50% (2) 50% found this document useful (2 votes) 4K views 38 pages Ieee 575
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here .
Available Formats
Download as PDF or read online on Scribd
Go to previous items Go to next items
Introduction and Scope: Introduces the purpose and objectives of the standard, providing an overview of the guidelines for sheath-bonding methods. References: Lists the documents and standards referenced throughout the guide, offering context and substantiation. Recent Developments: Discusses advancements related to sheath-bonding and voltage calculations, reflecting technological progress. Guidelines Summary: Summarizes the key guidelines, highlighting the essential safety protocols and practices for effective application. Bonding Methods: Describes different methods used for bonding cable sheaths, discussing both traditional and modern techniques. Grounding: Presents grounding procedures and techniques linked to sheath-bonding, ensuring electrical safety. Bibliography: A list of works cited in the document providing a foundation for further research and cross-reference. Effects on Parallel Telephone and Signal Cables: Analyzes the impacts of sheath-bonding on nearby telephone and signal cables, proposing mitigation strategies. Appendices: Includes additional detailed discussions, calculations, and specific analyses supplementary to the main text. IEEE Guide for the Application of
Sheath-Bonding Methods for
Single-Conductor Cables and the Calculation of
Induced Voltages and Currents in Cable Sheaths
ANSI/IEEE Std 575-1988
4
QD rentaney To rots of Eee and teens Eons, In 46 Eat 470 Suan, New York,NY 10017, USA
‘Aahorceé Wensec use neo, UNVERSITE PAIL SABATIER TOULOUSE 3. Deureased on November 25,2010 st 094040 UTC tom IEEE Xplore Reston ary‘dno cree se et URBVERSITE PAUL OABATEER TOULOUSE 3, Dowland on Novem 252010 t 024040 UIC fem EEE Xe, Restos 2ANSI/IBEE
‘Std 676-1988
An American National Standard
IEEE Guide for the Application of
Sheath-Bonding Methods for
Single-Conductor Cables and the Calculation of
Induced Voltages and Currents in Cable Sheaths
Sponsor
Ingulated Conductors Committee of
TERE Power Engineering Society
Approved March 13, 1088
IEEE Standards Board
Approved August 7, 1086
American National Standards Institute
© Copprigh 1387 by
‘The Institute of Electrical and Electrontes Engineers, Ine
‘345 Enst 47th Street, New York, NY 10017, USA
‘No part of ths plication may be reprtuced in ang form,
Tivan lcironte retrieval yt or other
teu the prior writan person ofthe pubter
‘Autores Nese unas o, UNIVERGITE PAUL SABKTICR TOULOUSE 3. Domioadd on November 28,2010! 094040 UTC fom IEEE Xplore. Restcions apymittees of the IEEE Societies and the Standards Coordinating Commit-
tees of the IRFE Standards Board. Members of the committees serve
voliitarily and without compensation, They are not necessarily mem-
bore of the Ineitule. The standards developed within IBEE represent
‘8 consensus of the broed expertise on the subject within the Institute
‘as well as Uhove activities outside of IEBE which have expressed an in-
terest in participating in the development of the standard
Use of an TEBE Standard is wholly voluntary, The existence of an
TERE Standard does not imply that there are no other ways to pro-
‘duce, test, measure, purchase, market, or provide other goods and ser.
vices related to the scope of the IBEE Standard. Furthermore, the view-
point expressed at the time a standard is approved and issued is subject
to change brought about Unrough developments in the state of the aL
and comments received from usors of the standard. Kvery IEEE §
dard is subjected to review at least once every five years for revision
OF reaffirmation. When a document is more than five yeats old, and has
not heen reaffirmed, It is reasonable to conclude that ils contents,
although sUill of some value, do not wholly réflect the present slate of
the art, Usote are eautioned lo check to dotermine that they have the
latest edition of any IEEE Standard,
‘Comments for revision of JEBE Standards are welcome from any
Interested party, regardless of membership affiliation with IBEB. Sus-
gestions for changes in documents should be in the form of a proposed
change of text, together with appropriate supporting comments,
Tntexpretations: Occasionally questions may atise regarding the mean-
ing of portions of standards as they relate to specific applications. When
the need for interpretations is brought to the allention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since
TEER Standards represent. a consensus of all concerned interests, it
important to ensure that any interpretation has also received the cor
citrrence of a balance of interests, For this reason IEBE and the mem:
bors of ite technical eommnittecs are not able to provide an instant re-
sponse to interpretation requests excopt in those cases where the matter
‘has previously received formal co
‘Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IBEE Standards Hoar
845 Boot 47th Steeet
New York, NY 10017
USA
“Ausized concod use ted UNVERSITE PAUL SABATIER TOULOUSE 9, Ooynouded on Movember 25,2010 04049 UTC om IEEE Kore, Resons emForeword
(Tis Foreword not a part of ANSI/IETE St 676-1088, IEEE Guile for she Appeation of Sheath Bandog Mths fo
‘Sige-Condvctor Cables snd he Callin of tnduced Wages sn Curents a Cable Sheaha)
‘This gulde has been prepared because of the increasing use of single conductor eable systems brought
‘about by the extended use of solid dielectric metalic sheathed cable and revival of Interest in single-
conductor oi-filed cable
‘The activities of the IEEE working group have closely paralleled those of CIGRE Working Group 21-07.
‘The close cooperation of the CIGRE group and Uve Chatrman, E, If Ball, has heen most welcome. The
TEEE group acknowledges with gratitude the rights to reproduce parts of the text and some of the
drawings from the report produced by the CIGRE group.
‘Over-a period of many years Task Group 3-51 met many times and Inevitably there were many changes
$n both membership and chairmen. The original group who contributed most of the engineering content,
even though many of them have now retired or resigned, are included in the Task Group as follows:
N. R. Spencer, Chairman
i Hateern
8 ions
dat
Pabst?
Rik Posten
Re Wteon
‘yrmer Chena
J.M, Cooney and D. J. Horrocks, although not members ofthe working geoup, have been respos
‘uch of the technical work and editing, and their contelbutions are ulso gratefully acknowledged.
‘The following persons were on the balloting c
the IEEE Standards Board:
Gt Adan Frank Gunn
NAb ET Dhan
fW Aton, Je 1M. aty
WO. Andersen, tr Davenport
Anarene Docnch
UA tnnske Hee Deepen, te
At hee EK Dolly
ay Dortaias C8 Roger
EL tates Je Lic eaterting
ELL Boonat BD ee
‘ou erstan RAL Beker
hares Wes 28 Eneeerd
Raber Dskensy AQ Funct
Hebert 8 lodge i Bigpate
Rete Borowsat Goi Biron
Ken Bow BA Ford
Cv Hou EO, Fonter
HD. Bache 1 Fuster
Pw argemecsire Wes EE Kinsey
ee Bungharce 1D. Pocomer dt Htchens
WA Dara 2M Gardner n't Roos
Mito DCs 4.3.Gonana
Ghats on tired Carla
Jab Carson DiC aa
Temy Ch P divznne Metaroeia
Dente Clarke Ri Ges 8 Lasy
ward J Cottey E cary “age Lawn
Wayne Bote Sm Giter WE Leac
defn Cosy OL oiertson Roca he Louteia
Li Gmper 1 Godashien TW Ling
‘ohn Corte Wrens BM Lowe
Deree A Coteo tartan Gaga
CA Hstat Citas
DiC Heyes Rbatier
‘Authored Icons veined 1 UNIVERSITE PAUL SARATIER TOULOUSE 3, Osun on November 25,2010 094040 UTC hom IEEE Xplor. Resisons apply.NB Miecone Weal Stare
. San Prong Diesen
rune 3 asp Stine
Baul i Dik Sevan
Dadd 7 Poesagen Pur stoctun
dain Gate Aether
‘reg Prey rine A Tet
2° eco aromas
Fe Rotertson Apttermen, Sr
Robert A ond Waar Ave
oho 3. Rueckert ogee 8 Turner
© Sailer eck ak
Dat Satie Fn Ware
2 Sansorea BB Mn Herman, tr
George W Seeder amen ¥ Magner
caren ‘Sven Mort
EL, scon Roverd Maton
Svein olan HW, Wats
ohn FSinsbock he Metron
Dana ser Giscten ite
ober Sites ‘ina Bess
Morey Singer Tevet 0. Wibinscn
Syma # Sat Aviators
sph Snow
iN’ Spacer
Samuel ¢ Tones Naga Sra
white IRafhony 83 tou
‘When the IEEE Standards Board approved this standard on March 13, 1980, it had the following
membership:
Jobn E. May, Chairman Irving Kolodny, Viee Chairman
Sava I. Sherr, Secretary
Jack Kinn eter F eontree
Soseph 1 ooprinzer™ Maria Stour
ward ahve Ghey Worelie
erence V. MeCall Richard Weger
Bonaid F Miche! ido 1, Mens
oreo Mig Halen 1 Wood
Kenneth D. Hendrie Stanley Owens Chane Wyle
Irvin Howell Sohn Rigenat Dovel, poe
Prank L Howe
*Marber cme
‘uthornedicensd use miedo: UNVERSITE PAUL SABATEER TOULOUSE 9 Donloaed on Hoorn 2.2013 84040 UTE ramEEE Xe Resse spContents
srenox
1. Introduetion and Scope.
2 RofEEENCES eee coeecseeceseesneeeeeee
8, Recent Developments: i
Guldolines: Summary ...
Bonding Methods i
S11 Infroduetion 22222
52 General
53 Design...
5A. Single-Point Bonding...
54.1 Sheath Standing Voltages.
B42 Multiple Leogthe......
at
544 Circuit Arrangements
65 Impedanee-Bonding Methods
56 Cross Bonding ..
86.1 Basie Circuit Arrangement
562 Longer Cable Circuits .
5.03 Sectionalized Cross Bonding
5.64 Modified Scetionalized Cross Bonding
580 Continuous Cross Bonding. .
5.86 Mixed Systems .........
567 _Imbalanced Systens «...
57 Sheath Sectionalizing Joints.
5B Choice of Bonding Systems.
58.1 Use of Single Point Nonding
582 Advantages of Cross Bondi
‘Choieo of Cross-Bonded System « 7
Advantages of Sectionalized! Cross Bonding
8S Adrants of Convo Cros nding
6.0 Sheath Standing Voltage
50.1 Single Point Bonding
692 Sectionalized Cross Bonding
583 Continuous Crass Bonding.
594A Double-Gircult Systems
Sheath Voliage Limiters,
61 Inteoduetion aia
62 Nonlinear Resistances ......-
6.3 Nonlinear Resistances in Series with Sark ‘Gap.
G4 Spark Gaps:
66 Selection of Sheath Velie Limiters -
86 Use of Sheath Voltage Limiters ....
66.1 Single-Point Boncled Cables
862 Cross Bonded Systems :
7. Bifec an Paralte! Telephone and Control Cables .
TA Coupling .......2+
72 Shielding ash
7.3 Common-Mode and Metalic Voltages...
8. DAiography .......
‘Aurea censuses UNVERSITE PAUL SABATIER TOULOUSE 3. Doolanded on Novenbr 25,2010 0940 40 UT FomIEEE Xp. Renton eprroures.
Fig 1 Induced Sheath Voltage Gradient for a Conductor Current of 1000 A
Fig 2 Transposition of Parallel Conductor to educe Induced Vollage with Power
Cables in Flat Formation or Trefoil
Fig 9 Single Point Donding Diagrams for Circus Cormprising One Gable Length Only
(@) Bni-Point Bonding (0) Midpoint Bonding .
sens 18
Lig 4 Single-Point Bonding Dingram for Circuit Comprising Three Cable L ti ae
Fig 5 Grose Bonded Cables Without Transposition
Fig 6 Grose Bonded Gables with Transposition ..
Fig 7 Sectionaized Cross-Bonded Cable with Tee Major Sections...
Fig 8 Modifed Sectionalized Cross-Bonding Tyye 1 Without Transposition «
Fig 0 Modified Sectionalized Cross-Bonding Type 1 with Transposition
Fig 10 Modified Sectionalized Cross-Donding Type 2 Without Transpositions .
