Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Vertiv™Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
TABLE OF CONTENTS
i
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
ii
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
2 Product Overview
The Vertiv™ Liebert® CRV CRC30 and CRC60 chilled water cooling units are specifically created and designed for small to
medium data centers, computer rooms, equipment rooms, and similar high heat density environments.
1 2 3 4 5 6 7 8 9 10 11 12
C R C 3 0 5 - P D 2 0 A
1 C
Vertiv™ Liebert® CRV
2 R
3 C Chilled water
4
30, 60 Model number
5
7 - Separator
0: Cooling only
8 0, P
P: Reheat and humidifier
11 0 Free digit
12 A- Z Revision
2 Product Overview 3
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Item Description
1 Front door
4 2 Product Overview
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
2 Product Overview 5
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
6 2 Product Overview
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 2.5 Vertiv™ Liebert® CRV CRC30 Component Location (Rear View)
4 Three-way valve
2 Product Overview 7
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 2.6 Vertiv™ Liebert® CRV CRC60 Component Location (Front View)
8 2 Product Overview
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 2.7 Vertiv™ Liebert® CRV CRC60 Component Location (Rear View)
2.4 Accessories
The accessories provided with the unit are listed in the table below.
2 Product Overview 9
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Input power consumption without heater and Rated value: 1.06 Rated value: 1.9
humidifier kW Maximum value: 1.68 Maximum value: 1.9
Number of fans 7 8
Heating capacity kW 3 -
35 °C (95 °F) DB, 24% RH, 10 °C (50 °F) EWT, 5.5 38 °C (100 °F) DB, 24% RH, 15 °C (59 °F) EWT, 5.5
Return-air condition
°C (10 °F) Water Rise °C (10 °F) Water Rise
10 2 Product Overview
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Voltage ± 10%
Power supply tolerances
Frequency ± 2 Hz
NOTE: The operating limits refer to new units and those that have been correctly installed and serviced.
CRC60 100% 80.6 Right 78 25.9 32.1 37.9 42.5 50.5 51.3 53.2 55.5
Front 78.9 23.4 25.4 32.7 37.8 40.3 45.4 50.2 55.6
CRC30 100% 76.5 Right 74.5 22.3 25.8 38.1 37.8 42.8 46.9 48.9 52
Front 75.6 22.5 23.4 31.1 35.6 38.3 42.1 48.5 54.5
CRC30 89% 73.2 Right 71.1 22.2 24.4 32.2 34.3 40.7 43.9 46.9 50.8
2 Product Overview 11
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
1/3 Octave Band Center 315 400 500 630 800 1 1.25 1.6
Average Sound Freq Hz Hz Hz Hz Hz kHz kHz kHz
Fan Pressure
Model Location
Speed Sound Pressure
Level dB(A) dB dB dB dB dB dB dB dB
Level dB(A)
CRC60 100% 80.6 Right 78 59.4 66.3 75.9 66.6 66.1 71.4 69 71.8
Front 78.9 61.9 70.2 67.9 65.6 68.8 69.5 72.6 73.9
CRC30 100% 76.5 Right 74.5 57.4 69.3 66.6 63.9 66.3 65.2 67.5 69.4
Front 75.6 61.2 68.3 62.9 63.2 67.6 66.4 68.8 68.8
CRC30 89% 73.2 Right 71.1 56.5 64.7 60.2 61.6 66 62 64.9 64.3
CRC60 100% 80.6 Right 78 70.3 71.1 68.1 65.3 63.5 59.7 55.7 50
Left 78.3 70.7 71.7 68.8 65.9 63.6 60.1 55.3 49.5
Front 78.9 71.9 73.8 71.3 69.5 66.3 64.4 60.6 56.3
CRC30 100% 76.5 Right 74.5 66.7 68.1 65.1 62 59.7 56.2 51.9 46.8
Front 75.6 69.3 71.2 67.9 65.8 62.4 60.4 56.4 52.2
CRC30 89% 73.2 Right 71.1 63.9 64.8 61.9 58.3 55.9 52.4 48.1 42.8
Left 71.5 64.2 65.4 62.5 58.7 55.9 52.3 47.3 41.5
NOTE: The sound level is measured in free field at three locations, each of which is 1 m (3.3 ft) high and 2 m (6.6 ft)
away from the air conditioner, with fans in operation.
12 2 Product Overview
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
3 Pre-installation Preparation
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from or prepare the unit for installation.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
NOTICE
Risk of passageway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a passageway while on or off the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to
fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness, freezing temperatures
and contact damage.
NOTICE
Risk of a leaking coil due to freezing during improper storage. Can cause equipment and serious building
damage.
