OUTSULATION X™ SYSTEM

An Exterior Wall Insulation and Finish System


With Moisture Drainage That Incorporates Continuous Insulation
Utilizing Dow® XNERGY™ Rigid Insulation Board
DS837

Outsulation X System
Installation Details
TABLE OF CONTENTS
DETAIL DETAIL
OUTSULATION X SYSTEM CUTAWAY OX 0.0.01 HORIZONTAL TERMINATION AT OX 0.0.29
AWRB APPLICATION AND OX 0.0.02 STUCCO
FASTENING PATTERN HORIZONTAL TERMINATION AT OX 0.0.30
OPENING PREPARATION- OX 0.0.03 LAPPED SIDING
AQUAFLASH® SYSTEM OPTION VERTICAL EIFS EXPANSION JOINT OX 0.0.31
OPENING PREPARATION- OX 0.0.04 THROUGH-WALL EXPANSION JOINT OX 0.0.32
BACKSTOP® NT OPTION VERTICAL EXPANSION JOINT - OX 0.0.33
OPENING FLASHING INTEGRATION OX 0.0.05 FLUSH AND RECESSED OPTIONS
INSIDE/OUTSIDE CORNERS OX 0.0.06 VERTICAL EXPANSION JOINT - OX 0.0.34
OUTSIDE CORNER - HIGH IMPACT OX 0.0.07 DOUBLE SEAL OPTION
TERMINATION AT GRADE OX 0.0.08 VERTICAL TERMINATION OX 0.0.35
TERMINATION AT CONCRETE CURB OX 0.0.09 AT STONE VENEER
TERMINATION AT ADA COMPLIANT OX 0.0.10 PENETRATIONS OX 0.0.36
SIDEWALK SIGN ATTACHMENT OX 0.0.37
INSULATION PREPARATION AT OX 0.0.11 AESTHETIC REVEALS OX 0.0.38
WALL PENETRATIONS EPS SHAPES OX 0.0.39
STOREFRONT WINDOW SILL - JAMB OX 0.0.12
FLANGED WINDOW SILL - JAMB OX 0.0.13
STOREFRONT AND FLANGED OX 0.0.14
WINDOW HEAD
TERMINATION AT OX 0.0.15
WOOD FRAMED DECK
TERMINATION AT OX 0.0.16
WATERPROOF DECK NOTE
PREPARATION AT PARAPET/ OX 0.0.17
WALL INTERSECTION DRYVIT MAKES NO REPRESENTATION REGARDING
TERMINATION ATPARAPET - OX 0.0.18 CONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDING
CAP FLASHING CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,
TERMINATION AT ROOF MEMBRANE OX 0.0.19 OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED
TERMINATION AT SLOPED ROOF OX 0.0.20 IN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE
VERTICAL WALL/ SUSPENDED OX 0.0.21 REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE
SOFFIT TRANSITION DESIGNED, DETAILED, AND ENGINEERED BY
TRANSITION AT SOFFIT/ OX 0.0.22 REPRESENTATIVES OF THE ARCHITECT, OWNER, OR
FASCIA INTERSECTION CONTRACTOR TO BE IN CONFORMANCE WITH MODEL
FASCIA/ UNINSULATED SOFFIT OX 0.0.23 CODES, ARCHITECTURAL, AND ENGINEERING
TRANSITION REQUIREMENTS PERTAINING TO SPECIFIC BUILDING
TERMINATION AT OX 0.0.24 PROJECTS.
UNINSULATED SOFFIT VENT
HORIZONTAL JOINT AT FLOOR LINE OX 0.0.25 DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,
WITHOUT WEEPS AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR
HORIZONTAL JOINT AT FLOOR LINE OX 0.0.26 WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS
WITH WEEPS OR PRODUCTS.
HORIZONTAL JOINT - OX 0.0.27
SUBSTRATE CHANGE THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THE
HORIZONTAL TERMINATION OX 0.0.28 OUTSULATION X LIMITED COMMERCIAL WARRANTY.
AT STONE VENEER CONTACT DRYVIT FOR A FULL AND COMPLETE COPY OF
THE WARRANTY.

Outsulation® X System

The architecture, engineering, and design of the project using the


Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.01

FRAMING

DRYVIT GENESIS® ADHESIVE APPLIED IN VERTICAL NOTCHED


TROWEL CONFIGURATION TO BACK OF INSULATION BOARD

DRYVIT APPROVED WASHER WITH CORROSION


RESISTANT FASTENER (SEE NOTE 2)
APPROVED DOW® XNERGY™ RIGID INSULATION BOARD

NORMAL IMPACT APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS™ REINFORCING MESH


EMBEDDED IN DRYVIT GENESIS BASE COAT

DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS


OF DRYVIT AP ADHESIVE™

FRAMING

DRYVIT GENESIS ADHESIVE APPLIED IN VERTICAL NOTCHED


TROWEL CONFIGURATION TO BACK OF INSULATION BOARD

DRYVIT APPROVED WASHER WITH CORROSION


RESISTANT FASTENER (SEE NOTE 2)
APPROVED DOW XNERGY RIGID INSULATION BOARD

HIGH IMPACT APPROVED SUBSTRATE

DRYVIT AIR/WATER - RESISTIVE BARRIER COATING

DRYVIT GENESIS BASE COAT

DRYVIT PANZER REINFORCING MESH

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS REINFORCING MESH


EMBEDDED IN DRYVIT GENESIS BASE COAT

DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT DRAINAGE STRIP ADHERED WITH DABS


OF DRYVIT AP ADHESIVE

Outsulation® X System

Outsulation X System Cutaway
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH discretion, whether this detail or a functionally equivalent detail is
IMPACT ZONES SHOULD BE INDICATED best suited for the project. Use of a functionally equivalent detail does
ON CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. INSTALL FASTENERS IMMEDIATELY
FOLLOWING BOARD PLACEMENT, WHILE
ADHESIVE IS STILL WET.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.02

