You are on page 1of 144

Technical Data

Compact 5000 I/O Modules and EtherNet/IP Adapters


Specifications
Digital I/O Module Catalog Numbers 5069-IA16, 5069-IB16, 5069-IB16F, 5069-IB16K, 5069-IB6F-3W, 5069-OA16, 5069-OB8, 5069-
OB16, 5069-OB16F, 5069-OB16K, 5069-OW4I, 5069-OW16, 5069-OX4I
Analog I/O Module Catalog Numbers 5069-IF8, 5069-IY4, 5069-IY4K, 5069-OF4, 5069-OF4K, 5069-OF8
High-speed Counter Module Catalog Number 5069-HSC2xOB4
Safety I/O Module Catalog Numbers 5069-IB8S, 5069-IB8SK, 5069-OBV8S, 5069-OBV8SK
Serial Module Catalog Number 5069-SERIAL
Field Potential Distributor Catalog Number 5069-FPD
Address Reserve Module Catalog Number 5069-ARM
EtherNet/IP Adapter Catalog Number 5069-AENTR, 5069-AENTRK, 5069-AEN2TR
Topic Page
Summary of Changes 2
Digital I/O Modules 3
Analog I/O Modules 51
Safety I/O Modules 84
5069-HSC2xOB4 High-speed Counter Module 104
5069-SERIAL Serial Module 113
5069-FPD Field Potential Distributor 123
5069-ARM Address Reserve Module 127
5069-AENTR and 5069-AENTRK EtherNet/IP Adapters 130
5069-AEN2TR EtherNet/IP Adapter 135
Minimum Spacing Requirements 140
Additional Resources 142

The Compact 5000™ I/O architecture provides a wide range of input and output modules to span many applications,
from high-speed digital to process control. The architecture uses Producer/Consumer technology that allows input
information and output status to be shared among multiple Logix 5000™ controllers.
Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Compact 5000 I/O modules are used as local I/O modules in CompactLogix™ 5380 and Compact GuardLogix® 5380
controller systems or as remote I/O modules with CompactLogix 5380, Compact GuardLogix 5380 controllers, and
some other Logix 5000 controllers. The modules are configured with the Studio 5000 Logix Designer® application.

The I/O modules require a removable terminal block (RTB) to connect field-side wiring. RTBs are not included with
the I/O modules. You must order RTBs separately.

Summary of Changes
This publication was revised for the following:

Change Page
To add information about the following new Compact 5000 I/O modules:
5069-IB16K digital 16-point conformally coated sinking input module 9
5069-OB16K digital 16-point conformally coated sinking input module 30
5069-IY4K analog conformally coated current/voltage/RTD/thermocouple input module 60
5069-OF4K analog conformally coated analog current/voltage output module 75
5069-IB8S and 5069-IB8SK digital safety input modules 84
5069-OBV8S and 5069-OBV8SK digital safety output modules 92
5069-AENTRK - conformally coated EtherNet/IP™ adapter 130
Update the wiring diagram for the 5069-OW16 module 41
Update the functional block diagram for the 5069-OW16 module 42
Update information about the devices that the 5069-IF8 modules supports 51
Update information about the devices that the 5069-IY4 and 5069-IY4K modules support 60
Update the wiring diagrams for the 5069-OB4, 5069-OB4K, and 5069-OB8 modules 75

2 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Power Compact 5000 I/O Modules


There are different types of power that are used with Compact 5000 I/O modules.

Power Type Description Related Specifications


Name Description
Level of MOD Power current that the module
System-side power that is used to operate a local or remote system. Power passes across a MOD Power
Module draws from the MOD Power bus
MOD Power bus. Modules draw current from the bus and pass the remaining current to
(MOD) Power MOD Power Maximum level of MOD Power current that
the next module.
Passthrough, max the module can pass to the next module.
Field-side power that some modules uses to power field-side devices. Power passes across Level of SA Power current that the module
SA Power
an SA Power bus. Some modules draw current from the bus and pass the remaining draws from the SA Power bus
current to the next module. Other modules do not draw current from the bus but do pass
the current to the next module.
Sensor/ You use 5069-FPD field potential distributors to establish new SA Power buses in a
Actuator (SA) system.
Power IMPORTANT: Remember the following: SA Power Maximum level of SA Power current that the
• If the system includes DC type modules and AC type modules, you must use a field Passthrough, max module can pass to the next module.
potential distributor to install them on separate SA Power buses.
• You cannot install AC type modules directly next to a Compact GuardLogix 5380
controller. You must first install a field potential distributor.
Field-side power that some Compact 5000 I/O modules use instead of SA power. Modules
that use LA power do not use SA power. They only pass SA power to the next to the next
Local I/O module in the system. Maximum level of LA Power current that you
Actuator (LA) LA Power can apply to the module, by channel, group, or
Power You must install modules that use LA Power on an SA Power bus with the same module module.
type. For example, you must install a 5069-OB8 module on an SA Power bus that includes
DC type modules.

For more information on MOD power, SA power, and LA power, see the user manuals listed in Additional Resources on
page 142.

Digital I/O Modules

I/O Type Cat. No. Description Pages


AC digital input 5069-IA16 79…264V AC 16-point, input module 4
5069-IB16 10…32V DC 16-point, sinking input module
5069-IB16K 10…32V DC 16-point, conformal coated sinking input module 9
DC digital input
5069-IB16F 10…32V DC 16-point, sinking fast input module
5069-IB6F-3W 10…32V DC 6-point, 3-wire, sinking fast input module 14
AC digital output 5069-OA16 85…264V AC 16-point, output module 20
5069-OB8 10…32V DC 8-point, sourcing high-current output module 25
069-OB16 10…32V DC 8-point, sourcing high-current output module
DC digital output
5069-OB16K 10…32V DC 16-point, conformal coated sourcing output module 30
5069-OB16F 10…32V DC 16-point, sourcing fast output module
5069-OW4I 5…264V AC /125V DC 4-point, isolated normally open relay output module 35
Relay output 5069-OW16 5…264V AC/125V DC 16-point, normally open relay output module 41
5069-OX4I 5…264V AC /125V DC 4-point, isolated normally open/normally closed relay output module 46

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 3


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-IA16 Digital 16-point 120/240V AC Input Module

This figure shows a wiring diagram for the 5069-IA16 module.

5069-IA16 Wiring Diagram

Channel Connections
The diagram shows devices that are connected to channels 0, 2, 4, 6, 8,
and 10. You are not restricted to using only those channels.
You can connect devices to any channel or combination of channels as
needed.
SA Power
Connections to an external power supply that provides SA Power via
the SA Power RTB on one of the following: Input Channel 0 0

• CompactLogix 5380 controller Input Channel 1 1

Input Channel 2 2
• CompactLogix 5480 controller
Input Channel 3 3
• 5069-AENTR or 5069-AEN2TR EtherNet/IP adapter
Input Channel 4 4
• 5069-FPD field potential distributor
Input Channel 5 5
IMPORTANT: Remember the following:
Input Channel 6 6
• The 5069-IA16 module uses AC SA power. You must connect AC
Input Channel 7 7
power to the component, that is, CompactLogix 5380 controller,
adapter, or field potential distributor, that provides SA Power to the Input Channel 8 8

module. Input Channel 9 9

• If you install a 5069-IA16 module as a local I/O module in a Input Channel 10 10

Compact GuardLogix 5380 controller system, you must install Input Channel 11 11

a field potential distributor that has AC power that is connected to it Input Channel 12 12

and install the 5069-IA16 module next to the field potential SA+ (L1) Input Channel 13 13
distributor. 120V/240V AC
Input Channel 14 14
SA– (L2)
You cannot install modules that draw AC SA power next to a Input Channel 15 15
Compact GuardLogix 5380 controller. Compact GuardLogix 5380 No Connect 16
controllers do not support AC power on their SA Power RTBs.
No Connect 17
• The 5069-IA16 module inputs use a shared common. The inputs
have a return through internal module circuitry to the SA (–)
terminal on the SA Power RTB.
• If you install modules in a system that use AC SA power and DC SA
power, you must install them on separate SA Power buses.
• You use a 5069-FPD field potential distributor to establish a new SA
Power bus in a system. SA Power buses are isolated from each other.
To keep the modules on separate SA Power buses, complete these
steps.
1. Install the modules that use one type of SA power, for example
DC, to the right of the adapter or controller, that is, the first SA
Power bus.
2. Install the 5069-FPD field potential distributor to establish a
second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.

4 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-IA16 module.

5069-IA16 Functional Block Diagram

Module 24V DC
Status Power
Indicators Supply MOD 5
Power 0
6
SA Power AC (+) 9
Backplane
Input Communication
B
Current Limiting Backplane a
Isolation
Input Circuits ASIC Nonvolatile c
Memory k
Input p
l
a
n
SA Power AC (–) e

SA Power AC (+)

Technical Specifications - 5069-IA16


Attribute 5069-IA16
On-state voltage, min 79V AC
On-state voltage, nom 120/240V AC
On-state voltage, max 264V AC
Off-state voltage, max 40V AC
Input current per channel, max 15 mA @ 264V AC
2 mA @ 79V AC
On-state current, min
3 mA @ 164V AC
5 mA @ 120V AC/50 Hz
6 mA @ 120V AC/60 Hz
On-state current, nom
9 mA @ 240V AC/50 Hz
11 mA @ 240V AC/60 Hz
On-state current, max 15 mA @ 264V AC
Off-state current, max 2 mA
24 kΩ @ 120V AC/50 Hz
20 kΩ @ 120V AC/60 Hz
Input impedance, nom
27 kΩ @ 240V AC/50 Hz
22 kΩ @ 240V AC/60 Hz
Input impedance, min 17.6 kΩ @ 264V AC/63 Hz
Inrush current, max 600 mA
Input delay time
Off to On 10 ms (typ) @ 0...60 °C (32…140 °F)
On to Off 10 ms (typ) @ 0...60 °C (32…140 °F)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 5


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IA16


Attribute 5069-IA16
Input filter times
Hardware delay: 10 ms (typ) + filter time
Off to On User-selectable filter times:
• 120V AC input - 1 ms
• 240V AC input - 1 ms, 2 ms, 5 ms
Hardware delay: 10 ms (typ) + filter time
On to Off User-selectable filter times:
• 120V AC input - 10 ms, 20 ms
• 240V AC input - 5 ms, 10 ms, 20 ms
With the 5069-IA16 module, the Logix Designer application lets you choose multiple filter values, including values that are invalid for some input signals. For example, the only
valid Off to On filter value when a 120V AC signal is connected to the module is 1 ms. However, you can choose 1 ms, 2 ms, or 5 ms. If you select an invalid input filter value, the
module can read signal levels incorrectly. For more information, see the 5000 Series Digital I/O Modules in Logix 5000 Control Systems User Manual, publication 5000-UM004.

General Specifications - 5069-IA16


Attribute 5069-IA16
Number of inputs 16 (One group of 16)
Voltage category 120/240V AC
Voltage and current ratings
Input voltage range 79…264V AC
Input voltage frequency 47…63 Hz
MOD Power 75 mA @ 18…32V DC
MOD Power Passthrough, max(1) 9.55 A @ 18…32V DC
SA Power 240 mA @ 79…264V AC
SA Power Passthrough, max(2) 9.975 A @ 79…264V AC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
The 5069-IA16 module complies to ATEX/IECEx when used at or below 125V AC.
Power dissipation, max 3.5 W
Thermal dissipation, max 11.9 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage Type tested at 1800V AC for 60 s
No isolation between individual channels
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
16 yellow/red I/O status indicators
Slot width 1
Dimensions (HxWxD) 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
RTB keying None
2 - input ports
Wire category 2 - power ports
1 wire per terminal for each signal port

6 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IA16


Attribute 5069-IA16
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
5069-RTB18-SPRING connections in.) max diameter including insulation, single wire connection only.
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
5069-RTB18-SCREW connections in.) max diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type rating None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
IEC Input Compatibility Type 1
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.

Jp

Environmental Specifications - 5069-IA16


Attribute 5069-IA16
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 7


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-IA16


Attribute 5069-IA16
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±4 kV @ 5 kHz on signal ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Corrosion resistance classification ISA S71.04 G2

Certifications - 5069-IA16
Certification(1) 5069-IA16
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM • EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

8 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-IB16, 5069-IB16K, and 5069-IB16F Digital 16-point Sinking Input Modules

This figure shows a wiring diagram for the 5069-IB16, 5069-IB16K, and 5069-IB16F modules.

5069-IB16, 5069-IB16K, and 5069-IB16F Wiring Diagram


Channel Connections
The example shows devices that are connected to channels 0, 3, and 6.
You are not restricted to using only those channels. DC INPUT

You can connect devices to any channel or combination of channels


as needed.

SA Power 5069-IB16

Connections to an external power supply that provides SA power via the


SA Power RTB on one of the following:
Input Channel 0 0
• CompactLogix 5380 controller Input Channel 1 1
• Compact GuardLogix 5380 controller Input Channel 2 2
• CompactLogix 5480 controller 2-wire
Sensor Input Channel 3 3

• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Input Channel 4 4

• 5069-FPD field potential distributor Input Channel 5 5


DC (+) 3-wire
IMPORTANT: Remember the following: Input Channel 6 6

• The 5069-IB16, 5069-IB16K, and 5069-IB16F modules use DC SA DC (–) Sensor


Input Channel 7 7

power. You must connect DC power to the component, that is, Input Channel 8 8

controller, adapter, or field potential distributor, that provides SA Input Channel 9 9


Power to the modules. Input Channel 10 10
• The 5069-IB16, 5069-IB16K, and 5069-IB16F module inputs use a Input Channel 11 11
shared common. The inputs have a return through internal module
Input Channel 12 12
circuitry to the SA (–) terminal on the SA Power RTB.
Input Channel 13 13
• If you install modules in a system that use AC SA power and DC SA
Input Channel 14 14
power, you must install them on separate SA power buses.
Input Channel 15 15
• You use a 5069-FPD field potential distributor to establish a new SA
No Connect 16
Power bus in a system. SA Power buses are isolated from each other.
To keep the modules on separate SA Power buses, complete these No Connect 17

steps.
1. Install the modules that use one type of SA power, for example DC,
to the right of the adapter or controller, that is, the first SA
Power bus.
2. Install the 5069-FPD field potential distributor to establish a
second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.
IMPORTANT: The 5069-IB16K and 5069-IB16K modules are wired the
same as the wiring diagram that is shown for the 5069-IB16 module.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 9


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-IB16, 5069-IB16K, and 5069-IB16F modules.

5069-IB16, 5069-IB16K, and 5069-IB16F Functional Block Diagram

Module 24V DC
Status Power
Indicators Supply MOD 5
Power 0
6
DC (+) Backplane 9
Input Communication
B
Current Limiting Backplane a
Isolation
Input Circuits ASIC Nonvolatile c
Memory k
Input p
Transient l
Suppression a
n
SA Power DC (–) e

SA Power DC (+)

Technical Specifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Attribute 5069-IB16, 5069-IB16K 5069-IB16F
On-state voltage, min 10V DC
On-state voltage, nom 24V DC
On-state voltage, max 32V DC
On-state current, min 4 mA @ 10V
On-state current, nom 6 mA @ 24V DC
On-state current, max 7.4 mA @ 32V DC
Off-state voltage, max 5V DC
Off-state current, max 1.5 mA
Input impedance, min 1.33 kΩ
Input impedance, nom 4.1 kΩ
Input impedance, max 7.0 kΩ
Inrush current, max < 250 mA peak (decaying to, 37% in 22 ms, without activation)
Input delay time (screw to backplane)
Off to On ≤ 100 μs, ±10 μs @ 25 °C (77 °F) ≤ 10 μs, ±1 μs @ 25 °C (77 °F)
On to Off ≤ 100 μs, ±10 μs @ 25 °C (77 °F) ≤ 10 μs, ±1 μs @ 25 °C (77 °F)
Input drift over temperature span ±100 ns/°C (55.6 ns/°F) from 0…60 °C (32…140 °F) < 10 ns/°C (5.56 ns/°F) from 0…60 °C (32…140 °F)
Input On to Off minimum pulse width 60 μs 6 μs
Input Off to On minimum pulse width 60 μs 6 μs

10 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Attribute 5069-IB16, 5069-IB16K 5069-IB16F
Input filter time
Hardware delay: 50 μs + filter time Hardware delay: 2 μs + filter time
Off to On
User-selectable filter time: 0…50 ms User-selectable filter time: 0…50 ms
Hardware delay: 50 μs + filter time Hardware delay: 3 μs + filter time
On to Off
User-selectable filter time: 0…50 ms User-selectable filter time: 0…50 ms
Reverse polarity protection Yes
Overvoltage protection, max 36V (fuse protected)
Pulse and period measurements Not supported ±2 μs
Counter frequency 0 - fmax = 500 Hz (inv period 2 ms) 0 - fmax = 30 kHz (inv period 33.3 μs)
Frequency counter 0 - fmax = 500 Hz (inv period 2 ms) 0 - fmax = 30 kHz (inv period 33.3 μs)
±10 μs accuracy
Timestamp of inputs Not supported
1 ns resolution
Overrides Not supported
Pulse latching Not supported Supported
Four events supported (triggered by any input or simple
Events Not supported counters)
Pattern matching Not supported Supported
Extended counters Not supported

General Specifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Attribute 5069-IB16, 5069-IB16K 5069-IB16F
Inputs 16 Channels (1 group of 16), sinking
Voltage category 12/24V DC Sink
Voltage and current ratings
Input ratings 4…7.4 mA per channel @ 10…32V DC
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
SA Power 200 mA @ 10…32V DC
(2)
SA Power Passthrough, max 9.95 A @ 10…32V DC
Power dissipation, max 3.9 W
Thermal dissipation, max 13.3 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage No isolation between SA Power and input ports
No isolation between individual input ports
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
16 yellow/red I/O status indicators
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 11


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Attribute 5069-IB16, 5069-IB16K 5069-IB16F
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
RTB keying None
2 - input ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
5069-RTB18-SPRING connections in.) max diameter including insulation, single wire connection only.
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
5069-RTB18-SCREW connections in.) max diameter including insulation, single wire connection only.
5069-RTB18-SPRING connections: 10 mm (0.39 in.)
Insulation stripping length
5069-RTB18-SCREW connections: 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX/IECEx temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Attribute 5069-IB16, 5069-IB16K, 5069-IB16F
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
0…60 °C (32…140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

12 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Attribute 5069-IB16, 5069-IB16K, 5069-IB16F
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on input ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on input ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

Certifications - 5069-IB16, 5069-IB16K, and 5069-IB16F


Certification(1) 5069-IB16, 5069-IB16K, 5069-IB16F
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 13


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-IB6F-3W Digital 3-wire Sinking Input Module

This figure shows a wiring diagram for the 5069-IB6F-3W module.

5069-IB6F-3W Wiring Diagram

Channel Connections
The diagram shows devices that are connected to channels 0
and 2. You are not restricted to using only those channels.
You can connect devices to any channel or combination of
channels as needed.
DC INPUT

SA Power
5069-IB6F-3W
Connections to an external power supply that provides SA power
are made via the SA Power RTB on one of the following:
• CompactLogix 5380 controller Input Channel 0 0

• Compact GuardLogix 5380 controller 3-wire SA+ (24V DC) 1

• CompactLogix 5480 controller Sensor SA- (24V DC Return) 2

• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Input Channel 1 3

• 5069-FPD field potential distributor SA+ (24V DC) 4

IMPORTANT: Remember the following: SA- (24V DC Return) 5

• The 5069-IB6F-3W module uses DC SA power. You must Input Channel 2 6

connect DC power to the component, that is, controller, 2-wire SA+ (24V DC) 7

adapter, or field potential distributor, that provides SA Power Sensor SA- (24V DC Return) 8

to the module. Input Channel 3 9

• If you install modules in a system that use AC SA power and DC SA+ (24V DC) 10

SA power, you must install them on separate SA power buses. SA- (24V DC Return) 11

• You use a 5069-FPD field potential distributor to establish a Input Channel 4 12

new SA Power bus in a system. SA Power buses are isolated SA+ (24V DC) 13
from each other. To keep the modules on separate SA Power SA- (24V DC Return) 14
buses, complete these steps.
Input Channel 5 15
1. Install the modules that use one type of SA power, for
SA+ (24V DC) 16
example DC, to the right of the adapter or controller, that
SA- (24V DC Return) 17
is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to establish
a second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.

14 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-IB6F-3W module.

5069-IB6F-3W Functional Block Diagram

Module 24V DC
Status
Power
Indicators
Supply MOD
Power
5
0
6
Backplane 9
Communication
Input B
Backplane
Isolation
ASIC
a
Nonvolatile c
Current Limiting
Prot DC (+) Transient Memory k
3-wire Input Circuits and
Sensor Suppression Protection p
Prot DC (Return) l
a
n
SA Power DC (Return) e

SA Power DC (+)

Technical Specifications - 5069-IB6F-3W


Attribute 5069-IB6F-3W
On-state voltage, min 10V DC
On-state voltage, nom 24V DC
On-state voltage, max 32V DC
Off-state voltage, max 5V DC
On-state current, min 4 mA @ 10V DC
On-state current, nom 6 mA @ 24V DC
On-state current, max 7.4 mA @ 32V DC
Off-state current, max 1.5 mA
Input impedance, nom 4.1 kΩ
Input impedance, max 7.0 kΩ
Inrush current, max < 250 mA peak (decaying to, 37% in 22 ms, without activation)
Input delay time (screw to backplane)
Off to On ≤ 10 μs, ±1 μs @ 25 °C (77 °F)
On to Off ≤ 10 μs, ±1 μs @ 25 °C (77 °F)
Input drift over temperature span ±10 ns/°C (5.56 ns/°F) from 0…60 °C (32…140 °F)
Input On to Off minimum pulse width 6 μs
Input Off to On minimum pulse width 6 μs

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 15


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IB6F-3W


Attribute 5069-IB6F-3W
Input filter time
Hardware delay: 2 μs + filter time
Off to On
User-selectable filter time: 0…50 ms
Hardware delay: 3 μs + filter time
On to Off
User-selectable filter time: 0…50 ms
Reverse polarity protection Yes
Overvoltage protection, max 36V (fuse protected)
Pulse width and period measurements ±2 μs
Simple counters
0 - fmax = 30 kHz (inv period 33.3 μs)
Counter frequency
Frequency counter 0 - fmax = 30 kHz (inv period 33.3 μs)
±10 μs accuracy
Timestamp of inputs
1 ns resolution
Overrides Not supported
Pulse latching Supported
Events 4 events supported (triggered by any input or simple counters)
Pattern matching Supported
Extended counters Not supported

General Specifications - 5069-IB6F-3W


Attribute 5069-IB6F-3W
Inputs 6 Channels (1 group of 6), sinking
Voltage category 12/24V DC Sink
Voltage and current ratings
Input ratings 4…7.4 mA per channel @ 10…32V DC
150 mA per channel @ 10…32V DC
Output supply ratings
900 mA per module @ 10…32V DC
MOD Power 75 mA @ 18V…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
SA Power 900 mA @ 10…32V DC
(2)
SA Power Passthrough, max 9.95 A @ 10…32V DC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
Power dissipation, max 2.4 W
Thermal dissipation, max 8.1 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage No isolation between SA Power and input ports
No isolation between individual input ports
Module keying Electronic, module keying, software configurable
1 green/red module status indicator
Indicators
6 yellow/red I/O status indicators
Slot width 1

16 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IB6F-3W


Attribute 5069-IB6F-3W
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
2 - input ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB18-SPRING removable terminal block diameter including insulation, single wire connection only.
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB18-SCREW removable terminal block diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SPRING removable terminal block 10 mm (0.39 in.)
5069-RTB18-SCREW removable terminal block 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type rating None (Open - style)
North American temp code T4
ATEX/IECEx temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 17


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-IB6F-3W


Attribute 5069-IB6F-3W
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max. 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharge
IEC 61000-4-2 8 kV air discharge
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on input ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on input ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

18 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-IB6F-3W
Certification(1) 5069-IB6F-3W
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 19


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OA16 Digital 16-point 120/240V AC Output Module

This figure shows a wiring diagram for the 5069-OA16 module.

