Dosimass Modbus RS485 Table of contents
Table of contents
Endress+Hauser 3
Document information Dosimass Modbus RS485
1 Document information
Expert Parameter 1
Parameter n
System
Sensor
Input
Output
Communication
Application
Diagnostics
A0022576-EN
1 Sample graphic
4 Endress+Hauser
Dosimass Modbus RS485 Document information
Language
Operation Language
Parameter 1
Parameter n
Submenu 1
Submenu n
Setup Device tag
Wizard 1/Parameter 1
Wizard n/Parameter n
Parameter n
Submenu 1
Submenu n
Diagnostics Parameter 1
Parameter n
Submenu 1
Submenu n
A0022577-EN
2 Sample graphic
For information about the operating philosophy, see the "Operating philosophy"
chapter in the device's Operating Instructions
Endress+Hauser 5
Document information Dosimass Modbus RS485
Symbol Meaning
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Write-protected parameter
6 Endress+Hauser
Dosimass Modbus RS485 Overview of the Expert operating menu
Expert
Locking status → 9
‣ System → 10
‣ Diagnostic handling → 11
‣ Administration → 17
‣ Sensor → 18
‣ Measured values → 19
‣ System units → 23
‣ Process parameters → 31
‣ Sensor adjustment → 40
‣ Calibration → 45
‣ Testpoints → 46
‣ Supervision → 50
‣ Input → 51
‣ Status input → 51
‣ Communication → 53
‣ Modbus configuration → 53
‣ Modbus information → 57
Endress+Hauser 7
Overview of the Expert operating menu Dosimass Modbus RS485
‣ Application → 59
‣ Totalizer 1 to 3 → 60
‣ Batching → 65
‣ Diagnostics → 82
Actual diagnostics → 82
Timestamp → 83
Actual diagnostics → 83
Previous diagnostics → 83
Timestamp → 84
Previous diagnostics → 84
Operating time → 84
‣ Diagnostic list → 85
‣ Event logbook → 90
‣ Device information → 91
‣ Min/max values → 94
‣ Simulation → 96
8 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Expert
Locking status → 9
‣ System → 10
‣ Sensor → 18
‣ Input → 51
‣ Communication → 53
‣ Application → 59
‣ Diagnostics → 82
Locking status
Description Use this function to view the active write protection. If two or more types of write
protection are active, the write protection with the highest priority is shown on the local
display. In the operating tool all active types of write protection are selected.
The -symbol appears in front of parameters that cannot be modified due to write
protection.
Endress+Hauser 9
Description of device parameters Dosimass Modbus RS485
Description Shows the access authorization to the parameters via the operating tool.
Factory setting 0
‣ System
‣ Diagnostic handling → 11
‣ Administration → 17
10 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Diagnostic handling
Alarm delay → 11
‣ Diagnostic behavior → 12
Alarm delay
Description Use this function to enter the time interval until the device generates a diagnostic
message.
The diagnostic message is reset without a time delay.
User entry 0 to 60 s
Factory setting 0s
Endress+Hauser 11
Description of device parameters Dosimass Modbus RS485
‣ Diagnostic behavior
12 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 140
Description Use this function to change the diagnostic behavior of the diagnostic message 140 Sensor
signal.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 046
Description Use this function to change the diagnostic behavior of the diagnostic message 046 Sensor
limit exceeded.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 834
Description Use this function to change the diagnostic behavior of the diagnostic message 834 Process
temperature too high.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Endress+Hauser 13
Description of device parameters Dosimass Modbus RS485
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 835
Description Use this function to change the diagnostic behavior of the diagnostic message 835 Process
temperature too low.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 912
Description Use this function to change the diagnostic behavior of the diagnostic message
912 Medium inhomogeneous.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 913
Description Use this function to change the diagnostic behavior of the diagnostic message
913 Medium unsuitable.
Selection • Off
• Alarm
• Warning
• Logbook entry only
14 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 192
Description Use this function to change the diagnostic behavior of the diagnostic message 192 Special
event 9.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 274
Description Use this function to change the diagnostic behavior of the diagnostic message 274 Main
electronic failure.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 392
Description Use this function to change the diagnostic behavior of the diagnostic message 392 Special
event 10.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Endress+Hauser 15
Description of device parameters Dosimass Modbus RS485
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 592
Description Use this function to change the diagnostic behavior of the diagnostic message 592 Special
event 11.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 992
Description Use this function to change the diagnostic behavior of the diagnostic message 992 Special
event 12.
Selection • Off
• Alarm
• Warning
• Logbook entry only
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 991
Description Use this function to change the diagnostic behavior of the diagnostic message 991 Batch
time exceeded.
Selection • Off
• Alarm
• Warning
• Logbook entry only
16 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Administration
Device reset → 17
Permanent storage → 17
Device tag → 18
Device reset
Description Use this function to choose whether to reset the device configuration - either entirely or in
part - to a defined state.
Selection • Cancel
• To delivery settings
• Restart device
Permanent storage
Endress+Hauser 17
Description of device parameters Dosimass Modbus RS485
Selection • Off
• On
Factory setting On
Device tag
Description Use this function to enter the name for the measuring point.
User entry Max. 16 characters such as letters, numbers or special characters (e.g. @, %, /).
‣ Sensor
‣ Measured values → 19
‣ System units → 23
‣ Process parameters → 31
‣ Sensor adjustment → 40
‣ Calibration → 45
‣ Testpoints → 46
‣ Supervision → 50
18 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Measured values
‣ Process variables → 19
‣ Totalizer → 20
‣ Input values → 22
‣ Process variables
Mass flow → 19
Volume flow → 19
Density → 20
Temperature → 20
Mass flow
Description Use this function to view the mass flow currently measured.
Volume flow
Endress+Hauser 19
Description of device parameters Dosimass Modbus RS485
Density
Temperature
Totalizer
‣ Totalizer
Totalizer value 1 to 3 → 21
Totalizer overflow 1 to 3 → 21
20 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Totalizer value 1 to 3
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 60) of the Totalizer 1 to 3 submenu:
• Volume flow
• Mass flow
User interface
The value of the process variable totalized since measuring began can be positive or
negative. This depends on the settings in the Totalizer operation mode parameter
(→ 62).
The unit of the selected process variable is specified for the totalizer in the Assign
process variable parameter. If the following is selected in the Assign process
variable parameter:
• Volume flow option: Volume flow unit parameter (→ 24)
• Mass flow option: Mass flow unit parameter (→ 23)
Example
Calculation of the current totalizer reading when the value exceeds the 7-digit display
range:
• Value in the Totalizer value 1 parameter: 196 845.7 m3
• Value in the Totalizer overflow 1 parameter: 1 ⋅ 107 (1 overflow) = 10 000 000 [m3]
• Current totalizer reading: 10 196 845.7 m3
Totalizer overflow 1 to 3
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 60) of the Totalizer 1 to 3 submenu:
• Volume flow
• Mass flow
Endress+Hauser 21
Description of device parameters Dosimass Modbus RS485
User interface
The unit of the selected process variable is specified for the totalizer in the Assign
process variable parameter. If the following is selected in the Assign process
variable parameter:
• Volume flow option: Volume flow unit parameter (→ 24)
• Mass flow option: Mass flow unit parameter (→ 23)
Example
Calculation of the current totalizer reading when the value exceeds the 7-digit display
range:
• Value in the Totalizer value 1 parameter: 196 845.7 m3
• Value in the Totalizer overflow 1 parameter: 2 ⋅ 107 (2 overflows) = 20 000 000 [m3]
• Current totalizer reading: 20 196 845.7 m3
‣ Input values
Navigation Expert → Sensor → Measured val. → Input values → Val. status inp.
