Issued in 2003
For R410A
Power-Inverter.qxp 04.7.15 5:38 PM Page 2
Contents
P U H Z - R P 3 V H A Control: A-control
3
Power-Inverter.qxp 04.7.15 5:38 PM Page 4
Composition change of R410A in the gas cylinder Composition change of R410A in the gas cylinder
when taken out from the liquid phase when taken out from the gas phase
HFC-32 Density [wt%]
Ratio of refrigerant left in gas cylinder Ratio of refrigerant left in gas cylinder
(Weight/Volume of gas cylinder) [kg/r] (Weight/Volume of gas cylinder) [kg/r]
Valve
When the refrigerant is taken out from
the gas phase, the composition
change of refrigerant in the gas cylin-
der is greater than the case where the
Refrigerant gas
cylinder with siphon
refrigerant is taken out from the liquid
phase. Therefore, charge the refriger-
ant by taking it out from the liquid
Liquid phase of gas cylinder.
Since the gas cylinder for R410A is
Gas cylinder
Electronic scale for refrigerant charge equipped with siphon, the refrigerant
can be taken out from the liquid phase
The type of refrigerant "R410A" is written on the pink sticker affixed to the gas cylinder. without turning the gas cylinder
upside down.
4
Power-Inverter.qxp 04.7.15 5:38 PM Page 5
Dimension "A"
Dimension
"B"
Outside +0 Outside
Nominal Dimension "A"( -0.4 ) Nominal diameter Dimension "B"
diameter
diameter [mm] R22 R410A diameter [mm] R22 R410A
1/4" 6.35 9.0 9.1 1/4" 6.35 17 17
3/8" 9.52 13.0 13.2 3/8" 9.52 22 22
1/2" 12.7 16.2 16.6 1/2" 12.7 24 26
5/8" 15.88 19.4 19.7 5/8" 15.88 27 29w
3/4" 19.05 23.3 3/4" 19.05 36
w:36.0mm for indoor unit of RP4,5 and 6.
5
Power-Inverter.qxp 04.7.15 5:38 PM Page 6
Checking the con- 1Use the refrigerant pipe whose wall thickness is WRequiredwithstand pressure
struction place specified in the page5. can be secured.
2Prepare the following tools exclusive for R410A WThe size of screw for
Preparation before service port is changed
construction beforehand. (For installation)
from 7/16 UNF to 1/2 UNF. 5
Gauge manifold ·Flare tool
Inserting the sleeves ·Charge hose WThe materials suitable for 8
·Vacuum pump HFC refrigerant are used. 9
·Backflow prevention device (for vacuum pump) WWrong use of R22 is avoided. 10
(For refrigerant charge) WIf the oil in the vacuum 16
pump flows backward into
·Electronic scale for refrigerant charge 17
the unit, the unit could
·Refrigerant gas cylinder
malfunction.
·Charge mouth for refrigerant gas cylinder
Observe the followings to keep the inside of pipe clean and WIf there is foreign material or
Installing the airtight. moisture in the pipe, the
indoor unit 1Use the pipe whose inside is clean.
2Do not let any foreign material go into the pipe when
cooling effect could be
Refrigerant pipe insufficient or the comp-
leaving the pipe unconnected.
work
3Flare the pipe closely. ressor could malfunction.
4Apply the specified oil to the flared part of pipe. WIf the refrigerant leaks, the 5
Drain pipe work
(Ester oil, ethereal oil and alkyl benzene oil, etc.) unit could stop due to 11
5Check the dimension of opposite side and shape of flare nut.
Duct work abnormality or the unit's 12
6Use the torque wrench to tighten the pipe securely.
7Blow nitrogen into the pipe when brazing is performed. capacity could beinsufficient. 13
Heat insulation 8Before connecting the pipe to the unit, discharge the air in the
work 14
pipe from the pipe connections.