5069-OA16 Wiring Diagram

Channel Connections
The diagram shows devices that are connected to channels
0, 4, 8, and 12. You are not restricted to using only those
channels.
You can connect devices to any channel or combination of
channels as needed.

SA Power
Connections to an external power supply that provides SA CR Output Channel 0 0
Power via the SA Power RTB on one of the following:
Output Channel 1 1
• CompactLogix 5380 controller Output Channel 2 2
• CompactLogix 5480 controller Output Channel 3 3

• 5069-AENTR or 5069-AEN2TR EtherNet/IP adapter CR Output Channel 4 4

• 5069-FPD field potential distributor Output Channel 5 5

IMPORTANT: Remember the following: Output Channel 6 6

• The 5069-OA16 module uses AC SA power. You must Output Channel 7 7

connect AC power to the component, that is, CR Output Channel 8 8

CompactLogix 5380 controller, adapter, or field potential Output Channel 9 9


distributor, that provides SA Power to the module. Output Channel 10 10

If you install a 5069-OA16 module as a local I/O Output Channel 11 11


module in a Compact GuardLogix 5380 controller CR Output Channel 12 12
system, you must install a field potential distributor that Output Channel 13 13
has AC power that is connected to it and install the Output Channel 14 14
5069-OA16 module next to it.
Output Channel 15 15
You cannot install modules that draw AC SA power next to
SA- (L2) No Connect 16
a Compact GuardLogix 5380 controller. 120/240V AC
SA+ (L1) No Connect 17
Compact GuardLogix 5380 controllers do not support AC
power on their SA Power RTBs.
• The 5069-OA16 module outputs use a shared common.
The outputs have a return through internal module
circuitry to the SA (–) terminal on the SA Power RTB.
• If you install modules in a system that use AC SA power
and DC SA power, you must install them on separate SA
Power buses.
• You use the 5069-FPD field potential distributor to
establish a new SA Power bus in a system. SA Power buses
are isolated from each other. To keep the modules on
separate SA Power buses, complete these steps.
1. Install the modules that use one type of SA power, for
example DC, to the right of the adapter or controller,
that is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to
establish a second SA Power bus.
3. Install the modules that use the other type of SA
power, for example AC, on the second SA Power bus.

20 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OA16 module.

5069-OA16 Functional Block Diagram

Module 24V DC
Status
Power
Indicators
Supply MOD 5
Power 0
6
Backplane 9
Output Communication
B
Output Backplane a
Isolation
Circuitry ASIC Nonvolatile c
Memory k
p
l
a
Isolation n
Field Power Loss e
Detection Circuitry SA+ (L1)

SA- (L2)

Technical Specifications - 5069-OA16


Attribute 5069-OA16
On-state voltage, min 85V AC
On-state voltage, nom 120/240V AC
On-state voltage, max 264V AC
On-state voltage drop, max 1.5V AC @ 0.5 A
Output current per channel, max 0.5 A
Output current per module, max 4A
(1) 1 mA
Off-state leakage current, max
Surge current per point 5 A max for 25 ms per point, repeatable every 2 s
Output delay time (backplane to screw)
Off to On 1/2 cycle time (typ) @ 0...60 °C (32…140 °F)
On to Off 1/2 cycle time (typ) @ 0...60 °C (32…140 °F)
Field power loss detection Yes
No load detection diagnostics Not supported
Output short circuit/overload/overtemp detection Not supported
Output short circuit/overload protection Not supported
Reverse polarity protection Not supported
Overvoltage protections, max Not supported
Scheduled outputs Not supported
Resistive/General Pilot Duty
Pilot duty rating
0.5 A pilot duty
• Hold Last State
Output control in fault state per point • On
• Off (default)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 21


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OA16


Attribute 5069-OA16
• Hold Last State
Output states in program mode per point • On
• Off (default)
• Hold Last State
Output states in fault mode per point • On
• Off (default)
• 1s
• 2s
Duration of fault mode per point • 5s
• 10 s
• Forever (default)
(1) Recommended Loading Resistor - To limit the effects of leakage current through solid-state outputs, you can connect a loading resistor in parallel with your load. For 120V AC operation, use a 15 KΩ, 2 W resistor. For 240V AC
operation, use a 15 KΩ, 5 W resistor.

General Specifications - 5069-OA16


Attribute 5069-OA16
Number of outputs 16 (One group of 16)
Voltage category 120/240V AC
Voltage and current ratings
Output voltage range 85…264V AC
Output voltage frequency 47…63 Hz
MOD Power 100 mA @ 18…32V DC
MOD Power Passthrough, max(1) 9.55 A @ 18…32V DC
SA Power 4 A @ 85…264V AC
(2)
SA Power Passthrough, max 9.975 A @ 85…264V AC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
The 5069-OA16 module complies to ATEX/IECEx when used at or below 125V AC.
Power dissipation, max 3.4 W
Thermal dissipation, max 11.6 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage Type tested at 1800V AC for 60 s
No isolation between individual channels
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
16 yellow/red I/O status indicators
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.

22 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OA16


Attribute 5069-OA16
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
RTB keying None
2 - output ports
Wire category 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
5069-RTB18-SCREW connections in.) max diameter including insulation, single wire connection only.
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
5069-RTB18-SPRING connections in.) max diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type rating None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.

Environmental Specifications - 5069-OA16


Attribute 5069-OA16
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 23


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OA16


Attribute 5069-OA16
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±4 kV @ 5 kHz on signal ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Corrosion resistance classification ISA S71.04 G2

Certifications - 5069-OA16
Certification(1) 5069-OA16
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM • EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
When used at or below 125V DC or 30V DC
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

24 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OB8 Digital 8-point 24V DC Output Module

This figure shows a wiring diagram for the 5069-OB8 module.

5069-OB8 Wiring Diagram

Channel Connections
The diagram shows devices that are
connected to channels 0 and 3. You are not
restricted to using only those channels.
You can connect devices to any channel or
combination of channels as needed.

LA Power
The Local Actuator (LA+ and LA –)
connections are used to supply field-side
power to the module.
Output channels 0…3 use LA0 +/–, and
output channels 4…7 use LA1 +/–. CR Output Channel 0 0

Output Channel 1 1

Output Channel 2 2

• The 5069-OB8 module does not draw Output Channel 3 3

current from the SA power bus. LA0 – 4

Still, the module is a DC-type module, LA0 – 5

and you must install it on a DC SA Power LA0 – 6

bus. – LA0 – 7

• If you install modules in a system that 24V DC


+ LA0 + 8
use AC SA power and DC SA power, you
Output Channel 4 9
must install them on separate SA Power
buses. Output Channel 5 10

• You use a 5069-FPD field potential Output Channel 6 11

distributor to establish a new SA Power Output Channel 7 12

bus in a system. SA Power buses are LA1 – 13

isolated from each other. To keep the LA1 – 14

modules on separate SA Power buses, LA1 – 15

complete these steps. LA1 – 16

1. Install the modules that use one type LA1 + 17

of SA power, for example DC, to the


right of the adapter or controller, that
is, the first SA Power bus.
2. Install the 5069-FPD field potential
distributor to establish a second SA
Power bus.
3. Install the modules that use the other
type of SA power, for example AC, on
the second SA Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 25


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OB8 module.

5069-OB8 Functional Block Diagram

Module 24V DC
Status
Power
Indicators
Supply MOD 5
Power 0
6
Backplane 9
Communication
Output B
Output Backplane a
Isolation
Circuitry ASIC Nonvolatile c
Inductive Kickback Memory k
Suppression p
l
LAx + a
n
e
Soft Start 24V DC to 5V DC
Circuitry Converter

LAx -

Technical Specifications - 5069-OB8


Attribute 5069-OB8
(1)
On-state voltage, min 10V DC
(1)
On-state voltage, nom 24V DC
On-state voltage, max(1) 32V DC
(1)
On-state voltage drop, max 0.25V DC
(1)
Off-state voltage, max < 10V DC
(1)
Off-state voltage, max 5V DC
On-state current per channel, min(1) 1 mA
(2)
Off-state leakage current per point, max 0.5 mA
Output current per channel, max 2A
Output current per group, max 8A
Output current per module, max 16 A
Surge current per point 4 A max for 10 ms per point, repeatable every 2 s
Output delay time (backplane to screw)
Off to On ≤ 100 μs @ 25 °C (77 °F) @ 2 A
On to Off ≤ 100 μs @ 25 °C (77 °F) @ 2 A
Pulse width, min ≤ 200 μs Ton min + Toff min @ 2 A @ 25 °C (77 °F)
Output drift over temperature span ±100 ns/°C (55.6 n/°F) from 0…60 °C (32…140 °F) @ 2 A
Field power loss detection Yes
No load detection diagnostics Yes (per channel diagnostics)
Output short circuit/overload/overtemp detection Yes (per channel diagnostics)
Output short circuit/overload protection Yes
Reverse voltage protection Yes
Overvoltage protection, max 36V (fuse protected)

26 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OB8


Attribute 5069-OB8
Resistive/General Pilot Duty
Pilot duty rating
2 A pilot duty
• Hold Last State
Output control in fault state per point • On
• Off (default)
• Hold Last State
Output states in program mode per point • On
• Off (default)
• Hold Last State
Output states in fault mode per point • On
• Off (default)
• 1s
• 2s
Duration of fault mode per point • 5s
• 10 s
• Forever (default)
(1) Local Actuator (LA) Field Power related attributes.
(2) Recommended Loading Resistor - To limit the effects of leakage current through solid-state outputs, you can connect a loading resistor in parallel with your load. For 24V DC operation, use a 5.6 KΩ, 0.5 W resistor for
transistor outputs.

General Specifications - 5069-OB8


Attribute 5069-OB8
Number of outputs 8 (Two groups of 4)
Voltage category 24V DC
Voltage and current ratings
Output voltage range 10…32V DC
MOD Power 75 mA @ 18…32V DC
(1) 9.55 A @ 18…32V DC
MOD Power Passthrough, max
2 A per channel @ 10…32V DC
LA Power 8 A per group @ 10…32V DC
16 A per module @ 10…32V DC
SA Power Passthrough, max(2)
9.95 A @ 10…32V DC
The module does not draw SA Power current.
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
Power dissipation, max 3.2 W
Thermal dissipation, max 10.9 BTU/hr
250V (continuous), Basic Insulation Type
Type tested at 1800V AC for 60 s
Isolation voltage
No isolation between LA power and output ports
No isolation between individual output ports
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
8 yellow/red I/O status indicators
Slot width 1
Dimensions (HxWxD) 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 27


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OB8


Attribute 5069-OB8
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
RTB keying None
2 - output ports
Wire category 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
5069-RTB18-SPRING connections in.) max diameter including insulation, single wire connection only.
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
5069-RTB18-SCREW connections in.) max diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
Weight, approx 175 g (0.39 lb)
Enclosure type rating None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.

Environmental Specifications - 5069-OB8


Attribute 5069-OB8
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)

28 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OB8


Attribute 5069-OB8
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±4 kV @ 5 kHz on signal ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Corrosion resistance classification ISA S71.04 G2

Certifications - 5069-OB8
Certification(1) 5069-OB8
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
RCM Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act,
KC Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 29


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OB16, 5069-OB16K, and 5069-OB16F Digital 16-point Sourcing Output Modules

This figure shows a wiring diagram for the 5069-OB16, 5069-OB16K, and 5069-OB16F modules.

5069-OB16, 5069-OB16K, and 5069-OB16F Wiring Diagram

Channel Connections
The diagram shows devices that are
connected to channels 0, 2, 4, and 6. You are
not restricted to using only those channels.
DC OUTPUT
You can connect devices to any channel or
combination of channels as needed.

LA Power 5069-OB16
The Local Actuator (LA+ and LA –)
connections are used to supply field-side
power to the module. Output Channel 0 0

Output Channel 1 1

Output Channel 2 2
• The 5069-OB16, 5069-OB16K, and 5069- Output Channel 3 3
OB16F modules do not draw current
Output Channel 4 4
from the SA Power bus.
Output Channel 5 5
Still, the modules are DC type modules,
and you must install them on a DC SA Output Channel 6 6

Power bus. Output Channel 7 7

• If you install modules in a system that Output Channel 8 8

use AC SA power and DC SA power, you LA (–) Output Channel 9 9

must install them on separate SA Power Output Channel 10 10


buses. Output Channel 11 11
• You use a 5069-FPD field potential Output Channel 12 12
distributor to establish a new SA Power Output Channel 13 13
bus in a system. SA Power buses are Output Channel 14 14
isolated from each other. To keep the
Output Channel 15 15
modules on separate SA Power buses, +
complete these steps. LA+ 16
24V DC
– LA- 17
1. Install the modules that use one type
of SA power, for example DC, to the
right of the adapter or controller, that
is, the first SA Power bus.
2. Install the 5069-FPD field potential
distributor to establish a second SA
Power bus.
3. Install the modules that use the other
type of SA power, for example AC, on
the second SA Power bus.
IMPORTANT: The 5069-OB16K and
5069-OB16K modules are wired the same as
the wiring diagram that is shown for the
5069-OB16 module.

30 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OB16, 5069-OB16K, and 5069-OB16F modules.

5069-OB16, 5069-OB16K, and 5069-OB16F Functional Block Diagram

Module 24V DC
Status
Power
Indicators
Supply MOD 5
Power 0
6
Backplane 9
Communication
Output
B
Output Backplane a
Isolation
Circuitry ASIC Nonvolatile c
Inductive Kickback Memory k
Suppression p
l
TB-16 a
LA+ n
Soft Start 24V DC to 5V DC e
LA- Circuitry Converter

TB-17

Technical Specifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Attribute 5069-OB16, 5069-OB16K 5069-OB16F
(1)
On-state voltage, min 10V DC
(1)
On-state voltage, nom 24V DC
(1)
On-state voltage, max 32V DC
(1)
On-state voltage drop, max < 0.2V DC
(1)
On-state current per channel, min 1 mA
(1)
Off-state voltage, max 5V DC with 1 mA min load
(2)
Off-state leakage current per point, max < 0.5 mA per point
0.5 A resistive per channel @ 10…32V DC
Output current rating
8 A resistive per module @ 10…32V DC, max
Surge current per point 1 A max for 10 ms per point, repeatable every 2 s
Output delay time (backplane to screw)
Off to On ≤ 100 μs, ±10 μs @ 25 °C (77 °F) @ 0.5 A 10 μs, ±1 μs @ 25 °C (77 °F) @ 0.5 A
On to Off ≤100 μs, ±10 μs @ 25 °C (77 °F) @ 0.5 A 10 μs, ±1 μs @ 25 °C (77 °F) @ 0.5 A
Pulse width, min 200 μs @ 0.5 A @ 25 °C (77 °F) 20 μs @ 0.5 A @ 25 °C (77 °F)
±100 ns/°C (55.6 ns/°F) from 0…60 °C (32…140 °F) @ ±10 ns/°C (5.56 ns/°F) from 0…60 °C (32…140 °F) @
Output drift over temperature span 0.5 A 0.5 A
No load detection diagnostics Yes (per channel diagnostics)
Output short circuit/overload/overtemp detection Yes (per channel diagnostics)
Output short circuit/overload protection Yes
Reverse voltage protection Yes
Overvoltage protection, max 36V (fuse protected)
Pilot duty rating 0.5 A pilot duty rating per channel @ 10…32V DC

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 31


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Attribute 5069-OB16, 5069-OB16K 5069-OB16F
• Hold Last State
Output control in fault state per point • On
• Off (default)
• Hold Last State
Output states in program mode per point • On
• Off (default)
• Hold Last State
Output states in fault mode per point • On
• Off (default)
• 1s
• 2s
Duration of fault mode per point • 5s
• 10 s
• Forever (default)
±10 μs accuracy
Scheduled outputs Not supported
1 ns resolution
(1) Local Actuator (LA) Field Power related attributes.
(2) Recommended Loading Resistor - To limit the effects of leakage current through solid-state outputs, you can connect a loading resistor in parallel with your load. For 24V DC operation, use a 5.6 KΩ, 0.5 W resistor for
transistor operation.

General Specifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Attribute 5069-OB16, 5069-OB16K 5069-OB16F
Outputs 16 Channels (1 group of 16), sourcing
Voltage category 12/24V DC source
Voltage and current ratings
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
0.5 A per channel @ 10…32V DC
LA Power
8 A per module @ 10…32V DC
SA Power Passthrough, max(2)
9.95 A @ 10…32V DC
The module does not draw SA Power current.
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 3.25 W (16 channels @ 0.5 A)
Thermal dissipation, max 11.09 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage No isolation between LA power and output ports
No isolation between individual output ports
Module keying Electronic, module keying, software configurable
1 green/red module status indicator
Indicators
16 yellow/red I/O status indicators
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.

32 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Attribute 5069-OB16, 5069-OB16K 5069-OB16F
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
2 - output ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB18-SPRING removable terminal block diameter including insulation
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB18-SCREW removable terminal block diameter including insulation
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open - style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Attribute 5069-OB16, 5069-OB16K, 5069-OB16F
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max. 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 33


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Attribute 5069-OB16, 5069-OB16K, 5069-OB16F
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on output ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on output ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD power port
IEC 61000-4-29

Certifications - 5069-OB16, 5069-OB16K, and 5069-OB16F


Certification(1) 5069-OB16, 5069-OB16K, 5069-OB16F
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

34 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OW4I Digital 4-point Isolated Relay Output Module

This figure shows a wiring diagram for the 5069-OW4I module.

5069-OW4I Wiring Diagram

Channel Connections
The diagram shows a device that is connected to RELAY OUTPUT

channel 0. You are not restricted to using only


this channel.
You can connect devices to any channel or
combination of channels as needed. 5069-OW4I

SA Power Power
Supply 0A 0

• The 5069-OW4I module does not draw current 0B 1


from the SA power bus. 1A 2
Still, the module is a DC-type module, and you 1B 3
must install it on a DC SA Power bus. Load
2A 4
• If you install modules in a system that use AC SA
2B 5
power and DC SA power, you must install them on
separate SA Power buses. 3A 6

3B 7
• You use a 5069-FPD field potential distributor to
8
establish a new SA Power bus in a system. SA
Power buses are isolated from each other. To keep 9

the modules on separate SA Power buses, complete 10

these steps. 11
1. Install the modules that use one type of SA 12
power, for example DC, to the right of the Terminals are unused
13
adapter or controller, that is, the first SA
14
Power bus.
15
2. Install the 5069-FPD field potential distributor
16
to establish a second SA Power bus.
17
3. Install the modules that use the other type of SA
power, for example AC, on the second SA
Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 35


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OW4I module.

5069-OW4I Functional Block Diagram

24V DC
SA
Power
5
0
6
9
Module 24V DC
Status B
Power
Indicators a
Supply MOD
Power c
0A
k
p
Backplane l
Communication a
0B Backplane n
ASIC Nonvolatile e
Memory

Technical Specifications - 5069-OW4I


Attribute 5069-OW4I
2 A resistive per channel @ 5…30V DC
2 A resistive per channel @ 5…264V AC, 50/60 Hz
Relay rating(1) 2 A general use per channel @ 5…250V AC, 50/60 Hz
2 A @ 5…125V AC, ATEX/IECEx
8 A per module, max
Off-state leakage 0 mA (dry contact, no onboard snubbers)
2 A per channel
Output current rating, max
8 A per module
Output delay time, max
Off to On 10 ms
On to Off 10 ms
Switching frequency 1 operation every 3 seconds (0.3 Hz at rated load)
Initial contact resistance, max 30 mΩ
Bounce time, mean 500 μs
• Hold last state
Output control in fault state per point • On
• Off (default)
• Hold last state
Output states in program mode per point • On
• Off (default)
• Hold Last State
Output states in fault mode per point • On
• Off (default)

36 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OW4I


Attribute 5069-OW4I
• 1s
• 2s
Duration of fault mode per point • 5s
• 10 s
• Forever (default)
Delay to fault Supported
Fusing Outputs are not fused.
Minimum load current 1 mA
Expected contact life 300K cycles resistive, 100K cycles inductive
5…240V AC, 50/60 Hz, C300 pilot duty per channel
Pilot duty rating
5…125V DC, R150 pilot duty per channel
(1) Surge Suppression - Connecting surge suppressors across your external inductive load extends the life of the module. For additional details, see the Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley®
publication 1770-4.1.

Relay Contact Ratings - 5069-OW4I

Continuous Amps Amperes Voltamperes


Volts, max NEMA ICS 2-125
per Point, max Make Break Make Break
240V AC 2A 7.5 A 0.75 A 1800VA 180VA C300
(1)
125V DC 0.27 A 0.22 A(2) 28VA R150
(2)
24V DC 2.0 A 1.16 A 28VA -
(1) Calculated based on the Rockwell Automation® component derating guideline: 90% of rated contact current, that is, 0.3 A at 125V DC.
(2) For DC voltage applications, the make/break ampere rating for relay contacts is determined by dividing 28VA by the applied DC voltage. For example, 28VA/48V DC = 0.58 A.

