Industrial Refrigeration
Ammonia and CO2 Applications
Content Page
Introduction ................................................................................................................................................................................... 3
1.1 Refrigerants ............................................................................................................................................................................. 4
1.2 Refrigerant feed to the evaporator ............................................................................................................................................ 6
1.3 One-stage systems ................................................................................................................................................................... 8
1.4 Two-stage/multistage systems .................................................................................................................................................. 9
1.5 Cascade systems .................................................................................................................................................................... 12
1.6 Transcritical systems .............................................................................................................................................................. 13
Compressor controls ..................................................................................................................................................................... 18
2.1 Reverse flow control ............................................................................................................................................................... 19
2.2 Suction pressure control ......................................................................................................................................................... 20
2.3 Compressor capacity control ................................................................................................................................................... 21
2.4 Discharge Temperature Control with Liquid Injection ................................................................................................................ 24
2.5 Economizer damper ................................................................................................................................................................ 26
2.6 Summary ............................................................................................................................................................................... 27
Condenser controls ....................................................................................................................................................................... 28
3.1 High-pressure float valve operation ......................................................................................................................................... 28
3.2 Low-pressure float valve operation .......................................................................................................................................... 29
3.3 Air-cooled condensers............................................................................................................................................................. 29
3.4 Evaporative condensers .......................................................................................................................................................... 33
3.5 Water-cooled condensers ........................................................................................................................................................ 36
3.6 Summary ............................................................................................................................................................................... 38
Liquid level regulation ................................................................................................................................................................... 39
4.1 High-pressure liquid level regulation system (HP LLRS) ............................................................................................................. 41
4.2 Low-pressure liquid level regulation system (LP LLRS) .............................................................................................................. 47
4.3 Summary ............................................................................................................................................................................... 52
Evaporator controls ...................................................................................................................................................................... 53
5.1 Temperature controls ............................................................................................................................................................. 54
5.2 Liquid supply control............................................................................................................................................................... 58
5.3 Injection with a solenoid valve (EVRA)..................................................................................................................................... 65
5.4 Injection with a pulse width modulation AKV(A) valve............................................................................................................... 65
5.5 Risers .................................................................................................................................................................................... 68
5.6 Defrost methods .................................................................................................................................................................... 73
5.7 Summary ............................................................................................................................................................................... 90
Oil systems .................................................................................................................................................................................. 92
6.1 Oil cooling controls ................................................................................................................................................................. 93
6.2 Oil differential pressure controls .............................................................................................................................................. 98
6.3 Oil recovery system .............................................................................................................................................................. 102
6.4 Summary ............................................................................................................................................................................. 106
Safety systems ........................................................................................................................................................................... 107
7.1 Pressure relief devices .......................................................................................................................................................... 107
7.2 Pressure and temperature limiting devices ............................................................................................................................. 110
7.3 Liquid level safety devices ..................................................................................................................................................... 111
7.4 Refrigerant detection ............................................................................................................................................................ 112
Refrigerant pump controls........................................................................................................................................................... 116
8.1 Pump protection with differential pressure control .................................................................................................................. 117
8.2 Pump bypass flow control ..................................................................................................................................................... 120
8.3 Pump pressure control .......................................................................................................................................................... 122
8.4 Summary ............................................................................................................................................................................. 123
Others ....................................................................................................................................................................................... 124
9.1 Filter driers in fluorinated systems ......................................................................................................................................... 124
9.2 Water removal for CO2 systems ............................................................................................................................................ 126
9.3 Water removal for ammonia systems ..................................................................................................................................... 128
9.4 Air purging systems .............................................................................................................................................................. 130
9.5 Heat recovery systems.......................................................................................................................................................... 135
Using CO2 in refrigeration systems ............................................................................................................................................ 136
10.1 CO2 as a refrigerant ........................................................................................................................................................... 137
10.2 Comparision of line sizings in CO2 systems........................................................................................................................... 138
10.3 -Subcritical CO2 systems ..................................................................................................................................................... 145
10.4 Special considerations for CO2 refrigeration systems............................................................................................................. 153
10.5 Conclusion ......................................................................................................................................................................... 157
10.6 Safety and gas detection ..................................................................................................................................................... 159
10.7 Gas detection ..................................................................................................................................................................... 159
10.8 Pressure control CO2 systems ............................................................................................................................................. 161
10.9 Cascade system controls ..................................................................................................................................................... 163
10.10 Control methods for hot gas defrosting .............................................................................................................................. 164
10.11 Oil in CO2 systems ............................................................................................................................................................ 171
10.12 Water in CO2 Systems....................................................................................................................................................... 174
Transcritical CO2 systems ......................................................................................................................................................... 179
11.1 Explanation of the transcritical cycle. ................................................................................................................................... 179
11.2 Typical CO2 transcritical system types.................................................................................................................................. 184
11.3 CO2 in Industrial refrigeration ............................................................................................................................................. 190
11.4 Industrial CO2 transcritical systems. .................................................................................................................................... 193
11.5 Defrosting of industrial pump-circulated transcritical systems ................................................................................................ 209
11.6 Oil management ................................................................................................................................................................. 211
11.7 Oil return ........................................................................................................................................................................... 212
11.8 Heat recovery ..................................................................................................................................................................... 217
11.9 Design pressure and safety ................................................................................................................................................. 223
Heat exchangers ...................................................................................................................................................................... 225
12.1 Heat transfer fundamentals ................................................................................................................................................. 230
12.2 Plate heat exchangers ......................................................................................................................................................... 237
12.3 Installation of heat exchangers ............................................................................................................................................ 242
Foreword:
www.danfoss.com\ir
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Introduction
The refrigeration systems and their applications de- the refrigerant to condense and release heat. When
scribed in this guide are all vapour compression re- the refrigerant is fully condensed, it is expanded to
frigeration systems. lower the pressure, the evaporation pressure, corre-
sponding to a saturation temperature that is low
Vapour compression refrigeration systems utilise the
enough for the refrigerant to absorb heat from the
heat absorbed or released in a phase change, the la-
cooled environment, thus evaporating, and the pro-
tent heat, of refrigerants. The boiling temperature
cesses repeat themselves.
changes with the pressure of the refrigerant.
To visualise the processes, a log(p)-h diagram is
The refrigerant is pressurised at different pressure
shown in Figure 1.1. The log(p)-h diagram shows the
levels, evaporation pressure levels and condensation
thermodynamic properties of a refrigerant. It is used
pressure levels, to absorb heat from the heat source
for representing refrigeration cycles by plotting in
(cold room) and release heat to the heat sink (ambi-
state points from the refrigeration cycle. It can also
ent), thus the refrigerant acts as a heat transport
be used for reading values for the state points in a
media. The refrigerant is evaporated and absorbs
refrigeration cycle. The log(p)-h diagram has been
heat from the environment that is to be cooled.
created with the Danfoss calculation tool Coolselec-
Once the refrigerant is evaporated, it is compressed
tor2.
to a higher pressure level, where the saturation tem-
perature is higher than the ambient temperature for
A simple one-stage ammonia refrigeration cycle is (1)) and the condensation ((2) to (3)). The area to the
shown in the log(p)-h diagram above. In this exam- left of the bell shape is the liquid phase, while the
ple, the evaporation temperature is -10°C and the area to the right of the bell shape is the vapour/gas
condensation temperature is 35°C. phase. In the gas phase, the pressure is increased
from (1) to (2) - this is the vapour compression. From
The bell shape seen in the diagram is the two-phase
(3) to (4), the refrigerant liquid is expanded to the
area of the refrigeration and the horizontal lines in-
evaporation pressure level.
side the bell shape represent the evaporation ((4) to
1.1 Refrigerants
The refrigerant is the medium that transports energy Ammonia is toxic and flammable (in certain concen-
from the evaporator to the condenser. Different re- trations), so proper safety precautions must be
frigerants have different thermodynamic properties, taken when handling large amounts of ammonia.
such as latent heat, density, critical point etc. Differ-
1.1.2 Carbon dioxide (CO2) – R744
ent refrigerants also have different safety precau- CO2 is a non-toxic (in small concentrations), non-
tions, environmental impacts and regulations to be flammable substance that is present in the atmos-
taken into account when designing a refrigeration phere. CO2 has become more popular in recent years
system. as CFC refrigerants have been phased out, especially
The most common refrigerants used in industrial sys- in smaller systems and as a secondary refrigerant in
tems are: commercial applications.
Ammonia – R717 The challenges regarding CO2 are the high pressure
Carbon dioxide (CO2) – R744
for condensation/recuperating and the low critical
temperature, requiring transcritical operation with
Halocarbons – CFCs, HCFCs and HFCs
warm ambient temperatures. CO2 can be dangerous
Hydrocarbons – HCs when leaking, as it is not self-alarming like ammonia.
Safety systems, such as safety relief valves and gas Large concentrations of CO2 can cause dizziness and,
detectors are described in chapter 7. in the most extreme cases, death. The other side of
CO2’s high pressure is that it is very efficient at low
1.1.1 Ammonia - R717 temperatures, making it a good refrigerant for freez-
Ammonia is a natural refrigerant with the chemical
ing applications. However, CO2’s triple point at -
composition NH3. Ammonia is inexpensive, easy to
56.6°C/5.1 bar abs is the lower limit for its use.
manufacture and has a high amount of latent heat,
which is why it is a very commonly used refrigerant 1.1.3 Halocarbons – CFCs, HCFCs and HFCs
in industrial applications. At ambient conditions, Halocarbons are made by replacing one or more hy-
20°C and 1 atm, ammonia is lighter than air. Addi- drogen atoms with halogens in methane and ethane
tionally, ammonia has no ozone depletion potential molecules.
(ODP) and no global warming potential (GWP). Three classes of these exists: CFCs (chlorofluorocar-
Ammonia’s operational area as a refrigerant ranges bons), HCFCs (hydrochlorofluorocarbons) and HFCs
from around -40°C of evaporation temperature and (hydrofluorocarbons). These refrigerant classes are
up. Ammonia is not compatible with copper, so steel known for:
components should be used. CFCs: All hydrogen atoms are substituted by either
chloride or fluoride, e.g. R11. These are very stable
compounds with a long lifetime. CFCs are non-toxic R134a can normally replace R12 in new and existing
and non-flammable refrigerants. However, these re- systems. Many new blends are entering the market
frigerants have been phased out because they con- at the present time though. However, due to the rel-
tribute to the breakdown of the ozone layers in the atively high GWP compared to natural refrigerants,
Earth’s stratosphere when they are leaked. there is a risk that these will be phased out in the fu-
ture.
HCFCs: At least one hydrogen atom is present in
these molecules, e.g. R22, which is used to replace 1.1.4 Hydrocarbons – HCs
R12. These components are less stable and have Hydrocarbons have become very common in domes-
shorter lifetimes, thus they are less harmful regard- tic refrigeration applications. Hydrocarbons are flam-
ing ozone layer depletion and global warming poten- mable and explosive, but in small systems the charge
tial. HCFCs are being phased out by some countries. is typically too low to pose any risk, and these sys-
tems are typically hermetic. Isobutane - R600a is a
HFCs: These halocarbons do not contain either chlo- hydrocarbon refrigerant which is used in domestic
rine or bromine, e.g. R134a, and are therefore not applications. R290 – propane – is used in some larger
ozone depleting. However, they do still have a high chillers but is yet to be seen in large-scale industrial
GWP and are therefore on a phasedown. The prop- applications.
erties of R134a are close to R12, and therefore
One-stage or single-stage refrigeration systems are can be constructed and controlled in a number of
refrigeration systems where the compression from ways. A log(p)-h diagram for a one-stage system can
low pressure to high pressure is done in one stage. A be seen in Figure 1.1. The numbers shown in
one-stage refrigeration system with the most basic
Figure 1.4 corresponds to the numbers shown for
components is shown in
the state points in the log(p)-h diagram.
Figure 1.4.
Oil Cooler
1 Oil Separator 2
Compressor
Evaporator Condenser
4 Expansion valve 3
A two-stage or multistage refrigeration systems are compressors or results in other undesirable operat-
refrigeration systems with two or more stages of va- ing conditions. Additionally, the desire for another
pour compression. temperature level or efficiency considerations may
result in a two-stage system being chosen over a sin-
Industrial two-stage refrigeration systems usually
gle stage.
have inter-stage cooling between compression
stages to cool the discharge gas from the first com- It is therefore suitable to have two or more stages of
pression stage. compression to have the compressors operating at
their optimal compression ratio, and within their op-
By cooling the discharge gas from the low-pressure
eration limits.
compressor, excessively high discharge tempera-
tures from the high-pressure compressor are A system sketch of a two-stage refrigeration system
avoided. The cooling in the inter-stage cooler is sup- is shown in Figure 1.5. The figure is shown with an
plied by expanding some of the liquid refrigerant inter-stage cooler and economiser. An economiser
from the condenser to the intermediate pressure, like the one shown in the system diagram is used for
where some of it evaporates in the process of cool- subcooling the refrigerant after the condenser by by-
ing the LP compressor discharge gas. The gas mixed passing and flashing some refrigerant. The bypassed
from cooled LP compressor discharge gas, refriger- refrigerant is evaporated and fed to an economiser
ant flashed and refrigerant evaporated is passed to port in the high-pressure compressor which can in-
the HP compressor. crease the capacity and/or the efficiency of the sys-
tem. The LP compressor may also have an econo-
Two or more stages of vapour compression are used
miser, but it is not shown here.
when there is a large difference between the evapo-
rating and condensing temperature, which often re-
sults in compression ratios that are too high for the
Oil Cooler
LP Compressor
1 3 Oil Separator
2
HP Compressor
4
8 5
Expansion valve 7 Economizer
A log(p)-h diagram for the two-stage system is temperature from the high-pressure compression
shown in Figure 1.6. The numbering in Figure 1.5 fol- stage. If no inter-stage cooling was used, the line (1)
lows the numbering of the state points shown in the to (2) would be extended and end on the same hori-
log(p)-h diagram. It should be noted that the evapo- zontal level as (4), but shifted to the right, thus in-
ration temperature is -30°C and the condensation creasing the discharge temperature to around
temperature is kept at 35°C, as for the example for 160°C, which is not acceptable (primarily for oil con-
the one-stage system. It should be noted how the in- siderations).
ter-stage cooler helps to keep a low discharge gas
(4)
(5)
(7) (2)
(6) (3)
(8) (1)
In the above Log(P)-H diagram, the economiser is This is utilised with the economiser, which is a heat
not shown. The economiser port is a port in screw exchanger that further cools the liquid from the con-
compressors that allows access to the compression denser. To do this, a little of the condenser liquid
chamber after the suction port has closed. As such, if flow is flashed to a lower pressure/temperature,
a high enough pressure is applied to the economiser where it is evaporated to cool the remaining liquid.
port, an additional refrigerant flow can be added to That modifies the Log(P)-H diagram a little:
the compressor without affecting the suction flow.
Figure 1.7: Log(p)-h diagram for two-stage ammonia system with economizer on the high stage
Low-stage compression from (1) to (2), de-super- the remaining liquid from (7) to (9). It is noteworthy
heating in the inter-stage cooler from (2) to (3) and that the liquid flashed to the intermediate tempera-
initial high-stage compression from (3) to (4) is the ture is further to the left than it would have been
same as in the non-economized system. The dis- without the economizer, thus the enthalpy differ-
charge from the high-stage compressor (6) is con- ence from (10) to (3) is bigger and that increases the
densed from (6) to (7) as before. After the condenser compressor’s cooling capacity. The power consump-
(7), a small amount of refrigerant is flashed to a tion is increased as well, because there is an addi-
lower temperature (8), where it is evaporated and tional mass flow that needs to be compressed, but
added to the partially compressed suction gas of the the overall effect – depending on the operating con-
high-stage compressor. The resulting mixture is (5), ditions – is a higher cooling capacity and, usually, a
which is compressed together to the final discharge higher COP.
at (6). The evaporative capacity is used to sub-cool
A cascade system consists of two separate refrigera- A system diagram for a cascade system is shown in
tion circuits. The separate refrigeration circuits are Figure 1.8. The cascade system diagram is somewhat
connected by a heat exchanger, which acts as a con- similar to the two-stage system, where the inter-
denser for the low-temperature circuit and an evap- stage cooler is replaced by a cascade cooler, thus
orator for the high-temperature circuit. making two closed cycles. A cascade system is usu-
ally more complex than a two-stage system, but it
The refrigerants for the two circuits can be different
offers some benefits. CO2 is very efficient down to
and optimised for each circuit. For example, the re-
very low evaporating temperatures where ammo-
frigerant for the high-temperature circuit could be
nia‘s efficiency drops, while ammonia can condense
ammonia, and the refrigerant for the low-tempera-
at relatively low pressure against warm ambient
ture circuit could be CO2.
temperatures, where CO2 has to go transcritical
A CO2/ammonia system needs a smaller charge of where the efficiency drops. So, choosing CO2 in the
ammonia and proves to be more efficient in low- LP circuit and ammonia in the HP circuit allows for
temperature refrigeration than a similar two-stage the best of both worlds.
ammonia system.
Oil Cooler
LP Compressor
1 Oil Separator
2 5
HP Compressor
6
8
4
Expansion valve 3 Economizer
The properties of CO2 make it necessary to operate Above the critical point, the refrigerant is called a
the system in a different way. The ‘critical point’ – transcritical fluid. The transcritical fluid does not
the top of the bell-shaped two-phase area – is at condense, but rather displays a gradual change of
31°C / 72.8 bara. In areas/periods where the ambi- density as it is cooled. In a traditional condensing
ent temperature is low, CO2 can be operated with process, the condensing temperature defines the
condensing below the critical point. In that case the pressure, but in the transcritical fluid there is no
cycle is, in principle, the same as for other refriger- such connection. Thus, the gas cooling pressure
ants (different pressures and enthalpies), but if the (equal to compressor discharge pressure) needs to
ambient temperature is relatively high, it is no be controlled.
longer possible to condense in the traditional way.
Figure 1.9: Log(p)-h diagram for transcritical CO2 system
Evaporation takes place from (4) to (1) and controlled by the expansion device that expands to
compression from (1) to (2) as in other refrigeration (4). The actual pressure in the gas cooler is based on
systems. From (2) to (3) is the ‘gas cooling’ process an analysis of the cycle. Consider a case where the
that replaces the condensing process. Point (3) is gas cooler outlet is at 40°C, but different pressures
defined by the outlet temperature of the gas cooler are controlled. The corresponding cycles are as
– here set to 40°C – and the pressure that is shown below:
Figure 1.10: Log(p)-h diagram for a transcritical CO2 system at different gas cooler pressures
The cooling capacity of the system is the enthalpy amount of liquid – especially with DX operation of
difference between points (1) and (4) multiplied by the low-pressure evaporators – it is simply not possi-
the mass flow. The necessary compression power is ble to have an expansion valve serve both purposes
the enthalpy difference between points (2) and (1) at once.
(horizontally) multiplied by the mass flow. The COP
of the system is thus (H1-H4)/(H2-H1), which is inde-
pendent of the mass flow. It can be seen that if the
pressure is varied up (red) or down (blue), both the
cooling capacity and power consumption change.
Calculating the COP along the (red) temperature
curve, it can be found to have a maximum at a spe-
cific pressure, which for 40°C works out to be 102.4
bar. Mapping this maximum COP across different gas
cooler exit temperatures has resulted in a curve that
expresses the best pressure for a given gas cooler
exit temperature. This curve has been implemented
in the Danfoss EKC 326 controller.
The solution is to make an intermediate stop in the the evaporators as necessary, while the gas part is
form of a receiver. The transcritical fluid is flashed reduced in pressure and fed to the compressor’s suc-
from the gas cooler exit through the high-pressure tion line, thereby controlling the pressure in the re-
valve into the receiver. In the receiver, the gas and ceiver.
liquid part is separated, the liquid part is flashed to
4 2
Gas cooler
Receiver
6
1
TC 7
Figure 1.12: Log(p)-h diagram for a transcritical CO2 system with intermediate pressure receiver
This process can be optimised. The gas from the re- compressor to compress this gas to gas cooler pres-
ceiver is reduced in pressure to the compressor suc- sure with a higher efficiency due to the higher suc-
tion, however it is possible to take advantage of the tion pressure. This is called parallel compression.
higher pressure in the receiver to employ another
Figure 1.13: Transcritical CO2 system with parallel compression
4 2
Gas cooler
Receiver
6
1
TC 7
Figure 1.14: log(P)-h diagram for a transcritical CO2 system with parallel compression
One further optimisation for CO2 transcritical sys- ent ways of employing this is to lift part of the suc-
tems is the use of ejectors. Ejectors utilise the power tion gas from the low-stage compressor to the suc-
in the expansion from gas cooler pressure to lift a tion of the parallel compressor, resulting in an effi-
gas flow to a higher pressure. One of several differ- ciency gain.
Figure 1.15: Transcritical CO2 system with parallel compression and gas ejectors
4 2
Gas cooler
Receiver
6
1
TC 7
Compressor controls
Oil Cooler
Oil Separator
Compressor
Evaporator Condenser
Expansion valve
The compressor is the “heart” of the refrigeration If the compressor capacity is greater than the de-
system. It has two basic functions: mand, the evaporating pressure and temperature
will be lower than that required, and vice versa.
Maintain the pressure in the evaporator so that the
liquid refrigerant can evaporate at the required tem- Additionally, the compressor should not be allowed
perature. to operate outside of the approved operation enve-
lope for the mechanical safety of the compressor
Compress the refrigerant so that it can be con-
and operational safety of the entire system.
densed at a higher temperature.
Reverse flow and condensation of refrigerant during flow can cause reversed rotation and damage to the
stand-still from the condenser to the oil separator compressor bearings. To avoid this reverse flow, it is
and the compressor should be avoided at all times. necessary to install a check valve on the outlet of the
For piston compressors, reverse flow can result in oil separator.
liquid hammering. For screw compressors, reverse
RT 1A RT 5A SCA
To condenser
Compressor
ICFS
ICFE
ICFF
ICFO
ICF
The stop check valve SCA can function as a check Pressure switches RT 1A and RT 5A are shown in the
valve when the system is running and can also shut suction line and discharge line of the compressor. It
off the discharge line for service as a stop valve. This is important to have pressure switches to cut-out or
combined stop/check valve solution is easier to in- cut-in operation if the pressure fluctuates outside
stall and has lower flow resistance compared to a the operational range in the suction and discharge
normal stop valve plus check valve installation. line. Not all compressors are delivered with built-in
controls and safety switches, therefore the RT 1A
When selecting a stop check valve, it is important to:
and RT 5A are shown. The pressure switches are not
Select a valve according to the capacity and not the shown for all application examples, but they should
pipe size. always be present in the system. Often these
switches are part of the compressor package.
Consider both the nominal and part-load working
conditions. The velocity in the nominal condition For details on how to select valves, please refer to
should be close to the recommended value, while at the product catalogue and use the Danfoss software
the same time, the velocity in the part-load condi- tool Coolselector2 for sizing the valve according to
tion should be higher than the minimum recom- the system capacity.
mended velocity.
During start-up or after defrosting, the suction pres- piston reciprocating compressors, or bypass some
sure needs to be controlled, otherwise it may be too suction gas for screw compressors with slide valves,
high, and the compressor motor will be overloaded. etc.
The electric motor for the compressor may be dam- Control the suction pressure for reciprocating com-
aged by this overloading. pressors. By installing a back pressure-controlled
regulating valve in the suction line, which will not
There are two ways to overcome this problem:
open until the pressure in the suction line drops be-
Start the compressor at part load. The capacity con- low the set value, suction pressure can be kept un-
trol methods can be used to start the compressor at der a certain level.
part load, e.g. unload part of the pistons for multi-
SCA
CVC To condenser
Compressor
ICFS
ICFE
ICFF
ICFO
ICF
In order to control the suction pressure during start- ICS will not open until the downstream suction pres-
up, after defrosting, or in other cases when the suc- sure falls below the set value of the pilot valve (CVC).
tion pressure may be too high, the pilot-operated In this way, the high-pressure vapour in the suction
servo valve (ICS) with the back pressure controlled line can be released into the compressor gradually,
pilot valve (CVC) is installed in the suction line. The which ensures a manageable capacity for the com-
pressor motor.
Compressor
pack
SCA
EKC 331 SCA
To condenser
AKS 33
FIA
SCA
ICFS
ICFE
ICFF
ICFO
ICF
A step control solution for compressor capacity can signal from a pressure transmitter, e.g. Danfoss AKS
be achieved by using a step controller, e.g. Danfoss 33. Based on a neutral zone control, EKC 331 can
EKC 331. EKC 331 is a four-step controller with up to control a pack system with up to four equally sized
four relay outputs. It controls the loading/unloading compressor steps or, alternatively, two capacity-con-
of the compressors/pistons or the electric motor of trolled compressors (each with one unload valve).
the compressor according to the suction pressure
VLT
Controller M
AKS 33
FIA
From evaporator/
SVA SVA To oil separator
liquid separator
Compressor
The VLT frequency converter is controlled by a con- Frequency converter control offer the following ad-
troller module that adjusts the control signal to the vantages:
converter from an input signal from a pressure
Energy savings
transmitter, e.g. AKS 33. The controller module can
be either a Danfoss AK-CC or a PLC/OEM module. Improved control and product quality
The VLT frequency converter can also receive the Noise reduction
signal from the pressure transmitter and work with- Longer lifetime
out a separate controller.
Simplified installation
SCA
CVC To condenser
Compressor
Oil
ICS SVA Separator
FIA ICFS
ICFE
SVA
CVC
EVM
ICFF
ICFO
1 ICF
ICS SVA
SVA
Evaporator ICFS
ICFE
From receiver
SVA TEA
ICFF
ICFO
ICF
Hot gas bypass can be used in specific cases to com- Hot gas bypass is energy inefficient and should not
pensate for a suddenly reduced cooling load. Nor- be used as a primary solution to “control” the com-
mally in industrial refrigeration plants, the compres- pressor, but rather as a safety measure to avoid ex-
sors will be speed controlled or step controlled. cessively low suction pressure.
These controls can, however, be too slow in reacting
The pilot-operated servo valve ICS (1) with a CVC pi-
in cases where there is a sudden drop in cooling
lot valve is used to control the hot gas bypass flow
load. This sudden drop will initially cause the com-
according to the pressure on the suction line. The
pressor to decrease the suction pressure. Hot gas by-
CVC is a back-pressure controlled pilot valve which
pass can be used as a fast response to a sudden de-
opens the ICS (1) and increases the flow of hot gas
crease in cooling load, which will prevent the suction
when the suction pressure is below the set value. In
pressure from dropping too low. The hot gas is by-
this way, the suction pressure ahead of the compres-
passed to the evaporator until the compressor has
sor is kept constant, and thus the refrigeration ca-
ramped down to match the reduced cooling load.
pacity satisfies the actual cooling load.
Compressor manufacturers generally recommend There are several ways to reduce the discharge tem-
limiting the discharge temperature below a certain perature. One way is to install water-cooled heads in
value to prevent overheating of the compressor and reciprocating compressors. Another method is liquid
its parts, prolonging their life and preventing the injection, which involves liquid refrigerant from the
breakdown of oil at high temperatures. outlet of the condenser or receiver being injected
into the suction line, the intermediate cooler be-
Referring to the log p-h diagram in chapter 1, it can
tween compressors, or the side port of the screw
be seen that the discharge temperature may be high
compressor.
when:
the compressor runs with high pressure differential.
RT 107
Screw compressor
To oil
Separator
From evaporator/
SVA
liquid separator
FIA
ICFS
Oil injection
ICFE
SVA From
TEAT receiver
ICFF
ICFO
ICF
When the discharge temperature rises above the set thermostatic injection valve (TEAT) controls the in-
value of the thermostat RT 107, RT 107 will energize jected liquid flow according to the discharge temper-
the solenoid valve ICFE which will start liquid injec- ature, which prevents the discharge temperature
tion into the side port of the screw compressor. The from rising further.
To oil
Separator
From evaporator/ AKS 21
SVA
liquid separator
FIA EKC 361
ICAD
ICFS
ICAD Single component solution
ICFE
Oil injection SVA
ICM
SVA ICM
EVRA FIA
ICFO ICFF
ICF From
ICFS
receiver
An electronic solution for liquid injection control can The EKC 361 controls the ICAD actuator which ad-
be achieved with the motorized valve ICM. An AKS justs the opening degree of the ICM motor valve in
21 temperature sensor will register the discharge order to limit and maintain the required discharge
temperature and transmit the signal to the tempera- temperature.
ture controller EKC 361.
An economizer is used to increase system capacity Pulsations need to be dampened to avoid compo-
and efficiency. nent damage. Correct and well considered dimen-
sioning of economizer lines is necessary to reduce
However, pulsations from the compressor are trans-
pulsations. The Danfoss Eco-Damper combines three
ferred into the economizer line which damages com-
components into a high-impact solution which re-
ponents and leads to valve chattering. The pulsa-
duces pulsations significantly and ensures high oper-
tions will lead to increased maintenance costs and
ational reliability thanks to its solid design. The
downtime if they are not taken care of.
Danfoss Eco-Damper is based on the Danfoss ICV
platform.