Electrical work
Installing the
outdoor unit WIf the refrigerant leaks, the unit
1Apply the specified oil to the flared part of pipe.
could stop due to abnormality or
Connecting the (Ester oil, ethereal oil and alkyl benzene oil, etc.) the unit's capacity could be 16
refrigerant pipe 2Use the torque wrench to tighten the pipe securely. insufficient.
WIf the refrigerant leaks, the unit
1Use nitrogen gas to raise the pressure to the designed
could stop due to abnormality or
Airtight test pressure of unit, and perform the airtight test for 7
the unit's capacity could be
24 hours. insufficient.
1Use the vacuum pump equipped with a backflow pre- WIf the oil in the vacuum
Vacuuming vention function or use the conventional vacuum pump pump flows backward into
the unit, the unit could 8
together with a backflow prevention device.
malfunction. 9
2Perform vacuuming fully (for about 1 hour or more
after the low pressure has reached -0.1Mpa.). WRemoving moisture and air
fully prevents oil deterioration.
Do not use any refrigerant to purge air.
1Take out R410A from the liquid phase of gas cylinder. WIf R410A is taken out from the gas
phase, the composition of refrigerant
Charging the add- (If the gas cylinder with siphon is used, turning it charged changes, and the unit could
itional refrigerant upside down is not necessary.) stop easily due to abnormality or the 4
2Use the gauge manifold and charge hose exclusive unit's capacity could be insufficient 17
easily.
for R410A. WWrong charge of refrigerant is
avoided.
Checking the
Use the refrigerant leak detector for alternative WThe conventional refrigerant 10
gas leakage leak detector cannot detect
refrigerant. 17
R410A.
Test run
For units equipped with the replacement filter WThe replacement filter recovers
Explanation of comple- (RP4,RP5,RP6), perform pipe washing operation in the chemical compound containing 14
tion of installation and chlorine remained in the pipe.
cooling mode for about 2 hours.
operation method to
customers
6
Power-Inverter.qxp 04.7.15 5:38 PM Page 7
4.Airtight Test
After finishing the refrigerant pipe work, check if the gas leaks from the pipe connected in the field.
Caution
1. Perform the airtight test with the stop valve and ball valve of outdoor unit closed. <See Photo 1.>
2. Do not use chlorine refrigerant, oxygen or flammable gas as pressurized gas.
(The use of oxygen could result in an explosion.)
Indoor unit
4.3 Connection Outdoor unit
Liquid pipe
·Connect the testing tools, referring to the illustration
Gas pipe
on the right.
·Connect them to the service port of stop valve on
Gauge manifold
either liquid pipe side or gas pipe side. Low
( )
High Connect the testing tools to the
Knob (Low) Knob (High) service port of stop valve on either
Nitrogen gas liquid pipe side or gas pipe side.
Apply pressure to the outdoor unit gradually. Do not raise it to the specified pressure at a stretch.
Procedures Pressurization and
waiting time
Apply pressure of 0.5MPa (5kgf/f) to the outdoor unit and wait for
1 10.5MPa
5 minutes. After that, make sure the pressure does not decrease.
Raise the pressure from 0.5MPa to 1.5MPa (15kgf/f) to apply it to
5 min.21.5MPa
2 the outdoor unit and wait for 5 minutes. After that, make sure the
pressure does not decrease.
5 min.34.15MPa
Raise the pressure from 1.5MPa to 4.15MPa (42.3kgf/f) to apply
3 it to the outdoor unit and record the ambient temperature and the 24 hours
pressure.
·Remove the nitrogen gas cylinder and wait for 1 day (24 hours). After that, make sure the pressure does not decrease.
·After removing the gas cylinder, be sure to put a stopper on the part where the cylinder was connected to prevent refrig-
erant leakage.
Example when the nitrogen gas cylinder is removed
Gauge manifold
Liquid pipe
Gas pipe
·If the specified pressure holds for about 1 day and does not decrease, the refrigerant pipe have passed the airtight test.