DRYVIT BACKSTOP® NT™ - TEXTURE


OVER DRYVIT GRID TAPE™

DRYVIT BACKSTOP NT - TEXTURE


FRAMING

APPROVED SUBSTRATE

DRYVIT AIR/WATER - RESISTIVE


BARRIER COATING

DRYVIT APPROVED WASHER WITH


CORROSION RESISTANT FASTENER
(SEE NOTE 5)

APPROVED DOW® XNERGY™ RIGID


INSULATION BOARD

4" (102 MM)

SPACE FASTENERS MAXIMUM


12" (305 MM) ALONG CORNERS AND
OTHER SYSTEM TERMINATIONS

Outsulation® X System

AWRB Application and Fastening Pattern
NOTE: The architecture, engineering, and design of the project using the
1. ALTERNATE FASTENERS AT EACH STUD. Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
2. STAGGER VERTICAL JOINTS AT ALL INSIDE AND OUTSIDE standards. This detail is for general information and guidance only
CORNERS. and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
3. INSTALL INSULATION BOARD IN RUNNING BOND PATTERN. project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
4. TIGHTLY BUTT ALL INSULATION BOARDS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
5. INSTALL THREE FASTENERS PER 2 FT (610 MM) BY 4 FT (1219 MM) notice. Contact Dryvit to ensure you have the most recent version.
INSULATION BOARD IMMEDIATELY FOLLOWING BOARD
PLACEMENT WHILE ADHESIVE IS STILL WET.

6. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER DETAILS, REFER


TO DRYVIT PUBLICATION DS840.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.03

APPLY DRYVIT AQUAFLASH® SYSTEM


(SEE NOTES 1 AND 3)
INSTALL DIAGONAL STRIP OF DRYVIT
AQUAFLASH MESH AT CORNERS
DRYVIT AIR/WATER-RESISTIVE AND EMBED IN AQUAFLASH LIQUID
BARRIER COATING (SEE NOTES 1, 3)

STEP #1 STEP #2

INSTALL DRYVIT AQUAFLASH


SYSTEM AT JAMBS
(SEE NOTES 1 AND 3)

INSTALL DRYVIT AQUAFLASH


SYSTEM AT HEADS
(SEE NOTES 1, 3 AND 4)

STEP #3 STEP #4

Outsulation® X System
™ Opening Preparation -
AquaFlash® System5 Option
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT AQUAFLASH SHALL EXTEND TO 4. INSTALL WINDOW UNIT AND ASSOCIATED Dryvit products is the responsibility of the project's design
INTERIOR FACE OF OPENING. FLASHINGS PER MANUFACTURER'S professional. All systems must comply with local building codes and
RECOMMENDATIONS, CODE REQUIREMENTS AND standards. This detail is for general information and guidance only
2. REFER TO HEAD, SILL AND JAMB DETAILS PROJECT DOCUMENTS. and Dryvit specifically disclaims any liability for the use of this detail
FOR FLASHING INTEGRATION. and for the architecture, design, engineering or workmanship of any
5. AQUAFLASH SYSTEM CONSISTS OF AQUAFLASH project. The project design professional determines, in its sole
3. DRYVIT FLASHING TAPE SURFACE MESH AND AQUAFLASH LIQUID. discretion, whether this detail or a functionally equivalent detail is
CONDITIONER™ AND DRYVIT FLASHING TAPE™ best suited for the project. Use of a functionally equivalent detail does
MAY BE USED IN LIEU OF DRYVIT 6. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER not violate Dryvit's warranty. This detail is subject to change without
AQUAFLASH SYSTEM. DETAILS, REFER TO DRYVIT PUBLICATION DS840. notice. Contact Dryvit to ensure you have the most recent version.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.05

REFER TO OX 0.0.03, AND OX 0.0.04 FOR


PREPARATION OF OPENING PRIOR TO
FLASHING INSTALLATION

STEP #1

REFER TO OX 0.0.12 & OX


0.0.13 FOR JAMB DETAIL

INSTALL WINDOW UNIT AND


APPLY DRYVIT AQUAFLASH® ASSOCIATED FLASHINGS AND
SYSTEM SPLICES LAPPING OVER APPLY DRYVIT AQUAFLASH
LIP OF SILL PAN FLASHING. SYSTEM OVER VERTICAL LEG OF
(SEE NOTES 1 AND 2) FLASHING (SEE NOTES 1 AND 2)

STEP #2 STEP #3

Outsulation® X ™ System Opening Flashing Integration


NOTE: The architecture, engineering, and design of the project using the
1. REFER TO OX 0.0.12 THROUGH OX 0.0.14 Dryvit products is the responsibility of the project's design
FOR INTEGRATION OF FLASHING. professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
2. DRYVIT FLASHING TAPE SURFACE and Dryvit specifically disclaims any liability for the use of this detail
CONDITIONER™ AND DRYVIT FLASHING and for the architecture, design, engineering or workmanship of any
TAPE™ MAY BE USED IN LIEU OF DRYVIT project. The project design professional determines, in its sole
AQUAFLASH SYSTEM. discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
3. FOR ADDITIONAL AIR/WATER-RESISTIVE not violate Dryvit's warranty. This detail is subject to change without
BARRIER DETAILS, REFER TO DRYVIT notice. Contact Dryvit to ensure you have the most recent version.
PUBLICATION DS840.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.06

DRYVIT APPROVED WASHER


WITH CORROSION
RESISTANT FASTENER

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING

DRYVIT BACKSTOP® NT™-TEXTURE


OVER DRYVIT GRID TAPE™
DRYVIT GENESIS® ADHESIVE APPLIED IN
VERTICAL NOTCHED TROWEL CONFIGURATION
TO BACK OF INSULATION BOARD

