terminals?
Ans: In PNP type of wiring, the command of the digital input is executed when the
digital input terminal is connected to the positive terminal of 24V dc power supply
as shown in Fig1-A.
In NPN type of wiring, the command execution is done by short-circuiting the
digital input terminal to the dc common terminal (CM) as shown in Fig1-B.
Fig1-A Fig1-B
Q2: Which type of VFD open loop control should be used to reduce the effect of
loading on the speed regulation?
Ans: Slip compensation control mode which enable the motor to run at a constant
speed by compensating the inherent slip of the induction motor.
Q3: What is meant by torque boost, and where it should be used?
Ans: It is a function that increases the VFD output voltage to increase the starting
torque at low speed. it should be used with loads that require high starting torques
like cranes.
Q4: Is it possible to run two motors using one VFD unit? If the answer is yes,
mention in details what do you have to do to achieve that under full protection of
both motors?
Ans: Yes it is possible and to achieve that do the following:
1- Set one of the multi-function input terminals for second motor operation.
2- Assign the suitable values for the 2nd motor operation.
Q5: Is it possible to run a single phase load using single phase input/ three phase
output VFD unit? If the answer is yes, state how to do that.
Ans: yes it is possible. To allow powering signle phase load, the output loss phase
protection should be disabled.
Q8: What one must do to let the VFD displays the shaft mechanical speed instead
of the rpm of the revolving field.
Ans: By setting the Gain for motor speed display (H74)
Shaft mechanical speed=(120 ×f/P) × Gain for motor speed display.