·If the ambient temperature changes by 1 , the pressure changes by about 0.03MPa (0.3kgf/f).
Therefore, correction is needed.
Correction value = (Temperature in 24 hours - Temperature when the pressure is raised to 4.15MPa)o0.03
There is refrigerant leakage if the pressure decreases on the steps 1 to 3. Repair the part where the refrigerant leaks.
7
Power-Inverter.qxp 04.7.15 5:38 PM Page 8
Vacuum torr
degree (mmHg) 760 525 355 234 149 90 55 36 17 9 4.6 1 0.003
-7
Absolute MPa 0.1013 0.070 0.047 0.031 0.022 0.012 0.0073 0.0048 0.0027 0.0012 0.0006 0.00013 3.9o10
pressure (abs) (Atmosphe-
ricpressure)
Caution
1.If the oil in the vacuum pump flows backward into the refrigerant cycle, this could be a major cause of damage to the
unit. Therefore, use the vacuum pump together with a backflow prevention device to prevent the oil in the vacuum
pump from flowing backward.
2.Since the refrigerant oil used in the HFC refrigerant cycle is highly hygroscopic to moisture, it will generate acidic
material even if a slight amount of moisture gets mixed into it. Therefore, remove moisture fully by the vacuum pump
(0.5 Torr or less) that provides a high vacuum.
5.4 Connection ·If the oil flows backward from the unit or the
·Connect the apparatus, referring to the illustration below (initial state). vacuum pump, the thermistor vacuum gauge
(Close the stop value and ball valve of outdoor unit.) could be damaged. Therefore, use the vacuum
Gauge manifold valve to prevent the oil from flowing backward.
Low High
Blue valve on low-pressure Red valve on high-pressure
side (Opened) side (Closed)
Vacuum valve equipped with backflow
Blue prevention function (Opened)
With pin Yellow
Backflow prevention
device Thermistor
vacuum gauge
Cord
Service port of stop valve · Use it to perform vacuuming
on liquid pipe side of unit properly.
· Use the vacuum pump equipped with a Vacuum
backflow prevention function or use the pump
vacuum pump together with a backflow
prevention device to prevent the oil in the
vacuum pump from flowing backward.
Note 1) A vacuum gauge can be used as an alternative for thermistor vacuum gauge.
If the vacuum gauge is used, be sure to use the vacuum valve to prevent the pressure of refrigerant from being
applied to the vacuum gauge and to prevent the oil from flowing backward. After completion of vacuuming, close
the valves at the inlet/outlet of vacuum gauge.
8
Power-Inverter.qxp 04.7.15 5:38 PM Page 9
5.5 Procedures
Low High
3.After completion of vacuuming, close the vacuum valve and set the
switches of vacuum pump and backflow prevention device to OFF.
Wait for 1 or 2 minutes and make sure the pressure does not
increase by observing the scales of gauge manifold and thermistor
vacuum gauge.
(If the pressure increases, this shows that there is refrigerant
eakage. Check the part where the refrigerant leaks by the airtight
test and carry out repairs. Then, perform vacuuming again.)
After that, set the switch of thermistor vacuum gauge to OFF.
5.Fully open the ball valve on gas pipe side and the stop valve on liq-
uid pipe side.
/Now, the vacuum drying has been finished when there is no need to charge additional refrigerant.
9
Power-Inverter.qxp 04.7.15 5:38 PM Page 10
6.2 Tools
Alternative refrigerant needs 25-40 times the detection capability of the conventional refrigerant leak detector for R22.
Even if the detection sensitivity of the conventional refrigerant leak detector is raised, the refrigerant leak detector could
operate wrongly since it detects the substances other than halogen gas.
Therefore, use the refrigerant leak detector for HFC refrigerant to check if there is gas leakage. Such a refrigerant leak
detector is supersensitive.
Caution
Use the refrigerant leak detector for HFC refrigerant.
6.3 Procedures
Be sure to check if the refrigerant leaks from the processed part of pipe (connected part of flare nut or brazed part).