APPROVED DOW® XNERGY™ RIGID


INSULATION BOARD
DRYVIT GENESIS BASE COAT
DRYVIT STANDARD PLUS REINFORCING MESH
EMBEDDED IN DRYVIT GENESIS BASE COAT

DRYVIT GENESIS BASE COAT

MUST OVERLAP DRYVIT FINISH


8" (203 MM) MIN.
(SEE NOTES 2, 3 AND 4)
8"
(203 MM)
MIN
8"
(203 MM)
MIN.
MUST OVERLAP
8" (203 MM) MIN.
SEE NOTE 3
APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT GENESIS ADHESIVE APPLIED IN VERTICAL
NOTCHED TROWEL CONFIGURATION TO BACK OF
INSULATION BOARD
APPROVED DOW XNERGY RIGID
INSULATION BOARD
DRYVIT BACKSTOP NT-TEXTURE
OVER DRYVIT GRID TAPE
DRYVIT STANDARD PLUS REINFORCING MESH
EMBEDDED IN DRYVIT GENESIS BASE COAT

DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT APPROVED WASHER


WITH CORROSION
RESISTANT FASTENER

Outsulation® X System

Inside/Outside Corners
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 4. INSULATION BOARD EDGES SHALL BE Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES OFFSET AT INSIDE AND OUTSIDE CORNERS. professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. DOUBLE WRAP OUTSIDE CORNERS WITH notice. Contact Dryvit to ensure you have the most recent version.
REINFORCING MESH OR USE CORNER MESH.

3. DO NOT LAP REINFORCING MESH WITHIN


8" (203 MM) OF A CORNER.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.07

APPROVED SUBSTRATE
DRYVIT APPROVED WASHER WITH
CORROSION RESISTANT FASTENER
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING

DRYVIT GENESIS® ADHESIVE


APPLIED IN VERTICAL
NOTCHED TROWEL
CONFIGURATION TO BACK OF
INSULATION BOARD

APPROVED DOW® XNERGY™


RIGID INSULATION BOARD

DRYVIT BACKSTOP® NT™-TEXTURE


OVER DRYVIT GRID TAPE™

DRYVIT GENESIS BASE COAT

DRYVIT PANZER®
REINFORCING MESH

DRYVIT CORNER MESH™

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH OVERLAP
MIN. 8" (203 MM) AT CORNER

DRYVIT FINISH

8" 8"
(203 MM) (203 MM)
MIN. MIN.

Outsulation® X System

Outside Corner - High Impact
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. INSULATION BOARD EDGES SHALL BE
OFFSET.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.08
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT APPROVED WASHER WITH


CORROSION RESISTANT FASTENER
BY OTHERS
DRYVIT GENESIS® ADHESIVE APPLIED IN
VERTICAL NOTCHED TROWEL CONFIGURATION
TO BACK OF INSULATION BOARD OUTSULATION X
SYSTEM

APPROVED SUBSTRATE

2'-0"
(610 MM) MAX.
DRYVIT FINISH
(SEE NOTE 2)
DRYVIT GENESIS BASE COAT
DRYVIT STANDARD PLUS REINFORCING MESH
EMBEDDED IN DRYVIT GENESIS BASE COAT
APPROVED DOW® XNERGY™
8" RIGID INSULATION BOARD
(203 MM) DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 4)
MIN.
DRYVIT DETAIL MESH® WRAPPED
TO BACKSIDE OF INSULATION BOARD
MIN. 2-1/2" (64 MM)
DRYVIT BACKSTOP® NT™-TEXTURE
OVER DRYVIT GRID TAPE™

DRYVIT DRAINAGE STRIP™ ADHERED


WITH DABS OF DRYVIT AP ADHESIVE
(SEE NOTE 3)

SLOPE GRADE AWAY


FROM FOUNDATION WALL

Outsulation® X System

Termination At Grade
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. ENSURE BOTTOM EDGE OF DRAINAGE Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES STRIP IS LEFT FREE TO DRAIN. professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE 4. DRYVIT FLASHING TAPE SURFACE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH CONDITIONER™ AND DRYVIT FLASHING and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD TAPE™ MAY BE USED IN LIEU OF DRYVIT project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH AQUAFLASH SYSTEM. discretion, whether this detail or a functionally equivalent detail is
IMPACT ZONES SHOULD BE INDICATED best suited for the project. Use of a functionally equivalent detail does
ON CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. EXPANSION JOINT IS REQUIRED ALONG
TOP OF FOUNDATION IF 2'-0" (610 MM)
DIMENSION IS EXCEEDED.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.09

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT GENESIS® ADHESIVE APPLIED IN VERTICAL NOTCHED


TROWEL CONFIGURATION TO BACK OF INSULATION BOARD BY OTHERS
APPROVED DOW® XNERGY™
RIGID INSULATION BOARD
OUTSULATION X
SYSTEM
APPROVED SUBSTRATE

DRYVIT APPROVED
WASHER WITH
CORROSION RESISTANT
FASTENER

DRYVIT GENESIS
BASE COAT

DRYVIT STANDARD
PLUS REINFORCING
MESH EMBEDDED IN
DRYVIT GENESIS BASE
COAT
DRYVIT FINISH

3/4"
(19 MM) MIN.
(SEE NOTE 4)

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

DRYVIT BACKSTOP® NT™


TEXTURE OVER DRYVIT
GRID TAPE™
DRYVIT DRAINAGE STRIP™ ADHERED WITH
DABS OF DRYVIT AP ADHESIVE (SEE NOTE 2)
DRYVIT AQUAFLASH® SYSTEM
(SEE NOTE 3)