CVP EVM
Screw compressor
Max 150 mm ICD Max 150 mm
ICC Max 150 mm ICS
Oil injection
From economizer
vessel
From evaporator/
SVA
liquid separator
FIA
The Danfoss Eco-damper solution consists of 3 com- The ICD Eco-damper comes with an integrated
ponents. The Eco-damper (ICD), the Eco-check valve strainer, and is applicable for ammonia systems,
(ICC) and a standard control valve, e.g. an ICS servo along with R134a and R407C systems.
valve with CVP, constant pressure pilot valve, and
The ICC Eco-check valve has a solid design and is fully
the EVM solenoid valve. The combination shown in
opening at low differential pressure to prevent oscil-
the application example can dampen the pulsations
lating movements. The ICC Eco-check valve is appli-
by up to 80% and prevent premature failure of econ-
cable for ammonia, CO2 and HFC systems.
omizer components and reduce system downtime.
The Eco-damper solution unit has a unique broad- For less severe or occasional pulsation issues, the ro-
band damping effect in the 100-500 Hz working bust Eco-check valve (ICC) and the control valve can
range. be used without an Eco-damper (ICD). Note! In this
case, the pulsations from the compressor eco-port
Support on pipe segments is essential to reduce the
will not be damped.
pulsations and thus reduce vibrations induced by the
pulsations. Therefore, each pipe segment between It is recommended to have a maximum pipe length
the components in the Eco-damper solution must be of 150 mm between the individual components and
fixed to a pipe support element which can absorb between the ICD and the economizer port in the
the pulsations. The tube on the Eco-damper (ICD) compressor.
must also be fixed to a pipe support element that
can absorb the pulsations.
2.6 Summary
Hot gas bypass using ICS Applicable to Fast response to sudden Should not be used as
and CVC compressors with fixed drops in cooling load. The primary compressor
PC
capacities. Used as safety hot gas can help the oil capacity control. Energy
measure against return from the inefficient.
excessively low suction evaporator.
pressure
Electronic solution for Applicable to systems Flexible and compact. Not applicable to
liquid injection control where the discharge Possible to monitor and flammable refrigerants.
TC
with EKC 361 and ICM/ICF temperatures may run control remotely. Injection of liquid
M too high. refrigerant may be
dangerous to the
compressor. Not as
efficient as intermediate
cooler.
Condenser controls
Oil Cooler
Oil Separator
Compressor
Evaporator Condenser
Expansion valve
In areas where there are large variations in ambient Condenser installation depends on the way injection
air temperatures and/or load conditions, it is neces- to the low-pressure side of the refrigeration system
sary to control the condensing pressure to prevent it is controlled. Note that the terms ‘high-pressure
from falling too low. Excessively low condensing pres- float valve operation’ and ‘low-pressure float valve
sures result in there being insufficient pressure dif- operation’ refer to the mode of operation, not spe-
ferential across the expansion device and the evapo- cifically the use of a float valve. Both operation
rator not being supplied with enough refrigerant. It modes can be achieved by using level
means that condenser capacity control is mainly switches/transmitters and a normal expansion valve.
used in the temperate climate zones and to a lesser
3.1 High-pressure float valve operation
degree in subtropical and tropical zones.
High-pressure float valve operation is expansion of
The basic idea of condensing capacity control is to
the liquid immediately after the condenser. Any vari-
control the condenser capacity when the ambient
ation in the charge volume due to variations in ca-
temperature is low, so that the condensing pressure
pacity must be handled at the low-pressure side, e.g.
is maintained above the minimum acceptable level
in a liquid separator. Since the flow after the expan-
and to keep the condensing pressure as low as possi-
sion valve is two-phase, it is not suitable for distribu-
ble for optimal efficiency. This condensing capacity
tion to more than one location and thus it is primar-
control is achieved either by regulating the flow of
ily used in systems with only one low-pressure sepa-
circulating air or water through the condenser, or by
rator, such as a chiller unit.
reducing the effective heat exchanger surface area.
High-pressure float valves are usually mounted im-
Different solutions can be designed for different
mediately after the condenser and, as such, pose no
types of condensers:
special problems with regard to condenser installa-
Air cooled condensers tion.
Evaporative condensers
3.2 Low-pressure float valve operation tion of the charge volume due to variations in capac-
ity must be handled on the high-pressure side, e.g. in
Low-pressure float valve operation controls the ex-
a receiver.
pansion of the condensed liquid to keep a given level
in one or more low-pressure separators. Any varia- To ensure proper functioning of a condenser in a
low-pressure float valve system, the installation
must be correct.
3.3 Air-cooled condensers Air-cooled condensers are used on industrial refrig-
eration systems where the relative air humidity is
An air-cooled condenser consists of tubes mounted
high. Air-cooled condenser application examples are
within a fin block. The condenser can be horizontal,
depicted below as low-pressure float valve opera-
vertical or V-shaped. The ambient air is drawn across
tion.
the heat exchanger surface with axial or centrifugal
fans. Controlling the condensing pressure for air-cooled
condensers can be achieved in the following ways:
Application Example 3.3.1: Air flow control of air-cooled condenser with step controller EKC 331
EKC 331
AKS 33
From SVA
discharge line Condenser
h
SVA
SFA SFA
SCA
SNV
DSV
Liquid trap
Receiver
LLG
SVA
EKC 331 is a four-step controller with up to four re- receiver with a liquid trap at the bottom will allow
lay outputs. It controls the switching of the fans ac- the build-up of liquid in the drop leg. The liquid col-
cording to the condensing pressure signal from a umn in the drop leg will provide a positive pressure
pressure transmitter AKS 33. to counter the pressure drop in the condenser. The
height of the drop leg must be larger than the pres-
Based on neutral zone control, EKC 331 can control
sure loss in the condenser, expressed in metres of
the condensing capacity so that the condensing pres-
liquid. In some installations, EKC 331T is used. In this
sure is maintained above the required minimum
case, the input signal could be from a PT 1000 tem-
level.
perature sensor, e.g. AKS 21. The temperature sen-
The bypass pipe (thin red line) where SVA is installed sor is usually installed in the outlet of the condenser.
is an equalizing pipe, which helps balance the pres-
Note! The EKC 331T + PT1000 temperature sensor
sure in the receiver with the inlet pressure of the
solution is not as accurate as the EKC 331 + pressure
condenser so that the liquid refrigerant in the con-
transmitter solution, because the condenser outlet
denser can be drained into the receiver.
temperature may not entirely reflect the actual con-
It is important to account for the pressure drop in densing pressure due to the liquid subcooling or the
the condenser when designing the piping from the presence of incondensable gasses in the refrigera-
condenser to the receiver. The pressure at the outlet tion system. If the subcooling is too low, flash gas
of the condenser can be lower than the pressure in may occur when the fans start.
the receiver, which will restrict the flow to the re-
ceiver. Using a drop leg between the condenser and
VLT
AKS
From
discharge line SVA
Condenser
h
SVA
SFA SFA
SCA
SNV
DSV
Liquid trap
Receiver
LLG
SVA
To expansion device
To oil cooler
The VLT frequency converter is controlled by the It is important to account for the pressure drop in
condensing pressure signal from a pressure transmit- the condenser when designing the piping from the
ter, e.g. Danfoss AKS 33, on the discharge line. The condenser to the receiver. The pressure at the outlet
VLT frequency converter adjusts the speed of the of the condenser can be lower than the pressure in
fans in the air-cooled condenser according to the sig- the receiver, which will restrict the flow to the re-
nal from the pressure transmitter. ceiver. Using a drop leg between the condenser and
receiver, with a liquid trap at the bottom, will allow
Frequency converter control offers the following ad-
the build-up of liquid in the drop leg. The liquid col-
vantages:
umn in the drop leg will provide a positive pressure
Energy savings to counter the pressure drop in the condenser. The
Improved control and product quality height of the drop leg must be greater than the pres-
sure loss in the condenser, expressed in metres of
Noise reduction
liquid.
Longer lifetime
Simplified installation
Application Example 3.3.3: Area control of air-cooled condenser (for cold climates)
CVP
ICS SVA
Condenser
CVPP
Suction
line h
Receiver
LLG
SVA
To oil cooler
To expansion device
This regulating solution maintains the pressure in It is important to account for the pressure drop in
the receiver at a sufficiently high level during low the condenser when designing the piping from the
ambient temperatures. condenser to the receiver. The pressure at the outlet
of the condenser can be lower than the pressure in
The ICS pilot-operated servo valve in the discharge
the receiver, which will restrict the flow to the re-
line opens when the discharge pressure reaches the
ceiver. Using a drop leg between the condenser and
set pressure on the CVP pilot valve and closes when
receiver, with a liquid trap at the bottom, will allow
the pressure drops below the set pressure of the
the build-up of liquid in the drop leg. The liquid col-
CVP pilot valve.
umn in the drop leg will provide a positive pressure
The ICS pilot-operated servo valve with the CVPP to counter the pressure drop in the condenser. The
constant differential pressure pilot in the pressure height of the drop leg must be greater than the pres-
equalization line (thin red line) maintains sufficient sure loss in the condenser, expressed in metres of
pressure in the receiver. liquid.
An evaporative condenser is a condenser cooled by the surface of the main heat exchanger pipes is re-
ambient air combined with water sprayed through duced.
orifices and air baffles in counterflow with the air.
This type reduces the water consumption considera-
The water evaporates, and the evaporation effect of
bly compared to a normal water-cooled condenser.
the water drops adds considerably to the condenser
Capacity control of an evaporative condenser can be
capacity, as the air is cooled to the ‘wet bulb’ tem-
achieved by either a two-speed fan or variable speed
perature.
control of the fan and, at very low ambient tempera-
Today’s evaporative condensers are enclosed in a ture conditions, switching off the water circulation
steel or plastic enclosure with axial or centrifugal pump.
fans at the bottom or at the top of the condenser.
The use of evaporative condensers is limited in areas
The heat exchanger surface in the wet air stream with high relative humidity. In cold surroundings
consists of steel pipes. (ambient temperatures < 0°C), frost damage preven-
tion must be carried out by removing the water in
Above the water spray orifices (in the dry air) it is
the evaporative condenser.
common to have a de-superheater made of steel
pipes with fins to reduce the discharge gas tempera- The applications shown in this section are depicted
ture before it reaches the heat exchanger in the wet as low-pressure float valve operated.
air stream. In this way, the build-up of limescale on
Application Example 3.4.1: Step control of evaporative condenser with pressure controller RT
RT 5A RT 5A
SCA
Water
SVA pump
Suction line
Compressor
Condenser h
SVA
SFA SFA
SCA
SNV
DSV
Liquid trap
Receiver
LLG
SVA
To expansion device
To oil cooler
This solution maintains the condensing pressure, as In extremely low ambient temperatures, when the
well as the pressure in the receiver at a sufficiently condensing pressure drops below the setting of RT
high level in low ambient temperatures. 5A after all the fans have been switched off, RT 5A
will stop the water pump.
When the inlet pressure of the condenser drops be-
low the setting of the pressure controller RT 5A, the When the pump is stopped, the condenser and the
controller will switch off the fan to decrease the con- water pipes should be drained to avoid scaling and
densing capacity. freezing.
Application Example 3.4.2: Step control of evaporative condenser with step controller EKC 331
EKC 331
AKS 33
SCA
SVA Water
pump
Suction line
Compressor
Condenser h
SVA
SFA SFA
SCA
SNV
DSV
Liquid trap
Receiver
LLG
SVA
To expansion device
To oil cooler
This solution works in the same way as Application EKC 331T version can accept a signal from a PT 1000
Example 3.4.1, but operated via step controller EKC temperature sensor, which may be necessary for
331. secondary systems.
In the past, the water-cooled condenser was typi- Control of the condensing pressure can be achieved
cally a shell and tube heat exchanger, but today it is using a pressure-controlled water valve, or a motor-
very often a plate heat exchanger in a modern de- ized water valve controlled by an electronic control-
sign. ler to control the flow of the cooling water according
to the condensing pressure.
Water-cooled condensers with open water loops are
not commonly used, because in many places it is not The applications shown in the following section are
permitted to use the large amount of water these depicted as high-pressure float valve operation.
types consume (water shortage and/or high prices Thus, no receiver is shown in the following applica-
for water). However, such restrictions usually do not tions.
apply in maritime applications.
Application Example 3.5.1: Water flow control of water-cooled condensers with a water valve
SFA SFA
SNV DSV
Cooling water out
SCA
SVA
Suction line
Compressor WVS
This solution maintains the condensing pressure at a The condenser is shown as a Danfoss semi-welded
constant level. The refrigerant condensing pressure plate heat exchanger.
is directed through a capillary tube to the top of the
water valve WVS and adjusts the opening of WVS ac-
cordingly. The water valve (WVS) is a P-regulator.
Application Example 3.5.2: Water flow control of water-cooled condenser with a motor valve
Controller
AMV 20
SFA SFA
SNV
AKS 33 DSV
SCA
SVA Cooling water out
VM2
Suction line
Compressor
The controller receives the condensing pressure sig- VM 2 and VFG 2 are motor valves designed for dis-
nal from the pressure transmitter AKS 33 and sends trict heating and can also be used for water flow
out a corresponding modulating signal to actuator control in refrigeration plants.
AMV 20 of the motor valve VM 2. In this way, the
Alternatively, an AB-QM pressure-independent bal-
flow of cooling water is adjusted, and the condens-
ancing and control valve can be used. The AB-QM
ing pressure is kept constant.
valve consists of 2 functions: a differential pressure
In this solution, PI or PID control can be configured in controller and a control valve. The differential pres-
the controller. sure controller maintains a constant differential
pressure across the control valve, while the control
valve adjusts the flow through the valve.
3.6 Summary
Receiver
Fan speed control of air- Applicable to all Low start-up current Very low ambient
cooled condensers. condensers with the Energy savings temperatures.
PT
PC
Liquid flow control with a PT Chillers, heat recovery It is easy to capacity This type of installation is
motior valve Water out condensers control the condenser more expensive than a
Compressor
M
and the heat recovery. normal set up.
Condenser Water in Possible to control Not applicable when
remotely. water availability is a
problem.
Liquid level regulation High-pressure liquid level regulation systems are typ-
Liquid level regulation is an important element in the ically characterized by:
design of industrial refrigeration systems. It controls The sensing device (sensor/float) is placed on the
the liquid injection to maintain a constant liquid high-pressure side of the system.
level. An increase in liquid level will open the expansion de-
vice and pass high-pressure liquid to the low-pres-
Two main different principles may be used when de- sure side of the system, e.g. the regulation attempts
signing a liquid level regulation system: to keep the high-pressure side level constant.
LP seperator
Expansion
valve
HP Receiver
Evaporator Condenser
LP seperator
Expansion
valve
HP Receiver
Evaporator Condenser
When designing a HP LLRS, the following points must evaporator or the liquid separator, causing liquid
be taken into consideration: carryover into the compressor, as well as liquid ham-
mering. If the system is undercharged, the evapora-
As soon as liquid is “formed” in the condenser/con-
tor will be starved. The size of the low-pressure ves-
denser outlet, the liquid is fed to the low-pressure
sel (liquid separator/evaporator) must be carefully
side (the evaporator).
designed so that it can accommodate the refrigerant
The liquid leaving the condenser will have little or no in all conditions without causing liquid carryover.
sub-cooling. This is important to consider when the
For the reasons mentioned above, HP LLRS are espe-
liquid flows to the low-pressure side. If there is pres-
cially suitable for systems that require a small refrig-
sure loss in the piping or the components, flash-gas
erant charge, such as chiller units or small freezers.
may occur and cause the capacity of the expansion
Liquid chiller units usually do not need receivers,
device to be reduced.
however, if a receiver is necessary in order to install
If it is a critical charged system, the refrigerant a liquid sensing device and/or provide refrigerant to
charge must be precisely calculated in order to en- an oil cooler, the receiver (priority vessel) could be
sure that there is adequate refrigerant in the system. physically small.
SVA
From condenser
SFA
SVA
SNV SVA
Pressure equalization line DSV
SNV
SV1
Receiver
LLG
Priority for oi l
cooler
SNV
SVA SVA
To oil cooler
PMFH
SNV
On large HP LLRS, the SV1 or SV3 float valve is used signal to the PMFH main valve to open.The re-
as a pilot valve for a PMFH, main valve. As illustrated ceiver’s function here is to provide a more stable sig-
above, when the liquid level in the receiver rises nal for the SV1 float to work with.
above the set level, the SV1 float valve provides a
SVA
From condenser
AKS
SFA 4100
SVA SVA
SNV
Pressure equalization line DSV
SNV
Receiver
LLG EKE 347
Priority for oi l
cooler
SNV
SVA SVA
To oil cooler
ICAD
ICFS
ICM
To separator
ICFF
ICFS
ICF
The system illustrated is an AKS 4100/4100U level The liquid injection can be regulated in several dif-
transmitter which sends a level signal to an EKE 347 ferent ways:
liquid level controller. The ICM motor valve acts as
With a modulating motor valve type ICM with an
an expansion valve.
ICAD actuator (as shown in the application example
When designing an electronic LLRS solution, the liq- above).
uid level signal can be given either by an LLS
With a pulse-width-modulating expansion valve type
4000/AKS 38, which is a level switch (ON/OFF), or an
AKVA. The ICFA (in an ICF valve station)/AKVA valve
AKS 4100/4100U, which is a level transmitter (4-20
should be used only where the pulsation from the
mA).
valve is acceptable. Line size should be sized to the
The electronic signal is sent to an EKE 347 electronic full capacity of the ICFA/AKVA valve.
controller which controls the injection valve.
With a regulating valve REG acting as an expansion
valve and an ICS/EVRA solenoid valve to implement
ON/OFF regulation.
Application Example 4.1.3: Electronic solution for HP liquid level regulation with small/no HP receiver. Same
principle for other evaporative condensers or other condenser types.
Pressure
equalization line
AKS
4100
SVA
Cooling water in
EKE 347
PHE
Condenser
SNV
To receiver/
SVA
SVA expansion device
Application Example 4.1.4: Mechanical solution for HP liquid level regulation with HFI
SNV HFI
Cooling water in
PHE
Condenser
To separator
The HFI is a direct-acting high-pressure float valve; liquid from entering the float housing and thereby
therefore, no differential pressure is required to acti- prevent the HFI valve from opening.
vate the valve.
During standstill of the plant system, the pressure
If the condenser is a plate heat exchanger, the me- will slowly equalize, allowing the entire refrigerant
chanical float valve HFI can be mounted directly on charge to transfer to the coldest part of the system.
the heat exchanger header plate. (During wintertime, this can be the condenser).
It may be necessary to connect an equalization line If pressure equalization is not desired, a solenoid
to either the HP or LP side to remove refrigerant va- valve and/or check valve must be fitted.
pour from the float housing, as this may prevent the
To enable any liquid condensate to flow to the HFI If the HFI is installed close to the condenser and the
by gravity, the HFI must be installed underneath the pipe design allows vapour/gas to return freely and
condenser. easily to the condenser, then the bypass orifice
might not be needed/need to be in operation.
To ensure trouble-free operation, in most cases a by-
pass orifice must be installed. We generally recommend installing/preparing the
bypass orifice.
The by-pass orifice connects the gas space in the HFI
housing with the outlet connection of the HFI. Guidelines for size of by-pass orifice:
Application Example 4.1.5: Installation example for HFI fitted away from condenser with standard HFI hous-
ing:
By-pass orifice
(washer with hole) in HP liquid from
this line condenser
SNV
HFI
SVA
SNV
SVA
REG
Application Example 4.1.6: Installation example for HFI fitted away from condenser with HFI housing with
two extra connections:
SNV
HP liquid from
By-pass orifice condenser
(washer with hole) in
this line
SNV
HFI
SVA
For drain of
liquid in float
SVA
REG
SNV
To LP separator For manual operation/
expansion
When designing an LP LLRS, the following points The HP receiver must be large enough to accumulate
must be taken into consideration: the liquid refrigerant coming from the evaporators.
When the content of refrigerant in some evapora-
The liquid level in the low-pressure vessel (liquid
tors varies with the cooling load, some evaporators
separator/ shell-tube evaporator) is maintained at a
are shut off for service, or part of the evaporators
constant level. This is safe for the system, since an
are drained for defrosting.
excessively high liquid level in the liquid separator
may cause liquid carryover to the compressor, and As a result of the above, LP LLRS are especially suita-
an excessively low level may lead to cavitation of the ble for decentralised systems in which there are
refrigerant pumps in a pump circulation system. many evaporators, and there is a large refrigerant
charge, e.g. cold stores. With LP LLRS, these systems
Often, LLS 4000/AKS 38s are employed as high- and
can run safely even though it is impossible to pre-
low-level alarms, although when a level transmitter
cisely calculate the refrigerant charge.
is used, the low-level alarm is usually taken from the
level transmitter.
SNV
SVA
SVA
SVA
SVA
SVA SFA Suction line
SNV SVA
EVM SNV
Wet return line
DSV From
SVA
DAN FOSS
SVA receiver
SNV PMFL FIA
SVA
LLS 4000/
Liquid AKS 38 SV4
LLG separator
LLS 4000/
AKS 38
SVA
SNV
SVA
SVA
If the system capacity is large, the float valve SV4 is As illustrated above, when the liquid level in the liq-
used as a pilot valve for the PMFL main valve. uid separator falls below the set level, the float valve
SV4 provides a signal to the PMFL value to open.
SVA
Suction line
ICFS
SVA SFA
SNV ICM ICFE
EKE 347
AKS
Wet return line 4100
DSV SVA From
receiver
SNV
ICFO ICFF
LLS 4000/
Liquid AKS 38
SNV
SVA
SVA
The level transmitter AKS 4100/4100U monitors the The solenoid valve ICFE on the ICF valve station is
liquid level in the separator and sends a level signal being used as an additional solenoid valve to ensure
to the liquid level controller EKE 347, which sends a 100% closure during “off” cycles.
modulating signal to the ICAD actuator of the motor
The liquid level controller EKE 347 also provides re-
valve ICM on the ICF valve station. The ICM motor
lay outputs for upper and lower limits and for alarm
valve acts as an expansion valve.
levels. However, it is recommended that a level
switch LLS4000/AKS38 is fitted as a mechanical high-
level alarm.
EKE 347
SVA
Suction line
ICFS
SVA SFA
SNV ICFE
ICFA
AKS
Wet return line 4100
DSV SVA From
receiver
SNV
ICFO ICFF
LLS 4000/
Liquid AKS 38
ICFS
separator
LLG ICF
SNV
SVA
SVA
This solution is similar to the solution shown in Ap- The line should be sized to the full capacity of the
plication Example 4.2.3. However, with this example ICFA valve, or AKVA valve if serially connected.
the motor valve ICM is replaced by a pulse-width
The liquid level controller EKE 347 also provides re-
electronically operated expansion valve ICFA on the
lay outputs for upper and lower limits and for alarm
ICF valve station. The solenoid valve ICFE, which is
level. However, it is recommended that a level
also mounted on the ICF valve station, is being used
switch LLS4000/AKS38 be fitted as a mechanical
as an additional solenoid valve to ensure 100% clo-
high-level alarm.
sure during “off” cycles.
SVA
Suction line
ICFR ICFS
SVA SFA
SNV SVA ICFE
ICFO ICFF
LLS 4000/
Liquid AKS 38 ICF
ICFS
separator LLS 4000/
LLG AKS 38
LLS 4000/
AKS 38
SNV
SVA
SVA
4.3 Summary
Low-pressure liquid level regulation system (LP LLRS)– see section 4.2
Low-pressure mechanical Liquid
Applicable to small Purely mechanical. Limited capacity.
solution: SV4-6 separator systems Simple, low cost solution. Complicated to change
setpoint if not correct.
Low-pressure electronic LC
AKVA
Particularly applicable to Flexible and compact. Not permitted for
solution: AKS 4100 + EKE LT decentral systems like Possible to monitor and flammable refrigerants.
347 +AKVA cold storages. control remotely.
Liquid
separator
Covers a wide range of
capacities. Easy to install.
Low-pressure solution: LC
Particularly applicable to Simple. Just 40 mm for level
LLS 4000/AKS 38 decentral systems like Inexpensive. adjustment.
+ICFE+ICFR Liquid
cold storages. Very dependent on the
separator adjustment of the REG
valve. Not suitable for
systems with big capacity
fluctuations.
Complicated to change
setpoint if not correct.
Evaporator controls
Oil Cooler
Oil Separator
Compressor
Evaporator Condenser
Expansion valve
The evaporator is the part of the refrigeration sys- Liquid supply controls (Section 5.2): Describes meth-
tem where the effective heat is transferred from the ods for controlling liquid injection for a direct expan-
media you want to cool down (e.g. air, brine, or the sion (DX) evaporator and liquid supply for a pumped
product directly) to the refrigerant. circulation evaporator.
Therefore, the primary function of an evaporator Defrost Methods (Section 5.6): Briefly describes the
control system is to achieve the desired media tem- different methods for defrosting evaporators.
perature. Furthermore, the control system should
Hot Gas Defrosting Controls (Section 5.6.3): De-
also keep the evaporator operating efficiently and
scribes the steps of the hot gas defrost sequence
trouble-free at all times.
and general considerations. Hot gas defrosting appli-
Specifically, the following control methods may be cation examples are covered separately for DX evap-
necessary for evaporators: orators and pumped circulation evaporators, since
they differ, for example, in the draining methods.
Temperature controls (Section 5.1): Describes meth-
ods for controlling media temperature within tight
thresholds with high accuracy, as well as for operat-
ing evaporators at different temperature levels.
Application Example 5.1.1: Media temperature control using either pilot-operated valve or motor-operated
valve
Option 1 Option 2
ICAD
ICAD
CVP CVE
ICFO ICFF
ICFS
Serial solution
Application Example 5.1.1 shows a solution for accu- The servo valve (ICS) is controlled by the two serially
rate media temperature control. Furthermore, there connected pilot valves (CVE) in the S2 port, con-
is a need to protect the evaporator against an exces- trolled by a media temperature controller, e.g.
sively low pressure to prevent the products from Danfoss EKC 361, and CVP in the S1 port.
freezing up in the application.
The CVP is adjusted according to the lowest pressure
This design can be applied for DX or pumped liquid permitted for the application.
circulation evaporators with any type of defrost sys-
The functionality of the pilot-operated servo valve
tem.
solution (ICS) is described on the next page.
The media temperature controller will control the This solution will control the temperature with an
temperature in the application at the desired level accuracy of +/- 0.25°C. If the temperature falls below
by controlling the opening of the CVE pilot valve, and this range, the EKC controller can close the solenoid
thereby controlling the evaporating pressure to valve in the liquid line.
match the required cooling load and temperature.
The media temperature controller EKC 361 will con-
The second control option is the motor valve ICM, trol all functions of the evaporator, including ther-
where a media temperature controller controls the mostat and alarms.
opening degree of the ICM motor valve.
For more details, please refer to the manual of the
EKC 361 controller.
Application Example 5.1.2: Evaporator pressure control - changeover between two pressure levels
P: CVP
To liquid separator
ICS SVA
ICFO ICFF
ICFS
Serial solution
Application Example 5.1.2 shows a solution for con- CVP pilot in the S2 port. When the solenoid is de-en-
trolling two evaporating pressures in evaporators. ergized, the evaporator pressure will follow the set-
This solution can be used for DX or pumped liquid ting of the CVP pilot in the P port.
circulation evaporators with any type of defrost sys-
The Danfoss ICS pilot-operated servo valve solution
tem.
has options for being controlled by either 1 pilot or 3
The servo valve ICS is equipped with one EVM (NC) pilots. The 1-pilot system works by having a pilot
solenoid valve pilot in the S1 (serial 1) port and two valve to the opening of the servo valve based on the
CVP constant pressure pilots in ports S2 and P re- pilot’s set conditions. The 3-pilot system has two
spectively. lines of pilots, one line with 1 pilot (the parallel line)
and another line with 2 pilots serially connected (S1
The CVP in the S2 (serial 2) port is adjusted to the
and S2 ports). Having 2 pilots serially connected al-
lower operating pressure and the CVP in the P port is
lows more options to be set for the operation of the
adjusted to the higher operating pressure.
servo valve. The pilot in the parallel line (P port) can
When the solenoid in the S1 port is energized, the open the servo valve independently of the pilots in
evaporator pressure will follow the setting of the
ICS ICS
1 pilot 3 pilots
Example:
I II
Temperature 5K 6K
change
Liquid supply to the evaporator is controlled differ- For natural circulation, a liquid refrigerant is driven
ently depending on the system complexity, refriger- by gravity to the evaporator. Since the refrigerant
ant and application. flow is driven by gravity, and not a pump, special
consideration must be given to the distance from
There are 3 different liquid supplies to the evapora-
separator to evaporator and the height of risers in
tor: Direct expansion (DX), pump circulation and nat-
the return lines. The refrigerant is partially evapo-
ural circulation.
rated, like for the pump-circulated system, and re-
For direct expansion, high-pressure liquid refrigerant turned to the separator. Controls for natural circula-
is supplied to the evaporator through an expansion tion are similar to those for a pump-circulated sys-
valve. In the evaporator it is fully evaporated and su- tem, therefore they are covered in the section with
perheated to avoid liquid hammering in the com- pump-circulated controls.
pressor. The liquid supply is controlled by a super-
heat-controlled expansion valve.
