Tracer CH530™
Control System for Chillers
RTWD/RTUD 060-250
RLC-SVU05A-E4
General information
Warranty Training
Warranty is based on the general To assist you in obtaining the best
terms and conditions of the use of it and maintaining it in
manufacturer. The warranty is void perfect operating condition over a
if the equipment is repaired or long period of time, the
modified without the written manufacturer has at your disposal a
approval of the manufacturer, if the refrigeration and air conditioning
operating limits are exceeded or if service school. The principal aim of
the control system or the electrical this is to give operators and
wiring is modified. Damage due to technicians a better knowledge of
misuse, lack of maintenance or the equipment they are using, or
failure to comply with the that is under their charge. Emphasis
manufacturer's instructions or is particularly given to the
recommendations is not covered by importance of periodic checks on
the warranty obligation. If the user the unit operating parameters as
does not conform to the rules of well as on preventive maintenance,
this manual, it may entail which reduces the cost of owning
cancellation of warranty and the unit by avoiding serious and
liabilities by the manufacturer. costly breakdown.
Maintenance contract
It is strongly recommended that you
sign a maintenance contract with
your local Service Agency. This
contract provides regular
maintenance of your installation by
a specialist in our equipment.
Regular maintenance ensures that
any malfunction is detected and
corrected in good time and
minimizes the possibility that
serious damage will occur. Finally,
regular maintenance ensures the
maximum operating life of your
equipment. We would remind you
that failure to respect these
installation and maintenance
instructions may result in
immediate cancellation of the
warranty.
RLC-SVU05A-E4 3
Contents
General Information 2
Overview 5
DynaView Interface 6
Display Screens 8
Diagnostics 28
TechView Interface 54
Software Download 55
4 RLC-SVU05A-E4
Overview
The Trane CH530 control system The CH530 uses the IPC3 protocol
that runs the chiller consists of based on RS485 signal technology
several elements: and communicating at 19.2 Kbaud
• The main processor collects to allow 3 rounds of data per
data, status, and diagnostic second on a 64-device network.
information and communicates Most diagnostics are handled by the
commands to the LLID (for Low DynaView. If a temperature or
Level Intelligent Device) bus. The pressure is reported out of range by
main processor has an integral a LLID, the DynaView processes this
display (DynaView).
information and calls out the
• LLID bus. The main processor diagnostic. The individual LLIDs are
communicates to each input and
not responsible for any diagnostic
output device (e.g. temperature
and pressure sensors, low functions.
voltage binary inputs, analog Note: It is imperative that the CH530
input/output) all connected to a Service Tool (TechView) be used to
four-wire bus, rather than the facilitate the replacement of any
conventional control architecture LLID or reconfigure any chiller
of signal wires for each device. component.
• The communication interface to
a building automation system
(BAS). Controls Interface
• A service tool to provide all DynaView (picture on cover)
service/maintenance capabilities.
Main processor and service tool Each chiller is equipped with the
(TechView) software is DynaView interface. DynaView has
downloadable from the capability to display additional
www.Trane.com. The process is information to the advanced
discussed later in this section operator including the ability to
under TechView Interface. adjust settings. Multiple screens are
DynaView provides bus available and text is presented in
management. It has the task of multiple languages as factory-
restarting the link, or filling in for ordered or can be easily
what it sees as "missing" devices downloaded online.
when normal communications
has been degraded. Use of
TechView may be required. TechView
TechView can be connected to the
DynaView module and provides
further data, adjustment
capabilities, diagnostics
information, downloadable
software, and downloadable
languages.
RLC-SVU05A-E4 5
DynaView Interface
Figure 1
Figure 2
6 RLC-SVU05A-E4
DynaView Interface
The second screen (Figure 3) will The third screen is the first screen
display for 15-25 seconds. If a valid of the application.
configuration is present, "Tracer
CH530" will also be displayed. If the
MP configuration is found to be
invalid, "MP: Invalid Configuration"
is displayed indefinitely. Contact
your local Trane service technician.
Figure 3
Figure 4
RLC-SVU05A-E4 7
DynaView Interface
Display Screens
The main body of the screen is used
for description text, data, setpoints,
or keys (touch sensitive areas). The
Chiller Mode is displayed here.
A double arrow pointing to the right
indicates more information is
available about the specific item on
that same line. Pressing it will bring
you to a sub-screen that will
present the information or allow
changes to settings.
8 RLC-SVU05A-E4
DynaView Interface
The bottom of the screen (7) is Touching the AUTO key will enable Keypad/Display Lockout
present in all screens and contains the chiller if no diagnostic is
the following functions. The present. (A separate action must be
Feature
contrast (8,9) may require re- taken to clear active diagnostics.) Note: The DynaView display and
adjustment at ambient The AUTO and STOP keys take Touch Screen Lock screen is shown
temperatures significantly different precedence over the Enter and above. This screen is used if the
from those present at last Cancel keys. (While a setting is Display and touch screen and lock
adjustment. The other functions are being changed, AUTO and STOP feature is enabled. Thirty minutes
critical to machine operation. The keys are recognized even if Enter or after the last keystroke, this screen
AUTO and STOP keys are used to Cancel has not been pressed.) The is displayed and the Display and
enable or disable the chiller. The ALARMS button appears only when Touch Screen is locked out until the
key selected is in black (reverse an alarm is present, and blinks (by sequence "159 <ENTER>" is
video). The chiller will stop when alternating between normal and pressed. Until the proper password
the STOP key is touched and after reverse video) to draw attention to is entered, there will be no access
completing the Run Unload mode. a diagnostic condition. Pressing the to the DynaView screens including
ALARMS button takes you to the all reports, setpoints, and
corresponding tab for additional Auto/Stop/Alarms/Interlocks. The
information. password "159" can not be changed
from either DynaView or TechView.
Note: screens may differ according For setting changes, use the
to unit type or configuration. They password "314 <ENTER>".
should be considered as examples.
RLC-SVU05A-E4 9
DynaView Interface
Auto Stop
10 RLC-SVU05A-E4
DynaView Interface
Chiller Mode Touching the double arrow to the Active Water Setpoint Arbitration
The machine-operating mode left of the Active Chilled Water Subscreen
indicates the operational status of Setpoint or to the left of the Active The active water setpoint is that
the chiller. A subscreen with Hot Water Setpoint will take the setpoint to which the unit is
additional mode summary user to the respective active water currently controlling. It is the result
information will be provided by setpoint arbitration sub-screen. of arbitration between the front
selection of an additional panel, BAS, and external setpoints.
information icon (>>). The The active chilled water water
operating mode line will remain setpoint may also be subjected to a
stationary while the remaining form of chilled water reset.
status items scroll with the up/down
arrow keys.
Active Chilled Water Setpoint and Figure 8 - Active Chilled Water Subscreen
Active Hot Water Setpoint
The active chilled water setpoint is
the setpoint that is used in cool
mode. The active hot water setpoint
is the setpoint that is used in heat
mode. Both setpoints result from
the logical hierarchy of setpoint
arbitration by the main processor.
The water setpoint will be displayed
to 0.1 degrees Fahrenheit or
Celsius. :
RLC-SVU05A-E4 11
DynaView Interface
12 RLC-SVU05A-E4
DynaView Interface
Local Stop Chiller is stopped by the DynaView Stop button command- cannot be remotely overridden.
Chiller is stopped by the DynaView Immediate Stop (by pressing the Stop then Immediate Stop
Immediate Stop
buttons in succession) - previous shutdown was manually commanded to shutdown immediately.
No Circuits Available The entire chiller is stopped by circuit diagnostics or lockouts that may automatically clear.
Diagnostic Shutdown - Manual Reset The chiller is stopped by a diagnostic that requires manual intervention to reset.
Only possible when Condenser Head Pressure Control option is enabled and the condenser pump is
Cond Pmp Strt Dly (Head Pres Ctrl) min:sec being manually commanded to run - this wait may be necessary due to the Head Pressure control
device's stroke time.
The chiller is currently being inhibited from starting (and running), but may be allowed to start if the
Run Inhibit
inhibiting or diagnostic condition is cleared.
No Circuits Available The entire chiller is stopped by circuit diagnostics or lockouts that may automatically clear.
The chiller is inhibited from running as the Ice Building process has been normally terminated on the
Ice Building Is Complete evaporator entering temperature. The chiller will not start unless the ice building command (hardwired
input or Building Automation System command) is removed or cycled.
The chiller is inhibited from running for a brief period of time if it is commanded from active ice
building mode into normal cooling mode via the ice building hardwired input or Tracer. This allows time
Ice to Normal Transition for the external system load to "switchover" from an ice bank to the chilled water loop, and provides for
a controlled pull down of the loop's warmer temperature. This mode is not seen if the ice making is
automatically terminated on return brine temperature per the mode below.
