SynCon STATCOM
SynCon STATCOM
Abstract—When wind farms are integrated in weak grids, The synchronous condenser is implemented with a Type-4
stability issues such as low-frequency oscillations arise. The wind farm power system in this paper. Since the wind farm
grid industry used synchronous condensers instead of Static is interfaced to a grid through a grid-following converter, the
Synchronous Compensator (STATCOM) to improve stability.
The goal of this paper is to compare performance of the two systems may face high risk of instability when the grid is
VAR devices on stability improvement for grid-interconnected weak. Some studies about the stability issue of wind farm in
wind farms. The topology structure and operation principle weak grid have been reported in the literature [4], [5].
of the system with a wind farm, a synchronous condenser or As comparison, a STATCOM is also installed. Fig. 1
a STATCOM are presented. The simulation is performed in
presents the system topology. A STATCOM mainly consists
the MATLAB/SimPowerSystems environment. Simulation results
show that the synchronous condenser can effectively improve sta- of a solid-state voltage source and three-phase voltage source
bility of the power system even without reactive power injection, converts (VSCs). The reactive power regulation is realized by
while STATCOM only enhances system strength through reactive controlling the voltage at the point of interface.
power compensation.
Index Terms—reactive power compensation; synshronous con-
denser; STATCOM; wind; weak grid instability Pw+jQw
Rg+jXg Wind
I. I NTRODUCTION Grid
farm
When wind farms are integrated in weak grids, stability
issues such as low-frequency oscillations arise. For example, Ps+jQs VAR
VA R
Electric Reliability Council of Texas (ERCOT) observed os- devices
devicess
cillations at 4 Hz in a wind power plant under weak grid
Fig. 1: Single-line diagram of the study system.
condition [1]. ERCOT installed two synchronous condensers
(each +175/ − 125 MVA) at 345 kV level to offer reactive
While a number of literature consider the synchronous
power support to Panhandle region and enhance the power
condenser as a reactive power compensation to improve system
system strength in April 2018. The estimated Panhandle export
performance [6]–[8], this paper is to demonstrate the syn-
limit improvement is 250 MW [2]. The added synchronous
chronous condenser can enhance stability not only by reactive
condenser is one of contributions to increase the Panhandle
power injection but also by increasing the system strength.
Generic Transmission Constraint limit average to 3500 MW,
Comparison with STATCOM is also conducted. Simulation is
a 13% increase of 3100 MW in 2017 [3].
performed in MATLAB/SimPowerSystems, and the results are
Synchronous condenser is one type of VAR generators in
presented and compared. The rest of this paper is organized
power systems. Functionally, it can be seen as a synchronous
as follows. The detailed Type-4 wind farm system model and
machine without mechanic input. A synchronous condenser
its stability investigation are depicted in Section II. Section
can either generate or absorb reactive power to/from the
III introduces the structure and performance of STATCOM.
power grid and maintain the terminal voltage within limits.
Section IV presents the characteristics of a synchronous con-
Similarly, STATCOM is also a type of VAR generators, though
denser without reactive power compensation and Section V
STATCOM relies on power electronic converter technology to
concludes the paper.
generate reactive power only.
With both can provide reactive power support, it is under-
standable that both devices can help voltage stability. The goal II. TYPE-4 WIND FARM IN WEAK GRID
of this paper, however, is to investigate which one can improve With the extensively investigating of Type-4 wind farm, the
dynamic stability. Hence, we will investigate if the system stability issues when connected with a weak grid are widely
shows stability improvement when a device is connected to reported in the literature.
the system while providing 0 reactive power. This section will illustrate the structure of a Type-4 wind
978-1-7281-8192-9/21/$31.00 © 2021 IEEE farm system and its oscillation under a weak grid.
A. System model B. Simulation result
A type-4 wind farm consists of a synchronous genera-
To investigate the dynamic performance of the wind farm,
tor, wind turbine, DC-link capacitor, machine side converter
the Xg is given a step change from 0.2 pu at 5 second to
(MSC) and grid side converter (GSC). The synchronous
emulates a parallel line tripping events. The PCC bus voltage
generator is connected to MSC, and a capacitor is placed
VPCC are displayed for different final values of Xg in Fig.
between MSC and GSC. An inductor L1 and capacitor C1 are
3. The dynamic responses are compared when Xg changes to
aggregated as a filter. After point of common coupling (PCC)
0.41 and 0.42. It can be observed that the system becomes
bus, Rg and Lg represent the impedance and inductance of
unstable when Xg changes to 0.42 and keeps stable when Xg
transmission line, respectively.