Fig LI Modified Sectlonalized Gross-Bonding Type 2 with ‘Transpositions
Fig 12 Continuous Cross Donding i
ination of Crose-Donded System with Single Point Bonded Length
Fig 13
arpeannnes
Appendix A Termvology. 25
‘Appendix Discussion of Barly Practices an 26
‘Appendix C Current Practice... ae car
‘Appendix D Calculation of Induced Voliages. _ 228,
‘Appendix ‘Transient Voltages and Voltage Withstand Requiements of Protective Backes
Ta
Power Frequency Sheath Overvoltages .....+..+-
to-Ground Conductor) for Varous Faults
in Single Point Bonded-Cable System (Flat Formation) .. :
Fig h2 Single Major Section of Crose-Donded Cables During Single Phase Fault...
FES Maximum Induced Sheath Voltage Cradionts (Sheath to Sheath) for Various Fauts
in Sectionalized Cross Bonded Cable System (Flat Formation)
au
36
‘puiesce ens se base to: UNVERSIFE PAL. SABATIER TOULOUSE 8, Downed on over 252010 al 84040 UTC tom EEE XHO
Reston aptAn American National Standard
IEEE Guide for the Application of
Sheath-Bonding Methods for
Single-Conductor Cables and the Calculation of
Induced Voltages and Currents in Cable Sheaths
1. Introduetton and Seope
14 Introduction. Since the first installation In
1096, high-pressure, ollfled, pipe-type cable has
become the dominant system in Narth America
for cables operating at 60 kV and above, For the
‘wo decades following 1935, he number of instal
lations of self-contained cables decreased steaily
However, with the development of tow los, high
dietectricastrength insulating materials and im.
proved cable Jackets in the mid-1960's, and their
pplication at subteansmission and transmission
voltages, there hax heen renewed interest in the
use of single-conductor cables and the problems
‘of the induced voltages and currents associated
‘with their use. Many of ese problems (Tor exain-
ple, failure of sheath insulators, failure of cable
Jackets, and sheath corrosion) have been recog
nized since metalic sheathed cables were first
used, and che fundamentals of esteulating sheath
voltages and currents have been defined for many
yeurs. However, the increased ampucity require-
‘ments and short-clreuit capabilities of modern
power systems have accentuated some problems,
while improvements in sheath insulations have
virtually eliminated others.
‘Thus it has become evident that there is anced
for some guidelines whereby the cable engineer
‘ean select the sheath-bonding method that best
fits the needs of a particular installation,
Although the following text was written on
wduced voltages and currents in metal sheaths,
the prineiptes apply equally to concentrle new
tals or cable shld,
1.2 Scope. This guide describes the most com-
mon sheath-bonding systems now in use and the
‘methods of calculating sheath voltages and eur-
rents, particularly as applied to three-phase sys
tems operating at 60 KV and above, with the
neutral grounded directly or through an im-
pedance.
‘The user is cautioned to make sure that a
design does not contravene any local oF national
regulations.
2, References
‘This guide shall be used in conjunction with the
following publications.
[1] Accessories for Spocially Bonded Extruded
Dielectric Transinission Cable Systems. Palo Alto,
CA; Blectrie Power Research Institute, Project RP
7800-1.
[2] A Spark Gap for Protection of Underground
Cable Sheaths at the Terminal. Ontario, Canada:
Ontario Hydro Research Division, Report no
66-242,
{3] BALL, Hand OCCHINI, B. Over-Voltages in
the Sheaths of High-Voltage Cables Due to Special
‘Sheath Donding Connections. IEEE Winter Power
Meeting, 1964,
[a] BALL, BH, OCCHINE, B, and LUONI, 6.
Sheath Overvoltages in High-Voltage Cables
to Special Sheath Bonding Connections. IEEE
‘Transactions (Power Apparatus and Systems),
val PAS.84, 1965, pp 974-088,
‘Authored tons weed UNVERSHTE PAUL SABATIER TOULOUSE 3 Dowlpade on Novenbor 252010 a 084040 UTC kam EEE Xjle. Resins opAtrrzed eens
aes
‘Suan HEATIANONDINO METHODS FOR SINGLE CONDUCTOR CABLES AND THE,
{5] Cable Sheath. Bonding Methods, Ontario,
Canada; Ontario Hydro Research Division, Report
no 55-286.
[6) CARSON, JR. Wave Propagation In Overhead
Wires with Ground Return. Bell System Technical
Journal, vol 8, Oct 1926, pp 639-564.
(7) CLARK, D. J. and SETH, I, P, Cross-Honding
Single-Care Power Cables. Hectrical Review, Feb
10, 1961, pp 237-242.
[8] HAGA, K. and KUSANO, T. Surge
fon the Shesths of Cross Bonded, Three:Phase
Gable Systems, Journal Institute of Electrical
Engineers of Japan, 1958, p 1680.
JO] HALPERIN, I, CLEM, 3, and MILLER, K
W, Transtent Voltages on Bonded Cable Sheaths.
AIEE Transactions, vol 64, 1996, pp 73-82.
(10] HALPERIN, and MILLER, K, W. Reduction
‘of Sheath Losses in Slngle-Conductor Cables,
‘AIEE. Transactions, vol 48, April 1929, pp
590-416,
[1] HASLEE, 8. P, POTTER, M, E, REID, W.
and SECRFST,S R. Shield interrupt Overvoltages
‘on 198 LV Extruded Dielectric Cables. [BBE Trans
actions (Power Apparatus and Systens), vol PAS-
103, Nov 1984, pp 3927-9838.
[12) TASSLER, 8. P, POTTER, MB, W. E. REID,
and SECREST, 8, MOON. Arrester Protection of
Shield Interrupts, on 138 KV Extruded Dielectric
Gables, IEEE Transactions (Power Apparatus
‘and Systems), vol PAS-103, No 1984, pp
3334-34
13] IRC Publication 287 (1982), Cal
the Continuous Current Rating of Cables (100%
Vaail Factor) (Second dition)"
[24] KLEWE, 11 RS. Interference Between Power
Systems and Telecommunieation Lines. London
‘Arnold, 1968.
[16] KUWAHARA, K. and DENCH, ©. Evalu
tion of Power Frequency Sheath Currents and
Voltages in Single Conductor Cables for Various
Sheath-Donding Methods. IRE Transactions
(Power Apparatus and Systoms), Special Sup-
plement, 1963, pp 206-296, Iten 3784,
{16} OGORODNIKOY, ¥. B. Surges on Metallic
Gable Sheaths. Montreal: Canadian Electrical
Association Winter Meeting, Paper, 1964.
7 Tac pblicatons me waa rm he les Department,
American Nitioat Sedan taste, 490 Droadvay, New
Sc, ve.
[17] Protection of Shoath Insutating Joints on
High-Voltage Cable Circuits. Ontario, Canada:
‘Ontario Hydro Research Division, Report no
62-78,
(18) SEARING, H.R. and KIRKE, W.B, Reduction
(of Sheath Losses in Single- Conductor Cable. Blo
trical World, vol 92, Oct 6, 1828, pp 685-688,
[19] SIMMONS, D. M, Calculation of Blectrical
Problems of Underground Cables, The Electric
Journal, vol 25, May-Nov, 1932.
20] WATSON, W. and ERVEN, C, C. Surge Poten
tials on Underground Cable Sheath and Jolat
Insulation. AISE Transactions, June 1963, pp
230-240.
[21] WOLLASTON, F. D. and KIDD, K. Ht. Cable
‘Sheath Jacket Requirements to Withstand Abnor
nal Voltage Stresses. AIBE Transactions (Power
Apparatus and Systems), pt Il, Feb 1962, pp
1116-1123,
22) WOODLAND, Jr, F. Blectrieal Interference
Aspects of Buried Blectric,Power and Telephone
Lines. IEBE Transactions (Power Apparatus art
Systems), vol PAS-89, no 2, Feb 1970, pp
216-280,
3, Recent Developments
Modern polymerie insulated cables usually em-
body a semiconducting insulation steld, with
some provision for faut-current return by a con-
centric metalic path in the form of helically
applied wires or tapes, or by a solid metallic
sheath,
FFurtiver coverings, when employed, are primar.
ity for mechanical and corrosion protection but
the Introduction of low-cost cable jackets capable
of withstanding high electrical stress has, ln uddl-
tion to providing the necessary mechanteal and
corrosion protection, permitted higher standing
voltages on the sheath or shield and the use of
ondlng systems for increased cireull ampacitles.
‘Sheath voltage limiters, which protect sheath
insulators ani cable jackets, have been developed.
‘These sheath voltage limiters are designed to limit
the
(1) ‘Transient voltages associated wit lightning,
(2) Switching surges
(3) Fault initiation
‘The use of sheath voltage limiters is Intended to
reduice the problems of fallures of sheath insula
tors and cable jackets encountered in early
installa
so inte to: UNWVERSITE PALL SABATIER TOULOUSE 3 Dowleaded on Novnber 252010 094049UTC Gem EEE Xe, Resticons sy‘CALCULATION OF INDUCED VOLTAGES AND CURRENTS IN CABLE SHEATHS
4. Guidelines: Summary
4.1 Safety precautions and practices in design,
construction, operation, and maintenance should
bbe based on the principle that the voltage on the
Insulated sheath of a transmission cable may be
nsidered analogous to the voltage on the con
ductor of nonshielded secondary cables,
4.2 Solidly bonded and grounded sheaths are the
simplest solution to the problem of sheath volt-
‘ages, and special bonding methads, by which ate
‘meant systems other than solidly bonded and
grounded sheaths, are only Justified on the basia,
of economies (usualy at loads above 600 A) or at
‘extremely heavy loads where all hent generation
has to be miniinized.
4.3 The simplest and most effective method of
special sheath bonding is single-point bonding, a
rajor disadvantage is that maximum cable length
4s governed by the permissible sheath standing
voltage. Asa reaull, when very tow liming valzes,
of sheath voltage are specified, this method will
ot be applieable. Single-point bonding may
require a separate ground-return conductor
whereas cross honding does not.
44 OF the other bonding systems in use, cross
bonding is the most widely used, This system is
especially sultable for long cable lengths.
4.5 Cable sheaths are usually expected to be
nominally at ground potential but in a specially
bonded system they may have appreciable volt-
‘ages with respect to ground. Under some cir.
‘cumstances, even solidly bonded nnd grounded.
sheaths can be well ahove ground potential. Some
tities allow sheath standing voltages as high a
300 V. With present-day jacket materials, sheath
voltages of 600 V are possible,
4.6 Complete suppression of circulating sheath
currents may not always be possible because of
practical difficulties inthe choice ofeable lengths
and spacings. It may then be necessaty to cate
lite these residval sheath currents and assess
thelr effect on the eable rating.
4.7 The use of special bonding gives rise to sheath
overvoltages during system transients and faults
and the Values ofthese overvoltages must be con-
sidered. For: higher voltage systems a sheath
voltage limiting device is needed, and in all cases,
avarice
sia 66-18
consideration must be given to the coordination
of the sheath insutation levels in relation to the
overvoltages to which this Insulation will be
subjected,
4.8 Failure of apart of thesheath insulation or of
4 sheath voltage limiter may result in considera-
Die sheath currents and losses and hence may
‘cause overheating of the cables. Consideration
‘must therefore be given to the duty imposed on
‘the sheath-voltage limiting device and tothe n
{oring and maintenance of the complete systems
in operation,
6. Bonding Methods
5.1 Introduetion, ‘Thesheath ofa single-condue
(or cable for ac service acis as a secondary of a
transformer, the current in the conductor induces,
8 voltage in the sheath. When the sheaths of
single-conductor cables arebonded to each other,
as is common practice for multleanductor cables,
Ue induced voltage causes eurrent to low in the
completed circu. This current causes losses in
the sheaths, Various methods of bonding may he
used for the purpose of minimizing sheath losses,
Formerly, where special bonding was employed
for the prevention of sheath losses on lead
sheathed cables without an insulating jacket, the
sheaths were subjected to ac voltages, and the
bonding was designed to keep the magnitude of
the Induced voltages within small limits 0 a5 to
prevent the possibilty of sheath corrosion due to
ac electrolysis.
Various levels of permissible sheath voltage to
sound were propel a eetala tines Saag
‘Wom TEV 6 17 V, to prevent Sovran due te
‘Sectroljai Ache present te, cablevaresteny
‘ralyain ACRE present tine, cables are uswally
“MamTactured with an insulating Jacket, so that
Induced voltages no longer constitute a corrosion
problem, and voltages comparable to secondary
‘cable voltages may he acceptable.