Stepladder Forklift
3 Pre-installation Preparation 13
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Unit Dimensions (Wide x Depth x Height) mm Shipping Dimensions (Wide x Depth x Height) mm Net Weight kg Shipping Weight kg
Model
(in.) (in.) (lb) (lb)
CRC30 300 × 1132 × 2000 (11.8 × 44.6 × 78.7) 776 × 1276 × 2228 (30.6 × 50.2 × 87.1) 242 (533.5) 322 (709.9)
CRC60 300 × 1132 × 2000 (11.8 × 44.6 × 78.7) 776 × 1276 × 2228 (30.6 × 50.2 × 87.1) 235 (518) 315 (694.5)
NOTE: 915 mm (36 in.) distance should be reserved in front of the front door and the rear door for maintenance and
repair purposes.
14 3 Pre-installation Preparation
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 3.2 Vertiv™ Liebert® CRV CRC30 and CRC60 Clearance Requirements Unit mm (in.)
Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv™ or to your sales
representative.
• Make sure the fork length is suitable for the width of the pallet.
• Do not tilt the unit more than 20 degrees in any direction to prevent the unit from falling over.
• Refer to the following figure for the location of the center of gravity.
3 Pre-installation Preparation 15
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Center of Gravity X Y Z
CRC30 and CRC60 150 ± 50 mm (5.9 ± 2 in.) 550 ± 50 mm (21.7 ± 2 in.) 970 ± 100 mm (38.2 ± 3.9 in.)
1. Pull straight the latches on the wooden box using a claw hammer.
2. Remove the side wooden panels. And then remove the top wooden panel and the cushioning from the top of the
unit.
3. Remove the starch wrap that attach the ramp to the unit. Remove the ramp and set it aside until needed for
moving the unit. Remove the bag around the unit.
16 3 Pre-installation Preparation
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
WARNING! Risk of unsecured unit rolling off pallet. Ensure that the unit and pallet are located on a flat
surface before loosening the hardware securing the unit to the pallet.
WARNING! Two or more properly trained and qualified personnel are required to move the unit to its
installation location.
1. Remove the front and rear shipping brackets from the pallet by removing two M6 hex screws and two M8 hex
screws from each bracket.
2. Remove the front and rear holding brackets from the pallet by removing two M8 hex screws from each bracket.
Remove the screws with a socket wrench.
3. Remove the left and right shipping brackets from the pallet by removing three M8 hex screws from each
bracket.
3 Pre-installation Preparation 17
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
4. Place two ramps on the pallet by fitting the tabs into the holes on the pallet.
5. Lift the four leveling feet under the unit. Lift the unit one corner at a time.
a. Use an adjustable wrench to loosen the fixing nut on each foot in counter-clockwise direction.
b. Use an adjustable wrench to turn the hex bolt clockwise to adjust feet up.
18 3 Pre-installation Preparation
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
2 Hex bolt
6. Move the unit to its installation location using the built-in casters.
7. Remove four anti-tip brackets from the unit by removing two hex M6 x 16 screws from each bracket.
3 Pre-installation Preparation 19
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Item Description
1 Rear door
20 3 Pre-installation Preparation
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
1. Use an adjustable wrench to loosen the fixing nut on each foot in counter-clockwise direction.
2. Rotate the hex bolt on the base of each foot in clockwise or counter-clockwise direction until the foot rises or
falls to a suitable position. Use a gradient measuring tool to ensure that the cabinet is level.
3. Tighten the fixing nut on each foot.
Item Description
1 Fixing nut
2 Hex bolt
1. Open the front door. Install two baying brackets with M6 x 10 countersunk screws on the left frame. Fix each
screw at position A. Install two baying brackets with M6 x 10 countersunk screws on the right frame. Fix each
screw on position B.
2. Open the rear door and install two baying brackets the same way as for the front door.
1. Use an adjustable wrench to loosen the fixing nut on each foot in counter-clockwise direction. Rotate the hex
bolt counter-clockwise until each foot drops from the unit.
2. The unit provides four holes (diameter: 13.5 mm (0.5 in.)) on the bottom frames of the unit. Install M12 x 25
screws in the holes to fix the unit onto the floor bracket of the equipment room.
Item Description
Item Description
1 Top frame
1. Install the top frame and fixed it with four M12 × 30 screws
2. Move the V logo to the top frame.
Figure 4.5 Installing the Top Frame without the Front Frame
2 V logo
NOTE: After the top frame is installed, use plastic caps to cover the unused holes on the top plate.
2 Front frame
1. Open the front door, disconnect the power cable and the communications cable from the HMI by unplugging
the two connectors from the PWR port and the CAN1 port.