Outsulation® X System

Termination At Concrete Curb
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND FLOOR 4. TO PREVENT DEBRIS ACCUMULATION IT IS Dryvit products is the responsibility of the project's design
APPLICATIONS AND ALL FACADES EXPOSED TO RECOMMENDED TO TERMINATE SYSTEM professional. All systems must comply with local building codes and
ABNORMAL STRESS, HIGH TRAFFIC, OR 2" (51 MM) ABOVE SIDEWALK. standards. This detail is for general information and guidance only
DELIBERATE IMPACT HAVE THE BASE COAT and Dryvit specifically disclaims any liability for the use of this detail
REINFORCED WITH PANZER® MESH PRIOR TO and for the architecture, design, engineering or workmanship of any
STANDARD PLUS™ MESH. LOCATION OF HIGH project. The project design professional determines, in its sole
IMPACT ZONES SHOULD BE INDICATED ON discretion, whether this detail or a functionally equivalent detail is
CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. ENSURE BOTTOM EDGE OF DRAINAGE STRIP IS notice. Contact Dryvit to ensure you have the most recent version.
LEFT FREE TO DRAIN.

3. DRYVIT FLASHING TAPE SURFACE


CONDITIONER™ AND DRYVIT FLASHING TAPE™
MAY BE USED IN LIEU OF DRYVIT AQUAFLASH
SYSTEM.
© Dryvit Systems, Inc.
Issued: 10/2016
OX 0.0.10
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT APPROVED WASHER WITH


CORROSION RESISTANT FASTENER

DRYVIT GENESIS® ADHESIVE APPLIED IN VERTICAL NOTCHED BY OTHERS


TROWEL CONFIGURATION TO BACK OF INSULATION BOARD

OUTSULATION X
SYSTEM
APPROVED SUBSTRATE
APPROVED DOW®
XNERGY™ RIGID
INSULATION BOARD

DRYVIT GENESIS
BASE COAT

DRYVIT STANDARD
PLUS REINFORCING
MESH EMBEDDED IN
DRYVIT GENESIS BASE
COAT
DRYVIT FINISH

3/4" (19 MM) MIN.


(SEE NOTE 5)

2" (51 MM) MAX.


OVERLAP

DRYVIT DETAIL MESH® WRAPPED TO BACKSIDE


METAL PROTECTION SHEET, OF INSULATION BOARD MIN. 2-1/2" (64 MM)
BY OTHERS DRYVIT DRAINAGE STRIP™ ADHERED WITH
DABS OF DRYVIT AP ADHESIVE (SEE NOTE 4)
FULLY ADHERED FOUNDATION
WATERPROOFING MEMBRANE, DRYVIT AQUAFLASH® SYSTEM
BY OTHERS

COMPRESSIBLE FILLER BOARD, ADA COMPLIANT SIDEWALK SLOPED


BY OTHERS AWAY FOR POSITIVE DRAINAGE

Outsulation® X System

Termination At ADA Compliant Sidewalk
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND FLOOR 4. ENSURE BOTTOM EDGE OF DRAINAGE Dryvit products is the responsibility of the project's design
APPLICATIONS AND ALL FACADES EXPOSED TO STRIP IS LEFT FREE TO DRAIN. professional. All systems must comply with local building codes and
ABNORMAL STRESS, HIGH TRAFFIC, OR standards. This detail is for general information and guidance only
DELIBERATE IMPACT HAVE THE BASE COAT 5. TO PREVENT DEBRIS ACCUMULATION IT IS and Dryvit specifically disclaims any liability for the use of this detail
REINFORCED WITH PANZER® MESH PRIOR TO RECOMMENDED TO TERMINATE SYSTEM and for the architecture, design, engineering or workmanship of any
STANDARD PLUS™ MESH. LOCATION OF HIGH 2" (51 MM) ABOVE SIDEWALK. project. The project design professional determines, in its sole
IMPACT ZONES SHOULD BE INDICATED ON discretion, whether this detail or a functionally equivalent detail is
CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. USE OF THIS DETAIL IS LIMITED TO notice. Contact Dryvit to ensure you have the most recent version.
SLAB-ON-GRADE APPLICATIONS.

3. INCORPORATE MEASURES TO PROTECT


STRUCTURE FROM MOISTURE INSTRUSION,
DAMPNESS, AND FROST HEAVE.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.11

DRYVIT APPROVED APPROVED DOW® XNERGY™


WASHER WITH CORROSION RIGID INSULATION BOARD
RESISTANT FASTENER (SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

DRYVIT DETAIL REINFORCING MESH


9 1/2" (241 MM) X 12" (305 MM) (TYP.)
(SEE NOTE 3)

Outsulation® X System

Insulation Preparation At Wall Penetrations
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. APPLY A PIECE OF 9 1/2" (241 MM) X 12" (305 MM) Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES DETAIL REINFORCING MESH DIAGONALLY AT professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH EACH CORNER. standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. LOCATE INSULATION BOARDS SUCH
THAT BOARD EDGES DO NOT ALIGN WITH
CORNERS OF PENETRATION.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.12

3/4" (19 MM) MIN.

