AEGIS Series for Process, Waste Water, Boiler and Cooling Tower Applications
Features
Inhibitor Feed Using PPM Setpoints MODBUS
Volumetric Timer Controls Industrial and Commercial Series
Relay Mirroring Plug and Play Upgrades
Optional Ethernet Communications Aquatrac Thermal Flow Switch
Aquatrac Instruments, Inc. • 1957 Cedar Street • Ontario, CA 91761 • (800)-909-9283 • www.aquatrac.com
AEGIS
AEGIS Series for Process, Waste Water, Boiler and Cooling Tower Applications
Rating—Detail Notes
Analog-Sensor I/O
Tower, Boiler, Condensate & Integral Default tower sensor includes 1GPM
Conductivity Sensor
Flowswitch sensors integral flowswitch
Fixed Temperature Thermal compensation for both pH and Con-
Displayed as o F, o C or o K
Sensor Input ductivity
Fixed 4-20mA Current Assignable to control any relay or variable
Single point calibration if 4mA=0
Loop input frequency control
4 max. 4-20mA Current DC isolated, Manual & Auto modes, Each optional current output uses a dual
Outputs Interlocking, Alarm sensor card slot
7 max. Manual-Inventory- Alarmed Delay prevents premature
track drop counts, inventory, tank level, ppm
ppm Inputs system alarms
Communications User Interface
5 key tactile feedback, universal
Keypad - LCD Scan rate 100 mS nominal
characters, 2 line, backlit
10Base T, TCP/IP Ethernet HTML, Micro Web Server with Static IP
LAN (optional) user definable IP address Browser shows controller in real time
Controls for ON/OFF & Variable Frequency
Feed a fixed volume for every
Sequential Volume Setpoints Meter only, fault tolerant feed controls
make-up volume
Blocking Any of 8 controls may block any other control Prevents incompatible concurrent controls
Up to 4 contact sets can be ‘AND’ed or Relays & Frequency controls OFF when
Interlocking
‘OR’ed contact set opens
Each control selectable
9 Biocide Event Controls Each of 9 controls includes 28 timed events
for 1,7 & 28 day cycles
System
Power 120 or 230VAC, 50/60 Hz Line voltage selectable
Fusing for 5 AC powered
5 Amps @ 120VAC or 2.5Amps @ 230VAC Alarm on open AC load fuse
loads
Relay 2-5 N.O. contacts snubbed @ 0.1uF,
Surge Suppression Varistor on AC line input
150 ohm
15-22VDC, Unregulated, Thermally Fused @
Accessory Power Auto-recovery on fault cleared.
50mA
7.5” W x 11.3” H x 5.5” D
Enclosure Non-metallic, NEMA4X
(190mm W x 287mm H x 140mm D)
Certifications
CSA: Pending CSA tested to comply with UL, (Pending)