2. Remove the front door by removing three hinges that connect the door to the vertical post.
a. Remove the circlip from the bottom of each hinge using a needle nose pliers.
b. Take out the pin from each hinge.
c. Remove two M6 Philips head screws from each hinge.
1 Pin 3 Circlip
3. Install the front frame to the unit with ten M5 × 12 screws (six on the left and right frames and four on the top
and bottom frames).
Item Description
4. Install the top frame on the top panel of the unit with four M12 × 30 screws.
Item Description
1 M12 × 30 screw
5. Install back the front door. Connect the power cable and communications cable to the HMI.
6. Move the V logo to the top frame.
NOTE: After the top frame is installed, use plastic caps to cover the unused holes on the top plate.
5 Piping Connections
CAUTION: Equipment damage and personal injury can result from improper piping installation, leak
checking, fluid chemistry and fluid maintenance.
NOTICE
Risk of no-flow condition. Can cause equipment damage. Do not leave the water/coolant fluid-supply circuit in a
no-flow condition. Idle fluid allows the collection of sediment that prevents the formation of a protective oxide
layer on the inside of tubes. Keep unit switched On and water/coolant fluid-supply circuit system operating
continuously.
5 Piping Connections 29
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
1 Cable access 7 Pump drainage hole and humidifier water inlet hole
2 Chilled water inlet connection 8 Chilled water inlet and outlet hole
Figure 5.2 Location and Dimension of Pipe and Cable Outlets on Top Plate and Base Plate (CRC60) (Unit: mm (in.))
30 5 Piping Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
NOTE: The water pressure should overcome the pressure drop in the system.
NOTE: The pump flow should be 20% to 25% larger than the maximum water flow in the unit.
NOTE: For CRC30, it is recommended that the inlet water temperature is 5 °C to 15.5 °C (41 °F to 59.9 °F). For CRC60,
it is recommended that the inlet water temperature is 10 °C to 22 °C (50 °F to 71.6 °F).
5 Piping Connections 31
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 5.3 Removing the Upper and Lower Filters (CRC30 as An Example)
1 The handle in the middle of the fastening plate 3 The fastening plate above the lower filter
3. Open the air discharge valve to release the Nitrogen from the pipeline. The valve is located as shown in the
figure below.
Item Description
1 Rear door
32 5 Piping Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
1. Remove the caps from the inlet and outlet pipe connectors that are located on the top panel.
2. Connect the field-supplied pipes with the pipe connectors. Tighten connections to 100 Nm (73.8 ft-lb). The
connections should be properly sealed.
3. Install insulation on the provided pipes to prevent loss of cooling capacity.
NOTE: If the top frame has been installed, you can install a pipe extension between the water inlet/outlet pipe and the
provided pipe. The pipe extension must be higher than 267 mm (10.5 in.).
5 Piping Connections 33
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. Remove the humidifier together with the support bracket (only for CRC30).
a. Loosen the hose clamp and disconnect stream pipe from the top of the humidifier.
b. Disconnect the electrode wires from the top of the humidifier.
c. Disconnect the level sensor cables from the top of the humidifier.
d. Unscrew the soft pipe from the bottom of the humidifier.
e. Loosen the hose clamp and disconnect the water supply pipe under the humidifier.
34 5 Piping Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
f. Remove three M5 x 16 pan head screws from the support bracket for humidifier. Pull the support bracket
from the unit to remove the humidifier.
Figure 5.7 Removing the Humidifier together with the Support Bracket (Only for CRC30)
3. Remove the caps from the chilled water inlet and outlet pipe connectors located inside the unit. Connect the
field-supplied pipes to the connectors. Tighten connections to 100 Nm (73.8 ft-lb). The connections should be
properly sealed.
4. Knock off the cover plate on the bottom panel using a claw hammer. Route the field-supplied pipes through the
chilled water inlet and outlet hole and connect them to your water supply and return system.
5 Piping Connections 35
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 5.8 Connecting Water Inlet and Outlet Pipes from Bottom Panel
2 Chilled water inlet connector (for bottom connection) 4 Cover plate on the chilled water inlet and outlet hole
The specification of the pump drainage connector on the top plate is as follows:
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. To connect pump drain through the base plate, unscrew the soft pipe from the pump's drainage tube.
36 5 Piping Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
3. Take out the soft pipe from the accessories bag and connect it to the drainage tube. Then route the soft pipe
through the pump drainage outlet on the base plate to your drainage system.
4. Gravity drainage pipe has been pre-installed from the drain pan. Route the pipe through the gravity drainage
hole on the base plate and connect it to your drainage system. Wrap a drain trap under the drain pan.