DRYVIT DETAIL MESH® WRAPPED TO


BACKSIDE OF INSULATION BOARD
MIN. 2-1/2" (64 MM)
(SEE NOTE 6)

DRYVIT GENESIS® BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
AIR SEAL PER MANUFACTURER'S
IN DRYVIT GENESIS BASE COAT
REQUIREMENTS, BY OTHERS

DRYVIT COMPATIBLE SEALANT


WITH CLOSED CELL BACKER ROD,
SLOPED SHIM AS
BY OTHERS (SEE NOTE 4)
REQUIRED, BY OTHERS

DRYVIT DETAIL MESH® WRAPPED DRYVIT FINISH


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM) CONTINUOUS FLASHING, BY
OTHERS, TURN UP 1/2" (12.7 MM) MIN.
AT JAMBS - SEE DETAIL BELOW

DRYVIT COMPATIBLE
SEALANT, BY OTHERS

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
IN DRYVIT GENESIS BASE COAT
DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 2 & 3)

APPROVED DOW®
XNERGY™ RIGID
INSULATION BOARD DRYVIT APPROVED WASHER WITH
CORROSION RESISTANT FASTENER
EPS SHAPE (OPTIONAL)
ADHERED USING DRYVIT
GENESIS ADHESIVE
2 1/2"
DRYVIT GENESIS (64 MM) MIN.
BASE COAT

APPROVED SUBSTRATE

DRYVIT
AIR/WATER-RESISTIVE DRYVIT GENESIS ADHESIVE 1/2" (12.7 MM)
BARRIER COATING APPLIED IN VERTICAL NOTCHED
TROWEL CONFIGURATION TO
BACK OF INSULATION BOARD
SILL PAN FLASHING
DETAIL

Outsulation® X System

Storefront Window Sill - Jamb
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. DRYVIT BACKSTOP® NT™-TEXTURE OVER GRID TAPE™ Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES IS AN ALTERNATIVE OPTION AT JAMB AND HEAD professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH CONDITION PER DETAIL OX 0.0.04 standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® 4. SEALANT SHOULD NOT BE IN DIRECT CONTACT WITH and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. DRYVIT FLASHING TAPE; STAINING MAY OCCUR. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. 5. SILL PAN FLASHING MUST HAVE WATER TIGHT SEAMS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. DRYVIT FLASHING TAPE SURFACE 6. EDGE WRAPPING METHOD IS ACCEPTABLE AT SILL AND notice. Contact Dryvit to ensure you have the most recent version.
CONDITIONER™ AND DRYVIT FLASHING JAMB IN LIEU OF BACK WRAPPING. DRYVIT REINFORCING
TAPE™ MAY BE USED IN LIEU OF DRYVIT MESH MUST BE FULLY EMBEDDED IN DRYVIT BASE COAT
AQUAFLASH SYSTEM. AT INSULATION BOARD EDGE AND MUST EXTEND ONTO
SUBSTRATE 2-1/2" (64 MM) MIN.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.16

FRAMING

APPROVED SUBSTRATE

DRYVIT GENESIS® ADHESIVE APPLIED IN


VERTICAL NOTCHED TROWEL CONFIGURATION
TO BACK OF INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING

APPROVED DOW® XNERGY™ RIGID


INSULATION BOARD

DRYVIT APPROVED WASHER WITH


CORROSION RESISTANT FASTENER

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED IN
DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT DRAINAGE STRIP™


ADHERED WITH DABS OF DRYVIT
AP ADHESIVE (SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION BOARD
MIN. 2-1/2" (64 MM)

2"
(51 MM)
MIN.

COMPATIBLE WATERPROOF DECK


COATING, BY OTHERS

CANT STRIP, BY OTHERS

SLOPE CONCRETE DECK SURFACE


AWAY FROM VERTICAL WALL

Outsulation® X System

Termination at Waterproof Deck
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. ENSURE BOTTOM EDGE OF DRAINAGE
STRIP IS LEFT FREE TO DRAIN.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.17
FRAMING
FLASHING SLEEVE,
APPROVED SUBSTRATE BY OTHERS

DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING

DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 1)

8"
(203 MM)
MIN.

6"
(152 MM) 6"
(152 MM)

STEP #1 STEP #2

DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 1)

STEP #3

Outsulation® X ™ System Preparation At Parapet/ Wall Intersection


NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT FLASHING TAPE SURFACE Dryvit products is the responsibility of the project's design
CONDITIONER™ AND DRYVIT FLASHING professional. All systems must comply with local building codes and
TAPE™ MAY BE USED IN LIEU OF DRYVIT standards. This detail is for general information and guidance only
AQUAFLASH SYSTEM. and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.18

METAL CAP FLASHING


ASSEMBLY FASTENED TO
BLOCKING, BY OTHERS

ROOF ASSEMBLY, BY OTHERS

DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 2)

FRAMING, 2 1/2"
BY OTHERS (64 MM) MIN.

DRYVIT COMPATIBLE
SEALANT, BY OTHERS
ROOF
ASSEMBLY DRYVIT DETAIL MESH® WRAPPED
TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)
(SEE NOTE 3)

DRYVIT FINISH

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
IN DRYVIT GENESIS BASE COAT

APPROVED DOW® XNERGY™ RIGID


INSULATION BOARD

DRYVIT APPROVED WASHER WITH


CORROSION RESISTANT FASTENER

DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING

DRYVIT GENESIS® ADHESIVE


APPLIED IN VERTICAL NOTCHED
TROWEL CONFIGURATION TO
BACK OF INSULATION BOARD

APPROVED SUBSTRATE

Outsulation® X ™ System Termination At Parapet - Cap Flashing


NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. EDGE WRAPPING METHOD IS Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES ACCEPTABLE IN LIEU OF BACK WRAPPING. professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH DRYVIT REINFORCING MESH MUST BE standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE FULLY EMBEDDED IN DRYVIT BASE COAT AT and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH INSULATION BOARD EDGE AND EXTEND and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD ONTO SUBSTRATE 2-1/2" (64 MM) MIN. project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.19

METAL CAP FLASHING


ASSEMBLY FASTENED TO
BLOCKING, BY OTHERS DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

