INSTALLATION DIAGRAM INDICATING ALARM PANEL Part Number = 3.10.02 (Alarm Panel Only) = 3.10.106K (Alarm Pane! with Kit) 1 exemal 5A Fuse ‘CABLE COLOR! = | vain Power supply s224v00 1 RED POWER SUPPLY 12-24 (+) D6 2BLACK POWER SUPPLY (-) 3.CREAM NOTUSED Enghe Snutdown, 4.BROWN NOTUSED Relay Contacis| S.CLEAR ‘SHUTDOWN COMMON, rrr WHITE SHUTDOWN NO | rr in Pa 7GREY SHUTDOWN NIG Os nceres ePINK ‘MOT USED. ae S.ORANGE NOT USED OPURPLE DETECTOR COMMON VLYELLOW-GREEN FIRE DETECTOR FIRE ALARM PRESSURE SWITCH 12BLUE LOW PRESSURE DETECTOR ~— Closed at pross = 0 KPa ‘open at press = 200 KPa + ‘Open 47KOhm EOL resistor active —_ fe LOW PRESSURE SWITCH (Open at press =0 KPa Closed at press = 900KP a + 12 PIN DEUTSCH PLUG MALE (FRONT VIEW) Faults Code Alarm Panel LED Fault and Beeps Code Fault Description 1 Beep + 1 Flash Fire Detector 1 Fault *) 2 Beeps + 2 Flashes Fire Detector 2 Fault or Electric Manual Actuator Fault 3 Beeps + 3 Flashes Cylinder Low Pressure Fault *) 4 Beeps + 4 Flashes Solenoid Valve Fault *) 5 Beeps + 5 Flashes Battery Backup Fault Notes: *) Only applies to Control & indicating panel. Fault indications are not latching. This means that the fault indication will disappear when the fault is repaired without resetting the alarm. The fault audible beep sound can be muted by pressing the “Mute” button.