GENERAL KEY PLAN:


N

LA
QIB
B
Vs = ULT WIND SPEED (3-sec gust) BASED ON SBC 301-18
Qa = ALLOWABLE BEARING SOIL CAPACITY

E Vs = 48 m/s Qa = 1.50 Kg/cm²

COLUMN
A DESIGN FORCES Foundation Dimensions REINFORCEMENT
HEIGHT "H"

G
PRESET ANCHOR BOLT

H/2 max
(m) MOMENT SHEAR A B C D Bar Bar Bar Bar Bar Bar
STIFFENER PLATE
(T.m) (T) (m) (m) (m) (m) 01 02 03 04 05 06

EMBEDDED LENGTH
A
02 F B
E F
8 m SOLAR POLE WITH
3.8 0.56 0.7 1.8 1.1 0.6
SINGLE BRACKET

(L)
BOLT DIAMETER (H)
10 m SOLAR POLE WITH
3.8 0.56 0.7 1.8 1.1 0.6
SINGLE BRACKET
F
E NOTES:
01
7 STEEL ANCHOR PLATE 1. FOR LEGEND, GRAPHICAL SYMBOLS, GENERAL NOTES, AND LIGHTING FIXTURES DESCRIPTION, REFER TO
DWG NO. 13-253001-2900001131-DAH-ELE-DRG-020001.
- SCALE: N.T.S.
2. FOR TYPICAL DETAILS AND SCHEMATICS, REFER TO DWG NO.
13-253001-2900001131-DAH-ELE-DRG-510001 TO 51000X SERIES.

8 PRESET ANCHOR BOLT DETAILS


- SCALE: N.T.S.

6 PLAN NOTES:

- SCALE: N.T.S.
1. THE COLUMN BASES ARE DESIGNED ASSUMING A WIND SPEED AND A SOIL
BEARING CAPACITY AS SPECIFIED IN THE TABLE. IN CASE OF ANY DEVIATION FROM
THE SPECIFIED VALUES, THE DESIGN OF THE FOUNDATIONS SHALL BE REVISED
ACCORDINGLY.

D 2. ALL DIMENSIONS OF STEEL TEMPLATE, STEEL BASE PLATE AND ANCHOR BOLTS
SHOULD BE VERIFIED BY THE MANUFACTURER.

3. DESIGN OF THE FOUNDATION IS BASED ON THE CALCULATED MOMENT AND SHEAR


SHOWN IN THE TABLE, THESE VALUES SHALL BE VERIFIED BASED ON THE FINAL
A SOLAR PANEL SELECTION OF THE LIGHTING POLE, IF FOUND DIFFERENT THE DESIGN OF THE
FOUNDATIONS SHALL BE REVISED ACCORDINGLY.

FINISH AROUND COLUMN TO MATCH 4. CEMENT TYPE AND REINFORCEMENT SHALL BE ACCORDING TO STRUCTURAL
SIDEWALK FINISH
SPECIFICATIONS. REFERENCE NUMBER DESCRIPTION
1m
WASHER AND NYLOC NUT BATTERY AND CONTROLLER 5. FOR EXACT DIMENSIONS OF STEEL TEMPLATES, STEEL ANCHOR PLATE AND BOLTS
UNDER GREASE FILLED BITUMEN COATING - 250mm LED LUMINAIRE REFER TO MANUFACTURER REQUIREMENTS
PROTECTIVE COVER ABOVE SIDEWALK LEVEL

6. THIS BELONG TO A PROPRIETARY ITEM AND DETAIL ARE GIVEN FOR GUIDANCE.
THE SUPPLIER CAN PROPOSE ALTERNATIVE DETAILS FOR EASE OF CONSTRUCTION
LED LUMINAIRE

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF NEOM. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT FROM NEOM.
SAND FILL