General Specifications - 5069-OW4I


Attribute 5069-OW4I
Outputs 4 - Form A (normally open)
Voltage and current ratings
5…125V DC
Output voltage range
5…264V AC
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
(2)
SA Power Passthrough, max
9.95 A @ 0…32V DC
The module does not draw SA Power current.
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 2.3 W
Thermal dissipation, max 7.85 BTU/hr
Isolation voltage 250V (continuous), Basic Insulation Type
Module keying Electronic keying via programming software
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 37


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OW4I


Attribute 5069-OW4I
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
1 green/red module status indicator
Indicators
4 yellow/red I/O status indicators
1 - relay ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB18-SPRING removable terminal block diameter including insulation
Use minimum 18 AWG, 105 °C (221 °F) rated wire for load connections to relay output modules.
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB18-SCREW removable terminal block diameter including insulation
Use minimum 18 AWG, 105 °C (221 °F) rated wire for load connections to relay output modules.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

38 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OW4I


Attribute 5069-OW4I
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±4 kV @ 5 kHz on relay ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on relay ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 39


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-OW4I
Certification(1) 5069-OW4I
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • II 3 G Ex nA nC IIC T4 Gc
• DEMKO 15 ATEX 1484X
When used at or below 125V DC or 30V DC
IECEx System, compliant with:
• IEC 60079-0; General Requirements
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
IECEx • II 3 G Ex nA nC IIC T4 Gc
• IECEx UL 15.0055X
When used at or below 125V DC or 30V DC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

40 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OW16 Digital 16-point Relay Output Module

This figure shows a wiring diagram for the 5069-OW16 module.

5069-OW16 Wiring Diagram

The 5069-OW16 module requires SA power to function. The module is a DC-type module, so you must install it on an
SA power bus that uses DC-type power.

You can connect AC-type devices, DC-type devices, or, as shown below, a combination of the two types to the module.
Because the module has two commons, each shared across a set of eight output channels, make sure that you do not
connect devices of different power types to the same set of commons. For example, you cannot connect a device that uses
AC-type power to output channel 0 and a device that uses DC-type power to output channel 1.

Channel Connections
The example shows devices connected to channels 0, 2, 4, 6,
8, 10, 12, and 14. You are not restricted to using only those
channels. RELAY OUTPUT

You can connect devices to any channel or combination of


channels as needed.
SA Power
Connections to an external power supply that provides SA 5069-OW16

power are made via the SA Power RTB on one of the


following:
• CompactLogix 5380 controller CR Output Channel 0 0

Output Channel 1 1
• Compact GuardLogix 5380 controller
CR Output Channel 2 2
• CompactLogix 5480 controller
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Output Channel 3 3

• 5069-FPD field potential distributor Output Channel 4 4

IMPORTANT: Remember the following: Output Channel 5 5


L2
• The 5069-OW16 module requires DC SA power. You must Output Channel 6 6
connect DC power to the component, that is, controller, Output Channel 7 7
adapter, or field potential distributor, that provides SA AC-type L1
Power Supply Common 0 8
Power to the module.
• If you install modules in a system that uses AC SA power CR Output Channel 8 9

and DC SA power, you must install them on separate SA Output Channel 9 10

power buses. CR Output Channel 10 11


• You use a 5069-FPD field potential distributor to Output Channel 11 12
establish a new SA Power bus in a system. SA Power
Output Channel 12 13
buses are isolated from each other. To keep the modules
on separate SA Power buses, complete these steps. -24V DC Output Channel 13 14

1. Install the modules that use one type of SA power, for Output Channel 14 15

example DC, to the right of the adapter or controller, Output Channel 15 16


DC-type +24V DC
that is, the first SA Power bus. Common 1
Power Supply 17
2. Install the 5069-FPD field potential distributor to
establish a second SA Power bus.
3. Install the modules that use the other type of SA
power, for example AC, on the second SA Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 41


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OW16 module.

5069-OW16 Functional Block Diagram


24V DC

SA Power
SA
Power
5
Supply 0
6
9
Module 24V DC
Status B
Power
Indicators a
Supply MOD
Power c
Common x
k
p
Backplane l
Communication a
Output Channel x Backplane n
ASIC Nonvolatile e
Memory

Technical Specifications - 5069-OW16


Attribute 5069-OW16
2 A resistive per channel @ 5…30V DC
2 A resistive per channel @ 5…264V AC, 50/60 Hz
Relay ratings
2 A general use per channel @ 5…250V AC, 50/60 Hz
2 A @ 5…125V AC, ATEX/IECEx
Off-state leakage current per point, max 0 mA (dry contact, no onboard snubbers)
Output current per group, max 8A
Output current per module, max 16 A
Output delay time, max
Off to On 10 ms
On to Off 10 ms
Switching frequency 1 operation every 3 seconds (0.3 Hz at rated load)
Initial contact resistance, max 30 mΩ
Bounce time, mean 500 μs
Delay to fault Supported
Fusing Outputs are not fused
Minimum load current 1 mA
Expected contact life 300K cycles resistive, 100K cycles inductive
5…240V AC, 50/60 Hz, C300 pilot duty per channel
Pilot duty rating
5…125V DC, R150 pilot duty per channel
• Hold Last State
Output control in fault state per point • On
• Off (default)
• Hold Last State
Output states in program mode per point • On
• Off (default)

42 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OW16


Attribute 5069-OW16
• Hold Last State
Output states in fault mode per point • On
• Off (default)
• 1
• 2
Duration of fault mode per point • 5
• 10 s
• Forever (default)

Relay Contact Ratings - 5069-OW16


Volts, max Continuous Amps Amperes Voltamperes NEMA ICS 2-125
per Point, max
Make Break Make Break
240V AC 2A 7.5 A 0.75 A 1800VA 180VA C300
(1)
125V DC 0.27 A 0.22 A(2) 28VA R150
(2)
24V DC 2.0 A 1.16 A 28VA -
(1) Calculated based on the Rockwell Automation component derating guideline: 90% of rated contact current, that is, 0.3 A at 125V DC.
(2) For DC voltage applications, the make/break ampere rating for relay contacts is determined by dividing 28VA by the applied DC voltage. For example, 28VA/48V DC = 0.58 A.

General Specifications - 5069-OW16


Attribute 5069-OW16
Outputs 16 (Two groups of 8) - Form A (normally open)
Voltage and current ratings
5…125V DC
Output voltage range
5…264V AC
MOD Power 75 mA @ 18…32V DC
(1) 9.55 A @ 18…32V DC
MOD Power Passthrough, max
SA Power 150 mA @ 18…32V DC
(2)
SA Power Passthrough, max 9.95 A @ 18…32V DC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
The 5069-OW16 module complies with ATEX/IECEx when used at or below 125V AC or 30V DC.
Power dissipation, max 3.0 W
Thermal dissipation, max 10.2 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage Type tested at 1800V AC for 60 s
No isolation between individual channels
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
16 yellow/red I/O status indicators
Slot width 1.5
Dimensions (HxWxD), approx 144.57 x 36 x 105.42 mm (5.69 x 1.42 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 43


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OW16


Attribute 5069-OW16
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
RTB keying None
1 - relay ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
5069-RTB18-SPRING connections in.) max diameter including insulation, single wire connection only.
Use minimum 18 AWG, 105 °C (221 °F) rated wire for load connections to relay output modules.
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
5069-RTB18-SCREW connections in.) max diameter including insulation, single wire connection only.
Use minimum 18 AWG, 105 °C (221 °F) rated wire for load connections to relay output modules.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 240 g (0.53 lb.)
Enclosure type rating None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-OW16


Attribute 5069-OW16
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)

44 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OW16


Attribute 5069-OW16
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on relay ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on relay ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Corrosion resistance classification ISA S71.04 G2

Certifications - 5069-OW16
Certification(1) 5069-OW16
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM • EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • II 3 G Ex nA nC IIC T4 Gc
• DEMKO 15 ATEX 1484X
When used at or below 125V DC or 30V DC
IECEx System, compliant with:
• IEC 60079-0; General Requirements
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
IECEx • II 3 G Ex nA nC IIC T4 Gc
• IECEx UL 15.0055X
When used at or below 125V DC or 30V DC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 45


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OX4I Digital 4-point Isolated Normally-open/Normally-closed Output Module

This figure shows a wiring diagram for the 5069-OX4I module.

5069-OX4I Wiring Diagram

Channel Connections
The diagram shows devices that are connected to RELAY OUTPUT
channels 0 and 1. You are not restricted to using
only those channels.
Power
You can connect devices to any channel or Supply
combination of channels as needed. 5069-OX4I

SA Power Load (0 N.C.) 0

• The 5069-OX4I module does not draw (0 N.O.) 1


current from the SA power bus. (O COMMON) 2
Still, the module is a DC-type module, and you (1 N.C.) 3
must install it on a DC SA Power bus. Power
Supply (1 N.O.) 4
• If you install modules in a system that use AC (1 COMMON) 5
SA power and DC SA power, you must install
(2 N.C.) 6
them on separate SA Power buses.
(2 N.O.) 7
• You use a 5069-FPD field potential distributor Load
to establish a new SA Power bus in a system. SA (2 COMMON) 8

Power buses are isolated from each other. To (3 N.C.) 9

keep the modules on separate SA Power buses, (3 N.O.) 10

complete these steps. (3 COMMON) 11

1. Install the modules that use one type of SA 12

power, for example DC, to the right of the 13


adapter or controller, that is, the first SA Terminals 14
Power bus. are unused 15
2. Install the 5069-FPD field potential
16
distributor to establish a second SA Power
17
bus.
3. Install the modules that use the other type
of SA power, for example AC, on the second
SA Power bus.

46 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OX4I module.

5069-OX4I Functional Block Diagram

24V DC
SA
Power
5
0
6
9
Module 24V DC
Status B
Power
Indicators a
Supply MOD
Power c
k
0 N.C. p
Backplane
l
0 N.O. Communication
a
Backplane n
0 COMMON ASIC Nonvolatile e
Memory

Technical Specifications - 5069-OX4I


Attribute 5069-OX4I
2 A resistive per channel @ 5…30V DC
2 A resistive per channel @ 5…264V AC, 50/60 Hz
Contact current rating(1) 2 A general use per channel @ 5…250V AC, 50/60 Hz
2 A @ 5…125V AC, ATEX/IECEx
8 A per module, max
Off-state leakage 0 mA (dry contact, no onboard snubbers)
2 A per channel
Output current rating
8 A per module, max
Output delay time, max
Off to On 15 ms
On to Off 15 ms
Switching frequency 1 operation every 3 seconds (.3 Hz at rated load)
Initial contact resistance, max 30 mΩ
Bounce time, mean 500 μs
• Hold last state
Output control in fault state per point • On
• Off (default)
• Hold last state
Output states in program mode per point • On
• Off (default)
• Hold Last State
Output states in fault mode per point • On
• Off (default)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 47


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OX4I


Attribute 5069-OX4I
• 1s
• 2s
Duration of fault mode per point • 5s
• 10 s
• Forever (default)
Delay to fault Supported
Fusing Outputs are not fused.
Minimum load current 10 mA
Expected contact life 300K cycles resistive, 100K cycles inductive
5…240V AC, 50/60 Hz, C300 pilot duty per channel
Pilot duty rating
5…125V DC, R150 pilot duty per channel
(1) Surge Suppression - Connecting surge suppressors across your external inductive load extends the life of the module. For additional details, see the Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1.

Relay Contact Ratings - 5069-OX4I


Volts, max Continuous Amps Amperes Voltamperes NEMA ICS 2-125
per Point, max
Make Break Make Break
240V AC 2A 7.5 A 0.75 A 1800VA 180VA C300
(1)
125V DC 0.225 A 0.22 A(2) 28VA R150
(2)
24V DC 2.0 A 1.16 A 28VA -
(1) Calculated based on the Rockwell Automation component derating guideline: 90% of rated contact current, that is, 0.25 A at 125V DC.
(2) For DC voltage applications, the make/break ampere rating for relay contacts is determined by dividing 28VA by the applied DC voltage. For example, 28VA/48V DC = 0.58 A.

General Specifications - 5069-OX4I


Attribute 5069-OX4I
Outputs 4 - Form C (SPDT)
Voltage and current ratings
5…125V DC
Output voltage range
5…264V AC
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
(2)
SA Power Passthrough, max
9.95 A @ 0…32V DC
The module does not draw SA Power current.
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 2.6 W
Thermal dissipation, max 8.88 BTU/hr
Isolation voltage 250V (continuous), Basic Insulation Type
Module keying Electronic keying via programming software
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.

48 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OX4I


Attribute 5069-OX4I
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
1 green/red module status indicator
Indicators
4 yellow/red I/O status indicators
1 - relay ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB18-SPRING removable terminal block diameter including insulation
Use minimum 18 AWG, 105 °C (221 °F) rated wire for load connections to relay output modules.
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB18-SCREW removable terminal block diameter including insulation
Use minimum 18 AWG, 105 °C (221 °F) rated wire for load connections to relay output modules.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-OX4I


Attribute 5069-OX4I
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 49


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OX4I


Attribute 5069-OX4I
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±4 kV @ 5 kHz on relay ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on relay ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

Certifications - 5069-OX4I
Certification(1) 5069-OX4I
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • II 3 G Ex nA nC IIC T4 Gc
• DEMKO 15 ATEX 1484X
When used at or below 125V DC or 30V DC
IECEx System, compliant with:
• IEC 60079-0; General Requirements
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
IECEx • II 3 G Ex nA nC IIC T4 Gc
• IECEx UL 15.0055X
When used at or below 125V DC or 30V DC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

50 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Analog I/O Modules

I/O Type Cat. No. Description Page


5069-IF8 8-channel current/voltage input module 51
Analog input 5069-IY4 4-channel current/voltage/RTD/Thermocouple input module
60
5069-IY4K 4-channel conformal coated current/voltage/RTD/Thermocouple input module
5069-OF4 4-channel current/voltage output module
Analog output 5069-OF4K 4-channel conformal coated current/voltage output module 75
5069-OF8 8-channel current/voltage output module

5069-IF8 Analog 8-channel Current/Voltage Input Module

The following table lists the devices that are supported with the 5069-IF8 module.

Device Mode(s)(2) Supported Wiring Diagram Example


Current page 52
2-wire analog device Yes
Voltage page 53
4-wire analog device(1)
Combination of current and voltage Yes page 54
1-wire analog device
3-wire analog device
N/A - These devices are not supported
2-wire Thermocouple device No —
regardless of the channel mode configuration.
2-wire RTD device
3-wire RTD device
(1) These devices are 2-wire current and voltage devices with 2-wire sensor power connections.
(2) Make sure that the channel configuration in your Logix Designer application project matches the input device type that is connected to the channel. You choose the input type in the Channels category on the Module Properties
dialog box. For example, if a current input device is connected to channel 0 on the module, the module configuration for channel must be Input Type = Current.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 51


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-IF8 module with channels configured for current mode.

5069-IF8 Wiring Diagram - Current Mode

Channel Connections
The diagram shows devices that are connected to channels 0, 2, 5,
and 7. You are not restricted to using only this channel.
You can connect devices to any channel or combination of
channels as needed.
ANALOG INPUT

IMPORTANT
i
• Place additional loop devices, for example, strip chart
recorders, at either A location in the current loop. 2-wire – A
• This example shows separate power supplies for each device. Differential 5069-IF8

Current + Power A
We recommend that you use separate power supplies to help supply
+ –
improve the noise immunity. Input 0 + 0

However, if you use separate power supplies, you must verify Shield Ground Input 0 – 1

that the common mode voltage between any two power Input 1 + 2

supplies does not exceed 10V DC. +


Input 1 – 3

• This module has only two shield terminals. Compact 5000 I/O 4-wire +
Power Input 2 + 4
module RTBs only support one wire per terminal. Differential
supply Input 2 –
Current – 5
If you connect more than two devices to the module, you can Input 3 +
– 6
ground two devices at the shield terminals. You must ground Shield Ground Input 3 – 7
the remaining devices somewhere else, such as, to the DIN rail
via a terminal strip. i Input 4 + 8

Input 4 – 9
2-wire – A
SA Power Differential Input 5 + 10

Connections to an external power supply that provides SA power Current + Power A Input 5 – 11

are made via the SA Power RTB on one of the following: supply – Input 6 + 12
+
• CompactLogix 5380 controller Input 6 – 13

• Compact GuardLogix 5380 controller Input 7 + 14

• CompactLogix 5480 controller Input 7 – 15

• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Shield 16

+ Shield 17
• 5069-FPD field potential distributor
4-wire +
IMPORTANT: Remember the following: Power Differential
• The 5069-IF8 module uses DC SA power. You must connect DC supply Current –
power to the component, that is, controller, adapter, or field –
potential distributor, that provides SA Power to the modules.
• If you install modules in a system that use AC SA power and DC
SA power, you must install them on separate SA power buses.
• You use a 5069-FPD field potential distributor to establish a
new SA Power bus in a system. SA Power buses are isolated
from each other. To keep the modules on separate SA Power
buses, complete these steps.
1. Install the modules that use one type of SA power, for
example DC, to the right of the adapter or controller, that
is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to establish
a second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.

52 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-IF8 module with channels configured for voltage mode.

5069-IF8 Wiring Diagram - Voltage Mode

ANALOG INPUT

+
4-wire
24V DC Differential 5069-IF8
Channel Connections Voltage
The diagram shows devices that are connected to channels 0, 2, 5, –
and 7. You are not restricted to using only this channel. Input 0 + 0

Shield Ground Input 0 – 1


You can connect devices to any channel or combination of
channels as needed. Input 1 + 2
+ Input 1 – 3
4-wire +
Input 2 + 4
24V DC Differential
IMPORTANT Voltage – Input 2 – 5

• This example shows separate power supplies for each device. – Input 3 + 6

We recommend that you use separate power supplies to help Shield Ground Input 3 – 7

improve the noise immunity. Input 4 + 8

However, if you use separate power supplies, you must verify + Input 4 – 9

that the common mode voltage between any two power 4-wire Input 5 + 10
supplies does not exceed 10V DC. 24V DC Differential
Voltage Input 5 – 11

• This module has only two shield terminals. Compact 5000 I/O – Input 6 + 12
module RTBs only support one wire per terminal. Input 6 – 13
If you connect more than two devices to the module, you can Input 7 + 14
ground two devices at the shield terminals. You must ground
Input 7 – 15
the remaining devices somewhere else, such as, to the DIN rail
via a terminal strip. Shield 16

+ Shield 17

4-wire +
24V DC Differential
Voltage –

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 53


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-IF8 module with different device types connected to different channels.
The device type and mode configuration for each channel must match.

5069-IF8 Wiring Diagram - Combination of Device Types Connected to the Module

Channel Connections ANALOG INPUT


The diagram shows devices that are connected to channels 0, 2, 5,
and 7. You are not restricted to using only this channel. i
You can connect devices to any channel or combination of channels 2-wire – A
as needed. Differential 5069-IF8

Current + Power A
+ supply –
IMPORTANT Input 0 + 0

• Place additional loop devices, for example, strip chart recorders, Shield Ground Input 0 – 1

at either A location in the current loop. Input 1 + 2


+
• This example shows separate power supplies for each device. Input 1 – 3

We recommend that you use separate power supplies to help 4-wire + Input 2 +
Power 4
improve the noise immunity. Differential
supply Input 2 –
Current – 5
However, if you use separate power supplies, you must verify Input 3 +
– 6
that the common mode voltage between any two power Shield Ground Input 3 – 7
supplies does not exceed 10V DC.
Input 4 + 8
• This module has only two shield terminals. Compact 5000 I/O
Input 4 – 9
module RTBs only support one wire per terminal. 2-wire –
Input 5 + 10
• This example shows separate power supplies for each device. Differential
Current + Power Input 5 – 11
We recommend that you use separate power supplies to help
supply – Input 6 + 12
improve the noise immunity. +
Input 6 – 13
• However, if you use separate power supplies, you must verify
that the common mode voltage between any two power Input 7 + 14

supplies does not exceed 10V DC.This module has only two Input 7 – 15

shield terminals. Compact 5000 I/O module RTBs only support Shield 16

one wire per terminal. + Shield 17

If you connect more than two devices to the module, you can 4-wire +
ground two devices at the shield terminals. You must ground 24V DC Differential
the remaining devices somewhere else, such as, to the DIN rail Voltage –
via a terminal strip. –

SA Power
Connections to an external power supply that provides SA power are made via the SA Power RTB on one of the following:
• CompactLogix 5380 controller
• Compact GuardLogix 5380 controller
• CompactLogix 5480 controller
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter
• 5069-FPD field potential distributor
IMPORTANT: Remember the following:
• The 5069-IF8 module uses DC SA power. You must connect DC power to the component, that is, controller, adapter, or field potential distributor, that provides SA
Power to the modules.
• If you install modules in a system that use AC SA power and DC SA power, you must install them on separate SA power buses.
• You use a 5069-FPD field potential distributor to establish a new SA Power bus in a system. SA Power buses are isolated from each other. To keep the modules on
separate SA Power buses, complete these steps.
1. Install the modules that use one type of SA power, for example DC, to the right of the adapter or controller, that is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to establish a second SA Power bus.
3. Install the modules that use the other type of SA power, for example AC, on the second SA Power bus.

54 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-IF8 module.