Start(ing is)* Inhibited by External Source The chiller is inhibited from starting or running by the "external stop" hardwired input.
Diagnostic Shutdown - Auto Reset The entire chiller is stopped by a diagnostic that may automatically clear.
Waiting for BAS Communications (to Establish The chiller is inhibited because of lack of communication with the BAS. This is only valid 15 minutes
Operating Status)* after power up.
Start(ing is)* Inhibited by Local Schedule The chiller is inhibited from starting based on the local time of day scheduling (option)
RLC-SVU05A-E4 13
DynaView Interface
The chiller is not currently running but can be expected to start at any moment given that the proper
Auto
conditions and interlocks are satisfied.
Auto Sub Modes Description
The unit will wait up to 20 minutes in this mode for water flow to be established per the flow switch
Waiting For Evap(orator)* Water Flow
hardwired input.
The chiller will wait indefinitely in this mode, for a leaving water temperature higher than the Chilled
Waiting For A Need To Cool
Water Setpoint plus some control dead-band.
The chiller will wait indefinitely in this mode, for a leaving water temperature lower than the Hot Water
Waiting For A Need To Heat
Setpoint plus some control dead-band.
Power Up Delay Inhibit: min:sec On Power up, the chiller will wait for the Power Up Delay Timer to expire.
The chiller is not currently running and there is a call for cooling but the lead circuit start is delayed by
Waiting to Start
certain interlocks or proofs. Further information is provided by the sub-mode:
Waiting to Start
Description
Sub Modes
The chiller will wait up to 4 minutes in this mode for condenser water flow to be established per the
Waiting For Condenser Water Flow
flow switch hardwired input.
The chiller will wait up to 30 minutes (user adjustable) in this mode for to allow the condenser water
Cond Water Pump PreRun Time min:sec
loop to equalize in temperature
Only possible when Condenser Head Pressure Control option is enabled, this wait may be necessary
Cond Pmp Strt Dly (Head Pres Ctrl) min:sec
due to the Head Pressure control device's stroke time.
Only possible when Condenser Head Pressure Control option is enabled, this wait may be necessary
Cprsr Strt Delay (Head Pres Ctrl) min:sec
due to the Head Pressure control device's stroke time
At least one circuit on the chiller is currently running, but the operation of any of the circuits on the
chiller is being actively limited by a chiller level limit. Other sub modes that apply to the Chiller
Running - Limit
Running top level modes may also be displayed here. Refer to the list of circuit limit modes for circuit
limits that will cause display of this Chiller Level Running Limit mode.
Running - Limit
Description
Sub Modes
Design Note: Hot Start Limit is applied and annunciated at a circuit level, even though it is based on
<none applicable>
the chiller's leaving water temperature.
14 RLC-SVU05A-E4
DynaView Interface
The chiller is still running but shutdown is imminent. The chiller is going through a compressor run-
Shutting Down unload or extended operational pumpdown of the lag circuit/compressor (or all circuits
simultaneously).
Shutting Down Sub Modes Description
The lag circuit (or all circuits) is in the process shutting down by performing an operational pumpdown
just prior to stopping the circuit's compressor. The EXV is commanded closed. Pumpdown will
Operational Pumpdown
terminate when both the liquid level and the evap pressure are low (below specific criteria) or after a
specific time has expired.
The Evaporator water pump is continuing to run past the shutdown of the compressors, executing the
Evaporator Water Pump Off Delay: MIN:SEC
pump off delay timer.
The Condenser water pump is continuing to run past the shutdown of the compressors, executing the
Cond Water Pump Off Delay: MIN:SEC
pump off delay timer.
Chiller Level Mode
Misc. These sub modes may be displayed in most of the top level chiller modes
Misc. Sub Modes Description
Manual Evap(orator)* Water Pump Override The Evaporator water pump relay is on due to a manual command.
Diagnostic Evap Water Pump Override The Evaporator water pump relay is on due to a diagnostic.
Diagnostic Cond Water Pump Override The Condenser water pump relay is on due to a diagnostic.
The local time of day scheduler (option) is operational and could automatically change modes or
Local Schedule Active
setpoints as scheduled
Manual Condenser Water Pump Override The condenser water pump relay is on due to a manual command.
Manual Compressor Control Signal Chiller capacity control is being controlled by DynaView or TechView.
The Night Noise Setback feature has been activated. If the unit is running, fans will be running at low
Night Noise Setback
speed.
Hot Water Control
These modes are mutually exclusive and they indicate that the chiller is controlling to the active hot
Chilled Water Control
water setpoint, the active chilled water setpoint, or the active ice termination setpoint respectively.
Ice Building
RLC-SVU05A-E4 15
DynaView Interface
16 RLC-SVU05A-E4
DynaView Interface
The following modes annunciations have not been implemented as a display but are actually operational in the EXV liquid level control algorithm. The
modes included here as possible future annunciated modes
Liquid level control of the Electronic Expansion Valve has temporarily been suspended. The EXV is
being modulated to control for a minimum differential pressure. This control implies low liquid levels
EXV Controlling Differential Pressure and higher approach temperatures, but only as is necessary to provide minimum oil flow for the
compressor until the condenser water loop can warm up to approx 50F. (Future mode display - display
of mode not implemented in Phase 1 or 2 although present in algorithms.)
Liquid level control of the Electronic Expansion Valve has temporarily been suspended. The EXV is
being modulated to control for a minimum evaporator pressure that is based of the pressure of the
Low Refrigerant Temperature Cutout. This control will tend to increase the liquid level above the
EXV Controlling for Low Evaporator Pressure setpoint or to open the valve more quickly than liquid level control can, in order to avoid an LRTC trip.
It is most often invoked transiently to help open the EXV in the event of rapidly falling liquid level and
rapidly declining evaporator pressures. (Future Mode display, - display of mode not implemented in
Phase 1 or 2 although present in algorithms.)
Circuit Level Mode
The circuit, and compressor are currently running, but the operation of the chiller/compressor is being
Running - Limit actively limited by the controls. Further information is provided by the sub-mode.* See the section
below regarding criteria for annunciation of limit modes
Running - Limit
Description
Sub Modes
The compressor is running and its capacity is being limited by high currents. The current limit setting
Current Limit is 120% RLA (to avoid overcurrent trips) or lower as set by the compressor's "share" of the active
current limit (demand limit) setting for the entire chiller.*
The circuit is experiencing condenser pressures at or near the condenser limit setting. Compressors
High Condenser Pressure Limit
on the circuit will be unloaded to prevent exceeding the limits.*
The circuit is experiencing saturated evaporator temperatures at or near the Low Refrigerant
Low Evaporator Rfgt Temperature Limit
Temperature Cutout setting. Compressors on the circuit will be unloaded to prevent tripping. *
This mode will occur if the leaving evaporator water temperature exceeds 75F (for SW version 6.30
and earlier) or 90 F (for software 7.01 and later) at the point at which the step load for the respective
circuit would be desired. This is often the case in a high water temperature pulldown. While in this
mode, no compressor on the circuit will be allowed to load past its minimum load capacity step, but it
Hot Start Limit
will not inhibit other compressors from staging on. This mode is necessary to prevent nuisance trips
due to Compressor Overcurrent or High Pressure Cutout. Reasonable pulldown rates can still be
expected despite this limit, since the compressor's capacity even at partial load is much greater at
high suction temperatures.
RLC-SVU05A-E4 17
DynaView Interface
The circuit is in the process shutting down by performing an operational pumpdown just prior to
stopping the last running compressor. The EXV is commanded closed. Pumpdown will terminate
Operational Pumpdown
when both the liquid level and the evap pressure are low (below specific criteria) or after a specific
time has expired.
The compressor is in its run unload time. The number of seconds remaining in run unload is shown in
Compressor Unloading: MIN:SEC
the submode. The run unload time must expire before the compressor will shut down.
Circuit Level Mode
Top Level Mode Description
Misc. These sub modes may be displayed in most of the top level circuit modes
Restart Time Inhibit: MIN:SEC If there is accumulated Restart Inhibit Time, it must expire before a compressor is allowed to start.
* Mode text strings in parenthesis for TechView display only - available space for DynaView text strings is limited.
18 RLC-SVU05A-E4
DynaView Interface
RLC-SVU05A-E4 19
DynaView Interface
20 RLC-SVU05A-E4
DynaView Interface
RLC-SVU05A-E4 21
DynaView Interface
Settings Screen
The Settings screen provides a user
the ability to adjust settings justified
to support daily tasks. The layout
provides a list of sub-menus,
organized by typical subsystem.