reaches to 0.41. So the marginal stable condition is Xg =
A vector control is used in GSC to regulate the DC-link
0.41 and oscillation frequency is about 9 Hz. Reference [9]
voltage vdc and PCC bus voltage vac . This control system
demonstrates this kind of oscillation is caused by weak grid
includes two cascaded loops as an inner current loop and
system.
outer vdc /vac loop. The inner-loop is decoupled into dq
frame, where the d-axis current order is determined by outer-
loop vdc control and q-axis by vac control. Meanwhile, the
outer-loop regulates vdc and vac by comparing them with 1.2 X g =0.41
VPCC (pu)
the parameters are listed in TABLE I in Appendix. A diagram 1
of type-4 wind farm with its control system is shown in Fig.
2. 0.9
0.8
MSC GSC P,Q
R1 L1 va Rg Lg 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
AC + C DC vb
SG vDC Grid
DC
- AC vc 1.2
X g =0.42
Synchronous vd
Sa,b,c
Generotor θPLL abc
vq dq vDC* 1.1
PLL
vd
VPCC (pu)
+ + -+
abc PI PI vDC
-+ -i* d
id ia
1
ωL1 abc
iq dq ib
ωL1
-+ ic 0.9
+ +
dq PI PI vd
+ + iq* -
vq 0.8
vd* 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
θPLL
Time(s)
(a)
ω0 Fig. 3: PCC voltage of wind farm system.
vq Δω + 1
θPLL
PI + s III. STATCOM
(b)
Fig. 2: EMT testbed of a Type-4 wind farm in a weak grid. (a) Schematics
STATCOMs have been widely used in modern power system
of Type-4 wind farm and its control system. (b) Block diagram of PLL. to enhance the stability performance by providing reactive
power compensation [10]. STATCOMs are also a hot topic in
A phase-locked-loop (PLL) aligns the d axis with PCC research area due to its advantages such as good characteristics
voltage space vector and provides angle θ for abc to dq at low voltage and fast response. A STATCOM consists of
conversion. The PCC voltage is decoupled into vd and vq , a three-phase GTO/IGBT voltage source converters (VSCs),
and vq is applied to the PLL. So the vq is kept as zero and step-down transformer with leakage reactance, DC capacitors
vd has the same magnitude with VPCC . Then the wind farm and VSC controller. Fig. 4 shows a STATCOM connecting in
power P and reactive power Q can be notated as P = vd id PCC bus. The reactive power can be absorbed or generated at
and Q = −vd iq . Since −Q is proportional to iq , and VPCC the its output terminal. Voltage difference across transformer
and related to Q, the ac voltage control is a positive feedback leakage reactance determines the direction and amount of
control. Similarly, vdc control can be referred to P control. In reactive power transferred between STATCOM and power
order to adjust vDC , we only need to change d-axis current system.
id , and change iq to adjust Q, separately. This is the principle The transferred active power and reactive power transferred
of the vector control. STATCOM can be derived as:
PCC bus
Xs
C
Transformer
48 pulse
GTO VSC
Fig. 4: STATCOM Model.
1.2
VPCC (pu)
1.1
0.5 X g =0.41
1
0.9
Q (pu)
0.8
-0.5 0.7
4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
Time(s)
5 6 7 8 9 10 11 12 13 14 15
X g =0.42 2
1
1.5
0.5
Q (pu)
Q (pu)
0 1
-0.5
0.5
5 6 7 8 9 10 11 12 13 14 15
Time(s) 0
4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
Time(s)
Fig. 7: Reactive power from STATCOM as Xg : 0.2→0.41 pu and 0.2→0.42
pu.
Fig. 9: PCC voltage and injected reactive power by STATCOM when Xg :
0.2→0.42 pu.
X =0.41
g
1.2 realized by a dc generator, and the dc current provided to
VPCC (pu)
Synchronous condenser is a synchronous generator without Fig. 10: Exciter model [14].
mechanical input, so it provides reactive power support and
additional short circuit power capacity. An excitation system is
used to generates direct current for the synchronous motor field B. Simulation results
winding. It controls the field voltage and injects or absorbs The synchronous condenser connected to the wind farm is
reactive power to/from the system [13]. shown in Fig. 1. The generated reactive power is controlled by
Excitation systems can be divided as DC and AC excitation an exciter. This synchronous condenser is connected to PCC
system based on their power supply. The DC excitation is bus via a 30 MVA Y-Δ connection transformer (22/220 kV ).
