Chapter 4 (Part 2)
Chapter 4 (Part 2)
3
(ASHRAE 62.1: Table 6-1)
Note: Ventilation air supply requirements for occupancies regulated by the California
Energy Commission are found in the California Energy Code.
Max (Zp) Ev
<0.15 1.0
<0.25 0.9
<0.35 0.8
<0.45 0.7
<0.55 0.6
<0.55 Use ASHRAE 62.1, Appendix A
(Minimum efficiency
Area Designated Minimum Number of reporting value MERV)5
Filter Banks No. 11 No. 21
All areas for inpatient care, 2 30% 80%
treatment and/or diagnosis, and
those areas providing direct
service or cleaning supplies (13) (8)
Administrative, bulk storage, 1 30%
soiled holding, laundries and
food prep areas (8)