Masterpact ® circuit breaker

introduction

interrupting ratings
UL489/NEMA AB1 UL1066/ANSI C37-13/NEMA SG3 ➁
type rating 480V 600V short type rating 480V 600V short
(A) time (A) time
standard interrupting rating special interrupting rating
MP08 H1 800 65kA 65kA 50kA MC08 N1 800 50kA 50kA 42kA
MP12 H1 1200 65kA 65kA 50kA MC16 N1 1600 50kA 50kA 50kA
MP16 H1 1600 65kA 65kA 50kA standard interrupting rating
MP20 H1 2000 75kA 75kA 75kA MC08 H1 800 65kA 65kA 50kA
MP25 H1 2500 75kA 75kA 75kA MC16 H1 1600 65kA 65kA 50kA
MP30 H1 3000 75kA 75kA 75kA MC20 H1 2000 65kA 65kA 65kA
MP40 H1 4000 100kA 100kA 100kA MC32 H1 3200 65kA 65kA 65kA
MP50 H1 5000 100kA 100kA 100kA MC40 H1 4000 100kA 100kA 100kA
MP63 H1 6300 ➀ 100kA 100kA 100kA MC50 H1 5000 100kA 100kA 100kA
high interrupting rating ➁ drawout only
MP08 H2 800 100kA 65kA 50kA the circuit breaker exceeds, without
MP12 H2 1200 100kA 65kA 50kA additional costs, the UL standard 1,500
MP16 H2 1600 100kA 65kA 50kA operations required in endurance. The
heavy duty mechanism and the contact
MP20 H2 2000 100kA 75kA 75kA
design provide a mechanical endurance of
MP25 H2 2500 100kA 75kA 75kA 10,000 operations (approx.) without
MP30 H2 3000 100kA 75kA 75kA maintenance (see page 38).
MP40 H2 4000 125kA 100kA 100kA
MP50 H2 5000 125kA 100kA 100kA
single design up to 6300A
All frame sizes have been designed with the
MP63 H2 6300 ➀ 150kA 100kA 100kA
same technology featuring identical depth
➀ not UL listed and door cutouts, and common control units
■ JEC, JIS and accessories.
ratings ■ marine applications:
■ homologated by Bureau Veritas high short-time current rating:
type ampere sensor ratings (A) ■ approved by Det Norske Veritas
rating (A) and Germanische Lloyd's
up to 100kA for 1 sec.
08 800 250-400-600-800 ■ listed by Lloyd's Register of Shipping The exceptional short-time rating of 75,000A
12 1200 800-1000-1200 ■ American Bureau of Shipping application in a 3000A frame and 100,000A in a 4000A
16 1600 1200-1600 ■ UL marine frame and above allows the circuit breakers
to be fully selective up to their interrupting
20 2000 1600-2000
ratings.
25 2500 2000-2500 other performances
30 3000 2500-3000 100% rated
The UL 489 and UL1066 (ANSI C37-13)
32 3200 2500-3200 standard performance assure that the The circuit breakers are designed for
40 4000 2500-3000-4000 circuit breaker has sufficient characteristics continuous operation at 100% of their
50 5000 4000-5000 to be used in normal conditions. However, current rating.
63 6300 5000-6300

tropicalization 63 40-50 32 08-30


The standard moisture and fungus protection
ensure normal operation under extreme ambient
conditions. Masterpact® circuit breakers comply
with T2 tropicalization (IEC standard 68-2-30);
relative humidity 95% at 113°F (45°C) and
80% at 131°F (55°C) (hot, humid climate).
Salt spray resistance as per IEC 68-2-11. push to reset
reset V
I

LG
IG

L
LI

off
G
LIG

masterpact
I I M08 H2

standard compliance
I1 I2 I3 O circuit breaker
push ON 3 pole
90%
push OFF 600V 50/60Hz

STR 58 U
frame size 2000A
operation
suitable for continious
in a minimum
cubical
50% at 100% rating by W21 by D14.1/4
inches
space H17.5 not required
ventilation is

■ UL489: MP08 to MP50 circuit breakers


20% discharged
E63335

tr 120 240
O UND. LAB. O
List.
CIRCUIT BREAKER
Ir
Io=3000A .88
.9 .92
.95 60 OPEN 00000 Doles. Issue
N° LM-8792

