Outsulation X System
Installation Details
TABLE OF CONTENTS
DETAIL DETAIL
OUTSULATION X SYSTEM CUTAWAY OX 0.0.01 HORIZONTAL TERMINATION AT OX 0.0.29
AWRB APPLICATION AND OX 0.0.02 STUCCO
FASTENING PATTERN HORIZONTAL TERMINATION AT OX 0.0.30
OPENING PREPARATION- OX 0.0.03 LAPPED SIDING
AQUAFLASH® SYSTEM OPTION VERTICAL EIFS EXPANSION JOINT OX 0.0.31
OPENING PREPARATION- OX 0.0.04 THROUGH-WALL EXPANSION JOINT OX 0.0.32
BACKSTOP® NT OPTION VERTICAL EXPANSION JOINT - OX 0.0.33
OPENING FLASHING INTEGRATION OX 0.0.05 FLUSH AND RECESSED OPTIONS
INSIDE/OUTSIDE CORNERS OX 0.0.06 VERTICAL EXPANSION JOINT - OX 0.0.34
OUTSIDE CORNER - HIGH IMPACT OX 0.0.07 DOUBLE SEAL OPTION
TERMINATION AT GRADE OX 0.0.08 VERTICAL TERMINATION OX 0.0.35
TERMINATION AT CONCRETE CURB OX 0.0.09 AT STONE VENEER
TERMINATION AT ADA COMPLIANT OX 0.0.10 PENETRATIONS OX 0.0.36
SIDEWALK SIGN ATTACHMENT OX 0.0.37
INSULATION PREPARATION AT OX 0.0.11 AESTHETIC REVEALS OX 0.0.38
WALL PENETRATIONS EPS SHAPES OX 0.0.39
STOREFRONT WINDOW SILL - JAMB OX 0.0.12
FLANGED WINDOW SILL - JAMB OX 0.0.13
STOREFRONT AND FLANGED OX 0.0.14
WINDOW HEAD
TERMINATION AT OX 0.0.15
WOOD FRAMED DECK
TERMINATION AT OX 0.0.16
WATERPROOF DECK NOTE
PREPARATION AT PARAPET/ OX 0.0.17
WALL INTERSECTION DRYVIT MAKES NO REPRESENTATION REGARDING
TERMINATION ATPARAPET - OX 0.0.18 CONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDING
CAP FLASHING CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,
TERMINATION AT ROOF MEMBRANE OX 0.0.19 OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED
TERMINATION AT SLOPED ROOF OX 0.0.20 IN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE
VERTICAL WALL/ SUSPENDED OX 0.0.21 REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE
SOFFIT TRANSITION DESIGNED, DETAILED, AND ENGINEERED BY
TRANSITION AT SOFFIT/ OX 0.0.22 REPRESENTATIVES OF THE ARCHITECT, OWNER, OR
FASCIA INTERSECTION CONTRACTOR TO BE IN CONFORMANCE WITH MODEL
FASCIA/ UNINSULATED SOFFIT OX 0.0.23 CODES, ARCHITECTURAL, AND ENGINEERING
TRANSITION REQUIREMENTS PERTAINING TO SPECIFIC BUILDING
TERMINATION AT OX 0.0.24 PROJECTS.
UNINSULATED SOFFIT VENT
HORIZONTAL JOINT AT FLOOR LINE OX 0.0.25 DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,
WITHOUT WEEPS AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR
HORIZONTAL JOINT AT FLOOR LINE OX 0.0.26 WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS
WITH WEEPS OR PRODUCTS.
HORIZONTAL JOINT - OX 0.0.27
SUBSTRATE CHANGE THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THE
HORIZONTAL TERMINATION OX 0.0.28 OUTSULATION X LIMITED COMMERCIAL WARRANTY.
AT STONE VENEER CONTACT DRYVIT FOR A FULL AND COMPLETE COPY OF
THE WARRANTY.