NOTE: All water drainage pipes should resist heat higher than 90 °C (194 °F).
NOTE: There must be a drain trap placed at least 200 mm (7.9 in.) below the drain tray. Fill the drain trap with water.
NOTE: The pressure of your water supply system should be within 100 kPa to 700 kPa (14.5 psig to 101.5 psig).
The specification of the inlet for humidifier connector on the top plate is as follows:
5 Piping Connections 37
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
NOTE: The end of the humidifier supply pipe is G 3/4" connector. You can use the convertor provided in the
accessories bag to convert the connector to Rc 1/2".
38 5 Piping Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
6 Electrical Connections
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supply disconnect
switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective
equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can
cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not
isolate power from the unit, even in the “Unit Off” mode. Some internal components require and receive
power even during the “Unit Off” mode of the controller. The only way to ensure that there is NO voltage
inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all
local codes.
WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before working within
any electric connection enclosures. Service and maintenance work must be performed only by properly
trained and qualified personnel and in accordance with applicable regulations and manufacturers’
specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
WARNING! If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
qualified personnel to avoid a hazard.
• The unit has been fixed to the floor or the adjacent cabinets.
• All electrical components are in good condition.
• All terminal screws are tight.
• The supply voltage and frequency are as indicated on the unit.
CRC30 8 14 10.3
CRC60 13 - -
NOTE: The heater and humidifier will not work at the same time.
6 Electrical Connections 39
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
NOTE: Dual power supplies are provided to the unit, with power supply 1 as the primary power feed and power supply
2 as secondary. When power supply 1 fails, power supply 2 automatically takes over. When power supply 1 restores, it
automatically resume its function as the primary power feed.
1. Open the rear door. Remove the cover plate from the electrical box 1 (main circuit breaker) by removing three
M4 x 10 pan head screws.
2. Route the power supply cables into the unit from the top or bottom of the unit and connect the cables to the L1,
L2, L3, N, and PE terminals of the main circuit breaker.
3. Fix the cables to the cable clamps in the electrical box.
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. Remove the cover plate from the electrical box 1 (main circuit breaker) by removing three M4 x 10 pan head
screws.
3. Place the power supply cables into the unit from the top or bottom of the unit and connect the cables to the L,
N, and PE terminals of the main circuit breaker.
4. Fix the cables to the cable clamp in the electrical box.
40 6 Electrical Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
NOTE: The RJ45 port on the back of HMI is not available for any usage.
6 Electrical Connections 41
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
50/24 Custom alarm (fire sensor alarm or smoke sensor alarm) 20MA/12V Static pressure sensor
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
42 6 Electrical Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
2. Hold the handle and pull the electrical box 2. Remove the side cover from the box by removing five M4 x 10
pan head screws for CRC30 and four M4 x 10 pan head screws for CRC60.
3. Remove the 10DI board from the iCOM Edge board.
6 Electrical Connections 43
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
0 ON ON ON ON ON ON ON ON Primary Unit
Secondary
1 OFF ON ON ON ON ON ON ON
Unit 1
Secondary
2 ON OFF ON ON ON ON ON ON
Unit 2
Secondary
3 OFF OFF ON ON ON ON ON ON
Unit 3
Secondary
4 ON ON OFF ON ON ON ON ON
Unit 4
Secondary
5 OFF ON OFF ON ON ON ON ON
Unit 5
Secondary
6 ON OFF OFF ON ON ON ON ON
Unit 6
Secondary
7 OFF OFF OFF ON ON ON ON ON
Unit 7
Secondary
8 ON ON ON OFF ON ON ON ON
Unit 8
Secondary
9 OFF ON ON OFF ON ON ON ON
Unit 9
Secondary
10 ON OFF ON OFF ON ON ON ON
Unit 10
Secondary
11 OFF OFF ON OFF ON ON ON ON
Unit 11
Secondary
12 ON ON OFF OFF ON ON ON ON
Unit 12
Secondary
13 OFF ON OFF OFF ON ON ON ON
Unit 13
Secondary
14 ON OFF OFF OFF ON ON ON ON
Unit 14
Secondary
15 OFF OFF OFF OFF ON ON ON ON
Unit 15
NOTE: The iCOM Edge can connect up to 16 units. Unit CAN ID address must be set in sequence from 0 to 15.
NOTE: CAN ID 0 is primary unit. Teamwork parameters only can be set in primary unit and then shared to secondary
units. Secondary unit uploads operation status and alarms to the primary unit.
44 6 Electrical Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
NOTE: If the cable between the 37 and 38 terminals is removed and no remote on/off device is connected to the
terminals, the unit cannot be powered on.