5069-IF8 Functional Block Diagram

24V DC
SA Power 5
0
Field DC-DC 6
Converter 9
Vref B
A/D Converter, Module 24V DC
In x + Status a
Voltage/ Voltage, and Power
Indicators MOD c
Current In x – Current, Supply
Source 4-channel Power k
Shield Signal p
Conditioning Backplane l
A/D Converter, Communication a
Voltage, and Backplane n
Isolator e
Current, ASIC Nonvolatile
4-channel
Memory

Technical Specifications - 5069-IF8


Attribute 5069-IF8
Inputs 8 differential
±10V
Input range, voltage 0…10V
0…5V
0…20 mA
Input range, current
4…20 mA
Voltage: >1 MΩ
Input impedance
Current: 90 Ω typical, 70…110 Ω range
Common mode voltage (channel to channel) ±10V
Sigma-Delta,
Module conversion method
Two 24-bit multiplexed ADC
±10.5V: <320 μV/count
(15 bits plus sign bipolar)
Resolution, voltage(1) 0…10.5V: <160 μV/count
(16 bits at 10 Hz notch filter) (16 bits unipolar)
0…5.25V: <80 μ/V count
(16 bits unipolar)
0…21 mA: <0.32 μA/count
Resolution, current(1) (16 bits)
(16 bits at 10 Hz notch filter) 3.6…21 mA: <0.27 μA/count
(16 bits)
Voltage 0.10% full scale
Calibrated accuracy at 25 °C
Current 0.10% full scale
Voltage 0.20% full scale
Accuracy drift with temperature
Current 0.30% full scale
Input Total Unadjusted Error (TUE)(2) Voltage 0.30% full scale
(Over full temperature range) Current 0.40% full scale

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 55


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IF8


Attribute 5069-IF8
Scan Time
Per channel 625 μs
Per group (channel group 0…3 or channel group 4…7) 2.5 ms
Notch filter at minimum RPI
(0.2 ms, 1 channel enabled) 62.5 kHz
Minimum notch filter frequency at RPI of 2.5 ms 10 kHz
Step response time to 63% of value
7.5 ms
(Notch filter 10 kHz)
Input notch filter (Hz) selections 5, 10 (50/60 Default), 15, 20, 50, 60, 100, 200, 500, 1000, 2500, 5000, 10000, 15625, 25000, 31250, 62500
Input anti-aliasing filter cutoff frequency, nom 500 Hz
First order lag,
Input digital filter
0 ms (Default)…32,767 ms (32.767 s)
HART handheld compliance Add an external 250 Ω resistor into the current loop for HART transmitter compliance.
Voltage and Current modes:
Overvoltage protection, max
± 30V DC
Overcurrent protection, max Current mode: ±30 mA
Full scale, overrange flag,
Data value during overload condition
Data uncertain / data bad
Voltage: + full scale, < 2 s
Open circuit detection time
Current: 4…20 mA range, <2 s
Onboard data alarming Yes
Scaling to engineering units Yes
Real-time channel sampling Yes
Data format IEEE 32-bit floating point
(1) Notch filter dependent.
(2) Includes offset, gain, non-linearity, and repeatability error terms.

General Specifications - 5069-IF8


Attribute 5069-IF8
Voltage and current ratings
MOD Power 75 mA @ 18…32V DC
MOD Power Passthrough, max(1) 9.55 A @ 18…32V DC
SA Power 100 mA @ 18…32V DC
SA Power Passthrough, max(2) 9.95 A @ 18…32V DC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw.
Voltage mode: 2.1 W
Power dissipation, max
Current mode: 2.4 W
Voltage mode: 7.2 BTU/hr
Thermal dissipation, max
Current mode: 8.2 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage 50V Functional Isolation between SA power and input ports
No isolation between individual Input ports
Factory calibrated
Calibration methods
User-performed (optional)

56 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IF8


Attribute 5069-IF8
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
8 yellow/red I/O status indicator
Slot width 1
Common mode noise rejection ratio 130 dB @ 50/60 Hz
Normal mode noise rejection ratio 65 dB @ 50/60 Hz, notch filter dependent
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
2 - shielded input ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB18-SPRING removable terminal block diameter including insulation
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB18-SCREW removable terminal block diameter including insulation
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temperature code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 57


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-IF8


Attribute 5069-IF8
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 880% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on shielded input ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±2 kV line-earth (CM) on shielded input ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

58 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-IF8
Certification(1) 5069-IF8
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 59


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-IY4 and 5069-IY4K Analog Input Modules

The following table lists the analog devices that are supported with the 5069-IY4 and 5069-IY4K modules.

Device Mode(s)(2) Supported Wiring Diagram Example


Current page 61
2-wire analog device Yes
Voltage page 62
4-wire analog device(1)
(3)
Any combination of current, voltage, RTD, Thermocouple Yes page 66 and page 67

2-wire RTD device RTD Yes page 63 and page 64


3-wire RTD device (3)
Any combination of current, voltage, RTD, Thermocouple Yes page 66 and page 67
(4)
Thermocouple Yes page 65
2-wire Thermocouple device (3)
Any combination of current, voltage, RTD, Thermocouple Yes page 66 and page 67
1-wire analog device N/A - These devices are not supported regardless of the
No —
3-wire analog device channel mode configuration.
(1) These devices are 2-wire current and voltage devices with 2-wire sensor power connections.
(2) Make sure that the channel configuration in your Logix Designer application project matches the input device type that is connected to the channel. You choose the input type in the Channels category on the Module Properties
dialog box. For example, if a current input device is connected to channel 0 on the module, the module configuration for channel must be Input Type = Current.
(3) You must use the 5069-RTB14CJC RTB if at least one thermocouple is connected to the module. If there are no thermocouples connected to the module, we recommend that you use the
5069-RTB18 RTB.
(4) You must use the 5069-RTB14CJC RTB.

60 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for 5069-a IY4 module with channels configured for current mode.

5069-IY4 and 5069-IY4K Wiring Diagram - Current Mode

Channel Connections
The diagram shows devices that are connected to channels 0, 1, 2,
and 3. You are not restricted to using only this channel.
ANALOG INPUT
You can connect devices to any channel or combination of
channels as needed. i

IMPORTANT 2-wire – A
Differential 5069-IY4
• Place additional loop devices, for example, strip chart Power A
Current +
recorders, at either A location in the current loop. supply
+ – 0
• This example shows separate power supplies for each device.
We recommend that you use separate power supplies to help Shield Ground 1

improve the noise immunity. Input 0 + 2

However, if you use separate power supplies, you must verify + Input 0 – 3

that the common mode voltage between any two power RTD – 4
4-wire +
supplies does not exceed 10V DC. Power Input 1 + 5
Differential
• This module has only two shield terminals. Compact 5000 I/O supply Input 1 – 6
Current –
module RTBs only support one wire per terminal. – RTD – 7

If you connect more than two devices to the module, you can Shield Ground Input 2 + 8

ground two devices at the shield terminals. You must ground i Input 2 – 9

the remaining devices somewhere else, such as, to the DIN 2-wire – RTD – 10

rail via a terminal strip. A


Differential 11

Current + Power A 12
SA Power supply Input 3 +
+ – 13
Connections to an external power supply that provides SA power Input 3 – 14
are made via the SA Power RTB on one of the following: RTD – 15

• CompactLogix 5380 controller Shield 16

• Compact GuardLogix 5380 controller Shield 17


+
• CompactLogix 5480 controller
4-wire +
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Power Differential
• 5069-FPD field potential distributor supply Current –
IMPORTANT: Remember the following: –
• The 5069-IF8 module uses DC SA power. You must connect DC
power to the component, that is, controller, adapter, or field
potential distributor, that provides SA Power to the modules.
• If you install modules in a system that use AC SA power and DC
SA power, you must install them on separate SA power buses.
• You use a 5069-FPD field potential distributor to establish a
new SA Power bus in a system. SA Power buses are isolated
from each other. To keep the modules on separate SA Power
buses, complete these steps.
1. Install the modules that use one type of SA power, for
example DC, to the right of the adapter or controller, that
is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to establish
a second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 61


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for a 5069-IY4 module with channels configured for voltage mode.

5069-IY4 and 5069-IY4K Wiring Diagram - Voltage Mode

ANALOG INPUT

Channel Connections +
4-wire +
The diagram shows devices that are connected to channels 0, 1, 2, Differential
24V DC 5069-IY4
and 3. You are not restricted to using only this channel. Voltage –
You can connect devices to any channel or combination of –
0
channels as needed.
Shield Ground 1

IMPORTANT Input 0 + 2

• This example shows separate power supplies for each device. Input 0 – 3

+
We recommend that you use separate power supplies to help RTD – 4
4-wire +
improve the noise immunity. Input 1 + 5
24V DC Differential
However, if you use separate power supplies, you must verify Voltage – Input 1 – 6

that the common mode voltage between any two power – RTD – 7

supplies does not exceed 10V DC. Shield Ground Input 2 + 8

• This module has only two shield terminals. Compact 5000 I/O Input 2 – 9
+
module RTBs only support one wire per terminal. RTD – 10
4-wire +
If you connect more than two devices to the module, you can 24V DC Differential 11

ground two devices at the shield terminals. You must ground Voltage – 12

the remaining devices somewhere else, such as, to the DIN – Input 3 + 13
rail via a terminal strip.
Input 3 – 14

RTD – 15

Shield 16

Shield 17
+
4-wire +
24V DC Differential
Voltage –

62 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for a 5069-IY4 module with channels configured for RTD mode.

5069-IY4 and 5069-IY4K Wiring Diagram - 3-wire RTD

ANALOG INPUT

Channel Connections
The diagram shows devices that are connected to
5069-IY4
channels 0, 2, and 3. You are not restricted to using only
this channel.
You can connect devices to any channel or combination 0

of channels as needed. 1

Input 0 + 2
3-wire RTD
Input 0 – 3
IMPORTANT - This module has only two shield RTD – 4
terminals. Compact 5000 I/O module RTBs only support
Input 1 + 5
one wire per terminal. Shield Ground Input 1 – 6
If you connect more than two devices to the module,
RTD – 7
you can ground two devices at the shield terminals. You
Input 2 + 8
must ground the remaining devices somewhere else, 3-wire RTD Input 2 – 9
such as, to the DIN rail via a terminal strip.
RTD – 10

11

12

Input 3 + 13
3-wire RTD
Input 3 – 14

RTD – 15

Shield 16

Shield 17

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 63


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for a 5069-IY4 module with channels configured for RTD mode.

5069-IY4 and 5069-IY4K Wiring Diagram - 2-wire RTD

Channel Connections
ANALOG INPUT
The diagram shows a device that is connected to
channels 0, 2, and 3. You are not restricted to using
only these channels.
You can connect devices to any channel or 5069-IY4
combination of channels as needed.
0

1
IMPORTANT 2-wire RTD Using Input 0 + 2

• When you use a 2-wire RTD in 3-wire mode, as 3-wire Mode Input 0 – 3

shown on the RTDs that are connected to channel RTD – 4


3, you must jumper terminals Input x- and RTD x Input 1 +
Shield Ground 5
together. Input 1 – 6

• This module has only two shield terminals. RTD – 7


Compact 5000 I/O module RTBs only support one 2-wire RTD Using Input 2 + 8
wire per terminal. 3-wire Mode Input 2 – 9
If you connect more than two devices to the
RTD – 10
module, you can ground two devices at the shield
11
terminals. You must ground the remaining devices 12
somewhere else, such as, to the DIN rail via a
terminal strip. 2-wire RTD Using Input 3 + 13

2-wire Mode Input 3 – 14

RTD – 15

Shield 16

Shield 17

64 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for a 5069-IY4 module with channels configured for thermocouple mode.

5069-IY4 and 5069-IY4K Wiring Diagram - Thermocouple Input

ANALOG INPUT

5069-IY4
Channel Connections
The diagram shows a device that is connected to
channel 0 and channel 2. You are not restricted to
using only these channels. Thermocouple
You can connect devices to any channel or Input 0 + 2

combination of channels as needed. Input 0 – 3

RTD – 4

IMPORTANT - When you use the 5069-IY4 and Input 1 + 5

5069-IY4K analog input modules in Input 1 – 6

Thermocouple mode, you must use one of these RTD – 7

CJC type RTBs: + Input 2 + 8


mV Source Input 2 –
• 5069-RTB14CJC-SPRING (shown) – 9

• 5069-RTB14CJC-SCREW RTD – 10

Input 3 + 13

Input 3 – 14

RTD – 15

Shield 16

Shield 17

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 65


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-IY4 module with different device types connected to different channels.

5069-IY4 and 5069-IY4K Wiring Diagram - Current, Voltage and RTD Device Types Connected to the Module
Channel Connections
The diagram shows an analog current device connected to channel
0, an analog voltage device connected to channel 1, and an RTD
connected to channel 2. You are not restricted to using those
devices with those channels.
You can connect devices to any channel or combination of
channels as needed. ANALOG INPUT

IMPORTANT:
• In this example, the module can use a 5069-RTB18 RTB because i
no thermocouple devices are connected to the module.
2-wire – A 5069-IY4
• When an analog current device is connected to the module, Differential
place additional loop devices, for example, strip chart recorders, Current + Power A
at either A location in the current loop. supply 0
• This example shows separate power supplies for each the + –
1
current and voltage devices. We recommend that you use
separate power supplies to help improve the noise immunity. Shield Ground Input 0 + 2

However, if you use separate power supplies, you must verify Input 0 – 3

that the common mode voltage between any two power + RTD – 4
supplies does not exceed 10V DC. 4-wire +
Input 1 + 5
• This module has only two shield terminals. Compact 5000 I/O 24V DC Differential
Voltage – Input 1 – 6
module RTBs only support one wire per terminal.
– RTD – 7
If you connect more than two devices to the module, you can
ground two devices at the shield terminals. You must ground Input 2 + 8

the remaining devices somewhere else, such as, to the DIN rail Input 2 – 9

via a terminal strip. RTD – 10


3-wire RTD
SA Power 11

Connections to an external power supply that provides SA power are 12

made via the SA Power RTB on one of the following: Input 3 + 13

• CompactLogix 5380 controller Input 3 – 14

• CompactLogix 5480 controller RTD – 15

• Compact GuardLogix 5380 controller Shield 16

• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Shield 17

• 5069-FPD field potential distributor


IMPORTANT: Remember the following:
• The 5069-IY4 and 5069-IY4K modules use DC SA power. You must
connect DC power to the component, that is, controller, adapter,
or field potential distributor, that provides SA Power to the
modules.
• If you install modules in a system that use AC SA power and DC SA
power, you must install them on separate SA power buses.
• You use a 5069-FPD field potential distributor to establish a new
SA Power bus in a system. SA Power buses are isolated from each
other. To keep the modules on separate SA Power buses,
complete these steps.
1. Install the modules that use one type of SA power, for
example DC, to the right of the adapter or controller, that is,
the first SA Power bus.
2. Install the 5069-FPD field potential distributor to establish a
second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.

66 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for 5069-a IY4 module with channels configured for current, voltage, RTD, and
thermocouple modes.

5069-IY4 and 5069-IY4K Wiring Diagram - Current, Voltage, RTD, and Thermocouple Modes
Channel Connections
IMPORTANT: In this example, the module uses a 5069-RTB14CJC
The diagram shows specific devices connected to channels 0, 1, RTB because a thermocouple is connected to the module.
2, and 3, respectively. You are not restricted to using those
devices with those channels.
You can connect devices to any channel or combination of
channels as needed.

IMPORTANT: ANALOG INPUT

• When an analog current device is connected to the module,


place additional loop devices, for example, strip chart
recorders, at either A location in the current loop. i
• This example shows separate power supplies for each the
2-wire – A 5069-IY4
current and voltage devices. We recommend that you use
Differential
separate power supplies to help improve the noise Current + Power
immunity. A
supply
However, if you use separate power supplies, you must + –
verify that the common mode voltage between any two Shield Ground
power supplies does not exceed 10V DC. Input 0 + 2

• This module has only two shield terminals. Compact 5000 +


Input 0 – 3
I/O module RTBs only support one wire per terminal. +
Differential RTD – 4
If you connect more than two devices to the module, you 24V DC Voltage
can ground two devices at the shield terminals. You must – Input 1 + 5

ground the remaining devices somewhere else, such as, to – Input 1 – 6

the DIN rail via a terminal strip. RTD – 7

SA Power 3-wire RTD Input 2 + 8

Connections to an external power supply that provides SA Input 2 – 9

power are made via the SA Power RTB on one of the following: RTD – 10
• CompactLogix 5380 controller
• CompactLogix 5480 controller
• Compact GuardLogix 5380 controller
Input 3 + 13
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter
• 5069-FPD field potential distributor Input 3 – 14

RTD – 15
IMPORTANT: Remember the following:
• The 5069-IY4 and 5069-IY4K modules use DC SA power. You Shield 16

must connect DC power to the component, that is, Thermocouple


Shield 17
controller, adapter, or field potential distributor, that
provides SA Power to the modules.
• If you install modules in a system that use AC SA power and
DC SA power, you must install them on separate SA power
buses.
• You use a 5069-FPD field potential distributor to establish a
new SA Power bus in a system. SA Power buses are isolated
from each other. To keep the modules on separate SA Power
buses, complete these steps.
1. Install the modules that use one type of SA power, for
example DC, to the right of the adapter or controller,
that is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to
establish a second SA Power bus.
3. Install the modules that use the other type of SA power,
for example AC, on the second SA Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 67


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-IY4 and 5069-IY4K modules.

5069-IY4 and 5069-IY4K Functional Block Diagram


24V DC
SA Power 5
0
Field DC-DC
6
Converter
9
In x +
Voltage/ Vref
Current/mV/ In x – Module B
Status 24V DC
TC Source Shield Power a
Indicators
Supply MOD c
A/D Power
Converter, k
Signal
In x + Conditioning Voltage, Backplane p
RTD, Current, Communication l
2 or In x –
milli-volt/TC, a
3-wire RTD – Backplane
RTD, 4- Isolator n
Shield channel ASIC Nonvolatile e
Memory

CJC CJC x – A/D Converters,


Thermistors, CJC x – Signal CJC Thermistor Isolator
Top/Bottom Conditioning (Top and
Bottom)

Technical Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Inputs 4 differential
±10V
Input range, voltage 0…10V
0…5V
0…20 mA
Input range, current
4…20 mA
1…500 Ω
2…1000 Ω
Input range, resistive
4…2000 Ω
8…4000 Ω
100, 200, 500, 1000 Ω platinum, alpha=385
100, 200, 500, 1000 Ω platinum, alpha=3916
Input type, RTD 120 Ω nickel, alpha=672
100, 120, 200, 500 Ω nickel, alpha=618
10 Ω copper 427
Input range, thermocouple / millivolt ± 100 mV
Input type, thermocouple B, C, D, E, J, K, L (TXK/XK), N, R, S, T
Voltage: >1 MΩ
Current: 90 Ω typical, 70…110 Ω range
Input impedance
RTD: >1 MΩ
Thermocouple/millivolt: >1 MΩ
Common mode voltage (channel to channel) ±10V

68 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Sigma-Delta,
Module conversion method
One 24-bit multiplexed ADC
±10.5V: <320 μV/count
(15 bits plus sign bipolar)
Resolution, voltage(1) 0…10.5V: <160 μV/count
(16 bits at 10 Hz notch filter) (16 bits unipolar)
0…5.25V: <80 μ/V count
(16 bits unipolar)
0…21 mA: <0.32 μA/count
Resolution, current(1) (16 bits)
(16 bits at 10 Hz notch filter) 3.6…21 mA: <0.27 μA/count
(16 bits)
< 7.9 mΩ/cnt in 1…500 Ω mode
Resolution, RTD(1)
< 15.8 mΩ/cnt in 2…1000 Ω mode
(16 bits at 10 Hz notch filter)
< 31.7 mΩ/cnt in 4…2000 Ω mode
3 Wire mode
< 63.4 mΩ/cnt in 8…4000 Ω mode
Resolution, thermocouple / millivolt(1)
< 3.1 μV/cnt in ±100 mV mode
(16 bits at 10 Hz notch filter)
600 μA, 3 wire mode
RTD excitation current
100 μA, 2 wire mode
Wire impedance (3-wire RTD mode only) 25 Ω maximum for specified accuracy
RTD sensor types/temperature range:
(Each sensor type in a cell supports all temperature ranges in the corresponding column to the right.)
-200…+870 °C
-328…+1598 °F
100, 200, 500, 1000 Ohm PT 385
73…1143 °K
132…2058 °R
-200…+630 °C
-328…+1166 °F
100, 200, 500, 1000 Ohm PT 3916
73…903 °K
132…1626 °R
-200…+260 °C
-328…+500 °F
10 Ohm CU 247
73…533 °K
132…960 °R
-80…+320 °C
-112…+608 °F
120 Ohm NI 672
193…593 °K
348…1068 °R
-60…+250 °C
-76…+482 °F
100, 120, 200, 500 Ohm NI 618
213…523 °K
384…942 °R

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 69


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Thermocouple type/temperature range
21…1820 °C
68…3308 °F
Thermocouple Type B
293…2093 °K
528…3768 °R
0…2320 °C
32…4208 °F
Thermocouple Type C
273…2593 °K
492…4668 °R
0…2320 °C
32…4208 °F
Thermocouple Type D
273…2593 °K
492…4668 °R
-270…+1000 °C
-454…+1832 °F
Thermocouple Type E
3…1273 °K
6…2292 °R
-210…+1200 °C
-346…+2192 °F
Thermocouple Type J
63…1473 °K
114…2652 °R
-270…+1372 °C
-454…+2502 °F
Thermocouple Type K
3…1645 °K
6…2961 °R
-270…+1300 °C
-454…+2372 °F
Thermocouple Type N
3…1573 °K
6…2832 °R
-50…+1768 °C
-58…+3215 °F
Thermocouple Type R
223…2041 °K
402…3674 °R
-50…+1768 °C
-58…+3215 °F
Thermocouple Type S
223…2041 °K
402…3674 °R
-270…+400 °C
-454…+752 °F
Thermocouple Type T
3…673 °K
6…1212 °R
-200…+800 °C
-328…+1472 °F
Thermocouple Type TXK/XK (L)
73…1073 °K
132…1932 °R
Thermocouple linearization ITS-90

70 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Two CJC sensors
2 thermistors embedded in 5069-RTB14CJC-(SCREW or SPRING) RTB
CJC inputs -or-
(for thermocouple mode use only) 2 thermistors wired to 5069-RTB18-(SCREW or SPRING) RTB
Thermistor type:
Measurement Specialties, Inc. 10K3A1A
Local CJC sensor accuracy ± 0.3 °C
Remote CJC sensor accuracy
± 0.3 °C
(Based on specified thermistor)
Voltage 0.100% full scale
Current 0.100% full scale
Calibrated accuracy at 25 °C
RTD 0.100% full scale
Thermocouple/millivolt 0.100% full scale
Voltage 0.200% full scale
Current 0.300% full scale
Accuracy drift with temperature
RTD 0.200% full scale
Thermocouple/millivolt 0.200% full scale
Voltage 0.300% Full Scale
Input Total Unadjusted Error (TUE)(2) Current 0.400% Full Scale
(Over full temperature range) RTD 0.300% Full Scale
Thermocouple/millivolt 0.300% Full Scale

Scan time
• Per channel 625 μs
• Per group (channel group 0…3) 2.5 ms
Notch filter at minimum RPI
62.5 kHz
(0.2 ms, 1 channel enabled)
Minimum notch filter frequency at RPI of 2.5 ms 10 kHz
Step response time to 63% of value
7.5 ms
(Notch filter 10 kHz)
Input notch filter (Hz) selections 5, 10 (50/60 default), 15, 20, 50, 60, 100, 200, 500, 1000, 2500, 5000, 10000, 15625, 25000, 31250, 62500
Input anti-aliasing filter cutoff frequency, typical 500 Hz
First Order Lag,
Input digital filter
0 ms (Default)…32,767 ms (32.767 s)
HART handheld compliance: Add an external 250 Ω resistor into the current loop for HART transmitter compliance.
Voltage, current, RTD, and thermocouple/mV modes:
Overvoltage protection, max
± 30V DC
Overcurrent protection, max Current mode: ± 30 mA
Full scale, overrange flag,
Data value during overload condition
Data uncertain / data bad
Voltage: + full scale, < 2 s
Current: 4…20 mA range, < 2 s
Open circuit detection time, nom
RTD: < 2 s
Thermocouple / millivolt: + full scale, < 10 s
Onboard data alarming Yes

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 71


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Scaling to engineering units Yes
Real-time channel sampling Yes
Data format IEEE 32-bit floating point
(1) Notch filter dependent.
(2) Includes offset, gain, non-linearity, and repeatability error terms.

General Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Voltage and current ratings
MOD Power 75 mA @ 18…32V DC
MOD Power Passthrough, max(1) 9.55 A @ 18…32V DC
SA Power 100 mA @ 18…32V DC
SA Power Passthrough, max(2) 9.95 A @ 18…32V DC
Do n ot exceed 10 A MOD or SA Power (Passthrough) current draw
Voltage mode: 1.8 W
Current mode: 2.1 W
Power dissipation, max
RTD mode: 2.1 W
Thermocouple / millivolt mode: 1.8 W
Voltage mode: 6.1 BTU/hr
Current mode: 7.2 BTU/hr
Thermal dissipation, max
RTD mode: 7.2 BTU/hr
Thermocouple/millivolt: 6.1 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage 50V Functional Isolation between SA Power and input ports
No isolation between individual input ports
Factory calibrated
Calibration methods
User-performed (optional)
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators 4 yellow/red I/O status indicators
2 yellow/red CJC status indicators
Slot width 1
Common mode noise rejection ratio 130 dB @ 50/60 Hz
Normal mode noise rejection ratio 65 dB @ 50/60 Hz, notch filter dependent
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SCREW
• 5069-RTB18-SPRING
RTB • 5069-RTB14CJC-SCREW (Thermocouple mode)
• 5069-RTB14CJC-SPRING (Thermocouple mode)
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.

72 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
RTB torque (5069-RTB18-SCREW, 0.4 N•m (3.5 lb•in)
5069-RTB14CJC-SCREW)
RTB keying None
2 - shielded input ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
5069-RTB18-SPRING and 5069-RTB14CJC-SPRING 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
connections in.) max diameter including insulation, single wire connection only.
5069-RTB18-SCREW and 5069-RTB14CJC-SCREW 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
connections in.) max diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Enclosure type None (open-style)
Weight, approx 175 g (0.39 lb)
North American temperature code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 73


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-IY4 and 5069-IY4K


Attribute 5069-IY4, 5069-IY4K
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on shielded input ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±2 kV line-earth (CM) on shielded input ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

Certifications - 5069-IY4 and 5069-IY4K


Certification(1) 5069-IY4, 5069-IY4K
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

74 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OF4, 5069-OF4K, and 5069-OF8 Analog Current/Voltage Output Modules

This figure shows a wiring diagram for the 5069-OF4 and 5069-OF4K modules when used in current mode.

5069-OF4 and 5069-OF4K Wiring Diagram - Current Mode

Channel Connections
The diagram shows a device that is connected to channels 0, 2,
and 3. You are not restricted to using only these channels.
You can connect devices to any channel or combination of
channels as needed. i
Differential +
IMPORTANT: A
ANALOG OUTPUT
Current
• Place more loop devices, for example, strip chart recorders, at Receiver or
– A
either A location in the current loop. Input
• This module has only two shield terminals. Compact 5000 I/O 5069-OF4
module RTBs only support one wire per terminal. Shield Ground
If you connect more than two devices to the module, you can
ground two devices at the shield terminals. You must ground Output 0 + 0

the remaining devices somewhere else, such as, to the DIN rail Output 0 – 1

via a terminal strip i Output 1 + 2

Differential + Output 1 – 3
SA Power
Current A Output 2 + 4

Connections to an external power supply that provides SA power Receiver or Output 2 –


are made via the SA Power RTB on one of the following: – A 5

Input Output 3 + 6

• CompactLogix 5380 controller Output 3 – 7

• Compact GuardLogix 5380 controller 8

• CompactLogix 5480 controller i 9

• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Differential + 10


Current A
• 5069-FPD field potential distributor 11
Receiver or A
IMPORTANT: Remember the following: Input – 12

• The 5069-OF4 module uses DC SA power. You must connect DC 13

power to the component, that is, controller, adapter, or field 14

potential distributor, that provides SA Power to the modules. 15

• If you install modules in a system that use AC SA power and DC Shield 16

SA power, you must install them on separate SA power buses. Shield 17

• You use a 5069-FPD field potential distributor to establish a


new SA Power bus in a system. SA Power buses are isolated
from each other. To keep the modules on separate SA Power
buses, complete these steps.
1. Install the modules that use one type of SA power, for
example DC, to the right of the adapter or controller, that
is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to establish
a second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 75


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-OF8 module when used in current mode.

5069-OF8 Wiring Diagram - Current Mode

ANALOG OUTPUT

5069-OF8
i
Channel Connections Differential +
The diagram shows devices that are connected to channels 0, 4, Current A Output 0 + 0

and 7. You are not restricted to using only those channels. Receiver or A Output 0 – 1

Input –
You can connect devices to any channel or combination of Output 1 + 2

channels as needed. Output 1 – 3

Shield Ground Output 2 + 4

Output 2 – 5

IMPORTANT: i Output 3 + 6

• Place more loop devices, for example, strip chart recorders, at Differential + Output 3 – 7

either A location in the current loop. Current A Output 4 + 8

Receiver or Output 4 –
• This module has only two shield terminals. Compact 5000 I/O – A 9

Input Output 5 +
module RTBs only support one wire per terminal. 10

If you connect more than two devices to the module, you can Output 5 – 11

ground two devices at the shield terminals. You must ground Output 6 + 12

the remaining devices somewhere else, such as, to the DIN rail Output 6 – 13

via a terminal strip. Output 7 + 14

Output 7 – 15

Shield 16

Shield 17

Differential + i
Current A
Receiver or A
Input –

76 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-OF4 and 5069-OF4K modules when used in voltage mode.

5069-OF4 and 5069-OF4K Wiring Diagram - Voltage Mode

Differential + ANALOG OUTPUT


Voltage
Receiver or
Input –
5069-OF4

Channel Connections Shield Ground


The diagram shows a device that is connected to channels 0,
Output 0 + 0
2, and 3. You are not restricted to using only these channels.
Output 0 – 1

You can connect devices to any channel or combination of Output 1 + 2

channels as needed.
Differential + Output 1 – 3

IMPORTANT: Voltage Output 2 + 4

• This module has only two shield terminals. Compact 5000 Receiver or Output 2 – 5

I/O module RTBs only support one wire per terminal. Input –
Output 3 + 6

If you connect more than two devices to the module, you Output 3 – 7

can ground two devices at the shield terminals. You must 8

ground the remaining devices somewhere else, such as, to 9


the DIN rail via a terminal strip. Differential + 10

• The 5069-OF4K module uses the same wiring diagram as Voltage


11
shown for the 5069-OF4 module. Receiver or
Input – 12

13

14

15

Shield 16

Shield 17

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 77


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-OF8 module when used in voltage mode.

5069-OF8 Wiring Diagram - Voltage Mode

ANALOG OUTPUT

5069-OF8

Differential +
Channel Connections Voltage Output 0 + 0

The diagram shows a device that is connected to channels 0, 2, Receiver or Output 0 – 1

Input –
and 3. You are not restricted to using only these channels. Output 1 + 2

You can connect devices to any channel or combination of Output 1 – 3

channels as needed. Shield Ground


Output 2 + 4

Output 2 – 5

IMPORTANT: This module has only two shield terminals. Output 3 + 6

Compact 5000 I/O module RTBs only support one wire per Differential + Output 3 – 7

terminal. Voltage Output 4 + 8

If you connect more than two devices to the module, you can Receiver or Output 4 – 9

Input –
ground two devices at the shield terminals. You must ground Output 5 + 10

the remaining devices somewhere else, such as, to the DIN rail Output 5 – 11

via a terminal strip. Output 6 + 12

Output 6 – 13

Output 7 + 14

Output 7 – 15

Shield 16

Shield 17

Differential +
Voltage
Receiver or
Input –

78 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a functional block diagram for the 5069-OF4 and 5069-OF4K modules.

5069-OF4 and 5069-OF4K Functional Block Diagram

24V DC
SA Power 5
0
Field DC-DC 6
Converter 9

Module
B
Vref 24V DC
Status a
Power
Indicators MOD c
Supply
Power k
p
Backplane l
Out x + Communication a
Voltage/ D/A Converter,
Current Out x – Signal Voltage, and Backplane n
Load Isolator e
Shield Conditioning Current, ASIC Nonvolatile
4-channel Memory

This figure shows a functional block diagram for the 5069-OF8 module.

5069-OF8 Functional Block Diagram

24V DC
SA Power 5
0
Field DC-DC 6
Converter 9
Vref B
D/A Converter, Module 24V DC
Status a
Voltage, and Power
Indicators MOD c
Current, Supply
4-channel Power k
p
Backplane l
Out x + Communication a
Voltage/ D/A Converter,
Current Out x – Signal Voltage, and Backplane n
Load Isolator e
Shield Conditioning Current, ASIC Nonvolatile
4-channel Memory

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 79


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OF4, 5069-OF4K, 5069-OF8


Attribute 5069-OF4, 5069-OF4K 5069-OF8
Outputs 4 voltage or current 8 voltage or current
± 10V
Output range, voltage 0…10V
0…5V
0…20 mA
Output range, current
4…20 mA
16 bits across ± 10.5V - 320 μV/bit
16 bits across 10.5V - 160 μV/bit
Resolution
16 bits across 5.25V - 80 μV/bit
16 bits across 21 mA - 320 nA/bit
Voltage - 1000 Ω min
Drive capability
Current - 500 Ω max
Capacitive load, max (voltage mode only) 1 μF
Inductive load, max (current mode only) 1 mH
Open circuit detection Current mode only
Short circuit detection Voltage mode only – output electronically limited to 16 mA or less
Data format IEEE 32-bit floating point
Module conversion method R-Ladder DAC, monotonicity with no missing codes
Conversion time per channel 25 μs

Scan time
• Per group 0…3 (OF4/OF8) 1.0 ms
• Per group 0…7 (OF8 only) 2.0 ms
Voltage mode – 18 μs max
Step response time to 63% of value
Current mode – 1 ms max
Overvoltage protection, max ± 32V DC
Repeatability 0.05%
Voltage - 0.10% full scale
Calibrated accuracy at 25 °C (77 °F)
Current - 0.10% full scale
Voltage - 0.30% full scale
Accuracy drift with temperature
Current - 0.50% full scale

80 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OF4, 5069-OF4K, and 5069-OF8


Attribute 5069-OF4, 5069-OF4K 5069-OF8
Voltage and current ratings
Analog output ratings +/–10V DC, 0…20 mA per channel
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
SA Power 150 mA @ 18…32V DC 250 mA @ 18…32V DC
(2)
SA Power Passthrough, max 9.95 A @ 18…32V DC
Power dissipation, max 3.3 W 5.3 W
Thermal dissipation, max 11.3 BTU/hr 18.1 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage 50V Functional Isolation between SA power and output ports
No isolation between individual output ports
Factory Calibrated
Calibration methods
User-performed (optional)
Module keying Electronic keying via programming software
1 green/red module status indicator 1 green/red module status indicator
Indicators
4 yellow/red I/O status indicators 8 yellow/red I/O status indicators
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
2 - shielded input ports
Wire category(3) 2 - power ports
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB18-SPRING removable terminal block diameter including insulation
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB18-SCREW removable terminal block diameter including insulation
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 81


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OF4, 5069-OF4K, and 5069-OF8


Attribute 5069-OF4, 5069-OF4K 5069-OF8
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-OF4, 5069-OF4K, and 5069-OF8


Attribute 5069-OF4, 5069-OF4K, 5069-OF8
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…200 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

82 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OF4, 5069-OF4K, and 5069-OF8


Attribute 5069-OF4, 5069-OF4K, 5069-OF8
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on shielded output ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±2 kV line-earth (CM) on shielded output ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

Certifications - 5069-OF4, 5069-OF4K, and 5069-OF8


Certification(1) 5069-OF4, 5069-OF4K, 5069-OF8
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 83


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Safety I/O Modules


I/O Type Cat. No. Description Page
5069-IB8S 18…32V DC 8-point, safety sinking input module
DC safety sinking input 84
5069-IB8SK 18…32V DC 8-point, conformal coated safety sinking input module
18…32V DC 8-point, safety output module that can be used as a Bipolar output module or
5069-OBV8S sourcing output module
DC safety output 92
18…32V DC 8-point, conformal coated safety output module that can be used as a Bipolar output
5069-OBV8SK module or sourcing output module

5069-IB8S and 5069-IB8SK Safety Sinking Input Modules


When the module is wired as shown, it is suitable for applications that are rated up to, and including, Category 3 as
defined in ISO 13849-1.
Important:
• The switches are suitable for applications that are rated up to,
and including, SIL CL3, PLe, Cat. 3.
• The light curtain is suitable for applications that are rated up to,
and including, SIL CL3, PLe, Cat. 4.

Channel Connections
The diagram shows devices that are connected to safety input
channels 0, 1, 6, and 7. You are not restricted to using only those 5069-IB8S
channels.
You can connect devices to any safety input channel or
combination of channels as needed. Safety Input 0 0

Safety Input 1 1
SA Power
Safety Input 2 2
Connections to an external power supply that provides SA power
via the SA Power RTB on one of the following: Safety Input 3 3

• Compact GuardLogix 5380 controller Safety Input 4 4


• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter
Safety Input 5 5
• 5069-FPD field potential distributor
+ OSSD1 Safety Input 6 6
IMPORTANT: Remember the following: 24V DC SELV/PELV- Light
• The 5069-IB8S and 5069-IB8SK modules use DC SA power. You listed power supply Curtain OSSD2 Safety Input 7 7

must connect DC power to the component, that is, controller, –


Test Output 0 8
adapter, or field potential distributor, that provides SA Power to
the modules. Test Output 0 9

• If you install modules in a system that use AC SA power and DC Test Output 1 10

SA power, you must install them on separate SA power buses. Test Output 1 11
• You use a 5069-FPD field potential distributor to establish a
Test Output/Muting Output 2 12
new SA Power bus in a system. SA Power buses are isolated
from each other. To keep the modules on separate SA Power Test Output/Muting Output 2 13

buses, complete the following steps. Test Output/Muting Output 3 14


1. Install the modules that use one type of SA power, for
Test Output/Muting Output 3 15
example DC, to the right of the adapter or controller, that is,
the first SA Power bus. COM 16

2. Install the 5069-FPD field potential distributor to establish a COM 17


second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.
• The SA Power to adjacent SA Power electrical isolation that the
5069-FPD field potential distributor provides has a rating of
240V AC (continuous) reinforced insulation type.

84 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

When the module is wired as shown, and the requirements listed are met in the project of the safety controller, it is
suitable for applications that are rated up to, and including, Category 4 as defined in ISO 13849-1. To achieve that
suitability rating, you may have to perform diagnostic testing and monitoring of the safety function.

One diagnostic test method is to configure the safety input channel for Safety Pulse Test to test the circuit for short
circuits to 24V DC. Safety input pairs must be associated with different Test Output sources.

Channel Connections
The diagram shows devices that are connected to safety
input channels 0 and 1, and to test outputs 0 and 1.
You are not restricted to using only those safety input
channels.
You can connect devices to any channel or combination of
channels as needed.

SA Power 5069-IB8S
Connections to an external power supply that provides SA
power via the SA Power RTB on one of the following:
• Compact GuardLogix 5380 controller Safety Input 0 0

• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Safety Input 1 1

• 5069-FPD field potential distributor Safety Input 2 2


IMPORTANT: Remember the following:
Safety Input 3 3
• The 5069-IB8S and 5069-IB8SK modules use DC SA
power. You must connect DC power to the component, Safety Input 4 4

that is, controller, adapter, or field potential distributor, Safety Input 5 5


that provides SA Power to the modules.
Safety Input 6 6
• If you install modules in a system that use AC SA power
and DC SA power, you must install them on separate SA Safety Input 7 7

power buses. Test Output 0 8


• You use a 5069-FPD field potential distributor to
establish a new SA Power bus in a system. SA Power Test Output 0 9

buses are isolated from each other. To keep the modules Test Output 1 10

on separate SA Power buses, complete these steps.


Test Output 1 11
1. Install the modules that use one type of SA power,
12
for example DC, to the right of the adapter or Test Output/Muting Output 2
controller, that is, the first SA Power bus. Test Output/Muting Output 2 13

2. Install the 5069-FPD field potential distributor to


Test Output/Muting Output 3 14
establish a second SA Power bus.
3. Install the modules that use the other type of SA Test Output/Muting Output 3 15

Muting
power, for example AC, on the second SA Power bus. Lamp COM 16

• The SA Power to adjacent SA Power electrical isolation COM 17

that the 5069-FPD field potential distributor provides


has a rating of 240V AC (continuous) reinforced
insulation type.

IMPORTANT: When the power supply and muting lamp


are configured for a test output, you much connect the
return wire on the device to a COM point on the module.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 85


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

When the module is wired as shown, and the requirements listed are met in the project of the safety controller, it is
suitable for applications that are rated up to, and including, Category 3 as defined in ISO 13849-1.

To achieve that suitability rating, you must meet the following requirements:
• Fault Exclusion is External Wiring fault.
• Use a SIL CL3, PLd, Cat. 3 qualified sensor.
• One of the following configuration combinations:
– Input Point Mode = Safety Pulse Test
– Test Output Mode = Pulse Test

– Input Point Mode = Safety


– Test Output Mode = Power Supply

Channel Connections
The diagram shows a device that is connected to safety input channel
0 and test output channel 0. You are not restricted to using only
those channels.
You can connect devices to any safety input channel or combination
of channels as needed.
We recommend that you connect even-numbered input points to
even-numbered test output points and odd-numbered input points
to odd-numbered test output points. SIL CL3, PLd, Cat. 3 qualified sensor 5069-IB8S
This wiring practice can maximize diagnostic independence and
separation.
Safety Input 0
SA Power Safety Input 1
Connections to an external power supply that provides SA power via Safety Input 2
the SA Power RTB on one of the following:
• Compact GuardLogix 5380 controller Safety Input 3
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Safety Input 4
• 5069-FPD field potential distributor Safety Input 5
IMPORTANT: Remember the following: Safety Input 6
• The 5069-IB8S and 5069-IB8SK modules use DC SA power. You
must connect DC power to the component, that is, controller, Safety Input 7
adapter, or field potential distributor, that provides SA Power to Test Output 0
the modules.
Test Output 0
• If you install modules in a system that uses AC SA power and DC
SA power, you must install them on separate SA power buses. Test Output 1
• You use a 5069-FPD field potential distributor to establish a new Test Output 1
SA Power bus in a system. SA Power buses are isolated from each
Test Output/Muting Output 2
other. To keep the modules on separate SA Power buses, complete
these steps. Test Output/Muting Output 2
1. Install the modules that use one type of SA power, for example Test Output/Muting Output 3
DC, to the right of the adapter or controller, that is, the first SA
Test Output/Muting Output 3
Power bus.
2. Install the 5069-FPD field potential distributor to establish a COM
second SA Power bus. COM
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.
• The SA Power to adjacent SA Power electrical isolation that the
5069-FPD field potential distributor provides has a rating of 240V
AC (continuous) reinforced insulation type.