Application Example 5.2.1: Direct expansion (DX) evaporator with thermostatic expansion
To suction line
SVA
Evaporator
From receiver
SVA TEA SVA
EVRA FIA
Application Example 5.2.1 shows a typical installa- This solution can also be applied to DX evaporators
tion for a DX evaporator without hot gas defrosting. with natural or electric defrost.
The liquid injection is controlled by the thermostatic Natural defrost is only possible if the cold room tem-
expansion valve, TEA, which maintains the refriger- perature is well above 0°C. It is achieved by stopping
ant superheat at the outlet of the evaporator at a the refrigerant flow to the evaporator, and keeping
constant level. TEA is designed for ammonia. the fans running. Electric defrost is achieved by stop-
Danfoss also supply thermostatic expansion valves ping the fans and the refrigerant flow to the evapo-
for fluorinated refrigerants. For CO2 DX systems, rator, and at the same time switching on an electric
electronic expansion valves should be used, such as heater inside the evaporator fin block.
an ICM motor valve.
Application Example 5.2.2: Direct expansion (DX) evaporator with electronic expansion by a motor valve
(ICM)
To suction line
SVA
ICFS
ICFE
Evaporator
From receiver
ICFO ICFF
ICFS
Application Example 5.2.2 shows a typical installa- in order to maintain the superheat at the optimum
tion for an electronically controlled DX evaporator level.
without hot gas defrost.
At the same time, the evaporator controller oper-
The ICF control solution is shown in the liquid supply ates as a digital thermostat which controls the
line, but the serial solution could be used instead. on/off switching of the solenoid valve, ICFE/EVRA,
The ICF will accommodate up to six different mod- depending on the media temperature signal from a
ules assembled in the same housing, offering a com- temperature sensor on the evaporator.
pact and easy-to-install control solution.
Compared with the solution in Application Example
The liquid injection is controlled by the motor valve, 5.2.1, this solution will constantly adapt the opening
ICM, which is controlled by an evaporator controller, degree of the injection valve to ensure maximum ca-
e.g. EKC 315A (not shown). The evaporator control- pacity and efficiency. Furthermore, this solution of-
ler will measure the superheat by means of a pres- fers more accurate control of media temperature.
sure transmitter and a temperature sensor on the
This solution can also be applied to DX evaporators
outlet of the evaporator. The evaporator controller
with natural or electric defrost.
controls the opening degree of the ICM motor valve
Application Example 5.2.3: Direct expansion (DX) evaporator with electronic expansion by a PWM AKVA valve
To suction line
SVA
ICFF
ICFS
Serial solution
SVA SVA
FIA
AKVA
Application Example 5.2.3 shows an installation for EKC 315A (not shown). The evaporator controller will
an electronically controlled DX evaporator without measure the superheat by means of a pressure
hot gas defrost. transmitter and a temperature sensor on the outlet
of the evaporator. The evaporator controller con-
This application example shows an ICF control solu-
trols the opening degree of the ICFA valve in order to
tion for an electronically controlled DX evaporator
maintain the superheat at the optimum level.
without hot gas defrost.
Compared with the solution in Application Example
The ICF control solution is shown in the liquid supply
5.2.1, this solution will constantly adapt the opening
line, but the serial solution could be used instead.
degree of the injection valve to ensure maximum ca-
The ICF can accommodate up to six different models
pacity and efficiency. Furthermore, this solution of-
in the same housing, offering a compact and easy-to-
fers more accurate control of media temperature.
install control solution.
This solution can also be applied to DX evaporators
The liquid injection is controlled by the pulse width
with natural or electric defrost.
modulation (PWM) electronic expansion valve, ICFA,
which is controlled by an evaporator controller, e.g.
The injected liquid at the correct temperature is AKV valves for both distribution control (orifice size)
and PWM temperature control.
pumped from a separator to the evaporators. When
liquid is needed, a solenoid valve in front of the
evaporator is opened. A manual regulating valve is
usually fitted after the solenoid valve to allow the re-
quired circulation rate to be set and hydraulic bal-
ance to be achieved in the system.
To separator
SVA
AKVA
Option 1
From separator
SVA REG SVA
EVRA FIA
Option 2
5.3 Injection with a solenoid valve (EVRA) 5.4 Injection with a pulse width modulation
AKV(A)
In a traditional flooded system, liquid injection is valve
controlled by a thermostat which constantly
Instead of injecting periodically, as described above,
measures the air temperature.
one can also constantly adapt the liquid injection to
The solenoid valve is opened for several minutes or the actual demand. This can be done by means of a
longer until the air temperature has reached the set- pulse-width-modulated (PWM) AKV(A) valve type
point. During injection, the mass of the refrigerant controlled by an AK-CC 450.
flow is constant.
The air temperature is constantly measured and
This is a very simple way to control the air tempera- compared to the reference temperature. When the
ture. However, the temperature fluctuation caused air temperature reaches the setpoint, the opening of
by the differential of the thermostat may cause un- the AKV(S) is reduced, giving it a smaller opening an-
wanted side effects in some applications, e.g. dehu- gle during a cycle, resulting in less capacity and vice
midification and inaccurate control. versa. The duration of a cycle is adjustable between
30 sec. and 900 sec.
differential affects the amplification of the regulator This approach to liquid injection in a flooded system
and can therefore not be set to less than 2K to en- is very versatile. The amount of injected liquid can
sure regulation stability. In a flooded system, this be precisely controlled.
means that the average refrigerant flow is constantly
A direct effect of this is a lower average surface tem-
controlled and adapted to the demand, with the cir-
perature of the air cooler, resulting in a smaller ΔT
culation rate decreasing when less refrigerant is in-
between the refrigerant and the air. This increases
jected.
the accuracy and the energy efficiency of the sys-
tem.
Application Example 5.4.1: Pumped liquid circulation evaporator with solenoid valve for liquid injection
To liquid separator
SVA
ICFO ICFF
ICFS
Serial solution
Application Example 5.4.1 shows a typical installa- The amount of liquid injected into the evaporator is
tion for a pumped liquid circulation evaporator with- controlled by the opening of the manual regulating
out hot gas defrost and can also be applied to valve, ICFR/REG. It is important to set this regulating
pumped liquid circulation evaporators with natural valve at the right opening degree. Too high an open-
or electric defrost. ing degree will lead to frequent operation of the so-
lenoid valve with resultant wear. Too low an opening
The media temperature is maintained at the desired
degree will starve the evaporator of liquid refriger-
level by a digital thermostat, e.g. EKC 202, which
ant.
controls the on/off switching of the solenoid valve,
EVRA, according to a media temperature signal from
a temperature sensor, e.g. AKS 21.
Application Example 5.4.2: Pumped liquid circulation evaporator with pulsed width modulated (PWM) AKV
valve for liquid injection
To liquid separator
SVA
ICFF
ICFS
Serial solution
SVA SVA
FIA
AKVA
Instead of injecting periodically, as described above, In a flooded system, this means that the average re-
one can also constantly adapt the liquid injection to frigerant flow is constantly controlled and adapted
the actual demand. This can be done with a PWM to demand.
AKVA valve or an ICF with an ICFA solenoid module.
This approach to liquid injection in a flooded system
The air temperature is constantly measured and is very versatile. The amount of injected liquid can
compared to the reference temperature with a digi- be precisely controlled, which increases the accuracy
tal thermostat, e.g. AK-CC 450. When the air temper- and the energy efficiency of the system.
ature reaches the setpoint, the AKVA valve opening
is reduced. This decreases the degree of opening
during the cycle, resulting in less capacity. The dura-
tion of a cycle is adjustable between 30 sec. and 900
sec.
5.5 Risers
Two-phase flow – a flow that is a mixture of vapour from flooded evaporators, which are evaporators
and liquid – presents some special problems with re- where more refrigerant is circulated than is evapo-
gard to the design of piping. Two-phase flow is usu- rated. The amount evaporated is proportional to the
ally in the return line
Not all valves are shown.
Not to be used for construction purposes
capacity of the heat exchanger and usually the situa- The flow pattern: The flow pattern describes how
tion is described with a capacity and a ‘circulation the two phases flow, mixed or separately. Depend-
rate’. ing on the composition (% of each phase) and overall
speed, the combined flow behaves very differently,
There are two key considerations for two-phase
and the pressure loss is a result of the combined be-
lines:
haviour.
The pressure loss: The pressure loss of a two-phase
The topic of flow pattern is very complex, so only a
flow is much higher than a single phase (vapour)
simple explanation will be given here. Looking at the
flow at the same speed, so the speed in two-phase
sketched flow patterns in horizontal pipes in Figure
lines is usually kept lower than in vapour-only lines.
5.5.1 below, it can generally be seen that from top
For low temperature applications, pressure loss pre-
to bottom and left to right there is an increasing
sents a large performance penalty, while for ther-
amount of vapour and with that a higher overall ve-
mosyphon (self-circulation) systems, the pressure
locity.
loss must be small to ensure proper circulation.
Note how a higher vapour speed disturbs the liquid to liquid falling and possibly inducing pressure fluc-
through friction on the surface, inducing waves that tuations, but transport of the liquid to the destina-
eventually reach the top of the pipe to enclose gas tion is almost guaranteed. With upward flow, how-
‘slugs’. Eventually the speed becomes so high that ever, the liquid transport is not guaranteed and that
the friction forces are stronger than the gravitational can give rise to problems in refrigeration systems.
forces, and the ‘annular’ flow pattern is reached. In
In Figure 5.5.2 below, a different flow pattern in up-
the annular flow, the liquid flows in a ‘film’ on the in-
wards flow is shown. The vapour speed generally in-
ner surface of the pipe with the high-speed vapour
creases from left to right. With very low velocity, the
flowing in the centre of the pipe.
pipe fills with liquid and the vapour bubbles through
In a horizontal pipe, any of these flow patterns are it. Increased velocity collects the vapour in larger
usually not a problem, provided the pressure loss is ‘slugs’ that, with a further increase, start to fill the
accounted for. It is common practice to install two- centre of the pipe. Once the slugs collect to form a
phase ‘horizontal’ lines with a small downward slope channel in the middle, the flow is said to be annular.
towards the destination to ensure that the liquid is The remarkable thing about annular flow is that the
safely transported to the destination. friction forces on the vapour/liquid surface can drag
the liquid on the pipe wall upwards, thereby provid-
In a vertical pipe, however, it is very different. Down-
ing an upward liquid transport.
ward flow presents its own problems, mainly relating
Since the amount of vapour is determined by the m/s2 = 0.19 bar. The pressure loss is most likely
evaporating capacity, it is not usually an option to in- somewhat lower since, because of the vapour bub-
crease vapour flow. However, the same vapour flow bles, the average density is lower than saturated liq-
can yield higher velocities in a smaller pipe and thus uid, though not much lower.
the Figure 5.5.2 above can be seen as the same va-
Reducing the pipe size increases the speed. Below in
pour flow with pipe size decreasing left to right.
Figure 5.5.3 is a Coolselector2 calculation of a 3m
Most technicians would intuitively think that a DN50 pipe with 100kW evaporator capacity at -10°C
higher velocity means greater pressure loss, but that R717, circulation rate 3. It is remarkable that the
is not the case with vertical upward two-phase flow. speed is relatively high at 14 m/s, but the pressure
loss is only 0.022 bar. The explanation is that the
In the ‘bubbly’ flow pattern, the liquid fills up most
pressure loss relates to (almost) pure gas running in
of the pipe from top to bottom before it starts to
a slightly smaller ‘pipe’ (the channel in the centre of
overflow the top. Thus, the pressure loss associated
the pipe) and the friction of this pulls up the liquid.
with this flow is the height of the pipe, multiplied by
The gravitational pressure loss is no longer the major
the liquid density and the gravitational constant. In
part of the pressure loss, but rather the frictional
an example with R717 at -10°C in a large pipe with a
pressure loss dominates.
height of 3 meters, this is 652 kg/m3 * 3 m * 9.81
Figure 5.5.3: Pressure loss in riser at appropriate circulation rate
The above 100kW at -10°C R717, circulation rate 3, Figure 5.5.4. The speed is now 0.48 m/s – 1/28th
equates to 833.9 kg/hr. Using the same flow but that of before – but the pressure loss is now 0.14 bar
with a much larger circulation rate simulates a very – approximately 6 times higher. This is due to the
low capacity and thus a low vapour flow as shown in pipe filling up with liquid.
An excessively high pressure loss has, as mentioned the return pipe starts to fill up with liquid and pro-
above, some serious penalties. In low temperature vide a greater pressure loss.
applications, a pressure loss of 0.15 bar could have a
The resulting pressure loss should be added to the
significant impact on the efficiency and capacity of
pressure loss in the evaporator with the pressure
the system. For thermosyphon systems, the com-
loss in the valves and compared to the driving pres-
bined pressure loss in the return pipe and the heat
sure. A good margin is recommended for this.
exchanger must be smaller than the driving pressure
provided by the liquid column in the inlet of the It is also important to consider the circulation rate at
evaporator. Similar to the pressure loss calculation part-load operation of the evaporators.
above, the driving pressure is the product of liquid
density, height and gravitation. The vertical part of A properly designed vertical return pipe, utilizing the
the return pipe is, more or less, the same as the ver- annular flow, is called a ‘riser’. The Danfoss calcula-
tical pipe providing the driving height, so a liquid- tion software Coolselector2 can be used to calculate
filled return pipe provides a pressure loss that is an appropriate circulation rate for a riser.
more or less the same as the driving pressure – leav- Pressure drop in risers can pose challenges when op-
ing very little pressure drop available for the evapo- erating an evaporator in part-load conditions. The
rator. In effect, that means that there will be no cir- evaporator is typically dimensioned for a certain cir-
culation in the system, the evaporator performance culation rate at full load. A rule of thumb is that a cir-
will drop and it will not deliver what is expected of it. culation rate of 3 results in reasonable operation of
The return pipe therefore needs to be designed the evaporator and pressure drop. However, it is ex-
carefully to avoid too great a pressure drop. The top tremely challenging to control the circulation rate,
Coolselector2 calculation in Figure 5.5.3 represents a hence the mass-% of evaporated refrigerant under
good solution. Pressure loss is relatively low, and it part-load conditions.
shows that it is possible to reduce capacity on the Figure 5.5.5 shows the pressure drop in a riser for a
heat exchanger without passing into the area where flooded evaporator with ammonia and DN 65 piping.
The blue lines intersect at 67 kW, which is the refer- circulation rate is kept constant. The solid green line
ence value condition at full load and a circulation represents a situation with 1.5 in constant circula-
rate of 3. The solid blue line shows the pressure drop tion rate under part-load conditions, which yields an
at constant mass flow, hence the circulation rate even lower pressure drop. This clearly demonstrates
varies with part-load conditions. The broken blue that being able to control the circulation rate of a
line shows the pressure drop at a constant circula- flooded evaporator can result in a better part-load
tion rate, hence the mass flow varies. It can clearly system performance.
be seen that the pressure drop in the riser is signifi-
cantly lower during part-load operation when the
Evaporator
Liquid Feed Line
1
Defrost sequence
1 Liquid feed
2 Wet return
3 Hot gas
4 Defrost valve
5 Fan
A B C D E F G H I
CO2 in this phase, the method described above is Analogue. The opening degree is controlled, and the
generally accepted to be the safest. lifting height responds proportionally with an ana-
logue input signal (i.e. 0-20/4-20mA and 0-10/2-10V)
C: Stabilizing phase
On/Off. The valve responds to a digital input contact
The wet suction line closes (Valve 2) and the fans
and the opening speed can be set to the requested
stop. Now all valves around the evaporator are
demand. The valve is fully closed or fully open or
closed and any remaining liquid can collect at the
moving towards one of these positions.
bottom of the evaporator and enable a smooth start
to defrost. ICS+EVM: An ICS servo valve with an EVM solenoid
valve as pilot valve acting as a solenoid valve step 2
D & E: Soft opening phase
with a small EVRS solenoid as bypass valve acting as
Hot gas injection, step 1 and 2. It is generally not rec- step 1.
ommended to inject hot gas without any control. Re-
F: Defrosting phase
maining liquid in transport lines or evaporators must
be prevented from causing liquid hammer. Further- During the actual defrost phase, the main purpose is
more, the pressure differences in the evaporator to defrost as efficiently as possible. In this phase, the
should be considered. This depends on the refriger- liquid supply valve (1), wet suction valve (2), and a
ant used in the system. The pressure difference in condensate drain valve for the main hot gas supply
CO2 systems is much higher compared to NH3 or line (not shown) are closed. The hot gas supply line
Freon, so this further recommends the need for a valves (3) are open.
controlled way of opening valves.
At the start of defrosting, the warm hot gas will con-
As an example, a generally accepted defrost temper- dense in the evaporator.
ature of 10°C in CO2 systems is equal to a pressure
During the defrosting cycle, the pressure in the evap-
of 47.23 bar. The pressure of an evaporator at -40°C
orator will gradually rise. This phase must be con-
is 10 bar. The pressure difference is 37.23 bar. A sim-
trolled, otherwise large amounts of uncondensed
ilar situation with NH3 or R 404a only results in a
hot gas (blow-by gas) return to the liquid separator
pressure difference of 5.87 bar and 7.33 bar, respec-
and must be re-compressed by the compressors, de-
tively.
creasing system efficiency.
The pressure of the evaporator must be increased
5.6.5 Controlling the defrost phase:
slowly. There are several ways to do this with
Pressure-controlled defrost (valve 4)
Danfoss valve solutions:
The pressure control method is the most common
ICSH: Dual position solenoid valve. Step 1 is 20% of method for controlling the defrost pressure in evap-
the kV value of step 2 and allows a smooth pressure orators. The pressure control method is a simple and
build-up in the evaporator. Steps 1 and 2 are con- reliable method, but it is not the most effective. The
trolled by an EVM pilot valve and, for maximum op- defrost pressure is controlled at a set pressure corre-
erating freedom, step 2 can be made dependent or sponding to 7-12°C saturated pressure. Valve 4 can
independent of step 1. The steps can be controlled be an ICS main control servo valve with a constant
by a PLC where the delay between steps 1 and 2 can pressure CVP-H pilot to control the required defrost
be freely set. pressure. Hot gas will condense in the evaporator
and pressure will gradually increase. When the set-
ICM: Proportional motor valve type. The valve is con- point is reached, the control valve starts to open and
trolled by an actuator, ICAD. The ICAD motor is con- control the pressure. During this process, the
nected to the ICM valve with a magnetic coupling, amount of flash-gas gradually increases, decreasing
enabling easy service and maintenance activities the system efficiency.
without the need to open the ICM valve. The valve is
designed to be controlled in 2 ways:
The liquid drain method is very important for the energy and time spent on defrosting. The liquid drain
method determines how much of the energy bound in the hot gas is used for defrosting the evaporator.
D* D B
E* E
Figure 5.6.3 shows the hot gas defrosting process in a log(p)-h diagram. Comparing Figure 5.6.3 to Figure
5.6.1, the process (A) to (B) shows pressure reduction from the compressor’s discharge pressure to the hot
gas supply pressure set by the main hot gas supply valve (3) in Figure 5.6.1. The pressure in point (C) is not
defined but depends on the components in the hot gas defrost line. Point (D) corresponds to the defrost
pressure in the evaporator, however the horizontal position of (D), the dimensioning quality, depends on the
liquid drain method. (E) is the evaporator pressure in cooling mode.
Liquid drain controlled defrost: The dimensioning quality of a liquid drain controlled defrost should be 0.0,
as the hot gas will be fully condensed to point (D*). The purpose of a float valve in the defrost drain line is to
prevent gas passing through.
Pressure-controlled defrost: Initially all the hot gas supplied to the evaporator will condense, and the drain
valve will only see liquid at its inlet. When the temperature in the evaporator has been increased, some gas
will not be condensed in the evaporator, and a mixture of liquid and gas will be at the valve inlet. This is the
process seen from (D*) to (D) in Figure 5.6.3. Selecting the right dimensioning quality for a pressure-con-
trolled drain is important for selecting the right valve size. A dimensioning quality that is too low will result in
a smaller valve, which will prolong the defrost time. If the dimensioning quality is set too high, the valve
could be too large, resulting in a lot of gas being bypassed, which results in higher energy consumption for
the defrost sequence. Consult Coolselector2 when dimensioning your system’s drain valve. Generally, a rela-
tively low dimensioning quality (around 0.05) is recommended when sizing valves for the drain line.
Defrost capacity
The needed amount of hot gas for an efficient defrost depends on the evaporator size, the requested defrost
time, and the liquid drain method. As a rule of thumb, the design mass flow (hot gas) for each evaporator
requires 2-3 times the required mass flow during the cooling (based on complete evaporation (1:1). The
lower the evaporating temperature, the more the ratio goes in the direction of 3. Max. 1/3 of the total num-
ber of evaporators in the same installation can be defrosted at the same time (the “two‐to‐one rule”).
When determining the mass flow needed for the defrost sequence, one should be aware of the capacity of
the liquid drain valves and the pressure in the hot gas supply line. They create the defrost pressure graph,
which is shown in
Figure 5.6.4. On the x-axis, the mass flow of hot gas of the hot gas defrosting system, and on the y-axis
is shown, which corresponds to the defrost capacity the pressure is shown.
Figure 5.6.4 shows 5 different lines. The vertical bro- A thorough guide to dimensioning the mass flow hot
ken line is the specified mass flow of hot gas to the gas defrost lines can be found in the Danfoss calcula-
evaporator. The green horizontal line is the reduced tion tool Coolselector2.
hot gas pressure (B) from Figure 5.6.3, where the
Injecting hot gas
solid blue line is the hot gas defrost pressure at the All examples in this document are shown with hot
evaporator inlet (C), the red line is the pressure in gas injection into evaporators in the top of the evap-
the defrost drain line/evaporator outlet (D), and the orator. This method is generally seen as a safe solu-
purple line at the bottom is the relieving pressure (E) tion with a very low risk for “liquid hammer”.
corresponding to the evaporator pressure in cooling
mode. Other hot gas injection methods can be used safely,
but generally they will require more detailed docu-
The green area between the evaporator inlet and mentations to ensure safe operation.
the evaporator outlet shows the pressure drop avail-
able for the evaporator during defrost, if no compo- Liquid hammer
nents have been added to the end of the hot gas line This is the “nickname” given to various phenomena
to simulate the pressure drop in the evaporator. that result in high-pressure impact in the system.
Two of these are important when designing hot gas
For the hot gas system to function properly, it is im- defrost systems:
portant that the hot gas mass flow is kept within the
green area. If the mass flow should go beyond that Pressure impact caused by vapour-propelled liquid in
area, the following steps can be taken: gas lines where liquid pockets are present. It can typ-
ically occur in hot gas supply and wet return lines.
Increase the reduced pressure – and check it against The design should be such that liquid pockets cannot
the condensation pressure in the system occur and that valves open slowly.
Decrease the hot gas mass flow – at the cost of a Pressure impact caused by collapsing gas pockets in
slower defrost liquid lines trapped by moving liquid. The impact can
be reduced by removing as much liquid as possible
Decrease the defrost pressure, and thus the defrost
from the evaporator prior to defrosting, having a
temperature – at the cost of a slower defrost
The Application Example 5.6.5 above is a DX evapo- The two-step solenoid valve ICLX/motor valve ICM in
rator system with hot gas defrost. The same applica- the suction line is kept open, and the defrosting sole-
tion is shown on the next page for large-scale sys- noid valve ICFE in the hot gas supply line is kept
tems with the larger sizes of the Danfoss ICF valve closed.
station range. The numbering of the lines in this ap-
The servo valve ICS in the discharge line is kept open
plication example follows the numbering of the lines
by its solenoid valve pilot EVM.
in Figure 5.6.1, hence the lines shown there corre-
spond to the lines shown in the application examples Defrost Cycle
in this chapter. Whilst this method of defrosting is
not common, it is even less so for ammonia DX evap- After initiation of the defrost cycle, the liquid injec-
orator systems and is more applicable to fluorinated tion solenoid valve ICFE/EVRA in line (1) is closed.
and CO2 systems. The serial solution for components The fan is kept running for 120 to 600 seconds, de-
in the hot gas line and liquid supply line is only appli- pending on the evaporator size, to pump down the
cable for ammonia systems. evaporator of liquid.
Refrigeration Cycle The fans are stopped and the pilots on the ICLX are
de-energized. The servo piston is kept open by the
The solenoid valve, ICFE, in the liquid line is kept hot gas pressure. However, in cooling mode the hot
open. The liquid injection is controlled by the motor gas condenses in the cold ICLX valve, so that the
valve ICM. servo piston chamber is filled with liquid at hot gas
pressure. The pressure between the hot gas and the
suction line is equalized by the NO-pilot, when it is
de-energized, on the ICLX and the servo piston
chamber is slowly drained by the bleed line in the noid valve will have a capacity of just 10% at high dif-
NO-pilot. The equalized pressure between the piston ferential pressure, allowing the pressure to be equal-
chamber and the suction line lets the main spring ized before opening fully to ensure smooth opera-
push the servo piston down to close the valve. tion and avoid liquid slugging in the suction line.
The exact time taken from when the pilot valves As an alternative to the ICLX two-step solenoid valve,
changes position to complete closing of the valve de- an ICM motor valve with an ICAD actuator could be
pends on the temperature, pressure, refrigerant and used for the soft opening of the suction line. This is
valve size. It is therefore not possible to state an ex- recommended for CO2 systems for more accurate
act closing time for the valves, but lower pressures control.
generally result in longer closing times.
After the ICLX/ICM fully opens, ICFE in the liquid line
It is very important to take the closing times into is opened to restart the refrigeration cycle. The fan is
consideration when hot gas defrost is used in evapo- started after a delay in order to freeze remaining liq-
rators. uid droplets on the surface of the evaporator.
The CVPP pilot for the ICS in the discharge line then
creates a differential pressure, Δp, between hot gas
pressure and the receiver pressure. This pressure
drop ensures that the liquid which is condensed dur-
ing defrosting is forced out into the liquid line
through a check valve, CHV.
Application Example 5.6.6: DX evaporator with hot gas defrost system for large-scale systems
Option 2
ICAD Option 2
Option 1 CVP
ICFS ICFE
ICM Liquid drain
CHV
line
4 ICS
ICFR ICFS Single component solution
ICFD ICFS
ICFE
Evaporator From liquid
1 separator
REG CHV SVA
ICFC ICFF EVRA FIA
ICFW
Drip Tray
ICFS Single component solution
ICFE
Hot gas
supply line
3 SVA SVA
EVRA FIA
ICFF
ICFS
SVA SVA
ICSH FIA
Application Example 5.6.7 shows the typical installa- be used instead of an ICLX), and the defrosting sole-
tion options for pumped liquid circulation evapora- noid valve ICFE/EVRA is kept closed. It is recom-
tors with hot gas defrost systems. This application mended that an ICM motor valve be used for soft-
example is shown with ICF valve stations which can opening in the wet suction line for CO2 systems.
accommodate up to 6 modules in the same housing.
Defrost Cycle
The same application is shown on the next page for
large-scale systems with the larger sizes of the After initiation of the defrost cycle, the liquid supply
Danfoss ICF valve station range. The numbering of solenoid ICFE is closed. The fan is kept running for
the lines in this application example follows the 120 to 600 seconds, depending on the evaporator
numbering of the lines in Figure 5.6.1, hence the size, to pump down the evaporator of liquid.
lines shown there correspond to the lines shown in
the application examples in this chapter. The appli- The fans are stopped and the pilots on the ICLX are
cation can also be made with components in a serial de-energized. The servo piston is kept open by the
connection instead, which is only applicable for am- hot gas pressure. However, in cooling mode the hot
monia systems. gas condenses in the cold ICLX valve, so that the
servo piston chamber is filled with liquid at hot gas
Refrigeration Cycle pressure. The pressure between the hot gas and the
suction line is equalized by the NO-pilot, when it is
The solenoid valve ICFE/EVRA on the liquid line (line
de-energized, on the ICLX and the servo piston
(1)) is kept open. The liquid injection is controlled by
chamber is slowly drained by the bleed line in the
the manual regulating valve ICFR/REG.
NO-pilot. The equalized pressure between the piston
The two-step solenoid valve ICLX in the suction line chamber and the suction line lets the main spring
is kept open (alternatively, an ICM motor valve can push the servo piston down to close the valve.
The exact time taken from when the pilot valves delay to freeze remaining liquid droplets on the sur-
change position to complete closing of the valve de- face of the evaporator.
pends on the temperature, pressure, refrigerant and
valve size. It is therefore not possible to state an ex-
act closing time for the valves, but lower pressures
generally result in longer closing times.