NOTE: Only one remote temperature sensor is provided with the unit.
1. Insert the connector of the sensor to the RS485-1 port. Route the cable through the top or bottom of the unit.
Connect the second sensor to the first sensor.
2. Fix the sensor on rack surface using the magnets provided in the kit. Do not fix it on an empty rack. Set the
address on the dialing switch on the sensor, according to the following table.
Table 6.3 Address Settings of Remote Temperature Sensors
Sensor 1 2 3 4 5 6 ID
6 Electrical Connections 45
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
46 6 Electrical Connections
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
7 Start-up
7.1 Commissioning
WARNING! Risk of hair, clothing and jewelry entanglement with high speed rotating fan blades. Can cause
equipment damage, serious injury or death. Keep hair, jewelry and loose clothing secured and away from
rotating fan blades during unit operation.
WARNING! Risk of contact with high-speed, rotating fan impeller blades. Can cause injury or death. Open all
local and remote electrical-supply disconnect switches, verify with a voltmeter that power is off, and verify
that all fan impellers have stopped rotating before working in the unit.
• There is no leakage in the water inlet and outlet pipes, the water supply pipe of the humidifier, and the
drainage pipe.
• The filters are correctly installed, and the surface is clean.
• The air inlet and outlet are not blocked.
• The voltage of the main power supply is within ±10% of the rating.
• The power cables and control cables are correctly connected.
• The power cables and low voltage control cables are laid away from each other.
Supply chilled water to the unit. Open the air discharge valve on the water outlet pipe till water flow can be observed in the
transparent soft pipe under the air discharge valve. Close the valve.
7 Start-up 47
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
7.2 Start-up
7.2.1 First Start-up (or After Long Standstill)
To start up the unit:
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. If the supplied pipe is installed with variable frequency pump, close the manual shut-off valve on the bypass
pipe and check that the electric three-way valve is open. If the supplied pipe is installed with constant
frequency pump, open the manual shut-off valve on the bypass pipe and check that the electric three-way
valve is open.
NOTE: If the electric three-way valve is closed, press the button and rotate the handle in counter-clockwise direction
to the open position.
48 7 Start-up
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Figure 7.2 Location of Electric Three-way Valve and Manual Shut-off Valve
a CRC30 2 Button
7 Start-up 49
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
50 7 Start-up
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
8 HMI Display
8.1 Appearance
The HMI display is a 7-inch touch-screen color display.
The indicator (1) is located under the screen. Its colors and indication are described in the table below.
Yellow Unit is shut down, or the display fails to communicate with iCOM Edge
Red An alarm has been generated and the buzzer keeps generating sound (you can tap the display to stop the buzzer)
8 HMI Display 51
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
NOTE: If no password is entered, you can only view the menu settings.
Refer to Table 8.2 on the facing page to see the list of the touch keys.
52 8 HMI Display
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
View and configure the operation status, alarm information, temperature and humidity settings, parameter
1 Menu button
settings, and temperature and humidity graph. View version information and service information
Show the graphs of the average return air temperature, average return air humidity, average supply air
4 Graph button
temperature, and average remote temperature
5 Toggle button 1 Switch between the graphical display mode and the list display mode
9 ON/OFF button Press the button for three seconds to start or stop the unit
11 Toggle button 2 Switch between the sensor data page and the alarm page
12 Alarm list Show current alarms and the time when they are generated
Show the data of cooling, fan, electric heater, humidifier, dehumidifier, fan speed, heating status, and
13 Status display
humidifier status
14 Control mode Show unit settings and temperature and humidity data
15 Operating status Display the current state of the unit: unit run, remote off, display off, monitor off, and standby
8 HMI Display 53
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
2 Supply air temperature, return air temperature, or remote temperature, depending on the control mode
3 Desired supply air temperature, return air temperature, or remote temperature set by user
5 Control mode: chilled water valve is controled according to supply air temperature, return air temperature, or remote temperature
6 Control mode: chilled water valve is controled according to supply air humidity
NOTE: Alarms are displayed in time sequence, starting with the latest one.
NOTE: Up to 500 historical alarms can be stored. They will not be cleared when unit is powered off.
54 8 HMI Display
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Standby function
One or several units can be defined as standby unit. The standby unit fan runs at the speed of 0% by default. If the Back
Draft Control (BDR) mode is enabled, the standby unit fan will run at 20%. If a critical alarm or normal alarm is generated on
the master unit, a standby unit will start to run.
• Critical alarms: fan failure alarm (when the alarm handling is set to shut down), water leakage alarm (when the
alarm handling is set to shut down).
• Normal alarms:
• Airflow loss alarm, high supply temperature alarm, high return temperature alarm, and high remote
temperature alarm.