DRYVIT DETAIL MESH WRAPPED TO BACKSIDE


OF INSULATION BOARD MIN. 2-1/2" (64 MM).
(SEE NOTE 4)
2 1/2" APPROVED SUBSTRATE
(64 MM)
MIN.
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
APPROVED SEALANT, BY OTHERS
DRYVIT GENESIS® ADHESIVE
DRYVIT APPROVED WASHER WITH
APPLIED IN VERTICAL NOTCHED
CORROSION RESISTANT FASTENER
TROWEL CONFIGURATION TO
DRYVIT GENESIS BASE COAT BACK OF INSULATION BOARD

DRYVIT STANDARD PLUS APPROVED DOW® XNERGY™


REINFORCING MESH EMBEDDED RIGID INSULATION BOARD
IN DRYVIT GENESIS BASE COAT DRYVIT AQUAFLASH®
DRYVIT FINISH SYSTEM (SEE NOTE 2)

DRYVIT DRAINAGE STRIP™ SET IN


DABS OF DRYVIT AP ADHESIVE
3/4"
(19 MM) DRYVIT DETAIL MESH® WRAPPED
MIN. TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

ROOF FLASHING AND COUNTER


FLASHING, BY OTHERS

8"
(203 MM)
MIN.

ROOF ASSEMBLY,
BY OTHERS

DRYVIT COMPATIBLE SEALANT


DRYVIT DEMANDIT® OR COLOR W/CLOSED CELL BACKER ROD
PRIME™ ON SURFACE(S) TO AND WEEP TUBES EVERY
RECEIVE SEALANT 610 MM (24") BY OTHERS
(SEE NOTE 3)

Outsulation® X System

Termination At Roof Membrane
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. SEALANT SHOULD NOT BE IN DIRECT Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES CONTACT WITH DRYVIT FLASHING TAPE; professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH STAINING MAY OCCUR. standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® 4. EDGE WRAPPING METHOD IS and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. ACCEPTABLE IN LIEU OF BACK WRAPPING. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD DRYVIT REINFORCING MESH MUST BE discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. FULLY EMBEDDED IN DRYVIT BASE COAT best suited for the project. Use of a functionally equivalent detail does
AT INSULATION BOARD EDGE AND not violate Dryvit's warranty. This detail is subject to change without
2. DRYVIT FLASHING TAPE SURFACE EXTEND ONTO SUBSTRATE 2-1/2" (64 MM) notice. Contact Dryvit to ensure you have the most recent version.
CONDITIONER™ AND DRYVIT FLASHING MIN.
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.22

FRAMING

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER


COATING (SEE NOTE 3)

DRYVIT GENESIS® ADHESIVE APPLIED


IN VERTICAL NOTCHED TROWEL
CONFIGURATION TO BACK OF
DRYVIT DRAINAGE STRIP™ INSULATION BOARD
ADHERED WITH DABS OF DRYVIT
AP ADHESIVE (SEE NOTE 2) APPROVED DOW® XNERGY™
RIGID INSULATION BOARD

DRYVIT BACKSTOP® NT™-TEXTURE DRYVIT APPROVED WASHER


OVER DRYVIT GRID TAPE™ WITH CORROSION RESISTANT
FASTENER

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
IN DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT GENESIS® ADHESIVE APPLIED


TO BACK OF INSULATION BOARD

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

DRYVIT FINISH

Outsulation® X ™ System Transition At Soffit/ Fascia Intersection


NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. DRYVIT AIR/WATER-RESISTIVE BARRIER IS Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES REQUIRED OVER VERTICAL SUBSTRATES, professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH APPLICATION OVER HORIZONTAL SOFFIT standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE SUBSTRATE IS OPTIONAL UNLESS REQUIRED AS and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH PART OF A CONTINUOUS AIR BARRIER SYSTEM. and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. ENSURE BOTTOM EDGE OF DRAINAGE
STRIP IS LEFT FREE TO DRAIN.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.25
DRYVIT GENESIS® ADHESIVE
APPLIED IN VERTICAL NOTCHED
TROWEL CONFIGURATION TO
BACK OF INSULATION BOARD

FRAMING

APPROVED SUBSTRATE BY OTHERS


DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
OUTSULATION X
SYSTEM

APPROVED DOW® XNERGY™


RIGID INSULATION BOARD
SLIP TYPE DRYVIT APPROVED WASHER
CONNECTION WITH CORROSION RESISTANT
(SEE NOTE 6) FASTENER

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
IN DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

3/4" (19 MM) MIN.

SLOPE SURFACE
OUTSIDE OF SEALANT 1:5
MIN. OUTWARD TO DRAIN

CLOSED CELL BACKER DRYVIT COMPATIBLE


ROD, BY OTHERS SEALANT WITH CLOSED
(SEE NOTE 2) CELL BACKER ROD, BY
OTHERS (SEE NOTE 5)
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT

DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS OF


DRYVIT AQUAFLASH® DRYVIT AP ADHESIVE ABOVE THE FLOOR LINE LEAVING
SYSTEM (SEE NOTE 4) BOTTOM FREE TO FLOAT OVER SHEATHING JOINT

DRYVIT DETAIL MESH® DRYVIT STANDARD PLUS


WRAPPED TO BACKSIDE REINFORCING MESH EMBEDDED IN
OF INSULATION BOARD DRYVIT GENESIS BASE COAT
MIN. 2-1/2" (64 MM)