‘The problem of sheath losses becomes partit-
Jely important when large, single-conductor
cables comprising a clreult are placed in separate
duets, or spacing between directly buried eables i
\ereased to reduce the effects of
as signficently higher vollages are in
ceable sheaths. The major purpase of special sheath
bonding for single-conductor eabtesis the preven
tlon or reduction of sheath losses,
eons uso inate: URIVERSITE PAUL GABKTIER TOULOUSE 3, Dovetonted on November 25,2010 0840 40 UTC om IEEE Xplore
»
Resins slyasst
‘sar
62 General
6.2.1 Single-conductor, bare lead-
ceabies have been Installed in duets a
fully operated in North Ameriea for many decades
‘The operating sh
tain value (normally 12 V-17 V between sheath
and ground), which was governed predominantly
by. considerations of electralvle corrosion.
Metallic sheathed single-conductor cables are
now protected by jackets of various kinds. Where
fonce these coverings were to serve only as an
anticotrosion protection of the sheath under
normal operating conditions, more recently 1
properties of the Jacket are dictated by require
nents arising out of abnormal operation of the
electrical circuits s0 that the jacket Itself has
become an insulator, Limitations remain on the
"upper value of permissible induced votages, b
‘at a much higher level They are ax follows:
(1) Breakdown voltage (puncture vottage) of
the insulating jacket under fault conditions
(@) Flasliver voltage of sheath sectionaliing
Joints,
152.2 Any sheath bonding or grounding method
rust perform the following funetions:
(1) Limit sheath voltages ns required by the
heath sectionaizing joints
2) Reduce or ef
(@) Maintain a continuous sheath elreuit to
permit fault current return, and adequate light
hing and switching surge protection
‘To salisy these requirements either fully or
partially, te cable sheaths are divided into a
‘number of sections by means of sheath sectional
faing joints, The length of these sections is deter
Inne he permis ent otage etl fr
“te mets of bn
‘eussed in 63. tn all eases, a cable with an it
ing jacket is assumed
sheath losses
5A Destgu. In the design of special sheath.
Ddonding arrangements, consideration must be
given to the following aspects:
(1) The choice of sheath-bonding systern to be
adopted (see 68)
(2) Cable sheaths are usually expected to be
nominally at ground potential bat In a spectally
bonded system they may have appreciable volt.
‘ages with respect to ground. Consideration should
De given to any safety aspects tat may arise and
to any Hiiting values of sheath voltage that are
specified.
(8) Complete suppression of circulating sheath
SEATILONDING BIETHODS FOR SINGLE CONDUCTOR
10
£8 AND THE
currents may fot alvays be possible because of
Practical dificulties in the choice of cable lengths
and spacings. Ibis hen necessary to calculate the
residual sheath currents and assess thelr effect
‘on the cable rating
(4) The use of special bonding gives rise to
sheath overvoltages duringsystem transients and
faulls and the magnitudes of Utose overvoltages
muss be considered. For higher voltage systems, a
‘sheath voltage limiter will be needed and in all
‘cases consideration must be given to the coord
nation of the sheath insulation Ievelsin relation to
Insulation will be
nsulation oF
of # sheath vollage limiter may result in large
‘sheath currents and losses and hence may eause
‘overheating of the eables. Consideration must
therefore be given to the duty Imposed on the
sheath voltage liniting device and to the monitor
{ng and maintenance of the complete system In
operation.
For single-conductor eable circuits carrying
Jags ewrvents in excess of 600 A, special bonding
fs often economically desirable as the reduction
losses allows an appreciably smaller conductor
size to be used.
"There is ao clear-cut point at whlch special
bonding should be introduced and the extra cost
of the larger conductor size cables needed for a
solidly bonded system must be balanced against
the cost of the additional equipment and the
riaintenance cost arising from te greater €or
plexity of specially bonded system,
64 Single-Polnt Bonding. The simplest form of
special bonding consists In arranging for the
sheaths of the three eables to be connected and
‘rounded at one polat only along their length, At
al other points, aveltage will peer from siveath,
to ground that will be a maxlimuan at the farthest
point from the ground bond. ‘he sheaths must
therefore be adequately insulated from: ground
Since there is no closed sheath cirevit, except
Uhrough the sheath voltage limiter (if any),
eurrent does not normally Now longitudinally
along the shenths and no sheath elrealating
‘current foss occurs (slieath eddy loss will still be
present),
6.4.1 Sheath Standing Voltages. Values of
sheath standing voltage can be found using Fig
Por a typical circuit having a conductor current
1 = 10004
3
av?
‘nubosaes toons use eo UNVERSITE PAUL SABKTEER TOULOUSE 3. ConeionesenNovexber 252010 91084040 UTC fom IEEE Xpbe, Reston pp‘CALCULATION OF INDUCED VOLTAGES AND CULIRENTS I CABLE
. 28 4 Be 7aer
ansiricee
mH side
22 4 8 6 7880
20
‘outen castes oF GRUP
m0 INFLAT FORMATION
“CABLES IN TREFOH, ANO CENTER
‘CABLE OF GROUP IN FLAT FORMATION
7 CT) 3S
ano 578
Pit
Induced Sheath Voltage Gradient for a Conductor Current of 1000 A
where be connected at some other point, for example,
5 = contertocenter cable
d= mean sheath diameter
‘the sheath voltage willbe 103 V/kam and 1:18 V/kan
{or trefoil and flat formation respectively. Since
the cable sheath may at soine points be exposed
tocontact by personnel who might expect it to be
‘ator near (o ground potential, itis common prac:
tice to specify a maximum voltage permissible
uring fulltoad operation. [is recognized that
this voltage wil be greatly exceeded during ays
tem transients and short eireuis. The maximum
sheath voltage permitted st full fond varies con-
siderably between countries.
5.4.2 Multiple Lengths. When the circuit
length i uch tha the sheath standing volage
tation is exceeded when the ground bond Is
‘connected at one end of the circu, thisone may
the center of the length. The sheath standing
voltage on each of the two minor sections $0
formed is then correspondingly reduced. When
the eircult Is too long to be deale with by this
means it may be sectionalized by the use of sheath
sectionalizing joimts so that the sheath standi
voltage for each minor section is within Ue lita
tion imposed,
6.4.8 Parallel Ground Continuity Conductor.
During a yround fault on the power systern, the
zero-sequence current carried by the eable coi
‘ductors returns by whatever external paths are
available. Since a single-point, bonded cable
‘sheath is grounded at one position only, itcannot,
except in the case ofa cable fault, carry any of the
returning curcent. This being $0, unless some
parallel external conductor is available or Is pr:
vided to servo as an alternative path, the return
‘Authored anced we nted to UNVERBIE PAUL SABATIER TOULOUSE 3 Doanoased on Novener 25.2010 al 02404D1NTC em IEEE Xplore, Restcns apyastra
Steve 1888
cena
9
90,
nero
cook
e10se)
SieAMILDONDIN HIENODS FOR SINGLE CONDUCTOR CAOLES AND THE
ee
Fie
‘Transposition of Parallel Conductor to
Reduce Induced Voltage with
Power Cables in Fint Formation or Trefoll
‘current ean flow only by way of the ground sel
Because the resistivity of the ground is very high
compared with that of good conductors, the
return current is very widely diffused through
the ground and the mean effective depth of the
power frequency components is many Wundced
meters, Bocaure the returning current, on aver-
‘age, isso remote from the conductor current, te
voltage gradients induced along paralel co
tors, including the cable sheaths, are very hi
‘urthermore,in the absence ofa parallel ground
conductor, theacevrrence ofa ground faultin the
Imimediate vicinity of « eable could cause 1 major
difference (o arise between the ground potentials
at the two ends of a cable system. Depending to
some extent on the particular design of the volt:
fge limiters (i'any) employed, hazards could then
‘ene to personnel or equipment.
‘Accordingly, it [s recommended that a single
growed at both ends of the route, The spacing,
12
of this conductor from the eable circuit should be
sufficiently close to limit the voltage rise of the
sheath to an acceptable level during a single:
phase fault. The size of this condiictor must be
Adequate to carry the full expected fault current
for the cable system.
“The parallel ground continuity conductor is
usually insulated so as to avold any cocroston risk
‘and it willbe subject to voltage induction from the
power cables in the same way as any other paral:
{el conductor, To avokd citculating eurrents and
losses in this conductor it is preferable when the
power cables are not transposed, to transpose the
parallel yround continulty conductor using the
methods described in Appendix D, D3.
GAA Clreult Arrangements. Figures 8 and 4
show the application of single-point bonding to
‘single length and multiple length elreuits respec:
tively, These diagrame do not shaw the discon:
necting boxea to permit testing of the sheath
Insulatlon.
‘utnsed tconsed une ine os UNVERSITE PAUL SABATIER TOULOUSE 3 Dounatoa on Movenber 282010084940 UTC rom IEEE Kot. Reavsiricee
"ALCUTATION OF INDUCED VOLTAGES AND CURES IW CARL SHEATHS ssa 576-108
swearn voLrase Lens
anmenncounens 7
note —*
TeaMvartons.
PAMALLEL GROUND CONTINUITY CONDUCTOR:
@)
ssi may bo uss.
[NOTE Other patra of ground conus
‘Se AppcndleD, Oa
Fig 9
‘Single-Point Bonding Dlagrams for Cireuits
Comprising One Cable Length Only
(a) End-Polnt Bonding (b) Midpoint Bonding
SHEATASCOHONAWAHG TRaNarOSINON OF ABLE,
aed Powencaates”” TENMIMATION
{
Panautet GROUND.
‘CONTHUITY CONDUCTOR
SHEATH VOLTAGE LANTENS (WHEN ReQbIRED)
Rig 4
‘Single Point Bonding Dlagram for Cireult
‘Comprising Three Cable Lengths
‘mone eens ute nia UNIVERSE PAUL SABATIER TOULOUSE 2. Dosnnudedn Nove 220101 09:4040 UTC fomIEEE Xplore RessAxsi/ne,
55 Impedancesonding Methods. In impedance:
bonding methods, the eable sheath sections a
bonded together in some manner throught
impedance. This impedance may consist of simple
reactors or of devices such as saturable reactors
and bonding transformers. In all hese methods a
certain amount of sheath current is permitted so
fas to reduce losses and sheath voltages, To pro-
‘vide round connections, the Impedance devices
arenormally designed with center taps or ground
ing points,
'AL one time resistors were used, However, in
general, resistance bonding is wot practical, since
the resistors have to be sized to take the fault
currents and they are considered very large for
‘high faute currents.
‘Although # partial suppression of induced
sheath voltagesis obtained using impedance bond.
Inginethods, there are a number of disadvantages
tat limi the application of these methods. The
principal disadvantages are as follows:
() Additional manhole space is required,
(@) Theimpedance devices are relatively expen:
sive since they must be designed to withstand
aut currents.
(2) In normal operation, id hartnonkes
be introduced into the sheath, and these
‘cause Interference on nearby telephone tines.
Stray direct currents, entering through the
‘grounding, may cause saturation of the iron cores
fand upset the operation of the reactors or
transformers.
Cross Bonded Cables
SHEATIC-DONDING METIODS POR SINGLE-CONDUCTOR CADIS AND THE
5.6 Cross Bonding
‘BA.1 Basle Cireult Arrangement, Cross bond-
ing consists essentially In sectidnalizing the
sheaths into miner sections and eross connecting
them 20 as to approximately neutralize che total
induced voltage in three consecutive sections, as
‘shown In Fig 5,
‘With unteansposed enbles, as illustrated in Fig,
Is impossible to achieve an exact balance of
duced sheath voltages unless the eables are laid
in trefoil When, for the reasons given in Appendix:
D, D3, the enble conductors are transposed at
each joint position, the induced sheath voltages
will be neutralized irrespective of eable format
provided the three minor sections ate Identical
Figure 6 shows how this can be dane for a cirevit
fof three minor sections only. The sheaths are
bonded and grounded at Loti ends of the route.
In this arrangement, the three minor sections
together are termed a major section.
5.0.2 Longer Cable Clreuits. Cross bonding
‘can be extended to longer cabte circuits by the
methods deseribed in 6.63 through 5.7.