This organization allows each
subscreen to be shorter in length
which should improve the users
navigation.
Unit
Feature Settings
Control Settings
Manual Control Settings
Display Settings
Settings Menu
Description
1. Chiller
2. Feature Settings
3. Manual Control Settings
4. Display Settings
22 RLC-SVU05A-E4
DynaView Interface
Chiller
Description Resolution or (Enumerations), Units
Default
1. Front Panel Cool/Heat Command (Cool, Heat), Cool Enum
2. Front Panel Chilled Water Setpt (2) Temperature
+ XXX.X
3. Front Panel Hot Water Setpt (2) Temperature
+ XXX.X
4. Front Panel Current Limit Setpt 1 %RLA
5. Front Panel Ice Build Cmd On/Auto Enum
6. Front Panel Ice Termination Setpoint XXX.X Temperature
7. Setpoint Source (BAS/Ext/FP, Ext/ Front Panel, Enum
Front Panel), BAS/Ext/FP
8. Leaving Water Temp Cutout XX.X Temperature
9. Low Refrigerant Temp Cutout XX.X Temperature
10. Staging Sequence (Bal Starts/Hrs, Fixed), Bal Starts/Hrs Enum
11. Condenser Pump Prestart Time XX , 0 minutes
Feature Settings
Note: Purple Box Designates Phase 2 Air Cooled RTUD items.
Description Resolution or (Enumerations), Units
Default
1. Cooling Low Ambient Lockout (Enable, Disable), Enable Enum
1a. Cooling Low Ambient Lockout (Enable, Disable), Enable Enum
1b. Cooling Low Amb Lockout Setpt XXX.X Temperature
2. Noise Setback Command (Auto, On, Schedule), Auto Enum
3. Ice Building (Enable, Disable), Disable Enum
4. Ext Chilled/Hot Water Setpt (Enable, Disable), Disable Enum
5. Ext Current Limit Setpoint (Enable, Disable), Disable Enum
6 Chilled Water Reset (Const Return, Outdoor,
Return, Disable), Disable
6a. Chilled Water Reset (Const Return, Outdoor, Enum
Return, Disable), Disable
6b. Return Reset Ratio XXX Percent
6c. Return Start Reset XXX.X Temperature
6d. Return Maximum Reset XXX.X Temperature
6e. Outdoor Reset Ratio XXX Percent
6f. Outdoor Start Reset XXX.X Temperature
6g. Outdoor Maximum Reset XXX.X Temperature
7. LCI-C Diag Language (English, Selection 2, Enum
Selection 3) English (0)
8. LCI-C Diag Encoding (Text, Code) Text Enum
Items 1 and 6 are top level. If user presses this line another screen opens to allow user to change relevant
setpoints.
Items 7 and 8 are present if comm5 LCI-C option is installed.
RLC-SVU05A-E4 23
DynaView Interface
1. Evap Water Pump (Auto, On), Auto (6) 1) Water Flow status
Enum
1.a.Evap Water Pump <Auto / On Buttons> 2) Override Time Remaining
2. Cond Water Pump (Auto, On), Auto (6) 1) Water Flow status Water Cooled only (i.e.
Enum RTWD or RTUD with
2.a. Cond Water Pump <Auto / On Buttons> 2) Override Time Remaining ACFC=None)
1) Override status -
3. Head Pressure Control (Auto, Manual), Auto (7) Only if Cond Head pressure
Enum Auto/Manual
control option is installed
3.a. Head Pressure Control <Auto / Manual Buttons> (7)
Only if Cond Head pressure
4. Staging/Stepping Control (Auto, Manual), Auto (7)
Enum control option is installed
4.a. Staging/Stepping Control <Auto / Manual Buttons> (7)
Only if Cond Head pressure
5. Capacity Modulation Control (Auto, Manual), Auto (7)
control option is installed
Enum
5a. Capacity Modulation Control <Auto / Manual Buttons> (7)
1) Resettable Energy consumption 1) Resettable Energy
6. Clear Energy Consumption
totalization (kWh) consumption totalization (kWh) Only if Energy Meter option
Enum
is installed
6.a. Clear Energy Consumption <Clear Button>
1) Override status:
1. Compressor Pumpdown (Continue, Not Available)
NotAvailable / Continue / Starting / Pumpdown
Enum
1.a. Compressor Pumpdown <Pumpdown / Abort Buttons> (8) 2) Suction Pressure
2. Front Panel Ckt Lockout (Not Locked Out, Locked Out), Not Locked Out
Enum
2.a. Front Panel Ckt Lockout <Not Locked Out / Locked Out Buttons>
24 RLC-SVU05A-E4
DynaView Interface
RLC-SVU05A-E4 25
DynaView Interface
Figure 11
26 RLC-SVU05A-E4
DynaView Interface
Reset Diags
RLC-SVU05A-E4 27
Diagnostics
Severity: Defines the severity of the Reset Level: Defines the lowest level
above effect. Immediate means of manual diagnostic reset
immediate shutdown of the effected command which can clear the
portion, Normal means normal or diagnostic. The manual diagnostic
friendly shutdown of the effected reset levels in order of priority are:
portion, Special Mode means a Local and Remote. A diagnostic that
special mode of operation (limp has a reset level of Local, can only
along) is invoked, but without be reset by a local diagnostic reset
shutdown, and Info means an command, but not by the lower
Informational Note or Warning is priority remote Reset command
generated. whereas a diagnostic listed as
Remote reset can be reset by either.
Affects Target itemized with an *
asterisk: applied to many comm
loss and starter module derived
diagnostic targets, listed as circuit
targeted diagnostics, but should be
understood as "cprsr" targeted
diagnostics.
28 RLC-SVU05A-E4
Diagnostics
Starter 1A Dry Run *Circuit Immediate Starter Dry Run Mode While in the Starter Dry Run Mode either 50 % Line Local
Test Latch Voltage was sensed at the Potential Transformers or 10
% RLA Current was sensed at the Current Transformers.
Starter 2A Dry Run *Circuit Immediate Starter Dry Run Mode While in the Starter Dry Run Mode either 50 % Line Local
Test Latch Voltage was sensed at the Potential Transformers or 10
% RLA Current was sensed at the Current Transformers.
Phase Loss - *Circuit Immediate Start Sequence and a) No current was sensed on one or two of the current Local
Compressor 1A Run modes transformer inputs while running or starting (See
Nonlatching Power Loss Diagnostic for all three phases
lost while running). Must hold = 20% RLA. Must trip =
5% RLA. Time to trip shall be longer than guaranteed
reset on Starter Module at a minimum, 3 seconds
Latch
maximum. Actual design trippoint is 10%. The actual
design trip time is 2.64 seconds. b) If Phase reversal
protection is enabled and current is not sensed on one
or more current xformer inputs. Logic will detect and
trip in a maximum of 0.3 seconds from compressor
start.
RLC-SVU05A-E4 29
Diagnostics
Power Loss - *Circuit Immediate All compressor The compressor had previously established currents Remote
Compressor 1A running modes while running and then all three phases of current were
[all compressor lost. Design: Less than 10% RLA, trip in 2.64 seconds.
starting and non- This diagnostic will preclude the Phase Loss Diagnostic
running modes] and the Transition Complete Input Opened Diagnostic
from being called out. To prevent this diagnostic from
occurring with the intended disconnect of main power,
the minimum time to trip must be greater than the
guaranteed reset time of the Starter module. Note: This
NonLatch diagnostic prevents nuisance latching diagnostics due to
a momentary power loss - It does not protect
motor/compressor from uncontrolled power
reapplication. See Momentary Power Loss Diagnostic
for this protection. This diagnostic is not active during
the start mode before the transition complete input is
proven. Thus a random power loss during a start would
result in either a "Starter Fault Type 3" or a "Starter Did
Not Transition" latching diagnostic.
Power Loss - *Circuit Immediate All compressor The compressor had previously established currents Remote
Compressor 2A running modes while running and then all three phases of current were
[all compressor lost. Design: Less than 10% RLA, trip in 2.64 seconds.
starting and non- This diagnostic will preclude the Phase Loss Diagnostic
NonLatch running modes] and the Transition Complete Input Opened Diagnostic
from being called out. To prevent this diagnostic from
occurring with the intended disconnect of main power,
the minimum time to trip must be greater than the
guaranteed reset time of the Starter module.
Severe Current *Circuit Immediate All Running Modes A 30% Current Imbalance has been detected on one Local
Imbalance - phase relative to the average of all 3 phases for 90
Compressor 1A Latch continuous seconds.