(Applying soapy water to the part where the refrigerant leak detector detects gas leakage makes it easy to find the
exact part where the gas leaks.)
10
Power-Inverter.qxp 04.7.15 5:38 PM Page 11
The wall thickness of existingpipe meets The wall thickness of existing pipe
specifications and the existing pipe is does not meet specifications or the
not damaged. existing pipe is damaged.
Since the existing pipe can be Since the existing pipe cannot
reused, install the new unit. be used, use new pipe.
11
Power-Inverter.qxp 04.7.15 5:38 PM Page 12
<Table 2> Additional refrigerant charging amount for pipe of standard diameter
Additional refrigerant charging amount for pipe
Permitted length exceeding 30 m (kg) Number of Height
Outdoor unit pipe length bends difference
31 — 40m 41 — 50m 51 — 60m 61 — 75m
PUHZ-RP3 50m or below 0.6Kg 1.2Kg — — 30m or
15
PUHZ-RP4 — RP6 75m or below 0.6kg 1.2kg 1.8kg 2.4kg above
<Table 3>
Permitted Additional refrigerant charging amount for recharging (above) and pipe length exceeding 30m (below) (kg)
Outdoor unit pipe length 10m or below 11 — 20m 21 — 30m 31 — 40m 41 — 50m 51 — 60m 61 — 75m
4.1 4.7 — —
PUHZ-RP3 50m or below 3.1 3.3 3.5
0.6 1.2 — —
6.1 6.7 7.3 7.9
PUHZ-RP4 — RP6 75m or below 5.1 5.3 5.5
0.6 1.2 1.8 2.4
<Table 4> Additional refrigerant charging amount for liquid pipe which is one size larger than
standard diameter
Liquid pipe dia Chargeless Max. pipe length Additional refrigerant charging amount
RP3 [12.7 20m 30m 100 g addition per 1 m when pipe length exceeds 20 m
RP4 — RP6 [12.7 20m 50m 100 g addition per 1 m when pipe length exceeds 20 m
12
Power-Inverter.qxp 04.7.15 5:38 PM Page 13
13
Power-Inverter.qxp 04.7.15 5:38 PM Page 14
7.2 Reprocessing of pipe end and Operation when reusing the existing pipe
When reusing the existing pipe, reprocess the flared part of pipe to make it suitable for R410A. Moreover, replace the flare
nut with one attached to the unit.
·After turning on the power supply, a small clicking noise may be heard from the
machine chamber, this is because the electronic expansion valve works to adjust the ON
opening. < SW4 >
Therefore, this sound does not show a malfunction of unit. OFF
·A clanging noise may be heard from the machine chamber for a few seconds after the
1 2
compressor starts operating.
Stop Cooling
This sound generates from the valve element located the inside of the restrictor valve
since the differential pressure in the pipe is small. Therefore, this sound does not show a malfunction of unit.
wThe operation mode cannot be changed by SW4-2 during the test run.
(To change the operation mode of test run, stop the test run by SW4-1 first. Then change the operation
mode and resume the test run by SW4-1.)
14
Power-Inverter.qxp 04.7.15 5:38 PM Page 15
Flare tool
Dice Dice
(Rotor) Copper pipe
A[mm]
Pipe When the tool for When the tool for
·Flare tool for R410A ·Flare gauge diameter R410A is used R22 is used
[mm] Clutch type Clutch type Wing nut type
6.35 0 - 0.5 1.0 - 1.5 1.5 - 2.0
9.52 0 - 0.5 1.0 - 1.5 1.5 - 2.0
12.7 0 - 0.5 1.0 - 1.5 2.0 - 2.5
15.88 0 - 0.5 1.0 - 1.5 2.0 - 2.5
19.05 0 - 0.5 1.0 - 1.5 2.0 - 2.5
or
If the tool for R22 is used to flare the copper pipe for
& R410A, make the dimension "A" bigger than the case
Flare tool for R22 where the copper pipe for R22 is to be flared so that the
flared part of pipe can meet the pecified dimension.