22 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ System units
Mass unit → 24
Volume unit → 26
Density unit → 26
Temperature unit → 27
Date/time format → 28
‣ User-specific units → 28
Description Use this function to select the unit for the mass flow.
Custom-specific units
• User mass/s
• User mass/min
• User mass/h
• User mass/d
Endress+Hauser 23
Description of device parameters Dosimass Modbus RS485
Options
For an explanation of the abbreviated units: → 100
Customer-specific units
The unit for the customer-specific mass is specified in the User mass text parameter
(→ 29).
Mass unit
Description Use this function to select the unit for the mass.
Custom-specific units
User mass
Customer-specific units
The unit for the customer-specific mass is specified in the User mass text parameter
(→ 29).
Description Use this function to select the unit for the volume flow.
24 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Custom-specific units
• User vol./s
• User vol./min
• User vol./h
• User vol./d
Options
For an explanation of the abbreviated units: → 100
Endress+Hauser 25
Description of device parameters Dosimass Modbus RS485
Customer-specific units
The unit for the customer-specific volume is specified in the User volume text
parameter (→ 29).
Volume unit
Description Use this function to select the unit for the volume.
Customer-specific units
The unit for the customer-specific volume is specified in the User volume text
parameter (→ 29).
Density unit
Description Use this function to select the unit for the density.
26 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Custom-specific units
User dens.
Options
• SD = specific density
The specific density is the ratio of the density of the fluid to the density of water at a
water temperature of +4 °C (+39 °F), +15 °C (+59 °F), +20 °C (+68 °F).
• SG = specific gravity
The specific gravity is the ratio of the density of the fluid to the density of water at a
water temperature of +4 °C (+39 °F), +15 °C (+59 °F), +20 °C (+68 °F).
For an explanation of the abbreviated units: → 100
Customer-specific units
The unit for the customer-specific density is specified in the User density text
parameter (→ 30).
Temperature unit
Description Use this function to select the unit for the temperature.
Endress+Hauser 27
Description of device parameters Dosimass Modbus RS485
Options
For an explanation of the abbreviated units: → 100
Date/time format
Description Use this function to select the desired time format for calibration history.
‣ User-specific units
28 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Description Use this function to enter a text for the user-specific unit of mass and mass flow. The
corresponding time units (s, min, h, d) for mass flow are generated automatically.
User entry Max. 10 characters such as letters, numbers or special characters (@, %, /)
Example
If the text CENT for "centner" is entered, the choose list of the Mass flow unit parameter
(→ 23) shows the following options:
• CENT/s
• CENT/min
• CENT/h
• CENT/d
Description Use this function to enter a quantity factor for the user-specific mass and mass flow unit.
Description Use this function to enter a text for the user-specific unit of volume and volume flow. The
corresponding time units (s, min, h, d) for volume flow are generated automatically.
User entry Max. 10 characters such as letters, numbers or special characters (@, %, /)
Endress+Hauser 29
Description of device parameters Dosimass Modbus RS485
Example
If the text GLAS is entered, the choose list of the Volume flow unit parameter (→ 24)
shows the following options:
• GLAS/s
• GLAS/min
• GLAS/h
• GLAS/d
Description Use this function to enter a quantity factor for the user-specific volume and volume flow
unit.
Description Use this function to enter a text or the user-specific unit of density.
User entry Max. 10 characters such as letters, numbers or special characters (@, %, /)
Example
Enter text “CE_L” for centners per liter
30 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Description Use this function to enter the zero point shift for the user-specific density unit.
Value in user-specific unit = (factor × value in base unit) + offset
Factory setting 0
Description Use this function to enter a quantity factor for the user-specific density unit.
‣ Process parameters
Flow damping → 32
Density damping → 32
Temperature damping → 33
Flow override → 33
Endress+Hauser 31
Description of device parameters Dosimass Modbus RS485
Flow damping
Description Use this function to enter a time constant for flow damping. Reduction of the variability of
the flow measured value (in relation to interference). For this purpose, the depth of the
flow filter is adjusted: when the filter setting increases, the reaction time of the device also
increases.
Factory setting 0s
Effect
The damping affects the following variables of the device:
• Low flow cut off → 34
• Totalizer → 60
User entry
• Value = 0: no damping
• Value > 0: damping is increased
Density damping
Description Use this function to enter the time constant for density damping.
Factory setting 0s
32 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Temperature damping
Description Use this function to enter a time constant for temperature damping.
Factory setting 0s
Flow override
Description Use this function to select whether to interrupt the evaluation of measured values. This is
useful for the cleaning processes of a pipeline, for example.
Selection • Off
• On
Description
The mass flow and therefore also the volume flow are set to 0.
Endress+Hauser 33
Description of device parameters Dosimass Modbus RS485
Navigation Expert → Sensor → Process param. → Low flow cut off → Assign variable
Description Use this function to select the process variable for low flow cutoff detection.
Selection • Off
• Mass flow
• Volume flow
Navigation Expert → Sensor → Process param. → Low flow cut off → On value
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 34):
• Mass flow
• Volume flow
Description Use this function to enter a switch-on value for low flow cut off. Low flow cut off is
activated if the value entered is not equal to 0 → 35.
34 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Navigation Expert → Sensor → Process param. → Low flow cut off → Off value
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 34):
• Mass flow
• Volume flow
Description Use this function to enter a switch-off value for low flow cut off. The off value is entered as
a positive hysteresis from the on value→ 34.
Factory setting 50 %
Q 2 2
4
H
3
t
1 A 1 A
A0012887
Q Flow
t Time
H Hysteresis
A Low flow cut off active
1 Low flow cut off is activated
2 Low flow cut off is deactivated
3 On value entered
4 Off value entered
Endress+Hauser 35
Description of device parameters Dosimass Modbus RS485
Navigation Expert → Sensor → Process param. → Low flow cut off → Pres. shock sup.
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 34):
• Mass flow
• Volume flow
Description Use this function to enter the time interval for signal suppression (= active pressure shock
suppression).
Factory setting 0s
Example
When closing a valve, momentarily strong fluid movements may occur in the pipeline,
which are registered by the measuring system. These totalized flow values lead to a false
totalizer status, particularly during batching processes.