90 480
.98 30
%Ir .85
1
15
.8 at 1,5Ir NEMA
105 cat. no. 54775 xIo
for masterpact
In = 6000A
tm.4 interrupting rating
amps
max RMS sym
with sensors
Im .3
5

and their accessories are listed under UL


4 .2
3
6 .3
Volts Amps
8 .2
.1 240 100K
2
10
.1 0
480 100K
1.5 off
xIo on I t
2

600 65K
I 8 12

Ir : 6 17
t
22
Ir fault 4
Im : 2 off

files E63335, E103955 and E113555


xIn T
tr th : th .4 .4
Ih 600 .3
500
800 .3
Ih
Im fault 400 690V 50/60Hz
fault
tm 1000 .2
.1
.2
IEC 957-2 rating
320 .1
th I 250
1200
on I t
2 off interrupting 75KA
A
R Icu 380/440V 75KA
i Ic2.8 660V
Ic1 .9 .93
.85 75KA
+S– .95 .7
.9
Icu 380/440V 75KA
.86
.95 660V

■ UL1066/ANSI: MC08 to MC50 circuit


short time rating
.98 .6
.85 1
test .5 sec.
Icw=75KA 0.5
1
.8 xIr
xIr
–T+

F test

breakers are UL Listed according to UL1066


(ANSI C37-13) under file E161835 connected
test

■ international standards: the Masterpact®


disconnected

circuit breaker has been designed to meet


all the major standards including:
MP1024A.0
■ IEC 947-2 and related standards such as
VDE, BS, etc.

Courtesy of NationalSwitchgear.com
Masterpact ® circuit breaker
advantages

drawout circuit breaker true 2-step stored energy designed for no


design mechanism maintenance...
■ the drawout assembly mechanism allows The closing time is less than 5 cycles. The circuit breaker has fewer parts (by a
the circuit breaker to be racked in 4 positions The circuit breaker is operated via a stored factor of at least 5) than conventional circuit
(connected, test, disconnected and withdrawn). energy mechanism which can be manually breakers while performing the same
■ the closing and opening push buttons, the or motor charged. Closing and opening functions. This leads to greatly enhanced
racking handle and racking mechanism are operations can be initiated either from the reliability and reduction in maintenance.
accessible through the front door cutout. local push buttons on the circuit breaker Under normal operating conditions, given by
Disconnecting the circuit breaker will be front face, or by remote control. standards and controlled by tests, the circuit
therefore possible without opening the door O-C-O cycle is possible without recharging. breaker does not require maintenance.
and accessing live parts. Safety shutters can
be provided for protection from live parts field-installable accessories …but exceeds the standard
when the circuit breaker is removed. ■ as the installation develops and changes with an easy and reduced
connected position the circuit breaker can develop and change
with it. Most accessories are field-installable, maintenance
without losing the UL Listing mark, without It is easy to remove the arc chutes and
any adjustment and with only the aid of a visually inspect the contacts and wear
screwdriver. indicator. The operation counter (spring
■ the uniform design of the circuit breaker charging motor option) can also indicate
line allows these accessories to be common when inspections and possible maintenance
for the whole line. should be done.
After operating conditions exceeding those
given by standards, it is possible to extend
the circuit breaker life by:
■ replacement of arc chutes and spring
charging motor by the user.
■ replacement of main contacts by an after
sale service team.
Note: see page 37 for additional information.

test position

MP1026A.0

front connection of
secondary circuits
All accessory terminals are located on a
connecting block which is accessible from
the front even with the circuit breaker in the
test or disconnected position. This is
particularly useful for field inspection and
disconnected position modification.

MP1025A.0 MP1027P.0 MP1028A.0


MP1025A.0

Courtesy of NationalSwitchgear.com
Masterpact ® circuit breaker
advantages

improved features
■ segregated compartment
Once the front cover has been removed,
giving access to the auxiliary compartment,
the main contacts remain fully isolated.
Furthermore, interphase partitioning allows
full insulation between each pole even if the
front cover has been removed.
■ isolation function by positive
indication of contact status
The mechanical indicator is truly
representative of the status of all three main
contacts.
■ reinforced insulation
Two insulation barriers separate the front of
the circuit breaker from main circuits.
■ disconnecting through door
The racking handle and racking mechanism
are accessible through the front door cutout.
Disconnecting the circuit breaker will
therefore be possible without opening the
door and giving access to live parts.

