Professional Documents
Culture Documents
Voltage Disturbance Com Power Engineering Medium Voltage Cable Construction
Voltage Disturbance Com Power Engineering Medium Voltage Cable Construction
Here is a picture of a 15kV class Medium Voltage Cable (High Voltage Cable) with the
outer jacket removed.
2. Conductor Shield
3. Insulation
4. Insulation Shield
5. Outer Shield
1) Conductor: The conductor carrying current could be copper or Aluminum and the
diameter of the cable varies by the load that the cable is designed to carry. The
conductor itself could be of many di몭erent types:
Solid
Stranded Compact Concentric Round is found to be commonly used for larger diameter
cables whereas for very small diameters, solid conductor is commonly used.
Compact Sector
The bene몭ts of stranded conductor is that it o몭ers improved 몭exibility. For similar
ampacity, a solid conductor will have smaller diameter compared to a stranded
conductor.
Conductor Shield
It should be noted here that the term ‘semiconducting material’ does not refer to silicon
based semiconductors. Rather the semiconducting material refers to material that is
‘somewhat conducting’. These are made by adding carbon to insulation materials like PE
or XLPE. See a closeup picture of semiconducting insulating layer towards the end of this
article.
Thermoplastic material loses their form upon subsequent heating, while thermoset
material tends to retain their form. This is because, once the wire is extruded on to wire,
it undergoes a chemical change known as vulcanization, cross-linking or curing. These
processes 몭x the physical property such that subsequent heating will not cause it to
melt, 몭ow or drip.
Example of thermoplastic material is PVC and thermoset example is XLPE insulation and
EPR. There are also variants of these insulation systems in the market. Tree retardant
XLPE is one such example.
1. Polyethylene
In the earlier part of 20th century paper insulated cables (PILC) were common before the
advent of polymer-insulated cables. Some of those original cables are still in use! These
are known as PILC cables, which stands for Paper Insulated Lead Covered are not very
common currently. They are required sometimes where it is necessary to splice in to
existing PILC cables system and some manufacturers do still o몭er them.
Dissipation Factor: Ratio of resistive to capacitive current drawn by cable. This is also
known as loss angle, loss tangent.
Additional consideration on selecting insulation is the ground fault clearing time, based
on which 100%, 133% or 173% insulation may be selected.
100% Insulation: Applications in which ground faults will be cleared in less than 1 minute.
133% Insulation: Applications in which ground faults will be cleared in less than 1 hour.
173% Insulation: Applications in which ground faults clearing time is in몭nite. This usually
is used in industries where orderly shutdown of equipment is necessary to protect
equipment or personnel. The shutdown process could take an inde몭nite amount of time
and hence the insulation will be subjected to additional stress over a long period of time.
The selection of 100%, 133% or 173% insulation will progressively result in larger diameter
cable for a given conductor size. 133% insulation is often preferred insulation system for
15kV and above voltages even for systems with ground fault protection that could clear
in less than a minute. Probably this is done as an assurance or designing on the
conservative side.
It should be noted here that the term ‘semiconducting material’ does not refer to silicon
based semiconductors. Rather the semiconducting material refers to material that is
‘somewhat conducting’. These are made by adding carbon to insulation materials like PE
or XLPE.
5) Outer Shield: This is a metallic wire or tape covering over the insulation shield. The
outer shield will carry the capacitive leakage current and sometimes the fault current
itself to the ground. Grounding the shield also results in symmetrical electric 몭eld
distribution within the insulation resulting in better stress distribution. By grounding the
outer metallic shield (which could be tape or wire) the potential of the outer surface of
the cable is referenced to ground. This will prevent any dangerous touch voltage
accumulating on the high voltage cable.
A concentric neutral cable is produced using a would wire over the insulation in lieu of a
tape shield. The wire would o몭er all the bene몭ts of a shield plus it will be rated to carry
the neutral current. Additional discussion on concentric cable is at the end of this article.
It should be noted that there are two methods of grounding the outer shield:
The purpose of shield as mentioned in section 5 above is to have the electric 몭eld stress
evenly distributed within the insulation. When a conductor in a cable is energized,
electric 몭eld originates from the conductor to the grounded surface. For an unshielded
cable touching a grounded surface at one point, the electric 몭eld will be ‘crowded’ at the
interface between the conductor and the ground. Or stated otherwise, the insulation will
be stressed more between the conductor and the ground.
Electric 몭eld overstress on insulation due to unshielded power cable touching a grounded surface.
In a shielded cable, the shield is typically grounded. The electric 몭eld lines originate at
the conductor and will spread out evenly from the conductor through the insulation to
the shield ground. The electric 몭eld stress is hence distributed ‘evenly’ around the
circumference of the cable rather than ‘crowded’ in the case of non-shielded cable. This
will reduce electric 몭eld stress on the cable and helps prolong its life.
Electric 몭eld is evenly distributed within insulation for shielded power cable touching a grounded surface. The shield itself
will be grounded.
15kV cable with conductor shield and insulation shield (outer shield and jacket are removed)
Terminating the shielded power cable requires special consideration and is not
straightforward as terminating non-shielded cable. At the point of termination, the outer
shield will have to be stripped back and this will cause insulation to be over stressed at
the termination due to electric 몭eld that becomes ‘crowded’ at the interface. Suitable
stress relieving termination (Stress cones) will have to be applied at the termination to
avoid premature cable failure.
The neutral is usually wound helically around the insulation shield and is expected to
carry the full neutral return current. For single phase utility cables, the neutrals are
usually full size meaning the cross section of the helically wound neutral is the same as
the center phase conductor.
Concentric neutral cables are extensively used in utility residential feeder applications-
majority with full neutral wires and also for feeding commercial and industrial customers
majority with full neutral wires and also for feeding commercial and industrial customers
though to a limited extent.
As the outer jacket deteriorates, the neutral wires could come in contact with earth and
this has been one of the reasons behind stray voltage issues encountered in many areas
using underground concentric neutral cables.
PREVIOUS NEXT
“To invent, you need a good imagination and a pile of junk.” – Thomas A. Edison About Us | Disclaimer | Contact Us