36 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Q D C D
1 2 3 4
6
5
t
A B
A0012888
Q Flow
t Time
A Drip
B Pressure shock
C Pressure shock suppression active as specified by the time entered
D Pressure shock suppression inactive
1 Valve closes
2 Flow falls below the on-value of the low flow cut off: pressure shock suppression is activated
3 The time entered has elapsed: pressure shock suppression is deactivated
4 The actual flow value is now displayed and output
5 On value for low flow cut off
6 Off value for low flow cut off
Endress+Hauser 37
Description of device parameters Dosimass Modbus RS485
Navigation Expert → Sensor → Process param. → Partial pipe det → Assign variable
Description Use this function to select a process variable to detect empty or partially filled measuring
tubes.
Selection • Off
• Density
Navigation Expert → Sensor → Process param. → Partial pipe det → Low value
Prerequsite The Density option is selected in the Assign process variable parameter (→ 38).
Description Use this function to enter a lower limit value to enable detection of empty or partially filled
measuring tubes. If the measured density falls below this value, monitoring is enabled.
Limit value
If the displayed value is outside the limit value, the measuring device displays the
diagnostic message S862 Partly filled pipe.
Navigation Expert → Sensor → Process param. → Partial pipe det → High value
Prerequsite The Density option is selected in the Assign process variable parameter (→ 38).
Description Use this function to enter an upper limit value to enable detection of empty or partially
filled measuring tubes. If the measured density exceeds this value, detection is enabled.
38 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
User entry
The upper limit value must be greater than the lower limit value defined in the Low value
partial filled pipe detection parameter (→ 38).
The unit is dependent on the process variable selected in the Assign process variable
parameter.
Limit value
If the displayed value is outside the limit value, the measuring device displays the
diagnostic message S862 Partly filled pipe.
Navigation Expert → Sensor → Process param. → Partial pipe det → Response time
Prerequsite In the Assign process variable parameter (→ 38), the Density option is selected.
Description Enter the minimum length of time (debouncing time) the signal must be present for the
diagnostic message S862 Partly filled pipe to be triggered if the measuring pipe is
empty or partially full.
Factory setting 1s
Navigation Expert → Sensor → Process param. → Partial pipe det → Max. damping
Prerequsite In the Assign process variable parameter (→ 38), the Density option is selected.
Description Use this function to enter a damping value to enable detection of empty or partially filled
measuring tubes.
Factory setting 0
Endress+Hauser 39
Description of device parameters Dosimass Modbus RS485
case of non-homogeneous media or air pockets, the damping of the measuring tubes
increases.
Not relevant to most applications.
User entry
The function is enabled only if the input value is greater than 0.
‣ Sensor adjustment
Installation direction → 40
Installation direction
Description Use this function to change the sign of the medium flow direction.
40 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Progress → 42
Navigation Expert → Sensor → Sensor adjustm. → Zero point adj. → Zero point adj.
Description Use this function to select the start of the zero point adjustment.
Pay attention to conditions → 41.
Selection • Cancel
• Busy
• Zero point adjust failure
• Start
Endress+Hauser 41
Description of device parameters Dosimass Modbus RS485
Progress
Density offset → 44
Density factor → 44
Temperature offset → 44
Temperature factor → 45
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Mass flow offset
Description Use this function to enter the zero point shift for the mass flow trim. The mass flow unit
on which the shift is based is kg/s.
42 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Mass flow factor
Description Use this function to enter a quantity factor for the mass flow. This multiplication factor is
applied over the mass flow range.
Factory setting 1
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Vol. flow offset
Description Use this function to enter the zero point shift for the volume flow trim. The volume flow
unit on which the shift is based is m³/s.
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Vol. flow factor
Description Use this function to enter a quantity factor for the volume flow. This multiplication factor
is applied over the volume flow range.
Factory setting 1
Endress+Hauser 43
Description of device parameters Dosimass Modbus RS485
Density offset
Description Use this function to enter the zero point shift for the density trim. The density unit on
which the shift is based is kg/m³.
Density factor
Description Use this function to enter a quantity factor for the density. This multiplication factor is
applied over the density range.
Factory setting 1
Temperature offset
Description Use this function to enter the zero point shift for the temperature trim. The temperature
unit on which the shift is based is K.
Factory setting 0K
44 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Temperature factor
Description Use this function to enter a quantity factor for the temperature. In each case, this factor
refers to the temperature in K.
Factory setting 1
‣ Calibration
Calibration factor → 45
Zero point → 46
Nominal diameter → 46
C0 to 5 → 46
Calibration factor
Endress+Hauser 45
Description of device parameters Dosimass Modbus RS485
Zero point
Description Use this function to enter the zero point correction value for the sensor.
Nominal diameter
C0 to 5
Factory setting 0
46 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Testpoints
Oscillation frequency 0 to 1 → 47
Frequency fluctuation 0 to 1 → 48
Oscillation amplitude 0 to 1 → 48
Oscillation damping 0 to 1 → 48
Signal asymmetry → 49
Exciter current 0 to 1 → 49
RawMassFlow → 50
Oscillation frequency 0 to 1
DN fAir fWater
15 ½ 687 594
25 1 825 697
Endress+Hauser 47
Description of device parameters Dosimass Modbus RS485
Frequency fluctuation 0 to 1
Oscillation amplitude 0 to 1
Description Displays the relative oscillation amplitude of the sensor in relation to the optimum value.
Limit values
5%
Oscillation damping 0 to 1
Example
0.002 A/12.5 µm = 160 A/m
48 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Typical values
• Low oscillation damping < 500 A/m: homogeneous medium
• High oscillation damping > 1 000 A/m: inhomogeneous medium
Signal asymmetry
Description Displays the relative difference between the oscillation amplitude measured at the inlet
and outlet of the sensor.
Typical value
• ±10 %
• A change > ±10 % can indicate deposit buildup in the measuring tubes, corrosion or
abrasion.
Exciter current 0 to 1
Endress+Hauser 49
Description of device parameters Dosimass Modbus RS485
RawMassFlow
Description Displays the unprocessed mass flow (contains all sensor corrections etc.).
Dependency
The unit is taken from the Mass flow unit parameter (→ 23)
‣ Supervision
Description Use this function to enter a limit value for measuring tube damping.
50 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Input
‣ Status input → 51
‣ Status input
Active level → 52
Description Use this function to select the function for the status input.
Selection • Off
• Start batch
• Start & stop batch
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
Endress+Hauser 51
Description of device parameters Dosimass Modbus RS485
Active level
Description Use this function to determine the input signal level at which the assigned function is
activated.
Selection • High
• Low
52 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Description Use this function to enter the minimum time period for which the input signal level must
be present before the selected function is activated.
Factory setting 50 ms
‣ Communication
‣ Modbus configuration → 53
‣ Modbus information → 57
‣ Modbus configuration
Bus address → 54
Baudrate → 54
Parity → 55
Byte order → 55
Telegram delay → 56
Endress+Hauser 53
Description of device parameters Dosimass Modbus RS485
Failure mode → 56
Interpreter mode → 57
Bus address
Baudrate
Selection • ASCII
• RTU
54 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Parity
Selection • Odd
• Even
• None / 1 stop bit
• None / 2 stop bits
Byte order
Description Use this function to select the sequence in which the bytes are transmitted. The
transmission sequence must be coordinated with the Modbus master.