‘6.6.8 Sectionalized Cross Bonding. This cross-
bonding system isoften called Kirke-Searing bond:
ing although the system used by H.R. Searing and
WB. Kirke did not involve transposition of exbles
‘the numberof minor sections isdivis-
Fig
‘Without Transposition
{Mason SECTION,
Pig &
Croxs:Donded Cables with Transposition
-uthodeod icons ele o: UNVERSITE PAUL SABATIER TOULOUSE'S Donsfooded on Nayenbe 262010 a! 094040 UTC fen IEEE Xin.
lw
esvetans apyansirtece
‘CALCULATION OF INDUCED VOLTAGES AND CURRENTS IN CADLE SHEATHS sd 696 108
BeeroNaueme
JOnts
‘GROUNOING
tas
“THESE JonV1S MAY ALSO AE VNTHOUT SHEATH SECTIONALIZNG
INSULATORS, AND MAY BE CONNECTED DINECTCY TO THE
Ceca aroUNo,
Pig 7
Sectionalized Cross-‘tonded Cable
with Three Major Sections
uit can be arranged three, Balanced voltage conditions wlthin a given,
to.consist of one or more major sections in series, major section consisting of four minor sections
AL the junction of two major sections and at the can be achleved by subdividing one minor section
fends of the circuit, the sheaths’ are bonded into two subsections, 68 follows:
together and grounded, although the grounds at_—_(1) One short length (or subsection) followed
te junctions of major sections will generally be by two equal lengths (or minor sections) with
only local ground rods (See Fig 7 in which each another short length (or subsection) completing
Abie exactly by three, the
separate major section is connected as in Fig 6). the major section; the combined length of the two
5.0.4 Modified Sectionalized Cross Bonding. subsections should be equal to the length of one
In this modified version ofthessectionalized cross: minor section as shown on Figs 8 and 9,
bonding system, itis not necessary to have the (2) One short length (or subsection) followed
umber of minor sections exactly divisible by by one longer length (or minor section) then
6
‘utroead ican use tne fo: UNIVERSE PAUL SAGANIER TOULOUSE 3. Dunlosded on Novehe 25201009 40:49 UTC KonlEFE Xo. Resticons apyANSIARKE,
Serr 038 SUIKATILNONDING METHODS FOR SINGLE CONDUCTON. CAMLES AND ITE
‘ L a
Fig 8
Modified Sectlonalized Cross-Donding
‘aype 1 Without Traneposttions
LU and U2 @LENGIH OF SUBSECTIONS
ENGTH OF HINOR BECTIONS
uae
Fig
‘Modified Sectionalized Crose-Honding
‘Type 1 with Transpositions
Fig 10
Modified Sectlonllzed Cross-Bonding
“type 2 Without Transpositions
16
‘aunts hcansd se Hoda a: UBVERSITE PAUL SABATIER TOULOUSE 3 Oowrinafed on November 26,2010 024040 UTC Ho FEE Xone, Reston efaxsicer
seis 88
~ecvenEO
TRANSPOStTION
‘nD chOSS BONDING
(ans = LeNom OF suBsecTiONS
Leng OF Mavon seerions
uate
Fig 1
Modified Sectionalized Cros Bonding
‘Type 2 with Transposition
‘shea
SEenONALENG
TOs
| sett
SS unrens
Loca,
‘GROUWO—
Fig 12
Continuous Cross Bonding
subsection) followed by 6.8.6 Continuons Cross Bonding. In this sys
‘one longer fength (or minor section) to complete tem the sheaths are cross bonded at the end of
tho mafor section; the two longer lengths (or each minor section throughout the whote cable
rwinor sections) should be equal and the com- route. Thethreesheathe arebonded and grounded
bined length of the two subsections showld be at the two ends of the route only, 8 shown in
‘equal tothelength of one minor section as shown Pig 12. It is again generally desirable that the
on Figs 10 and 11. In this ease, the frst cross eables are transposed so that exch conductor
bonding must be reversed. ‘occupies each of tte three pasitons for one third
anotiver short length (0
”
‘hc eens ue fit lo UNVERGITE PAUL SABATIER TOULOUSE 3. Downloade on November 282010102 4D4DUTC tom EEE Yor Reston aptasian:
‘sate
‘svearn vourace
een
‘smc rowt
WORDED LENT
‘SitEATHLBONDING METHODS FOR St
05S-80NDED SYSTEM
‘CONDUCTOR CADIS AND THE,
Panases 6xouNo
onnivutry cowoucton
Fig 13
‘Termination of Cross-Bonded System with
‘Single-Point Bonded Length
of the total length. "The mumber of mateled minor
sections should preferably be exactly divisible by
‘hee, bul this becomes less important as the total
rnuniber of minor sections increases (see 6.6.2)
6.6.6. Mixed System, When the number of
minor sections fs not exactly divisible by three, the
system may consist of a mixture of Kirke-Searing
(regular and modified) and single-point bonded
Tengths. When necessary, on account of a large
raunber of minor sections having unequal lengths,
the eross bonding may be of the continuous type.
Figute 18 shows the arrangement ofa final single.
point bonded length at the end of a cross bonded
system.
150.7 Imbalanced Systems, It is not generally
possible to divide the route length into exactly
matched minor section lengths, nor is it always
possible to maintain a constant spacing of the
‘cables throughout the route. i continuous cross:
Doniled systems, it may also be desirable to have a
total number of minor sections not exactly divs
be by thrce. In practical ayatems, there is there:
8
fore generally some inobalance, and it may be
necessary to ealeulate the circulating sheath cur:
rents that are present so as to assess their effect
fon the eable rating, See [13] and [15] for methods
oF calculation.
6.7 Sheath Sectionallzing Joints, When the
sheath losses of single conductor cables must be
reduced or eliminated sheath sectionalizing joints
fre required for interrupting the electrieal conti
nolty ofthe sheath circult. To perform thetr func
ton satsfactorily there are several major factors
involved in the design of theseoints Meclvanically
‘hey must be rugged, impervious to moisture, and
fuld tight under all operating conditions, Blectri
cally, they must be designed to withstand the vol
tage stresses oecurring under faut, and lightning
tnd switehlng surge conditions
‘One of the quantities that must be evatuated
before a sheath sectionalizingjolat can be used in
a bonaling seheme Is te
‘vired at the Joint. This ean be deter
nutnoreadeene use tod e:UNVERSITE PAUL SABATIER TOULOUSE 2. Dosnionéean Hovender 252010 040.40 UT homEEE Rol, Resicons api‘CALCULATION OF INDUCED VOLTAGES AND CLIENTS IN
1g the maximum voleage appearing aerass
veto faults and lightning and switehing
‘surges, This subject ls discussed in Appendix E,
5.8 Choice of Bonding System. Impedance bond-
Ing methods are less satisfactory than the other
methods deseribed, Por this reason these methods
are not recommended for general use,
Bonding transformers may be econ
some tsolated eases such a
(2) Suitable balancing for eross bonding is
possible and single-point bonding is unacceptable
(that is, no empty duct is avallable for a ground
continuity conductor).
(2) A spare eable (a fonrth cable for a single
circuit or a seventh cable for a double cireut) is
installed; in this case, reconnecting the cross
voniding whenever the spare cable is needed is a
lengthy and complex operation, wheress recon
necting of Londing transformers is simple and
straightforward,
Users of this method! may refer to 56 and [0],
10}, f20), {21}, and {20},
Purther discussion will therefore be limited to
consideration of the other bonding methods.
5.8.1 Use of Single-Polnt Bonding, A mi
1m of three minor sections are needed to form.
‘A cross-honded system, and itis normal practice
to use sheath sectionalizing insulators only at
Joint positions. Henes, cross bonding is not nor-
‘mally applicable to cable circuts comprising only
‘one or two tengths, and, for such cireults, single
point bonding is widely used.
6.8.2 Advantages of Cross Bonding. Although
the cable sheaths ofa single-point bonded syste
are generally of a eross-sectionsl area and con.
‘ductivity that makes them quite eapable of carry.
ing short circuit currents due to thxough faults in
the power system, they are unable to do s0
because they are grom
Daraite! ground continuity conductor is therefore
recommended (see 5.4.8), and this adds appreci
ably to the eost of the cable system,
‘The principal advantage of cross bonding is
that, while Induced sheath currents are inhibited
ring norma! balanced load operation, thesheaths
do forma continuous path from end to end of the
cable circuit and are grounded at both ends.
Sheath currents ean therefore Now duringground
Faults, and the necessity for the parallel ground
contliulty conductor is removed, In addition to
the economy achieved by the elimination of the
round conductor, the cable sheaths funetion
more effectively as sereening conductors during
meal in
7
19
ansiniees
SmEATHS sia 67 108
round faults than a parallel ground continuity
conductor, Hence, the voltages induced in parallel
cables are less during ground faults in a eross:
bonded system than for a similar single point
bonded system
5.8.8 Cholce of CrosuTonded System, For
Jong cable circuits, there isa choiee between see
Lionalized cross bonding (see 6.63 and 6.64) and
continuous eross bonding (see 5.6). The relative
advantages are us fllows:
5.84 Advantages of Sectionalized Cross
Bonding
(1) Since each major section forme a separate
electrical mesh, itis relatively straightforward to
calculate the sheath currents when the lengths or
spacings of the minor sections are not uniform,
In a nonuniform section having an equilateral
ceable configuration the ratio of sheath loss with
cross bonding to that with solid bonding Is given
wy
H-BOAg+ ALAS ADdGIT
where
x = cross-honded loss
1 © solidly bonded loss
Aye Ags Ay = per unit lengths of the three min
sections, that shy + Rg + Ay =
EXAMPLE When
Aye od
dy 02
Ay = Od
the loss with eross-bonded sheaths Is 4% of the
loss with solidly bonded sheathe
(2) The sheath bond at the junction of each
ior section allows fault current due to a cabte
failure to be distributed between the three sheaths
‘except within the major section containing the
Falk,
(8) The sheath bonds and grounds at the jun
tions of major seetions tend to reduce transient
sheath voltages,
(4) The number of sheath voltage limiters
required is reduced,
(6) The sheath bonds at the junction of major
sections ensure that there will be no eharging
‘current flow beyond the neutrat points of the
bonds irrespective of any inequality inthe tengths
fof the minor sections.
5.8.8 Advantages of Continuo
Bonaing
(2) ‘The effects of nonuniform minor sections
Cross
‘Ashonwes eens se lined UNIVERSITE PAUL SABATIER TOULOUSE 3. Oowelodad on Hover 2520101004040 UTC fem KEE Xplor. Heston apyansinees:
Sito
may be redviced when they form part of a total
sheath eizeult containing 2 number of sections It
ray also be possible to use a total number of see
Yon not exactly divisible by dhree
(2) Tes possible to monitor sheath currents
throughout Ue whole cireult, irrespective of the
amber of minor sections, at one point along the
Fength,
(2) Atleast for low-resistance faults, the moni
toring ofthe sheath insulation and sheath voltage
limiters becomes easier because there are only
‘ovo sheath bonds and geound links to be removed,
ven on alongeircuit, to enable tests to be applied
From the ends of the cable circuit,
5 Sheath Standing Voltage
591 Skngle Point Bonding. Figure I shows the
sheath voltages per kilometer due to balanced
Toads in the eable conductors
159.2 Sectionalized Cross Honding. In ayy m=
nor section, tive sheath standing voltage per kilo-
meter will be as state in Fig 1 and the longest
Wr section shall be taken for calculating the
maximum standing vollage. With the modified
bonding method deseribed in BG-4(L) the maxt
umn standing voltage thus eutculated is reduced
fs much as 138% (see Appendix D, D5). This max
{nw reduction applies when the two short tengths
(Coraubseetions) are equal (thats, 11 =12=08 1).
See Figs # and 8.
‘When the major section is nonuniform, the
reath standing voltage can be taken as that cal
cailated for the longer of the two grounded minor
section lengths, When the nonualformity causes
‘appreciable sheath current, there will be same
reduetion of the sheath standing vokage.
5.9.8 Continvous Cross Boning. When the
‘whole system between sheath bonds consists of «
number of uniform minor sections exactly divis
ble by three and the cables are transposed so that
‘each conductor occupies each of the three post
is for one third of the total length, then 110
sheath current flows, and the maximutn sheath
‘slandingvoltages per meter are asstated in Fig}.