Application Example 5.6.8: Pumped liquid circulation evaporator with hot gas defrost system
ICAD
Option 2
SVA
SVA
ICM
ICF-65
Option 1
SVA ICLX
SVA
To liquid
2 separator
ICF-65
Soft-opening options
Option 2
Option 1 CVP
ICFS ICFE
Liquid drain
CHV
line
4 ICS
ICFR ICFS Single component solution
ICFD ICFS
ICFE
Evaporator From liquid
1 separator
REG CHV SVA
ICFW
ICFC ICFF EVRA FIA
Drip Tray
ICSH
SVA
SVA
Hot gas
supply line
3
ICF-50 FIA
Soft-opening
Application Example 5.6.7: Pumped liquid circulation evaporator with hot gas defrost system
Application Example 5.6.9: Pumped plate freezer with hot gas defrost system
Soft-opening
SVA
SVA
ICSH
Hot gas
supply line
3
ICF-50
FIA
Soft-opening options
Option 1
ICAD
SVA
ICM
SVA
To liquid
separator
2
ICF-65
Option 2
SVA ICLX
SVA
ICF-65
AKS Option 2
4100
Option 1
ICFS
Plate freezers ICFE Gas
From liquid
separator
1
ICFW
ICFC ICFF
The solutions shown in the broken-line boxes are op- Option 2 for the liquid drain line (4) is sending the
tions that depend on the cooling capacity of the condensate to a vessel with a liquid level transmit-
plate freezer and the refrigerant. In the wet return ter, AKS 4100. A regulating valve allows gas to by-
line (2), ICF-65 with ICM (option 1) is recommended pass to avoid increasing the pressure in the vessel,
for ammonia and CO2 systems, since the alternative, while a motor valve, ICM, is controlled by the level
ICLX, has a long closing time, which must be consid- transmitter to drain liquid from the vessel. This solu-
ered when defrosting a plate freezer. The extended tion would be the alternative for CO2 systems, until
closing time of the ICLX can lead to bypassing hot gas the ICFD is approved for CO2.
to the wet suction line, which increases the energy
consumption for the defrosting sequence. The ICF-
65 with ICLX (option 2) can be used if the defrosting
time of the plate freezer is less critical for the quality
of the frozen product in the plate freezer. In the liq-
uid drain line (4), use of the ICFD module (option 1)
is limited by the defrost capacity/demand of the
plate freezer and the refrigerant. The ICFD module is
only available for ammonia systems. Consult Coolse-
lector2 to examine the limits of the ICFD solution.
5.7 Summary
Media temperature M
Very precise temperature The ICM will control the Maximum capacity is ICM
control with motor valve ICM control. temperature very 150.
ICM Option of running at accurately, by adjusting
different temperatures. the opening degree.
Multi-temperature PC CVP Applicable to all Low start-up current Pressure drop in suction
control with ICS and CVP PC
compressors with the Energy savings line.
EVM CVP ability to run at reduced Lower noise
ICS
speed. Longer lifetime
Simplified installation
Pumped liquid circulation Pump circulating systems High capacity and Fluctuations, and high
evaporator with solenoid efficient evaporator refrigerant charge.
valve or pulse-width- Fewer fluctuations when
modulated AKVA valve using the AKVA solution.
Pumped liquid All pumped circulated Quick defrost. The hot Not applicable for
EVM
circulation evaporator ICLX
systems gas can bring out the oil systems with fewer than
CVP PC
Oil systems
Oil Cooler
Oil Separator
Compressor
Evaporator Condenser
Expansion valve
Generally, industrial refrigeration compressors are There are generally some supporting components
lubricated with oil, which is forced by the oil pump and equipment within refrigeration systems for oil
or by the pressure difference between the high and cleaning, oil separation from the refrigerant, oil re-
the low-pressure sides to the moving parts of the turn from the low-pressure side, equalization of the
compressors (bearings, rotors, cylinder walls etc.). oil level in systems with several piston compressors
To guarantee reliable and efficient operation of the and oil drain-off points. Most of these are supplied
compressor, the following oil parameters should be by the compressor manufacturer.
controlled:
The oil system design of an industrial refrigeration
Oil temperature. This should be kept within the lim- plant depends on the type of compressor (screw or
its specified by the manufacturer to avoid degrada- piston) and on the refrigerant (ammonia, HFC or
tion of the oil. The oil should have the correct viscos- CO2). An immiscible oil type is generally used for
ity and the discharge temperature from the com- ammonia, and a miscible one for fluorinated refrig-
pressor should be kept below the temperatures at erants and CO2. As oil systems are very closely re-
which the oil starts to decompose. lated to compressors, some of the above-mentioned
points have been described in Compressor controls
Oil pressure. Oil pressure difference should be kept
(section 2) and Safety systems (section 7).
above the minimum acceptable level specified by
the compressor manufacturer.
Refrigeration compressors (including all screw com- also necessary to control it. The oil temperature is
pressors and some piston compressors) generally re- usually specified by the compressor manufacturer.
quire oil cooling. Discharge temperatures that are
There are a few different types of oil cooling systems
too high can destroy oil, which leads to damage of
used in refrigeration. The most common types are:
the compressor. It is also important for the oil to
have the right viscosity, which is heavily dependent water cooling
on the temperature level. It is not enough just to air cooling
keep the temperature below the critical limit, it is
refrigerant cooling
Oil can also be cooled by means of injection of the all, as temperature is less critical than for screw com-
liquid refrigerant directly into the intermediate com- pressors, with the oil being cooled in the crankcase
pressor port. For piston compressors, it is quite com- of the piston compressor.
mon not to have any special oil cooling systems at
Cooling water in
SVA WVTS
SNV
ORV
Cooling water in
SVA
SNV
These types of systems are normally used in plants Please contact your local Danfoss sales company to
where it is possible to get a cheap water source. check the suitability of components to be used with
Otherwise, it is necessary to install a cooling tower sea water as the cooling medium.
to cool down the water. Water-cooled oil coolers are
quite common for marine refrigeration plants.
Hot oil
ORV
Cold oil Oil cooler
FIA
In this case, the ORV divides the flow from the oil
separator and regulates based on the change in oil
return temperature.
SCA
SVA
RT 1A
RT 5A SVA
Condenser
From liquid
separator
Oil separator
SVA SVA
Overfeed riser
SVA
Compressor
SFA
Sight glass
These types of systems are very convenient, as oil is The oil temperature is maintained at the correct
cooled inside the system. It is only necessary to over- level by the oil regulating valve (ORV), a three-way
size the condenser for the amount of heat taken valve. The ORV keeps the oil temperature within the
from the oil cooler. Conversely, Refrigerant oil cool- limits defined by its thermostatic element. If the oil
ing requires additional piping on site and it is some- temperature rises too high, then all the oil will re-
times also necessary to install an additional priority turn to the oil cooler. If it is too low, then all the oil
vessel (in cases where the HP liquid receiver is flow is bypassed around the oil cooler.
placed too low or not installed). In the case above,
the feed pipe to the liquid separator is placed at a
certain height above the bottom of the receiver ves-
sel to create a priority for the oil cooler that is
drained from the bottom of the receiver.
During normal running of the refrigeration compres- The first is to use an external oil pump, and the sec-
sor, oil is circulated by the oil pump and/or pressure ond is to install a control valve on the compressor
difference between the HP and LP sides. The most discharge line after the oil separator.
critical phase is during start-up.
For the latter method, it is necessary to check if the
It is vital to have a quick build-up of oil pressure, oth- compressor manufacturer allows a few seconds of
erwise the compressor may be damaged. dry operation. Normally, this is possible for screw
compressors with ball bearings, but not possible for
There are two basic ways to quickly build up oil dif-
those with slide bearings
ferential pressure in the refrigeration compressor.
Application Example 6.2.1: Oil differential pressure control with ICS and CVPP
CVPP
SCA
To condenser
RT 1A
RT 5A ICS
From liquid
separator
Oil separator
SVA
Compressor
To oil cooler
In this application, a servo-operated valve, ICS, com- The main advantage of this solution is its flexibility,
plete with differential pilot, CVPP, should be used. as differential pressure can be readjusted on site
The pilot line from the CVPP valve is connected to and, using other pilots, the ICS can also serve some
the suction line. ICS is closed when the compressor is other functions.
started up.
In areas with a very low ambient temperature, an ex-
As the piping between the compressor and the valve cessively high setpoint of the differential pressure pi-
is very short, the discharge pressure increases rap- lot valve (CVPP) will result in no benefit from the
idly. It requires very little time before the valve fully lower condensation temperature, since the com-
opens and the compressor runs at normal condi- pressor will need to provide the required discharge
tions. pressure to open the pilot valve.
KDC
To condenser
RT 1A
RT 5A
From liquid
separator
Oil separator
SVA Check valve
Compressor
To oil cooler
The principle of operation for this example is the The multifunctional compressor valve, KDC, has two
same as for Application Example 6.2.1. The multi- primary functions, which are described below. The
functional compressor valve (KDC) opens when the steps of the KDC valve are shown in the figure be-
pressure difference between the discharge line and low:
the suction line exceeds the setting value and, at the
Pressure control function: The KDC valve is a pres-
same time, the pressure in the oil separator is
sure control valve. The valve controls the discharge
greater than the condensing pressure.
pressure of the compressor to ensure fast build-up
However, the KDC also has some limitations. The of pressure and oil pressure.
valve is not adjustable and there are a limited num-
Check valve function: The valve also ensures against
ber of differential pressure settings available, and it
backwards flow when the cone initially is in closed
is necessary to have a check valve in the suction line.
position (step 1), and the differential pressure across
If this check valve is not present, there could be a the cone increases. The pressure in the cone is con-
very large reverse flow through the compressor from nected to the suction pressure. The valve remains
the oil separator. It is not permitted to have a check closed when the valve moves to step 2.
valve between the compressor and oil separator;
otherwise it may take too long for the KDC to close.
Application Example 6.2.3: Oil differential pressure control with KDC and EVM pilots
CVH CVH
KDC
To condenser
RT 1A
RT 5A
From liquid
separator
Oil separator
SVA
Compressor
To oil cooler
When there is no possibility to install a check valve in When the compressor stops, EVM NC should be
the suction line or there is a check valve in the line closed and EVM NO opens. That equalizes the pres-
between the compressor and the oil separator, it is sure over the KDC spring, and it closes.
possible to use the KDC valve equipped with EVM so-
Please note the installation direction of the CVH and
lenoid pilot valves.
EVM pilot valves.
This solution minimizes the pressure drop in the suc-
tion line compared to the solution shown in Applica-
tion Example 6.2.2.
The compressors within industrial refrigeration sys- Oil rectifiers are used for refrigerants which do mix
tems are generally the only components that require with oil. The oil and liquid refrigerant mixture is
oil lubrication. Therefore, the function of the com- drained from the liquid separator and heated by hot
pressor oil separator is to prevent any of the lubri- liquid from the condenser in a heat exchanger. The
cating oil passing into the refrigeration system. oil and refrigerant are separated by evaporating the
refrigerant, so that the oil can be recovered.
However, oil can be carried over through the oil sep-
arator into the refrigeration system and often col- The oil return system can therefore have two func-
lects in the low-pressure side in liquid separators tions:
and evaporators, decreasing their efficiency.
To remove oil from the low-pressure side
If too much oil carries over from the compressor into To feed the oil back to the compressor.
the system, the amount of oil in the compressor will
be reduced and there is then a risk of the oil level
falling below the minimum limit set by the compres-
sor manufacturer. Oil return systems are primarily
used together with refrigerants that can be mixed
with the oil e.g. HFC/HCFC systems.
AKS 38
Liquid separator
LLG
AKS 38
SVA SVA
BSV
PI
SVA
SVA
SNV
Oil receiver
In ammonia systems, immiscible oil is used. As the Therefore, oil in ammonia systems is normally
oil is heavier than liquid ammonia, it stays at the drained from the liquid separator into an oil re-
bottom of the liquid separator and is unable to re- ceiver. This makes the separation of oil from ammo-
turn to the compressor via the suction line. nia easier.
First, check that ventilation fans are operating in the valve up-stream of the QDV valve when all the oil
area from which oil is drained. Before draining the has been drained. When the SVA between the QDV
oil, close the stop valve from the separator to the oil and the oil receiver is closed, re-open the QDV for
receiver. Turn on the electric heating coil to warm up sufficient time to allow any trapped liquid to be
the oil. Let ammonia liquid in the oil receiver boil off drained.
to the wet return line, before draining the oil.
When the oil has been drained, re-open the SVA be-
When the ammonia in the oil receiver has been tween the separator and oil receiver and the SVA be-
boiled off, the stop valve SVA between the oil re- tween the oil receiver and the wet return line.
ceiver and the wet return line is closed.
Measure and note down the amount of drained oil.
Make sure that oil can be drained to a bucket or ves-
It is, however, extremely important to be aware that
sel before opening the drain valve. Ensure that the
any oil removed from the low-pressure side of the
pressure in the oil receiver is above atmospheric
ammonia cooling system is usually unsuitable for
pressure. Open the stop valve up-stream of the QDV
further use with the compressor and should be dis-
valve approx. one turn. Then slowly press down the
carded.
handle on the quick-closing oil drain valve, QDV. Do
not mechanically block the handle of the QDV in the Necessary precautions during drainage of oil from
open position. If the oil drain rate is not satisfactory, ammonia should be taken to avoid draining large
adjust the opening degree of the SVA valve up- amounts of ammonia. Safety equipment must be
stream of the QDV valve accordingly. Close the stop used when draining oil from the receiver.
Application Example 6.3.2: Oil drain from fluorinated systems and CO2 systems
+
SVA To suction line
ICAD
SVA
SVA Sight
Liquid separator glass
AKS 38
SVA
LLG SVA
Liquid level
Heat
AKS 38 exchanger
ICFE
SVA ICFS
SVA
ICFF
ICFR
To refrigerant pump
In fluorinated and CO2 systems, miscible oil is pre- Low-pressure refrigerant is heated up by high-pres-
dominantly used. In a DX system, oil recovery is not sure liquid refrigerant and evaporates.
a problem as the oil is returned in the suction line,
The evaporated refrigerant gas mixed with oil re-
provided good piping practice is followed (slopes, oil
turns to the suction line. Refrigerant from the liquid
loops, speed etc.).
separator is taken from the working level.
However, in flooded systems oil recovery requires
The regulating valve ICFR in the oil/refrigerant mix-
the use of an oil rectifier as the oil accumulates in
ture line is adjusted in such a way that there are no
the low-pressure separator. An oil rectifier is a small
drops of liquid refrigerant seen in the sight glass, to
heat exchanger that evaporates part of the (rela-
ensure superheat of the oil/refrigerant mixture. The
tively oil-rich) refrigerant liquid in the separator and
superheated refrigerant gas will entrain the flow of
returns the oil content to the suction line or an oil
oil back to the compressor.
collection vessel. The heat for the evaporation pro-
cess is usually provided by the liquid for the expan- For CO2 systems: Be aware that the AKS 38 level
sion device, making the oil rectifier energy-neutral. switch is only applicable up to 25 bar-a.
In the system above, the refrigerant moves from the
liquid separator into the heat exchanger by gravity.
Application Example 6.3.3: Oil drain from fluorinated system and CO2 systems with drain from pump dis-
charge line
ICAD
SVA
SVA Sight
glass
AKS 38
Liquid separator SVA
LLG SVA
Heat
AKS 38 exchanger
ICFA
SVA ICFS
EKC 315A
ICFF
ICFS
SVA
Pump
To evaporator
Oil separator
solenoid but l
tion tions pilot installat piping,
Oil Cooling Controls – see section 6.1 valves. ion of no
check change
Water Marine Simple Could be valve in of
Hot oil in
cooling installatio and expensive, suction setting
with WVTS ns, plants efficient requires line is possibl
water Cold oil out where an separate not e
valve or inexpensiv water necessa
with TC e cold- piping ry
three-way Hot oil in ORV water
oil
regulating
source is
available
Oil Recovery System – see section 6.3
Cold oil out
valve, ORV
Oil Liquid All Simple, Requires
Air cooling TC “Heavy Simple, no Big recover
separator
ammoni but manual
with Hot oil in
ORV
commerci additional fluctuation y for a should operatin
three-way al” piping or s in oil ammoni systems be g
QDV BSV
oil refrigerati water temperatu a handle
regulating on required re possible systems Oil receiver d with
valve, ORV systems in with a great
Cold oil out
with different quick care
power seasons; drain
packs Air coolers valve,
might be QDV
too big for
large
Oil Low
To suction line
Does Complica
installatio M
ORV
Flexible Require d
l pressure , s system
controlled differen installat s.
Oil separator
by ICS t ion of
solution settings check
possibl valve
Screw e
compress
Controlled or (should Require It is
by the be s no necessa
Oil separator
Safety systems
All industrial refrigeration systems are designed with Pressure limiter is a device that protects against
different safety systems to protect them against un- high or low pressure with automatic resetting.
safe conditions, such as excessive pressure. Any
Safety pressure cut-out are safety switches that are
foreseeable excessive internal pressure should be
designed for limiting the pressure with manual reset-
prevented or relieved with minimum risk to people,
ting.
property and the environment.
Differential pressure cut-out is a device that
Requirements for the safety systems are heavily con-
measures the minimum differential pressure for safe
trolled by authorities, and it is therefore always nec-
operation of a pump or a compressor. Pump cavita-
essary to verify the requirements in the local legisla-
tion can be detected through excessively low differ-
tion in various countries. The illustrations in this
ential pressure and the pump must be stopped. In-
chapter generally reflect the EN 13136 standard, but
sufficient oil differential pressure in a compressor
some should be regarded as ‘best practice’.
can lead to insufficient lubrication and requires the
Pressure relief device, e.g. pressure relief valve, is compressor to be stopped.
designed to relieve excessive pressure automatically
Liquid level cut-out is a liquid level actuated device
at a pressure not exceeding the permissible limit and
designed to prevent unsafe liquid levels.
reseat after the pressure has fallen below the per-
missible limit. Refrigerant detector is a sensing device which re-
sponds to a pre-set concentration of refrigerant gas
Temperature limiting device or temperature limiter
in the environment. Danfoss produces GD-type re-
is a temperature actuated device that is designed to
frigerant detectors type, please see specific applica-
avoid unsafe temperatures so that the system can
tion guide for more information.
be stopped partly or completely in case of a defect
or malfunction.
Safety valves are installed to prevent the pressure in The main parameters for safety valves are the relief
the system from rising above the maximum allowa- pressure and reseating pressure. Normally the relief
ble pressure of any component and the system as a pressure should not exceed more than 10% of the
whole. In case of excessive pressure, safety valves set pressures. Furthermore, if the valve does not re-
relieve refrigerant from the refrigeration system. seat or reseats at too low a pressure, there can be
significant loss of system refrigerant.
SVA
Oil level
From condenser
SFA/SFV
SVA
SNV DSV
Pressure equalization line
SNV
Receiver
LLG
SVA
To oil cooler
To expansion
device
Pressure relief devices should be installed on all ves- compressor flow, again according to EN 13136, ISO
sels in the systems, as well as on compressors. 625, ANSI IIAR2 or another local standard.
Generally, back pressure-dependent safety relief CoolSelector2 can dimension valves and lines in ac-
valves (SFA) are used. Safety valves should be in- cordance with EN 13136 and ISO 5149.
stalled with a changeover valve DSV, to enable the
Generally, the safety valve set pressure must be the
servicing of one valve whilst the other is still in oper-
minimum of the maximum pressures of the compo-
ation. As only one of the two safety valves is active
nents in the section it services.
at a time, they should both be dimensioned to the
full relief capacity. Please note: Some countries do not allow installa-
tion of a u-trap in relief pipes.
Pressure relief devices should be mounted close to
the part of the system they are protecting. To check The relief pipe from the safety valve should be de-
if the relief valve has discharged to the atmosphere, signed in such a way that people are not endangered
a u-trap filled with oil and with a sight glass mounted in the event that refrigerant is relieved.
can be installed after the valve.
A pressure drop in the relief pipe to the safety valves
For vessels, the safety valves must be sized based on is important for the function of the valves. Check the
the size of the external surface, e.g. according to EN applicable standards for recommendations on how
13136, ISO 5149, ANSI IIAR2 (depending on the lo- to size these pipes.
cally applicable standard). For compressors, the
safety valve must be dimensioned according to the
Oil level
Oil separator
Suction line LLS 4000 /
SVA SVA AKS 38
FIA
ICFS
ICFE
ICFO ICFF
ICF-15
To relieve refrigerant from the high-pressure side to In many cases, an oil separator can be considered a
the low-pressure side, only back pressure-independ- vessel and it must be protected accordingly. In cases
ent relief valves should be used (BSV/ POV). where the oil separator is not considered a vessel
but can be separated with stop valves from the con-
BSV can act either as a direct relief valve with low ca-
denser and compressor safety valves, then it also re-
pacity or as a pilot valve for the POV main valve.
quires a separate safety valve.
When the discharge pressure exceeds the set pres-
sure, BSV will open the POV to relieve high-pressure This protection can be achieved with standard safety
vapour into the low-pressure side. relief valves SFA combined with a changeover valve
DSV.
BSV and POV must be sized according to the dis-
charge volume flow of the compressor at relief con- Safety valves must be sized according to the size of
ditions. the external surface, e.g. in accordance with EN
13136, ISO 5149, ANSI IIAR2 (depending on the lo-
The back pressure-independent relief valves are in-
cally applicable standard).
stalled without changeover valve. If it becomes nec-
essary to replace or readjust the valves, the com- LLSs can be mounted in the oil separator to detect
pressor must be stopped. overfilling or an excessively low oil level.
RT 1A MP 55A RT 107 RT 5A
To protect the compressor from an excessively high For piston compressors, the oil differential switch
discharge pressure and temperature, or an exces- MP 54/55 is used to stop the compressors if oil pres-
sively low suction pressure, KP/RT switches are used. sure becomes too low, which can result in insuffi-
RT1A is a low-pressure control, RT 5A is a high-pres- cient lubrication of the compressor.
sure control, and RT 107 is a thermostat.
The oil differential switch cuts out the compressor if,
These controls are for the protection of the com- after a defined period of time (0-120 s), it does not
pressor against operation outside of the approved build up enough differential pressure for sufficient
operating limits, and as such do NOT replace normal lubrication during start-up.
safety valves.
These controls are often part of the compressor
Setting of the high-pressure controls should be be- package/control, but if they are not, they should be
low the setting of the safety valves on the high-pres- as shown here.
sure side. The setting on the low-pressure switch is
specified by the compressor manufacture.
SVA
Suction line
LLS 4000/
Liquid AKS 38
separator
LLG
LLS 4000/
AKS 38
SNV
SVA
SVA
Vessels on the high-pressure side and low-pressure A high-level switch is installed to protect compres-
side have different liquid level switches. sors against liquid in the suction line (sufficient liquid
separation).
High-pressure receivers only need to have a low
level switch (LLS 4000 / AKS 38) in order to guaran- Safety valves must be sized according to the size of
tee minimum refrigerant level to feed expansion de- the external surface, e.g. in accordance with EN
vices. 13136, ISO 5149, ANSI IIAR2 (depending on the lo-
cally applicable standard).
The sight glass (LLG) for visual monitoring of the liq-
uid level can also be installed. In case of low temper- Note that lower connection of the LLS 4000 / AKS 38
atures, the LLG might ice up heavily and in those / AKS 4100 standpipe slopes down to avoid oil build-
cases it is recommended that the sight adapter be up in the standpipe, which can result in erroneous
mounted to ensure a visual inspection of the liquid level measurement and/or incorrect function of the
level despite the build-up of ice. switches/level indicator.
Gas detection equipment is usually used in a fixed in- How many sensors are needed?
stallation with a number of sensors located in areas Where and how should the sensors be positioned and
where refrigerant might be expected to accumulate calibrated?
in the event of a plant leak. Which alarm limits are appropriate? How many are re-
quired? How is the alarm information processed?
These locations depend on the layout of the machin-
ery room and adjacent spaces, on the configuration Danfoss offers a wide range of gas detection equip-
of the plant and on the refrigerant in question. ment. See GD documentation for detailed infor-
mation.
Which gases need to be measured and in what quan-
tities?
For machinery rooms: Start emergency ventilation from the room (unless
refrigerant is R744)
For ventilated If a detector is used for starting ventilation: Not applicable
enclosures Start ventilation at 25% LFL (see Danfoss Application Guide –
Gas detection in refrigeration systems - Annex II)
For systems us- If a detector is used for starting ventilation: Not applicable
ing alternative Start ventilation at 50% ATEL/ODL/RCL or 25% LFL (see
risk manage- Danfoss Application Guide – Gas detection in refrigeration
ment systems - Annex II)
7.4.3 Summary
Solution Application
Pressure relief devices – see section 7.1
Safety valves SFA + Protection of
change over valve vessels,
DSV compressors, and
heat exchangers
against excessive
pressure
Receiver
When installing the pump, proper care must be )ƚ)f ƚ)d > NPSH Refrigerant
taken to prevent cavitation. Cavitation occurs if a lo- pump
In order to keep the refrigerant pump in trouble-free Therefore, systems should be designed for the refrig-
operation, the flow through the pump should be erant pump to keep this flow within the operating
maintained within the permissible operating range, range.
as shown in Figure 8.2.
H2
NPSH
Pumps are easily damaged by cavitation. To avoid For example, incorrect operations on the evapora-
cavitation, it is important to maintain sufficient posi- tors may cause increased flow through the pump,
tive suction head for the pump. To achieve enough the low-level switch may fail, and the filter in the
suction head, an AKS 38 low-level switch is installed pump line may be blocked, etc.
on the liquid separator.
All of these may lead to cavitation. Therefore, it is
However, even if the low-level switch installed on necessary to shut down the pump for protection
the liquid separator is kept above the minimum ac- when the differential pressure drops below H2 in
ceptable level, cavitation can still occur. Figure 8.2 (equivalent to Qmax).
Application Example 8.1.1: Pump protection with differential pressure control RT 260A
SVA
To suction line
Wet return line
SVA AKS 4100
SFA SFA SVA From receiver
BSV SNV SVA
DSV
AKS 38
LLG AKS 38
REG REG
SVA SVA
SVA
SVA SVA
To oil receiver SNV
SNV
RT 260A RT 260A
Pump Pump
PDI PDI
VLT VLT
SNV SNV
*FIA FIA*
SCA SNV SNV
Differential pressure controls are used for protection If the filter is installed in the suction line before the
against an excessively low pressure difference. RT pump, it will primarily protect the pump against par-
260A are supplied without a timing relay and cause a ticles. This is particularly important in the initial
momentary cut-out when the differential pressure clean-up during commissioning. However, installing
drops below the pressure controls setting. the filter in the pump suction line will add an addi-
tional pressure loss, which should be taken into ac-
The filter (FIA*) is installed on the pump line to re-
count in order to avoid cavitation in the pump.
move particles and protect automatic control valves
and pumps from damage, blockage, and general Since pressure drop can lead to cavitation, it is rec-
wear and tear. The filter can be installed in either ommended to install a 500µ mesh. Finer meshes
the suction line or discharge line of the pump. could be used during the clean-up, but be sure to
take into account the pressure drop when designing
the piping. Additionally, it is necessary to replace the against reverse flow (pressure) during standstill and
mesh after a period of time. to function as a stop valve for service of the pump.
If a filter is installed in the discharge line (as shown), The internal safety relief valve (BSV) should be di-
pressure drop is not as crucial and a 150-200µ filter mensioned according to the length of the pipe on
can be used. It is important to note that in this in- the liquid feed line between the SCA stop-check
stallation, particles can still enter the pump before valve and the solenoid valve at the evaporator,
being removed from the system. where liquid can be trapped, so that the pressure in
the liquid feed line can be relieved.
The stop-check valve (SCA) is installed on the dis-
charge lines of the pumps to protect the pumps
The most common way to keep the flow through the Even if the liquid supply to all evaporators in the sys-
pump above the minimum permissible value (Qmin in tem is stopped, the bypass line can still maintain a
Figure 8.2) is to design a bypass flow for the pump. minimum flow through the pump.
Application Example 8.2.1: Pump bypass flow control with differential pressure pilot-operated servo valve
ICS+CVPP
SVA
To suction line
Wet return line
SVA AKS 4100
SFA SFA SVA
BSV From receiver
SNV SVA
DSV
AKS 38
LLG AKS 38
CVPP CVPP
SVA SVA
SVA
ICS ICS
SVA SVA
To oil receiver SNV
SNV
RT 260A RT 260A
Pump Pump
PDI PDI
VLT VLT
SNV SNV
*FIA FIA*
SCA SNV SNV
The bypass line is designed for each pump with dif- The internal safety relief valve (BSV) should be di-
ferential pressure pilot-operated servo valve mensioned according to the length of the pipe on
(ICS+CVPP). the liquid feed line between the SCA stop-check
valve and the solenoid valve at the evaporator,
The internal safety valve (BSV) is designed for safety
where liquid can be trapped, so that the pressure in
relief when there is excessive pressure. For example,
the liquid feed line can be relieved.
when the stop valves are closed, the liquid refriger-
ant trapped in the pipes may be heated to exces-
sively high pressure.
It is of great importance to some types of pump cir- By using the pilot-controlled servo valve (ICS) and pi-
culation systems that a constant differential pres- lot valve (CVPP), it is possible to maintain a constant
sure can be maintained across the permanently set differential pressure across the pump, and therefore
throttle valves before the evaporators. a constant differential pressure across the throttle
valve.