Severe Current *Circuit Immediate All Running Modes A 30% Current Imbalance has been detected on one Local
Imbalance - Latch phase relative to the average of all 3 phases for 90
Compressor 2A continuous seconds
Starter Fault Type I - *Circuit Immediate Starting - Y Delta This is a specific starter test where 1M(1K1) is closed Local
Compressor 1A Starters Only first and a check is made to ensure that there are no
Latch currents detected by the CT's. If currents are detected
when only 1M is closed first at start, then one of the
other contactors is shorted.
30 RLC-SVU05A-E4
Diagnostics
Starter Fault Type III *Circuit Immediate Starting As part of the normal start sequence to apply power to Local
- Compressor 1A [Adaptive Frequency the compressor, the Shorting Contactor (1K3) and then
Starter Type] the Main Contactor (1K1) were energized. 1.6 seconds
Latch later there were no currents detected by the CT's for
the last 1.2 Seconds on all three phases. The test above
applies to all forms of starters except Adaptive
Frequency Drives.
Starter Fault Type III *Circuit Immediate Starting As part of the normal start sequence to apply power to Local
- Compressor 2A [Adaptive Frequency the compressor, the Shorting Contactor (1K3) and then
Starter Type] the Main Contactor (1K1) were energized. 1.6 seconds
Latch later there were no currents detected by the CT's for
the last 1.2 seconds on all three phases. The test above
applies to all forms of starters except Adaptive
Frequency Drives.
Compressor Did Not *Circuit Info Start Mode The compressor did not come up to speed (fall to Remote
Accelerate: <85%RLA) in the allotted time defined by the Maximum
Transition - Latch Acceleration Timer and a transition was forced (motor
Compressor 1A put across the line) at that time. This applies to all
starter types.
Compressor Did Not *Circuit Info Start Mode The compressor did not come up to speed (fall to Remote
Accelerate: <85%RLA) in the allotted time defined by the Maximum
Transition - Latch Acceleration Timer and a transition was forced (motor
Compressor 2A put across the line) at that time. This applies to all
starter types.
RLC-SVU05A-E4 31
Diagnostics
Transition Complete *Circuit Immediate All running modes The Transition Complete input was found to be opened Local
Input Opened - with the compressor motor running after a successful
Compressor 2A completion of transition. This is active only for Y-Delta,
Auto-Transformer, Primary Reactor, and X-Line Starters.
Latch
To prevent this diagnostic from occurring as the result of
a power loss to the contactors, the minimum time to
trip must be greater than the trip time for the power
loss diagnostic.
Motor Current Circuit Immediate Cprsr Energized Compressor current exceeded overload time vs. trip Local
Overload - Latch characteristic. Must trip = 140% RLA, Must hold=125%,
Compressor 1A nominal trip 132.5% in 30 seconds
Motor Current Circuit Immediate Cprsr Energized Compressor current exceeded overload time vs. trip Local
Overload - Latch characteristic. Must trip = 140% RLA, Must hold=125%,
Compressor 2A nominal trip 132.5% in 30 seconds
Starter Contactor Chiller Special Starter Contactor not Detected compressor currents greater than 10% RLA on Local
Interrupt Failure - Action Energized [Starter any or all phases when the compressor was
Compressor 1A Contactor Energized] commanded off. Detection time shall be 5 second
minimum and 10 seconds maximum. On detection and
until the controller is manually reset: generate
diagnostic, energize the appropriate alarm relay,
Latch continue to energize the Evap Pump Output, continue to
command the affected compressor off, fully unload the
effected compressor and command a normal stop to all
other compressors. For as long as current continues,
perform liquid level, oil return, and fan control on the
circuit effected.
Starter Contactor Chiller Special Starter Contactor not Detected compressor currents greater than 10% RLA on Local
Interrupt Failure - Action Energized [Starter any or all phases when the compressor was
Compressor 2A Contactor Energized] commanded off. Detection time shall be 5 second
minimum and 10 seconds maximum. On detection and
until the controller is manually reset: generate
diagnostic, energize the appropriate alarm relay,
Latch continue to energize the Evap Pump Output, continue to
command the affected compressor off, fully unload the
effected compressor and command a normal stop to all
other compressors. For as long as current continues,
perform liquid level, oir return, and fan control on the
circuit effected.
Over Voltage Chiller Normal Pre-Start and Any Nom. trip: 60 seconds at greater than 112.5%, + 2.5%, Remote
NonLatch Ckt(s) Energzd Auto Reset at 110% or less for 10 cont secs.
32 RLC-SVU05A-E4
Main Processor Diagnostics
Unexpected Starter Circuit Normal All Cprsr Running The Starter module status reported back that it is NA
Shutdown modes, Starting, stopped when the MP thinks it should be running and
Running and Preparing no Starter diagnostic exist. This diagnostic will be
NonLatch to Shutdown logged in the active buffer and then automatically
cleared. This diagnostic could be caused by intermittent
communication problems from the Starter to the MP, or
due to misbinding.
High Motor Winding Circuit Immediate All The respective compressor's motor winding thermostat Local
Temperature - Latch is detected to be open
Compressor 1A
High Motor Winding Circuit Immediate All The respective compressor's motor winding thermostat Local
Temperature - Latch is detected to be open
Compressor 2A
Low Evaporator Circuit Immediate All Ckt Running The inferred Saturated Evap Refrigerant Temperature Remote
Refrigerant Modes (calculated from suction pressure transducer dropped
Temperature - below the Low Refrigerant Temperature Cutout Setpoint
Circuit 1 for 1125°F-sec (25°F-sec max rate) while the circuit was
running. The minimum LRTC setpoint is -5°F (18.7 Psia)
the point at which oil separates from the refrigerant.
During the time that the trip integral is non zero, the
Latch unload solenoid(s) of the running compressors on the
circuit, shall be energized continuously and the load
solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps
above the cutout setpoint. The integral is held
nonvolatily though power down, is continuously
calculated, and can decay during the circuit's off cycle as
conditions warrant.
Low Evaporator Circuit Immediate All Ckt Running The inferred Saturated Evap Refrigerant Temperature Remote
Refrigerant Modes (calculated from suction pressure transducer dropped
Temperature - below the Low Refrigerant Temperature Cutout Setpoint
Circuit 2 for 1125°F-sec (25°F-sec max rate) while the circuit was
running. The minimum LRTC setpoint is -5°F (18.7 Psia)
the point at which oil separates from the refrigerant.
During the time that the trip integral is non zero, the
Latch unload solenoid(s) of the running compressors on the
circuit, shall be energized continuously and the load
solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps
above the cutout setpoint. The integral is held
nonvolatily though power down, is continuously
calculated, and can decay during the circuit's off cycle as
conditions warrant.
RLC-SVU05A-E4 33
Main Processor Diagnostics
Low Oil Flow - Circuit Immediate Cprsr Energized and The intermediate oil pressure transducer for this Local
Compressor 2A Delta P above 15 Psid compressor was out of the acceptable pressure range
for 15 seconds, while the Delta Pressure was greater
Latch than 15 Psid (172.4 kPa).: Acceptable range is 0.50 >
(PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.28 > (PC-PI) / (PC-PE) thereafter.
Loss of Oil - Circuit Immediate Starter Contactor In running modes , Oil Loss Level Sensor detects lack of Local
Compressor 1A Latch Energized oil in the oil sump feeding the compressor
(Running) (distinguishing a liquid flow from a vapor flow)
Loss of Oil - Circuit Immediate Starter Contactor In running modes , Oil Loss Level Sensor detects lack of Local
Compressor 2A Latch Energized oil in the oil sump feeding the compressor
(Running) (distinguishing a liquid flow from a vapor flow)
Loss of Oil - Circuit Immediate Compressor Pre-start Oil Loss Level Sensor detects a lack of oil in the oil Local
Compressor 1A and Special [all other modes] sump feeding the compressor for 90 seconds just prior
(Stopped) Action Latch to attempted compressor start. Note: Compressor start
is delayed while waiting for oil to be detected, and
compressor start is not allowed.
Oil Loss Level Sensor detects a lack of oil in the oil
Loss of Oil - Immediate sump feeding the compressor for 90 seconds just prior
Compressor Pre-start
Compressor 2A Circuit and Special Latch to attempted compressor start. Note: Compressor start Local
[all other modes]
(Stopped) Action is delayed while waiting for oil to be detected, and
compressor start is not allowed.
No Differential The system differential pressure was below 7.7 Psid (53
Compressor running
Refrigerant Circuit Immediate Latch kPa) for 6 seconds after the 11 seconds ignore time Remote
on Circuit
Pressure - Circuit 1 relative to cprsr/circuit startup had expired.