Ina practical aystem having variable lengths of
iinor sections, the sheath standing voltage ean
be taken as that ealeulated for the longest minor
section length. When appreciable sheath current
ows, the sheath standing voltages ts reduced
somewhat
6.0.4 Double-Circult Systeme. Where two
closely spaced cireuita are present, the sheath
‘standing voltages are wodifed by the presence of
the second eircut.
‘sieAIHIONDN
Mkaiobs FOR SINGLE CONDUCTOR CARLES AND THE
Because of tie infinite vailety of geometrical
arrangements coupled with differences in individ
tal eable loading and phase rotation, a universal
solution to sheath standing voltages'on multiple
eiceuits cannot be given here, Some of the more
‘common double-eircuit geometries ave deseribed
in [15] and (19)
‘A general solution requires the use of a digital
computer and finear algebra, However, when dis-
cretion is used in the selection of phaze rotation
land position, the effect of adjacent circuits does
not significantly Increase standing voltages pro-
vided these eizeults hve equal or lower balanced
phase currents,
‘A solution to a simple parallel dovble cireuit is
aiven in Appendix D, D2.
6, Sheath Voltage Limiters
G.L Introduction, Sheath sectional
tors in eross-bonded cable systems and the insu
Jators in a single point bonded cable system may
flashover due to overvoltages gonerated by light
jing, switching. surges, oF faults on the power
systein, Tt necessary to provide some form of
protection for these insulators inuder system tran:
sient conditions, At presont, shenth voltage
Timiters are used for this purpose. The three main
types are
(Q) Nontinear resistances
(2) Nonlinear resistances in series with spark
eps:
(@) Spark gaps
6.2 Nonlinear Resistances. Nonlinear resistances
‘can provide good protection (or transient volt-
‘ages, They do, however, have a limited capacity to
absorb energy and are not designed to carry a
60 Tis fault current. They must be sized to with-
stand 60 Hr faull-cutrent overvoltoge due to ays
tein faults external to the eable circuit, although
they are not normally expected to sitive over-
voltages resulting from fats internal tothe eable
circuit, The surge energy and 60 Fz vollayes, to
Which the resistor is subjected, dictates the
ccharactetisties of the resistor, Distribution class
arrestere are often adequate for the surge eneray
requirements when selected to withstand the
power frequency fault voltage without disehary-
ing, High hunuity tends to reduce the effective-
ness of nonlinear resistances, and they must,
therefore, be protected from moisture by a suit>
able ease or encapsulation
‘huhodzodtconse ne ed to UNVERSITE PAUL SABATIER TOULOUSE 3. Danloaed on Hoven 2.201 84040 UTC rom IEEE Xp
Revie spr6.3 Nonlinear Resistances in Series with Spark
Gap. Nonlinear resistances in series with spark
aps are widely used as surge arrester. In con
trast with the sheath voltage limiters described in
6.2, surge arresters have the advantage that 60 lz
currents owing in them wit be interrupted and
‘the maximum energy dissipated in the nonlinear
resistances will be correspondingly less. However,
although modern arresters will sparkover with
‘minim overvoltage on steeply rising waves,
they have the disadvantage that their response i
slower than that of the nonlinear resistance alone,
4 Spack Gaps. The spark gap isthe simplest of
‘he Unree voltage limiters, bt has the disadvan
tages that it may be damaged by high 60 Tz
currents following initial sparkaver, and its
response is slow, particularly to very steeply rising
transient overvollages. The gap length may be
Increased so that 60 Hz fault-eurrent voltages will
maintain an are. This, however, will reduce
the spark gop's protective value, particularly for
steeply rising voltage waves.
‘A spark gap has heen seveloped (2) that pro-
vides reliable surge protection, at the terminals,
for cable sheaths. The electrode arrangement of
the spark gap (referred to as a ring gap) is
dealgned to cause a motoring action of the are
that eliminates serious erosion af the electrodes,
‘These spark gaps are capable of conducting ares
‘of high current densities without deterioration of
the electrodes, and are used for protecting cable
sheaths atthe terminats on eircults up to 10 km,
in tengeh,
Spark gaps require periodic inspection and
muintenance, and itis therefore suggested that
‘hey be used only to protect single point bonded
circultsat the terminations where the gap is edd
lly accessible Ils recommended that they not be
used in ¢ross-honded systems where the gaps may
be installed in underground boxes and be rela-
tively inaccessible,
6.45 Selection of Sheath Voltage Limtters. In
selecting a sheath voltage limiter, the following
criteria should be considered:
(1) Tae fimiter should be suitable for continu.
(ous operation with an applied voltage equal tothe
sheath standing voltage under either normal or
‘emergency load (69)
(2) ‘The limiter should be able to withstand the
60 Hz overvoltages resulting from system faults,
Caution should be used in selection of nonlinear
resistance-type limiters because of problems asso.
2.AUION OF INDUCED VOLTAGES AND CUMRENTS IN CAULE SHEATHS
a
ansiibee:
sna 678-108
lated ith 60 te overvltages discussed In 62
‘Gee Appendix B).
With nonlinear resistance type Himiters, a anax-
mum time should be specified this tx normally
Grice the mtu fault clearing time for the
system Lo allow for reclosing.
When caleutating 60 He voltages appearing
seross sheath voltage Hier, allowance shoul
be made for the liters that are star or dela
connecte
(A) Spark yops and surge arresters should be
able to withstand impulse currents for the sare
uration as specied for the Impulse. require.
mens for de main lightning (surge) arresters on
the stem,
‘A nonlinear resistance-ype limiter should be
able co absorb, withowt damage, te energy diss
pated due to stching, inluding stehing asso
ated with a fault external to the cable circu.
Experience and calculations indicate thatthe
‘energy dissipated in the nonlinear teststances de
to switching is not an important design erlterion
crossonded eieuits, However, for
point bonded eleevits or lengths of
single-point bonded cable that terminate long
circuits, the switehing surge energy may be
limportai, and eatewatons shoutd be mate for
these eases [1], [11] and [12] The ealeutations
should be performed using a computer, since
normal methods cannot readily be used because
ofthe presence ofthe noilinear cireut element
“Typleal switching transentraveshapes should be
assumed See [2], (3), (8, (5} (7) I, 9} (16),
{26}, {17}, and (50).
6.6 Use of Sheauh Voltage Limiters
6.6.1 Single-Polne Bonded Cables. Sheath
voltage limiters are connected between the wa
bonded ends of the cable sheaths and ground,
generally with a separate limiter at each cable
termination, When the limiters are Installed
together a5 a unit, connections between sheaths
‘and the limiter unit, which may be 2 1m t0 3m
Jong, should be made with tow surge-Impedance
coaxial cables capable of carrying the luniter
design current.
Generally, the end of the cable eircuit that is
able to be subjected to the higher ineoming tran
sient voltages, due to lightaing oF switching,
should be grounded. However, when the ground
resistance Is very much lower at one end,
proferable to ground the sheath at that end. It
‘may also be preferable to install the sheath voll:
sage limiter inside a substation rather than in
‘Asted Toensd usenet. UNIVERSITE PAUL SABATIER TOULOUSE 3. Oountaed on Noverer 25.2010 at 2 4040 UTE tem ECE Xr. Rass ayySusie
‘a location accessible to the public, since there
Is soine isk of explosive falure of the imiter
{As there may be conflict between these factors,
local conditions will determine their relative
importance.
0.6.2 Crose-Bonded Systems. In direct burled
Installations, cross-bonding connections ave made
‘with links in surface link boxes, so that individual
cable sheaths may readily be iolated for voltage
testing of cable jackets. The sheath voltage init:
fers are then located in or adjacent: to the link
bboxea so chat maintenance is possible by remov-
ing the manhole cover. In these Installations, the
‘connections between the buried joint and the link
box may bo as tong as 10 m. Honding leads shoud
bie low surge-impedance coaxial cables, as short
1s possible, o minimize the effect of the connec
tions on the efficiency ofthe sheath voltage limit-
fers, The bond leads must be eapable of eanyying
the systern shortcircult currents
In tunnels or In ducts, or other installations,
where the jlnts are in manholes, cheshieath voll:
age thniters may be connected aetoss the sheath
sectionaliaing inaulators with relatively short
leads. The crass bonding leads should also be as
short as possible to minimke the magnitude of
front surges. The conductor erosssection must be
‘adequate to carry system short-circult currents.
7. EXfect on Parallel Telephone
‘and Control Cables
While the purpose of special, power-cabte
sheath bonding isto reduce sheath eurrents and
attensdant sheath lasses, sheath eurrents i
nication eabies, induced by the inductive nf
‘ence of the power-cable system, are utilized to
provide beneficial shielding effets. I i tho mag.
veltages induced in enclosed cireuits
{guidelines are given on the unfavorable conse-
‘quences of cross bonded power-cable sheaths and
‘te optimization (by transposition) of the elrcult
{geometries to reduce the nfiuence. In tis section
some additional factors are briefly noted.
7.1 Coupling, The coupling ofthe power circuit
to the communication circult Is evaluated in
terms of the mutual impedance. Residual or zero
‘sequence components of the power circuit often
hhave a ground return (that is, overhead fines).
“The induced currents in the communteation cable
_Auhored horse ute edo UNWVERSITE PAUL SABATIER TOULOUSE:S Downoated on Hoverba 25.2010: 094040 UTC Kom IEEE Xo
_SHEATILOONDING MeTMONS FOR SINOLE-CONDUCTOR CABLES AND THE,
sheath algo return through the ground. ARhough
‘most of the zera:sequence components of burled
power cable normally return through the sheath
‘or separate neutral conductor, sowe portlon may
return through the ground, These factors Intro-
duce uncertainties in the calculations of the
‘mutual Impedance, which can, however, be calew-
lated with reasonable accuracy using Carson's
eauations (6) Since the magnitude of the grownd.
return current has relatively large effect on the
mutual impedance, the approximation that all
zero-sequence current returns trough the sheath
ceannot be made,
‘While the coupling of the findamental power
frequency under steady-state balanced conditions
cean be nitnimized by suttable transposition, there
may be present add trIple harmonies (3rd, 9th,
16th, ete) that add in phase, and therefore, are
not neutralized by circuit geometry.
72 Shielding, ‘The design of the communication
ceable sheath and other outer coverings Is a fun
damental factor in the reduction of the voltage
induced in the communication eable pairs. The
reduction factor (often referred to as shielding
factor) is defined as the ratio of the induced elee-
tromotive ferce (emf between,
tors and ground to the to
force (evnf) that is Induced when metallic cable
‘covering are absent. [t may be expressed (where
nonmagnetic materials are used) a5
R
"Tee Goh P
where
+ reduction factor of the communication
cable
R= de resistance of the grounded metallic
ceable coverings including the grou
resistonces, 0/km
@ ~ angular frequency
Sans
Ly = inductance of the ground clreuit, H/kan
(approximately 2 milan)
From the above expression It can be seow that
the Induced fongitudina or common-mode vot
tage on the enclosed patrs of tte cable fs equal to
the JR drop inthe sheath ground circult including
the grounding resistances. [Lis therefore funda-
mental to provide low-resistance grounds. The
use of mage materials for outer coverings improves
the shielding efficiency substantially, untess the
Iagnetie feld strength results ln saturation
Jor. Resisons a4‘CALCULATION OF INDUCED VOLTAGES AND CURRENTS I CABLE SHEATIES
7.8 CommonMode and Metallic Voltages. ‘The
common-mode voltage or longitudinal voltage is
the voltage between the cable palrs and ground, It
Is the prime consideration relative fo connected
‘equipment or personnel hazards and is normally
of prime significance during faults in the power
system. The so-called metallic voltage isthe voll-
age between the two wires of @ pair and is mani-
fested by pair to ground imbalance that converts
‘he longitudinal voltage to the transverse voltage.
It is associated with nolse introduced into the
‘communication efreuit. When the affected pair
used in a protective eirenit for power-eireuit
relaying, (alse tripping of a protected power cir
‘cuit may oceur. Objectionable audio noise ean be
introduced Into volee frequency citcuits at quite
tow field strengths by power frequency harmonies
(Compare with 7.1). Ths effects the consequence
‘of the response of the human ear, the sensitivity
‘of which increases rapidly from 60 Hz to 1000 He.