SVA
To suction line
Wet return line
SVA AKS 4100
SFA SFA SVA From receiver
SNV SVA
DSV
AKS 38
LLG AKS 38
CVPP
SVA SVA
SVA
SNV SNV
*FIA FIA*
SCA SNV SNV
SCA
Liquid feed line
8.4 Summary
Pump bypass flow control Liquid separator Applicable to all pump Simple. Part of pump power
with differential pressure PDC
circulation systems. Effective and reliable in wasted.
pilot-operated servo keeping the minimum
valve (ICS+CVPP) and PD C
flow for the pump.
protection with safety Maintains a constant
relief valve (BSV). differential pressure
between valve inlet and
liquid.
Safety valve can
effectively prevent
excessive pressure.
Others
This chapter covers industrial refrigeration applica- tems, reducing the energy consumption and harvest-
tions for removal of water and air in the system, as ing excess heat for other purposes, e.g. space heat-
well as heat recovery systems. These applications ing or hot water production.
aim to optimize operation of the refrigeration sys-
Water, acids and particles appear naturally in fluori- rings, suction and discharge valve reeds etc. This
nated refrigeration systems. Water may enter the plating causes the bearings to run hotter as the lu-
system as a result of installation, service, leakage, brication gap in the bearings reduces as the plating
etc. gets thicker.
Acid is formed as a result of the breakdown of the Cooling of the bearings is reduced due to less oil cir-
refrigerant and oil. culating through the bearing gap. This causes these
components to get hotter and hotter. Valve plates
Particles usually result from soldering and welding
start to leak by causing a higher discharge super-
residue, the reaction between refrigerant and oil,
heating effect. As the problems escalate, compressor
etc.
failure becomes imminent.
Failure to keep the contents of acids, water and par-
Filter driers are designed to prevent all of the above
ticles within acceptable limits will significantly
circumstances. Filter driers serve two functions: a
shorten the lifetime of the refrigeration system and
drying function and a filtering function.
even burn out the compressor.
The drying function constitutes the chemical protec-
Too much moisture in systems with evaporating
tion and includes the adsorption of water and acids.
temperatures below 0°C could form ice, which may
The purpose is to prevent corrosion of the metal sur-
block control valves, solenoid valves, filters, and so
face, decomposition of the oil and refrigerant and
on. Particles increase the wear and tear on the com-
avoid burn-out of motors.
pressor and valves, as well as the possibility of creat-
ing a blockage. Acids are not corrosive if there is no The filter function constitutes the physical protec-
water. But in a water solution, acids can corrode the tion and includes retention of particles and impuri-
pipe work and plate the hot bearing surfaces in the ties of any kind. This minimizes the wear and tear of
compressor. the compressor, protects it against damage and sig-
nificantly prolongs its life.
This plating builds up on the hot bearing surfaces, in-
cluding the oil pump, crankshaft, con rods, piston
SVA
DCR SNV
SVA SGRI
SVA
To expansion
DCR SNV From receiver
device
SVA SGRI
SVA
DCR SNV
SVA SGRI
For fluorinated systems, filter driers are normally in- DC - 80% molecular sieve and 20% activated alumina
stalled in the liquid line before the expansion valve. solid core suitable for CFC & HCFC refrigerants and
In this line, there is only pure liquid flow through the compatible with HFC refrigerants;
filter drier (unlike the two-phase flow after the ex-
DA - 30% molecular sieve and 70% activated alumina
pansion valve).
solid core suitable for clean-up after compressor
The pressure drop across the filter drier is small, and burn-out and compatible with CFC / HCFC / HFC re-
the pressure drop in this line has little influence on frigerants.
the performance of the system. Installation of filter
driers could also prevent ice formation in the expan-
sion valve. In addition to the above normal solid cores, Danfoss
also provide other customer-tailored solid cores.
In industrial installations the capacity of one filter
Danfoss also provide filter driers with fixed solid
drier is not normally sufficient to dry the whole sys-
cores. For more information, please refer to the
tem, therefore several filter driers could be installed
product catalogue or contact your local sales compa-
in parallel.
nies.
DCR is a filter drier with interchangeable solid cores.
The sight glass with indicator for HCFC/CFC, type
There are three types of solid cores: DM, DC and DA.
SGRI, is installed after the filter drier to indicate the
DM - 100% molecular sieve solid core suitable for water content after drying. Sight glasses with indica-
HFC refrigerants and CO2; tor for other types of refrigerants can also be pro-
vided. For more information, please refer to the
Danfoss product catalogue.
CO2 is a non-polar molecule, so the removal process is different. Like water molecules, CO2 molecules are
small enough to pass through the molecular sieve. However, the water molecules adsorbed on the molecular
sieve tend to displace the CO2 molecules, due to the difference in polarity. Zeolite filter driers cannot be used
in ammonia systems because both water and ammonia are very polar. Even though the driers function differ-
ently in this respect in CO2 systems, the efficiency is fairly good. The water retention capacity is approximately
the same as in R134a systems.
Figure 9.2.1: Principle diagram – Filter drier installed in bypass line in a pumped circulation system
Heat
exchanger
Filter drier CO2 receiver
Sight glass
To install a filter drier in a CO2 system, the following It is recommended that a sight glass with indicator
criteria should be considered: be installed both before and after the filter drier.
The sight glass indicator before the filter indicates
Relative Humidity
whether there is any water present in the system,
The relative humidity should be high. and the sight glass indicator after the filter indicates
Pressure Drop whether the filter is still working.
The pressure drop across the filter drier should be
small. And the system performance should not be
sensitive to this pressure drop. In case of very low evaporating temperatures, the
sight glass might be blocked by ice building up on it.
9.2.1 Two-Phase Flow
In this case, it is recommended that a plexiglass ex-
Two-phase flow through the filter drier should be
tender be installed.
avoided, as it brings risk of freezing and blocking be-
cause of the unique water solubility characteristics.
Installation in other positions is not recommended In the wet suction line, there is a risk of “freezing”
for the following reasons: because of the two-phase flow, as mentioned.
In the compressor-condenser-expansion valve loop, In the liquid line before the refrigerant pumps, pres-
the RH is low. In the liquid separator, more than 90% sure drop increases the risk of cavitation to the
water exists in the liquid phase because of the much pumps.
lower solubility of vapour CO2 compared with liquid.
If the capacity of one filter drier is not enough, sev-
Therefore, little water is brought into the compres-
eral filter driers in parallel should be considered.
sor loop by the suction vapour. If filter driers are in-
stalled in this loop, the drier will have too little ca-
pacity.
Water and ammonia will co-exist and act as a kind of Change the charge
zeotropic refrigerant, whose saturated P-T relation- This is suitable for systems with small charges (e.g.
ship is no longer the same as anhydrous ammonia. chillers with plate type evaporators), and it should
comply with local legislation.
These are factors in why ammonia systems are sel-
dom designed as DX systems: on the one hand, the Purging from some evaporators
liquid ammonia is hard to completely vaporize when This is suitable for some gravity-driven systems with-
water is present, which will lead to liquid hammer; out hot gas defrost. In these systems, water remains
on the other hand, how can a thermostatic expan- in the liquid when ammonia vaporizes, and accumu-
sion valve function correctly when the saturated P-T lates in the evaporators.
relationship changes?
Water rectifier
Pumped liquid circulation systems could well avoid Part of contaminated ammonia is drained into the
the potential damages of water to the compressors. rectifier, where it is heated, with the ammonia va-
With only vapour entering the suction line, liquid porising and the water drained. This is the only way
hammer is avoided; and so long as there is not too of removing water for pumped liquid circulation sys-
much water in the liquid, the vapour will contain al- tems.
most no water (< the recommended max. of 0.3%),
For more information on water contamination and
which could effectively avoid the oil pollution by wa-
water removal in ammonia refrigeration systems,
ter.
please refer to IIAR bulletin 108.
While pumped liquid circulation systems effectively
It is necessary to mention that there is a downside to
avoid damage to the compressors, they still retain
the water content being too low – namely the possi-
the other penalties of water unnoticed:
bility of a specific kind of steel corrosion. However, it
COP of the system is reduced is not likely in a real-life system.
When there is water content, the saturated P-T rela-
Water will always end up in vessels, where only
tionship of the refrigerant will be different from pure
gas/evaporated refrigerant will leave it, e.g. low-
ammonia. Specifically, the refrigerant will evaporate
pressure separators or closed economizers.
at a higher temperature for a given pressure. This
will decrease the refrigeration capacity of the system There are many different water rectifiers and the
and increase power consumption. one shown in Application Example 9.3.1 is just one
of many different solutions.
Corrosion
Ammonia becomes corrosive with water present and
starts to corrode the pipe work, valves, vessels, etc.
Application Example 9.3.1: Water rectifier heated by HP condensed liquid and controlled by float valves
CVP
EVM
SVA
To suction line
REG ICS
BSV
SVA
ICFS
ICFE
Sight glass
Contaminated
SV4
ammonia
HP subcooled Water+ammonia
liquid solution
Procedure for removing water: De-energise the solenoid valve ICFE (for the contami-
nated ammonia feed line). After a certain time, all
Energise the solenoid valves ICFE (for the contami-
ammonia will be evaporated, and only contaminated
nated ammonia) and ICS+EVM. Contaminated am-
liquid will be left in the vessel. To drain the contami-
monia is drained into the rectifying vessel. The float
nated liquid from the vessel, the pressure inside the
valve SV4 will close when the liquid level in the ves-
vessel must be increased to a pressure above 0°C.
sel reaches the set level. Energise the solenoid valve
This is done by de-energising the solenoid valve
ICFE (for the HP condensed liquid).
ICS+EVM. Now the pressure inside the vessel is con-
Condensed liquid is fed to the coil inside the vessel trolled by the ICS+CVP. The water+ammonia solution
and starts to heat the contaminated ammonia. Am- should be drained carefully with a draining system.
monia starts to evaporate, and contaminated liquid
For safety considerations, safety relief valve BSV is
remains in the vessel. When ammonia evaporates in
installed on the vessel to avoid excessive pressure
the vessel and the liquid level drops, the float valve
build-up.
SV4 will open and drain more contaminated ammo-
nia into the vessel. After a certain time, based on ex-
perience, preparation for draining the contaminated
liquid can start.
Refrigeration systems can become contaminated, gasses cannot condense, they (usually) stay in the
leading to a significant reduction in efficiency or pos- high-pressure side where they, in sufficient amounts,
sibly a lack of capacity. Water, oil and air are the can block the condenser surface. Most gasses are
most common contaminants which should be han- heavier than ammonia gas at condensing pres-
dled for proper functioning of the system. This chap- sure/temperature and because of that, they will con-
ter deals with ‘air’ contamination and solutions for centrate on top of liquid surfaces. These locations
removing it. are the appropriate places to attempt to collect the
Non-condensables.
Referring to the contamination as ‘Air’ is a generali-
sation that covers a number of gases that all have in The below diagram shows the principle of what can
common the fact that at the temperatures and pres- happen in a condenser. The four different sections
sures that exist in a condenser, they cannot con- represent four possible scenario’s in a condenser
dense into their liquid form. Another common term (temperatures are examples):
is ‘Non-condensables’ (NC), which more accurately
describes the behaviour and problem. Since the NC
De-superheating. The discharge gas from the com- cooling that still exists on the outside of the coil will
pressor is cooled to saturation by the cooling outside sub-cool the refrigerant liquid.
the coil.
Liquid-filled section. This section is filled with refrig-
Condensing. The refrigerant is condensed by the erant liquid that is built up in the condenser, usually
cooling. as a result of incorrect piping out of the condenser.
In a correctly piped condenser, this section should
Air-filled section. On top of the liquid surface, the
not be present, but note that the liquid surface will
non-condensables will accumulate and remain fairly
be somewhere outside of the condenser, so the air
stationary. The liquid condensed in the previous sec-
will eventually accumulate enough to block some
tion passes through this air-filled section, where the
condenser surface. The cooling on the outside of the
coil will again result in a subcooling of the refrigerant In a condenser with proper function, the refrigerants
liquid. liquid is slightly subcooled, normally 1 to 1.5K. So, if
a subcooling (significantly) larger than that is ob-
Most people would think that subcooling is good,
served, then one or both of the problems from point
because it decreases the flashing to lower pressures
3 and 4 is present. Incorrect piping can be observed
and helps to prevent flash gas before expansion
from the outside (refer to the Condenser installation
valves etc. It is true that these benefits are present,
chapter), and if it is found to be correct, then a large
but subcooling created in the condenser uses sur-
subcooling signifies non-condensables in the con-
face that could have been used to keep the condens-
denser.
ing pressure down. So excessive subcooling from a
condenser is not a good thing. With an increased As the non-condensables accumulate above liquid
condensing pressure, the compressor needs to work surfaces, the appropriate place to collect these de-
harder to compress the refrigerant gas and the sys- pends on the condenser control. Please refer to the
tem efficiency drops. As a rule of thumb, the com- condenser control chapter for details on the conden-
pressor work increases 3-4% per degree Celsius of ser installation.
increase in condensing temperature.
Figure 9.3: Principle diagram of high-pressure float valve control for air-purging unit
Air
Air 2
4
Purger
5
6
The condenser (2) condenses the discharge gas from purger is passed to the low-pressure side through a
the compressor (1) and the float valve (3) passes it (small) float valve (6).
back to the low-pressure side. Since the liquid sur-
Note that most float valves have a small bypass be-
face is in the float valve itself, this is the appropriate
cause experience has shown that without it the float
place to collect non-condensables. An air purger (4)
valve can stop functioning. This is due to non-con-
is connected to the float valve through a solenoid
densables accumulating in the float valve preventing
valve (5) and any ammonia liquid created in the
the liquid surface from rising to open the valve. Con-
sequently, the bypass allows the non-condensables
1
Air
Air
7
Purger
2
5 6
8
3 Receiver
9
10
The discharge gas from the compressor (1) is con- sketched in the above drawing, the liquid level in the
densed in the condenser (2) and led to the receiver drop pipe is higher than the receiver level.
(3) for temporary storage before being led to the
In a low-pressure float valve system such as the one
low-pressure side through an expansion valve (4). To
above, non-condensables can accumulate in two dif-
allow for free movement of the liquid surface in the
ferent locations: on top of the liquid in the drop pipe
receiver, it is pressure equalized through the equali-
and on top of the liquid in the receiver. Conse-
zation line (5). However, this short circuits the con-
quently, the appropriate locations to purge the non-
denser and to ensure proper functioning of the con-
condensables are these two locations. Because of
denser, drop legs (6) needs to be installed with
that, the air purger (7) is connected to these two lo-
enough height to allow for a liquid build-up to com-
cations through two solenoid valves (8). Liquid cre-
pensate for the pressure loss in the condenser. As
ated in the air purger can be sent to the low-pres-
sure side through a dedicated float valve (10).
Note that it is important that only one solenoid valve Furthermore, it is important to ensure that liquid
on the purge points is opened at a time to avoid cannot accumulate in the air purger. The air purger
short-circuiting the system. In the above example, itself creates ammonia liquid through condensing
the pressure in the receiver is equalized to the dis- but unfortunate placement of the air purger and
charge line, but the pressure in the condenser outlet possibly an unfortunate placement of the purge
is lower because of the pressure loss in the conden- points can also lead ammonia liquid to the air
ser (which necessitates the drop leg in the conden- purger. The latter two should be avoided through
ser outlet). If both solenoids (8) are open at the proper installation and the drain valve (10) should be
same time, the drop leg function is compromised, sufficient to remove all liquid created. If the air
which would result in undesirable functioning of the purger is filled with ammonia liquid then it could
condenser system. lead the control to purge ammonia liquid rather than
ammonia-free air.
The free heat from de-superheating and/or condens- The purpose of control is to coordinate heat recov-
ing in the condenser can be reclaimed if there are re- ery and refrigeration:
quirements for heating in the plant. These include
The basic function of refrigeration should be ensured
heating of air in offices or shops, heating water for
whether heat recovery is running or not. The con-
washing or processing, preheating boiler feed water,
densing pressure should not be too high when heat
etc.
recovery stops. Furthermore, for DX systems, the
To make heat recovery an economic solution, it is condensing pressure should not be too low either
important to ensure that the free heat and the heat- (See section 3).
ing requirements match in terms of timing, tempera-
The requirements for heat recovery, e.g. the temper-
ture level and heat flow. For example, for production
ature and the heat flow, should be fulfilled.
of hot water, i.e. when heat at a high temperature
level is required, the de-superheating heat could be Trouble-free on/off control of the heat recovery loop
recovered; whilst for office heating, recovery of all according to demand.
the condenser heat could be considered.
Heat recovery control requires very sophisticated
A well-designed control system is crucial for trouble- design, which may vary from plant to plant.
free and efficient operation of refrigeration systems
with heat recovery.
for use in the shipping industry because it was nei- Triple point at a much higher pressure.
ther toxic nor flammable, whilst ammonia (NH3 or Critical point at a very low temperature.
R717) was more common in industrial applications
(ref. [2]). CO2 disappeared from the market, mainly
because the new "miracle refrigerant" Freon had be- While
come available and was marketed very successfully. the
triple
Ammonia has continued to be the dominant refriger-
point
ant for industrial refrigeration applications over the
and
years. In the 1990s there was renewed interest in
criti-
the advantages of using CO2, due to ODP (Ozone De-
cal
pletion Potential) and GWP (Global Warming Poten-
point
tial), which has restricted the use of CFCs and HFCs
are
and imposed limits on refrigerant charges in large
normally not important for common refrigerants,
ammonia systems.
CO2 is different. The triple point is relatively high at
CO2 is classified as a natural refrigerant, along with 5.2 bar [75.1 psi], but more importantly, higher than
ammonia, hydrocarbons such as propane and bu- normal atmospheric pressure.
tane, and water. All of these refrigerants have their
This can create problems unless suitable precautions
respective disadvantages.
are taken. Also, CO2’s critical point is very low:
Ammonia is toxic, hydrocarbons are flammable, and 31.1°C [88.0°F], which strongly affects design re-
water has limited application potential. By contrast, quirements.
CO2 is non-flammable and at normal conditions also
In the table below, various properties of CO2 are
non-toxic. However, CO2 is heavier than air and will
compared with those of R134a and ammonia.
collect in basements. Exposure to large CO2 concen-
trations can be fatal.
CO2 may be employed as a refrigerant in a number Transcritical CO2 systems were once only of interest
of different system types, including both subcritical for small and commercial applications, e.g. mobile
and supercritical. For any type of CO2 system, both air conditioning, supermarket refrigeration and small
the critical point and the triple point must be consid- heat pumps. However, with the phase-out of Freon
ered. refrigerants and concerns about the toxicity of am-
monia, transcritical CO2 has gained a significant mar-
The most common refrigeration cycle is subcritical,
ket share of new industrial applications. Transcritical
i.e. the entire range of temperatures and pressures
CO2 systems release heat at temperatures above the
are below the critical point and above the triple
critical point for CO2, thus making them suitable for
point. A single-stage subcritical CO2 system is sim-
applications worldwide. Transcritical CO2 systems
ple, but it also has disadvantages because of its lim-
and their applications are described in chapter 11.
ited temperature range and high pressure (Figure
10.1.1). Subcritical CO2 systems are therefore only The log(p)-h diagram for CO2 sketches a simple sub-
suitable in very cold areas or as a low temperature critical cycle and a simple transcritical cycle.
cycle in a cascade system.
(3) (2)
Transcritical cycle
(4) (1)
Subcritical cycle
The high pressure of CO2 offers advantages with regard to the diameter of pipework that is installed, as gas
density is high due to the pressure. Comparing to R134a and R717, the differences are clear.
A comparison of pump-circulating systems shows that for “wet return” lines, CO2 systems require much
smaller pipes than ammonia or R134a (table 3). In CO2 “wet return” lines, the allowable pressure drop for an
equivalent temperature drop is approximately 10 times higher than for ammonia or R134a wet return lines.
This phenomenon is a result of the relatively high density of the CO2 vapour. The below comparison is based
on a circulating rate of 3. The results are slightly different if the circulating rate is optimised for each refriger-
ant.
Table 10.2: Comparison of pipe sizes – wet return & pumped liquid lines
In the comparison of “dry suction” lines, the results are very nearly the same as in the previous comparison,
in terms of both pressure drop and line size.
Table 10.3: Comparison of pipe sizes – dry suction & HP liquid lines
For both recirculating and dry expansion systems, calculated sizes for CO2 liquid lines are much larger than those for
ammonia, but only slightly larger than those for R134a (table 1 and 2). This can be explained by ammonia’s much
greater latent heat relative to CO2 and R134a.
With reference to the table showing the relative liquid and vapour cross-sectional areas for the three refrigerants
(table 1), the total cross-section area for the CO2 system is approximately 2.5 times smaller than that of an ammo-
nia system and approximately seven times smaller than that of R134a. This result has interesting implications for
the relative installation costs for the three refrigerants.
Due to the relatively small vapour volume of the CO2 system and large volumetric refrigeration capacity, the CO2
system is relatively sensitive to capacity fluctuations. It is therefore important to design the liquid separator with
sufficient volume to compensate for the small vapour volume in the pipes.
The required compressor capacity for identical refrigeration loads is calculated for the three refrigerants (table 4).
As can be seen, the CO2 system requires a much smaller compressor than the ammonia or R134a systems.
For compressors of identical displacement, the capacity of the compressor for CO2 is times greater than for
ammonia and 13 times greater than for R134a.
The subcooling produced in a liquid riser of a given height “H” is calculated for the three refrigerants (table
5). The subcooling for the CO2 liquid riser is much smaller than that for ammonia and R134a. This characteris-
tic must be noted when designing CO2 systems in order to prevent cavitation and other problems with liquid
CO2 pumps.
The CO2 compressors also benefit from the high suction density, so the suction swept volume of the CO2
compressors is much smaller than for R134a and R717, however it must be noted that these numbers are
only for the low-pressure part of the system (condensing temperature is -15°C / -5°F).
One thing to consider is that the beneficial relationship between CO2 saturation pressure and temperature,
which allows for high pressure losses without significant temperature loss, leads to another effect. In a pump
drop leg from a pump separator, the pressure increases due to the liquid column on top and thus effectively
creates subcooling of the liquid in the bottom of the leg. In this case, the CO2 pressure/temperature relation-
ship becomes a disadvantage. The subcooling in K/F is much smaller than with other refrigerants. This is sig-
nificant, as even a small heat ingress in the drop leg moves CO2 closer to saturation – in % of the total sub-
cooling – than the other refrigerants. And since the subcooling expresses the height available to the pump as
NPSH, it can easily be too little, leading to cavitation.
CO2 is most commonly used in cascade or hybrid system designs in industrial refrigeration. CO2 cascade sys-
tems can be designed in different ways, e.g. direct expansion systems, pump-circulating systems, CO2 in vol-
atile secondary “brine” systems, or combinations of these.
This section covers subcritical CO2 systems in indus- Figure 10.3.1: Comparison between R717 and CO2
trial applications. Transcritical CO2 systems are de- defrost.
scribed in chapter 11.
Figure 10.3.2: Principal diagram - Cascade system with 1 evaporating level and CO2 hot gas defrost
CO2 R717
CO2 defrost
compressor
CO2
compressor
CO2 receiver
Cascade
cooler
Condenser
CO2 evaporator
Figure 10.3.3: Principle drawing - cascade system with 2 evaporation temperature levels and CO2 hot gas
defrost
CO2 R717
Defrost compressor
MT compressor
Cascade
cooler
10.3.4 and 10.3.5 shows a low-temperature refriger- Figure 10.3.4: Comparison between R717 two stage
ation system using CO2 as a “brine” system with am- and CO2 volatile brine cascade cycles
monia on the high- pressure side.
Figure 10.3.5: Principal diagram - Cascade system with CO2 as a volatile brine system
CO2 R717
CO2 receiver
Cascade
cooler
Condenser
CO2 evaporator
Figure 10.3.6 shows a mixed system with flooded side could also be a flooded evaporator with a low-
and DX-system, e.g. for a refrigeration system in a pressure separator, but for the sake of simplicity it is
supermarket, where two temperature levels are re- shown as a DX evaporator.
quired. The low-temperature evaporator on the CO2
Figure 10.3.6: Principal diagram - Cascade system with two temperature levels (supermarket system)
CO2 R717
Condenser
DX system
10.3.1 Efficiency
In CO2-NH3 cascade systems, it is necessary to use a However, compressors running with CO2 are more
heat exchanger. Using heat exchangers reduces sys- efficient and heat transfer is greater. The overall effi-
tem efficiency, due to the necessity of having a tem- ciency of a CO2- NH3 cascade system is not reduced
perature difference between the fluids. when compared to a traditional NH3 system.
Figure 10.3.11: Typically used design pressures in 2-stage CO2/ammonia cascade system
Pressure
Supercritical Vapour
Vapour
50 bar [725 psi]
Liquid
50 bar [725 psi]
Vapour
Liquid
Liquid 35 bar [507 psi]
20 bar [290 psi] Vapour
20 bar [290 psi]
Solid - Liquid
Liquid - vapour
0% solid CO2 at
50% solid CO2 at the triple point
Solid the triple point
Solid - Vapour
3% solid CO2 at
the triple point
Vapour
Vapour
Enthatpy (J)
If the set pressure of a safety valve in the vapour If a pressure relief valve is set to relieve liquid at 20
phase is 50 bar [725 psi], e.g. the middle line, the re- bar [290 psi], the relief products would pass through
lief line pressure will pass the triple point and 3% of the triple point, whereupon 50% of the CO2 would
the CO2 will be converted into solid during relief. In convert into solid upon further relief, subjecting the
a worst-case scenario (e.g. a long relief line with relief line to a high risk of blockage.
many bends), solid CO2 may block this line. The most
Thus, to safely protect liquid lines against formation
effective solution to this problem would be to mount
of dry ice, connect safety relief valves to a point in
the safety valve without an outlet line and relieve
the system at a pressure higher than the triple point
the system directly to the atmosphere. The phase
pressure of 5.2 bar [75.1 psi], e.g. internal safety
change of the CO2 does not take place in the valve,
valves only for liquid lines.
but just after the valve (in this case, in the atmos-
phere).
10.4.2 Evacuating CO2 systems prior to start-up
Because of ammonia’s high affinity to water, evacua- Removal of water
tion of such systems is not as critical as it is for HFC The boiling temperature of the water will reduce as
and CO2 systems. CO2 is very sensitive to water in the pressure is reduced in the system. Residual heat
the refrigeration system, thus starting up with a dry from pipes and vessel walls can evaporate the re-
system is the key to keeping a dry system. Refrigera- maining water if it is well-distributed in the system.
tion pipes are usually left open to the atmosphere
when the system is being constructed. Therefore, The recommendations according to IIAR are as fol-
water can condense in the pipes during the night, lows:
and this is why it is important to evacuate all water The vacuum pump capacity should be selected ac-
and air from the system before charging refrigerant. cording to the internal volume of the refrigeration
When evacuating a system before first start-up after system, so that the system can be evacuated to a
construction or maintenance, two things are vacuum pressure of 0.65 kPa (5,000 microns mer-
achieved: cury) where the boiling point of water is around 1°C.
Note that a lower vacuum can result in the remain-
Removal of non-condensable gases, for efficient con-
ing water freezing. This causes the evaporation to be
denser operation
much slower, possibly leading to the incorrect con- an additional evacuation is recommended. The last
clusion that the system is empty of water. vacuum should be broken with refrigerant-grade
CO2 VAPOUR.
Normally multiple evacuations are performed. A vac-
uum is pulled to 0.65 kPa (5,000 microns). The vac- WARNING: THE VACUUM MUST NEVER BE BROKEN
uum is relieved with dry nitrogen, which then ab- WITH LIQUID CO2. This will form dry ice, clog pipes
sorbs more of the residual water vapour in the sys- and immediately reduce the temperature to -78.5°C
tem. Another vacuum is pulled to 0.65 kPa (5,000 (-109.3°F).
microns). If the pressure drops slowly or resides in
between 1.32 kPa (10,000 microns) and 0.65 kPa
(5,000 microns), there is still water in the system and
10.4.3 Charging CO2
It is important to start up with CO2 in the vapour as a solid or vapour inside the refrigeration system.
phase and continue until the pressure has reached Also, the system will exhibit very low temperatures
5.2 bar [75.1 psi]. It is therefore strongly recom- until the pressure is sufficiently raised (Figure
mended to write a procedure for charging a CO2 sys- 10.11.1). For example, at 1 bar [14.5 psi] the subli-
tem. One must be aware when charging a refrigerant mation temperature will be –78.4°C [–109°F].
system that until the pressure reaches the triple
point, the CO2 can only exist
systems and must always be avoided. This risk is the relative liquid volume
even higher for CO2 systems than for ammonia or
30
20
PR717
PR134a
10
0
0 10 20 30
Temperature [°C]
10.5 Conclusion
CO2 has good properties, particularly at low tempera- are cascade systems with ammonia on the high-tem-
tures, but it is not a substitute for ammonia. The perature side of the system.
most common industrial CO2 refrigeration systems
CO2 is in many aspects a very uncomplicated refriger- 52-65 bar is good. Several manufacturers of equip-
ant, but it is important to realize that CO2 has some ment for traditional refrigerants can also supply
unique features compared with other common re- some components for CO2 systems. The availability of
frigerants. Knowing the differences, and taking these components for high-pressure industrial CO2 refriger-
into account during design, installation, commission- ation systems is growing, but the availability of criti-
ing and operation, will help to avoid problems. The cal components is an important factor in the growth
availability of components for industrial CO2 refriger- rate of CO2 use.
ation systems with pressures up to approximately
CO2 is an odorless, colorless substance classified as a The TLV safety limit is 25 ppm for ammonia and
non-flammable and non-toxic refrigerant, but even 5000 ppm (0.5%) for CO2.
though all of these properties may seem very posi-
Approx. 0.04% CO2 is present in the air. With higher
tive, CO2 also has some disadvantages.
concentrations, some adverse reactions are re-
Since CO2 is odorless, it is not self-alarming if leaks ported:
occur (ref. [6]). 2% 50% increase in breath rate
3% 100% increase in breath rate
CO2 is heavier than air, so it sinks to the ground or 5% 300% increase in breath rate
floor level. This can create dangerous situations, es- 8-10% Natural respiration is disrupted and breathing
becomes almost impossible. Headache, dizziness,
pecially in pits or confined spaces. CO2 can displace sweating and disorientation.
oxygen so much that the resulting mixture is lethal. > 10% Can lead to loss of consciousness and death.