The resulting PCC bus voltage and reactive power injections of
0.2
synchronous condenser are displayed in Fig. 11. At 5 seconds, X g =0.67
Xg is increased to 0.42 from 0.2 pu, the system shows a good 0.1
Q (pu)
0
short-time oscillation, the system is back to the steady-state
point. If the Xg continues to increase to 0.67 and 0.68 pu -0.1
Q (pu)
0
-0.1
1.1
-0.2
1.05 -0.3
VPCC (pu)
0.1
this paper shows that the synchronous condenser can enhance
0.05 the performance of a weak grid even without any reactive
Q (pu)
0
power injection. As comparison, the STATCOM has cannot
improve the system stability when no reactive reactive power
-0.05
transmitted.
-0.1
4.5 5 5.5 6 6.5 7 7.5 8
Time(s) A PPENDIX
Fig. 11: PCC voltage and reactive power injected by synchronous condenser TABLE I: Parameters of Type-4 wind farm
when Xg : 0.2→0.42 pu.
Parameters Value (SI)
Rated Power 100 M W
Rated voltage 575 V
Nominal freq. 60 Hz
1.3
X =0.67
g
DC-link voltage 1100 V
1.2 L 1 , R1 0.06 mH, 0.45 mΩ
C 90 mF
VPCC (pu)
1.1
1
Xd , Xd , Xd 313 mΩ, 71 mΩ, 60.5 mΩ
Xq , Xq 114 mΩ, 58.3 mΩ
Rs , Xls 1.44 mΩ, 40.8 mΩ
0.9
0.8 , T
Tdo 4.49 s, 0.0681 s
do
0.7 Tq 0.0513 s
4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
Inertia constant, pols 0.62, 2
Friction factors 0.01
1.3
X =0.68
g
Current PI controller 0.4 + 48s
1.2 DC voltage PI controller 1 + 100s
0.25 + 25
VPCC (pu)
0.8
R EFERENCES
[1] S. Huang, J. Schmall, J. Conto, J. Adams, Y. Zhang, and C. Carter,
“Voltage control challenges on weak grids with high penetration of wind
generation: Ercot experience,” in 2012 IEEE Power and Energy Society
General Meeting, 2012, pp. 1–7.
[2] B. Schwarz, “SU Panhandle Project Update, ERCOT Regional Planning
Group Meeting,” http://www.ercot.org/content/wcm/key documents
lists/77738/SU Panhandle Project Update.pdf, August 2016, accessed:
2020-06-29.
[3] “2018 state of the market report for the ercot electricity markets,”
Potomac Economics, 2019.
[4] Y. Li, L. Fan, and Z. Miao, “Stability control for wind in weak grids,”
IEEE Transactions on Sustainable Energy, vol. 10, no. 4, pp. 2094–2103,
2018.
[5] Y. Zhou, D. Nguyen, P. Kjaer, and S. Saylors, “Connecting wind power
plant with weak grid-challenges and solutions,” in 2013 IEEE Power &
Energy Society General Meeting. IEEE, 2013, pp. 1–7.
[6] “Crez reactive power compensation study,” ERCOT.
[7] S. Teleke, T. Abdulahovic, T. Thiringer, and J. Svensson, “Dynamic
performance comparison of synchronous condenser and svc,” IEEE
Transactions on Power Delivery, vol. 23, no. 3, pp. 1606–1612, 2008.
[8] E. Rehman, M. Miller, J. Schmall, and S. Huang, “Dynamic stability
assessment of high penetration of renewable generation in the ercot
grid,” ERCOT, Austin, Tx, 2018.
[9] Y. Li, L. Fan, and Z. Miao, “Wind in weak grids: Low-frequency
oscillations, subsynchronous oscillations, and torsional interactions,”
IEEE Transactions on Power Systems, vol. 35, no. 1, pp. 109–118, 2020.
[10] N. G. Hingorani and L. Gyugyi, “Static shunt compensators: Svc and
statcom,” 2000.
[11] ——, Understanding FACTS: concepts and technology of flexible AC
transmission systems. IEEE press, 2000.
[12] V. Perelmuter, Electrotechnical Systems: Simulation with Simulink® and
SimPowerSystemsTM. CRC Press, 2012.
[13] V. Jerković, K. Miklošević, and Š. Željko, “Excitation system models
of synchronous generator,” in SiP 2010 28th International Conference
Science in Practice, 2010.
[14] “IEEE Recommended Practice for Excitation System Models for Power
System Stability Studies,” IEEE Std 421.5-1992, pp. 1–56, 1992.