No Differential The system differential pressure was below 7.7 Psid (53
Compressor running
Refrigerant Circuit Immediate Latch kPa) for 6 seconds after the 11 seconds ignore time Remote
on Circuit
Pressure - Circuit 2 relative to cprsr/circuit startup had expired.
34 RLC-SVU05A-E4
Main Processor Diagnostics
High Refrigerant Circuit Immediate Service Pumpdown The pressure ratio for the respective circuit exceeded Remote
Pressure Ratio - Only 5.61 for 1 contiguous minute while in service
Circuit 1 Latch pumpdown. This pressure ratio is a fundamental
limitation of the compressor. The pressure ratio is
defined as Pcond (abs)/Pevap(abs).
High Refrigerant Circuit Immediate Service Pumpdown The pressure ratio for the respective circuit exceeded Remote
Pressure Ratio - Only 5.61 for 1 contiguous minute while in service
Circuit 2 Latch pumpdown. This pressure ratio is a fundamental
limitation of the compressor. The pressure ratio is
defined as Pcond (abs)/Pevap(abs).
High Discharge Circuit Immediate All The compressor discharge temperature exceeded 200°F Remote
Temperature - [compressor run (without oil cooler) or 230ºF (with oil cooler). This
Compressor 1A unload or compressor diagnostic will be suppressed during Run-Unload or after
not running] the compressor has stopped. Note: As part of the
Latch Compressor High Temperature Limit Mode (aka
Minimum Capacity Limit), the compressor shall be
forced loaded as the filtered discharge temperature
reaches 190ºF(without oil coolers), or 220ºF (with oil
coolers).
High Discharge Circuit Immediate All The compressor discharge temperature exceeded 200°F Remote
Temperature - [compressor run (without oil cooler) or 230ºF (with oil cooler). This
Compressor 2A unload or compressor diagnostic will be suppressed during Run-Unload or after
not running] the compressor has stopped. Note: As part of the
Latch Compressor High Temperature Limit Mode (aka
Minimum Capacity Limit), the compressor shall be
forced loaded as the filtered discharge temperature
reaches 190ºF(without oil coolers), or 220ºF (with oil
coolers).
RLC-SVU05A-E4 35
Main Processor Diagnostics
Fan Inverter Fault - Circuit (fan Special Mode Prestart and Running A fault signal has been detected from the respective
Circuit 2 control) (or in single w/ Low Ambient condenser's Variable Speed Inverter Drive (fan).
fan deck: NonLatch (or Variable Spd Fan Condenser Fan control will revert to constant speed
Circuit in single fan configured operation without the use of the inverter's fan. If the
Immediate deck:Latch) inverter's fault clears, fan control will switch back to
shutdown variable speed. For single fan deck configurations, this
diagnostic causes a latching circuit shutdown
BAS Failed to None Special At power-up The BAS was setup as "installed" and the BAS did not Remote
Establish Action communicate with the Lontalk LCIC within 15 minutes
Communication after chiller controls power-up. Refer to Section on
Setpoint Arbitration to determine how setpoints and
NonLatch operating modes may be effected. Note that this
diagnostic is never operational for BacNet
Communication interface (BCIC) and only operational
with a LonTalk Communication interface (LCIC) if so
configured by the BAS or Tracer system.
BAS None Special All The BAS was setup as "installed" at the MP and the Remote
Communication Action Lontalk LCIC lost communications with the BAS for 15
Lost contiguous minutes after it had been established. Refer
to Section on Setpoint Arbitration to determine how
setpoints and operating modes may be effected by the
comm loss. The chiller follows the value of the Tracer
NonLatch Default Run Command which can be previously written
by Tracer and stored nonvolatilely by the MP (either use
local or shutdown). Note that this diagnostic is never
operational for BacNet Communication interface (BCIC)
and only operational with a LonTalk Communication
interface (LCIC) if so configured by the BAS or Tracer
system.
Low Evaporator None Info Starter Contactor The liquid level sensor is seen to be at or near its low Remote
Liquid Level - Energized [all Stop end of range for 80 contiguous minutes while the
Circuit 1 modes] compressor is running and the EXV has not been in low
differential pressure control during that time. Design:
NonLatch
approx 20% or less of bit count corresponding to -40
mm or less liquid level for 80 minutes - the minute
counter is reset if EXV is in Low DP control for 5
iterations (10 sec) implemented as an integral.
36 RLC-SVU05A-E4
Main Processor Diagnostics
External Chilled/Hot None Info All a. Function Not "Enabled": no diagnostics. b. "Enabled ": Remote
Water Setpoint Out-Of-Range Low or Hi or bad LLID, set diagnostic,
Latch default CWS to next level of priority (e.g. Front Panel
SetPoint). This Info diagnostic will automatically reset if
the input returns to the normal range.
External Current None Info All a. Not "Enabled": no diagnostics. b. "Enabled ": Out-Of- Remote
Limit Setpoint Range Low or Hi or bad LLID, set diagnostic, default
Latch CLS to next level of priority (e.g. Front Panel SetPoint.
This Info diagnostic will automatically reset if the input
returns to the normal range.
Evaporator Water None Info Any Ckt(s) Energzd The entering evaporator water temp fell below the Remote
Flow (Entering [No Ckt(s) Energzd] leaving evaporator water temp by more than 2°F for
Water Temp) 100°F-sec. For falling film evaporators, this diagnostic
cannot reliably indicate loss of flow, but can warn of
Latch improper flow direction through the evaporator,
misbound water temperature sensors, improper sensor
installation, partially failed sensors, or other system
problems. Note that either entering or leaving water
temp sensor could be at fault.
Evaporator Bad Sensor or LLID. Note: Entering Water Temp Sensor
Entering Water is used in EXV pressure control as well as ice making so
Chiller Normal Latch All Remote
Temperature it must cause a unit shutdown even if ice or CHW reset
Sensor is not installed.
Evaporator
Leaving Water
Chiller Normal Latch All Bad Sensor or LLID Remote
Temperature
Sensor
Condenser
Info and RTWD only: Bad Sensor or LLID. If chiller running, and
Entering Water
Chiller Special Latch All condenser water regulating valve option installed, Remote
Temperature
Action force valve to 100% flow.
Sensor
RTWD only: Bad Sensor or LLID. If Chiller is running
Condenser
Info and in the heat mode of operation - normal chiller
Leaving Water
Chiller Special Latch All shutdown, otherwise, informational warning only. Remote
Temperature
Action Discontinue Min Capacity Limit forced cprsr loading
Sensor
due to Low DP in subsequent startups.
Condenser
Refrigerant
Pressure Circuit Immediate Latch All Bad Sensor or LLID Remote
Transducer -
Circuit 1
Condenser
Refrigerant
Pressure Circuit Immediate Latch All Bad Sensor or LLID Remote
Transducer -
Circuit 2
Suction
Refrigerant
Pressure Circuit Immediate Latch All Bad Sensor or LLID Remote
Transducer -
Circuit 1
RLC-SVU05A-E4 37
Main Processor Diagnostics
38 CG-SVU02C-E4
Main Processor Diagnostics
Very Low Chiller Immediate All The respective circuit's evaporator pressure dropped Local
Evaporator [compressor or circuit below 80% of the current Low Evap Refrig Press Cutout
Refrigerant Pressure in manual lockout] setting (see above) or 8 psia, whichever is less,
- Circuit 2 regardless of the running state of the circuit's
Latch
compressor. If a given compressor or circuit is locked
out, the suction pressure transducer(s) associated with
it, will be excluded from causing this diagnostic.
Low Evaporator Evap (and Special Unit in Stop Mode, or The leaving Evaporator water temp. fell below the Remote
Leaving Water Temp: circ) Pump Action in Auto Mode and No leaving water temp cutout setting for 30 degree F
Unit Off Ckt(s) Energzd [Any seconds while the Chiller is in the Stop mode, or in Auto
Ckt Energzd] mode with no compressors running. Energize small
Evap Circulating Pump (RTUD A/C) and Evap Water
pump Relay (but only if "Evap Water Pump Diagnostic
NonLatch Override" setting is enabled) until diagnostic auto resets,
then de-energize the circ pump and return to normal
evap pump control. Automatic reset occurs when the
temp rises 2°F (1.1°C) above the cutout setting for 30
minutes. This diagnostic even while active, does not
prevent operation of either circuit
CG-SVU02C-E4 39
Main Processor Diagnostics
Low Evaporator Evap (and Special Unit in Stop Mode, or The respective evap sat temp fell below the water temp Remote
Temp - Ckt 2: Unit circ) Pump Action in Auto Mode and No cutout setting while the evap liquid level was greater
Off Ckt's Energzd [Any than -36 mm for 150º-sec degree F seconds while
Ckt Energzd] Chiller is in the Stop mode, or in Auto mode with no
compressors running. Energize small Evap Circulating
Pump (RTUD A/C) and Evap Water pump Relay (but only
if "Evap Water Pump Diagnostic Override" setting is
NonLatch enabled) until diagnostic auto resets, then de-energize
the circ pump and return to normal evap pump control.