> 30% Quickly leads to death.
The relative density of CO2 is 1.529 (air=1 at 0°C
[32°F]). This risk requires special attention during de-
sign and operation. Leak detection and / or emer-
gency ventilation are always necessary.
The requirements for gas detection vary across dif- recommended that CO2 sensors be located 30-40
ferent countries. Below, one can find an overview of cm from the floor (below the breathing zone). For
gas detection requirements two of the most rele- CO2 monitoring when CO2 is used in a process (ra-
vant regulations for refrigeration systems; in Europe: ther than as a refrigerant), the recommendation is to
EN 378:2016 and in the USA: ASHRAE 15-2016. locate the sensor in the breathing zone, 1.5 metres
from the floor, and where people frequent.
Location of gas detectors
If mechanical ventilation exists in a machinery room,
There are two methods of locating sensors:
air will move towards the fan. In problematic loca-
Point Detection, where sensors are located as near tions, a smoke tube can indicate air movements in a
as possible to the most likely sources of leakage. space and assist in the location of sensors.
Perimeter Detection, where sensors surround the Consideration should also be given to the possibility
hazardous area completely. of pockets of gas collecting in the event of a leak.
The most appropriate method or a combination is Locations requiring most protection in a machinery
selected depending on the size and nature of the or plant room would be around gas boilers, com-
site. pressors, pressurized storage tanks, gas cylinders,
storage rooms or pipelines.
10.7.1 Location guidelines
Detectors shall be located high/low according to the
density of the actual refrigerant. Since CO2 is heavier
than air, it will drop to the floor, which is why it is
LT Compressor
5 Cascade cooler
3
LT receiver
10.8.1 Possible control devices in case of high pressure in the CO2 separator
If the pressure in the CO2 separator rises above the If the pressure continues to rise, a solenoid valve can
normal range, the following steps can be taken to be forced open to provide a controlled release of the
minimize the escape of CO2: CO2 pressure down to a defined pressure.
The CO2 compressor can be forced to start, and the The last device is the safety valve, which operates at
CO2 liquid pump forced to stop to prevent relatively its set pressure.
warm liquid returning to the CO2 separator.
10.8.2 Possible control devices in case of low pressure in the CO2 separator
If the pressure in the CO2 separator drops below the separator. This also prevents stopping of the com-
normal operating range, the following steps can be pressor if there is a sudden drop in cooling load, e.g.
taken to minimize the risk of dry ice formation: if there is a freezing process with variations in the
For cascade systems, two refrigeration cycles must sors are started, to avoid the CO2 compressors cut-
be controlled carefully in order to function correctly. ting out due to high pressure. Control components
should coordinate the operation of the compressors
Control of cascade systems can be divided into:
on the low-temperature side and high-temperature
Condenser capacity control side to ensure a smooth operation. On start-up, a
Compressor capacity controls suction pressure control valve will ensure that the
CO2 compressors are not overloaded.
Cascade injection control
10.9.1 Condenser capacity control 10.9.3 Cascade injection control
Capacity control of the condenser can be done by The injection of refrigerant into the cascade heat ex-
step regulation or speed control of the fans. As regu- changer should be controlled to regulate the con-
lating input for the capacity control, the condenser densation pressure in the low-temperature circuit.
pressure should be selected. The reference for the It is recommended that the CO2 gas be de-super-
regulation can be defined in two ways; either as a heated before it enters the cascade heat exchanger,
fixed reference or as a reference that varies accord- since the gas typically is around 60°C, thus heat can
ing to the outdoor temperature. The reference for be rejected to the ambient air or used for heat re-
the condensing pressure is set in °C [°F]. covery. Furthermore, de-superheating will reduce
10.9.2 Compressor capacity controls thermal stresses in the heat exchanger and mitigate
For a CO2/ammonia cascade system, the high-tem- high heat flux from the CO2 gas, thus creating more
perature compressor, e.g. one of the ammonia com- stable conditions on the evaporation side.
pressors, should be started before the CO2 compres-
Compressor
controller
CO2 R717
Condenser
PC
controller
CO2
compressor
CO2 receiver
Cascade
cooler
Injection
controller
Experience globally shows that there are several pit- The valves (1) through (4) are shown in the following
falls in hot gas defrost systems, which can lead to in- principle diagrams for hot-gas defrosting systems,
effective systems and, in a worst-case scenario, seri- and they represent the following: (1) is the liquid
ous accidents if appropriate design and operation of supply valve, which controls the liquid supply to the
the system are not followed. evaporator during cooling mode. (2) is the suction
solenoid valve in the wet return line/suction line
10.10.1 Hot-gas defrost on pump-circulated evaporators in
CO2 systems which is a soft-opening valve. (3) is the hot-gas sup-
From an efficiency point of view, the goal is to return ply valve which is a soft-opening valve. (4) is the liq-
the highest amount of liquid condensate from the uid drain valve, which for flooded systems can be ei-
evaporator back to the liquid receiver. All liquid will ther a float valve (ICFD), or a back-pressure con-
be separated in the receiver and pumped out to the trolled valve (ICS+CVP).
evaporators in cooling mode. In Figure 10.10.1 be-
low, the hot gas defrost principle for a pumped cir-
culated low-temperature evaporator is shown.
Figure 10.10.1: Hot-gas defrost principle for a low-temperature pump-circulated system with defrost
compressor
Suction
Hot gas supply pressure valve
PC
valve (soft-opening) Min. 31 bar
Defrost
compressor
M
Max. 25 bar
3 8 5
PC Max. 45 bar
PC Pressure
control valve
Min. 30 bar
6
Condensate
drain valve
7 9
Suction solenoid
valve (soft-opening) To MT Receiver/
Cascade cooler
2 LT
LT separator compressor
Liquid drain
4 valve
To MT Receiver
As shown in Figure 10.10.1, discharge gas from the The LT compressor might only compress the CO2 to
low-temperature compressor (LT) is bypassed to a a saturation pressure of -10°C if evaporators at a me-
defrost compressor to increase the pressure to a sat- dium temperature level are present in the system. A
uration pressure well above 0°C. The hot-gas pres- defrost compressor is therefore needed to increase
sure depends on the desired defrost sequence time.
the pressure to the defrost pressure level and ac- be under high pressure and subjected to low tem-
count for the total pressure loss in the hot gas sup- peratures. Liquid in the defrosting pipelines can form
ply line, evaporator and liquid drain line. liquid ‘projectiles’ during the start of defrosting, be-
ing propelled through the system by large pressure
The hot gas is supplied by the defrost compressor in
differences. This can lead to failures, component and
Figure 10.10.1. In many cases the defrosting is done
piping fractures and leakages that are potentially le-
on demand from the system and must be available
thal. Liquid can be drained from the defrosting sys-
within a very short time. Because of this, it is not al-
tem by mounting a drain system in locations where
ways an option to stop the defrosting compressor,
the liquid will collect (low points in the piping). From
and it needs to be able to run in an ‘idle’ mode. The
there it can be drained back to the separator
pressure control valve (6) is equipped with two dif-
through a solenoid valve that is opened a few sec-
ferent pilot valve systems, either to ensure a differ-
onds before a defrost starts. Since expansion takes
ential pressure in “idle” operation of the defrost
place across this valve, the valve must be suitable for
compressor or to limit the maximum discharge pres-
that or a manual expansion valve (regulating valve)
sure of the defrosting compressor during defrosting.
must be placed downstream of the solenoid valve. A
A solenoid valve opens for the ‘idle’ pilot when no
HP float valve can also be used if available in the ap-
defrosting is performed, while it closes and passes
propriate pressure range. In the sketch, a solenoid
control to the other pilot during defrosting.
solution (7) is shown. It is important that the drain-
The suction pressure valve (5) ensures a maximum age is mounted in the right place. Alternatively, the
suction pressure for the defrosting compressor, hot gas supply valve (3) can be opened slowly, drain-
keeping it within its operational limits. ing the liquid rather than creating liquid projectiles.
Another possible solution is to reduce the pressure
During defrost, where the saturation pressure in the in the defrost system by keeping the condensate
defrost line drops, a check valve (9) installed in a by- drain (7) open whenever defrosting is not being per-
pass line from the LT compressor can feed discharge formed. If the pressure is at suction temperature
gas to the defrosting process. This gas needs no then no condensation can occur, however the de-
compression and, as such, is a ‘free’ defrosting ca- frosting system will need to be pressurized and de-
pacity. pressurized repeatedly.
The motor valve (8) ensures that a drop in pressure The system suggested here takes care of many po-
in the defrosting system does not result in an exces- tential problems, however it is up to the designer to
sively low or even negative pressure ratio for the de- evaluate whether the various parts of the system are
frosting compressor. necessary.
It is recommended that possible variations be con- The pressure levels shown in Figure 10.10.1 are just
sidered for the defrost compressor’s suction and dis- random example values and must not be used for di-
charge pressures to ensure that the compressor is al- mensioning purposes. Proper dimensioning of de-
ways within its operational limits. frost systems should be done by the constructor.
It must be noted that there is a possibility that refrig-
erant can condense in the hot gas pipelines, as it can
Figure 10.10.2: Hot-gas defrost principle for a low-temperature pump-circulated system without defrost
compressor
3 5
Condensate
drain valve
7
M
Suction solenoid
valve (soft-opening)
To MT Receiver/
6
2 LT Cascade cooler
LT separator compressor
Liquid drain
4 valve
To MT Receiver
. Which solution is most feasible depends on how it can be drained back to the separator through a so-
much time and energy is spent on defrosting the lenoid valve that is opened a few seconds before a
evaporators. Having a separate defrost compressor defrost starts. Since expansion takes place across
is an additional investment, but it is more energy ef- this valve, the valve must be suitable for that or a
ficient than using the LT compressors. However, the manual expansion valve (regulating valve) must be
investment is saved by using the LT compressors, placed downstream of the solenoid valve. A HP float
though one pays the penalty of inefficient use of the valve can also be used if available in the appropriate
compressor. Generally, if it is expected to perform pressure range. In the sketch, a solenoid solution (7)
defrosting a large percentage of the total operation is shown. It is important that the drainage is
time, the separate defrosting compressor will be the mounted in the right place. Alternatively, the hot gas
most economically sound solution, while a pressure supply valve (3) can be opened slowly, draining the
increase will be suitable for lower percentages. liquid rather than creating liquid projectiles.
Figure 10.10.3: Hot-gas defrost principle for direct expansion system with defrost compressor
The principle diagram in Figure 10.10.3 shows the The suction pressure valve (5) ensures a maximum
hot-gas defrost system for a direct expansion evapo- suction pressure for the defrosting compressor,
rator with a defrost compressor. Many of the control keeping it within its operational limits.
valves for the defrost compressor and hot-gas supply
During defrost, where the saturation pressure in the
line shown are similar to the control valves shown in
defrost line drops, a check valve (9) installed in a by-
Figure 10.10.1. The discharge gas from the LT com-
pass line from the LT compressor can feed discharge
pressor is bypassed to the defrost compressor,
gas to the defrosting process. This gas needs no
which increases the pressure to the hot-gas pressure
compression and, as such, is a ‘free’ defrosting ca-
level.
pacity.
The pressure control valve (6) is equipped with two
The motor valve (8) ensures that a drop in pressure
different pilot valve systems, either to ensure a dif-
in the defrosting system does not result in an exces-
ferential pressure in “idle” operation of the defrost
sively low or even negative pressure ratio for the de-
compressor or to limit the maximum discharge pres-
frosting compressor.
sure of the defrosting compressor during defrosting.
A solenoid valve opens for the ‘idle’ pilot when no It is recommended that possible variations be con-
defrosting is performed, while it closes and passes sidered for the defrost compressor’s suction and dis-
control to the other pilot during defrosting. charge pressures to ensure that the compressor is al-
ways within its operational limits.
Figure 10.10.4: Hot-gas defrost principle for direct expansion system without defrost compressor
Hot gas supply
valve (soft-opening) Discharge pressure
M control valve
3 6
Condensate
drain valve
7
Suction solenoid
M
valve (soft-opening)
2 8
LT
compressor
TC
1 MT receiver
Liquid drain 4
valve
TC
10.10.3 Hot-gas defrost pressure in CO2 systems give satisfactory results in most cases. This is equal
The defrost cycle time can be reduced by increasing to a saturated pressure range of 41 to 47 bar.
the defrost temperature. However, moisture clouds
can be created in the cold room at an excessively Please be aware of pressure losses in pipes, compo-
high defrost temperature due to fast melting and nents and controls between the compressor dis-
heating of the frost layer on the evaporator. If mois- charge and the evaporator, where typically 1 bar
ture clouds are created, the moisture goes back into pressure loss equals approximately 1°C. The com-
the room and not out of the defrost drain, which is pressor discharge pressure during a defrost cycle
not a desirable situation. must be high enough to overcome this pressure loss.
To defrost a CO2 evaporator with hot gas, the satu- Note: using the superheat of a discharge gas with a
rated temperature in the evaporator during the de- saturated pressure below zero degrees will not give
frost cycle should be sufficiently above zero degrees. satisfactory results. For a proper defrost, the con-
A saturated temperature range in the evaporator densing energy of the hot gas should be used.
during a defrost cycle between 7-12°C has proven to
In CO2 systems with traditional refrigeration com- With miscible lubricants, such as polyol ester (POE),
pressors, both miscible and immiscible oil types are the oil management system can be much simpler.
used (see Table 10.2 below). POE oils have high affinity with water, so the chal-
lenge when using POE is to ensure the stability of the
For immiscible lubricants, such as polyalphaolefin
lubricant.
(PAO), the lubricant management system is rela-
tively complicated. The density of PAO is lower than In volatile brine systems using CO2 as a secondary
the density of the liquid CO2. The lubricant therefore refrigerant, and in recirculating systems with oil-free
floats on top of the refrigerant, making it more diffi- compressors, no oil is present in the circulated CO2.
cult to remove than in ammonia systems. Also, to From an efficiency point of view, this is optimum be-
avoid fouling evaporators, compressor oil separation cause it results in good heat transfer coefficients in
with non-miscible oils must be highly effective; basi- the evaporators. However, it requires that all valves,
cally, a virtually oil-free system is desirable. controls and other components can operate dry.
The oil concentration in the pump separator in- Pure CO2 liquid must never be returned to the com-
creases gradually because the oil cannot be directly pressor as this will damage the compressor. It is
sucked back to the compressor with the gas. If the therefore imperative that the CO2 at the oil rectifier
oil concentration in the evaporator becomes too outlet is superheated.
high, the adhesive forces will make the oil "stick" to
The superheat can be controlled by a REG valve fit-
the heat-transferring surfaces. This reduces the ca-
ted downstream of the solenoid valve for an oil rec-
pacity of the plant.
tifier with natural circulation.
By constantly boiling off part of the oil/CO2 liquid
from the pump separator, the oil concentration in
the plant remains low. During the boiling process in
the oil rectifier, the CO2 liquid is sub-cooled and the
oil/CO2 liquid mixture from the CO2 separator is
boiled off and sucked back to the CO2 compressor.
Figure 10.11.1: Oil recovery system for soluble oils driven by gravity
Heat
exchanger
CO2 receiver
Oil rectifier
REG
EVRST
Figure 10.11.1 shows an oil recovery system based 10.11.2. Here the mixture is controlled by an AKVA
on natural circulation by taking a liquid/oil mixture expansion valve which is controlled by the superheat
from the bottom of the CO2 receiver standpipe. controller EKC 315A, however the AKVA could be re-
placed by an ICF valve with expansion valve module.
An alternative is to recover the liquid/oil mixture
from the liquid feed line where the flow is driven by Detailed application examples for oil recovery with
the circulation pump head as shown in Figure oil rectifiers are shown in chapter 6 (Oil Systems).
Figure 10.11.2: Oil recovery system for soluble oils driven by circulation pump head
Heat
exchanger
CO2 receiver
Oil rectifier
EKC 315A
AKVA
Cascade
cooler
LT Separator MT Separator
Receiver
LT Evaporator MT Evaporator
Oil receiver
Heater
Oil recitifier
TC
In ammonia systems, the oil is changed regularly and Modern systems use filter driers to maintain the wa-
non-condensables are purged frequently to minimize ter content in the system at an acceptable level.
the accumulation of oil, water and solid contami-
The acceptable level of water in CO2 systems is
nants that can cause problems.
much lower than with other common refrigerants.
Compared to ammonia systems, CO2 is less sensi- The diagram in figure 10.12.1 shows the solubility of
tive, but if water is present, problems may occur. water in both the liquid and vapour phases of the
Some early CO2 installations reported problems with CO2 liquid and vapour as a function of temperature.
control equipment, among other components. Inves- The solubility in the liquid phase is much higher than
tigations revealed that many of these problems were in the vapour phase. The solubility in the vapour
caused by water freezing in the system. phase is also known as the dew point.
Liquid
Maximum solubility [ppm]
Vapour
The diagram in Figure 10.12.1 shows the maximum If the water is allowed to exceed this limit in a CO2
water solubility in ppm in CO2 with varying tempera- system, problems may occur, especially if the tem-
ture. The maximum solubility is about 10 times perature is below 0°C. In this case, the water will
higher in liquid CO2 than in vapour CO2 for the tem- freeze, and the ice crystals can block control valves,
perature range shown. solenoid valves, filters and other equipment. This
problem is especially significant in flooded and direct
Below these levels, water remains dissolved in the
expansion CO2 systems, but less so in volatile sec-
refrigerant and does not harm the system. Water
ondary systems because less sensitive equipment is
(H2O) molecules are dissolved if the concentration is
used.
lower than the maximum solubility limit, but they
precipitate out of solution into droplets if the water
concentration is higher than the maximum solubility
limit.
CO2 is a non-polar molecule, so the removal process The relative humidity is highest in the wet return line
is different. Like water molecules, CO2 molecules are since vapour CO2 has a lower solubility of water
small enough to pass through the molecular sieve. than liquid CO2. However, the relative humidity in
However, the water molecules adsorbed on the mo- the wet return line depends on the circulating rate.
lecular sieve tend to displace the CO2 molecules, In a DX system, the variation of the relative humidity
due to the difference in polarity. Zeolite filter driers differs, but also in this case the highest concentra-
cannot be used in ammonia systems, because both tion is in the suction line.
water and ammonia are very polar. Even though the
driers function differently in this respect in CO2 sys-
tems, the efficiency is good. The water retention ca-
pacity is approximately the same as in R134a sys-
tems.
Figure 11.1. Principle of a condensing process in a Table 11.1: Critical pressure and temperature for dif-
log(p)-h diagram ferent refrigerants
To overcome this problem, CO2 can be compressed phase change, which also means that when rejecting
to a pressure level above the critical pressure, thus heat above the critical point, the constant condens-
the CO2 can reject heat at a temperature above ing temperature no longer exists. With decreasing
31.1°C. When compressing CO2 beyond the critical enthalpy, the CO2 temperature is cooled down at a
point, the refrigeration process is called “transcriti- constant pressure. A gas cooler is used for rejecting
cal”. Above the critical point, there is no defined the heat, and the control is different compared with
condensers. An example of this process is show in means of condensing, the transcritical cycle by
Fig. 11.2. Fig. 11.3 shows a two-stage refrigeration means of gas cooling.
cycle for CO2. The sub-critical cycle rejects heat by
Fig. 11.2. CO2 in transcritical cycle Fig. 11.3. CO2 in a 2-stage transcritical operation
As explained, at temperatures higher than the criti- changes when CO2 is cooled. This makes gas coolers
cal point, CO2 is in a transcritical phase, unable to different from both water-to-refrigerant heat ex-
condense. The gas can only be cooled down and will changers, where the heat capacity is constant, and
not change phase. Consequently, pressure and tem- condensers, where the heat capacity in the gas
perature are no longer interdependent during the phase is relatively low and very high when gas starts
heat rejection process. The heat capacity of CO2 also to condense (Fig. 11.4).
Fig. 11.4. Heat rejection process of CO2 in sub-critical (condensing) and transcritical (gas cooling) state.
Gas coolers are used for rejecting heat when operating a transcritical CO2 system, since phase changes of
CO2 above the critical point are not possible and do not occur or behave the same way as condensation does
in a subcritical cycle.
In contrast to condensers, the refrigerant temperature is not constant in the gas cooler. It is therefore im-
portant to design a gas cooler with minimal thermal contact between gas cooler sections on the refrigerant
side, in order to avoid heating the cooled CO2 refrigerant at the gas cooler outlet.
11.1.2 Design of gas coolers
A CO2 gas cooler must be able to handle pressures of the refrigerant circuit to the cold end, which
that are a lot higher than pressures seen in a nor- would significantly reduce the efficiency of the gas
mal condenser with phase change, thus it needs to cooler. To reduce this heat flow as much as possi-
be more robust.The heat transfer in a CO2 gas ble, the thermal contact between the gas cooler
cooler also differs from a condenser. Where heat is sections must be minimized. The complete heat ex-
rejected at a constant temperature in a condenser, change between the gas cooler and the air must be
the temperature and thermodynamic properties counter-current flow or cross-counter-current. The
change a lot in a gas cooler on the refrigerant side. last tubes with the refrigerant before leaving the
This means that the part of the gas cooler where gas cooler should be located where the coldest air
the CO2 enters the gas cooler has a higher temper- enters. The gas cooler outlet temperature of the
ature than any other part, while the lowest temper- CO2 must be as low as possible.
ature occurs at the exit. If the gas cooler is not con-
structed properly, heat could flow from the hot end
Subcritical operation
The gas cooler pressure is controlled based on the If the gas cooler outlet temperature is too close to
gas cooler outlet temperature, regardless of the ambient temperature, and the subcooling too
whether it is in subcritical or transcritical operation. low, the condensing pressure will be raised to create
In subcritical conditions, the system is controlled as a sufficient subcooling. If the gas cooler outlet temper-
conventional refrigeration system where the sub- ature is too low (and the subcooling too high) com-
cooling is the control parameter. See Fig. 11.6. Sub- pared with the ambient temperature, the gas cooler
cooling is the temperature difference between ambi- pressure will be reduced. At temperatures approach-
ent temperature and gas cooler outlet temperature. ing the critical point, the gas cooler needs to be con-
The gas cooler outlet temperature (Tgco) is meas- trolled in a different way, as it is approaching tran-
ured and compared with the ambient temperature. scritical operation.
Modern CO2 transcritical systems have been devel- steps. By doing so, 1 stage takes care of the cooling
oped since 2005. The systems were initially seen in demand in low evaporating temperatures (LT) and
Food Retail applications where they could support the 2nd stage takes care of the heat rejection of the LT
the growing demand for the use of natural refriger- compressors and/or the cooling demand in medium
ants. The systems gained in popularity and developed evaporating temperatures (MT).
successfully. These days, the systems are also used in
Particularly when LT cooling demand is needed, a
larger commercial refrigeration systems. Typically,
booster system is unavoidable because of the unavail-
the liquid is injected into the evaporators by means of
ability of compressors with such a high pressure ratio.
direct expansion control with electronic expansion
In addition, a booster system helps to increase system
valves. So they are often DX-operated systems.
efficiency and reduce the discharge temperature. The
The most popular commercial CO2 system types are low temperature stage (1st stage) often serves freez-
so-called booster systems. In principle, these are 2- ing applications, whereas the 2nd stage serves me-
stage systems, combined into one system as we often dium-temperature applications. Booster systems
see in NH3 systems. The benefit of a CO2 booster sys- with more temperature levels are also possible, but
tem is that the huge pressure ratio is divided into 2 rarely seen in commercial systems.
The booster system is the most common CO2 tran- characterized by one compressor group for MT and
scritical system. It is mainly used in colder climates one for LT, a high-pressure valve and a gas bypass
and on smaller systems in warm climates. The system valve and, finally, direct expansion (DX) liquid injec-
is the simplest system that can accommodate two tion into the evaporator. See a principle drawing in
suction temperatures and multiple evaporators. It is Fig. 11.7
13 14 1 2
7
LT compressor MT compressor
Gas bypass
valve
12 10 6 3
LT evaporator MT evaporator
Intermediate
receiver
9 Gas cooler
11
MT EEV 8
5 4
HP valve
LT EEV
The liquid injection of both the LT and MT evapora- higher than the MT evaporator pressure in order to
tors is maintained with superheat-controlled elec- create sufficient pressure for the expansion valves.
tronic expansion valves (LT and MT EEV). Typically, The liquid (8) expands in both the LT and MT expan-
the superheat is 6 K -10 K depending on the combina- sion valves, both into (9), the MT evaporator, and into
tion of evaporator design and injection control. Often (11), the LT evaporator. This closes the cycle. Oil
higher superheat is seen on CO₂ systems compared to transport in the system is relatively simple since the
conventional systems. A special control algorithm typically miscible oils are used in these systems, and
evaporators is used to control the evaporators to the the DX operation ensures that oil does not accumu-
minimum superheat. Typically for commercial sys- late. The oil is transferred back to the suction lines of
tems, the evaporation temperature for MT is from - the compressors using the gas flow. Oil transfer with
6°C to -10°C, and on LT the evaporation temperature CO₂ is easier than with conventional refrigerants due
often ranges from -35°C to -30°C. The gas from the LT to the high density of the gas and good miscibility of
evaporators (12) is compressed in the LT compressor the oil and liquid. The booster system is simple and
(13) and is mixed with the gas from the MT evapora- has been used in supermarkets on a larger scale since
tors (10) and the gas from the gas bypass (7). This mix- 2007. It also has the largest installation bases of all
ture enters the MT compressor (1), where it is com- transcritical systems. The pros of the booster system
pressed (2), enters the gas cooler (3) and is cooled are simplicity and good scalability (from small to large
down. The gas outlet temperature (4) is controlled by systems). The cons are that in warm ambient temper-
means of the gas cooler controller. The high-pressure atures, the energy consumption is too high compared
(HP) valve expands the CO2 into a gas/liquid mixture to conventional systems. The high energy consump-
(5), which is injected into the intermediate receiver. tion can be addressed using some of the other system
Here the mixture is separated into liquid (8) and va- designs on the market.
pour (6). The intermediate pressure is kept slightly
In order to make the system more efficient, it is bet- called parallel compression booster systems. The
ter to have a dedicated compressor taking care of parallel compressor compresses some of the gas
the flash gas from the intermediate receiver pres- from the intermediate receiver (6), while the rest of
sure. This compressor is installed in a bypass line the gas is expanded (7) if necessary and fed to the
from the intermediate receiver, parallel to the MT suction line of the MT compressor (1). An example of
compressors, and that is why these systems are such a system is shown in Fig. 11.8.
Recompressing gas from a higher pressure level saves where the outlet temperature of the gas cooler will
some work from the MT compressor, and improves be high. A high outlet temperature of the gas cooler
the system efficiency compared to compressing eve- will result in a high amount of gas in the intermediate
rything from the MT pressure level as is done in a receiver when the cooled high-pressure fluid is ex-
booster system configuration. The benefit of parallel panded. The corresponding log(p)-h diagram is
compressions is especially seen in warmer climates, shown in Fig. 11.9.
In colder periods, the system works as a booster sys- sure flash gas (6). The gas bypass valve closes. Be-
tem, but in warmer periods the amount of flash gas cause of the higher suction pressure of the parallel
(5) from the HP expansion valve increases and the compressors, the efficiency of the system is better
parallel compressors take more intermediate pres- compared with a standard booster system.
Considerations
There are some things that need to be considered is on the system, and if this is sized for maximum load
when designing a system with parallel compression. then it will often be too big to have a good part load.
The consequence of using an oversized parallel com-
With higher suction pressure for the parallel com-
pressor is running periods that are too short, and thus
pressors, the oil carryover of the compressor in-
many unnecessary start-stop cycles. On the energy
creases. That in itself is not necessarily a problem, but
usage side, this configuration offers a very limited
it can be a challenge for the oil management system,
saving since it only runs in periods with high ambient
because all the oil consumed by the parallel compres-
temperatures and high load. Very often a better sys-
sors must be fed back because there is no oil in the
tem is achieved if the parallel compressor is sized to
suction gas. If the oil amount in the system is too
run at low temperatures and in part load. The conse-
great, the LT compressors can also be flooded be-
quence is that the parallel compressor will then be
cause they receive more oil than can be discharged
undersized in warm periods with
with the gas. Very often, only one parallel compressor
high load, but the system will compensate partly by often results in better total energy consumption be-
increasing the receiver pressure and bleeding the re- cause the parallel compressor has more hours of op-
maining gas through the gas bypass valve. This very eration.
