Battery testing Report (AVADI)

Start time : 11.30 AM 13V*24 312 V full charge battery


Stop time : 12.05 PM 12V*24 288 V
O/P Amp - 8.1A 10.5V*24 252 V Low battery
battery volt battery volt
sno Low battery
in mains mains off
1 13.10 11.97 10.40 V
2 13.09 11.95 10.32 V
3 13.05 11.93 10.22 V
4 13.08 11.94 10.42 V
5 13.04 11.91 10.32 V
6 13.06 11.95 9.89 V
7 13.02 11.90 10.10 V
8 13.05 11.93 10.00 V
9 13.09 11.90 9.88 V
10 13.03 11.92 9.99 V
11 13.06 11.95 10.50 V
12 13.05 11.91 9.91 V
13 13.04 11.96 9.81 V
14 13.06 11.90 9.99 V
15 open
16 13.08 11.92 10.20 V
17 13.11 11.89 10.10 V
18 13.06 11.91 9.89 V
19 13.02 11.98 10.02 V
20 13.05 11.90 10.10 V
21 13.06 11.92 10.34 V
22 13.08 11.89 10.23 V
23 13.09 11.85 10.42 V
24 open V
25 13.06 11.92 10.60 V
26 13.05 11.89 10.28 V
313.48 286.09 243.93 V

from 13V to 12V time taken is 22 minus.


from 12V to 10.5 (low battery )V
time taken is 10 minus.

Total backup time comes only 32 minus.