Tt becomes evident that the Inductive effects
fon parallel telephone and control cables are
dependent on many factors, including circ
‘geometries, mutual impedance, frequency, grou
resistivity, shield factors, wave shape, design of
connected equipment and te tke. Quantitative
estimations are faeilltaced by computer. In
‘unusual situations, where established practice is
‘not applicable, verification by field tests may be
equired (see {14} and (82).
8. Bibliography
{B1] ADAMSON, C, TAHA, H. and WEDEPOHL,
1, M. Comparative Stendy State Performance of
Cross-Bonded Cable Systems, Proceedings IEE,
vol 116, no 8, Aug 1968, pp 1147-1166.
[B2] ADAMSON, C, TAHA, H. and WEDEPOHL,
L. M. Determinatton of the Open-Circuit Sheath
Voltages of Cable Systems, Proceedings IBE, vol
116, no 8, Aug 1968, pp 1137-1146,
{B3] ARNOLD, A. H. The impedances of Three-
Phase Line of Single Conductor Lead Covered
Cables Arranged ina Plane, with the Middle Cable
Bquidistant from the Two Outer Cables, Journal
IBB, vol G1, 1929, pp 90-96,
[BA] ARNOLD, A. The Theory of Sheath Losses
in Single Conductor Lead-Covered Cables, Jou
nat IEE, vl 67, 1928, pp 60-89.
(B5] BERKE, LR, GEER, Jr, B.W, and TUCKER,
23
aveuiece
sidst6 a
D.R. Staged Fault Testing of Leased Audio-Tone
Relaying Channels Subject to Ground Potential
Rise and Induced Voltage. IEEE Transactions
Power Apparatus and Systems, vol PAS-92, no 1,
Jan/Feb 1973, pp 89-97
[B6] BULLER, F.H. A Technique for Calculating
Inductance, Reactance, Impedance, and Sheath
Voltage of Single-Conductor Cable in Duct Banks,
General Blectrie Review, vol 62, Mar L040, pp,
40-44,
(07) CLARK, W. $. and SHANKLIN, G. B. High
‘Tension Single Conductor Cables for Polyphase
Systems. Transactions AIBE, vol 38 (1919) p 017
{88} Design of Special Bonded Cable Systems,
(Paper presented by Working Group 07 of Study
Committee no 21) Blecira, May 1979, pp 55-81
and Design of Specially Nonded Cable Circuits,
Part IF (Second Report of Working Group 07 of
Study Committee no 21) Electra, no 47, Jul 1976,
|B9} Induced Voltages in the Sheaths of Gross
Bonded AC Cables. Proceetings IEE, vol 113, no
12, Dee 1966, pp 1990-1994,
10] DUNSHEATH, P. 33 KY Cables with Metal:
Sheathed Cores, with Special Reference to uve S..
‘Type. Journal TBE, vol 65, 1027, pp 469-478.
{B11} PALLOU, M. Application of Symmetrical
Components to the Caleulation ofthe Voltage Rise
‘of Metalic Single Core Cable Sheaths Due to Short
Cireuit from Phase:to-Ground. General Electric,
vol 27, no 6, 1963, pp 968-366,
[012] FISHER, H, W. Losses, Induced Volts and
Amperes in Atmor and Lead Cover of Cables.
AIBE Transactions vel 20, pt It (1989) pp 747-
‘10.
[B13] KELLAM, B. Problems and Experiences
With Protective Jackets on Metal Sheathed Cables
Ontario Hyitro Research Division, Report no
4
[B14] MILLER, K. W. Sheath Currents, Sheath
losses, Induced Sheath Voltages and Apparent
Conductor Impedances of Metal Sheathed Cables
Carrying Alternating Currents, Electrical Bngt
neering Thesis, University of Tino, 1929.
[815] RHODES, D. G. and WRIGHT, A. Induced
Voltages in. the Sheaths of Cross-Bonded AC
Cables. Proceestings IBE, vol 119, (1), 1966, pp
99-110,
B16} RILEY, B.W. stimation of Voice Frequency
Noise [a Communication Circuits, Procaodings of
‘Ashorued tensed use inet UNVERSITE PAI SABAIIER TOULOUSE 3. Dowlasted on Nove 26,2010 at 094940 UTC om IEEE ple, Restos epansineee
Se a
the 10th International Wire and Cable Sypmpo-
alum, Mantie City, Dee 1970, pp 144-164,
{817} SCHURIG, 0. R, KUEN, HP, and
BULLER, F. H. Losses in Armored Conductor
Lend Covered AC Cables. AIBE Tyansactions, vol
48, Apr 1929, pp 417-436,
SHEATILIONDING NEeTHODS FoR SINGLE
oNpucron CAM:
{B18} WEDMORE, G. B, MORGAN, P. D.. and
WHITEHEAD, S.A Critical Study of a Theee-
Phase Systein of Unarmored Single Conductor
Cables, from the Standpolnt ofthe Power Losses,
Line Constants, and interference with Comm-
nication Circuits. fournat IEE, vol 07, 1829, 9p
350-434
‘rubotued Icons ute tie os UMVERSITE PAUL SABATIER TOULOUSE 3 waded on November 25201081 94040 UTC fom EEE Xplore, Restcbons py,asia:
URRNTS IN CABLE SHEATHS ss 575-1088
Appendixes
{tees Appendixes ae nts pat of ANS/IEEE Su 6761088, IEE Guide forthe Appiaton of Shesth Bang Mesos or
‘singe Condntor bles an the Calculation of induced Veltages and ConrentsCabse heath
on
ede Moston
Appendix A
‘Terminology
bonding lead. ‘The insulated conductor forming
the connection between the sheath of a buried
cable oF joint and a link tn the link box
ee the taste of nets nat
scribed 86 of ths gle),
‘heer na the wasted conductor forming the co
‘ection tween ary of te fling components the 3
Ten: shesth, jolt eas bane (opie be) of termntions,
‘ound Us ed ground ro
‘continuous cross bonding. A form of exoss bond:
ing applicable to circuits conslting of at east four
minor sections in which the cable sheaths are suc
‘cessively cross honded at each junetion between
adjacent minor sections throughout the cable
route. At each end of the route the sheaths are.
solidly bonded and grounded.
‘eross bonding. The form of special bonding in
‘which the eable sheaths in consecutive minor sec
tions are eross connected so that each continwons
sheath eireultsurrounds the three-phase conduc-
tors consecutively,
‘lot formation. Three cxbles lald in & plane with
equal spacing between adjacent cables,
insulated sheath system, A cable system in
which the metallic sheatis of each exble is indi-
Vidually insulated throughout its length except
where any necessary grounding oF inter-sheath
connections are made,
Jolnt sleeve intuistion. ‘The external inswlation
applied to the metallic joint sleeve of a specially
bonded eabie.
link box, A box in which bonding or grounding
nections or both, are made through removable
‘and which may also contain sheath vottage
Mimivers
minor section, The length of cable system be-
‘oven sheath sectionalizing positions or between
sheath sectionalizing positions and terminations
NOTE te sates
ecessay (such sjptems
paraltel ground continuity conductor, A con-
‘ductor laid parallel to a cross bonded circuit to
provide a continuous metallic ground connection
between the grounding ystems atthe ends af the
‘cable route,
sectionallzed cross bonding. The form of cross
Lousling in which three consecutive minor sec-
tons are taken to form a single unit (termed a
‘major section), The three sheaths are solidly
bonded at hoth ends of a major section and may
be grounded at these points, At the tivo Interme-
diate positions the cables are transposed and the
‘sheaths are so interconnected that each continu
sheath cirewit through ¢he major section
‘occupies the same geometrical position in the
able formation. For tong cable routes there may
be a number of major sections
screening conductor. A conductor laid in paral
Jel with a current-carrying loop and itself forming
art ofa closed circu in which induced currents
may flow whose magnetic field will oppose the
fletd of the current-carrying loop.
sheath seetlonallzing Joint. A joint in which the
‘metalic sereen and easing are electrically inter-
rupted, the interruption in the easing ofthe joint
being by means of a sheath sectionatizing insw-
lawn.
‘shenth standing voltage. The voltage to ground
appearing on the sheath of 2 specially bonded.
cable when balanced fullJoad currents are flow
n the cable conductors; normally quoted at
the point along the cable length at which it ba
‘maximum (that is, at the ungrounded extremity
‘ofa minor section inthe ease of single-point bond
ny and at a cross-bonding point in the case of
‘erass bonding). When the voltages differ for the
three-phase cubles, the highest value fs normally
quoted.
sheath voltage limiter, A device connected to a
sheath or to the sheaths of specially bonded
‘cables intended co lit sheath overvoltages dur:
ing system transients,
single-polnt bonding. ‘The form of special bond
ng in which the three-cable sheaths of a minor
‘Aurcedcensod sented to, UNIVERSE PAUL SABATIER TOULOUSE S,Domibadd on November 2201051084040 UTE Ken IEFE Xp, Reston apysection are solidly bonded together and grounded
at one point only. For tong eabe routes this may
be repeated a nurnber of tines.
sold bond. An Inteesheath connection of mint
‘mum practicable impedance,
speclal bonding. Methous of bonding and ground:
Ing te sheaths of single-conductor cables 30 as t0
sninimize the sheath circulating currents resulting
from induction from the conductor currents.
transportation
(1) fn reation to poser cables, The practice
of laying. sigle-concluctor cables. so
phase eable successively oceupies, over equal
lengths of the route, each of te three geometrical
positions in the laying formation
SHWATIBIONDING METHODS FOR SINGLE-CONDUCTOR CABKES AND THE
(2) in relation to parallel conductors. ‘The
practice of ayia parallel conductor alongside a
minor section of untransposed power eables 0
that, n relation to the plane of symmetry of the
cable laying formation, the conductor over halfot
the section length oecuples one position and over
the other half occupies a syimmetrcally opposite
posit
{refoll. The formation of three cables so laid asto
bbe mutually equidistant (when viewed in erass
-cetion, the lines joining the eable centers form an
equilateral triangle)
‘uniform major section, A major section cow
iyo three similar uniform minor sect
caval lengths.
Appendix B
arly sel-contained cables were
1 combination of oll and paper
structed with a metalic sheath, which
‘88.9 barrler to moisture ingress and as a return
path for faule currents. The most common sheath
material was these cables were fee-
‘quently installed with protective jacket with th
sheaths solidly grounded.
In North America, they were usually installed
jn duets and manholes. In Europe, particularly
‘ny Britain, cables were often armored and direct
ly buried Many of these directly burled cables
were protected with hessian wrappings and
bituminous compounds, Asa general rate, power
losses in the sheaths were recognized. bu
accepted.
‘Ay system voltages and currents
26
cusston of Early Practices and Problems
ese losses assumed a greater importance, and
1s methods of reducing these losses were
levied over the years from 1010 to the «nid
990%. Most of these methods required the tse of
insulators inserted In the sheaths to break the
sheath elreuit into smaller electrical seetio
‘Although these systems were reasonably suc-
‘cessful the sheath insulators were often a source
fof problems because of leaks that permitted cable
oils to leak out and molsture to penetrate the
cables.
Because of factors, such as ac corrosion and
personnel safety, and also because of a natural
rehetance to depart too far from the practice of
solidly grounding the sheaths, a sheath voltage
init of approximately 12 Vto 17 Vseems to have
‘been commonly adopted in the early days.
‘aunoes ces wee ie a: UNVERSITE PAUL SABATIER TOULOUSE 8. Dosnlonde on Hoventer 22010 at 84040 UTC tom IEEE Xeoe, Resticons apasvinee
‘CALCULATION OF INDUICED VOLTAGES AND CURRENTS tM CADLE SHEATHS sid 676 1086
Appendix
Current Practice
Cl, Practice In the United States
Current practice in the United States appears
{o permit a steady-state sheath voltuge of 65 V-
90 V, although there is not much evidence to sub
stantate this A standard practice presently does
hot exist in the United States, and this i one of
the reasons why this guide was developed.
‘Some examples of current US practic
follows:
sheath voleage of 66 V.
(2) An installation in New England of « cross
bonded system with a limitation of 86 V.