Depending on the system, the intermediate receiver pressure can either be set to a certain pressure or con-
stantly adjusted. An adjusted intermediate receiver pressure can lead to energy savings compared to a fixed
pressure.
In Fig. 11.10, the blue cycle represents a traditional If the receiver pressure is raised, represented by the
parallel compression cycle with optimal receiver pres- red line (index h), the intermediate saturated temper-
sure for this specific gas cooler outlet condition. The ature (ITh) also rises. The amount of flash gas (Xh) for
medium temperature is shown as MT, the intermedi- the IT compressors reduces from Xm to Xh. This means
ate temperature cycle is marked with ITopt, the opti- that the intermediate compressors are supplied with
mal intermedium pressure. less flash gas, at a higher pressure level. The power
consumption therefore reduces. On the other hand,
the MT evaporators get more flash gas, at a lower The reduction of the receiver pressure, represented
pressure and the MT compressors need to produce a by the green line (index L) also leads to a higher
higher mass flow to meet the cooling demand. A power demand. The intermediate compressor re-
higher mass flow and a lower pressure result in a ceives more flash gas (Xl) at a lower pressure, which
higher power consumption. leads to a higher power consumption for the com-
pression. The MT compressor receives less flash gas
and its power consumption is reduced.
CO2 transcritical systems work by default with high systems more efficient. Danfoss has developed sev-
pressures but also with high pressure differences. eral ejector solutions, each with specific benefits and
For this reason, these systems are very suitable for functionality in the system. Ejectors’ efficiency de-
work with ejectors. Ejectors are a well-known tech- pends not just on the design, but also on a system’s
nology that have been used for more than 100 years layout, control algorithm, ambient conditions and
in different applications. Ejectors transform the maintenance practices. Danfoss has developed 3 dif-
available expansion energy delivered from the mo- ferent ejectors, each for a specific application and
tive flow into a driving force (entrainment flow). This resulting in a specific benefit. See examples in Fig.
driving force can be used in many ways to make the 11.11.
Fig. 11.11 A: High-pressure (HP) ejector, B: low-pressure (LP) ejector and C: liquid (LE) ejector.
A B C
In all three cycles, the ejector is placed in the same range of CO2 transcritical rack controllers and valves
location; motive flow from the gas cooler, suction to support these developments. Typical features on
flow from the MT evaporator and outlet flow to the these controllers are:
receiver. The control is different. The Danfoss HP
Capacity control
ejector (system A) is designed and controlled to de-
liver a high-pressure lift and a relatively low suction Booster control
gas flow. The Danfoss LP ejector (system B) is de- Gas cooler control
signed and controlled to deliver a relatively high suc- Heat recovery
tion gas flow at a low-pressure lift. The Danfoss LE
Intermediate pressure optimization
ejector (system C) is designed to deliver a low liquid
suction flow at a high-pressure lift. Whatever is en- Oil management
NH3 is a natural refrigerant and is generally still con- maintenance protocols to use this toxic and flamma-
sidered the logical, obvious choice for large industrial ble refrigerant successfully and safely. Of course, NH3
refrigeration systems. This is mainly due to its excel- charge reduction is a constant goal in order to miti-
lent thermodynamic properties, it being environmen- gate risks. There are several system solutions for do-
tally friendly (ODP and GWP = 0) and for being widely ing this, but we focus in this chapter on NH3/CO2 cas-
available. This industrial refrigeration industry devel- cade systems, but also on CO2 transcritical systems.
oped safety- and design standards, excelled in inno-
vative system design and continuously safeguarded
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
In the principle diagram in Fig 11.13, the pump-circulating Fig. 11.13. Typical NH3/CO2 pump circulation
NH3 part is replaced by CO2 as a refrigerant. The CO2 re- system
mains in the subcritical state and is condensed in a cascade
cooler, which is cooled down by an NH3 refrigeration sys-
tem.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
system is optimised, from an efficiency point of view it cannot compete with a two-stage R717 system, alt-
hough it does come relatively close in colder climates.
The changing refrigerant trends and the successful adaptation of 2-stage commercial transcritical CO2 refrig-
eration systems working with direct expansion in food retail applications and small commercial refrigeration
plants, however, has increased the interest in pump circulation systems for larger refrigeration capacities or
typical applications like ice rinks, plate freezers and common air coolers.
Other principles are possible of course, e.g. a combi- large LT load is available (e.g. plate freezers) and
nation of pumped on MT and DX on LT, see Fig. only a low-load MT (ie working areas), the MT load is
11.15 where the LT load is relatively low compared relatively low compared to the LT load. Then it might
to the MT load. Sometimes, by contrast, when a be considered to do MT with a DX cycle. See Figure .
Fig. 11.15 MT pump circulation and LT DX Fig. 11.16. LT pump circulation and MT DX
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
System description
The system as shown in Fig 11.17 is a combination of the commercial booster system, with parallel compres-
sion as described in chapter 11.2.2, together with a subcritical CO2 pump-circulation system that is well
known from the NH3/CO2 cascades. The transcritical system is represented in light grey and the subcritical
pump system in black. The transcritical system is, in this case, a 2-stage system with a low-temperature (
LT,11) and medium-temperature (MT,10) suction line. The suction lines are not connected to the evaporators
as is the case in direct expansion systems, but to CO2 LT and MT liquid receivers respectively. These receivers
contain CO2 liquid which is pumped around through the evaporators. Liquid and CO2 gas are separated in
these receivers and that is why they are called separators. The CO2 gas from the separators is taken to the
compressor suction lines which compress it to the gas coolers, where it is cooled (6) and stored as liquid (8)
in the intermediate receiver of the transcritical system. The liquid level of this receiver is proportionally con-
trolled and the liquid expands into a liquid/gas mixture (13) into the MT separator. Fig.11.18 shows the
log(P)-h diagram of the system.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
MT system
In a direct expansion system, this liquid (8) would be pressure to overcome the friction losses of the valve
injected into the evaporators. In a pump circulation trains, pipes and the MT evaporators. It is possible to
system however, the liquid expands (13) through the pump slightly more liquid through the evaporator, so
MT feed valve and is injected into the MT separator. that the evaporator’s internal surface is fully wetted
The liquid (14) accumulates in the MT separator and and optimally used to transfer heat. The liquid/gas
the gas (19) is drawn into the MT suction lines. The mixture at the evaporator outlet (15) is sent back
liquid (14) is increased in pressure (14’) and pumped into the MT separator again, where the gas (19) is
to the MT evaporators. The pump creates a head separated from the liquid (14).
LT system
Apart from being pumped through the MT evapora- The pump creates a head pressure to overcome the
tors, the liquid (14) from the MT receiver also ex- friction losses of the valve trains, pipes and the LT
pands (16) through the LT feed valve into the LT sep- evaporator. It is possible to pump slightly more liq-
arator. Again, in a direct expansion system this mix- uid through the evaporator, so that the evaporator’s
ture would be injected into the evaporators. In a internal surface is fully wetted and optimally used to
pump circulation system, however, this mixture is transfer heat. The liquid/gas mixture at the evapora-
separated into liquid and gas. The LT liquid (17) accu- tor outlet (18) is sent back into the LT separator
mulates in the LT separator and the gas (20) is drawn again where the gas (20) is separated from the liquid
into the LT suction lines. The liquid (17) is increased (17).
in pressure (17’) and pumped to the LT evaporators.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Can handle high peak demands safely and reliably due to the two-phase state and liquid separation
Liquid overfeed ensures optimal internal wetted surface and thus optimal efficiency of the evaporator.
Liquid overfeed also creates a better heat transfer coefficient for the evaporator.
There is no superheat available, so evaporator control is simple.
No superheat means lower temperature difference between evaporating temperature and ambient
temperature, evaporating temperature can rise and efficiency will increase.
Some evaporators, often very specialized evaporators, are not suited for DX operation and thus
flooded is necessary.
Hot-gas defrost is the most effective and energy efficient defrost method and this is relatively simple
in a pump circulation system, because the condensate drain can be safely returned into the separators.
And when using liquid drain control, the efficiency even increases.
The slight liquid overfeed we call circulation rate. A typical circulation rate for industrial air coolers working
with CO2 as a refrigerant is between 1.2 and 1.5.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Danfoss Industrial Refrigeration offers a full portfolio range incorporates the ICS control valves, the ICM
of low-temperature steel valves and control solutions motor valves, the ICF modular valve stations and the
suitable for both NH3 and CO2 pump-circulation sys- SVL line components. All of these products are de-
tems. The majority of the valves belong to the signed for NH3 and CO2 and have a PS of 52 bar and
Danfoss Flexline™ series which offers clever simplicity, a wide range of capacities is available.
advanced flexibilty and time-saving efficiency. The
In Fig 11.19 we see a typical principle diagram for a pump-circulating system with hot-gas defrost. The princi-
ple is described in Chapter 5.6. With CO2 as a refrigerant, the same principle can be followed. However, be-
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
cause the pressures and especially the differential pressures are higher, some consideration is needed re-
garding valve selection. First of all, the maximum working pressure is higher compared with NH3. Systems
with hot-gas defrost typically need a PS of 52 bar, so the valves must be approved for that, please always
verify that. Secondly, in some cases, higher standstill pressures are requested. Danfoss Industrial
Refrigeration has some specific valve types rated for 65 bar, please contact Danfoss. If higher standstill pres-
sures can occur, a standstill unit is needed to keep the pressure in the system under the permissible maxi-
mum. Because of these specific CO2-related differentiators, in the next paragraphs, the evaporator valves
and valve stations are explained specifically in relation to CO2.
11.4.4 Danfoss Industrial evaporator controller, EKE 400
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Figure 11.20. Example of Danfoss Industrial evaporator control in a CO2 pump-circulated system
Highlights
Distributed Control Systems (DCS) reduce the installation cost for controls compared to central PLC systems
Easy-to-use Wizard enables quick setup of key parameters, reduced need for PLC programming in the field
CANbus communication for interconnection of multiple EKE 400 controllers and process alignment
The injected liquid at the correct temperature is pumped from a separator to the evaporators. When liquid is
needed, a solenoid valve in front of the evaporator is opened. A manual regulating valve is usually fitted after
the solenoid valve to allow the required circulation rate to be set and hydraulic balance to be achieved in the
system.
ON/OFF solenoid valve for temperature control and regulating valve for distribution control
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
The solenoid valve is opened for several minutes or low, i.e. between 0.1 and 0.4 bar, depending on the
longer, and during injection the mass of the needed opening pressure differential. The pressure
refrigerant flow is constant. The circulating rate is drop across the regulating valve depends on how the
controlled by a manual regulating valve (ICFR). It is system is balanced, but is typically between 0.5 and 2
important to set this regulating valve at the right bar. A Danfoss 12W AC or 20 W AC coil can typically
opening degree. Too high an opening degree will lead do the job. In a traditional flooded system, the liquid
to frequent operation of the solenoid valve which injection is controlled by a thermostat which
results in increased wear. Too low an opening degree constantly measures the air temperature. Several
will starve the evaporator of liquid refrigerant. A options are available: as shown in Fig 11.21. Please
check valve is also installed to prevent hot gas use Danfoss Coolselector calculation software for a
entering the liquid line during defrost. The pressure correct selection of these valves.
drop across the solenoid valve should be relatively
Option 1
The compact ICF valve station incorporating multiple should be relatively low. Please always refer to the
valves, like a stop valve (ICFS), filter (ICFF), solenoid minimum needed pressure drop keeping the valve
valve (ICFE), check valve (ICFC), regulating valve (ICFR) open. A 12 or 20 W AC Danfoss coil can typically do
and stop valve (ICFS). Other configurations are also the job.
available. The pressure drop across the solenoid valve
Option 2
A combination of standalone valves. For the solenoid valves (CHV-X) and stop/check valves (SCA-X) are suit-
valve, EVRS(T) and ICS are suitable for CO2 as a refrig- able for use with CO2 as a refrigerant.PS of EVRS(T) is
erant. For the line components, stop valves (SVA), limited. Please check the specs
manual regulating valves (REG), filters (FIA), check
Figure 11.21. Application example of pumped liquid circulation with solenoid and regulation valves for liquid
injection
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Pulse Width Modulation (PWM) valves for both distribution and temperature control
Instead of injecting periodically, as described above, in a flooded system is very versatile. The amount of
one can also constantly adapt the liquid injection to injected liquid can be controlled exactly, which
the actual demand. This can be done with a PWM increases the accuracy and energy efficiency of the
AKVA valve or an ICF with an ICFA solenoid module. system. It is important to size the PWM valve
The air temperature is constantly measured and correctly. It should be checked that the pressure drop
compared to the reference temperature with a digital across the valve in relation to the circulation rate
thermostat. When the air temperature reaches the provides enough capacity. The pressure drop across
set point, the PWM valve opening is reduced. This the PWM valve alone in relation to the requested
decreases the degree of opening during the cycle, circulation rate will define the max. capacity of the
resulting in less capacity. The duration of a cycle is PWM valve. Several options are available: as shown
adjustable. In a flooded system, this means that the in Fig 11.22. Please use Danfoss Coolselector
average refrigerant flow is constantly controlled and calculation software for a correct selection of these
adapted to demand. This approach to liquid injection valves.
Figure 11.22. Application example of pumped liquid circulation with PWM valves for liquid injection
Option 1
The compact ICF valve station incorporating multiple confurations are also available. The PWM valve mod-
valves, like a stop valve (ICFS), filter (ICFF), PWM valve ule is only available for the ICF20 and is called ICFA20.
(ICFA), check valve (ICFC), and stop valve (ICFS). Other Please contact Danfoss for available orifices and se-
lection.
Option 2
A combination of standalone valves. The (CHV-X) and stop/check valves (SCA-X) are suitable
AKVA10/15/20 valves are the only valves allowed for for use with CO2 as a refrigerant. PS of AKVA is lim-
PWM operation due to the design. For the line com- ited. Please check the specs.
ponents, stop valves (SVA), filters (FIA), check valves
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
A wet return valve station in a typical pump-circu- a hot-gas defrost cycle, there is a high differential
lated system is located at position 2 as shown in Fig pressure between the evaporator and the suction
11.23. The function of the wet return valve is to close line, so it is necessary to relieve the pressure slowly,
the wet return line during defrost. During cooling allowing the pressure to be equalized before opening
mode, the pressure drop across the valve is advised fully to ensure smooth operation and avoid liquid
to be as low as practically possible in order to avoid slugging in the suction line.
generating system losses. Furthermore, at the end of
The main selection criteria for such a valve are: For CO2, the relationship between pressure and tem-
perature (dP/dT) is much higher than for NH3, i.e. 0.1
low pressure drop
bar pressure drop at -40 °C (-40°F) results in 2.8 K
slow opening characteristics after defrost to temperature drop in NH3 and only 0.3K temperature
avoid liquid hammer or pressure shock drop in CO2.
Sufficient Maximum Opening Pressure Differ- Especially for CO2 where these pressure differentials
ence (MOPD) to overcome the high pressure are much higher compared to, for example, NH3, the
difference between the evaporator and the MOPD of a valve must be checked. The MOPD is de-
liquid separator upon opening just after a de- pendent on the valve type and for solenoid vales also
frost. on the coil power. If the MOPD of the valve is lower
than the actual differential pressure across the valve
prior to opening, the valve will stay closed.
Example
%FGSPTUUFNQFSBUVSF$
&WBQPSBUJOHUFNQFSBUVSF 5F
$ '
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Figure 11.23. Application example of CO2 pumped liquid circulation with suction valves for the wet return
line
Please use Danfoss Coolselector calculation software for a correct selection of these valves.
The ICLX
This is a mechanical 2-step opening controlled sole- with 2 solenoid valves and only needs 2 wires (1 sig-
noid valve, which equalizes the evaporator pressure nal) from the controller for the voltage supply to the
and automatically opens the 2nd step whenever the coils. The MOPD of the valve is dependent on the ex-
pressure is equalized sufficiently. The valve fully ternal pressure and the used coils. This is especially
opens driven by external pressure, i.e. hot gas, allow- important for CO2 because sometimes the requested
ing use of the kV value at full opening degree, result- external pressure is outside the compressor enve-
ing in a lower pressure drop. The ICLX is controlled lope. Please refer to the instruction manual of ICLX.
The ICSH
This is a dual position solenoid valve originally de- Steps 1 and 2 are controlled by an EVM pilot valve
signed for controlled opening of hotgas lines. How- and, for maximum operating freedom, step 2 can be
ever for applications with CO2 as a refrigerant, it’s made dependent or independent of step 1. The steps
also approved to be used in the wet return lines. can be controlled by a PLC where the delay between
Here, it equalizes the evaporator pressure after a de- steps 1 and 2 can be freely set.
frost cycle. Step 1 is 20% of the kV value of step 2 and
allows a smooth pressure build-up in the evaporator.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
The ICM
ICM: Proportional motor valve type. The valve is con- On/Off. The valve responds to a digital input contact
trolled by an actuator, ICAD. The ICAD motor is con- and the opening speed can be set to the requested
nected to the ICM valve with a magnetic coupling, en- demand. The valve is fully closed or fully open or mov-
abling easy service and maintenance activities with- ing towards one of these positions.
out the need to open the ICM valve. The valve is de-
The MOPD of these valves depends on the valve size
signed to be controlled in 2 ways:
and the quality of the supply voltage sent to the step-
Analogue. The opening degree is controlled, and the per motor.
lifting height responds proportionally with an ana-
logue input signal (i.e. 0-20/4-20mA and 0-10/2-10V).
An explanation of hot-gas defrost in a pumped circu- even when insulated. Because liquid in hot-gas lines
lation system is described in chapter 5.6. This solution can create serious liquid hammer and CO2 plants
must only be used in refrigeration systems with three work with higher system- and differential pressures,
or more evaporators. As a rule of thumb, only a third the risk of liquid hammer in CO2 hot-gas defrost sys-
of the total evaporator capacity can be under defrost tems is higher than with ammonia. Some design prin-
at a given time. All examples in this document are ciples should therefore be observed:
shown with hot gas injection into evaporators in the
top of the evaporator in the suction line. This method
is generally seen as a safe solution with a very low risk Slowly increase the pressure in the evapora-
of “liquid hammer”. Hot-gas defrost systems must be tor at the start of a defrost cycle. Use valves
designed and controlled correctly to achieve the ex- principles that secure a controlled and slow
pected operation, behaviour and result. During a opening.
cooling cycle, the hot-gas supply line is closed. How-
It is good practice to install the hot-gas lines
ever, during a defrost cycle, the hot-gas supply valve
with a slope, and then install drain facilities
is slowly opened and injects hot gas into the evapora-
at the lowest point. This could be a float
tor. Liquid and wet suction lines are closed during the
valve, i.e. ICF with solenoid and ICFD func-
hot-gas injection. The hot gas condenses in the evap-
tion, or a periodically activated expansion
orator and defrosts the ice on both the evaporator
valve.
and the drip tray. The condensed liquid is sent back
via the drain line to the wet return line. The defrost Ensure sufficient Maximum Opening Pres-
time is either controlled by a timer or with a temper- sure Difference (MOPD) of the hotgas sup-
ature sensor on the evaporator. Hot-gas supply lines ply valves to overcome the high pressure
are designed to transport hot gas. However, because difference between the hot-gas supply line
these lines cross cold rooms or long areas with rela- and the evaporator at start of defrost.
tively low ambient temperatures, it is often inevitable
that some of the hot gas will condense in these lines,
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Example
&WBQPSBUJOHUFNQFSBUVSF 5F
$ '
Figure 11.24. Application example of pumped liquid circulation with hot-gas valves for the hot-gas supply line
Please use Danfoss Coolselector calculation software for a correct selection of these valves.
The ICSH
ICSH: Dual position solenoid valve. Step 1 is 20% of ating freedom, step 2 can be made dependent or in-
the kV value of step 2 and allows a smooth pressure dependent of step 1. The steps can be controlled by a
build-up in the evaporator. Steps 1 and 2 are con- PLC where the delay between steps 1 and 2 can be
trolled by an EVM pilot valve and, for maximum oper- freely set.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
The ICM
ICM: Proportional motor valve type. The valve is con- On/Off. The valve responds to a digital input contact
trolled by an actuator, ICAD. The ICAD motor is con- and the opening speed can be set to the requested
nected to the ICM valve with a magnetic coupling, en- demand. The valve is fully closed or fully open or mov-
abling easy service and maintenance activities with- ing towards one of these positions.
out the need to open the ICM valve. The valve is de-
The MOPD of these valves depends on the valve size
signed to be controlled in 2 ways:
and the quality of the supply voltage sent to the
Analogue. The opening degree is controlled, and the stepper motor.
lifting height responds proportionally with an ana-
logue input signal (i.e. 0-20/4-20mA and 0-10/2-10V).
Figure 11.25. Application example of drain control in the liquid drain defrost line.
During defrost, ideally, all hot gas should condense this results in an efficiency loss. So for a safe and effi-
and return as 100% liquid to the liquid seperator. The cient defrost, it is very important that these drain
benefit for a pump circulated CO2 transcritical system lines are controlled. As explained in chapter 5.6, there
is that condensed liquid remains in the subcritical part are two possible ways of doing so.
of the system and will not interfere with the tran-
scritical cycle. However, without any control, large
amounts of high-energy gas flow uncondensed back
to the system, which have to be recompressed and
Pressure-controlled defrost
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
The first one is pressure-controlled defrost. With 45 to 54 ˚F) has shown to be very effective. However,
pressure-controlled defrost, the evaporator pressure it is unavoidable that during the defrost process,
is controlled, ensuring a defrost process sufficiently some blow-by gas will be formed (with relatively high
above the melting point of ice. A controlled pressure enthalpy) and sent back to the system. This must be
with a saturated temperature between 7 to 12˚C (+/- recompressed and is a loss. See Fig. 11.26.
Note: if pressure-controlled defrost is chosen, it is mounted downstream of the pressure control valve
important that the condensate of the LT system is in order to prevent MT pressure being drained into
drained into the separator of the MT system. This the LT system during cooling mode.
maximises system efficiency. A check valve must be
Proportional motor valve type. The valve is The MOPD of these valves depends on the valve size
controlled by an actuator, ICAD. The ICAD motor is and the quality of the supply voltage sent to the step-
connected to the ICM valve with a magnetic coupling, per motor.
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
To ensure the correct selection of these valves, the must be defined. This can be done in Coolselector as
defrost temperature, the defrost capacity factor, the explained in chapter 5.6. Please use Danfoss
main hot-gas supply temperature, the reduced hot- Coolselector calculation software for a correct
gas supply temperature, and the drain conditions selection of these valves.
Liquid-controlled defrost
The second option is liquid-controlled defrost. The minimum amount of blow-by gass. This liquid has a
liquid-controlled defrost method is more efficient relatively low enthaply. The liquid can be sent back
than a pressure-controlled defrost. It ensures that to the liquid separators. See an example in Fig.11.27.
condensed liquid is sent back to the system with a
This module is designed for the drainage of defrost condensed liquid if needed. It is very important to get
liquid. It can be mounted on ICF20. and keep the refrigerant in the liquid phase. The ICFD
The ICF20D module is designed for NH3 and the defrost module must be installed at the drain outlet
ICFD20C module is designed for CO2. of the evaporators, which must be located at the low-
The gas in the system upon start-up of the defrost est point of the evaporator and equipped with P-traps
process is removed only through a small gas bypass as explained in Fig 11.28 and chapter 5.6.
orifice that is built into the ICFD defrost module. Fur-
thermore, the orifice provides sufficient lift for the
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
It is important to take the necessary precautions to the nozzles during defrost will create a certain pres-
minimize the pressure drop to avoid flash gas. Any sure drop in the drain line. This pressure drop must
pressure loss will reduce the liquid drain capacity. For be taken into account when determining the total
evaporators with distribution nozzles at the drain out- pressure loss. Please use Danfoss Coolselector calcu-
let (side/bottom feed in Fig. 11.29), the liquid passing lation software for a correct selection of these valves.
Always install a P-trap at the drain line connection to the evaporator to collect the liquid. See Fig 11.28.
To minimize total pressure drop, the lifting height of the liquid should not exceed 5 m (16.5ft).
For further information regarding placement of the ICFD liquid drain,please refer to the relevant doc-
umentation.
Figure 11.29. The drain lines should always be located at the lowest point of the evaporator
Classified as Business
Application Handbook Industrial Refrigeration ammonia and CO2 applications
Hot gas defrost is the most efficient way of defrosting. performance. Experience globally shows that there
It is a so-called “internal” defrost, meaning the heat is are several pitfalls in hot-gas defrost systems, which
supplied from inside the evaporator tubes. This re- can lead to ineffective systems, and in a worst case
sults in a good internal heat transfer coefficient, with scenario, serious accidents if appropriate design and
minimum convection losses to the cold room, so less operation of the system are not followed. From an ef-
compressor power is needed to compensate for that. ficiency point of view, the goal is to return the highest
Because they are relatively fast and effective for re- amount of liquid condensate from the evaporator
moving ice compared to some of the other methods, back to the liquid receiver. All liquid will be separated
it is generally accepted as the standard in the indus- in the receiver, and pumped out to the evaporators in
trial refrigeration sector. Despite being proven to be cooling mode. A complete description of how to per-
very efficient systems, they need to be designed and form hot-gas defrost is described in chapter 5.6
controlled correctly, in order to obtain the expected
Please be aware of possible pressure losses in pipes, components and controls to the evaporator. The hotgas
supply pressure during a defrost cycle must be high enough to overcome this pressure loss. Note: using the
superheat of a discharge gas with a saturated pressure below zero degrees will not give satisfactory results.
For a proper defrost, the condensing energy of the hot gas should be used. See Fig. 11.30
When hotgas defrost of evaporators in a sub critical defrost pressure and lower then the allowed maxi-
CO2 system is applied, the supplied hotgas pressure mum working pressure. If it is produced with com-
must be lower than the maximum working pressure pressors, then basically there are 2 options:Create
of the parts of the subcritical system, where the hot- hotgas with the discharge gas of LT compressors, or
gas supply lines are connected to. In order to enable create it with the discharge gas of MT compressors.
a safe and efficient hotgas defrost, it makes sense to The main difference between these 2 compressor
produce hotgas with a pressure close to the advised types are the reached discharge pressures and the
working envelopes.
For a reliable oil distribution under all load conditions, sensor. This sensor controls an oil supply valve to the
the application of a suitable oil management system oil receiver. The valve controls both the oil flow to the
is essential. Based on the combination of CO2 and POE oil receiver and simultaneously maintain the oil re-
oil, the oil return in commercial direct expansion sys- ceiver pressure. The oil reservoir is equipped with a
tems has proven to be reliable. Good miscibility of liq- differential pressure valve, ensuring de-gassing of
uid CO2 and POE oil, as well as high vapour densities CO2. The differential pressure must be higher than the
on the suction side of the system, lead to an easy re- highest suction pressure applied in the system, e.g.
turn of the lubricant to the compressors, provided the intermediate pressure level in the case of systems
that similar velocities in suction lines, e.g. with HFC with parallel compression. A level sensor inside the oil
refrigerants, are applied. Considering only a small receiver ensures that the oil level regulators on the
number of compressors are in operation during part compressors only open if this oil receiver level is suf-
load conditions in a commercial application, e.g. dur- ficiently high. This is to avoid a hot-gas bypass to the
ing night time in winter. Consequently, mass flows compressor crankcase. For booster systems, the oil
and velocities inside the evaporators and suction lines level regulators are assembled on the compressors of
are reduced and the return of lubricant becomes each suction group and connected to the common oil
more challenging. A sufficient oil supply to the com- reservoir. In booster systems with parallel compres-
pressors under various operating conditions can be sion or Multi Ejectors and high loads for air condition-
ensured with proper oil management systems. In Fig ing compared to the MT and LT load, oil management
11.33, a simplified principle diagram is shown for oil is more sensitive. Possible options in the case of ap-
management and oil return in a CO2 transcritical sys- plying POE oils are pplication of highly efficient oil
tem with miscible POE oil. Such a system obviously separators and oil reservoirs with a larger volume.
starts with a highly efficient oil separator and level And smart control strategies (pressurize reservoir on
Figure 11.33 Oil management in a CO2 transcritical DX system with miscible POE oil.