Outsulation® X System
™
FRAMING
DRYVIT FINISH
FRAMING
DRYVIT FINISH
Outsulation® X System
™
Outsulation X System Cutaway
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH discretion, whether this detail or a functionally equivalent detail is
IMPACT ZONES SHOULD BE INDICATED best suited for the project. Use of a functionally equivalent detail does
ON CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. INSTALL FASTENERS IMMEDIATELY
FOLLOWING BOARD PLACEMENT, WHILE
ADHESIVE IS STILL WET.
APPROVED SUBSTRATE
Outsulation® X System
™
AWRB Application and Fastening Pattern
NOTE: The architecture, engineering, and design of the project using the
1. ALTERNATE FASTENERS AT EACH STUD. Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
2. STAGGER VERTICAL JOINTS AT ALL INSIDE AND OUTSIDE standards. This detail is for general information and guidance only
CORNERS. and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
3. INSTALL INSULATION BOARD IN RUNNING BOND PATTERN. project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
4. TIGHTLY BUTT ALL INSULATION BOARDS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
5. INSTALL THREE FASTENERS PER 2 FT (610 MM) BY 4 FT (1219 MM) notice. Contact Dryvit to ensure you have the most recent version.
INSULATION BOARD IMMEDIATELY FOLLOWING BOARD
PLACEMENT WHILE ADHESIVE IS STILL WET.
STEP #1 STEP #2
STEP #3 STEP #4
Outsulation® X System
™ Opening Preparation -
AquaFlash® System5 Option
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT AQUAFLASH SHALL EXTEND TO 4. INSTALL WINDOW UNIT AND ASSOCIATED Dryvit products is the responsibility of the project's design
INTERIOR FACE OF OPENING. FLASHINGS PER MANUFACTURER'S professional. All systems must comply with local building codes and
RECOMMENDATIONS, CODE REQUIREMENTS AND standards. This detail is for general information and guidance only
2. REFER TO HEAD, SILL AND JAMB DETAILS PROJECT DOCUMENTS. and Dryvit specifically disclaims any liability for the use of this detail
FOR FLASHING INTEGRATION. and for the architecture, design, engineering or workmanship of any
5. AQUAFLASH SYSTEM CONSISTS OF AQUAFLASH project. The project design professional determines, in its sole
3. DRYVIT FLASHING TAPE SURFACE MESH AND AQUAFLASH LIQUID. discretion, whether this detail or a functionally equivalent detail is
CONDITIONER™ AND DRYVIT FLASHING TAPE™ best suited for the project. Use of a functionally equivalent detail does
MAY BE USED IN LIEU OF DRYVIT 6. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER not violate Dryvit's warranty. This detail is subject to change without
AQUAFLASH SYSTEM. DETAILS, REFER TO DRYVIT PUBLICATION DS840. notice. Contact Dryvit to ensure you have the most recent version.
STEP #1
STEP #2 STEP #3
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT GENESIS ADHESIVE APPLIED IN VERTICAL
NOTCHED TROWEL CONFIGURATION TO BACK OF
INSULATION BOARD
APPROVED DOW XNERGY RIGID
INSULATION BOARD
DRYVIT BACKSTOP NT-TEXTURE
OVER DRYVIT GRID TAPE
DRYVIT STANDARD PLUS REINFORCING MESH
EMBEDDED IN DRYVIT GENESIS BASE COAT
DRYVIT FINISH
Outsulation® X System
™
Inside/Outside Corners
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 4. INSULATION BOARD EDGES SHALL BE Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES OFFSET AT INSIDE AND OUTSIDE CORNERS. professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. DOUBLE WRAP OUTSIDE CORNERS WITH notice. Contact Dryvit to ensure you have the most recent version.
REINFORCING MESH OR USE CORNER MESH.
APPROVED SUBSTRATE
DRYVIT APPROVED WASHER WITH
CORROSION RESISTANT FASTENER
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT PANZER®
REINFORCING MESH
DRYVIT FINISH
8" 8"
(203 MM) (203 MM)
MIN. MIN.
Outsulation® X System
™
Outside Corner - High Impact
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. INSULATION BOARD EDGES SHALL BE
OFFSET.
APPROVED SUBSTRATE
2'-0"
(610 MM) MAX.