2, Canadian Practice
Practice varles from province to province. In
‘their installations of underground low-pressure
cilfilled (LPOP) cables, one utility utilizes the
scetionalized eross-bonding, method te minimize
sheath losses and also provide a low impedence
path for fault current. At all cross bonded posi-
tions, 2 KV lightning arresters are Installed to
‘minimize the transient overvoltage on the sheath
‘and joint casing insulation
‘The sheath Bonding and grounding arrange-
Iments are such that the standing sheath voltage
‘at maximum foad eurront does wot exceed 100 V
ny point along the cable.
ire the system will adequately withstand
anticipated transient overvoltages, the compo
nents ofthe circuit acted on by these overvoltages
are subjected to specied withstand levels
respect to ae ane! impulse voltages
‘Another utility hus installed eross-honled cable
systems in the past without any sheath sectional
faing joint insulator protection, However, some
pint insulators have falled in service and the sys.
tern is nol considered satistactory without some
‘method of joint insulator protection. The present
‘method heing utilized by this utility s single point
Dondlng with chug gaps atthe terminals. Standing
sheath voltages of 300 V-400 V on emergency
load are permitted at the terminals, However,
with increasing load currents and circuit lengths
this method ts approaching Its lit as it is not
proposed to exceed 600 V atthe terminals,
‘Aerts eons use init: UNVERSITE PAUL SABATIER TOULOUSE Dourisopdon November 2520
One rather unusual method of bonding has
been adopted by another utility for eable routes
‘with unequal lengths between manholes, ‘This
could be described as a modified sectionalized
cross-bonding scheme and fs deserihed In detail i
5.64 of this guide,
3. British Practice
3.1 British Practice. Cables in Britain have
from very early days had some form of outer
jacket over the sheath, Initially, these were
constructed by tapping various layers of sell
vulcanizing rabbers and pve in conjunction with
bitumastic compounds in hessian tapes. Because
these were electrically sound and of reasonable
electrical strength, It was judged that, even when.
special bonding comes into Vogue, here Is little
Weelthood of sheath voltages ever becoming high
enough to puncture any form of anticorres
Jackets. Polyvinyl chloride, polyethylene, an
igh -density polyethylene extruded jackets have
replaced these more complicated constructions.
‘This is contrary to the practices in the United
States where bare lead sheaths were In regular
use and sheath voltages were limited to 12 V or
thereabout, Spectal bonding circults were Intro
sd Into Britain ia the late 1950', at which
time the maximum standing sheath voltage was
limited to 60 V below ground and ¢o 25 V at the
terminations. These maximum permissible levels
were mandatory forthe central electriety gener-
ating board (CEGB) from 1959 to 1965, when it
was made permissible to increase che sheath vot
age below ground from 60 Vt0 65 V. The 66 V level
is the value used now, except in special installa-
tions in CEGB-owned tunnels. The River Severn
cable has induced sheath voltages of 100 V at Fall
load at various parts along the route but the
terminations are limited to 25 ¥.
‘The reason for selecting 60 V in the late 1950 bs
not clear, but It was increased to 66 V because it
‘was limiting drum lengths and increasing the coat
of many eable cireults.
Factory testing of the jackets has always been
wdatory, and it as heen wormal practice toast,
06
carry out a 10 RV directcurrent test for one
minute as follows:
(1) Immediately after laying
(2) After jointing (splicing)
(@) Just before commissioning tests on the
rnain insulation
“To ensure a good ground is available, the outer
jacket surface Is normally coated with graphite
during manufacture,
‘The effectiveness of the extruded jackets in
resisting corrosion is considerably beter tian the
tarlier taped servings, but both have a very sas
Factory record.
I Is essential with fully insulated systems to
ensure thal the disconnecting links are replaced
before Ute commissioning tests are earried out
When the sheaths are allowed to float, the effects
are catastrophic, To obviate this hazard, quite
sueArt-poNDUNG METLODS FoR SINGLE CONDUCTOR CAMLES AND TA
formateustomer/eontractor tink box precomnis-
soning inspection, certiteation, aul Jocking pro:
‘cedures have been introduced,
3.2 Practice in Europe. {n Burope, a standard
practice does not exist, but the following informa
tion Is an indication of the position in various
‘countees
In the Netherlands, a recognized Ymit on sheath
‘voltages has not been ageced upon. There is a25 ¥
Timi France for voltages on exposed auetal at a
termination, but there fs no lilt for sheath volt-
tes on insulated metat
|s used, tn taly,a fixed value has not been
‘upon, but exposed metal Is nornvally limited to
approximately 25 V,
Appendix D
Calculation of Induced Voltages
DI. Induced Voltages —General
Any conductor 2, lying parallel with a set of
three conductors carrying balanced three-phase
ceurrents will have a voltage gradient £, induced
sto c210° [tn (5452)
2 og,
(ead)
ut (A) in conductor b, rms value
lar frequency of system (2 1)
Sqy * axlal spacing of the parallel conductor
and phase a conductor
‘Sy, © axial spacing of the parallel conductor
‘and phase b conductor
Soy * axial spacing of the parallel conductor
land phase ¢ conduetor
and these spacings may be in any conventent
‘common unit
Tt fs agsumed that the phase rotation is such
hat
(402)
= hai
where
‘Jy ~ magnitude of the lond current
(Clearly, asthe spacings of the parallel conduc
tor increases in relation to the mutual spacings of
seanatd ve nied: UVERSITE PAUL SAARTIER TOULOUSE 3, Ooyniadeson Reve 252010 a 084040 UTC fom IEEE Xplore, Reson pny.[CALEVLATION OF INDUCED WOLEAGHS AND CURRENTS W CA
the ge
zero, Similarly, ithe three cables of the group are
regularly transposed at even intervals, the indiced
voltages in the parallel conductor sum to 2er0
‘over a complete eyele af transposition,
D2, Voltage Gradients Induced
in the Cable Sheath
nt induced in a cable sheath
a special ease in whieh the
parallel conductor isa sheath a « spacing from
the conductor that it embraces equal Uo the mean
radius of the sheath, When no other current:
carrying
sheath voltage gradients for a group of eables in
any formation
voltage gra
(a pa)
tre)
by
a
sf
#1 B toe ( $ | vm
(Eq D4)
= ols (210) [ 4 og, ( 282.
vw. ( 88¢)] vm
(Eq DB)
where
‘d_® yeometrie mean sheath diameter (arith-
metic mean may be assumed)
Sup = axial spacing of phases « and b
‘Sie = axial spacing of phases 6 and ¢
s.
fe = axial spacing of phases @ and ©
20
ansvinee
pis SMEATIBS sd 875 1085
2.2 Trefoll Formation Single Cireult. For
cables in trefoil where 8, ~ Sy. = Sye these equa
ets (2109)( $412) (23) vn
cea
be
= jot, (210-7) fo, (7) vm (ea07)
(on om
(Eq D8)
2.8 Plat Formation Singte Clreult. For th
‘ther common formation of cables laid nt
‘which the axial spacing of adjacent exbl
sheath voltage gradients are given by
Vr
Ba! vm
+a (20°]( i S05
(a D9)
Fon(2107) og, 28 wim env)
8
vf
Bo!) ym
abu)
24 Double-Cireult Systems. 11s imposable in
this text to cover all possible combinations of
geometry for multiple circuits but a solution toa
simple parallel double circuit is given below.
Assumptions
(2) Three or six eables are connected in three
phase eireuite
(2) All conductor currents are equal in may:
nitude
(@) For three eables — any arrangement Is
permissible
For six cables — point or line symmetry is
assumed
‘This means a line 0-0 oF a point 0 may be placed
‘Auhorued ceed ote lined lo: UNVERSITE PAUL SABKTIER TOULOUSE 3. Oounisdet an Novebir 262010 st 084049UTC fom EEE Xplue.Restlstens apansi6ee,
Suse
between’ the two circuits $0 that the distance
rom cable al to 0 equals the distance from cable
a2to0
where
al = a phase of Citeuit 1
‘a2 ~ @ phase of Gireult 2
nust be Lrue for cables BL and 62 and
cel and c2
(4) Poskive phase sequence rotation (phase a
leadit
2) was assurned in the equations. The effect
ence can be simulated on
ny interchanging cable pos:
nd 4 and 6 in the context
iWions t and 3
through 5p.
Conductor currents are as follows:
ir
LE gape eto)
L
ae
1 +5 0 assigned to cables 2 and 6) }S-1
(3 assigned to cables and 6)
saths to neutral are
Open cireui
1s follows:
Bag atau + fy*iKas Tet ae
By = La iRay + Le ihig + Leia
Big = tahoe tla ae +1 Soe
where
voltages ©
82
Koy K loge
83
a constant
2.08 10-7
distance froin cable 1 to cable 2
distance from cable 2 to cable 3
20
SHEATIEDONDING NETHODS FOR SINGL-CONDUCTOR CABLES AND TH
4 * distance from cable I to cable 3
Sig = distance from cable 1 to cable 4
‘Sig ~ distance from cable 2 to cable 6
‘Sop = distance from cable 3 to cable 6
Sip = distance from cable | to cable 6
‘Spy = distance from cable 3 to cable 6
‘Sip = distance from cable 1 (o cable 6
yg > mean sheath radios (meters)
Figure 1 of this guide shows values of the
sheath voltage gradient cateulated from the equa
tions in D2 (1), 2),(),and (4) for asinglecircult
inboth trefoil and fla formatton of te cables aga
fanction of the eatio S/d.
DS. Screening and Transposition
“The woltnge gradients calculated by the equa:
tdowe in D2 are due to the magnetic fek! of the
Uivee-phase earrents only, When any other eur
rent-cartying conductors ace inthe vicinity, these
voltages will be modifted, In particular, if any
parallel eonductor is present, which is bonded so
fas to carry induced current, then the vollage gra-
dient in any other paralle! conductor will be
reduced, This ceduction depends on the disposi
tion of the conductors and the impedance of the
current-carrying loop of which the screening
eonductor forms a part
Power cables frequently have communication
co protection cables laid with them in the same
treneh,
roinimom t
cables, When the sheaths of single conductor
power cables are continuous ond grounded at
both ends of the route, they act as screening con
‘ductors and thus reduce somewhat the voltage
induction in the parallel cables. In a specially
bonded syater, however, the power cable sheaths
no longer earry currents, and hence the sereening
fffect is absent, at least for balanced loads in the
power eables (During imbalanced loads or Faults,
Sheath eurrents will flow in the case of eros
bonded eables, and henee an important sereening
effect is present in this case. There wilt atso goner
ally'be a screening effect duc to the sheath or
tarmoe wices of the parallel cable ise)
‘The voltage Induction in parallel eabtes result
i from balanced loads can be reduced or elimi
nated by transposition, and this Is particularly
desirabte for specially bonded cables for the rea
sons given above, Transposition has the ud
tional advantage of balancing the impedances of
ator teense lea: UNIVERGITE PAUL SABATIER TOULOUGE:3. Donna en November 25,2010 at 54040 UIC WomIEEE Koos, Resticions sry.‘CALCULATION ar IIDUCED VOLTAGES AND CURRENTS I CARLE SHEATHS
the three-phase cables The transposition of heavy
ower cables is not generally practicable except
at joint positions, however, and hence tle com
plote transposition eycte ofthe three ph
‘oceupy three eable lengths. For eable cr
consist of only one oF to tengths, tis not asia!
{0 transpose the power cables, but the parallel
‘condduetor may be transposed as indicated below,
Figare 2 shows the methods to be used for
{transposition of the parale) cable or conductor
When the power cables are lid in lat formation
with wide spacing, the parallel conductor should
be between che power eables at the position
shown. If tere is insufficient space between the
power cable to ailopt this position precisely, the
parallel conductor should still be between the
Power cubles. If the cables are touching or in
trefoil, the parallel conductor should be taid
Immediately alongside the power cables. fn all
cases the parallel conductor should be trans-
posed at the center ofthe seetion length oF route
length to an identical position on the other side of
the formation
axsuvce
sas ie
D4, Sheath Standing Voltages
(see 69.2),
‘The bso corresponding vector dingeains for the
‘ross bonded sections are
For Figs 5 and 6
For Figs 8 ond 9
On both diagrams, point A corresponds to the
‘gronnded positions. Inthe first diagram the max
fanum standing voltage wil occur at paint B ands
of magnitude E, whereas in the second clagram,
the maximum standing voltage willoceur at point
C and fs of magnitude /3/2 £, then the valeage
reduetion is (1 ~ 8/2) 100% or 12.4%,
Appondix E
‘Transient Vollages and Voltage Withstand
Requirements of Protective Jackets
Power Frequency Sheath Overvoltages
EL, General
System fants produce an
voltage followed by
‘overvoltnge caused by the passage of the fault
current. This power frequency overvoltage fs not
‘generally high enough to be important in relation
{othe sheath insulation desiga, bu, as it persists
forthe duration of the faut, ie may be important
Inrelation tothe duty requirementsof the sheath
voltage limikers,
at
Annet ensue etd to: UNIVERSITE PAUL SABATIER TOULOUSE Dowels
‘Thecable installation must cleurly be capable of
safely withstanding the effects of any fault in the
ayatem external tothe cables. A faultin the cables
themselves inevitably involves repalr work and
hhence ic is not so important i che sheath insite
tion adjacent to the fault is also damaged, The
sheath bonding dosign should preclude the dam-
‘age cascading to other parts ofthe cable systen
Following system faults, sheath voltage liniters
ray be damaged, requiring inspection and possi-
Die replacement. ‘The sheath voltage gradients
oven: 25,2010 ot 0240.401UTE Hom EEE Kolo. Rescans ay,$10 76-1098
‘due to external faults of three types
ELL Three-phase symmettica faut,
E12 Phase-to-phase fault
EL Single-phase ground fault
‘are given ia the equations of €3.1, 3.2, and B33.
