Opening up on
control valves There are three key steps to ensuring that control valves don’t cause process plant
instability. Mark Perry explains the problems and their solutions
lant engineers and engineering managers valves themselves – to establish proper, optimal
CONTROL VALVES
CONTROL VALVES
Having established the right control valve, Full diagnostic tests are able to pinpoint the
actuator and positioner combination for a project reason for any deterioration, ensuring that only
(also taking into account pressure drop those components that need full service attention
requirements, fluid characteristics and the rest), the are stripped down or removed. Then, following
next phase is about maintaining performance. For repair and rebuild, plant engineers should carry out
this, plant engineers need to find a means of further tests to ensure that performance of the
measuring control valve behaviour inline, and of control valve has been retrieved to previous levels.
detecting when it deviates outside acceptable limits. Follow these steps and you’re on the path to
Many manufacturers offer digital positioners with minimising variability and plant efficiency problems,
predictive capabilities – among them Emerson’s whatever the fancy controls. PE
Fisher Fieldvue digital valve controller, which can run
periodic diagnostic tests while the plant remains fully
operational. Typically, diagnostic checks enable Turbine variability
friction and deadband to be monitored and trended, A gas-fired power station in the UK used to experience oscillations at the turbine, due to
while alarms alert engineers and operators to instability in the main gas stream supply pressure. This resulted in an uneven loading, which
measurements moving outside set limits – indicating increased turbine wear and necessitated additional maintenance. Under varying plant load, the
a requirement for maintenance. oscillations were amplified, which also led to occasional plant trips.
However, control valves are mechanical devices, Emerson consultants identified that the control valve itself was responsible for 70–80% of
so their condition will deteriorate over time to the the problem. Replacing the old valve controller with a Fisher digital valve controller reduced
point where, eventually, they will need repair and variability by 50%, immediately resulting in marked plant performance improvement.
reconditioning – the process termed retrieval. In addition, implementing refined controller tuning parameters, recommended by Emerson,
Identifying the nature of a problem and its causes is further reduced process variability and optimised loop operation. Total savings from these minor
also the job of today’s digital valve controllers. Now, modifications were in the region of £80,000 per annum as a result of reducing plant trips,
though, we’re talking about diagnostic tests, with improving plant life and reducing requirements for maintenance on the turbine.
the valve off-line or during plant shutdown.
Join SOE
TODAY
Five reasons
to join the SOE
Professional recognition
Your gateway to registration with ECUK
Career progression: SOE membership can help you
through the many stages of your career
Technical news delivered through Plant Engineer
Full access to SOE website, including 'members only' area
Applying for membership is easy and we're on hand to help
visit www.soe.org.uk
For more information or to talk to a membership advisor call 020 7630 6666