Outsulation® X System

Horizontal Joint at Floor Line without Weeps
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND FLOOR 4. DRYVIT FLASHING TAPE SURFACE Dryvit products is the responsibility of the project's design
APPLICATIONS AND ALL FACADES EXPOSED TO CONDITIONER™ AND DRYVIT FLASHING TAPE™ professional. All systems must comply with local building codes and
ABNORMAL STRESS, HIGH TRAFFIC, OR MAY BE USED IN LIEU OF DRYVIT AQUAFLASH standards. This detail is for general information and guidance only
DELIBERATE IMPACT HAVE THE BASE COAT SYSTEM OVER PREPARED JOINT. and Dryvit specifically disclaims any liability for the use of this detail
REINFORCED WITH PANZER® MESH PRIOR TO and for the architecture, design, engineering or workmanship of any
STANDARD PLUS™ MESH. LOCATION OF HIGH 5. SEALANT SHOULD NOT BE IN DIRECT CONTACT project. The project design professional determines, in its sole
IMPACT ZONES SHOULD BE INDICATED ON WITH ASPHALTIC ADHESIVE ON DRYVIT FLASHING discretion, whether this detail or a functionally equivalent detail is
CONTRACT DRAWINGS. TAPE. COVER DRYVIT FLASHING TAPE LAPS WITH best suited for the project. Use of a functionally equivalent detail does
POLYETHYLENE TAPE OR BACKER ROD. not violate Dryvit's warranty. This detail is subject to change without
2. LOCATE EXTERNAL SEALANT JOINT WITHIN notice. Contact Dryvit to ensure you have the most recent version.
2" (51 MM) OF BREAK IN SHEATHING. 6. FOR STEEL FRAMED CONSTRUCTION:
EXPANSION JOINT IS INTENDED TO
3. EXPANSION JOINT IN THE OUTSULATION X ACCOMMODATE MOVEMENT AT SLIP CONNECTION.
SYSTEM IS NECESSARY WHERE SIGNIFICANT FOR WOOD FRAMED CONSTRUCTION: EXPANSION
DIFFERENTIAL MOVEMENT IS EXPECTED AT JOINT IS INTENDED TO ACCOMMODATE CROSS
FLOOR LINES. GRAIN SHRINKAGE OF FLOOR BEAMS.
© Dryvit Systems, Inc.
Issued: 10/2016
OX 0.0.27
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHED
TROWEL CONFIGURATION APPLIED TO
BACK OF INSULATION BOARD

FRAMING
BY OTHERS
APPROVED
SUBSTRATE
OUTSULATION X
SYSTEM

APPROVED DOW® XNERGY™


RIGID INSULATION BOARD

DRYVIT APPROVED WASHER


WITH CORROSION RESISTANT
FASTENER

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
IN DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

3/4" (19 MM) MIN.

DRYVIT COMPATIBLE SEALANT


WITH CLOSED CELL BACKER
ROD, BY OTHERS (SEE NOTE 3)

DRYVIT DEMANDIT® OR COLOR


PRIME™ ON SURFACES TO
RECEIVE SEALANT

SLOPE SURFACE OUTSIDE OF


SEALANT 1:5 MIN. OUTWARD
TO DRAIN

DRYVIT DRAINAGE STRIP™™


ADHERED WITH DABS OF
DRYVIT AP ADHESIVE ABOVE
THE SUBSTRATE JOINT
LEAVING BOTTOM FREE TO
FLOAT OVER THE JOINT

DRYVIT AQUAFLASH® SYSTEM


(SEE NOTE 2)

DRYVIT BACKSTOP® NT™-TEXTURE


OVER GRID TAPE™

4
Outsulation® X System

Horizontal Joint - Substrate Change
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. SEALANT SHALL NOT BE IN DIRECT Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES CONTACT WITH ASPHALTIC ADHESIVE ON professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH DRYVIT FLASHING TAPE. COVER DRYVIT standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE FLASHING TAPE LAPS WITH POLYETHYLENE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® TAPE OR BACKER ROD. and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD 4. REFER TO DETAIL OX 0.0.26 FOR discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. CONFIGURATION REQUIRING WEEPS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. DRYVIT FLASHING TAPE SURFACE notice. Contact Dryvit to ensure you have the most recent version.
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM OVER PREPARED
JOINT AT CHANGE IN SUBSTRATE.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.29

APPROVED SUBSTRATE

FRAMING DRYVIT AIR/WATER-RESISTIVE


BARRIER COATING EXTENDED
BEHIND FLASHING (SEE NOTE 3)
DRYVIT AQUAFLASH® SYSTEM
(SEE NOTE 2) DRYVIT GENESIS® ADHESIVE
APPLIED IN VERTICAL NOTCHED
TROWEL CONFIGURATION TO
BACK OF INSULATION BOARD

APPROVED DOW® XNERGY™


RIGID INSULATION BOARD

DRYVIT APPROVED WASHER


WITH CORROSION RESISTANT
FASTENER

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS


REINFORCING MESH EMBEDDED
IN DRYVIT GENESIS BASE COAT

DRYVIT FINISH

DRYVIT DETAIL MESH® WRAPPED


TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)

3/4" (19 MM) MIN.

DRYVIT COMPATIBLE SEALANT


WITH CLOSED CELL BACKER ROD
AND WEEP TUBES EVERY
24" (610 MM), BY OTHERS
(SEE NOTE 4)
DRYVIT DEMANDIT® OR COLOR
PRIME™ ON SURFACE(S) TO
RECEIVE SEALANT

DRYVIT DRAINAGE STRIP™


ADHERED WITH DABS OF
DRYVIT AP ADHESIVE
CONTINUOUS FLASHING,
BY OTHERS
CEMENT PLASTER,
BY OTHERS

SEALANT WITH BOND BREAKER,


BY OTHERS

PAPER BACKED EXPANDED METAL LATH


OR OTHER SLIP SHEET, BY OTHERS

Outsulation® X System

Horizontal Termination at Stucco
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. FOR INSTALLATION OF DRYVIT Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES AIR/WATER-RESISTIVE BARRIER professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH COATING BENEATH CLADDINGS OTHER standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THAN DRYVIT EIFS, REFER TO DRYVIT and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH PUBLICATION DS840. and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT 4. SEALANT SHOULD NOT BE IN DIRECT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON CONTACT WITH DRYVIT FLASHING TAPE; best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. STAINING MAY OCCUR. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM.