Selection • 0-1-2-3
• 3-2-1-0
• 1-0-3-2
• 2-3-0-1
Endress+Hauser 55
Description of device parameters Dosimass Modbus RS485
Telegram delay
Description Use this function to enter a delay time after which the measuring device replies to the
request telegram of the Modbus master. This allows communication to be adapted to slow
Modbus RS485 masters.
Factory setting 6 ms
Description Use this function to select the diagnostic behavior for Modbus communication.
Selection • Off
• Alarm or warning
• Warning
• Alarm
Failure mode
Description Use this function to select the measured value output in the event of a diagnostic message
via Modbus communication.
56 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Interpreter mode
Description Use this function to select the interpreter mode. This mode defines the behavior of the
telegram reception interpreter.
Selection • Standard
• Ignore surplus bytes
‣ Modbus information
Device ID → 58
Device revision → 58
4) Not a Number
Endress+Hauser 57
Description of device parameters Dosimass Modbus RS485
Device ID
Device revision
Description Use this function to enter the scan list register. By entering the register address (1-based),
up to 16 device parameters can be grouped in the auto-scan buffer by assigning them to
the scan list registers 0 to 15. The data of the device parameters assigned here are read
out via the register addresses 5051 to 5081.
Factory setting 1
58 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Application
‣ Totalizer 1 to 3 → 60
‣ Batching → 65
Description Use this function to reset all totalizers to the value 0 and restart the totaling process. This
deletes all the flow values previously totalized.
Selection • Cancel
• Reset + totalize
Endress+Hauser 59
Description of device parameters Dosimass Modbus RS485
Description Use this function to reset the Overall batching quantity (→ 68) and the Batch
counter parameter (→ 66) to 0.
Selection • Reset
• Cancel
‣ Totalizer 1 to 3
Mass unit → 61
Volume unit → 61
Control Totalizer 1 to 3 → 63
Preset value 1 to 3 → 63
Failure mode → 64
Description Use this function to select a process variable for totalizer 1-3.
60 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Selection • Off
• Volume flow
• Mass flow
Options
If the Off option is selected, only Assign process variable parameter (→ 60) is
displayed in the Totalizer 1 to 3 submenu. All other parameters in the submenu are
hidden.
Mass unit
Prerequsite The Mass flow option is selected in the Assign process variable parameter (→ 60) of
the Totalizer 1 to 3 submenu.
Description Use this function to select the unit for the mass.
Custom-specific units
User mass
Volume unit
Prerequsite The Volume flow option is selected in the Assign process variable parameter (→ 60)
of the Totalizer 1 to 3 submenu.
Description Use this function to select the unit for the volume.
Endress+Hauser 61
Description of device parameters Dosimass Modbus RS485
Custom-specific units
User vol.
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 60) of the Totalizer 1 to 3 submenu:
• Volume flow
• Mass flow
Description Use this function to select how the totalizer summates the flow.
62 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Control Totalizer 1 to 3
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 60) of the Totalizer 1 to 3 submenu:
• Volume flow
• Mass flow
Description Use this function to select the control of totalizer value 1-3.
Selection • Totalize
• Reset + hold
• Preset + hold
• Reset + totalize
• Preset + totalize
• Hold
Preset value 1 to 3
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 60) of the Totalizer 1 to 3 submenu:
• Volume flow
• Mass flow
Description Use this function to enter a start value for totalizer 1-3.
Endress+Hauser 63
Description of device parameters Dosimass Modbus RS485
Example
This configuration is suitable for applications such as iterative filling processes with a fixed
batch quantity.
Failure mode
Prerequsite One of the following options is selected in the Assign process variable parameter
(→ 60) of the Totalizer 1 to 3 submenu:
• Volume flow
• Mass flow
Description Use this function to select how a totalizer behaves in an alarm condition.
Selection • Stop
• Actual value
• Last valid value
Options
• Stop
Totalizing is stopped in an alarm condition.
• Actual value
The totalizer continues to count based on the actual measured value; the error is
ignored.
• Last valid value
The totalizer continues to count based on the last valid measured value before the error
occurred.
64 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Batching
‣ Operation → 65
‣ Configuration → 71
"Operation" submenu
‣ Operation
Batch control → 66
Batch counter → 66
Batch unit → 69
Switch status 1 → 70
Endress+Hauser 65
Description of device parameters Dosimass Modbus RS485
Switch status 2 → 70
Batch control
Selection • Start
• Stop
"Stop" option
• The batching process is canceled as an emergency measure.
• A new drip quantity and a new drip correction quantity are not calculated (averaging and
single outliers).
• The number of batching processes is increased by 1.
• If no batching process is in progress, the Stop option does not have any effect.
Batch counter
66 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Description Use this function to display the total amount measured including the drip quantity from
the last batching process.
Dependency
The unit is taken from: Batch unit parameter (→ 69)
Description Use this function to display the drip quantity of the last batching process in the configured
batch unit.
Dependency
The unit is taken from: Batch unit parameter (→ 69)
Description Displays the duration (in seconds) of the last batch up to the end of drip quantity
measurement.
Endress+Hauser 67
Description of device parameters Dosimass Modbus RS485
Description Displays the closing duration (in ms) for the last batch from the switch-off time up to the
end of drip quantity measurement.
Description Use this function to display the drip correction quantity for the next batching process.
Dependency
The unit is taken from: Batch unit parameter (→ 69)
Description Use this function to display the total quantity measured for all batching processes.
68 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Example
Calculation of the current totalizer reading when the 7-digit display range is exceeded:
• Value in the Overall batching quantity parameter: 196 845.7 ml
• Value in the Overflow number overall batch. quantity parameter: 2 ⋅ 107 (2 overflows)
= 20 000 000 [ml]
• Current totalizer reading: 20 196 845.7 ml
Dependency
The unit is taken from: Batch unit parameter (→ 69)
Description Use this function to display the number of overflows for the overall batching quantity.
Example
Calculation of the current totalizer reading when the 7-digit display range is exceeded:
• Value in the Overall batching quantity parameter: 196 845.7 ml
• Value in the Overflow number overall batch. quantity parameter: 2 ⋅ 107 (2 overflows)
= 20 000 000 [ml]
• Current totalizer reading: 20 196 845.7 ml
Batch unit
Custom-specific units
• User mass
• User vol.
Endress+Hauser 69
Description of device parameters Dosimass Modbus RS485
Description Use this function to select a function for the switch output.
Selection • Close
• Open
• Batching
Switch status 1 to 2
Description Use this function to display the current status of the switch output.
70 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
"Configuration" submenu
‣ Configuration
Batch profile → 71
Batch profile
Description Use this function to select the right profile for the medium that was configured by the
customer.