Automatic reset occurs when the derived evap sat temp
rises 2°F (1.1°C) above the cutout setting for 1 minute or
the liquid level is below -36.0 mm for 20 minutes, or any
compressor restarts. OA temp is substituted for evap
sat temp in case of invalidity. This diagnostic even while
active, does not prevent operation of either circuit.
Low Evaporator Chiller Immediate Any Ckt[s] Energzd The evaporator water temp. fell below the cutout Remote
Water Temp: Unit On and Special [No Ckt(s) Energzd] setpoint for 30 degree F Seconds while the compressor
Action was running. Automatic reset occurs when the
NonLatch temperature rises 2° F (1.1°C) above the cutout setting
for 2 minutes. This diagnostic shall not de-energize the
Evaporator Water Pump Output.
Evaporator Water Chiller Normal Estab. Evap. Water Evaporator water flow was not proven within 20 Remote
Flow Overdue Flow on going from minutes of the Evaporator water pump relay being
STOP to AUTO or Evap energized in normal "Stop" to "Auto" transition. If the
NonLatch Pump Override. pump is overridden to "On" for certain diagnostics, the
delay on diagnostic callout shall be only 255 seconds.
The pump command status will not be effected by this
diagnostic in either case.
Evaporator Water Chiller Immediate [All Stop modes] a. The Evaporator water flow switch input was open Remote
Flow Lost for more than 6 contiguous seconds (or 15 seconds
for thermal dispersion type flow switch). b. This
NonLatch diagnostic does not de-energize the evap pump output
c. 6 seconds of contiguous flow shall clear this
diagnostic.
40 CG-SVU02C-E4
Main Processor Diagnostics
High Evaporator Chiller Info and Only effective if either The leaving water temperature exceeded the high evap Remote
Water Temperature Special 1)Evap Wtr Flow water temp limit (TV service menu settable -default
Action Overdue, 105F) for 15 continuous seconds. The evaporator water
2)Evap Wtr Flow Loss, pump relay will be de-energized to stop the pump but
or 3)Low Evap Rfgt only if it is running due one of the diagnostics listed on
Temp,-Unit Off, the left . The diagnostic will auto reset and the pump
diagnostic is active. will return to normal control when the temperature falls
5°F below the trip setting. The primary purpose is to
NonLatch stop the evaporator water pump and its associated
pump heat from causing excessive waterside
temperatures and waterside pressures when the chiller
is not running but the evap pump is on due to either
Evap Water Flow Overdue, Evaporator Water Flow Loss
, or Low Evap Temp - Unit Off Diagnostics. This
diagnostic will not auto clear solely due to the clearing
of the enabling diagnostic.
Condenser Water Chiller Normal Estab Cond Water Condenser water flow was not proven within 20 Remote
Flow Overdue Flow minutes of the condenser pump relay being energized.
The Cond Pump shall be commanded off. Diagnostic is
NonLatch
reset with return of flow (although only possible with
external control of pump).
Condenser Water Chiller Immediate Start and All Run The condenser water flow proof input was open for Remote
Flow Lost Modes more than 6 contiguous seconds (or 15 seconds for
thermal dispersion type flow switch) after flow had been
proven. This diagnostic is automatically cleared once the
compressor is stopped by a fixed time out of 7 sec. In
Cooling Mode: The Cond Pump shall be commanded off
but the Evap pump command will not be effected. -
NonLatch
once the diagnostic auto clears, if diff to start is met,
the cond pump can be restarted. In Heating Mode: The
Cond Pump shall remain on, and the Evap pump shall
shut off - once diagnostic auto clears, if diff to start is
met, the chiller may restart normally and the evap pump
can be restarted.
CG-SVU02C-E4 41
Main Processor Diagnostics
High Pressure Circuit Immediate All A high pressure cutout was detected on Compressor Local
Cutout - 1A; trip at 270 ± 5 PSIG. Note: Other diagnostics that
Compressor 2A may occur as an expected consequence of the HPC trip
will be suppressed from annunciation. These include
Latch Phase Loss, Power Loss, and Transition Complete Input
Open. For Air Cooled Condenser, check for dirty coils or
any fouling or restrictions as well as proper operation
and rotational direction of all fans..
Excessive Circuit Immediate All The condenser pressure transducer of this circuit has Remote
Condenser Pressure detected a pressure in excess of the safe high side
- Circuit 1 pressure as limited by the particular compressor type or
Latch the evaporator distributor present on this particular
chiller. For Air Cooled Condenser, check for dirty coils or
any fouling or restrictions as well as proper operation
and rotational direction of all fans.
Excessive Circuit Immediate All The condenser pressure transducer of this circuit has Remote
Condenser Pressure detected a pressure in excess of the safe high side
- Circuit 2 pressure as limited by the particular compressor type or
Latch the evaporator distributor present on this particular
chiller. For Air Cooled Condenser, check for dirty coils or
any fouling or restrictions as well as proper operation
and rotational direction of all fans.
RTUD with
Bad Sensor or LLID. If the outdoor temperature is
ACFC#NONE-
used for CHW reset, there shall be no CHW reset.
Normal
Outdoor Air Apply slew rates per Chilled Water Reset spec. RTUD:
Shutdown;
Temperature Chiller Latch All if this diagnostic occurs, operational pumpdown will Remote
Sensor be performed regardless of the last valid temperature.
OATS=INST-
For RTWD, if installed for low ambient lockout, there
Special Action
shall be no LA lockout .
Latch
42 CG-SVU02C-E4
Main Processor Diagnostics
Starter Module
Checksum on EEPROM copy of the Starter LLID
Memory Error Type Circuit Immediate Latch All Local
configuration failed. Factory default values used.
2 - Starter 1A
Starter Module
Checksum on EEPROM copy of the Starter LLID
Memory Error Type Circuit Immediate Latch All Local
configuration failed. Factory default values used.
2 - Starter 2A
MP Application
Chiller Immediate Latch All Modes Memory error criteria TBD Remote
Memory CRC Error
MP: Could not MP has determined there was an error with the
Store Starts and None Info Latch All previous power down store. Starts and Hours may Remote
Hours have been lost for the last 24 hours.
Starter Failed to Circuit Normal All Starter failed to arm or start within the allotted time Local
Arm/Start - Latch (15 seconds).
Cprsr 1A
Starter Failed to Circuit Normal All Starter failed to arm or start within the allotted time Local
Arm/Start - Latch (15 seconds).
Cprsr 2A
Oil Analysis Circuit Info "Service Messages" Diagnostic occurs when accumulated circuit operating Remote
Recommended - enabled hours since last initialized exceeds 2000 hours.
Ckt #1 Latch Diagnostic can be manually cleared but will reoccur
every month (720 hours on real time clock) as long as
accumulator is not re-initialized.
CG-SVU02C-E4 43
Main Processor Diagnostics
Oil Filter Change Circuit Info "Service (After RTUD release in Fall of 09:) Diagnostic occurs only Remote
Recommended - Messages" enabled when "service messages" are enabled and when Oil
Cprsr 1A Filter Life remaining falls below 5 %. Diagnostic can be
manually cleared but will reoccur every month real time
(720 hours on real time clock) as long as the oil filter life
remaining does not rise above 20% (through normal
Latch calculations or reinitializing) (Prior to RTUD Release in
Fall of 09): Diagnostic occurs only when "service
messages" are enabled and when average oil pressure
drop exceeds 18%. Diagnostic can be manually cleared
but will reoccur every month (720 hours on real time
clock) as long as average pressure drop does not fall
below 16%.
Oil Filter Change Circuit Info "Service (After RTUD release in Fall of 09:) Diagnostic occurs only Remote
Recommended - Messages" enabled when "service messages" are enabled and when Oil
Cprsr 2A Filter Life remaining falls below 5 %. Diagnostic can be
manually cleared but will reoccur every month real time
(720 hours on real time clock) as long as the oil filter life
remaining does not rise above 20% (through normal
Latch calculations or reinitializing) (Prior to RTUD Release in
Fall of 09): Diagnostic occurs only when "service
messages" are enabled and when average oil pressure
drop exceeds 18%. Diagnostic can be manually cleared
but will reoccur every month (720 hours on real time
clock) as long as average pressure drop does not fall
below 16%.