The dimension "A" can be secured by using the flare
gauge for adjusting the part of pipe protruded from the
dice.
(2) For environmental protection
(3) For securing quality Use the torque wrench to tighten the flare nut with
appropriate torque to prevent refrigerant from leaking
·Torque wrench due to insufficient tightening of flare nut and to prevent
the flared part of copper pipe being damaged due to
excessive tightening of flare nut.
Dimension "B"
Outside Dimension "B"
Nominal diameter Torque
diameter [mm] R22 R410A
1/4" 6.35 17 17 18N · m(180kgf · cm)
3/8" 9.52 22 22 42N · m(420kgf · cm)
1/2" 12.7 24 26 55N · m(550kgf · cm)
5/8" 15.88 27 29 75N · m(750kgf · cm)
5/8" 15.88 36 100N · m(1000kgf · cm) w
3/4" 19.05 36 36 100N · m(1000kgf · cm)
wfor indoor unit of RP4,5,6 models.
15
Power-Inverter.qxp 04.7.15 5:38 PM Page 16
·Electronic scale for refrigerant charge ·R410A gas cylinder for refrigerant charge
When the outside tempera- If the gas cylinder is
ture is high, refrigerant is equipped with the siphon,
easy to foam in the charg- the efrigerant can be taken
ing cylinder for R410A and out without turning the gas
this makes it difficult to cal- cylinder upside down.
culate the amount of refrig-
erant. Therefore, the scale
is recommended for refrig-
erant charge.
16
Power-Inverter.qxp 04.7.15 5:38 PM Page 17
4-way valve
Indoor heat
exchanger Outdoor heat
exchanger
Receiver
Compressor
Stop valve
Standard operation
17
Power-Inverter.qxp 04.7.15 5:38 PM Page 18
cooling
Heating
Heating RP3, 4, 5
and 6 models
Capacity ratio [%]
RP4 model
RP5 model
RP6 model
Note: The permitted pipe length is up to 55m for RP3 model.
100
Heating RP3
95
Capacity ratio [%]
90
85
Cooling RP3
80
5 10 15 20 25 30 35 40 45 50 55
Corrected pipe length
3 When gas pipe is one size larger than standard size for PUHZ-RP4, 5 and 6.
1 Capacity can be obtained by referring to capacity curves of standard size.
18
Power-Inverter.qxp 04.7.15 5:38 PM Page 19
Outdoor unit
Remote
controller
Main switch/fuse
The earth leakage breaker used for power-inverter air conditioner needs to be the one exclusive for
inverter (the one taken measures against higher harmonic and surge). There are two kinds of earth
leakage breakers. One is for general use and another is the one taken measures against higher harmonic
and surge.
When the unit is newly installed, using the existing earth leakage breaker for general use (the one that is
not designed for inverter) could cause shutoff unnecessarily by higher harmonic current generated from
the inverter air conditioner.
The inverter air conditioner rectifies AC to DC and then changes DC to AC at any frequency since the
high-speed switching element turns on and off automatically. Therefore, higher harmonic current
generates more frequently in the inverter air conditioner than in the non-inverter air conditioner, and the
inverter air conditioner could cause shutoff unnecessarily due to the capacitive coupling with the earth.
As a result, the earth leakage breaker exclusive for inverter (the one taken measures against higher
harmonic and surge) is the one designed to be less subject to higher harmonic to prevent such
unnecessary shutoff.
19
Power-Inverter.qxp 04.7.15 5:38 PM Page 20
20
Power-Inverter.qxp 04.7.15 5:38 PM Page 21
21
Power-Inverter.qxp 04.7.15 5:38 PM Page 22
22
Power-Inverter.qxp 04.7.15 5:38 PM Page 23
23
Power-Inverter.qxp 04.7.15 5:38 PM Page 24