MP1029A.0 MP1030A.0

control units STR 28D STR 38S STR 58U


state of the art protection basic features
and control long-time ➀ setting adjustable adjustable adjustable
The circuit breaker can be equipped with a delay fixed fixed adjustable
microprocessor-based, electronic control short-time pickup adjustable adjustable
unit which provides all the traditional
protection of the universal power circuit delay adjustable adjustable
breaker (long-time, short-time, instantaneous instantaneous adjustable fixed ➁ adjustable ➁
and ground-fault) ➂ plus other built-in test receptacle standard standard standard
functions: additional features
■ rms sensing (standard)
ground-fault protection ➂ ■ ■
■ alarm switch (standard)
■ overcurrent trip switch (standard) built-in ammeter ■ ■ ■
■ interchangeable rating plugs (standard) fault indicators ■ ■
■ thermal memory and I 2t ramp segregated alarm switch ■
(standard on STR 38-58 control unit) zone-selective interlocking ■
■ defeatable instantaneous load monitoring ■
(standard on STR 38-58 control unit)
communication outputs ■
■ zone-selective interlocking for ground
fault and short time (option) ➀ long-time pickup at 1.1 current setting
■ current and load meter (option) ➁ defeatable on N1 and H1 types
■ load monitoring outputs (option) ➂ two types: residual sensing (T) or residual
source ground return (W)
■ fault indicators (option)
■ communication ability (option)

Courtesy of NationalSwitchgear.com
Masterpact ® circuit breaker
description

description
1 control terminal covers
2 accessories and control unit front
connecting block
3 position carriage switches
4 arc chute
5 opening coils
6 spring charging motor
7 front cover
8 control unit
9 racking crank
10 handling handgrip
11 retractable rails
12 pull-out handgrip
13 safety shutters

MP1031P.0

front view
11 12 1 charging handle
2 manual opening push button
3 manual closing push button
4 stored energy mechanism status
indicator (charged or discharged)
5 main contact position indicator
(open or closed)
IG LI
LIG
I

push to reset
reset V
LG
L off
G

1
6 disconnected position locking
MERLIN GER
masterpact
IN
2 (key interlock)
I MP20

I1 I2 I3
I
O
push ON
H1
circuit breake
3 pole
600V 50/60H
z
r
7 disconnected position padlocking
90%
push OFF
STR 58 U frame size 2000A
operation
3 8 drawout position indicator showing that
suitable for continious
in a minimum
cubical
at 100% rating by W21 by D14.1/4
inches

the circuit breaker is in the connected, test


50% space H17.5 not required
ventilation is

discharged
20%

Ir .9 .92
.95 60
tr 120 240
O
OPEN 00000
E63335
UND. LAB. O

Doles. Issue
List.
CIRCUIT BREAKER
N° LM-8792
4 or disconnected position
Io=3000A .88
480
90 .98 30
interrupting rating
%Ir .85
1
15

9 racking crank housing


.8 at 1,5Ir
amps
max RMS sym
105 cat. no. 54775 xIo
for masterpact
In = 6000A
tm.4
with sensors
Im .3
Volts Amps

5
4 5 .2
3
6 .3 240 75K
8 .2
.1 480 75K

10 door escutcheon
2
1.5 10
.1 0
off
600 75K
on I t
2

xIo
75KA
I 8 12 short time rating
Ir : 6 17
t

11 fault indicator and reset button


22
Ir fault 4
Im : 2 off
xIn T
tr th : th .4 .4
Ih 600 .3
500
.3 Hz
690V 50/60
800

12 open position locking (key interlock)


Ih 400
fault
Im fault
1000 .2
.2 IEC 957-2 rating
interrupting
tm 320 .1
1200
.1 75KA
Icu 380/440V
th I 250 on I t
2 off
A 75KA
R
i Ic2.8 .85 660V 75KA
Ic1 .9 .93
.7
.9 Icu 380/440V 75KA
+S– .86
.95
660V
short time rating
.95
.98 .6
.85 1 sec.
Icw=75KA 0.5
test 1
.5
.8 xIr
xIr
–T+

F test

connected
6
test
d
disconnecte

10 9 8 7
MP1009A.0

Courtesy of NationalSwitchgear.com