WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION


CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD LEGEND
GENERAL NOTES
PARTIES WITHOUT EXPRESS AUTHORITY IS STRICTLY FORBIDDEN.
© ABB AG Calor Emag Medium Voltage Products
NON PRP LAN CAT6E 1. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE TECHNICAL SPECIFICATIONS FOR THE MV SCADA CONTROLS SYSTEM INCLUDED WITHIN ABB’S OFFER.
PRP LAN A CAT6E
2. THE EQUIPMENT MARKED WITH A * IS EXCLUDED FROM ABB’S SCOPE OF SUPPLY.
PRP LAN B CAT6E
3. THIS DRAWING SHOWS ONLY SERIAL AND ETHERNET-BASED COMMUNICATION. HARDWIRED CONTROL CABLING IS NOT EXHAUSTIVELY DEPICTED.
LAN A/B MM OPTICAL FIBER OM3
4. ALL IEDS INCLUDE LOCAL HMI NOT DEPICTED IN THIS DRAWING.
PRP A MM OPTICAL FIBER OM3
PRP B MM OPTICAL FIBER OM3

CONVENTIONAL COPPER CABLING

A A

MV SCADA Controls System Web Client


(max 3 concurrent)*

EMS (AF switchgear)*

NTP Time Server* BMS (Electracom)*

Ark Ethernet
Switches*

MV SCADA Wall-Mounted Operator HMI MV SCADA Wall-Mounted Operator HMI MV SCADA Cabinet A MV SCADA Cabinet B

SCADA HMI SCADA HMI SCADA HMI SCADA PLC Remote I/O SCADA HMI SCADA PLC Remote I/O
Client Client Server A Server A modules Server B Server B modules

Red Box Red Box

Ethernet Ethernet Ethernet Ethernet


Switch Switch Switch Switch
PRP LAN A PRP LAN B PRP LAN A PRP LAN B

B B

Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet
Local Controller and Local Controller and Local Controller and Local Controller and Local Controller and Local Controller and Local Controller and
Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch
Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED
PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B

Red Box Red Box Red Box Red Box Red Box Red Box
Red Box

Remote I/O G99 Ring Input Feeder Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Ring Output
Modules IED IED IED IED IED Modules IED IED IED Modules IED IED IED Modules IED IED IED Modules IED IED IED Modules IED IED IED Modules IED IED IED
Verwertung seines Inhaltes sind ohne ausdrückliche Zustimmung verboten.
Für dieses Dokument und den darin dargestellten Gegenstand behalten
wir uns alle Rechte vor. Vervielfältigung, Bekanntgabe an Dritte oder

Generator Generator Generator Generator Generator Generator


Power meter Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM Generator

C C
Controller* Controller* Controller* Controller* Controller* Controller* Power meter SWICOM
© A B B A G Ca lo r E m a g M i t t e l s p an n un g s pr o d u k t e

Controller*

GCP* Generator Switchgear EC1-GEN-HV-C01 GCP* Generator Switchgear EC1-GEN-HV-001 GCP* Generator Switchgear EC1-GEN-HV-002 GCP* Generator Switchgear EC1-GEN-HV-003 GCP* Generator Switchgear EC1-GEN-HV-004 GCP* Generator Switchgear EC1-GEN-HV-005 GCP* Generator Switchgear EC1-GEN-HV-006

Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet
Local Controller and Local Controller and Local Controller and Local Controller and Local Controller and Local Controller and Local Controller and
Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch Switch
Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED Gen Incomer IED
PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B PRP LAN A PRP LAN B

Red Box Red Box Red Box Red Box Red Box Red Box Red Box

Remote I/O G99 Ring Input Feeder Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Feeder Ring Output Remote I/O Ring Input Feeder Ring Output Remote I/O Ring Input Feeder Feeder Ring Output Remote I/O Ring Input Feeder Ring Output
Modules IED IED IED IED IED Modules IED IED IED Modules IED IED IED Modules IED IED IED IED Modules IED IED IED Modules IED IED IED IED Modules IED IED IED

Generator Generator Generator Generator Generator Generator Generator


Power meter Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM Power meter SWICOM
Controller* Controller* Controller* Controller* Controller* Controller* Controller*

GCP* Generator Switchgear EC1-GEN-HV-C02 GCP* Generator Switchgear EC1-GEN-HV-012 GCP* Generator Switchgear EC1-GEN-HV-011 GCP* Generator Switchgear EC1-GEN-HV-010 GCP* Generator Switchgear EC1-GEN-HV-009 GCP* Generator Switchgear EC1-GEN-HV-008 GCP* Generator Switchgear EC1-GEN-HV-007

D D

Erstellt / Prepared 2022-02-03 Greenwood ARK DATA CENTRES AG Zust. St./Resp. Dept.
MV SCADA CONTROLS SYSTEM =
Geprüft / Checked 0 + A3
Calor Emag
Freigegeben / Approved 0
UNION PARK Mittelspannungsprodukte
ELDS-GSD NETWORK ARCHITECTURE Offerte-Nr./Offer No. Unterlagen-Nr./Doc.-No. Visio Bl.-Nr./ Anz. Bl./

Änd.Ind./Rev. 03 2022-02-03 Greenwood ENERGY CENTER 1 Massstab/Scale : --- Dok.-Art/Doc.kind : D 20-3897709


Sheet No.of sh.