Performance Report

Hospital River of Life - 700RT (6)


Carrier Malaysia Sales Office
Date: 3/20/2021 10:24 AM Prepared By: Amir Bidin

19DV-G41G434425F9
Chiller
Starter / VFD VFD ±Unit Mounted (STD tier)
Refrigerant Type R-1233zd(E)
Envelope Stability Control Installed
Liquid Bypass Not Installed
Operation Type Cooling

Configuration Cooler Condenser


Size G41 G43
Waterbox Type Nozzle-in-Head, 150 psi (Standard) Nozzle-in-Head, 150 psi (Standard)
Passes 2 2
Nozzle Arrangement C - 2 Pass, Inlet on 2nd Stage End R - 2 Pass, Inlet on 2nd Stage End
Tubing B5 LP (SUPB5LP), .025 in., Copper (Standard) C5 LP (SUPC5LP), .025 in., Copper (Standard)
Fluid Type Fresh Water Fresh Water
Fouling Factor 0.000100 h·ft2·°F/Btu 0.000250 h·ft2·°F/Btu
Tube Quantity 398 632

Compressor
Size 442
Weights
Total Rigging Weight 34086 lb
Total Operating Weight 38816 lb
Refrigerant Weight 1205 lb
Motor and Starter
Motor Size NFH
Line Voltage-Phase-Hertz 400-3-50
VFD Code 5
VFD Size 5
Flow Controls
Condenser float valve HN
Economizer float valve LN

19DV AquaEdge Chiller Builder Version 2.1.0.0 (Asia) Page 1 of 4


Performance Report
Hospital River of Life - 700RT (6)
Carrier Malaysia Sales Office
Date: 3/20/2021 10:24 AM Prepared By: Amir Bidin

Performance
Chiller
Percent Load 100.00
Capacity WRQȆ
Input kW 386.2 kW
Cooling kW/tonR N:WRQȆ
Cooler
Entering Temperature 56.00 °F
Leaving Temperature 42.00 °F
Flow Rate 1198 gpm
Pressure Drop 18.6 ft HೣO
Condenser
Heat Rejection 9.718 MBtu/h
Leaving Temperature 96.31 °F
Entering Temperature 87.00 °F
Flow Rate 2100 gpm
Pressure Drop 25.4 ft HೣO
Motor and Starter
Motor Amps 661
Motor OLTA 714
Chiller line Amps 627
Chiller Inrush Amps 627
Max Fuse/ CB Amps 1200
Min Circuit Ampacity 783
Heat Exchangers
Condensing Temp 98.2 °F
Cooler Wall Temp 43.0 °F
Suction Temp 40.4 °F
Cooler Freeze Temp 36.0 °F
Cooler Tube Vel 5.89 ft/s
Cond Tube Vel 7.28 ft/s

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages
Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Certified units may be found in the AHRI Directory at www.ahridirectory.org

http://www.ahridirectory.org

19DV AquaEdge Chiller Builder Version 2.1.0.0 (Asia) Page 2 of 4


Performance Report
Hospital River of Life - 700RT (6)
Carrier Malaysia Sales Office
Date: 3/20/2021 10:24 AM Prepared By: Amir Bidin

Load Line
Chiller
Percent Load 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00
Capacity WRQȆ 700.0 630.0 560.0 490.0 420.0 350.0 280.0 210.0 140.0 70.00
Input kW kW 386.2 326.5 277.0 233.3 195.1 161.1 129.8 104.0 78.27 57.91
Cooling kW/tonR N:WRQȆ 0.5515 0.5182 0.4946 0.4760 0.4644 0.4601 0.4634 0.4949 0.5589 0.8271
Cooler
Entering Temperature °F 56.00 54.60 53.19 51.79 50.39 48.99 47.59 46.19 44.79 43.40
Leaving Temperature °F 42.00 42.00 42.00 42.00 42.00 42.00 42.00 42.00 42.00 42.00
Flow Rate gpm 1198 1198 1198 1198 1198 1198 1198 1198 1198 1198
Pressure Drop ft HೣO 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6 18.6
Condenser
Heat Rejection MBtu/h 9.718 8.674 7.665 6.676 5.706 4.750 3.803 2.875 1.947 1.038
Leaving Temperature °F 96.31 94.64 93.01 91.39 89.79 88.22 86.64 85.08 83.53 81.99
Entering Temperature °F 87.00 86.33 85.67 85.00 84.33 83.67 83.00 82.33 81.67 81.00
Flow Rate gpm 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100
Pressure Drop ft HೣO 25.4 25.5 25.5 25.5 25.5 25.5 25.5 25.6 25.6 25.6
Motor and Starter
Motor Amps 661 594 536 480 429 384 348 315 298 275
Motor OLTA 714 NA NA NA NA NA NA NA NA NA
Chiller line Amps 627 533 454 385 329 277 227 186 142 109
Chiller Inrush Amps 627 NA NA NA NA NA NA NA NA NA
Max Fuse/ CB Amps 1200 NA NA NA NA NA NA NA NA NA
Min Circuit Ampacity 783 NA NA NA NA NA NA NA NA NA
Heat Exchangers
Condensing Temp °F 98.2 96.3 94.4 92.6 90.8 89.1 87.3 85.6 83.9 82.2
Cooler Wall Temp °F 43.0 42.9 42.8 42.7 42.6 42.6 42.6 42.5 42.4 42.2
Suction Temp °F 40.4 40.6 40.8 40.9 41.1 41.1 41.1 41.0 41.0 41.2
Cooler Freeze Temp °F 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0
Cooler Tube Vel ft/s 5.89 5.89 5.89 5.89 5.89 5.89 5.89 5.89 5.89 5.89
Cond Tube Vel ft/s 7.28 7.28 7.28 7.28 7.29 7.29 7.29 7.29 7.29 7.29

19DV AquaEdge Chiller Builder Version 2.1.0.0 (Asia) Page 3 of 4


Performance Report
Hospital River of Life - 700RT (6)
Carrier Malaysia Sales Office
Date: 3/20/2021 10:24 AM Prepared By: Amir Bidin

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages
Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Certified units may be found in the AHRI Directory at www.ahridirectory.org

http://www.ahridirectory.org

19DV AquaEdge Chiller Builder Version 2.1.0.0 (Asia) Page 4 of 4


Foot Loading
Hospital River of Life - 700RT (6)
Carrier Malaysia Sales Office
Date: 3/20/2021 10:24 AM Prepared By: Amir Bidin

19DV-G41G434425F9

Chiller Rigging Weight(w/o water, w/o refrigerant charge) 34086 lb


Chiller Operation Weight(with water and refrigerant weights) 38816 lb
Chiller Refrigrant Weight 1205 lb

Unit Corner A Corner B Corner C Corner D

Corner Weight lb 9031 9026 10467 10292

Spring C12T-1D-14400 C12T-1D-14400 C12T-1D-14400 C12T-1D-14400

Spring Color Gray Gray Gray Gray

Note: The picture above is for demonstration only.

19DV AquaEdge Chiller Builder Version 2.1.0.0 (Asia) Page 1 of 1