DRYVIT FINISH
(SEE NOTE 2)
DRYVIT GENESIS BASE COAT
DRYVIT STANDARD PLUS REINFORCING MESH
EMBEDDED IN DRYVIT GENESIS BASE COAT
APPROVED DOW® XNERGY™
8" RIGID INSULATION BOARD
(203 MM) DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 4)
MIN.
DRYVIT DETAIL MESH® WRAPPED
TO BACKSIDE OF INSULATION BOARD
MIN. 2-1/2" (64 MM)
DRYVIT BACKSTOP® NT™-TEXTURE
OVER DRYVIT GRID TAPE™
Outsulation® X System
™
Termination At Grade
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. ENSURE BOTTOM EDGE OF DRAINAGE Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES STRIP IS LEFT FREE TO DRAIN. professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE 4. DRYVIT FLASHING TAPE SURFACE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH CONDITIONER™ AND DRYVIT FLASHING and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD TAPE™ MAY BE USED IN LIEU OF DRYVIT project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH AQUAFLASH SYSTEM. discretion, whether this detail or a functionally equivalent detail is
IMPACT ZONES SHOULD BE INDICATED best suited for the project. Use of a functionally equivalent detail does
ON CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. EXPANSION JOINT IS REQUIRED ALONG
TOP OF FOUNDATION IF 2'-0" (610 MM)
DIMENSION IS EXCEEDED.
DRYVIT APPROVED
WASHER WITH
CORROSION RESISTANT
FASTENER
DRYVIT GENESIS
BASE COAT
DRYVIT STANDARD
PLUS REINFORCING
MESH EMBEDDED IN
DRYVIT GENESIS BASE
COAT
DRYVIT FINISH
3/4"
(19 MM) MIN.
(SEE NOTE 4)
Outsulation® X System
™
Termination At Concrete Curb
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND FLOOR 4. TO PREVENT DEBRIS ACCUMULATION IT IS Dryvit products is the responsibility of the project's design
APPLICATIONS AND ALL FACADES EXPOSED TO RECOMMENDED TO TERMINATE SYSTEM professional. All systems must comply with local building codes and
ABNORMAL STRESS, HIGH TRAFFIC, OR 2" (51 MM) ABOVE SIDEWALK. standards. This detail is for general information and guidance only
DELIBERATE IMPACT HAVE THE BASE COAT and Dryvit specifically disclaims any liability for the use of this detail
REINFORCED WITH PANZER® MESH PRIOR TO and for the architecture, design, engineering or workmanship of any
STANDARD PLUS™ MESH. LOCATION OF HIGH project. The project design professional determines, in its sole
IMPACT ZONES SHOULD BE INDICATED ON discretion, whether this detail or a functionally equivalent detail is
CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. ENSURE BOTTOM EDGE OF DRAINAGE STRIP IS notice. Contact Dryvit to ensure you have the most recent version.
LEFT FREE TO DRAIN.
OUTSULATION X
SYSTEM
APPROVED SUBSTRATE
APPROVED DOW®
XNERGY™ RIGID
INSULATION BOARD
DRYVIT GENESIS
BASE COAT
DRYVIT STANDARD
PLUS REINFORCING
MESH EMBEDDED IN
DRYVIT GENESIS BASE
COAT
DRYVIT FINISH
Outsulation® X System
™
Termination At ADA Compliant Sidewalk
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND FLOOR 4. ENSURE BOTTOM EDGE OF DRAINAGE Dryvit products is the responsibility of the project's design
APPLICATIONS AND ALL FACADES EXPOSED TO STRIP IS LEFT FREE TO DRAIN. professional. All systems must comply with local building codes and
ABNORMAL STRESS, HIGH TRAFFIC, OR standards. This detail is for general information and guidance only
DELIBERATE IMPACT HAVE THE BASE COAT 5. TO PREVENT DEBRIS ACCUMULATION IT IS and Dryvit specifically disclaims any liability for the use of this detail
REINFORCED WITH PANZER® MESH PRIOR TO RECOMMENDED TO TERMINATE SYSTEM and for the architecture, design, engineering or workmanship of any
STANDARD PLUS™ MESH. LOCATION OF HIGH 2" (51 MM) ABOVE SIDEWALK. project. The project design professional determines, in its sole
IMPACT ZONES SHOULD BE INDICATED ON discretion, whether this detail or a functionally equivalent detail is
CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. USE OF THIS DETAIL IS LIMITED TO notice. Contact Dryvit to ensure you have the most recent version.
