Technical Data

11.1 General Device Data

11.1 General Device Data

11.1.1 Analog Inputs

Current Inputs

All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Protection-class current trans- Rated current Irated Measuring range of Measuring range of the
formers the modular devices non-modular devices
5A 0 A to 500 A 0 A to 250 A
1A 0 A to 100 A 0 A to 50 A
Instrument transformers 5A 0 A to 8 A 0 A to 8 A
1A 0 A to 1.6 A 0 A to 1.6 A
Power consumption per current Approx. 0.1 VA
circuit at rated current
Thermal rating 500 A for 1 s
(protection and instrument trans- 150 A for 10 s
formers) 20 A continuously
25 A for 3 min
30 A for 2 min
Dynamic load-carrying capacity 1250 A one half wave

Voltage Input

All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Input and output modules IO202, IO208, IO211, IO214 IO215
Measuring range 0 V to 200 V 0 V to 7.07 V
Input impedance < 0.1 VA < 0.01 VA
Thermal rating 230 V continuously 20 V continuously

Measuring-Transducer Inputs (via Module ANAI-CA-4EL)

Insulation class SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
Connector type 8-pin multiple contact strip
Differential current input channels 4
Measuring range DC -24 mA to +24 mA
Fault < 0.5 % of the measuring range
Input impedance 140 Ω
Conversion principle Delta-sigma (16 bit)
Permissible potential difference DC 20 V
between channels
Galvanic separation from ground/ DC 700 V
housing
Permissible overload DC 100 mA continuously
Measurement repetition 200 ms

Measuring-Transducer Inputs (via Module ARC-CD-3FO)

Connector type AVAGO AFBR-4526Z