STAGE:
STEEL TEMPLATE
100
9 SOLAR SYSTEM TYPICAL DETAIL
GRADING LEVEL
- SCALE: N.T.S. 3A - CONCEPT DESIGN
WASHER AND PLUMB GENERAL NOTES:
ADJUSTING NUTS
600
800 1. POLES INSTALLED IN OUTDOOR AREAS SHALL BE HOT DIPPED GALVANIZED STEEL
OR SEAMLESS ALUMINUM ALLOY.
A 3A - CONCEPT DESIGN G.S. 08.03.2023
2. FOR POLES THICKNESS, PLEASE REFER TO THE ELECTRICAL SPECIFICATIONS AND REV DESCRIPTION APP DATE
NOTE THAT THE COLUMNS SHALL HAVE A MINIMUM WALL THICKNESS OF 3mm AT
C BASE. PURPOSE OF ISSUE:
Ø 150 mm OPENING PLUGGED
WITH TAPERED WOODEN PLUGS IF
NOT USED
3* Ø150mm RESERVED FOR LV
3. BATTERY WITH 24V SYSTEM ALONG WITH 36V SOLAR PANEL AND SOLAR FOR APPROVAL
CABLES CROSSINGS CONTROLLER OF 24V TO CATER FOR TWO CONTINUOUS DAYS AND NIGHTS. THE
SAME SHALL BE FURTHER CONFIRMED BY THE SYSTEM MANUFACTURER/SUPPLIER. CLIENT: PROJECT MANAGEMENT CONSULTANT:
STEEL ANCHOR PLATE 4. LUMINAIRES : LUMINAIRES SHALL BE MARKED, LISTED OR LABELED BY AN
C
INDEPENDENT THIRD PARTY LABORATORY (NOTIFIED BODY) THE ASSOCIATED OCTAGONAL STEEL POLE
CERTIFICATE SHALL STATE EITHER THAT THE LUMINARIES MEET APPROPRIATE
02 DESIGNATED STANDARDS OR HAVE BEEN TESTED AND FOUND SUITABLE FOR USE
IN A SPECIFIED MANNER. CERTIFICATION SHALL BE FROM APPROVED BODIES, AS
IDENTIFIED BY NEOM.
H
01
5. LUMINARIES SHALL BE SUITABLE FOR THE ENVIRONMENT WHERE THEY ARE
INSTALLED. LUMINARIES INSTALLED OUTDOOR SHALL BE APPROVED AS WEATHER SEE DETAIL-A
PROOF AND DUST TIGHT. MOUNTING METHOD OF LUMINARIES SHALL BE BASED ON
THE BEST ARRANGEMENT FOR LUMINARY, AS WELL AS EASY AND SAFE ACCESS
DURING INSTALLATION AND MAINTENANCE.
06 LEAD ENGINEER : CONTRACTOR NAME & LOGO (s):
05
6. LED LUMINARY LIFETIME (THIS INCLUDES LED LIGHT SOURCE AND DRIVER, ETC.) COPPER BARE CONDUCTOR
SHALL NOT BE LESS THAN 50,000 HOURS AND FAILURE RATE NOT MORE THAN 3% (70mm²)
500
FOR THE ENTIRE LUMINARY LIFETIME PERIOD.

7. LIGHTING FIXTURE SAMPLES SHOULD BE PROVIDED TOGETHER WITH THE


SUBMITTALS.
G.L

D
500
OCTAGONAL STEEL POLE
M12 EARTHING NUT
100 mm BLINDLY (WELDED TO POLE) DESIGN CONSULTANT / CONTRACTOR: NEOM'S REVIEW:
B CONCRETE

04 M12 BOLT AND WASHER CONN. COMPRESSION TAP DRAWN: K.N./M.S. 08.03.2023
03
B (70mm²)
CHECKED: W.J. 08.03.2023 CHECKED:
LIGHTING COLUMN BASE DETAIL
APPROVED: G.S. 08.03.2023 APPROVED:
2400
GROUND ROD
(16mm Dis.) SCALE: N.T.S. SHEET SIZE: A1
CONN. COMPRESSION LUG 12 ELEVATION
(70mm²) - SCALE: N.T.S. DISCIPLINE NAME:
ELECTRICAL
1000 COPPER BARE CONDUCTOR
(70mm²)
2900001131/00
10 SOLAR LIGHTING POLE
- SCALE: N.T.S.
MISCELLANEOUS DETAILS 01
11 DETAIL - A
- SCALE: N.T.S.
PROJECT NAME:
2900001131/00-DAR-JETTY AND STAFF
ACCOMMODATION
13 - SINDALAH ISLAND
NEOM
A
KINGDOM OF SAUDI ARABIA
STREET LIGHTING POLES DETAILS
REGION ASSET CODE CONTRACT CODE

13 253001 2900001131
DRAWING NUMBER
ORIGINATOR DISCIPLINE DOCUMENT TYPE SEQUENTIAL NUMBER REV NO.

DAH ELE DRG 510001 A


NEOM-NEN-PRC-009_TMP13_02.00