• Supply temp sensor 1 failure alarm, supply temp sensor 2 failure alarm, and supply temp sensor 3 failure
alarm. The standby unit will start to run if all the three alarms are generated on the primary unit when the
water valve and fans are controlled according to supply air temperature.
• Return temp sensor 1 failure alarm, return temp sensor 2 failure alarm, and return temp sensor 3 failure
alarm. The standby unit will start to run if all the three alarms are generated on the primary unit when the
water valve and fans are controlled according to return air temperature.
• Remote temp sensor 1 failure alarm, remote temp sensor 2 failure alarm, ..., remote temp sensor 10 failure
alarm. The standby unit will start to run if all the ten alarms are generated on the primary unit when the
water valve and fans are controlled according to remote temperature.
Rotation function
This function ensures that all the units have equal run time.
This function prevents the units from performing conflicting operations, such as cooling and heating, humidifying and
dehumidifying. The primary unit will calculate the number of cooling units and heating units (or humidifying units and
dehumidifying units). If cooling units (or humidifying units) are more than heating units (or dehumidifying units), the heating
units (or humidifying units) will stop working.
Cascade function
If an alarm is generated on the primary unit or the running units cannot keep the specified temperature, a standby unit will
start to run.
8 HMI Display 55
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
56 8 HMI Display
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
9 Maintenance
WARNING! All maintenance operations must be carried out strictly observing the European and National
accident prevention regulations, especially the accident prevention regulations concerning electrical
systems, refrigerators and manufacturing resources. Maintenance may be done to air conditioning
equipment only by authorized and qualified technicians. To keep all warranties valid, the maintenance must
adhere to the manufacturer’s instructions.
WARNING! The work should be done on the system only when it is at switched-off. Stop the system by
switching off the air conditioner at the controller and the main switch. Check that the electrical components
of device are off and not receiving a power supply.
NOTICE
Only original spare parts made by Vertiv may be used. Using third-party material can invalidate the warranty.
When the spare parts must be brazed, be careful not to damage the internal parts (gaskets, seals, o-rings, etc.).
NOTICE
Risk of release of hazardous substances into the environment. Can cause environmental pollution and violation
of environmental regulations.
NOTICE
When the unit stops work for a long time, drain the water inside the unit through the water drainage valve under
the coil. To open the valve, remove the water drain pan filter and remove the cap from the valve. The location of
the water drain pan filter is shown in Removing the Water Filter on page 60
Maintenance Period
Component Check Items
Monthly by user 3 months 6 months 1 year
Check unit/remote
display for clogged-filter X
General warning
Check bearings X
Fan
Check that motor
supports are fixed X
securely
9 Maintenance 57
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Maintenance Period
Component Check Items
Monthly by user 3 months 6 months 1 year
Check electrical
X
connections
Electronics
Check the operation of
X
controller
58 9 Maintenance
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
The complexity of water/glycol solution condition problems and the variations of required treatment programs make it
extremely important to obtain the advice of a competent and experienced water-treatment specialist and follow a
regularly-scheduled coolant-fluid system-maintenance program. It is important to note that improper use of water
treatment chemicals can cause problems more serious than using none. Proper inhibitor maintenance must be performed in
order to prevent corrosion of the glycol system. Consult the glycol manufacturer for testing and maintenance of inhibitors.
Do not mix products from different manufacturers.
NOTE: When replacing a faulty component, follow the relevant manufacturer instructions.
NOTE: When the spare parts must be brazed, be careful not to damage the internal parts (gaskets, seals, O-rings,
etc.).
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. Disconnect the main circuit breaker.
3. If the filters appear dirty, replace them.
NOTE: Before replacing filters, check that the air differential pressure switch tube is not damaged.
NOTE: After replacing filters, clear the fan operating time. Press the menu button on the HMI display, choose
Maintenance > Parameter Reset, and select Yes for Confirm Filter Maintenance.
9 Maintenance 59
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Item Description
1 Butterfly screw
Condensate pump
To replace the pump:
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. Disconnect the main circuit breaker.
3. Unplug the two power cables (labeled "Pump") from the terminals near the pump. Loosen the hose clamp on
the connection between the water inlet tube and the soft pipe. Loosen the hose clamp on the connection
between the drainage tube and the soft pipe. Pull out the soft pipes.
4. Loosen the hose clamp around the pump. Remove the pump and replace it.
60 9 Maintenance
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
3 Drainage tube
9.7 Fan
WARNING! Risk of electric shock and contact with high speed rotating fans. Can cause injury or death. Switch
off all local and remote electrical supplies, verify that power is off with a voltmeter and verify that all fans
have stopped rotating before working inside the unit cabinet or disconnecting the fan power wires.