86 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-IB8S and 5069-IB8SK


Attribute 5069-IB8S, 5069-IB8SK
Safety Inputs
On-state voltage, min 10V DC
On-state voltage, nom 24V DC
On-state voltage, max 32V DC
On-state current, min 1.8 mA
On-state current, nom 2 mA
On-state current, max 2.2 mA
Off-state voltage, max 5V DC
Off-state current, max 1.5 mA
Input delay time
User selectable time: 0 ms…50 ms
Off to On
Default is 0 ms
User selectable time: 0 ms…50 ms
On to Off
Default is 0 ms
Safety integrity Level (SIL) SIL CL3, PLe, Cat. 4
Safety reaction time (SRT) 6 ms
Test Outputs
Output current per channel, max 0.3 A
Output current per group, max 1.2 A
Output current per module, max 1.2 A
Test output pulse width < 700 μs
Test output pulse period < 100 ms
Test output field capacitance, max 0.5 μF
Test output short circuit protection Yes
Test output leakage current 1.5 mA
(1)
Test output overvoltage protection Yes
SA Power reverse voltage protection Yes
SA Power overvoltage protection, max 36.5V DC
Timestamp of inputs No
CIP Sync™ Yes
Overrides No
Pulse latching No
Events No
Pattern matching No
Extended counters No
Scheduled outputs No
Power consumption 3.8 W
(1) Also known as Thermal Shutoff.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 87


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IB8S, 5069-IB8SK


Attribute 5069-IB8S, 5069-IB8SK
Inputs 8 channels, safety sinking
2 test output channels
Test Outputs
2 test output/muting output channels
Voltage category 12/24V DC source
Voltage and current ratings - System is mounted in Horizontal orientation
Input Rating 2.5 mA per channel
Test Output Rating 300 mA per channel
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 5 A @ 18…32V DC
SA Power 100 mA@ 18…32V DC
(2)
SA Power Passthrough, max 9.95 A @ 18…32V DC
Voltage and current ratings - System is mounted in any orientation other than Horizontal (module de-rating)(3)
Input Rating 2.5 mA per channel
Test Output Rating 200 mA per channel
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 5 A @ 18…32V DC
SA Power 100 mA @ 18…32V DC
(2)
SA Power Passthrough, max 5 A @ 18…32V DC
Do not exceed 5 A MOD or SA Power Passthrough current draw in any orientation other than Horizontal.
Power dissipation, max 3.5 W
Thermal dissipation, max 4W
Isolation voltage 250V (continuous), Basic Insulation Type
Module keying Electronic module keying, software configurable
1 green/red module status indicator
Indicators 1 green/red SA power status indicator
12 yellow/red I/O status indicators

88 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-IB8S, 5069-IB8SK


Attribute 5069-IB8S, 5069-IB8SK
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We
recommend that you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
RTB keying None
Wire type Copper
2 - signal ports
Wire category(4)
1 wire per terminal for each signal port
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm
5069-RTB18-SCREW removable terminal block (0.14 in.) max diameter including insulation
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm
5069-RTB18-SPRING removable terminal block (0.11 in.) max diameter including insulation
Insulation stripping length
5069-RTB18-SCREW connections 12 mm (0.47 in.)
5069-RTB18-SPRING connections 10 mm (0.39 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open - style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) The additional supported mounting orientations are Inverted Horizontal, Vertical, Inverted Vertical, Upside Down, and Upside Up.
(4) Use this Conductor Category information for planning conductor routing. For more information, see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 and the appropriate system-level installation
manual.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 89


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-IB8S, 5069-IB8SK


Attribute 5069-IB8S, 5069-IB8SK
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
-40…+85 °C (-40…+185 °F)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Temperature, surrounding air, max.
System is mounted in Horizontal orientation 60 °C (140 °F)
System is mounted in any orientation other than Horizontal 50 °C (122 °F)
(module de-rating)(1)
Temperature, ambient, max
System is mounted in Horizontal orientation 60 °C (140 °F)
System is mounted in any orientation other than Horizontal 50 °C (122 °F)
(module de-rating)(1)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
4.5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
15 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
20V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 20V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 20V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
±4 kV @ 5 kHz on signal ports
IEC 61000-4-4
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
IEC 61000-4-5
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on DC supply ports
IEC 61000-4-29
(1) The additional supported mounting orientations are Inverted Horizontal, Vertical, Inverted Vertical, Upside Down, and Upside Up.

90 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-IB8S, 5069-IB8SK


Certification(1) 5069-IB8S, 5069-IB8SK
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL
File E334470.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/42/EC MD, compliant with:
CE • EN 60204-1; Electrical equipment of machines
• EN ISO 13849-1; Safety-related parts of control systems
• EN 62061; Functional safety of safety-related control systems
• Cat. 4/PLe according to EN ISO 13849-1, and SIL 3 according to EN 626011/IEC 61508/IEC 62511
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM • EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• Ex nA IIC T4 Gc
• DEMKO 18 ATEX 2019X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• Ex nA IIC T4 Gc
• IECEx UL 18.0014X
TÜV Certified for Functional Safety;(2)
TÜV • Capable of SIL 3, CAT. 4/PLe
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
(2) When used with specified firmware revisions. See the Product Safety Certificate at http://www.rockwellautomation.com/global/certification/overview.page for a full list of safety-related certifications.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 91


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-OBV8S and 5069-OBV8SK Safety Output Modules


You can use the safety output modules in Bipolar mode or Sourcing mode.

Bipolar Mode

When the module is wired as shown, and the requirements listed are met in the project of the safety controller, it is
suitable for applications that are rated up to, and including, Category 4 as defined in ISO 13849-1.
To achieve that suitability rating, you may have to perform diagnostic testing and monitoring of the safety function. One
diagnostic test method is to configure the safety output channel for Safety Pulse Test to test the circuit for short circuits
to 24V DC.

• We strongly recommend that you connect separate shielded cables to the P terminal and the N terminal to reduce
the possibility of a wire short between the terminals. If a wire-short fault is detected across the P-N pair, the
module outputs are turned off, but the actuator that is connected to it remains on.

• Configure the application so that No Load and Overload conditions are only detectable at the P terminal.

For Cat.4 applications, if your application remains in safe state, that is, the output is off, for a prolonged duration, we
recommend that you take one of the following actions:

• Apply output monitoring at the actuator. The monitoring can be direct or indirect.
• Limit the safe state to no more than 24 hours.
• Conduct functional test if safe state dwell time increases.

92 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Actuator LA Power
In this wiring configuration, you must connect the LA+ terminal to an
SELV/PELV-listed power supply.
The LA+ and LA- on the actuator must be connected to the same power OUTPUT
supply as the LA+ and LA- on the module.
Connection Pairs
The terminals for each channel function as a Bipolar connection pair LA +
when you use a 5069-OBV8S or 5069-OB8VSK module in Bipolar
5069-OBV8S
switching mode. For example, the Safety Output 0 P (Sourcing) terminal
and Safety Output 0 N (Sinking) terminal are a Bipolar connection pair.
That is, they are a P-N pair. K1
Safety Output 0 P (Sourcing) 0
When the module is in Bipolar switching mode, you must connect the
device to both terminals. Safety Output 0 N (Sinking) 1

Channel Connections K2 Safety Output 1 P (Sourcing) 2

This wiring example shows connections to the P-N pair for Safety Output Safety Output 1 N (Sinking) 3
0. You are not limited to using channel 0 in this mode. You can use all
Safety Output 2 P (Sourcing) 4
channel pairs as determined by your application. LA –
M Safety Output 2 N (Sinking) 5
LA Power
Safety Output 3 P (Sourcing) 6
The Local Actuator (LA+ and LA –) power connections are used to supply
field-side power to the module. Safety Output 3 N (Sinking) 7

• The 5069-OBV8S and 5069-OBV8SK modules do not draw current Safety Output 4 P (Sourcing) 8

from the SA Power bus. Safety Output 4 N (Sinking) 9


Still, the modules are DC-type modules and you must install them on a Safety Output 5 P (Sourcing) 10
DC SA Power bus.
Safety Output 5 N (Sinking) 11
• If you install modules in a system that use AC SA power and DC SA
power, you must install them on separate SA power buses. Safety Output 6 P (Sourcing) 12

• You use a 5069-FPD field potential distributor to establish a new SA Safety Output 6 N (Sinking) 13
Power bus in a system. SA Power buses are isolated from each other. To Safety Output 7 P (Sourcing) 14
keep the modules on separate SA Power buses, complete the
following steps. Safety Output 7 N (Sinking) 15

1. Install the modules that use one type of SA power, for example DC, 24V DC + LA + 16

to the right of the adapter or controller, that is, the first SA SELV/PELV-listed
power supply – LA – 17
Power bus.
2. Install the 5069-FPD field potential distributor to establish a
second SA Power bus.
3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.
• We strongly recommend that, if you have a direct connection
between the safety output module and an input module and those
modules are powered by separate power supplies, that you connect
SA- and LA- together. This practice helps to eliminate grounding float
from disrupting diagnostics.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 93


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

When the module is wired as shown, and the requirements listed are met in the project of the safety controller, it is
suitable for applications that are rated up to, and including, Category 4 as defined in ISO 13849-1.

To achieve that suitability rating, you may have to perform diagnostic testing and monitoring of the safety function. One
diagnostic test method is to configure the safety output channel for Safety Pulse Test to test the circuit for short circuits
to 24V DC. Configure the application so that a No Load fault can only be detected if the wires from both the P- terminal
and the N- terminal are disconnected.

For Cat.4 applications, if your application remains in safe state, that is, the output is off, for a prolonged duration, we
recommend that you take one of the following actions:
• Apply output monitoring at the actuator. The monitoring can be direct or indirect.
• Limit the safe state to no more than 24 hours.
• Conduct functional test if safe state dwell time increases.
Connection Pairs
The terminals for each channel function as a Bipolar connection pair
when you use a 5069-OBV8S or 5069-OB8VSK module in Bipolar
OUTPUT
switching mode. For example, the Safety Output 0 P (Sourcing)
terminal and Safety Output 0 N (Sinking) terminal are a Bipolar
connection pair. That is, they are a P-N pair.
When the module is in Bipolar switching mode, you must connect
the device to both terminals. 5069-OBV8S

Channel Connections K1
This wiring example shows connections to the P-N pair for Safety Safety Output 0 P (Sourcing) 0

Output 0. You are not limited to using channel 0 in this mode. You Safety Output 0 N (Sinking) 1
can use all channel pairs as determined by your application.
K2 Safety Output 1 P (Sourcing) 2

Safety Output 1 N (Sinking) 3


LA Power
The Local Actuator (LA+ and LA –) power connections are used to Safety Output 2 P (Sourcing) 4

supply field-side power to the module. M Safety Output 2 N (Sinking) 5

• The 5069-OBV8S and 5069-OBV8SK modules do not draw Safety Output 3 P (Sourcing) 6
current from the SA Power bus.
Safety Output 3 N (Sinking) 7
Still, the modules are DC type modules, and you must install
them on a DC SA Power bus. Safety Output 4 P (Sourcing) 8

• If you install modules in a system that use AC SA power and DC Safety Output 4 N (Sinking) 9

SA power, you must install them on separate SA power buses. Safety Output 5 P (Sourcing) 10

• You use a 5069-FPD field potential distributor to establish a new Safety Output 5 N (Sinking) 11
SA Power bus in a system. SA Power buses are isolated from each
Safety Output 6 P (Sourcing) 12
other. To keep the modules on separate SA Power buses,
complete the following steps. Safety Output 6 N (Sinking) 13

1. Install the modules that use one type of SA power, for Safety Output 7 P (Sourcing) 14

example DC, to the right of the adapter or controller, that is, Safety Output 7 N (Sinking) 15
the first SA Power bus. +
24V DC LA + 16
2. Install the 5069-FPD field potential distributor to establish a SELV/PELV-listed
second SA Power bus. power supply – LA – 17

3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.
• We strongly recommend that, if you have a direct connection
between the safety output module and an input module and
those modules are powered by separate power supplies, that you
connect SA- and LA- together. This practice helps to eliminate
grounding float from disrupting diagnostics.

94 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

When the module is wired as shown, and the requirements listed are met in the project of the safety controller, it is
suitable for applications that are rated up to, and including, Category 4 as defined in ISO 13849-1. To achieve that
suitability rating, you may have to perform diagnostic testing and monitoring of the safety function. One diagnostic test
method is to configure the safety output channel for Safety Pulse Test to test the circuit for short circuits to 24V DC.

For Cat.4 applications, if your application remains in safe state, that is, the output is off, for a prolonged duration, we
recommend that you take one of the following actions:
• Apply output monitoring at the actuator. The monitoring can be direct or indirect.
• Limit the safe state to no more than 24 hours.
• Conduct functional test if safe state dwell time increases.
• A qualified actuator must be installed, for example, in accordance with IEC 60947.
Connection Pairs
The terminals for each channel function as a Bipolar connection pair when
you use a 5069-OBV8S or 5069-OB8VSK module in Bipolar switching mode.
For example, the Safety Output 0 P (Sourcing) terminal and Safety Output OUTPUT
0 N (Sinking) terminal are a Bipolar connection pair. That is, they are a
P-N pair.
When the module is in Bipolar switching mode, you must connect the
device to both terminals.
5069-OBV8S
Channel Connections Cat. 4 Actuator
This wiring example shows connections to the P-N pair for Safety Output 0. Subsystem
You are not limited to using channel 0 in this mode. You can use all channel Safety Output 0 P (Sourcing)
pairs as determined by your application. Safety Output 0 N (Sinking)
Safety Output 1 P (Sourcing)
LA Power
The Local Actuator (LA+ and LA –) power connections are used to supply Safety Output 1 N (Sinking)
field-side power to the module. Safety Output 2 P (Sourcing)
• The 5069-OBV8S and 5069-OBV8SK modules do not draw current Safety Output 2 N (Sinking)
from the SA Power bus.
Safety Output 3 P (Sourcing)
Still, the modules are DC type modules, and you must install them on a
DC SA Power bus Safety Output 3 N (Sinking)
• If you install modules in a system that use AC SA power and DC SA Safety Output 4 P (Sourcing)
power, you must install them on separate SA power buses. Safety Output 4 N (Sinking)
• You use a 5069-FPD field potential distributor to establish a new SA Safety Output 5 P (Sourcing)
Power bus in a system. SA Power buses are isolated from each other. To
keep the modules on separate SA Power buses, complete the Safety Output 5 N (Sinking)
following steps. Safety Output 6 P (Sourcing)
1. Install the modules that use one type of SA power, for example DC, Safety Output 6 N (Sinking)
to the right of the adapter or controller, that is, the first SA
Safety Output 7 P (Sourcing)
Power bus.
2. Install the 5069-FPD field potential distributor to establish a second Safety Output 7 N (Sinking)
SA Power bus. 24V DC + LA +
3. Install the modules that use the other type of SA power, for example SELV/PELV-listed
power supply – LA –
AC, on the second SA Power bus.
• We strongly recommend that if, you have a direct connection
between the safety output module and an input module and those
modules are powered by separate power supplies, that you connect SA-
and LA- together. This practice helps to eliminate grounding float from
disrupting diagnostics.
• The SA Power to adjacent SA Power electrical isolation that the
5069-FPD field potential distributor provides has a rating of 240V AC
(continuous) reinforced insulation type.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 95


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Sourcing Mode

When the module is wired as shown, it is suitable for applications that are rated up to, and including, Category 2 as
defined in ISO 13849-1.

To achieve that suitability rating, you may have to perform diagnostic testing and monitoring of the safety function. One
diagnostic test method is to configure the safety output channel for Safety Pulse Test to test the circuit for short circuits
to 24V DC.

Channel Connections OUTPUT


This wiring example shows connection to Safety Output 0.
You are not limited to using channel 0 in this mode. You
can use all channels as determined by your application.

5069-OBV8S

LA Power
The Local Actuator (LA+ and LA –) power connections are Safety Output 0 P (Sourcing) 0
K
used to supply field-side power to the module. Safety Output 0 N (Sinking) 1
• The 5069-OBV8S and 5069-OBV8SK modules do not
Safety Output 1 P (Sourcing) 2
draw current from the SA Power bus.
Still, the modules are DC type modules, and you must Safety Output 1 N (Sinking) 3

install them on a DC SA Power bus M Safety Output 2 P (Sourcing) 4


LA –
• If you install modules in a system that use AC SA power Safety Output 2 N (Sinking) 5
and DC SA power, you must install them on separate SA
power buses. Safety Output 3 P (Sourcing) 6

• You use a 5069-FPD field potential distributor to Safety Output 3 N (Sinking) 7


establish a new SA Power bus in a system. SA Power
Safety Output 4 P (Sourcing) 8
buses are isolated from each other. To keep the modules
on separate SA Power buses, complete the Safety Output 4 N (Sinking) 9
following steps. Safety Output 5 P (Sourcing) 10
1. Install the modules that use one type of SA power,
for example DC, to the right of the adapter or Safety Output 5 N (Sinking) 11

controller, that is, the first SA Power bus. Safety Output 6 P (Sourcing) 12

2. Install the 5069-FPD field potential distributor to Safety Output 6 N (Sinking) 13


establish a second SA Power bus.
Safety Output 7 P (Sourcing) 14
3. Install the modules that use the other type of SA
power, for example AC, on the second SA Power bus. Safety Output 7 N (Sinking) 15

24V DC +
• We strongly recommend that, if you have a direct LA + 16
SELV/PELV-listed
connection between the safety output module and an power supply – LA – 17
input module and those modules are powered by
separate power supplies, that you connect SA- and LA-
together. This practice helps to eliminate grounding
float from disrupting diagnostics.

96 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

When the module is wired as shown, it is suitable for applications that are rated up to, and including, Category 4 as
defined in ISO 13849-1.

To achieve that suitability rating, you may have to perform diagnostic testing and monitoring of the safety function. One
diagnostic test method is to configure the safety output channel for Safety Pulse Test to test the circuit for short circuits
to 24V DC.

For Cat.4 applications, if your application remains in safe state, that is, the output is off, for a prolonged duration, we
recommend that you take one of these actions:
• Apply output monitoring at the actuator. The monitoring can be direct or indirect.
• Limit the safe state to no more than 24 hours.
• Conduct functional test if safe state dwell time increases.
Connection Pairs
When you use dual-channel sourcing wiring on the 5069-OBV8S
or 5069-OBV8SK module, you must connect the devices to
dual-channel connection pairs. For example, the devices are
connected to channels 4 and 5 because they are a connection pair.
These channels are dual-channel connection pairs: OUTPUT

• Channels 0 and 1 (shown)


• Channels 2 and 3
• Channels 4 and 5
• Channels 6 and 7 5069-OBV8S

Channel Connections K1
This wiring example shows connections to Safety Output 0 P and Safety Output 0 P (Sourcing) 0

Safety Output 1 P. You are not limited to using channels 0 and 1 in


Safety Output 0 N (Sinking) 1
this mode. You can use all channel pairs as determined by your
application. Safety Output 1 P (Sourcing) 2
K2
Safety Output 1 N (Sinking) 3
LA Power
Safety Output 2 P (Sourcing) 4
The Local Actuator (LA+ and LA –) power connections are used to
supply field-side power to the module. Safety Output 2 N (Sinking) 5

• The 5069-OBV8S and 5069-OBV8SK modules do not draw M Safety Output 3 P (Sourcing) 6

current from the SA Power bus. Safety Output 3 N (Sinking) 7

Still, the modules are DC type modules, and you must install LA –
Safety Output 4 P (Sourcing) 8
them on a DC SA Power bus
• If you install modules in a system that use AC SA power and DC Safety Output 4 N (Sinking) 9

SA power, you must install them on separate SA power buses. Safety Output 5 P (Sourcing) 10

• You use a 5069-FPD field potential distributor to establish a new Safety Output 5 N (Sinking) 11
SA Power bus in a system. SA Power buses are isolated from Safety Output 6 P (Sourcing) 12
each other. To keep the modules on separate SA Power buses,
complete these steps. Safety Output 6 N (Sinking) 13

1. Install the modules that use one type of SA power, for Safety Output 7 P (Sourcing) 14

example DC, to the right of the adapter or controller, that is, Safety Output 7 N (Sinking) 15
the first SA Power bus. +
24V DC LA + 16
2. Install the 5069-FPD field potential distributor to establish a SELV/PELV-listed
second SA Power bus. power supply – LA – 17

3. Install the modules that use the other type of SA power, for
example AC, on the second SA Power bus.
• We strongly recommend that, if you have a direct connection
between the safety output module and an input module and
those modules are powered by separate power supplies, that
you connect SA- and LA- together. This practice helps to
eliminate grounding float from disrupting diagnostics.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 97


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

When the module is wired as shown on page 99, and the requirements listed are met in the project of the safety
controller, it is suitable for applications that are rated up to, and including, Category 4 as defined in ISO 13849-1.

To achieve that suitability rating, you may have to perform diagnostic testing and monitoring of the safety function. One
diagnostic test method is to configure the safety output channel for Safety Pulse Test to test the circuit for short circuits
to 24V DC.
• All power source cables must be installed separately, for example, with a separate cable duct or shielded cable.
Power source cables are connections to the MOD+, SA+, or LA+ terminals.
Otherwise, a Short Circuit condition between SA+ and P can be detected and the output is turned off but the
actuator that is connected to it remains on.

• You must connect two ground terminals. Otherwise, the maximum residual current at signal 0 cannot be
maintained if only one ground line is connected and it is interrupted.

• A qualified actuator must be installed, for example, in accordance with IEC 60947.

98 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

For Cat.4 applications, if your application remains in safe state, that is, the output is off, for a prolonged duration, we
recommend that you take one of these actions:
• Apply output monitoring at the actuator. The monitoring can be direct or indirect.
• Limit the safe state to no more than 24 hours.
• Conduct functional test if safe state dwell time increases.

Channel Connections
This wiring example shows connections to Safety Output 0. OUTPUT
You are not limited to using channel 0 in this mode. You
can use all channels as determined by your application.

LA Power
5069-OBV8S
The Local Actuator (LA+ and LA –) power connections are
Cat. 4 Actuator
used to supply field-side power to the module. Subsystem
• The 5069-OBV8S and 5069-OBV8SK modules do not Safety Output 0 P (Sourcing)
draw current from the SA Power bus.
Safety Output 0 N (Sinking)
Still, the modules are DC type modules, and you must
install them on a DC SA Power bus Safety Output 1 P (Sourcing)
• If you install modules in a system that use AC SA power Safety Output 1 N (Sinking)
and DC SA power, you must install them on separate SA Safety Output 2 P (Sourcing)
power buses. LA –
Safety Output 2 N (Sinking)
• You use a 5069-FPD field potential distributor to
establish a new SA Power bus in a system. SA Power Safety Output 3 P (Sourcing)
buses are isolated from each other. To keep the modules Safety Output 3 N (Sinking)
on separate SA Power buses, complete these steps.
Safety Output 4 P (Sourcing)
1. Install the modules that use one type of SA power,
for example DC, to the right of the adapter or Safety Output 4 N (Sinking)
controller, that is, the first SA Power bus. Safety Output 5 P (Sourcing)
2. Install the 5069-FPD field potential distributor to Safety Output 5 N (Sinking)
establish a second SA Power bus. Safety Output 6 P (Sourcing)
3. Install the modules that use the other type of SA
power, for example AC, on the second SA Power bus. Safety Output 6 N (Sinking)
• We strongly recommend that, if you have a direct Safety Output 7 P (Sourcing)
connection between the safety output module and an Safety Output 7 N (Sinking)
input module and those modules are powered by 24V DC + LA +
separate power supplies, that you connect SA- and LA- SELV/PELV-listed
together. This practice helps to eliminate grounding power supply – LA –
float from disrupting diagnostics.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 99


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-OBV8S, 5069-OBV8SK


Attribute 5069-OBV8S, 5069-OBV8SK
(1)
On-state voltage, min 17.5V DC
(1)
On-state voltage, nom 24V DC
(1)
On-state voltage, max 32V DC
(1)
On-state voltage drop, max 0.5V DC
(1)
On-state current per channel, min 1A
(1)
Off-state voltage, max 0.5V DC
(2)
Off-state leakage current per point, max 1.5 mA
Output current rating per channel 1A
Surge current per point, max 1.5 A
Output delay time (backplane to screw)
Off to On 4 ms, max
On to Off 4 ms, max
Safety Integrity Level SIL CL3, PLe, Cat. 4
Safety reaction time (SRT) 4.5 ms
Pulse width, min 400 μs
Field power loss detection Yes (per point)
No load detection diagnostics Yes (per point)
Output short circuit/overload detection Yes (per point)
Output short circuit/overload protection Yes (per point)
Output overtemperature detection Yes (per point)
Output overtemperature protection Yes (per point)
Reverse voltage protection Yes
Overvoltage protection, max Yes
CIP Sync Yes
Output control in fault mode per point No
Output states in program mode per point Off
Output states in fault mode per point Off
Forever - Safety outputs turn off when the fault is detected and remain off until the cause of the fault is
Duration of fault mode per point removed and the safety outputs are commanded into the safe state.
(1) Local Actuator (LA) Field Power related attributes.
(2) Recommended Loading Resistor - To limit the effects of leakage current through solid-state outputs, you can connect a loading resistor in parallel with your load. For 24V DC operation, use a 5.6 KΩ, 0.5 W resistor for
transistor operation.