Selection • Profile 1
• Profile 2
• Profile 3
• Profile 4
• Profile 5
• Profile 6
Input selector → 72
Batch unit → 73
Batch quantity → 73
Endress+Hauser 71
Description of device parameters Dosimass Modbus RS485
Batch levels → 77
Start level 2 → 78
Stop level 2 → 78
Input selector
Description Use this function to assign a measured variable for the batch profile.
Selection • Off
• Mass flow
• Volume flow
72 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Batch unit
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to select the unit for the process variable in the batch profile.
or
SI units US units
•l • ft³
• dm³ • fl oz (us)
• cm³ • gal (us)
• ml
Custom-specific units
User vol.
Batch quantity
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to enter the batch quantity in the specified batch unit of the selected
measured variable.
Endress+Hauser 73
Description of device parameters Dosimass Modbus RS485
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to enter the time used for drip quantity measurement.
Factory setting 1s
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to enter a fixed correction quantity in the set batch unit for the selected
measured variable.
74 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
If the following option is selected in the Drip correction mode parameter (→ 75):
• Off
– The Fixed compensation quantity (→ 74) is subtracted from the Batch quantity
(→ 73). The result is the target batch quantity.
– The target quantity must be greater than 0.
– If the target quantity is 0, batching cannot be started.
• Fixed time option or Fixed time or low flow cut off option
– The Fixed compensation quantity (→ 74) does not directly affect the target batch
quantity. Instead it is used for the value of the drip correction quantity for the next
batch.
– However, this is only the case if the Current drip correction quantity parameter
(→ 68) was 0 before batching and therefore the drip quantity has not yet been
recorded.
– If the Fixed compensation quantity (→ 74) is set to a value not equal to 0, this
value is used as the drip correction quantity for the first batch.
– If the Fixed compensation quantity (→ 74) is set to 0, a drip correction quantity of
10 % of the Batch quantity (→ 73) is adopted for the first batch.
The unit is taken from: Batch unit parameter (→ 73)
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to select the mode for implementing a drip correction.
Selection • Off
• Fixed time
• Fixed time or low flow cut off
Endress+Hauser 75
Description of device parameters Dosimass Modbus RS485
Description Use this function to select the filter depth of the drip median for the batch profile.
Selection • Off
• Median 3
• Median 5
• Median 7
Description Use this function to enter the number of batches used to obtain the median drip quantity.
Factory setting 5
76 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Batch levels
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to select the number of levels for the batch.
Selection • One-level
• Two-level
• One-level and blow out
Example
The example explains the parameterization of various batching functions with the input
format in % for the valve switch points.
The following batch is to be implemented:
• Two-level batch with a total batching quantity of 15 kg
• Rough batching quantity of 3 to 12 kg, valve opens once 20 % (3 kg) of the batching
quantity is reached and closes once 80 % (12 kg) is reached.
• Valve 1 opens at the start of batching and closes (automatically) once the batching
quantity (15 kg) is reached.
• The values should be input as percentages (%).
Endress+Hauser 77
Description of device parameters Dosimass Modbus RS485
v
3
2 4
t
1
0 3 V2 12 15
V1
x
A0027120
Start level 2
Description Use this function to enter the starting point of the second level in % of the target value.
The starting point must always be smaller than the finishing point.
Factory setting 0%
Stop level 2
Description Use this function to enter the finishing point of the second level in % of the target value.
The finishing point must always be greater than the starting point.
78 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Description Use this function to enter the delay for blow-out at the end of batching.
Factory setting 0s
Description Use this function to enter the duration for blow-out at the end of batching.
Factory setting 1s
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Endress+Hauser 79
Description of device parameters Dosimass Modbus RS485
Factory setting 0s
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to enter the maximum flow during batching.
Factory setting 0
Dependency
The unit depends on the process variable selected in the Input selector parameter
(→ 72).
80 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Prerequsite One of the following options is selected in the Input selector parameter (→ 72):
• Mass flow
• Volume flow
Description Use this function to enter a time (in seconds) in which pressure shock suppression is not
active after starting a batching process.
Factory setting 0s
E D E
1 2 3 4 5
7
6
t
A B C
A0026869
Q Flow
t Time
A Disable time pressure shock suppression
B Drip
C Pressure shock
D Pressure shock suppression active
E Pressure shock suppression inactive
1 Valve opens
2 Valve closes
3 Flow falls below the on-value of the low flow cut off: pressure shock suppression is activated
4 The time entered has elapsed: pressure shock suppression is deactivated
5 The actual flow value is now displayed and output
6 On value for low flow cut off
7 Off value for low flow cut off
Endress+Hauser 81
Description of device parameters Dosimass Modbus RS485
‣ Diagnostics
Actual diagnostics → 82
Timestamp → 83
Actual diagnostics → 83
Previous diagnostics → 83
Timestamp → 84
Previous diagnostics → 84
Operating time → 84
‣ Diagnostic list → 85
‣ Event logbook → 90
‣ Device information → 91
‣ Min/max values → 94
‣ Simulation → 96
Actual diagnostics
Description Displays the current diagnostic message. If two or more messages occur simultaneously,
the message with the highest priority is shown on the display.
User interface Symbol for diagnostic behavior, diagnostic code and short message.
82 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Example
For the display format:
S442 Frequency output
Timestamp
Description Displays the operating time when the current diagnostic message occurred.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
Actual diagnostics
Previous diagnostics
Description Displays the diagnostic message that occurred before the current message.
User interface Symbol for diagnostic behavior, diagnostic code and short message.
Endress+Hauser 83
Description of device parameters Dosimass Modbus RS485
Timestamp
Description Displays the operating time when the last diagnostic message before the current message
occurred.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
Previous diagnostics
Description Displays the service ID of the diagnostic message that occurred before the current
diagnostic message.
Description Use this function to display the time the device has been in operation since the last device
restart.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Operating time
Description Use this function to display the length of time the device has been in operation.
User interface Days (d), hours (h), minutes (m) and seconds (s)
84 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Diagnostic list
Diagnostics 1 → 85
Diagnostics 1 → 86
Timestamp → 86
Diagnostics 2 → 86
Diagnostics 2 → 87
Timestamp → 87
Diagnostics 3 → 87
Diagnostics 3 → 87
Timestamp → 88
Diagnostics 4 → 88
Diagnostics 4 → 88
Timestamp → 89
Diagnostics 5 → 89
Diagnostics 5 → 89
Timestamp → 89
Diagnostics 1
Description Use this function to display the current diagnostics message with the highest priority.
Endress+Hauser 85
Description of device parameters Dosimass Modbus RS485
User interface Symbol for diagnostic behavior, diagnostic code and short message.
Diagnostics 1
Description Displays the service ID of the current diagnostic message with the highest priority.
Timestamp
Description Displays the operating time when the diagnostic message with the highest priority
occurred.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
Diagnostics 2
Description Use this function to display the current diagnostics message with the second-highest
priority.
User interface Symbol for diagnostic behavior, diagnostic code and short message.
86 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Diagnostics 2
Description Displays the service ID of the current diagnostic message with the second-highest priority.