LCI-C Software Chiller Info All The neuron software in the LCI-C module does not Remote
Mismatch: Use BAS match the chiller type. Download the proper software
Tool into the LCI-C neuron. To do this, use the Rover service
NonLatch
tool, or a LonTalk® tool capable of downloading
software to a Neuron 3150®.
44 CG-SVU02C-E4
Main Processor Diagnostics
Software Error 1003: All Immediate All Reported if state chart misalignment occurred inferred Local
Call Trane Service functions from either the Capacity Control, Circuit, or Compressor
State Machines remaining in the Stopping state for
more than 3 minutes. The presence of this software
Latch error message suggests an internal software problem
has been detected. The events that led up to this
failure, if known, should be recorded and transmitted to
Trane Controls Engineering.
CG-SVU02C-E4 45
Diagnostics
Comm Loss: Male Port Load Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Compressor 1A Functional ID has occurred for a 30 second period.
Comm Loss: Male Port Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Unload Compressor 2A Functional ID has occurred for a 30 second period.
Comm Loss: Male Port Load Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Compressor 2A Functional ID has occurred for a 30 second period.
Comm Loss: Female Step Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Load Compressor 1A Functional ID has occurred for a 30 second period.
Comm Loss: Female Step Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Load Compressor 2A Functional ID has occurred for a 30 second period.
Comm Loss: Motor Winding Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Thermostat Compressor 1A Functional ID has occurred for a 30 second period.
Comm Loss: Motor
Continual loss of communication between the MP and the
Winding Thermostat Circuit Normal Latch All Remote
Functional ID has occurred for a 30 second period.
Compressor 2A
Comm Loss: External Continual loss of communication between the MP and the
Chiller Normal Latch All Remote
Auto/Stop Functional ID has occurred for a 30 second period.
Comm Loss: Emergency Continual loss of communication between the MP and the
Chiller Normal Latch All Remote
Stop Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Comm Loss: External Special Functional ID has occurred for a 30 second period. MP will
Circuit Latch All Remote
Circuit Lockout, Circuit #1 Action nonvolatily hold the lockout state (enabled or disabled) that
was in effect at the time of comm loss.
Continual loss of communication between the MP and the
Comm Loss: External Special Functional ID has occurred for a 30 second period. MP will
Circuit Latch All Remote
Circuit Lockout, Circuit #2 Action nonvolatily hold the lockout state (enabled or disabled) that
was in effect at the time of comm loss
Continual loss of communication between the MP and the
Ice
Comm Loss: External Ice Special Functional ID has occurred for a 30 second period. Chiller
Making Latch All Remote
Building Command Action shall revert to normal (non-ice building) mode regardless of
Mode
last state.
46 RLC-SVU05A-E4
Diagnostics
Comm Loss: Outdoor Air Chiller RTUD with Latch All Continual loss of communication between the MP and the Remote
Temperature ACFC#NONE- Functional ID has occurred for a 30 second period. If the
Normal outdoor temperature is used for CHW reset, there shall be
Shutdown; no CHW reset. Apply slew rates per Chilled Water Reset
spec. For RTUD if this diagnostic occurs, operational
OATS=INST- pumpdown will be performed regardless of the last valid
Special Action temperature. For RTWD, if installed for low ambient
lockout, there shall be no lockout
Comm Loss: Evaporator Chiller Normal Latch All Continual loss of communication between the MP and the Remote
Leaving Water Temperature Functional ID has occurred for a 30 second period.
Comm Loss: Evaporator Chiller Normal Latch All Continual loss of communication between the MP and the Remote
Entering Water Functional ID has occurred for a 30 second period. Note:
Temperature Entering Water Temp Sensor is used in EXV pressure
control as well as ice making & CHW reset, so it must
cause a unit shutdown even if Ice or CHW reset is not
installed.
Comm Loss: Condenser Chiller Info and Special Latch All RTWD Only: Continual loss of communication between the Remote
Leaving Water Temperature Action MP and the Functional ID has occurred for a 30 second
period. If Chiller is running in the heat mode of operation -
normal shutdown, otherwise, informational only.
Discontinue Min Capacity Limit forced cprsr loading due to
Low DP in subsequent startups.
Comm Loss: Condenser Chiller Info and Special Latch All RTWD Only: Continual loss of communication between the Remote
Entering Water Action MP and the Functional ID has occurred for a 30 second
Temperature period. If chiller running, and condenser water regulating
valve option installed, force valve to 100% flow.
Comm Loss: Discharge Circuit Normal Latch All Continual loss of communication between the MP and the Remote
Temperature Circuit 1, Functional ID has occurred for a 30 second period.
Cprsr 1A
RLC-SVU05A-E4 47
Diagnostics
Comm Loss: External External Special Action Latch All Continual loss of communication between the MP and Remote
Current Limit Setpoint Current the Functional ID has occurred for a 30 second period.
Limit Chiller shall discontinue use of the External Current limit
setpoint setpoint and revert to the next higher priority for
Current Limit setpoint arbitration
Comm Loss: High Circuit Immediate Latch All Continual loss of communication between the MP and Remote
Pressure Cutout Switch, the Functional ID has occurred for a 30 second period.
Cprsr 1A
Comm Loss: High Circuit Immediate Latch All Continual loss of communication between the MP and Remote
Pressure Cutout Switch, the Functional ID has occurred for a 30 second period.
Cprsr 2A
Comm Loss: Evaporator Chiller Immediate Latch All Continual loss of communication between the MP and Remote
Water Flow Switch the Functional ID has occurred for a 30 second period.
Comm Loss: Condenser Chiller Immediate Latch All RTWD only: Continual loss of communication between Remote
Water Flow Switch the MP and the Functional ID has occurred for a 30
second period.
Comm Loss: Suction Circuit Immediate Latch All Continual loss of communication between the MP and Remote
Rfgt Pressure, Circuit #1 [Ckt/Cprsr the Functional ID has occurred for a 30 second period.
lock out] Note: This diagnostic is replaced by diagnostic 5FB
below with Rev 15.0
Comm Loss: Cond Rfgt Continual loss of communication between the MP and
Circuit Immediate Latch All Remote
Pressure, Circuit #2 the Functional ID has occurred for a 30 second period.
48 RLC-SVU05A-E4
Diagnostics
Comm Loss: Oil Loss Circuit Normal Latch All Continual loss of communication between the MP and Remote
Level Sensor Input - the Functional ID has occurred for a 30 second period.
Circuit #1
Comm Loss: Oil Loss Circuit Normal Latch All Continual loss of communication between the MP and Remote
Level Sensor Input - the Functional ID has occurred for a 30 second period.
Circuit #2
Comm Loss: Evaporator Chiller Normal Latch All Continual loss of communication between the MP and Remote
Water Pump Relay the Functional ID has occurred for a 30 second period.
RLC-SVU05A-E4 49
Diagnostics
Comm Loss: Starter None Info Latch All Continual loss of communication between the MP and Local
Panel High the Functional ID has occurred for a 30 second period.
Temperature Limit ,
Compressor 1A
Comm Loss: Chiller Info Latch All Continual loss of communication between the MP and Remote
Condenser Rfgt the Functional ID has occurred for a 30 second period.
Pressure Output
Comm Loss: Cond Chiller Immediate Latch All Continual loss of communication between the MP and Remote
Head Press Cntrl the Functional ID has occurred for a 30 second period.
Output
Comm Loss: Chiller % Continual loss of communication between the MP and
Chiller Info Latch All Remote
RLA Output the Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and
Special Mode (or in
Comm Loss: Fan Circuit Latch (or in the Functional ID has occurred for a 30 second period.
single fan deck:
Inverter Fault, (fan single fan All Operate the remaining fans as fixed speed fan deck. For Remote
Circuit Immediate
Circuit #1 control) deck:Latch) single fan deck configurations, this diagnostic causes a
shutdown)
latching circuit shutdown
Continual loss of communication between the MP and
Special Mode (or in
Comm Loss: Fan Circuit Latch (or in the Functional ID has occurred for a 30 second period.
single fan deck:
Inverter Fault, (fan single fan All Operate the remaining fans as fixed speed fan deck. For Remote
Circuit Immediate
Circuit #2 control) deck:Latch) single fan deck configurations, this diagnostic causes a
shutdown)
latching circuit shutdown
Continual loss of communication between the MP and
Comm Loss: Fan Special Mode (or in
Circuit Latch (or in the Functional ID has occurred for a 30 second period.
Inverter Speed single fan deck:
(fan single fan All Operate the remaining fans as fixed speed fan deck. For Remote
Command, Circuit Immediate
control) deck:Latch) single fan deck configurations, this diagnostic causes a
Circuit #1 shutdown)
latching circuit shutdown
Continual loss of communication between the MP and
Comm Loss: Fan Special Mode (or in
Circuit Latch (or in the Functional ID has occurred for a 30 second period.