SLAB-ON-GRADE APPLICATIONS.
Outsulation® X System
™
Insulation Preparation At Wall Penetrations
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. APPLY A PIECE OF 9 1/2" (241 MM) X 12" (305 MM) Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES DETAIL REINFORCING MESH DIAGONALLY AT professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH EACH CORNER. standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. LOCATE INSULATION BOARDS SUCH
THAT BOARD EDGES DO NOT ALIGN WITH
CORNERS OF PENETRATION.
DRYVIT COMPATIBLE
SEALANT, BY OTHERS
APPROVED DOW®
XNERGY™ RIGID
INSULATION BOARD DRYVIT APPROVED WASHER WITH
CORROSION RESISTANT FASTENER
EPS SHAPE (OPTIONAL)
ADHERED USING DRYVIT
GENESIS ADHESIVE
2 1/2"
DRYVIT GENESIS (64 MM) MIN.
BASE COAT
APPROVED SUBSTRATE
DRYVIT
AIR/WATER-RESISTIVE DRYVIT GENESIS ADHESIVE 1/2" (12.7 MM)
BARRIER COATING APPLIED IN VERTICAL NOTCHED
TROWEL CONFIGURATION TO
BACK OF INSULATION BOARD
SILL PAN FLASHING
DETAIL
Outsulation® X System
™
Storefront Window Sill - Jamb
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. DRYVIT BACKSTOP® NT™-TEXTURE OVER GRID TAPE™ Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES IS AN ALTERNATIVE OPTION AT JAMB AND HEAD professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH CONDITION PER DETAIL OX 0.0.04 standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® 4. SEALANT SHOULD NOT BE IN DIRECT CONTACT WITH and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. DRYVIT FLASHING TAPE; STAINING MAY OCCUR. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. 5. SILL PAN FLASHING MUST HAVE WATER TIGHT SEAMS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. DRYVIT FLASHING TAPE SURFACE 6. EDGE WRAPPING METHOD IS ACCEPTABLE AT SILL AND notice. Contact Dryvit to ensure you have the most recent version.
CONDITIONER™ AND DRYVIT FLASHING JAMB IN LIEU OF BACK WRAPPING. DRYVIT REINFORCING
TAPE™ MAY BE USED IN LIEU OF DRYVIT MESH MUST BE FULLY EMBEDDED IN DRYVIT BASE COAT
AQUAFLASH SYSTEM. AT INSULATION BOARD EDGE AND MUST EXTEND ONTO
SUBSTRATE 2-1/2" (64 MM) MIN.
FRAMING
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT FINISH
2"
(51 MM)
MIN.
Outsulation® X System
™
Termination at Waterproof Deck
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. ENSURE BOTTOM EDGE OF DRAINAGE
STRIP IS LEFT FREE TO DRAIN.
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 1)
8"
(203 MM)
MIN.
6"
(152 MM) 6"
(152 MM)
STEP #1 STEP #2
DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 1)
STEP #3
DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 2)
FRAMING, 2 1/2"
BY OTHERS (64 MM) MIN.
DRYVIT COMPATIBLE
SEALANT, BY OTHERS
ROOF
ASSEMBLY DRYVIT DETAIL MESH® WRAPPED
TO BACKSIDE OF INSULATION
BOARD MIN. 2-1/2" (64 MM)
(SEE NOTE 3)
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
APPROVED SUBSTRATE
8"
(203 MM)
MIN.