Timestamp
Description Displays the operating time when the diagnostic message with the second-highest priority
occurred.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
Diagnostics 3
Description Use this function to display the current diagnostics message with the third-highest
priority.
User interface Symbol for diagnostic behavior, diagnostic code and short message.
Diagnostics 3
Description Displays the service ID of the current diagnostic message with the third-highest priority.
Endress+Hauser 87
Description of device parameters Dosimass Modbus RS485
Timestamp
Description Displays the operating time when the diagnostic message with the third-highest priority
occurred.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
Diagnostics 4
Description Use this function to display the current diagnostics message with the fourth-highest
priority.
User interface Symbol for diagnostic behavior, diagnostic code and short message.
Diagnostics 4
Description Displays the service ID of the current diagnostic message with the fourth-highest priority.
88 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Timestamp
Description Displays the operating time when the diagnostic message with the fourth-highest priority
occurred.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
Diagnostics 5
Description Use this function to display the current diagnostics message with the fifth-highest priority.
User interface Symbol for diagnostic behavior, diagnostic code and short message.
Diagnostics 5
Description Displays the service ID of the current diagnostic message with the fifth-highest priority.
Timestamp
Description Displays the operating time when the diagnostic message with the fifth-highest priority
occurred.
Endress+Hauser 89
Description of device parameters Dosimass Modbus RS485
User interface Days (d), hours (h), minutes (m) and seconds (s)
Example
For the display format:
24d12h13m00s
‣ Event logbook
Filter options → 90
Filter options
Description Use this function to select the category whose event messages are displayed in the events
list.
Selection • All
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
• Information (I)
90 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Device information
Device tag → 91
Serial number → 92
Firmware version → 92
Device name → 92
Order code → 92
ENP version → 94
Configuration counter → 94
Device tag
Description Displays a unique name for the measuring point so it can be identified quickly within the
plant. The name is displayed in the header.
User interface Max. 32 characters such as letters, numbers or special characters (e.g. @, %, /)
1 XXXXXXXXX
A0013375
3 Header text
Endress+Hauser 91
Description of device parameters Dosimass Modbus RS485
Serial number
User interface A maximum of 11-digit character string comprising letters and numbers.
Firmware version
Device name
Description Displays the device name. It can also be found on the nameplate.
Order code
User interface Character string composed of letters, numbers and certain punctuation marks (e.g. /).
92 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
The order code is generated from the extended order code through a process of reversible
transformation. The extended order code indicates the attributes for all the device features
in the product structure. The device features are not directly readable from the order code.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting Endress+Hauser.
Description For displaying the second part of the extended order code.
Additional information For additional information, see Extended order code 1 parameter (→ 93)
Description For displaying the third part of the extended order code.
Additional information For additional information, see Extended order code 1 parameter (→ 93)
Endress+Hauser 93
Description of device parameters Dosimass Modbus RS485
ENP version
Configuration counter
Description Displays the number of parameter modifications for the device. When the user changes a
parameter setting, this counter is incremented.
‣ Min/max values
‣ Medium temperature → 95
Description Use this function to select measured variables whose minimum, maximum and average
measured values are to be reset.
Selection Cancel
94 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
‣ Medium temperature
Minimum value → 95
Maximum value → 95
Maximum value
Minimum value
Endress+Hauser 95
Description of device parameters Dosimass Modbus RS485
‣ Simulation
Description Use this function to select a process variable for the simulation process that is activated.
Selection • Off
• Mass flow
• Volume flow
• Density
• Temperature
Prerequsite One of the following options is selected in the Assign simulation process variable
parameter (→ 96):
• Mass flow
• Volume flow
• Density
• Temperature
Description Use this function to enter a simulation value for the selected process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way,
users can verify whether the measuring device has been configured correctly.
Factory setting 0
96 Endress+Hauser
Dosimass Modbus RS485 Description of device parameters
Description Use this function to switch the device alarm on and off.
Selection • Off
• On
Endress+Hauser 97
Country-specific factory settings Dosimass Modbus RS485
4.1 SI units
Not valid for USA and Canada.
Mass g
Volume ml
Density kg/l
Temperature °C
8 2
15 7
25 20
4.2 US units
Only valid for USA and Canada.
Mass oz
Volume fl oz (us)
Density g/cm³
Temperature °F
98 Endress+Hauser
Dosimass Modbus RS485 Country-specific factory settings
³/₈ 0.08
½ 0.25
1 0.7
Endress+Hauser 99
Explanation of abbreviated units Dosimass Modbus RS485
5.1 SI units
Process variable Units Explanation
SD4°C, SD15°C, SD20°C Specific density: The specific density is the ratio of the
density of the fluid to the density of water at a water
temperature of 4 °C (39 °F), 15 °C (59 °F), 20 °C (68 °F).
SG4°C, SG15°C, SG20°C Specific gravity: The specific gravity is the ratio of the
density of the fluid to the density of water at a water
temperature of 4 °C (39 °F), 15 °C (59 °F), 20 °C (68 °F).
5.2 US units
Process variable Units Explanation
fl oz (us), gal (us), kgal (us), Mgal Fluid ounce, gallon, kilogallon, million gallon
(us)
bbl (us;liq.), bbl (us;beer), bbl Barrel (normal liquids), barrel (beer), barrel
(us;oil), bbl (us;tank) (petrochemicals), barrel (filling tanks)
100 Endress+Hauser
Dosimass Modbus RS485 Explanation of abbreviated units
Endress+Hauser 101
Modbus RS485 Register Information Dosimass Modbus RS485
6.1 Notes
Name of parameter Indicated in decimal • Float length = 4 Possible type of access Selection Specified number of pages
numerical format byte to parameter: List of the individual and cross-reference to
• Integer length = 2 • Read access via options for the standard parameter
byte function codes 03, parameter description
• String length, 04 or 23 • Option 1
depending on • Write access via • Option 2
parameter function codes 06, • Option 3 (+)
16 or 23
• Factory
setting
highlighted in
bold
• (+) = Factory
setting
depends on
country, order
options or
device
settings
User entry
Input range for the
parameter
NOTICE
If non-volatile device parameters are modified via the MODBUS RS485 function codes
06, 16 or 23, the change is saved in the EEPROM of the measuring device.
The number of writes to the EEPROM is technically restricted to a maximum of 1 million.
‣ Make sure to comply with this limit since, if it is exceeded, data loss and measuring
device failure will result.
‣ Avoid constantly writing non-volatile device parameters via the MODBUS RS485.