1. Open the rear door. For CRC30, disconnect the main circuit breaker. For CRC60, remove the filters and then
disconnect the main circuit breaker.
2. Open the front door.
3. Remove the fan frame assembly by removing the four M5 x 12 hex screws in the corners.
4. Set the fan assembly in a work area.
5. Remove the fan by removing the four M4 x 80 pan head screws, remove one grounding screw that attach the
fan to the fan frame, and unplug the power supply terminal from the power socket on the fan frame assembly.
6. Replace the fan.
9 Maintenance 61
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
a CRC30 3 Fan
WARNING! Risk of electric shock and contact with hot surface. Can cause injury or death. Switch off all local
and remote electrical supplies and verify that power is off with a voltmeter before working inside the unit
cabinet.
1. Open the rear door and disconnect the main circuit breaker.
2. Open the front door.
3. Remove seven fan frame assemblies.
4. Remove the power supply cables from the terminal block of the electric heater.
62 9 Maintenance
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
5. Remove the M4 x 12 pan head screws from the electric heater. Each electric heater is fixed by four screws (two
on top the two on bottom). Take out two electric heaters.
6. Inspect and clean heating elements.
7. Inspect and tighten support hardware.
Item Description
1 Electric heater
1. Open the rear door and remove filters. For details on removing filters, see Remove filters. on page 31 .
2. Drain all the water from the cylinder by turning the power switch to 1 on the electrical box near the humidifier.
3. Disconnect the main circuit breaker.
4. Loosen the hose clamp and disconnect stream pipe from the top of the humidifier.
5. Disconnect the electrode wires from the top of the humidifier.
6. Disconnect the level sensor cables from the top of the humidifier.
7. Unscrew the soft pipe from the bottom of the humidifier.
9 Maintenance 63
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
8. Loosen the hose clamp and disconnect the water supply pipe under the humidifier.
9. Loosen the rubber belt around the cylinder and pull the cylinder out of the support bracket.
10. Replace the cylinder.
CAUTION: To prevent possible harm to the environment or human health from uncontrolled waste disposal,
recycle it responsibly to promote the sustainable reuse of material resources. To return your used device,
please use the return and collection systems or contact the retailer where the product was purchased. They
can take this product for environmental safe recycling.
NOTICE
64 9 Maintenance
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Please be environmentally responsible and recycle this product through your recycling facility at its end of life.
Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper
disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE).
The machine has been designed and built to ensure continuous operation. The working life of some of the main components,
such as the fan and the compressor, depends on the operating condition and maintenance that they receive.
9.11 Troubleshooting
The following table lists possible issues and their cause and corrective steps.
Rack temperature is too high Inlet water temperature too high Check cooling water temperature
Insufficient room cooling capacity Reduce rack heat load or add cooling units
Fans will not modulate from 100% Fan control not properly set Contact your local Vertiv™ representative
9 Maintenance 65
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Leak in the humidifier filling hose Contact your local Vertiv™ representative
Local display is not operational and Unit main circuit breaker is Off Switch on the unit
unit does not operate Control board supply issue Contact your local Vertiv™ representative
Contractor is engaged and there is no MCB of the heater is disconnected Check that voltage of the contractor is within normal range
heating effect
Heater is damaged Replace the heater
66 9 Maintenance
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
10 Appendices
Appendix A: Menu Structure
Level 1 Menu Level 2 Menu Parameter
Return Temp 1
Return Hmd 1
Return Temp 2
Avg Return Temp
Avg Return Hmd
Supply Temp 1
Supply Temp 2
Supply Temp 3
Avg Supply Temp
Avg Supply Hmd
Remote Temp 1
Temp/Hmd Information Remote Temp 2
Remote Temp 3
Remote Temp 4
Remote Temp 5
Remote Temp 6
Remote Temp 7
Remote Temp 8
Operation Status
Remote Temp 9
Remote Temp 10
Avg Remote Temp
CW Inlet Temp
CW Outlet Temp
CW Flow
System Information Air Flow
Cooling Capacity
Filter Clogged
High Condensate Water
Condensate Water Level
Remote Shutdown
Switch Status
Water Leakage
Heater Failure
Custom 1
Humidifier Failure
10 Appendices 67
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Unit 01 Status
Unit 02 Status
Unit 03 Status
Unit 04 Status
Unit 05 Status
Unit 06 Status
Unit 07 Status
Unit 08 Status
Unit 09 Status
Unit 10 Status
Unit 11 Status
Unit 12 Status
Unit 13 Status
Unit 14 Status
Unit 15 Status
Active Alarms -