ROOF ASSEMBLY,
BY OTHERS
Outsulation® X System
™
Termination At Roof Membrane
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. SEALANT SHOULD NOT BE IN DIRECT Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES CONTACT WITH DRYVIT FLASHING TAPE; professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH STAINING MAY OCCUR. standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® 4. EDGE WRAPPING METHOD IS and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. ACCEPTABLE IN LIEU OF BACK WRAPPING. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD DRYVIT REINFORCING MESH MUST BE discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. FULLY EMBEDDED IN DRYVIT BASE COAT best suited for the project. Use of a functionally equivalent detail does
AT INSULATION BOARD EDGE AND not violate Dryvit's warranty. This detail is subject to change without
2. DRYVIT FLASHING TAPE SURFACE EXTEND ONTO SUBSTRATE 2-1/2" (64 MM) notice. Contact Dryvit to ensure you have the most recent version.
CONDITIONER™ AND DRYVIT FLASHING MIN.
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM.
FRAMING
APPROVED SUBSTRATE
DRYVIT FINISH
DRYVIT FINISH
FRAMING
DRYVIT FINISH
SLOPE SURFACE
OUTSIDE OF SEALANT 1:5
MIN. OUTWARD TO DRAIN
Outsulation® X System
™
Horizontal Joint at Floor Line without Weeps
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND FLOOR 4. DRYVIT FLASHING TAPE SURFACE Dryvit products is the responsibility of the project's design
APPLICATIONS AND ALL FACADES EXPOSED TO CONDITIONER™ AND DRYVIT FLASHING TAPE™ professional. All systems must comply with local building codes and
ABNORMAL STRESS, HIGH TRAFFIC, OR MAY BE USED IN LIEU OF DRYVIT AQUAFLASH standards. This detail is for general information and guidance only
DELIBERATE IMPACT HAVE THE BASE COAT SYSTEM OVER PREPARED JOINT. and Dryvit specifically disclaims any liability for the use of this detail
REINFORCED WITH PANZER® MESH PRIOR TO and for the architecture, design, engineering or workmanship of any
STANDARD PLUS™ MESH. LOCATION OF HIGH 5. SEALANT SHOULD NOT BE IN DIRECT CONTACT project. The project design professional determines, in its sole
IMPACT ZONES SHOULD BE INDICATED ON WITH ASPHALTIC ADHESIVE ON DRYVIT FLASHING discretion, whether this detail or a functionally equivalent detail is
CONTRACT DRAWINGS. TAPE. COVER DRYVIT FLASHING TAPE LAPS WITH best suited for the project. Use of a functionally equivalent detail does
POLYETHYLENE TAPE OR BACKER ROD. not violate Dryvit's warranty. This detail is subject to change without
2. LOCATE EXTERNAL SEALANT JOINT WITHIN notice. Contact Dryvit to ensure you have the most recent version.
2" (51 MM) OF BREAK IN SHEATHING. 6. FOR STEEL FRAMED CONSTRUCTION:
EXPANSION JOINT IS INTENDED TO
3. EXPANSION JOINT IN THE OUTSULATION X ACCOMMODATE MOVEMENT AT SLIP CONNECTION.
SYSTEM IS NECESSARY WHERE SIGNIFICANT FOR WOOD FRAMED CONSTRUCTION: EXPANSION
DIFFERENTIAL MOVEMENT IS EXPECTED AT JOINT IS INTENDED TO ACCOMMODATE CROSS
FLOOR LINES. GRAIN SHRINKAGE OF FLOOR BEAMS.
© Dryvit Systems, Inc.
Issued: 10/2016
OX 0.0.27
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHED
TROWEL CONFIGURATION APPLIED TO
BACK OF INSULATION BOARD
FRAMING
BY OTHERS
APPROVED
SUBSTRATE
OUTSULATION X
SYSTEM
DRYVIT FINISH
4
Outsulation® X System
™
Horizontal Joint - Substrate Change
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. SEALANT SHALL NOT BE IN DIRECT Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES CONTACT WITH ASPHALTIC ADHESIVE ON professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH DRYVIT FLASHING TAPE. COVER DRYVIT standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE FLASHING TAPE LAPS WITH POLYETHYLENE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® TAPE OR BACKER ROD. and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD 4. REFER TO DETAIL OX 0.0.26 FOR discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. CONFIGURATION REQUIRING WEEPS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. DRYVIT FLASHING TAPE SURFACE notice. Contact Dryvit to ensure you have the most recent version.
