TABLE D'ADRESSAGE Armoires de Clim VERTIV
TABLE D'ADRESSAGE Armoires de Clim VERTIV
Monitoring Manual
Product Documentation
English, code: 10012535 rev. 2021.02.19
INDEX
1. SCOPE 4
2. MONITORING PROTOCOLS 4
3. CONNECTIONS 5
ETHERNET CONNECTION ON ICOM3 MEDIUM 5
ETHERNET CONNECTION ON ICOM3 SMALL 5
4. MODBUS TCP/IP 6
INPUT STATUS 6
COILS 11
HOLDING AND INPUT REGISTERS 12
5. BACNET 24
BACNET IMPLEMENTATION 24
BINARY VALUES 25
ANALOG VALUES 31
MULTI STATE VALUES 36
INTEGER VALUES 42
6. SNMP 44
OID TABLE 44
7. FAQS 59
GENERAL FAQS 59
MODBUS RELATED FAQS 59
SNMP RELATED FAQS 59
BACNET RELATED FAQS 59
2. Monitoring Protocols
All the monitoring protocols provided are over IP through a dedicated Ethernet port, that is physically disconnected
from the rest of the other controller interfaces and communicating via serial RS485 protocol with the micro processor.
The web site is available at that address. At the first access the user is guided by a “First Boot Access” wizard that
forces the creation of the web user accounts.
The following standard monitoring protocols are made available together in parallel:
Modbus TCP/IP
- Port 502
- default address: 1
BACnet IP v1.14
- UDP Port 47808
- default address: 1
- default device name: NHES1
SNMP v2c
- UDP Port 161
- R/W community: “private”
- RO community: “public”.
The last column on every datapoints table reports the SW version from which the specific datapoint is made available.
Monitoring Port
Monitoring Port
Note: See the “Vertiv-iCOM3-MonitoringPort_Configuration-UM-EN-EMEA” manual for further info about how to
upload and activate a usable monitoring model into the Monitoring Port of an iCOM3 controller.
COILS
The following Boolean datapoints are available on:
- Coils Command 01
Segmentation Capability:
Able to transmit segmented messages Window Size: 16
Able to receive segmented messages Window Size: 16
Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security
GENERAL FAQS
Question / Issue Solution
1) Are the three monitoring protocols - Yes they are
available simultaneously?