Alarm Information
Historical Alarms -
Supply Temp SP
Temp Settings Return Temp SP
Temp/Hmd Settings
Remote Temp SP
Teamwork Mode
Unit Address
Unit Quantity
Standby Quantity
Rotation Quantity
Rotation Cycle
Rotate Interval Daily
Rotate At
Teamwork Settings Manual Rotation
Parameter Settings
Active/Standby Delay
Cascade Mode
Cascade Start Point
Cascade Stop Point
Cascade Max Point
Cascade Start Delay
Cascade Stop Delay
Cascade Min Time
68 10 Appendices
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Monitor Protocol
Communication Settings Monitor Baudrate
Monitor Address
Date Settings
Time Settings
Time Settings
Language
Display Settings Buzzer
Display Address
Level 1 Password
Password Settings
Level 2 Password
10 Appendices 69
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Country
Service Information Service
Enquiries
70 10 Appendices
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
High Return Temp The temperature of the return air is higher than the set value
Low Supply Temp The temperature of the supply air is lower than the set value
High Supply Temp The temperature of the supply air is higher than the set value
High Return Humidity The humidity of the return air is higher than the set value
Low Return Humidity The humidity of the return air is lower than the set value
Water Leakage The condensate water is leaking from the drain pan onto the room floor
High Condensate Water The condensate water in the drain pan reaches the highest level
Filter Maintenance The filter has not been maintained in the specified time period
Primary Unit Loss The primary unit cannot communicate with secondary units
Secondary Unit Loss The secondary unit cannot communicate with the primary unit
Return Temp Sensor 1 Failure, Return Temp Sensor 2 Failure, Return Temp The temperature of the return air is out of the detection range of the
Sensor 3 Failure return temperature sensor
The humidity of the return air is out of the detection range of the return
Return Humidity Sensor 1 Failure
humidity sensor
Supply Temp Sensor 1 Failure, Supply Temp Sensor 2 Failure, Supply Temp The temperature of the supply air is out of the detection range of the
Sensor 3 Failure supply temperature sensor
Remote Temp Sensor 1 Failure, Remote Temp Sensor 2 Failure, Remote Temp
Sensor 3 Failure, Remote Temp Sensor 4 Failure, Remote Temp Sensor 5
The air temperature is out of the detection range of the remote
Failure, Remote Temp Sensor 6 Failure, Remote Temp Sensor 7 Failure,
temperature sensor
Remote Temp Sensor 8 Failure, Remote Temp Sensor 9 Failure, Remote Temp
Sensor 10 Failure
Unit Address Duplicated The address of one unit is the same with the address of another unit
Low Return Temp The temperature of the return air is lower than the set value
10DI Communication Failure The 10DI board cannot communicate with the iCOM Edge board
Fan 1 Failure, Fan 2 Failure, Fan 3 Failure, Fan 4 Failure, Fan 6 Failure, Fan 8
The fan cannot work normally
Failure, Fan 9 Failure, Fan 10 Failure
This alarm can be set as Smoke Sensor Alarm or Fire Sensor Alarm. Or it
Custom 1
can be customized
10 Appendices 71
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Alarm Description
High CW Inlet Temp The temperature of the inlet chilled water is higher than the set point
Low CW Inlet Temp The temperature of the inlet chilled water is lower than the set point
High CW Outlet Temp The temperature of the outlet chilled water is higher than the set point
Low CW Outlet Temp The temperature of the outlet chilled water is lower than the set point
The temperature of the inlet chilled water is out of the detection range of
CW Inlet Temp Sensor Failure
the inlet CW temperature sensor
The temperature of the outlet chilled water is out of the detection range
CW Outlet Temp Sensor Failure
of the outlet CW temperature sensor
The static pressure is out of the detection range of the static pressure
Static Pressure Sensor Failure
sensor
The chilled water flow volume is out of the detection range of the CW flow
CW Flow Meter Failure
meter failure
72 10 Appendices
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
10 Appendices 73
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
kατ ασÀευαστ ρj δηλνξι ϋτ ι τ ο παÃϋν πÃοϊϋν εβναι Àατ ασÀευαmỲνο αỳm ωνα mε τ ιj οδηγβεj τ ηj E.E.:
2006/42/EC
2014/30/EU
74 10 Appendices
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Europe, the Middle East and Africa: For technical support, please contact your local Vertiv or Partner office. You can also
contact us using the contact details on our website: https://www.vertiv.com/en-emea/contacts2
10 Appendices 75
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
76 10 Appendices
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2021 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All
other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has
been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages
resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at
Vertiv’s sole discretion upon notice.
SL-70748_REVA_11-21