Inverter Speed single fan deck:
(fan single fan All Operate the remaining fans as fixed speed fan deck. For Remote
Command, Circuit Immediate
control) deck:Latch) single fan deck configurations, this diagnostic causes a
Circuit #2 shutdown)
latching circuit shutdown
Comm Loss: Fan
Continual loss of communication between the MP and
Control Relays, Circuit Normal Latch All Remote
the Functional ID has occurred for a 30 second period.
Circuit #1
Comm Loss: Fan
Continual loss of communication between the MP and
Control Relays, Circuit Normal Latch All Remote
the Functional ID has occurred for a 30 second period.
Circuit #2
Comm Loss: Ext Noise Continual loss of communication between the MP and
None Info Latch All Remote
Setback Command the Functional ID has occurred for a 30 second period.
50 CG-SVU02C-E4
Diagnostics
Err2: RAM Pattern 1 Failure There were RAM errors detected in RAM Test Pattern #1.
// Recycle power, if the error persists, replace MP.
Err2: RAM Pattern 2 Failure There were RAM errors detected in RAM Test Pattern #2.
//Recycle power, if the error persists, replace MP.
Err2: RAM Addr Test #1 There were RAM errors detected in RAM Address Test #1.
Failure // Recycle power, if error persists, replace MP.
Err2: RAM Addr Test #2 There were RAM errors detected in RAM Address Test #2.
Failure //Recycle power, if the error persists, replace MP.
No Application Present No Main Processor Application is present - There are no RAM Test Errors.
Please Load Application... // Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration information) and
download the configuration if prompted by TechView. Then proceed to download the most recent RTAC application or
specific version as recommended by Technical Service.
App Present. Running An application has been detected in the Main Processor's nonvolatile memory and the boot code is proceeding to run a
Selftest.… check on its entirety. 8 seconds later, the boot code had completed and passed the (CRC) test.
Selftest Passed // Temporary display of this screen is part of the normal power up sequence.
App Present. Running An application has been detected in Main Processor's nonvolatile memory and the boot code is proceeding to run a
Selftest… check on its entirety. A few seconds later, the boot code had completed but failed the (CRC) test.
Err3: CRC Failure //Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration information) and
download the configuration if prompted by TechView. Then proceed to download the most recent RTAC application or
specific version as recommended by Technical Service. Note that this error display may also occur durring the
programming process, if the MP never had a valid application any time prior to the download. If the problem persists,
replace the MP.
A Valid Configuration is A valid configuration is present in the MP's nonvolatile memory. The configuration is a set of variables and settings that
Present define the physical makeup of this particular chiller. These include: number/airflow,/and type of fans, number/and size of
compressors, special features, characteristics, and control options.
// Temporary display of this screen is part of the normal power up sequence.
Err4: UnHandled Interrupt An unhandled interrupt has occurred while running the application code. This event will normally cause a safe shutdown
Restart Timer: of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to
[3 sec countdown timer] restart the application and allow a normal restart of chiller as appropriate.
// This condition might occur due to a severe electro-magnetic transient such as can be caused by a near lightening
strike. Such events should be rare or isolated and if no damage results to the CH530 control system, the Chiller will
experience a shutdown and restart. If this occurs more persistently it may be due to an MP hardware problem. Try
replacing the MP. If replacement of the MP proves ineffective, the problem may be a result of extremely high radiated
or conducted EMI. Contact Technical Service.
If this screen occurs immediately after a software download, attempt to reload both the configuration and the
application. Failing this, contact Technical Service.
CG-SVU02C-E4 51
Diagnostics
Err5: Operating System An Operating System error has occurred while running the application code. This event will normally cause a safe
Error shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and
Restart Timer: attempt to restart the application and allow a normal restart of chiller as appropriate.
[30 sec countdown timer] // See Err 4 above
Err6: Watch Dog Timer Error A Watch Dog Timer Error has occurred while running the application code. This event will normally cause a safe
Restart Timer: shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and
[30 sec countdown timer] attempt to restart the application allowing a normal restart of chiller as appropriate.
Err7: Unknown Error An unknown Error has occurred while running the application code. This event will normally cause a safe shutdown of
Restart Timer: the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics, and attempt to restart
[30 sec countdown timer] the application allowing a normal restart of chiller as appropriate
Err8: Held in Boot by User The boot detected a key press in the center of the DynaView or both the + and - keys pressed on an EasyView while the
Key Press MP was in the boot code. Upon seeing this message the user can use Techview to connect to the MP to perform a
software download or another service tool function.
Converter Mode A command was received from the Service Tool (Tech View) to stop the running application and run in the "converter
mode". In this mode the MP acts as a simple gateway and allows the TechView service computer to talk to all the LLIDS
on the IPC3 bus.
Programming Mode A command was received by the MP from the Tech View Service Tool and the MP is in the process of first erasing and
then writing the program code to its internal Flash (nonvolatile) Memory. Note that if the MP never had a prior
application already in memory, the error code "Err3"will be displayed instead of this, during the programming download
process.
Software Error 1001: Call See item in Main Processor Diagnostics table above
Trane Service
Software Error 1002: Call See item in Main Processor Diagnostics table above
Trane Service
Design Note: In general, all failures/comm loss due to CH530 components should have a latching diagnostic and effect. All customer inputs failures (out of range, etc) are
generally nonlatching.
52 RLC-SVU05A-E4
Diagnostics
Programmable Relays targets Circuit 1, or any of the Head Pressure Relief Request
Compressors on Circuit 1. This relay output is energized
(Alarms and Status)
anytime the chiller or a single
CH530 provides a flexible alarm or Alarm Ckt 2 circuit on the chiller is running in
chiller status indication to a remote This output is true whenever there one of the following modes; Ice
location through a hard wired is any active latching or non- Making Mode, or Condenser
interface to a dry contact closure. latching shutdown diagnostic that Pressure Limit continuously for the
Four relays are available for this targets Circuit 2, or any of the duration specified by the Chiller
function, and they are provided Compressors on Circuit 2. Head Relief Relay Filter Time. The
(generally with a Quad Relay Output Chiller Head Relief Relay Filter Time
LLID) as part of the Alarm Relay Unit Limit Mode is a service setpoint. The relay
Output Option. This output is true whenever a output is de-energized anytime the
The events/states that can be circuit on the unit has been running chiller exits all above modes
assigned to the programmable in one of the limit modes continuously for the duration
relays are listed in the following continuously for the Limit Relay specified by the same Chiller Head
table and through a TechView debounce time. A given limit or Relief Relay Filter Time
configuration. overlapping of different limits must
be in effect continuously for the None:
Alarm - Latching debounce time prior to the output This selection is desireable to
This output is true whenever there becoming true. It will become false provide an easy way for a customer
is any active latching shutdown if no limits are present for the to defeat the effect of the relay, if it
diagnostic that targets the Unit, debounce time. has already been wired. For
Circuit, or any of the Compressors instance, if the relay was normally
on a circuit. Compressor Running programmed as an "alarm" relay,
The output is true whenever any and was wired to a claxon, it may
Alarm - NonLatching compressor is running. be desirable to temporarily defeat
the feature without changing wiring.
This output is true whenever there
is any active non-latching shutdown Circuit 1 Running
diagnostic that targets the Unit, The output is true whenever any
Default Assignments
Circuit, or any of the Compressors compressor of Circuit 1 is running. The four available relays the Alarm
on a circuit. Package Option shall be assigned
Circuit 2 Running with the following defaults as
Alarm follows:
The output is true whenever any
This output is true whenever there compressor of Circuit 2 is running.
is any active latching or non-
latching shutdown diagnostic that Maximum Capacity Operation of the Relays:
targets the Unit, Circuit, or any of The output is true whenever the If any of the four programmable
the Compressors on a circuit. unit has reached maximum capacity annunciation relays are assigned
continuously for the Max Capacity with the given event or state, that
Alarm Ckt 1 Relay debounce time. The output is relay shall be energized when the
This output is true whenever there false when the unit is not at event or state is true and de-
is any active latching or non- maximum capacity continuously for energized when the event or state is
latching shutdown diagnostic that the fitler debounce time. false pursuant to debounce or filter
timing that may be applied per the
Table 7 - Default settings
details of a given assignment.
LLID Software
LLID Name Output Name Default
Relay Designation
RLC-SVU05A-E4 53
TechView Interface
54 RLC-SVU05A-E4
TechView Interface
RLC-SVU05A-E4 55
Literature Order Number RLC-SVU05A-E4
Date 1109
New
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.