100 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OBV8S, 5069-OBV8SK


Attribute 5069-5069-OBV8S, 5069-OBV8SK
Outputs 8
Voltage category 24V DC
Voltage and current ratings - System is mounted in Horizontal orientation
Output Rating 1 A per channel
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 5 A @ 18…32V DC
1 A per channel @ 18…32V DC
LA Power
8 A per module @ 18…32V DC
SA Power Passthrough, max(2)
9.95 A @ 18…32V DC
The module does not draw SA Power current.
Do not exceed 5 A MOD Power Passthrough current draw.
Do not exceed 10 A or SA Power Passthrough current draw.
Voltage and current ratings - System is mounted in any orientation other than Horizontal (module de-rating)(3)
Output Rating 0.7 A per channel
MOD Power 75 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 5 A @ 18…32V DC
0.7 A per channel @ 18…32V DC
LA Power
5.6 A per module @ 18…32V DC
SA Power Passthrough, max(2)
5 A @ 18…32V DC
The module does not draw SA Power current.
Do not exceed 5 A MOD or SA Power Passthrough current draw in any orientation other than Horizontal.
Power dissipation, max 6.5 W
Thermal dissipation, max 6.5 W
250V (continuous), Basic Insulation Type
Isolation voltage No isolation between LA power and output ports
No isolation between individual output ports
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators 1 green/red SA power status indicator
16 yellow/red I/O status indicators
Slot width 1.5
Dimensions (HxWxD), approx 144.57 x 36 x 105.42 mm (5.69 x 1.42 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We
recommend that you order only the RTB type that your system requires.
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N·m (3.5 lb·in)
RTB keying None
Wire type Copper
2 - signal ports
Wire category(4)
1 wire per terminal for each signal port

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 101


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-OBV8S, 5069-OBV8SK


Attribute 5069-5069-OBV8S, 5069-OBV8SK
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm
5069-RTB18-SCREW connections (9/64 in.) insulated max diameter
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm
5069-RTB18-SPRING connections (1/8 in.) insulated max diameter
Insulation stripping length
5069-RTB18-SCREW connections 12 mm (0.47 in.)
5069-RTB18-SPRING connections 10 mm (0.39 in.)
Weight, approx 240 g (0.53 lb.)
Enclosure type rating None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) The additional supported mounting orientations are Inverted Horizontal, Vertical, Inverted Vertical, Upside Down, and Upside Up.
(4) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-OBV8S, 5069-OBV8SK


Attribute 5069-OBV8S, 5069-OBV8SK
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
-40…+85 °C (-40…+185 °F)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Temperature, surrounding air, max.
System is mounted in Horizontal orientation 60 °C (140 °F)
System is mounted in any orientation other than Horizontal 50 °C (122 °F)
(module de-rating)(1)
Temperature, ambient, max
System is mounted in Horizontal orientation 60 °C (140 °F)
System is mounted in any orientation other than Horizontal 50 °C (122 °F)
(module de-rating)(1)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
4.5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
15 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4

102 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-OBV8S, 5069-OBV8SK


Attribute 5069-OBV8S, 5069-OBV8SK
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
20V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 20V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 20V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
±4 kV @ 5 kHz on signal ports
IEC 61000-4-4
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
IEC 61000-4-5
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on DC supply ports
IEC 61000-4-29
(1) The additional supported mounting orientations are Inverted Horizontal, Vertical, Inverted Vertical, Upside Down, and Upside Up.

Certifications - 5069-OBV8S, 5069-OBV8SK


Certification(1) 5069-OBV8S, 5069-OBV8SK
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL
File E334470.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/42/EC MD, compliant with:
CE • EN 60204-1; Electrical equipment of machines
• EN ISO 13849-1; Safety-related parts of control systems
• EN 62061; Functional safety of safety-related control systems
• Cat. 4/PLe according to EN ISO 13849-1, and SIL 3 according to EN 626011/IEC 61508/IEC 62511
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM • EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• Ex nA IIC T4 Gc
• DEMKO 18 ATEX 2019X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• Ex nA IIC T4 Gc
• IECEx UL 18.0014X
TÜV Certified for Functional Safety;(2)
TÜV • Capable of SIL 3, CAT. 4/PLe
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
(2) When used with specified firmware revisions. See the Product Safety Certificate at http://www.rockwellautomation.com/global/certification/overview.page for a full list of safety-related certifications.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 103


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-HSC2xOB4 High-speed Counter Module


This figure shows a wiring diagram for the 5069-HSC2xOB4 module connected to a differential encoder.

5069-HSC2xOB4 Wiring Diagram - Differential Encoder

Channel Connections
Power Supply
The diagram shows connections to
channel 0. You are not restricted to +V DC COM
using only that channel. COUNTER

You can connect to any channel or


combination of channels as
Allen-Bradley 845H Series
needed. VS
Differential Encoder
GND 5069-HSC2xOB4

IMPORTANT: We recommend that


you use twisted-pair, individually A
Input A0+ 0
shielded cable with a maximum A-
length of 300 m (1000 ft) when Input A0- 1
B
connecting a differential encoder. Input B0+ 2
B-
For more information on the cable Input B0- 3
type to use, see the encoder Z
Input Z0+
documentation. Z- 4

Input Z0- 5

Shield Input A1+ 6

Input A1- 7

Input B1+ 8

Input B1-
9

Shield/Housing Input Z1+ 10


Connect only if the housing is electronically Input Z1-
isolated from the motor and ground. 11

Output 0 12

Output 1 13

Output 2 14
Output 3
Earth Ground 15

If the module is installed on a DIN Chassis


16
rail that is grounded, you can Chassis
17
connect the cable shield to either
terminal labeled Chassis instead
of the Earth Ground.

104 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-HSC2xOB4 module connected to a single-ended encoder.

5069-HSC2xOB4 Wiring Diagram - Single-ended Encoder

Power Supply
Channel Connections +V DC COM
COUNTER
The diagram shows connections to
channel 0. You are not restricted to
using only that channel.
Allen-Bradley 845H Series
You can connect to any channel or VS
Single-ended Encoder
combination of channels as needed. GND 5069-HSC2xOB4

R
A
IMPORTANT: We recommend that Input A0+ 0

you use twisted-pair, individually Input A0- 1


B
shielded cable with a maximum Input B0+ 2

length of 300 m (1000 ft) when Input B0- 3


connecting a single-ended Z
encoder. Input Z0+ 4

For more information on the cable Input Z0- 5

type to use, see the encoder Shield Input A1+ 6

documentation. Input A1- 7

Input B1+ 8

Input B1-
Shield/Housing 9

Connect only if the housing is electronically Input Z1+ 10

isolated from the motor and ground. Input Z1- 11

Output 0 12

Output 1 13
Earth Ground
Output 2 14
If the module is installed on a DIN
Output 3
rail that is grounded, you can 15

connect the cable shield to either Chassis 16


terminal labeled Chassis instead Chassis 17
of the Earth Ground.

IMPORTANT: External resistors, as indicated in the R location, are required if they are not internal to the encoder. The pull-up resistor (R) value depends on the power
supply value. The following table shows the maximum resistor values for typical supply voltages. To calculate the maximum resistor value, use this formula:
Where:
VDC - Vmin
R= R = Maximum pull-up resistor value
Imin
VDC = Power supply voltage
Vmin = 3.0V DC
Imin = 4.0 mA

Power Supply Voltage (V DC) Pull-up Resistor Value (R), Max(1)


5 500 Ω
12 2250 Ω
24 5250 Ω
(1) Resistance values can change, depending on your application. The minimum resistor (R) value
depends on the current sinking capability of the encoder.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 105


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-HSC2xOB4 module connected to a discrete input device.

5069-HSC2xOB4 Wiring Diagram - Discrete Input Devices

Channel Connections
The diagram shows connections to input Power Supply COUNTER
channels 0 and 1. You are not restricted to
using only those input channels. +V DC
You can connect to any input channel or COM
combination of input channels as needed.
5069-HSC2xOB4

VS
Proximity Sensor OUT
Input A0+ 0

COM
Input A0- 1

Input B0+ 2

Input B0- 3

R Input Z0+ 4

VS
Input Z0- 5
Photoelectric Sensor OUT
with Open Collector Input A1+ 6

Sinking Output COM


Input A1- 7

Input B1+ 8

Input B1- 9

+V DC Input Z1+ 10

COM Input Z1- 11

Power Supply Output 0 12

Output 1 13

Output 2 14

Output 3 15

Chassis 16

Chassis 17

IMPORTANT: External resistors, as indicated in the R location to the left, are required if they are not internal to the
encoder. The pull-up resistor (R) value depends on the power supply value. The following table shows the maximum
resistor values for typical supply voltages. To calculate the maximum resistor value, use this formula:
Where:
VDC - Vmin
R= R = Maximum pull-up resistor value
Imin
VDC = Power supply voltage
Vmin = 3.0V DC
Imin = 4.0 mA

Power Supply Voltage (V DC) Pull-up Resistor Value (R), Max(1)


5 500 Ω
12 2250 Ω
24 5250 Ω
(1) Resistance values can change, depending on your application. The minimum resistor (R)
value depends on the current sinking capability of the encoder.

106 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for the 5069-HSC2xOB4 module connected to a discrete output device.

5069-HSC2xOB4 Wiring Diagram - Discrete Output Devices

Channel Connections
The diagram shows connections to output channels 0 and
2. You are not restricted to using only those output
channels. COUNTER
You can connect to any output channel or combination of
output channels as needed.

5069-HSC2xOB4
SA Power
Connections to an external power supply that provides SA
power via the SA Power RTB on one of the following:
Input A0+ 0
• CompactLogix 5380 controller
Input A0- 1
• Compact GuardLogix 5380 controller
Input B0+ 2
• CompactLogix 5480 controller
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter Input B0- 3

• 5069-FPD field potential distributor Input Z0+ 4

IMPORTANT: Remember the following: Input Z0- 5

• The 5069-HSC2xOB4 module uses DC SA power. You SA Power Supply Input A1+ 6
must connect DC power to the component, that is,
controller, adapter, or field potential distributor, that Input A1- 7

provides SA Power to the module. SA+ Input B1+ 8

• The 5069-HSC2xOB4 module outputs use a shared SA- Input B1- 9

common. The outputs have a return through internal


Input Z1+ 10
module circuitry to the SA (–) terminal on the SA
Power RTB. Input Z1- 11

• If you install modules in a system that use AC SA power CR Output 0 12

and DC SA power, you must install them on separate SA Output 1 13


power buses.
Output 2 14
• You use a 5069-FPD field potential distributor to
establish a new SA Power bus in a system. SA Power Output 3 15

buses are isolated from each other. To keep the Chassis 16

modules on separate SA Power buses, complete these


Chassis 17
steps.
1. Install the modules that use one type of SA power,
for example DC, to the right of the adapter or
controller, that is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to
establish a second SA Power bus.
3. Install the modules that use the other type of SA
power, for example AC, on the second SA Power bus.

Recommended Surge Suppression


The module has built-in suppression that is sufficient for
most applications. For high-noise applications, we
recommend that you use a 1N4004 diode reverse-wired
across the load for transistor outputs switching 24V DC
inductive loads.
For additional details, see the Industrial Automation
Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 107


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows functional block diagrams for the 5069-HSC2xOB4 module inputs and outputs.

5069-HSC2xOB4 Functional Block Diagram


User Side Logic Side
Module Inputs
This graphic shows the
diagram for Counter 0. Current
A0 (+)
Counter 1 uses the same Limiting
Channel A0 Status
design.
Also, the modules only
supports a DC
A0 (–)
power source.

B0 (+) Current
Limiting
Channel B0 Status

B0 (–)

Current
Z0 (+) Limiting
Channel Z0 Status

Z0 (–)

Module Outputs SA Power Supply


Module 24V DC
Connections to external SA+ Status
Power
power supply that provides Indicators
Supply MOD 5
SA Power. SA-
Power 0
For more information, see 6
Backplane
page 107. 9
Output Communication

Output Backplane B
Isolation ASIC
Circuitry Nonvolatile a
Memory c
Inductive Kickback k
Suppression p
l
24V DC to 5V DC Soft Start SA+ a
Converter Circuitry n
e

SA-

108 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-HSC2xOB4


Attribute 5069-HSC2xOB4
Input current, max 8 mA
On-state voltage, min 3V DC
On-state voltage, nom 24V DC
On-state voltage, max 32V DC
On-state voltage drop, max < 0.3V DC
On-state current, min 4 mA
Off-state voltage, max 1.5V
Off-state current, max 1 mA
Output voltage range 10…32V DC
1 mA per channel
On-state output current, min
4 mA per module
Pulse width, min 125 ns
Pulse separation, min 100 ns
No load detection diagnostics Yes (per channel diagnostics)
Output short circuit/overload/overtemp detection Yes (per channel diagnostics)
Output short circuit/overload protection Yes
Reverse voltage protection 32V DC
Overvoltage protection, max 36V (fuse protected)
Pilot duty Yes (Make current electronically limited/protected @ 3.6 A)
• Hold last state
Output control in fault state per point • On
• Off (default)
• Hold last state
Output states in program mode per point • On
• Off (default)
• Hold Last State
Output states in fault mode per point • On
• Off (default)
• 1s
• 2s
Duration of fault mode per point • 5s
• 10 s
• Forever (default)

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 109


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-HSC2xOB4


Attribute 5069-HSC2xOB4
Inputs 2 quadrature (ABZ) differential inputs
Outputs 4 Channels (1 group of 4), sourcing
Voltage category 12/24V DC source
Voltage and current ratings
Counter input ratings 4 mA @ 3…32V DC
MOD Power 50 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
SA Power 3 A @ 18…32V DC
(2)
SA Power Passthrough, max 9.95 A @ 10…32V DC
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 3W
Thermal dissipation, max 10.2 BTU/hr
250V (continuous), Basic Insulation Type
No isolation between SA Power and I/O ports
Isolation voltage
No isolation between individual I/O ports
Type tested at 1500V AC for 60 s
Module keying Electronic keying via programming software
1 green/red module status indicator
Indicators
10 yellow/red I/O status indicator
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail • You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
One of these RTB types.
• 5069-RTB18-SPRING RTB
RTB • 5069-RTB18-SCREW RTB
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that
you order only the RTB type that your system requires.
RTB keying None
RTB torque (5069-RTB18-SCREW RTB only) 0.4 N•m (3.5 lb•in)
2 - on shielded output ports
Wiring category(3) 2 - on output power ports
2 - on shielded counter ports

110 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

General Specifications - 5069-HSC2xOB4


Attribute 5069-HSC2xOB4
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
5069-RTB18-SPRING connections in.) max diameter including insulation
0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
5069-RTB18-SCREW connections in.) max diameter including insulation
Insulation stripping length
5069-RTB18-SPRING connections 10 mm (0.39 in.)
5069-RTB18-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 5069-HSC2xOB4


Attribute 5069-HSC2xOB4
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95 % noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 111


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-HSC2xOB4


Attribute 5069-HSC2xOB4
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±4 kV @ 5 kHz on power ports
EFT/B immunity
±2 kV @ 5 kHz on shielded output ports
IEC 61000-4-4
±2 kV @ 5 kHz on shielded counter ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
Surge transient immunity
±2 kV line-earth (CM) on shielded output ports
IEC 61000-4-5
±2 kV line-earth (CM) on shielded counter ports
Conducted RF immunity
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29:

Certifications - 5069-HSC2xOB4
Certification(1) 5069-HSC2xOB4
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection “n”
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1455X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection “n”
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0007X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

112 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-SERIAL Serial Module


The Compact 5000 I/O serial module provides a network interface to RS-232, RS-422, and RS-485 devices.

This figure shows the 5069-SERIAL serial module.

SERIAL
SA Power
• The 5069-SERIAL module does not draw current
from the SA power bus.
Still, the module is a DC-type module, and you 5069-SERIAL

must install it on a DC SA Power bus.


• If you install modules in a system that use AC SA CH0 TXD
power and DC SA power, you must install them on CH0 RXD

separate SA Power buses. CH1 TXD


CH1 RXD
• You use a 5069-FPD field potential distributor to
establish a new SA Power bus in a system. SA
Power buses are isolated from each other. To keep
the modules on separate SA Power buses, CHANNEL 0
ISOLATED

complete these steps. Channel 0 Communication Port


1. Install the modules that use one type of SA
power, for example DC, to the right of the
adapter or controller, that is, the first SA Power
bus.
2. Install the 5069-FPD field potential distributor
Channel 1 Communication Port
ISOLATED

to establish a second SA Power bus.


CHANNEL 1

3. Install the modules that use the other type of


SA power, for example AC, on the second SA
Power bus.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 113


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-SERIAL Functional Block Diagram

Module 24V DC
DC-DC
Power
Converter MOD
Supply
Power 5
0
Status 6
Indicators 9

B
a
Dsub 9-pin Communication Backplane
c
Isolator k
Connector IC Communication
p
l
ASIC a
Dsub 9-pin Communication Isolator n
Connector IC e

DC-DC Volatile Nonvolatile


Converter Memory Memory

RS-232 Wiring Examples


Pins - RS-232C
Wiring
Pin RS-232C Input (i)/Output (o)(1)
No Handshaking Handshaking
1 Data Carrier Detect (DCD) (i) - -
(2)
2 Receive Data (RXD) (i) A A
6 1
3 Transmit Data (TXD) (o) A A
7 2
(3)
4 Data Terminal Ready (DTR) (o) B B
3
8 5 Common (COM) - A A
4
9 6 Data Set Ready (DSR) (i) - -
5 7 Request To Send (RTS) (o) B A
8 Clear To Send (CTS) (i) - A

9 - - - -

(1) From 5069-SERIAL


(2) A = Changing signal level (Active/Inactive)
(3) B = Fixing signal level (Active/Inactive)

114 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

The following graphics show RS-232 wiring.

5069-SERIAL to DTE Device (9-pin or 25-pin) without Hardware Handshaking

5069-SERIAL DTE Device (9-pin) 5069-SERIAL DTE Device (25-pin)

1 DCD DCD 1 1 DCD DCD 8

2 RXD RXD 2 2 RXD RXD 3

3 TXD TXD 3 3 TXD TXD 2

4 DTR DTR 4 4 DTR DTR 20

5 COM COM 5 5 COM COM 7

6 DSR DSR 6 6 DSR DSR 6

7 RTS RTS 7 7 RTS RTS 4

8 CTS CTS 8 8 CTS CTS 5

9 9 9

5069-SERIAL to DTE Device (9-pin or 25-pin) with “Half-duplex”

5069-SERIAL DTE Device (9-pin) 5069-SERIAL DTE Device (25-pin)

1 DCD DCD 1 1 DCD DCD 8

2 RXD RXD 2 2 RXD RXD 3

3 TXD TXD 3 3 TXD TXD 2

4 DTR DTR 4 4 DTR DTR 20

5 COM COM 5 5 COM COM 7

6 DSR DSR 6 6 DSR DSR 6

7 RTS RTS 7 7 RTS RTS 4

8 CTS CTS 8 8 CTS CTS 5

9 9 9

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 115


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-SERIAL to DCE Device with “Full-duplex”

5069-SERIAL DCE Device

1 DCD 1

2 RXD TXD 2

3 TXD RXD 3

4 DTR RTS 4

5 COM CTS 5

6 DSR DSR 6

7 RTS COM 7

8 CTS DCD 8

9 DTR 20

5069-SERIAL to DCE Device (Modem) with “Full or Half-duplex”

5069-SERIAL DCE Device

1 DCD 1

2 RXD TXD 2

3 TXD RXD 3

4 DTR RTS 4

5 COM CTS 5

6 DSR DSR 6

7 RTS COM 7

8 CTS DCD 8

9 DTR 20

116 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-SERIAL to DTE Device (9-pin or 25-pin) with “Full or Half-duplex” or Null Modem

5069-SERIAL Modem (DTE [9-pin]) 5069-SERIAL Modem (DTE [25-pin])

1 DCD DCD 1 1 DCD DCD 8

2 RXD RXD 2 2 RXD RXD 3

3 TXD TXD 3 3 TXD TXD 2

4 DTR DTR 4 4 DTR DTR 20

5 COM COM 5 5 COM COM 7

6 DSR DSR 6 6 DSR DSR 6

7 RTS RTS 7 7 RTS RTS 4

8 CTS CTS 8 8 CTS CTS 5

9 9 9

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 117


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

RS-422 Wiring Example


Pins - RS-422
Pin RS-422 Input (i)/Output (o)(1) Wiring
1 - - -
2 Receive Data + (RXD+) (i) A(2)
6 1
3 Transmit Data + (TXD+) (o) A
7 2
4 - - B
3
8 5 Common (COM) - A
4
9 6 - - -
5 7 Transmit Data - (TXD-) (o) A
8 Receive Data - (RXD-) (i) A

9 - - -

(1) From 5069-SERIAL


(2) A = Changing signal level (Active/Inactive)

The following graphic shows RS-422 wiring.

5069-SERIAL RS-422 Wiring

IMPORTANT Place the termination resistor between RxD+ and RxD- to implement this wiring.

