You are on page 1of 1

Date Page

Test report 14/01/2023 1

Circuit Breaker
GENERAL ELECTRIC F35-CB4

Circuit Breaker Data Test Data


Breaker ID1 CDK GIS 115KV Test ID CLOSE
Breaker ID2 E01 Test date 14/01/2023
Breaker ID3 TR3 Type
Breaker ID4 Reference
Serial no. 2001/L11-1000/1 Counter
Commission date 14-1-23 Operator GR
Interruping medium SF6 Plan ID BM-8011QW R01B
Rated frequency 60 Hz Plan description Plan de ensayo, Egil,Tiempo, Sin microc.
Rated voltage 115 kV
Rated current 2500 A
Rated short-circuit breaking current 40 kA
Rated motor voltage 125DC V
Rated supply voltage V
Nominal stroke 100.0 mm

Offset Y = -9 div

INTENSID: 1 A/div

PRINCIPAL A

PRINCIPAL B

PRINCIPAL C

Escala = 20.0 ms/div 0.0 40.0 80.0 120.0 160.0 200.0 240.0 280.0

Parámetros Valor Unidad


TIEMP.CIE. A 01M 91.300 ms
Rebote A 01M 4.200 ms
TIEMP.CIE. B 01M 91.800 ms
Rebote B 01M 3.600 ms
TIEMP.CIE. C 01M 91.400 ms
Rebote C 01M 3.800 ms
TIEMP.CIE. 91.800 ms
DIF. A-B-C 0.500 ms
TMPO.CIE.a AUXa -- -- -- ms
DIF. P-a AUXa -- -- -- ms
TMPO.APE.b AUXb -- -- -- ms
DIF. P-b AUXb -- -- -- ms
PICO INTEN CIR 2.900 A

You might also like