONDUCTOR:
SC:1.60+2=3.60m*100%=7.2m*3=21.6m
S:1.50+1.50+1.60+1.80=6.4m*100%=12.8m*2=25.6m
21.6m+25.6m=47.2m
3m
3m

6m

4m

8m
4m

3m
2.5m
2m
2m 2m
3.5m
METRADO DE CONDUCTOR DE TOMACORRIENTES DE 2 VIAS MAS TIERRA
DUCTO: 1.8+2+0.3=4.1m
DUCTO: 0.5+2.5+0.3= 3.3m/ 0.5+2+0.3=2.8m /0.5+3.5+0.3= 4.3m /0.5+8+0.3=8.8m
0.5+2+0.3=2.8m/0.5+3+0.3=3.8m /0.5+4+0.3=4.8m /0.5+4+0.3=4.8 /0.5+6+0.3=6.8m /1.8+3+0.3=3.8m
CONDUCTOR:0.5+0.12+4.1+0.12+0.15=4.99m
0.15+0.12+3.3+0.12+0.15= 3.84m*3=11.52m
/0.15+0.12+2.8+0.12+0.15=3.34m*3=10.02m/0.15+0.12+4.3+0.12+0.15= 4.84m*3=14.52m
0.15+0.12+8.8+0.12+0.15=9.34m*3=28.02m/0.15+0.12+2.8+0.12+0.15=3.34m*3=10.02m
/0.15+0.12+3.8+0.12+0.15=4.34m*3=13.02m/ 0.15+0.12+4.8+0.12+0.15=5.34m*3=16.02m
/0.15+0.12+6.8+0.12+0.15= 7.34m*3=22.02m/0.15+0.12+3.8+0.12+0.15= 4.34m*3=13.02m

NUMERO DE CONDUCTOR

EL CABLEADO GENERAL QUE SE UTILIZARA EN EL CIRCUITO DE TOMACORRIENTES ES DE 138.18 METROS


ESPECIFICACIONES UNIDAD CANTIDAD
Tablero principal PZA 1
Salida de techo PTOS 7
Salida de tomas PTOS 12
Lampara led PZA 8
Tomacorrientes dobles PZA 12
Interruptor simple PZA 6
Interruptor doble PZA 2
Interruptor de conmutación PZA 2
Tomacorriente doble con punto a tierra PZA 9
Conductor negro 12AWG ROLLO 100M
Conductor amarrillo verde 12 AWG ROLLO 100M
Conductor rojo 12 AWG ROLLO 100M