5069-SERIAL DTE Device

1 1

2 RXD+ RXD+ 2

3 TXD+ TXD+ 3

4 4

5 COM COM 5

6 6

7 TXD- TXD- 7

8 RXD- RXD- 8

9 9

118 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

RS-485 Wiring Example


Pins - RS-485
Pin RS-485 Input (i)/Output (o)(1) Wiring
1 - - -
2 - - -
6 1
Transmit/Receive Data +
7 2 3 (i/o) A(2)
(TRXD+)
3 4 - - -
8
4 5 Common (COM) - A
9
6 - - -
5
Transmit/Receive Data -
7 (i/o) A
(TRXD-)
8 - - -
9 - - -
(1) From 5069-SERIAL
(2) A = Changing signal level (Active/Inactive)

The following graphic shows RS-485 wiring.

5069-SERIAL RS-485 Wiring

IMPORTANT Place the termination resister between TRXD+ and TRXD- to implement this wiring.

5069-SERIAL DTE Device

1 1

2 2

3 TRXD+ TRXD+ 3

4 4

5 COM COM 5

6 6

7 TRXD- TRXD- 7

8 8

9 9

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 119


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-SERIAL


Attribute 5069-SERIAL
• Generic ASCII
Operating modes • Modbus RTU
• Modbus ASCII
• 2 full-duplex (RS-232, RS-422)
Inputs • 2 half-duplex (RS-485)
• 3…25V DC regarding signal ground (SG) 0, Asserted, ON, Space, Active
Serial input voltage signal • -3…-25V DC regarding signal ground (SG) 1, Disasserted, OFF, Mark, Inactive
Voltage and current ratings
MOD Power 100 mA @ 18…32V DC
MOD Power Passthrough, max 9.55 A @ 18…32V DC(3)
SA Power Passthrough, max
9.95 A @ 0…32V DC(4)
The module does not draw SA Power current.
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 2.8 W
Thermal dissipation, max 9.6 BTU/hr
250V (continuous), Basic Insulation Type, SA and MOD Power to Backplane
250V (continuous), Basic Insulation Type, Backplane to Communication Channels
250V (continuous), Basic Insulation Type, Backplane to Chassis Ground
250V (continuous), Basic Insulation Type, Between Communication Channels
250V (continuous), Basic Insulation Type, SA to MOD Power
Isolation voltage
250V (continuous), Basic Insulation Type, Communication Channels to Chassis Ground
250V (continuous), Basic Insulation Type, SA and MOD Power to Chassis Ground
250V (continuous), Reinforced Insulation Type, SA and MOD Power to Communication Channels
Basic Insulation Type tested at 2100V DC for 60 s
Reinforced Insulation Type tested at 4200V DC for 60 s
Transmit transaction ID 0…255
RTS/CTS hardware handshake always enabled.
Handshaking
RTS/CTS can be controlled by the user.
Module keying None
1 green/red module status indicator
Indicators
1 transmit data (TXD) and 1 receive data (RXD) yellow/red status indicator per channel
Slot width 1
Dimensions (HxWxD), approx 137.85 x 22 x 105.42 mm (5.43 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
RTB keying None
Serial port connectors Two DB-9 male with pins
2 - power ports
Wire category(1)(2)
2 - communication ports
Weight, approx 175 g (0.39 lb.)
Enclosure type None (open-style)

120 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-SERIAL


Attribute 5069-SERIAL
Corrosion resistance classification ISA S71.04 G2
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual
(3) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(4) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.

Environmental Specifications - 5069-SERIAL


Attribute 5069-SERIAL
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
0 °C < Ta < 60 °C (32 °F < Ta < 140 °F)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…185 °F)
Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on communication ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±2 kV line-earth (CM) on communication ports
Conducted RF immunity
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 121


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-SERIAL
Certifications(1) 5069-SERIAL
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM • EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4X Gc
• DEMKO15ATEX1484X
IECEx System, compliant with:
• IEC 60079-0; General Requirements
IECEx • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4X Gc
• IECEx UL 15.0055X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC • Article 58-2 of Radio Waves Act, Clause 3
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

122 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-FPD Field Potential Distributor


This figure shows wiring diagrams for the 5069-FPD field potential distributor connected to a discrete input device.

5069-FPD Wiring Diagrams

FIELD POWER FIELD POWER

DC Wiring AC Wiring
5069-FPD 5069-FPD

+ +
12/24V DC + 120/240V AC +
– –
– –
Ground Ground
Ground Ground

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 123


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-FPD


Attribute 5069-FPD
Voltage and current ratings
MOD Power Passthrough, max(1) 9.55 A @ 18…32V DC
10 mA @ 0…32V DC
SA Power 25 mA @ 0…240V AC, 47…63 Hz
ATEX/IECEX, 125V AC, max
9.99 A @ 0…32V DC
SA Power Passthrough, max(2) 9.975 A @ 0…240V AC, 47…63 Hz
ATEX/IECEX, 125V AC, max
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 4.0 W
Thermal dissipation, max 13.6 BTU/hr
250V (continuous), Basic Insulation Type
Isolation voltage
Type tested at 1500V AC for 60 s
Module keying None
Indicators 1 green module status indicator
Slot width 1
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
5069-RTB6-SCREW
RTB
5069-RTB6-SPRING
RTB torque (5069-RTB4-SCREW RTB only) 0.4 N•m (3.5 in•lb)
RTB keying None
(3)
Wire category 2 - on power ports
Wire size
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB6-SPRING connections diameter including insulation, single wire connection only.
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB6-SCREW connections diameter including insulation, single wire connection only.
Insulation stripping length
5069-RTB6-SPRING connections 10 mm (0.039 in.)
5069-RTB6-SCREW connections 12 mm (0.47 in.)
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

124 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-FPD


Attribute 5069-FPD
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
±4 kV @ 5 kHz on power ports
IEC 61000-4-4
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5
Conducted RF immunity
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 125


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-FPD
Certifications(1) 5069-FPD
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1455X
When used at or below 125V AC
IECEx System, compliant with:
• IEC 60079-0; General Requirements
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
IECEx • II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0007X
When used at or below 125V AC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

126 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-ARM Address Reserve Module


This figure shows the 5069-ARM module.

5069-ARM Module

ADDRESS RESERVE

5069-ARM

This figure shows a functional block diagram for the 5069-ARM module.

5069-ARM Functional Block Diagram

5
Module 24V DC 0
Status
Power 6
Indicators
Supply MOD 9
Power
B
Backplane a
Communication c
k
Backplane p
ASIC Nonvolatile l
Memory a
n
e

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 127


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-ARM


Attribute 5069-ARM
Voltage and current ratings
MOD Power 45 mA @ 18…32V DC
(1)
MOD Power Passthrough, max 9.55 A @ 18…32V DC
9.95 A @ 0…32V DC
SA Power Passthrough, max(2)
9.975 A @ 0…240V AC, 47…63 Hz
The module does not draw SA Power current.
ATEX/IECEX, 125V AC, max
Do not exceed 10 A MOD or SA Power (Passthrough) current draw
Power dissipation, max 1.0 W
Thermal dissipation, max 3.4 BTU/hr
Module keying None
Indicators 1 green/red module status indicator
Dimensions (HxWxD), approx 144.57 x 22 x 105.42 mm (5.69 x 0.87 x 4.15 in.)
Compatible zinc-plated chromate-passivated steel DIN rail.
DIN rail
You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail.
Weight, approx 175 g (0.39 lb)
Enclosure type None (open-style)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Level of MOD Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.
(2) Level of SA Power current that passes through the module depends on the system configuration, such as, module slot location and the other module types that are used in the system. For more information, see the
CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 5069-UM001, and EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, ENET-UM004.

Environmental Specifications - 5069-ARM


Attribute 5069-ARM
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock):
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating):

128 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-ARM


Attribute 5069-ARM
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC61000-4-2: 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
IEC61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Voltage variation
10 ms interruption on DC supply ports
IEC 61000-4-29:

Certifications - 5069-ARM
Certifications(1) 5069-ARM
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
CE • EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1455X
When used at or below 125V AC
IECEx System, compliant with:
• IEC 60079-0; General Requirements
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
IECEx • II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0007X
When used at or below 125V AC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 129


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-AENTR and 5069-AENTRK EtherNet/IP Adapters


This figure shows a wiring diagram for how to connect MOD power to the 5069-AENTR and 5069-AENTRK
EtherNet/IP adapters.

5069-AENTR and 5069-AENTRK Wiring Diagram - MOD Power (DC)

+
24V DC

+/L

–/N

Ground

Compact 5000™ I/O

This figure shows a wiring diagram for how to connect SA power (DC) to the 5069-AENTR and 5069-AENTRK
EtherNet/IP adapters.

5069-AENTR and 5069-AENTRK Wiring Diagram - SA Power (DC)

+/L
DC Power Source
–/N

Ground

Compact 5000™ I/O

130 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for how to connect SA power (AC) to the 5069-AENTR and 5069-AENTRK
EtherNet/IP adapters.

5069-AENTR and 5069-AENTRK - Wiring Diagram - SA Power (AC)

+/L
AC Power Source
–/N

Ground

Compact 5000™ I/O

Technical Specifications - 5069-AENTR and 5069-AENTRK


Attribute 5069-AENTR, 5069-AENTRK
Enclosure type rating None (open-style)
Voltage and current ratings
MOD Power 220 mA @ 18…32V DC
MOD Power inrush 1750 mA for 70 ms
(1)
MOD Power Passthrough, max 9.78 A @ 18…32V DC
5 mA @ 0…32V DC
SA Power 2 mA @ 0…240V AC, 47…63 Hz
ATEX/IECEx, 125V AC Max
9.95 A @ 0…32V DC
SA Power Passthrough, max(2) 9.975 A @ 0…240V AC, 47…63 Hz
ATEX/IECEx, 125V AC Max
Do not exceed 10 A current draw at the MOD or SA Power RTB.
MOD Power: 10…12A @ 22.5…43.2 A2t, Fast Acting
Recommended external overcurrent protection
SA Power: 20 A @ 250V AC
Power dissipation, max 8.5 W
Thermal dissipation, max 29 BTU/hr

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 131


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications - 5069-AENTR and 5069-AENTRK


Attribute 5069-AENTR, 5069-AENTRK
250V (continuous), Basic Insulation Type, SA, and MOD Power to Backplane
250V (continuous), Basic Insulation Type, SA to MOD Power
250V (continuous), Basic Insulation Type, Ethernet to Backplane
Type tested at 1500V AC for 60 s
Isolation voltage
250V (continuous), Double Insulation Type, Ethernet to MOD Power
250V (continuous), Double Insulation Type, Ethernet to SA Power
Type tested at 4242V DC for 60 s
No isolation between Ethernet ports
Module keying Electronic keying via programming software
Dimensions (HxWxD), approx 138 x 56 x 105 mm (5.43 x 2.20 x 4.15 in.)
We recommend that you order only the RTB type that your system requires. RTBs are available in separately ordered
5069 RTB kits. The following kits are available:
• Kit catalog number 5069-RTB5-SCREW kit contains two 5069-RTB5-SCREW RTBs.
RTB • Kit catalog number 5069-RTB5-SPRING kit contains two 5069-RTB5-SPRING RTBs.
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O EtherNet/IP adapters. We
recommend that you order only the RTB type that your system requires.
RTB torque (5069-RTB5-SCREW RTB only) 0.5…0.6 N•m (4.4…5.3 lb•in)
RTB keying None
2 - on signal ports
Wiring category(3), (4) 1 - on power ports
2 - on Ethernet ports
0.25…2.5 mm2 (22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.)
insulation m, single wire connection only.
Wire size Grounding: 2.5 mm2 (14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5mm (0.14in) max
diameter including insulation, single wire connection only.
Ethernet connections: Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2.
Insulation stripping length
5069-RTB5-SPRING connections 10 mm (0.39 in.)
5069-RTB5-SCREW connections 10 mm (0.39 in.)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Maximum level of MOD Power current that the adapter can pass through to the next module in the system.
(2) Maximum level of SA Power current that the adapter can pass through to the next module in the system.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(4) Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.

132 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications - 5069-AENTR, 5069-AENTRK


Attribute 5069-AENTR, 5069-AENTRK
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold), 0 °C < Ta < +60 °C
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry (+32 °F < Ta < +140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions CISPR 11/22, Class A
ESD immunity 6 kV contact discharges
IEC61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
IEC61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±3 kV @ 5 kHz on power ports
IEC 61000-4-4 ±3 kV @ 5 kHz on Ethernet ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on power and Ethernet ports
IEC 61000-4-6

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 133


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications - 5069-AENTR and 5069-AENTRK


Certifications(1) 5069-AENTR, 5069-AENTRK
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
AS/NZS CISPR 11; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
Ex • EN 60079-0; General Requirements
• II 3 G Ex nA IIC T4 Gc
• DEMKO 16 ATEX 1758X
IECEx System, compliant with:
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
IECEx • IEC 60079-0; General Requirements
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 16.0124X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

134 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

5069-AEN2TR EtherNet/IP Adapter


This figure shows a wiring diagram for how to connect MOD power to the 5069-AEN2TR EtherNet/IP adapter.

5069-AEN2TR Wiring Diagram - MOD Power (DC)

+
24V DC +

MOD Power
SA Power
Compact 5000™ I/O

This figure shows a wiring diagram for how to connect SA power (DC) to the 5069-AEN2TR EtherNet/IP adapter.

5069-AEN2TR Wiring Diagram - SA Power (DC) MOD Power


SA Power

+
DC Power Source +
Compact 5000™ I/O


Ground
Ground

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 135


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

This figure shows a wiring diagram for how to connect SA power (AC) to the 5069-AEN2TR EtherNet/IP adapter.

5069-AEN2TR - Wiring Diagram - SA Power (AC)

MOD Power
SA Power
+
AC Power Source +
Compact 5000™ I/O


Ground
Ground

Technical Specifications
Attribute 5069-AEN2TR
Enclosure type rating None (open-style)
Voltage and current ratings
MOD Power 450 mA @ 18…32V DC
MOD Power inrush 850 mA for 125 ms
MOD Power Passthrough, max(1) 9.55 A @ 18…32V DC
10 mA @ 0…32V DC
SA Power 25 mA @ 0…240V AC, 47…63 Hz
ATEX/IECEx, 125V AC Max
9.95 A @ 0…32V DC
9.975 A @ 0…240V AC, 47…63 Hz
SA Power Passthrough, max(2)
ATEX/IECEx, 125V AC Max
Do not exceed 10 A current draw at the MOD or SA Power RTB.
Recommended external overcurrent protection N/A
Power dissipation, max 8.5 W
Thermal dissipation, max 29 BTU/hr

136 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Technical Specifications
Attribute 5069-AEN2TR
250V (continuous), basic insulation type, SA, and MOD Power to backplane
250V (continuous), basic insulation type, SA to MOD Power
250V (continuous), basic insulation type, Ethernet to backplane
250V (continuous), double insulation type, Ethernet to MOD Power
250V (continuous), double insulation type, Ethernet to SA Power
Isolation voltage 50V (continuous), functional insulation type, Ethernet to USB
250V (continuous), basic insulation type, USB to backplane
250V (continuous), double insulation type, USB to MOD Power
250V (continuous), double insulation type, USB to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 s
Module keying Electronic keying via programming software
Dimensions (HxWxD), approx 138 x 98 x 137 mm (5.43 x 3.86 x 5.39 in.)
RTBs are available in separately ordered 5069 RTB kits. The MOD power connection uses a 4-point RTB, and the SA
power connection uses a 6-point RTBs. The following kits are available:
• Kit catalog number 5069-RTB64-SCREW contains RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW
RTB • Kit catalog number 5069-RTB64-SPRING contains RTB catalog numbers 5069-RTB6-SPRING and 5069-RTB4-SPRING
IMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O EtherNet/IP adapters. We
recommend that you order only the RTB type that your system requires.
RTB torque (5069-RTB4-SCREW and 5069-RTB6-SCREW 0.4 N•m (3.5 lb•in)
only)
RTB keying None
3 - on USB port
Wiring category(3) 2 - on power ports
2 - on Ethernet ports
Wire size
0.5...1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
5069-RTB4-SPRING, 5069-RTB6-SPRING diameter including insulation, single wire connection only
0.5...1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
5069-RTB4-SCREW, 5069-RTB6-SCREW diameter including insulation, single wire connection only
Ethernet connections Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2
Insulation stripping length
5069-RTB4-SPRING, 5069-RTB6-SPRING connections 10 mm (0.39 in.)
5069-RTB4-SCREW, 5069-RTB6-SCREW connections 12 mm (0.47 in.)
North American temp code T4
ATEX temp code T4
IECEx temp code T4
(1) Maximum level of MOD Power current that the adapter can pass through to the next module in the system.
(2) Maximum level of SA Power current that the adapter can pass through to the next module in the system.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 137


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Environmental Specifications
Attribute 5069-AEN2TR
Temperature, operating
IEC 60068-2-1 (Test Ab, Operating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry 0…60 °C (32…140 °F)
Heat),
IEC 60068-2-14 (Test Na, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F)
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
Relative humidity
5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
IEC61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity ±4 kV @ 5 kHz on power ports
IEC 61000-4-4 ±2 kV @ 5 kHz on Ethernet ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
IEC 61000-4-5 ±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on power and Ethernet ports
IEC 61000-4-6
Voltage variation
10 ms interruption on MOD Power port
IEC 61000-4-29

138 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Certifications
Certifications(1) 5069-AEN2TR
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM
EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements
Ex • II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1455X
When used at or below 125V AC
IECEx System, compliant with:
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• IEC 60079-0; General Requirements
IECEx • II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0007X
When used at or below 125V AC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC
Russian Customs Union TR CU 004/2011 LV Technical Regulation
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 139


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Minimum Spacing Requirements


There are minimum spacing requirements based on whether Compact 5000 I/O modules are installed in a
CompactLogix 5380 or Compact GuardLogix 5380 controller system or in a Compact 5000 I/O EtherNet/IP adapter
system.

Controller Minimum Spacing Requirements

The minimum distance between the controller system and enclosure walls, wireways, and adjacent equipment varies
based on current operating temperatures.

The minimum distances on all sides of the system are as follows:

• CompactLogix 5380 Controller


– 50.80 mm (2.00 in.) at 55 °C (131 °F)
– 101.60 mm (4.00 in) at 60 °C (140 °F)

• Compact GuardLogix 5380 Controller


– 50.80 mm (2.0 in.) at 50 °C (122 °F)
– 101.7 mm (4.00 in.) at 55 °C (131 °F)
– 152.4 mm (6.00 in) at 60 °C (140 °F)
End cap

Top
CompactLogix 5380 or
Compact GuardLogix

Compact 5000 I/O

Compact 5000 I/O


5380 Controller

Side Side

Bottom

For more information on how to install a CompactLogix 5380 or Compact GuardLogix 5380 controller system, see
these publications:

• CompactLogix 5380 Controllers Installation Instructions, publication 5069-IN013


• Compact GuardLogix 5380 SIL 2 Controllers Installation Instructions, publication 5069-IN014

140 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Adapter Minimum Spacing Requirements

The minimum distances on all sides of the adapter system are as follows:

• 25.40 mm (1.00 in) - If the system uses only Compact 5000 I/O standard modules.

• 50.80 mm (2.00 in) - If the system uses at least one Compact 5000 I/O safety module.

Horizontal Mounting Vertical Mounting


Only the 5069-AENTR adapter supports vertical mounting.

End cap End cap

Top
Top

Compact 5000 I/O


EtherNet/IP Adapter

EtherNet/IP Adapter
Compact 5000 I/O

Compact 5000 I/O

Compact 5000 I/O

Side Side
Compact 5000 I/O

Side Side Compact 5000 I/O

Bottom
Bottom

For more information on how to install a Compact 5000 I/O EtherNet/IP adapter system, see the Compact 5000 I/O
EtherNet/IP Adapters Installation Instructions, publication 5069-IN003.

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 141


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Additional Resources
These documents contain more information about related products from Rockwell Automation.

Resource Description
Compact 5000 I/O Digital Modules User Manual, Describes how to configure and operate Compact 5000 I/O digital modules.
publication 5069-UM004
Compact 5000 I/O Analog Modules User Manual, Describes how to configure and operate Compact 5000 I/O analog modules.
publication 5069-UM005
Compact 5000 I/O High-speed Counter Module User Describes how to configure and operate the Compact 5000 I/O high-speed counter module.
Manual, publication 5069-UM006
Compact 5000 I/O Serial Module User Manual, Describes how to configure and operate Compact 5000 serial modules.
publication 5069-UM003
CompactLogix 5380 and Compact GuardLogix 5380 Describes how to configure and operate CompactLogix 5380 and Compact GuardLogix 5380 controllers.
Controllers User Manual, publication 5069-UM001
Compact 5000 EtherNet/IP Adapters User Manual, Describes how to configure and operate the Compact 5000 I/O EtherNet/IP adapters.
publication 5069-UM007
Industrial Automation Wiring and Grounding Provides general guidelines for installing a Rockwell Automation industrial system.
Guidelines, publication 1770-4.1
Product Certifications website, http://
www.rockwellautomation.com/rockwellautomation/ Provides declarations of conformity, certificates, and other certification details.
certification/overview.page

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of


technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

142 Rockwell Automation Publication 5069-TD001H-EN-P - August 2019


Compact 5000 I/O Modules and EtherNet/IP Adapters Specifications

Notes:

Rockwell Automation Publication 5069-TD001H-EN-P - August 2019 143


Rockwell Automation Support
Use the following resources to access support information.

Knowledgebase Articles, How-to Videos, FAQs, Chat,


Technical Support Center www.rockwellautomation.com/knowledgebase
User Forums, and Product Notification Updates.
www.rockwellautomation.com/global/support/get-support-
Local Technical Support Phone Numbers Locate the phone number for your country. now.page
Find the Direct Dial Code for your product. Use the www.rockwellautomation.com/global/support/direct-
Direct Dial Codes code to route your call directly to a technical support dial.page
engineer.
Installation Instructions, Manuals, Brochures, and
Literature Library www.rockwellautomation.com/literature
Technical Data.

Product Compatibility and Download Center Get help determining how products interact, check
features and capabilities, and find associated www.rockwellautomation.com/global/support/pcdc.page
(PCDC) firmware.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/
documents/du/ra-du002_-en-e.pdf.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Allen-Bradley, Compact 5000, CompactLogix, GuardLogix, LISTEN. THINK. SOLVE, Logix 5000, Rockwell Automation, Rockwell Software, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.
CIP Sync and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication 5069-TD001H-EN-P - August 2019


Supersedes Publication 5069-TD001G-EN-P - June 2018 Copyright © 2019 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like