In deriving these equations, te following simpli.
fying assurmptfons are made:
(1) The shortcireuit current is kaown and is
unaffected in value by the characteristics of the
ceable system,
(2) For fault of type B1.2 and 1.3 the current
In the healthy phase conductor(s) Is negligible in
‘comparison with the short-cireult current, except
for the case of impedance grounding of the neu-
tral (see B2).
(8) No other sercening conductors are preset
(except for the parallel ground continuity com:
‘ductor inthe ease of faults of type B13 in single.
point bonded systems),
sists of balanced minor and
alized eros
bonding and a number of uniform minor sections
exactly divisible hy three the case of continuous
cross bonding. (For design purposes, itis satisfac-
tory to use these simplified equations also (or
practical systems in whieh imbalance does exist.)
Ez, Neutral Grounding
For faults of type BLL and B12, no zero.
sequence current flows. The equations given
in E3 for faults of this type are therefore equally
applicable to systems having the neutral ditectly
grounded or to those having impedance or reso
nant grounding of the system.
For faults of type E13 in systems having impe
dance of resonant grounding, iL1s no longer per
tmissible Co ignore the normal fond eutre
system, The ealculation of sheath voltages dri
Superposition of the voltages due to the symmet-
tical positive sequence load currents and those
‘due to the fault currents. The voltages due ta the
Fault current can aso be calculated by consider
ing te agyrametrical fault eurrents as te super
posttion of wn asymmetrical positive sequence
system and a zero-sequence system with currents,
ff the same magnitude, The superposition of
these currents results in to currents of equal
‘magnitude but separated in phase by an angle
SEATILWONDING METHIONS FOR SINGLE-CONDUCTOR CABLES AND THE
‘of 60° flowing in the unfauited phases, white
the faulted phase remains without current. The
sheath vokages resulting from these currents ean
all beealeulated from the following equations an
superimposed, However, in general, for systems
having impedance or resonant grounding of th
neutral, the sleath voltages resulting from faults
of type E1.3 willbe much lower than those due to
faults of type E2.1 and BL2, and hence for design
purposes faults of type EL In these systems can
De ignored.
£8, Single-Point Bonding
9,1 ThreePhase Symmetrical Fault. The
sheath voltage gradients are given n Appendix D,
2, wsing the appropriate value off
B52 Phase-to-Phase Fault. In the general case
of any cable formation, assuming a ful betwee!
phases a and b with no yround current flowing,
‘when J Js the Fault current, the sheath
arodients ace
25S
= Jal 2107) m4, 232 vn cou
aly 107) 9, 25% vim aD
5, = ty 210%) tg, SE Vin (Bab)
EA SinglePhose Ground Fault (Solidly
Growided Novitral), Precise calculation ofsheath
covervoltages under ground-fautt conditions ve
‘quires a knowiedge ofthe proportion ofthe return
feureent that fhows In the ground itself and the
proportion that returns by way of the parallel
round continuity conductor. This depends on a
number of factors, whieh are not usually accu.
rately known, Fortunately, however, the over
voltages of practical interest are those between
sheaths and the parallel ground continuity con
id these can be simply ealeulated by the
Assumption that this conductor earries the whole
ff the return current, This assumption is tor
mally accurate and leads to sheath evervoltayes
that are slightly higher then those observed in
practice
For a ground fault in phase « and the generat
‘case of any eable formation, when fog is the Fave
‘the sheath to ground conductor voltages
pulpit tcensed use ito: UNVERSITE PAUL EABATIER TOULOUSE 3 Cantons on Novenbe 2.701011 094040 UTC fom IEEE Xe
Resistor optans
‘Sa 67e 108 SHEATIADONDING METHODS FOR SINGLE CONDUCTOR CAILES AND 1H
' 2 3 4 8 678 2 3 4 6 6280
520
440 F once ounce
TO.GROUNO Faw.
200
pase ro niase
THE ruase
SYAIMETRICAL FAULT
i TT See 230
ano 8/4
Fig BL
Induced Sheath Voltage Gradient (Sheath-{o-Ground Conductor) for Varlous Faults In
‘Single Point Bonded-Cable System (Flat Formation)
+ ct09 2 | vm
(eae
+ oath S888) im
(Ba 05)
+ 5210-7) to, S80] vin
(89 86)
‘Aue teenseduse lmtedo: UNERSITE PALL SABATIE TOULOUSE’ Domlaaded a Nove 25,2010 1 0240.40 JTC om EE Xplore. Reticle sry
Say Siqs Sy Keometric mean spacings be
‘ween cables a, b, and ¢, respec-
tively, and che ground conductor
Ry = resistance of grow
om
‘= geometric meen radius of ground
conductor (for stranded conde
tors take 0.75 overall radius)
E34 Magnitude of Voltages. Typieal maxiiuan
values of sheath voltages calculated from these
33‘CALEULSTION OF INDUCED VOLTAOES AND CURRENTS IN CADLE SIEATHS
‘equations are given in Fig EL for a elreutt In dat
formation, for # current of 1000 A having a
transposed ground conductor. For a three-phase
symmetrical fault, the maximum voltage is
reached in the outer cables and Is the samme 29 it
Fig | of this guide but increased for higher cur:
rent, For the phase-to-phase fault, the highest
sheath voltage reaults when the fault is between
the outer cables so that 5,. = 28. For a ground
fault assuming the ground conductor to be laid as
shown in Fig 2 of this guide
Bog = Sig 2 S
Sig = O78. (eae
‘The highest of the three shesth voltages for a
fault in phase a is B,, and since the effect of fy
‘can generally be neglected the above equation for
B, can be expressed as
K,
sat 21079 (8)
(Eq B8)
sree a tere ee
eee ae
a8 1098
E4, Cross Bonding
E41 ThreePhase Symmetrleal Fault, ‘The
sheath voltage gradients are given by Appendix D,
'D23, Bas D9, D1O, and DIL, using the appropriate
value of f and using the longest minor section
length in the case of sectionallzed cross bonding
‘oF continuous cross bonding
FA Phaseto-Phase Fault. This ts « balanced
condition as regards induced sheath voltages, and
hence no sheath current fovs. The sheath voltage
‘gradients at the eross-bonding points areas glven
by 63:2 equations, using the longest mnor section
length in the case of sectionallzed cross bonding
‘or continuous cross bonding.
£4. SinglePhase Ground Fault. In thls case,
the returning current divides between the sheaths
and ground, and the caleuation of sheath voltages
becomes more complex.'The effect of the ground
currents ts important ih relatlon to the voltages
between sheaths and ground, and to calculate
these it is necessary to know tie values of ground
resistivity and of ground plate resistance appro-
printe to the circult, The voltages between sheaths.
fan be calculated as follows for a sectlonalized
‘eross bonded aystem (The behavlor of continu
‘ously cross-bonded cables during faults of this
type le stil being studied).
TEAA.1 Cables In Trefoll, Figure E2 shows a
single major section of eables in trefoll having the
Fig B2
si
‘won Section to
i a vt
Je Major Sectlon of Cross Bonded Cables During Single-Phase Fault
See eee
un |v
ws
cy
_auonued ices ute vedo: UMIVERSITE PAUL SABATIER TOULOUSE 3. Douroaed or November 28,2010 80840 <0 UTC Hom IEEE Xpre. Reston py‘CALAULATION OF IVDLICED VOLENGES AND CURRENTS IN CADLE SHAT
sheaths grounded at both ends,
‘A curvent 1, circulates in the path formed by
the three sheaths and the ground and divides
equally between the three sheath eircules
“The voltages induced In the three sheaths of Fig
82, minor Section No 1 are a3 follows:
8- Barta 1,
R) Wim
Cag 4 Bg) ~ Hy Vien
B= By Vim
where
T+
current as shown in Fig E2
‘The voltages etween sheaths at the cross
bhonating points are then
2+) V
Vy = May
YO V
Veg © Mag = Bay * RA) V
where
Zu = seltimpedance of sheath with ground
160240" (2)
2g = tant tat wt pond
aon aa
R, = resistance of sheath (A/mn)
length of minor section (1m)
‘These Impedances are functions of frequency
and of ground resistivity but in these equations
this factor disappears and
Mg = tt 2107) (38)
meno
E482 Cables In Plat Formation. When the
‘cables are lafd fat, the current no longer divides
equally between the sheaths, butitean be assumed
to do 90 with litle error. Assuming also that the
‘ground plate reslstanees are zero
avavtees:
sd 76-188
where
= matual impedance between sheaths of
outer cables with ground return (0/m)
eae ee gs
Zayy = mutwal impedance between sheaths of
inner and outer cables with ground
return (A/m)
1
Jo (210°) logy 5
ten
By El Boog? Bat) HE Ra) Wm
4 y-8tuy)- Ihe Wm
4g Bing Ba) Th Ws
[fan on) +1 lay by Ba] V
tee Uf ra Ba) * Hae 2)| v
aI : Cn Re-2a)} v
‘and substituting for Fin the equattons for Va, Yo
Mar 9 [ae Bly Bea +3) 3) V
(Coig~ Zong)
Wag © Bey * Tag
ning Ry can generally he
P-
and all terms cont
disregarded,
‘Then
-jtt 210° oge{ 28S.) y
Mog = Jolt (2.10°7) lox, (2) -V
t= wnase, (8) v
rs
‘Authorize ens woe 1: UNVERSITE PAUL SABATIER TOULOUSE 3, Dewan on November 2520101094049 UTC Kem FEE Xp, Resicons oprANSHIEEE
Sire oe
' 2 2 4 se 7reer 2 3.4 8 oF a8
0
PuAse-TO.PHASE
PAUL unce mance,
200
Einvim 1= 10008
20
20
Fly E3
Maximum Induced Sheath Voltage Gradtents (Sheath to Sheath) for
Various Faults in Sectionalized Croas-Bortded Cable System (Fiat Formation)
BAA Maguitude of Vollages. Figure BD shows
these voltages between slioaths atthe eross-bond
positon per unit length of I m of the minor sec:
tion Tength caleulited from the equations above
for single-phase faults and compared with the
voltages due to three-phase aymmetrieal Faults
and for phase-to-phase faults and for a short
cirevit eurtent of 1000 A. IL fs evident that the
voltage due (o the phaseto-phase fault is the
est,
ie sheath voltage limiter generally cansists of
fa star connected device having the star point
grounded to a local ground. The resistance of
These local ground plates are often high but some
‘currant will Now into the ground during a single-
36
phase fault, The calculation of these currents and
‘oF the vollages between the sheaths and the
{ground plates is complex and requires a kaovt
edge of the ground-plate resistances and the
ground resistivity along the eable route, These
Values are not generally known, especially at the
‘design stage, and hence itis usual to consider the
duty of the sheath voltage miter only in terms of
the voltage between sheaths, Experience and
‘measurements indicate that the sheath-to-ground
vollage rise Is not generally sufficient to damage
the sheathe-vottage limiver, but, when there is any
doubt, the star point should not be grounded,
‘hen tis is permissible, with respeet to trarstent
overvoltages.
aonzed head use tas to: UNVERSITE PAUL SABATIER TOULOUSE 3. Connooted on Novena 25,2010 84040 TE fom FEE Koo, Recto opp