© Dryvit Systems, Inc.


Issued: 10/2016
OX 0.0.37

FRAMING

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT GENESIS® ADHESIVE APPLIED IN VERTICAL
NOTCHED TROWEL CONFIGURATION TO BACK OF
INSULATION BOARD
APPROVED DOW® XNERGY™
RIGID INSULATION BOARD

DRYVIT APPROVED WASHER WITH


CORROSION RESISTANT FASTENER

DRYVIT GENESIS BASE COAT

DRYVIT STANDARD PLUS REINFORCING MESH


EMBEDDED IN DRYVIT GENESIS BASE COAT

BLOCKING, SECURED TO FRAMING

DRYVIT FINISH

DRYVIT COMPATIBLE SEALANT AND BOND


BREAKER TAPE, BY OTHERS (SEE NOTE 2)
NON-CORROSIVE PIPE SLEEVE, BY
OTHERS, SET IN SEALANT

SIGN FIXTURE, BY OTHERS

NEOPRENE WASHER, BY OTHERS

SCREW/BOLT ATTACHMENT TO BUILDING


FRAMING/BLOCKING, BY OTHERS

1/2" (12.7 MM) MIN.

Outsulation® X System

Sign Attachment
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. PERIMETER OF PIPE SLEEVE IS CAULKED notice. Contact Dryvit to ensure you have the most recent version.
TO PREVENT WATER ENTRY INTO WALL.

© Dryvit Systems, Inc.


Issued: 10/2016
December 2018

AccelerAged™ EIFS grade polystyrene insulation boards.


Polar Industries is a Connecticut manufacturer of white expanded polystyrene (EPS) and grey graphite
polystyrene (GPS) insulation products. Both are available for exterior insulation finish systems (EIFS)
and are sold under our AccelerAged™ and AccelerAged™ GPS trade names.

AccelerAged™ insulation boards are manufactured to ASTM E2430 or proponent specifications under
quality control procedures administered by RADCO Long Beach CA, a third party inspection agency.
See RADCO Listing 1201.

AccelerAged™ GPS insulation boards are manufactured using BASF Neopor® GPS 5300 Plus series
bead and conform to ASTM E2430 or proponent specifications. Quality control auditing is provided by
QAI Burnaby BC. Polar is co-listee on BASF ESR-3463.

The physical properties and R-value performance of AccelerAged™ and AccelerAged™ GPS are
shown on the following pages.

Note: To calculate R-value* performance; multiply R/Inch by board thickness (in inches).
To calculate board thickness (in inches) needed to provide a specified R-value; divide
target R-value by R/Inch.
* For residential applications use R-value measured at 75°F.

Polar Industries Inc.

32 Gramar Avenue
Prospect, CT 06712
800.237.3763
AccelerAged™ EIFS

AccelerAged™ EIFS is dimensionally stable polystyrene cut to exacting standards.


Polystyrene provides exceptional workability and maintains permanent high R-value
performance; an exceptional value.

R-Values Available
Thickness AccelerAged™
EIFS
1” R 3.85
1-1/2” R 5.78
2” R 7.7
3” R 11.55
4” R 15.4
File 1201

Properties ASTM C578 Standard Unit of Measure Acceleraged™ EIFS


Density (Type I) pcf .95/1.14
Flex Strength C203 psi 25-30
Compressive Strength D 1621 psi 10-14
Dimensional Stability Max % change 2
Service Temperature °F 167
Thermal Performance / In.
R Value / k Factor : C 518 25°F 4.35 / .23
R Value / k Factor : 75°F 3.85/ .26
Flame - Spread (class A) E 84 0-25
Smoke Developed 0-450

AccelerAged™ insulation products are


sold exclusively through distributors Caution:
serving professional contractors. All foam plastic insulation will ignite if
exposed to fire of sufficient heat and intensity.
This product should not be exposed to open
flame or other ignition sources. Install in
compliance with applicable building codes.
Helping homeowners turn carbon footprints
32 Gramar Avenue • Prospect, CT 06712 into thumbprints™
800•237•3763 ©2015 Polar Industries
www.polarcentral.com
AccelerAged™ GPS

AccelerAged™ GPS is dimensionally stable polystyrene impregnated with pure


graphite - crystalline carbon. Graphite increases the brilliance within the cell structure
creating surfaces that reflect and absorb radiant energy. The result is higher R-value.

R-Values Available
Thickness AccelerAged™ AccelerAged™
GPS C10 GPS C20
1-1/16” R5 R5
1-1/2” R7 R7
2-1/8” R 10 R 10
3-3/16” R 15 R 15

Properties ASTM C578 Unit of Measure AccelerAged™ AccelerAged™


Test GPS C10 GPS C20
Density D1622 pcf 1.05/1.14 1.45/1.55
(Type I) (Type II)
Flex Strength C203 psi 35-30 40-50
Compressive Strength D1621 psi 10-14 20-25
Dimensional Stability Max % change 2 2
Service Temperature °F 167 167
Thermal Performance / In.
R Value / k Factor : C518 25°F 5.1 / .20 5.1 / .20
R Value / k Factor : C518 75°F 4.7/ .21 4.7/ .21
Flame - Spread (class A) E84 0-25 0-25
smoke developed E84 0-450 0-450

AccelerAged™ GPS insulation products


are sold exclusively through distributors Caution:
serving professional contractors. All foam plastic insulation will ignite if
exposed to fire of sufficient heat and intensity.
This product should not be exposed to open
flame or other ignition sources. Install in
compliance with applicable building codes.