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM OVER PREPARED
JOINT AT CHANGE IN SUBSTRATE.
APPROVED SUBSTRATE
DRYVIT FINISH
Outsulation® X System
™
Horizontal Termination at Stucco
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND 3. FOR INSTALLATION OF DRYVIT Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES AIR/WATER-RESISTIVE BARRIER professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH COATING BENEATH CLADDINGS OTHER standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THAN DRYVIT EIFS, REFER TO DRYVIT and Dryvit specifically disclaims any liability for the use of this detail
THE BASE COAT REINFORCED WITH PUBLICATION DS840. and for the architecture, design, engineering or workmanship of any
PANZER® MESH PRIOR TO STANDARD project. The project design professional determines, in its sole
PLUS™ MESH. LOCATION OF HIGH IMPACT 4. SEALANT SHOULD NOT BE IN DIRECT discretion, whether this detail or a functionally equivalent detail is
ZONES SHOULD BE INDICATED ON CONTACT WITH DRYVIT FLASHING TAPE; best suited for the project. Use of a functionally equivalent detail does
CONTRACT DRAWINGS. STAINING MAY OCCUR. not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
2. DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM.
FRAMING
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT GENESIS® ADHESIVE APPLIED IN VERTICAL
NOTCHED TROWEL CONFIGURATION TO BACK OF
INSULATION BOARD
APPROVED DOW® XNERGY™
RIGID INSULATION BOARD
DRYVIT FINISH
Outsulation® X System
™
Sign Attachment
NOTE: The architecture, engineering, and design of the project using the
1. DRYVIT RECOMMENDS THAT GROUND Dryvit products is the responsibility of the project's design
FLOOR APPLICATIONS AND ALL FACADES professional. All systems must comply with local building codes and
EXPOSED TO ABNORMAL STRESS, HIGH standards. This detail is for general information and guidance only
TRAFFIC, OR DELIBERATE IMPACT HAVE THE and Dryvit specifically disclaims any liability for the use of this detail
BASE COAT REINFORCED WITH PANZER® and for the architecture, design, engineering or workmanship of any
MESH PRIOR TO STANDARD PLUS™ MESH. project. The project design professional determines, in its sole
LOCATION OF HIGH IMPACT ZONES SHOULD discretion, whether this detail or a functionally equivalent detail is
BE INDICATED ON CONTRACT DRAWINGS. best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
2. PERIMETER OF PIPE SLEEVE IS CAULKED notice. Contact Dryvit to ensure you have the most recent version.
TO PREVENT WATER ENTRY INTO WALL.
AccelerAged™ insulation boards are manufactured to ASTM E2430 or proponent specifications under
quality control procedures administered by RADCO Long Beach CA, a third party inspection agency.
See RADCO Listing 1201.
AccelerAged™ GPS insulation boards are manufactured using BASF Neopor® GPS 5300 Plus series
bead and conform to ASTM E2430 or proponent specifications. Quality control auditing is provided by
QAI Burnaby BC. Polar is co-listee on BASF ESR-3463.
The physical properties and R-value performance of AccelerAged™ and AccelerAged™ GPS are
shown on the following pages.
Note: To calculate R-value* performance; multiply R/Inch by board thickness (in inches).
To calculate board thickness (in inches) needed to provide a specified R-value; divide
target R-value by R/Inch.
* For residential applications use R-value measured at 75°F.
32 Gramar Avenue
Prospect, CT 06712
800.237.3763
AccelerAged™ EIFS
R-Values Available
Thickness AccelerAged™
EIFS
1” R 3.85
1-1/2” R 5.78
2” R 7.7
3” R 11.55
4” R 15.4
File 1201
R-Values Available
Thickness AccelerAged™ AccelerAged™
GPS C10 GPS C20
1-1/16” R5 R5
1-1/2” R7 R7
2-1/8” R 10 R 10
3-3/16” R 15 R 15