WINTER max.e3-pool-09
GENERAL DATA Supply Side Exhaust Side
Airflow 9000 m³/h 9000 m³/h
Dehumidification rate 57.2 l/h
Total Heating Capacity 96.3 kW
Specific Fan Power(SFP)-total for unit 1788 W/m³/s
System COP 6.52
Total power input 14.77 kW
Refrigerant R407C
Unit power supply 400 V/3 ph/50 Hz
Full load Current 43.80 A
Sea level 0 m
The system's Specific Fan Power (SFPe) calculation is based on clean filter and acc. to EN13779
DIMENSIONS AND WEIGHT
Width 1845 mm
Height 2045 mm
Lenght 3940 mm
Weight 1545 kg
PRESSURE DROP
Filter (F5 Pleated fiter cells)
Initial 31 Pa
Final 250 Pa
Supply Side Exhaust Side
Working point pressure drop 31 Pa 31 Pa
Mixing Box 62 Pa 62 Pa
Plate Heat Exchanger 160 Pa 167 Pa
Evaporator 144 Pa
Condenser 30 Pa
Heating coil 25 Pa

Bypass Damper 10 Pa
Total Internal Pressure Drops 318 Pa 404 Pa
External Static Pressure (ESP) 250 Pa 250 Pa
THE MIXING BOX
Incoming Temperature -18 °C 15.1 °C
Incoming Relative Humidity 80.0 % 100.0 %
Fresh air percentage 30.0 %
Outgoing Temperature 7.9 °C 15.1 °C
Outgoing Relative Humidity 96.7 % 100.0 %
PLATE HEAT EXCHANGER
Incoming Temperature 7.9 °C
Incoming Relative Humidity 97 %
Incoming Temperature 30 °C
Incoming Relative Humidity 60 %
Recovered Heat 43.7 kW
Temperature Efficiency 66 %
Outgoing Temperature 22.4 °C
Outgoing Relative Humidity 38 %
Outgoing Temperature 20.1 °C
Outgoing Relative Humidity 97 %
Condensation Rate 0 l/h 18.5 l/h
DV_Select 3.2 Page: 1 / 3
Date :
Reference:
Issued by :

Temperature to frost _ °C

EVAPORATOR
Incoming Temperature 20.1 °C Condensation Rate 38.7 l/h
Incoming Relative Humidity 97 %
Outgoing Temperature 15.1 °C
Outgoing Relative Humidity 100 %
Cooling capacity 42.3 kW
CONDENSER
Incoming Temperature 22.4 °C
Incoming Relative Humidity 38 %
Outgoing Temperature 39.8 °C
Outgoing Relative Humidity 14 %
Condensing capacity 52.6 kW
COMPRESSORS
Compressors COP 5.100
Quantity 2 n°
Operating Current 2 x 9.00 A
Full load Current 2 x 14.50 A
Locked rotor Current 2 x 66.00 A
Power supply 400 V/3 ph/50 Hz
Power input 2 x 5.15 kW
3 WAY VALVE
STATUS Close
FAN Supply Side Exhaust Side
Type: Plug Fan Plug Fan
Total Pressure 568 Pa 654 Pa
Fan speed 1660 rpm 1723 rpm
Fan Efficiency 67.7 % 69.0 %
(Static Eff. Impeller incl. motor and controller)
Power absorbed at fan shaft 2.099 kW 2.371 kW
Motor Duty 4.6 kW 4.6 kW
Motor Efficiency ErP conformity- 2015/EC controller integrated
Full load Current 7,4-6 A 7,4-6 A
Power supply 400 V/3 ph/50 Hz 400 V/3 ph/50 Hz
K-factor for air flow measuring 308 308

DV_Select 3.2 Page: 2 / 3


Date :
Reference:
Issued by :

SOUND PRESSURE LEVEL (*)


Octavian centre frequency (Hz)
63 125 250 500 1000 2000 4000 8000
70.0 72.0 72.5 70.0 68.0 64.0 63.0 62.0
measured at 1m. Distance from the unit in free field(without ducts)
(*) Sound Pressure Level-dB(A),

SOUND POWER LEVEL dB(A)


63 125 250 500 1000 2000 4000 8000 SUM
57.5 67.0 66.5 68.0 64.0 62.5 57.5 52.0 73.5 Supply Air Side - Supply
52.0 60.0 62.5 62.0 60.0 53.0 46.0 39.0 67.5 Supply Air Side - Fresh Air
47.0 55.5 50.5 59.0 60.0 57.0 55.5 49.0 65.0 Extract Air Side - Exhaust
44.0 53.0 56.5 63.0 59.0 54.0 47.0 40.0 66.0 Extract Air Side - Extract
70.0 72.0 71.0 67.0 63.0 60.0 52.0 47.0 76.5 Extract Air Side - Surroundings (**)
Sound Pressure Level is measured in acc. to ISO 5136-2003(with ducts)
(**) Surroundings (by ISO 3744: 2006), measured at max.airflow of 9000 m³/h

DV_Select 3.2 Page: 3 / 3


Date :
Reference:
Issued by :

WINTER max.e3-pool-09

0% 10% 20% 30%


44.4 .93
.90
41.2 C1 40%
38
50%
34.8
.88
60%
31.6 A2 70%
28.4
.85 80%
90%
25.2 100%
B1
22 B2 16
T[°C] .83
18.8
15.6
C2
12.4 11
.80
9.2 A1 9
6 7
2.8
.78 5
-.4
3
-3.6
1
-6.8.75
-10
0 1.6 3.2 4.8 6.4 8 9.6 11.2 12.8 14.4 16 17.6
x[g/Kg]
Supply Side Exhaust Side
A1 = 7.9°C / 96.7% A2 = 30°C / 60%
B1 = 22.4°C / 37.6% B2 = 20.1°C / 96.9%
C1 = 39.8°C / 13.9% C2 = 15.1°C / 100%