102 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
Function code Access type Register in accordance with "Modbus Register in accordance with
Applications Protocol Specification" "Modicon Modbus Protocol
Reference Guide"
Expert
‣ System → 109
‣ Administration → 110
‣ Sensor → 111
‣ Totalizer → 111
Endress+Hauser 103
Modbus RS485 Register Information Dosimass Modbus RS485
‣ Calibration → 117
C0 to 5 → 117
104 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
‣ Testpoints → 117
RawMassFlow → 117
‣ Supervision → 117
‣ Input → 118
‣ Communication → 118
Baudrate → 118
Parity → 118
Endress+Hauser 105
Modbus RS485 Register Information Dosimass Modbus RS485
Device ID → 119
‣ Application → 119
‣ Totalizer 1 to 3 → 119
‣ Batching → 120
‣ Operation → 120
‣ Configuration → 121
‣ Diagnostics → 123
Timestamp → 123
106 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
Timestamp → 123
Diagnostics 1 → 123
Diagnostics 1 → 123
Timestamp → 123
Diagnostics 2 → 124
Diagnostics 2 → 124
Timestamp → 124
Diagnostics 3 → 124
Diagnostics 3 → 124
Timestamp → 124
Diagnostics 4 → 124
Diagnostics 4 → 124
Timestamp → 124
Diagnostics 5 → 124
Diagnostics 5 → 124
Timestamp → 124
Endress+Hauser 107
Modbus RS485 Register Information Dosimass Modbus RS485
‣ Simulation → 125
108 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
Endress+Hauser 109
Modbus RS485 Register Information Dosimass Modbus RS485
"Administration" submenu
110 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
"Totalizer" submenu
Endress+Hauser 111
Modbus RS485 Register Information Dosimass Modbus RS485
112 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
Endress+Hauser 113
Modbus RS485 Register Information Dosimass Modbus RS485
114 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
User mass text 2531 String Read / Write Max. 10 characters such as letters, 29
numbers or special characters (@, %, /)
User volume text 2542 String Read / Write Max. 10 characters such as letters, 29
numbers or special characters (@, %, /)
User density text 2549 String Read / Write Max. 10 characters such as letters, 30
numbers or special characters (@, %, /)
On value low flow cutoff 5138 Float Read / Write Positive floating-point number 34
Endress+Hauser 115
Modbus RS485 Register Information Dosimass Modbus RS485
Low value partial filled pipe 5110 Float Read / Write Signed floating-point number 38
detection
High value partial filled pipe 5112 Float Read / Write Signed floating-point number 38
detection
Maximum damping partial filled 2414 Float Read / Write Positive floating-point number 39
pipe det.
116 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
"Calibration" submenu
"Testpoints" submenu
"Supervision" submenu
Limit value measuring tube 4333 Float Read / Write Positive floating-point number 50
damping
Endress+Hauser 117
Modbus RS485 Register Information Dosimass Modbus RS485
118 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
Endress+Hauser 119
Modbus RS485 Register Information Dosimass Modbus RS485
"Batching" submenu
"Operation" submenu
Close time last batch 2994 Float Read Positive floating-point number 68
Current drip correction quantity 3240 Float Read Signed floating-point number 68
Overflow number overall batch. 3552 Float Read –32 000.0 to 32 000.0 69
quantity
120 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
"Configuration" submenu
Endress+Hauser 121
Modbus RS485 Register Information Dosimass Modbus RS485
122 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
Maximum flow rate exceeded 1: 3862 Float Read / Write Positive floating-point number 80
2: 3864
3: 3866
4: 3868
5: 3870
6: 3872
Timestamp 2719 Integer Read Days (d), hours (h), minutes (m) and 83
seconds (s)
Timestamp 2068 Integer Read Days (d), hours (h), minutes (m) and 84
seconds (s)
Operating time from restart 2624 Integer Read Days (d), hours (h), minutes (m) and 84
seconds (s)
Operating time 2631 Integer Read Days (d), hours (h), minutes (m) and 84
seconds (s)
Timestamp 2710 Integer Read Days (d), hours (h), minutes (m) and 86
seconds (s)
Endress+Hauser 123
Modbus RS485 Register Information Dosimass Modbus RS485
Timestamp 2701 Integer Read Days (d), hours (h), minutes (m) and 87
seconds (s)
Timestamp 2692 Integer Read Days (d), hours (h), minutes (m) and 88
seconds (s)
Timestamp 2683 Integer Read Days (d), hours (h), minutes (m) and 89
seconds (s)
Timestamp 2675 Integer Read Days (d), hours (h), minutes (m) and 89
seconds (s)
Firmware version 7277 String Read Character string in the format xx.yy.zz 92
124 Endress+Hauser
Dosimass Modbus RS485 Modbus RS485 Register Information
"Simulation" submenu
Value process variable 6814 Float Read / Write Depends on the process variable selected 96
Endress+Hauser 125
Index Dosimass Modbus RS485
Index
A Density offset (Parameter) . . . . . . . . . . . . . . . . . . . . . 44
Access status tooling (Parameter) . . . . . . . . . . . . . . . 10 Density unit (Parameter) . . . . . . . . . . . . . . . . . . . . . . 26
Active level (Parameter) . . . . . . . . . . . . . . . . . . . . . . 52 Device ID (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 58
Actual diagnostics (Parameter) . . . . . . . . . . . . . . 82, 83 Device information (Submenu) . . . . . . . . . . . . . . . . . . 91
Administration (Submenu) . . . . . . . . . . . . . . . . . . . . 17 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . . 92
Alarm delay (Parameter) . . . . . . . . . . . . . . . . . . . . . . 11 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . . 17
Application (Submenu) . . . . . . . . . . . . . . . . . . . . . . . 59 Device revision (Parameter) . . . . . . . . . . . . . . . . . . . . 58
Assign behavior of diagnostic no. 046 (Parameter) . . . 13 Device tag (Parameter) . . . . . . . . . . . . . . . . . . . . 18, 91
Assign behavior of diagnostic no. 140 (Parameter) . . . 13 Diagnostic behavior (Submenu) . . . . . . . . . . . . . . . . . 12
Assign behavior of diagnostic no. 192 (Parameter) . . . 15 Diagnostic handling (Submenu) . . . . . . . . . . . . . . . . . 11
Assign behavior of diagnostic no. 274 (Parameter) . . . 15 Diagnostic list (Submenu) . . . . . . . . . . . . . . . . . . . . . 85
Assign behavior of diagnostic no. 392 (Parameter) . . . 15 Diagnostics (Submenu) . . . . . . . . . . . . . . . . . . . . . . . 82
Assign behavior of diagnostic no. 592 (Parameter) . . . 16 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . 85, 86
Assign behavior of diagnostic no. 834 (Parameter) . . . 13 Diagnostics 2 (Parameter) . . . . . . . . . . . . . . . . . . 86, 87
Assign behavior of diagnostic no. 835 (Parameter) . . . 14 Diagnostics 3 (Parameter) . . . . . . . . . . . . . . . . . . . . . 87
Assign behavior of diagnostic no. 912 (Parameter) . . . 14 Diagnostics 4 (Parameter) . . . . . . . . . . . . . . . . . . . . . 88
Assign behavior of diagnostic no. 913 (Parameter) . . . 14 Diagnostics 5 (Parameter) . . . . . . . . . . . . . . . . . . . . . 89
Assign behavior of diagnostic no. 991 (Parameter) . . . 16 Direct access
Assign behavior of diagnostic no. 992 (Parameter) . . . 16 Locking status (0004) . . . . . . . . . . . . . . . . . . . . . . 9
Assign diagnostic behavior (Parameter) . . . . . . . . . . . 56 Disable time pressure shock suppression (Parameter) 81
Assign process variable (Parameter) . . . . . . . . 34, 38, 60 Document
Assign simulation process variable (Parameter) . . . . . 96 Explanation of the structure of a parameter
Assign status input (Parameter) . . . . . . . . . . . . . . . . . 51 description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Average drip correction quantity (Parameter) . . . . . . . 76 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Batch control (Parameter) . . . . . . . . . . . . . . . . . . . . . 66 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Batch counter (Parameter) . . . . . . . . . . . . . . . . . . . . . 66 Using the document . . . . . . . . . . . . . . . . . . . . . . . . 4
Batch levels (Parameter) . . . . . . . . . . . . . . . . . . . . . . 77 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Batch profile (Parameter) . . . . . . . . . . . . . . . . . . . . . 71 Drip correction mode (Parameter) . . . . . . . . . . . . . . . 75
Batch quantity (Parameter) . . . . . . . . . . . . . . . . . . . . 73
Batch unit (Parameter) . . . . . . . . . . . . . . . . . . . . 69, 73 E
Batching (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . 65 ENP version (Parameter) . . . . . . . . . . . . . . . . . . . . . . 94
Baudrate (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 54 Enter access code (Parameter) . . . . . . . . . . . . . . . . . . 10
Blow out delay (Parameter) . . . . . . . . . . . . . . . . . . . . 79 Event logbook (Submenu) . . . . . . . . . . . . . . . . . . . . . 90
Blow out duration (Parameter) . . . . . . . . . . . . . . . . . 79 Exciter current 0 to 1 (Parameter) . . . . . . . . . . . . . . . 49
Bus address (Parameter) . . . . . . . . . . . . . . . . . . . . . . 54 Extended order code 1 (Parameter) . . . . . . . . . . . . . . 93
Byte order (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 55 Extended order code 2 (Parameter) . . . . . . . . . . . . . . 93
Extended order code 3 (Parameter) . . . . . . . . . . . . . . 93
C
C0 to 5 (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . . 46 F
Calibration (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 45 Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Calibration factor (Parameter) . . . . . . . . . . . . . . . . . . 45 SI units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Close time last batch (Parameter) . . . . . . . . . . . . . . . 68 US units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Communication (Submenu) . . . . . . . . . . . . . . . . . . . . 53 Failure mode (Parameter) . . . . . . . . . . . . . . . . . . 56, 64
Configuration (Submenu) . . . . . . . . . . . . . . . . . . . . . 71 Filter depth drip median (Parameter) . . . . . . . . . . . . . 76
Configuration counter (Parameter) . . . . . . . . . . . . . . 94 Filter options (Parameter) . . . . . . . . . . . . . . . . . . . . . 90
Control Totalizer 1 to 3 (Parameter) . . . . . . . . . . . . . . 63 Firmware version (Parameter) . . . . . . . . . . . . . . . . . . 92
Current drip correction quantity (Parameter) . . . . . . . 68 Fixed compensation quantity (Parameter) . . . . . . . . . 74
Flow damping (Parameter) . . . . . . . . . . . . . . . . . . . . 32
D Flow override (Parameter) . . . . . . . . . . . . . . . . . . . . . 33
Data transfer mode (Parameter) . . . . . . . . . . . . . . . . 54 Frequency fluctuation 0 to 1 (Parameter) . . . . . . . . . . 48
Date/time format (Parameter) . . . . . . . . . . . . . . . . . . 28 Function
Density (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 20 see Parameter
Density damping (Parameter) . . . . . . . . . . . . . . . . . . 32
Density factor (Parameter) . . . . . . . . . . . . . . . . . . . . 44 H
High value partial filled pipe detection (Parameter) . . 38
126 Endress+Hauser
Dosimass Modbus RS485 Index
Endress+Hauser 127
Index Dosimass Modbus RS485
Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
System units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Testpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Totalizer 1 to 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
User-specific units . . . . . . . . . . . . . . . . . . . . . . . . 28
Zero point adjustment . . . . . . . . . . . . . . . . . . . . . 41
Supervision (Submenu) . . . . . . . . . . . . . . . . . . . . . . . 50
Switch output function 1 to 2 (Parameter) . . . . . . . . . 70
Switch status 1 to 2 (Parameter) . . . . . . . . . . . . . . . . 70
System (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . . 10
System units (Submenu) . . . . . . . . . . . . . . . . . . . . . . 23
T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Telegram delay (Parameter) . . . . . . . . . . . . . . . . . . . 56
Temperature (Parameter) . . . . . . . . . . . . . . . . . . . . . 20
Temperature damping (Parameter) . . . . . . . . . . . . . . 33
Temperature factor (Parameter) . . . . . . . . . . . . . . . . 45
Temperature offset (Parameter) . . . . . . . . . . . . . . . . 44
Temperature unit (Parameter) . . . . . . . . . . . . . . . . . . 27
Testpoints (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 46
Time last batch (Parameter) . . . . . . . . . . . . . . . . . . . 67
Timestamp (Parameter) . . . . . . . . 83, 84, 86, 87, 88, 89
Totalizer (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . 20
Totalizer 1 to 3 (Submenu) . . . . . . . . . . . . . . . . . . . . 60
Totalizer operation mode (Parameter) . . . . . . . . . . . . 62
Totalizer overflow 1 to 3 (Parameter) . . . . . . . . . . . . . 21
Totalizer value 1 to 3 (Parameter) . . . . . . . . . . . . . . . 21
Tube damping fluctuation 0 to 1 (Parameter) . . . . . . . 49
U
User density factor (Parameter) . . . . . . . . . . . . . . . . . 31
User density offset (Parameter) . . . . . . . . . . . . . . . . . 31
User density text (Parameter) . . . . . . . . . . . . . . . . . . 30
User mass factor (Parameter) . . . . . . . . . . . . . . . . . . 29
User mass text (Parameter) . . . . . . . . . . . . . . . . . . . . 29
User volume factor (Parameter) . . . . . . . . . . . . . . . . . 30
User volume text (Parameter) . . . . . . . . . . . . . . . . . . 29
User-specific units (Submenu) . . . . . . . . . . . . . . . . . . 28
V
Value process variable (Parameter) . . . . . . . . . . . . . . 96
Value status input (Parameter) . . . . . . . . . . . . . . 22, 52
Volume flow (Parameter) . . . . . . . . . . . . . . . . . . . . . 19
Volume flow factor (Parameter) . . . . . . . . . . . . . . . . . 43
Volume flow offset (Parameter) . . . . . . . . . . . . . . . . . 43
Volume flow unit (Parameter) . . . . . . . . . . . . . . . . . . 24
Volume unit (Parameter) . . . . . . . . . . . . . . . . . . . 26, 61
Z
Zero point (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 46
Zero point adjustment (Submenu) . . . . . . . . . . . . . . . 41
Zero point adjustment control (Parameter) . . . . . . . . . 41
128 Endress+Hauser