11.7.2 Oil management in transcritical pump-circulating freon- and CO2 sub critical- pump circulated systems.
systems. If immiscible oil is used, it depends on the oil type and
system conditions where the oil rich layer is located
In CO2 pump circulation systems, the oil carried over in the liquid separator. Several collection points can
to the system ultimately collects in the liquid separa- be used to skim from the right location. Regardless of
tor. If there are more liquid separators, oil is collected the oil type, it has to be collected.
in all of them. This oil has to be rectified and sent back
to the compressors. The system oil can either be mis- In Figure 11.34, a principle diagram shows the oil
cible or immiscible. If miscible oil is used, the liquid management principle in a pump-circulated CO2
CO2/oil mixture can be relatively simply rectified transcritical system with only one temperature level
from the liquid separator. This is done with oil rectifi- on medium temperature and miscible oil.
ers, a well-known principle since many years in both
Figure 11.34. Principle of oil rectify- and return process in a pump-circulated CO2 transcritical system on MT
temperature and miscible oil
This is the same principle as described in chapter 6.3. In case the pump system only has an LT liquid separa-
The oil rectifier (B) essentially is a heat exchanger and tor, the principle of rectifying is the same. However if
boils off the oil-rich liquid CO2 into CO2 vapor and oil. the CO2/oil mixture is directly sent back to the LT suc-
In this example liquid is injected in the oil rectifier by tion lines, the LT compressors receive all of the col-
means of an electronic expansion valve (A), superheat lected oil, (included that lost from the MT/IT com-
controlled. The pump pressure enables the needed pressors) And as explained before, since the MT/IT
pressure drop across the expansion valve. The CO2 compressors have a much higher oil carryover than
vapor/oil mixture is sent back to the MT dry suction the LT compressors, the LT compressor would get an
line. For extra safety, a suction accumulator (C) can be overbalanced oil return, resulting in flooding. To over-
used to catch liquid drops. In the return line from the come that, the rectified oil can be collected in an oil
oil rectifier, sufficient speed is needed to secure oil receiver after the oil rectifier and sent back to the
being moved up to the suction line. The principle of parts of the system that need oil. Figure 11.35, shows
this is the same as in refrigerant risers. It is a possibil- a principle diagram of oil return from an LT liquid sep-
ity to run the oil rectifier with thermosyphon opera- arator with miscible oil .
tion if a pump is not available.
Figure 11.35. Principle of oil rectify- and return process in a pump-circulated CO2 transcritical system on LT
temperature and miscible oil
based on the distribution of capacity between LT and MT. In the case of a LT and a
MT separator that are both fed with condenser liquid, both have only vapor leaving and both need oil collec-
tion.
11.7.3 Oil rectifying and oil return in transcritical pump-circulating systems with immiscible oil
Oil rectifying in a pump-circulating system with im- where the oil collects – usually a number of nozzles in
miscible oil works similar to a system with miscible oil, the vessel. Which nozzle to use can be determined by
but the challenge is that the oil may collect at differ- the level if a level indicator is used, or it can simply be
ent levels in the separator. Depending on the oil type done by cycling through all collections points. After
and temperature range this might be on top of the collection from on or more of these points, the col-
CO2 liquid or on the bottom. Collecting this oil will be lected oil can be handled as in the examples above.
a matter of a device that can reach the different levels
The left part of the equation is oil flow into the LT sep- tor by the oil rectifier, expressed by the amount of re-
arator from the MT separator, specified by the refrig- frigerant being boiled off in the rectifier (giving the
erant flow multiplied by the oil content (%) in the MT rectifier capacity) and the oil content (%) in the LT
separator. The right side of the equation expresses separator. Rearranging this equation slightly gives an
the amount of oil being removed from the LT separa- interesting insight into the dynamics of this problem.
Suppose the content in the MT separator is 0.1% and in the oil rectifier. That leaves nothing for an actual
you want to keep 0.1% in the LT separator as well, cooling duty on the LT side, so that is hardly realistic.
then the simple math shows us that we need to evap- If we increase the LT oil content to 1%, then we need
orate all of the refrigerant flow into the LT separator
to evaporate 1/10 (= 10%) of the total LT flow in the and that will cascade down to the LT separator. So ul-
oil rectifier. timately the oil carryover from the compressors, to-
gether with the oil separator efficiency, is the most
The heat source of the oil rectifier is the subcooling of
important issue to manage. In some commercial sys-
the liquid from the MT into the LT, so we can actually
tems the oil carryover rate is around (or even above)
regain what is being boiled off in the oil rectifier as
1%, but that is not a problem when you run DX as you
subcooling, making it more or less energy-neutral.
will return the oil in the suction line immediately, and
However, there is a limit to how much heat we can
it will not accumulate in the evaporators. However,
extract from that flow. As an example of an MT tem-
on flooded systems you will get into the problems
perature of -5°C and an LT temperature of -30°C, then
mentioned above and, with insufficient handling, the
we have a maximum (!) of 25K to sub-cool the liquid,
oil content could be very high in the LT separator.
and even getting all of the 25K will require an infi-
nitely large oil rectifier. That energy content works An oil content that is very high could hurt the heat
out to around 20% of the total LT capacity available transfer in the evaporators, as just one of the many
to the oil rectifier. With a smaller difference between issues this can bring with it. The OCR of the LT/MT and
MT and LT the % is lower, so realistically we can guess IT compressors differ from each other, however the
that we can put aside 10% of the LT capacity for the average oil carryover will be close to that of the MT
oil rectifier, making the oil content in the LT separator compressors. This is because they carry over much
10 times the oil content in the MT separator. more oil than the LT compressors and obviously dom-
inate in quantity in a transcritical systems. Assuming
Applying the same rules for the content in the MT
that both rectifiers are in operation and that the rec-
separator, we will also find that it is impossible to
tifier capacity of each separator is proportional in re-
keep the oil content there below several times the
lation to its refrigeration capacity, this means that the
content in the inlet flow, e.g. from the compressors,
requested oil percentage in the separator defines the
oil rectifier capacity.
When applying heat reclaim in subcritical refrigera- unit between the high-pressure CO2 refrigerant and,
tion systems, there are certain limits that have to be for example, water for a hot water system. There-
considered. The primary limit of heat reclaim in sub- fore, it is possible to achieve very efficient heat re-
critical systems is that the condensation tempera- claim from the gas cooler. However, one should con-
ture is constant, which sets a natural limit on how sider the optimal condensation/gas cooler outlet
much heat can be reclaimed. Heat recovery systems temperature compared to the ambient temperature
for ammonia refrigeration systems are covered in when doing heat recovery.
chapter 9.5. When the CO2 is cooled in the gas
cooler under transcritical conditions, the tempera-
ture of the CO2 changes during the “phase change”,
as described in section 11.1.1. A low temperature
difference can therefore be kept in the heat reclaim
The economic feasibility of heat recovery should be the demand for hot water is somewhat constant
considered beforehand. Very little heat can be recov- throughout the year. In the figures below, examples
ered in cold periods, where the heating demand of temperature profiles are shown for heat reclaim in
might be high and vice versa. Hot water systems, e.g. a transcritical CO2 system and a subcritical CO2 sys-
for cleaning-in-place systems, could be a utility for tem.
which heat reclaim can be economically feasible, if
Figure 11.36. Heat reclaim in a transcritical CO2 sys- Figure 11.37: Heat reclaim in a subcritical CO2 sys-
tem tem
140 80
120 70
TCO2
TCO2
Tw ater
Tw ater 60
100
50
Temperature [°C]
80 Temperature [°C]
40
60
30
40
20
20
10
0
0 2 4 6 8 10 0 2 4 6 8 10
Q [kW] Q [kW]
In both systems, water is supplied at 10°C and 10 kW hot water systems, this is possible by heating water
of heat is recovered. For both systems, a minimum from a tap water supply temperature of around 10°C,
temperature difference of 5°C between the refriger- since the supply temperature of the water will set the
ant and the water must be observed. The tempera- “target” outlet temperature of the CO2 – the lower
ture glide in the transcritical system allows the water the water supply temperature, the lower the CO2
to be heated to 60°C. The constant temperature dur- outlet temperature – the more efficient the heat re-
ing condensation in the subcritical system limits the claim. However, the heat reclaim unit can not replace
heat transfer to the water and the temperature of the the gas cooler. The heat reclaimer should be installed
water reaches 29°C out of the de-superheater. For in series upstream to the gas cooler so that the heat
transcritical CO2 systems, the discharge temperature reclaimer can be used when there is a demand for hot
of the gas from the compressors could be well above water, for example. This demand can vary with the
120°C. With high discharge temperatures, there is a ambient temperature. Furthermore, ambient tem-
potential for heat recovery from the refrigeration sys- perature can also determine whether the system is
tem at the gas cooling pressure. In order to have an operated under transcritical conditions or under sub-
efficient heat reclaim, e.g. for hot water systems, the critical conditions.
CO2 gas needs to be cooled as much as possible. For
heat reclaim with two heat exchangers in series. In gas cooler. But the control strategy will be the same
this chapter, for the sake of clarity, there will be one as if more heat exchangers are needed.
heat exchanger for heat reclaim and one air cooled
From the compressor, the hot gas enters the first 3- cold gas goes through the second 3-way valve. This
way valve in tap water mode, where highest temper- valve directs the gas through the air-cooled gas cooler
atures are needed. In heat reclaim mode, the gas will or bypasses it directly to the high-pressure expansion
go to the heat reclaim heat exchanger. In the heat re- valve. In the gas cooler, the gas is cooled down further
claim heat exchanger, the gas is cooled down to as before it enters the high-pressure expansion valve.
low a temperature as possible. The most common This is the basic setup. There can be many variations
heat exchanger for heat reclaim is a tube-in-tube or of it, but this is the most common and most widely
plate heat exchanger. From the heat exchanger, the used.
11.8.2 Control strategy
To meet the objective of reclaiming the heat needed, at the needed temperature as efficient as possible, the
control strategy needs to cope with this. There are the following measures that can be used to do this.
The important thing is to use these measures in the controller. To explain a typical Danfoss In the follow-
right way to optimize the output of the system. The ing description will be followed by a small example.
Danfoss strategy is to do this in 6 steps. The heat load The focus is on heat reclaim with the following basic
on the heating system is feed back to the controller data for the example:
from the building management system or from a PI
Ambient temperature 0 °C
Water inlet temperature 25 °C
Water outlet temperature 65 °C
Exit temperature difference air cooled gas cooler subcritical 8 K
Exit temperature difference air cooled gas cooler transcritical 2 K
Exit temperature difference heat reclaim heat exchanger 5 K
Step 0
Step 1
The pump is turned on. There are different ways to switch in the water circuit is on and the temperature
control the pump speed, but normally the speed is in the water circuit is below 95°C, the 3-way valve is
controlled to maintain a fixed temperature out of the turned to position 1a-1c. The pump speed is adjusted
heat exchanger. However, temperature difference of so that the temperature setpoint is satisfied. This will
the water or ingoing water temperature can also be remove the part of the superheat with the highest
used. All of them make sense in different systems. temperature. If this is not enough to satisfy the heat
When the pump is at minimum speed and the flow load, the controller will be forced into step 2.
Step 2
The pump is still running according to the tempera- part of the system’s total heat rejection. By increasing
ture, but the high pressure is pushed up to make a the pressure, the part of the heat rejection that can
larger part of the heat available at the temperature be reclaimed increases and at the same time the dis-
needed. This is done by changing the reference set- charge temperature increases. However, at some
point in the high-pressure controller and thereby point it is no longer efficient to raise the pressure
closing the high-pressure expansion valve. The higher higher. The compressor workload would be too high
pressure increases the compressor workload but also and the reclaimed heat would not increase at the
hugely increases the heating capacity. In step 2, the same rate.
heat rejection in the air-cooled gas cooler is still a big
Step 3
The reference setpoint for the gas cooler fans is grad- in the heat reclaim system. Even when the fans are
ually increased up to the optimum COP, causing that stopped, the natural convection of the gas cooler is
at low ambient temperature conditions the fans stop. enough to take some capacity out of the system. By
This causes the heat rejection from the air-cooled gas reducing the condenser fan speed, the capacity is re-
cooler to decrease. This will result in a loss of cooling duced. Therefore, the part of the heat reclaimed in-
capacity, but the system will compensate by putting creases, and the part rejected to the ambient air de-
in more compressor capacity. This will also result in a creases.
higher compressor workload, but also more capacity
Step 4
The air-cooled gas cooler is bypassed to avoid natural in the heat reclaim system. At this point, no heat is
convection and thereby heat rejection from this part rejected to the ambient air and the system is basically
of the system. As in step 3, this reduces the cooling running as a heat pump system but with the control
capacity, but the system will compensate by putting sensor on the low-temperature side. By bypassing the
in more compressor capacity. This will also result in a gas cooler, all heat rejected from the system must go
higher compressor workload, but also more capacity into the heat reclaim system.
Step 5
In step 4, all heat put into the system is reclaimed. If lower than the other steps, but it represents an easy
the heating demand is still not satisfied, the load on solution for getting more heat. The efficiency should
the cold side of the system needs to be higher. This be looked at on a yearly basis, because the number of
can be done by adding an extra evaporator that takes hours running in step 5 should be taken into account.
heat from the ambient air. The efficiency of this is
Since it is possible to do a partial reclaim, the CO2 can The system can be forced into transcritical mode
be partially condensed in the heat-reclaim heat ex- when there is a need for heat reclaim. This will reduce
changer. When using more than one heat exchanger, the efficiency of the system, but the operation is safe
the problems grow accordingly, and the strategy be- because there is only one phase.
comes slightly more complex to prevent the various
The inlet water temperature can be kept high enough
problems that may occur. One problem that may oc-
(maybe 30°C) to ensure it is not possible to condense.
cur is that the liquid can build up in one part of the
This will not force the system to run transcritical, but
system, and then, due to the gas pressure, is pushed
will still reduce the efficiency. This control strategy
out into the system at high velocity, possibly causing
can be implemented with a mixing loop on the water
severe damage to parts of the system.
side.
This problem can be handled in many ways.
The pressure in the system can be controlled in such
a way that the superheat out of the heat-reclaim heat
exchanger is kept high enough to ensure condensa- Physically mount the heat exchangers and route the
tion does not occur. This is a safe and the most effi- piping to ensure that any liquid created will not accu-
cient way to control the process. mulate and is transported to the next heat exchanger
safely. This generally means downwards flow without
Ensure that the temperature between various heat
pockets.
exchangers is at an appropriate level.
In some system designs, condensation is not a prob-
lem, but this needs to be considered in the system de-
sign.
Since the temperature of the compressor discharge gas can be very high, measures must be taken to avoid
boiling of water in the water circuit of the heat reclaim heat exchanger.
11.8.4 Conclusion
Heat reclaim in a transcritical system can be attrac- shown that it is possible for correctly designed sys-
tive. Compared to HFC systems, the efficiency is tems, where the heat demand is not high, to elimi-
higher and the temperatures that can be obtained nate additional heat sources. This makes heat re-
are higher compared to HFC technology. It has been claim a very interesting option when looking at total
costs.
Close attention should be paid to precautions and bar/2030 psi. For practical and economic reasons, the
considerations when working with transcritical CO2 system is divided into zones which each have their
systems, due to the increased pressure levels in these specific design pressure. An example of such design
systems. A CO2 transcritical pump circulation system pressure levels for transcritical CO2 systems are
has different working pressures depending on the shown in Fig. 11.39 but can differ from system to sys-
system part. The variation can be wide. CO2 at satu- tem for design reasons, size of the liquid separators
rated freezing temperatures of -50°C/-58°F corre- and thethe actual LT/MT evaporating temperatures
spond to 6.8 bar(a)/89.6 psia. However, the transcriti-
cal discharge part is typically designed for 140
Figure 11.39. Typical design pressures in an industrial CO2 transcritical pump circulation system.
In this case, we typically see 6 zones: LT and MT evap- sign pressure of 52 bar is needed. The design pres-
orator zones, LT and MT separator zones, intermedi- sures for the separator zones are defined by the re-
ate pressure zone, and finally, the transcritical zone. quired working pressure of the separators. The inter-
For the LT and MT evaporator zones, the design pres- mediate working design pressures are 52/65 bar.
sure can be defined by looking at the evaporation Standstill pressures in large industrial systems are
temperatures. In that case, 40 bar should be suffi- typically lower than in smaller commercial systems
cient. However, when hot-gas defrost is applied, a de- because of the relatively large receiver volumes. The
General safety topics related to CO2 are described in chapter 10.4 to 10.7
Heat exchangers
Heat exchangers perform the primary duties of the Figure 12. below shows the heat exchangers that are
refrigeration/heat pump systems – heating and cool- normally used in a single-stage system. Note that
ing – as well as several internal functions. not all are necessary and that the heat exchangers
numbers (7) to (9) are not often all used at the same
For efficient operation of heat exchangers, it is nec-
time. Likewise, it is not normal to use all types of
essary that the system is both designed, constructed
evaporators – thermosyphon (1), pumped (2) and DX
and controlled appropriately.
(3) – in the same system. These variations are in-
cluded here to illustrate all possible variations. All
valves except expansion are omitted for clarity.
Figure 12.1: Overview of the most common heat exchangers in a refrigeration system
4
Oil cooler
Desuperheater
5
Superheater
Oil
separator
9 6
LP
Separator Condenser
2 Separator
1 7
Economizer
DX Evaporator
Thermosyphon evaporator: This type is a ‘flooded way that thermosyphon operation is not possible
evaporator’, signifying that more refrigerant is circu- (e.g. far away from the compressor/separator, for in-
lated than evaporated. Because of this, the exit flow stance in a cold store or a freezing tunnel). Plate
is a mixture of vapour and liquid and it is therefore freezers are another common type of pumped evap-
returned to a separator to ensure a dry suction gas is orator.
fed to the compressor. The thermosyphon evapora-
DX evaporator: DX is an abbreviation for ‘Direct ex-
tor is fed with liquid through natural circulation.
pansion’, signifying that the evaporator is fed with
Pumped evaporator: This type is also a ‘flooded high-pressure liquid through an expansion valve. The
evaporator’, but in comparison with the thermosy- control of the expansion valve ensures that the re-
phon, it uses a pump to feed liquid to the evapora-
tor. These are very often air coolers located in such a
frigerant return from the evaporator is fully evapo- Condenser: The condenser cools the compressor dis-
rated, e.g. with no liquid in it, and, as such, it can be charge gas and condenses it into liquid. Condensers
passed directly to the compressor. can be evaporative condensers (not shown), air-
cooled condensers (not shown) or a glycol/water-
Oil cooler: Screw compressors require oil cooling and
cooled heat exchanger as shown here. The heat de-
the oil cooler performs this task. Oil coolers can be
livered to the glycol/water circuit can either be dis-
glycol/water-cooled (as shown here) or thermosy-
persed by a cooling tower or used in a heat recovery
phon oil coolers (not shown) that evaporate liquid
system / heat pump.
from the condenser to cool the oil. Evaporated liquid
is returned to the compressor discharge line before Subcooler: The subcooler cools the condensed liquid
the condenser to be re-condensed. Water/brine- further using water/glycol or possibly air. With a
cooled oil coolers are often part of a heat recovery colder liquid being passed to the low-pressure side,
system or heat pumps. the compressor capacity increases. Subcoolers are
often part of a heat recovery / heat pump system.
De-superheater: The de-superheater cools discharge
gas from the compressor before entry into the con- Economizer: Screw compressors usually have an ad-
denser, usually for use in a heat recovery system or ditional port, the economizer port, that allows refrig-
heat pump. The higher temperatures in the de-su- erant to be fed in after the compression has started.
perheater enable a higher heat recovery tempera- As such, it can be used to compress additional refrig-
ture than is possible in the condenser. erant at a starting pressure above the evaporating
pressure, without compromising the compressor’s
capacity at evaporating pressure. Generally, two dif-
ferent economizer types exist – the ‘open’ econo-
mizer (not shown) and the ‘closed’ economizer. The
open economizer is a simple vessel without heat ex-
changers, so it will not be covered here. The econo-
mizer cools the condensed liquid further, increasing
the compressor capacity in the same way as a sub-
cooler. The cooling is performed by flashing and
evaporating some of the condenser liquid and this
vapour is passed to the compressor’s economizer
port. In the closed economizer, a heat exchanger
performs the cooling duty.
For the sake of clarity, four noteworthy additions to Side load: It is not unusual to add an evaporator to
the above diagram were not added. an economizer, allowing external cooling to be per-
formed at an additional (higher than evaporating
temperature) temperature level. This is often re-
ferred to as ‘side load’.
From evaporator
Economizer
separator
3 2
To evaporator
Figure 12.3: Inter-stage cooler Cascade cooler: A cascade cooler is the connection
between the two refrigerant circuits in a cascade
From evaporator
system. Typically, the low temperature refrigerant
Condenser will be R744 (CO2), while the high temperature re-
frigerant is R717. The cascade cooler condenses
Inter-stage cooler
1 R744. The cooling for this process is provided by
evaporating R717 at a temperature below the R744
condensing temperature.
2 5
To evaporator
R744 R717
In much the same way as on the economizer, a heat Typically, R744 is condensed at -10°C and R717 evap-
exchanger can be added to provide a refrigeration orates at -15°C. The temperature difference in the
duty at the interstage pressure (not shown), either cascade cooler can be considered an efficiency loss,
through thermosyphon operation or pumped opera- so it is recommended to examine the change in op-
tion. Alternatively, a separator can be added in par- erating cost (compressor power) versus the installa-
allel with the intercooler. tion cost of a larger cascade cooler that operates at,
for instance, a 3°C temperature difference.
To compressor
2 1
Convection: When heat is transferred between a liq- Finally, the properties of the wall between the two
uid, gas, or phase-changing refrigerant and a solid sides are usually given by the actual heat exchanger
material, e.g. when evaporating refrigerant flow through the materials and the geometry selected.
through the evaporator pipes, and heat is trans- All of these factors combine to form the total heat
ferred from the pipe wall to the evaporating refriger- transfer coefficient. It is noteworthy that it is the
ant. side with the lowest heat transfer coefficient (which
is the largest resistance to heat transfer) which dom- Figure 12.1.1: Temperature profile for co-current
inates the total heat transfer coefficient. For in- heat exchanger
stance, an evaporator with very low speed on the
water/glycol side will have a low heat transfer coeffi-
cient on that side, so the evaporative side can basi-
cally be very high without any significant difference
to the overall heat transfer coefficient.
12.1.1 Co-current vs counter-current In this case, the cold stream can be heated to 60°C
Co-current and counter-current are terms that refer and the hot stream can be cooled to 45°C. All other
to the direction of the flows in a heat exchanger rel- parameters are the same. The difference is that the
ative to one another. LMTD is higher at 20.0°C, some 25% of which is di-
Co-current: A co-current flow heat exchanger has rectly reflected in the capacity as well. As a conclu-
the hot and cold flow to flow in the same direction. sion, the counter-flow heat exchanger is much more
The figure above is a co-current heat exchanger. By efficient than a co-current.
having the flows in the same direction, a high heat Visually the difference in LMTD can be seen as the
transfer is achieved around the inlet of the heat ex- area between the two curves. Although the co-cur-
changer. However, for a co-current heat exchanger, rent starts out with a high temperature difference, it
the hot-side flow cannot be cooled below the outlet drops quickly to near zero, while the counter-current
temperature of the cold-side flow and vice versa, the maintains a large difference throughout the whole
cold-side flow cannot be heated above the outlet heat exchanger.
temperature of the hot-side flow.
12.1.3 Condensers
In a heat exchanger with phase change, it is a little
more complex. During the phase change the refriger-
ant will remain at a constant temperature, or con-
stant temperature glide (slope) for refrigerant mix-
tures, when the phase change takes place. Below is a
sketch of condensing ammonia in a heat exchanger.
Plate heat exchangers consist of layers of metal If the corrugation angle is small, the plate is referred
plates. The metal plates are designed as corrugated to as a long plate, since the flow path is long, and a
plates to create small channels between each plate, large corrugation angle yields a short flow path, and
which make plate heat exchangers very efficient the plate is referred to as a short plate. The flow
compared to other heat exchanger types, since a path for a long and a short plate is shown in Figure
larger surface area for heat transfer is obtained. 12.2.2.
The channels on a plate are typically formed as fish- Figure 12.2.2: Flow path for a long and short plate
bone shapes. The angle of the fishbone, the chevron
angle or corrugation angle, is an important design
parameter for a plate along with the depth of the
corrugations. They determine the length of the path
inside a channel that the fluid must travel. The chan-
nel and path lengths determine the pressure drop
and the heat transfer capacity of the plate heat ex-
changer. A fish-bone plate is shown in Figure 12.2.1.
Figure 12.2.1: A fishbone plate for a plate heat ex- Long: 30°
changer
Distribution area
Pitch
Pressing depth
The plates have gaskets mounted at the outer rim to Figure. The thick red front plate in the frame is called
make the space for the channels between the plates a ‘Head’ and the thick back plate is called a ‘Fol-
and gaskets mounted on the plate to keep the fluids lower’.
from mixing.
The semi-welded plate heat exchanger shown in Fig- are welded together, giving a low pressure drop but
also a low heat transfer rate.
ure could be a condenser, as the high-pressure hot
fluid is passed through the welded cassette. It is possible to change the flow direction of a media
in the plate heat exchanger by using a multi-pass so-
The cassettes in a semi-welded plate heat exchanger
lution. Changing the flow direction can be beneficial,
can have various properties depending on which e.g. for evaporators when running co-current in an
type of plates are combined into the cassette. The evaporation section to kickstart the evaporation
combination of cassette types that are used in the with a large temperature difference, while running
plate heat exchanger will determine the properties
counter-current in the superheating section.
of the PHE. Three types of cassettes are used in
semi-welded plate heat exchangers: The plate materials for semi-welded plates are typi-
cally stainless steel or titanium, which supports am-
Long: Long cassettes consist of two long plates that
are welded together, giving a high heat transfer rate monia, HFCs and brines.
and a high pressure loss.
The plate thicknesses available are 0.5 mm, 0.6 mm
Mixed: Mixed cassettes consist of a long plate and a and 0.7 mm. The thickness of the plates determines
short plate that are welded together.
The last plate in the plate rack, the end plate, does
not usually have connection ports where fluid runs
through as the other plates. When performing evac-
uation of the system before start-up, one should be
aware of the vacuum pressure that is applied to the
plate heat exchanger. If the connection ports are
large, an excessively low vacuum pressure can cause
the area of the connection ports on the end plate to
deform permanently. This affects the strength of the
plate heat exchanger and can lead to unwanted and
unsafe operation of the heat exchanger. One should
pay attention to the vacuum pressure that is used to
evacuate the system when plate heat exchangers are
installed. Typically, the thickness of the end plate
will be as thick as possible, e.g. 0.7 mm.
12.3.1 Evaporators
It is crucial that evaporators are installed in a correct gas is led to the compressor through the suction noz-
way, so that pressure loss is minimized, liquid is fed zle (6). The evaporator has two SVA service valves
properly and oil in the evaporator is handled to (7) and (8).
avoid fouling and loss of cooling capacity.
Thermosyphon evaporators
Thermosyphon evaporators are the most critical
component with regard to installation. Thermosy-
phon evaporators rely on a natural circulation to
maintain a sufficient flow of refrigerant, and if the
system does not support this, the performance will
suffer.
From receiver
1
2
Liquid
separator
8
4
7
Thermosyphon
Evaporator
In some cases, an external vessel is attached at the While this will drain oil from the evaporator, it is not
bottom of the drop leg to collect oil. If automatic oil recommended because it means that the oil is al-
return is desired, this vessel can be isolated from the ready in the evaporator. In the ‘port’ – the channel
separator by solenoid valves and the oil moved back created by the holes in the plates – the flow can be
to the compressor through the use of the compres- rather turbulent and the oil might not be available
sor’s discharge pressure. for collection before a large amount is present in the
evaporator.
12.3.3 Condensers
Condenser installation depends on the way injection terms ‘high-pressure float valve operation’ and ‘low-
to the low-pressure side is controlled. Note that the pressure float valve operation’ refer to the mode of
operation, not specifically the use of a float valve. Low-pressure float valve operation
Both operation modes can be achieved by using level Low-pressure float valve operation controls the ex-
switches/transmitters and a normal expansion valve. pansion of the condensed liquid to keep a given level
in one or more low-pressure separators. Any varia-
High-pressure float valve operation
tion of the charge volume due to variations in capac-
High-pressure float valve operation is expansion of
ity must be handled on the high-pressure side, e.g. in
the liquid immediately after the condenser. Any vari-
a receiver.
ation in the charge volume due to variations in ca-
pacity must be handled at the low-pressure side, e.g. To ensure proper functioning of a condenser in a
in a liquid separator. Since the flow after the expan- low-pressure float valve system, the installation
sion valve is two-phase, it is not suitable for distribu- must be correct.
tion to more than one location and thus it is primar-
ily used in systems with only one low-pressure sepa-
rator, such as a chiller unit.
Figure 12.3.3: Low-pressure float valve operation build up in the drop leg. This liquid build-up will pro-
with connection to bottom of receiver vide a positive pressure that counters the pressure
drop in the condenser. The height of the drop leg
1
must be larger than the pressure loss in the conden-
ser, expressed in metres of liquid. In the diagram
above in Figure 12.3.3, the liquid trap is secured
through entering the receiver from the bottom, us-
2 ing the liquid level in the receiver as the top level. An
alternative solution is to enter the receiver through
the top while having an external liquid trap, as de-
5 6 picted below.
3 Receiver
1
4
Liquid trap
The oil coolers described in this section are either brine/water or refrigerant-cooled. Air-cooled oil coolers
are shown in chapter 6.
Brine/water-cooled oil coolers often deliver the oil cooling load to a heat recovery system, but it is also com-
mon to disperse the oil cooling load in a separate air-cooled cooling tower. Brine/water cooled oil coolers
pose no special problems to install.
The (screw) compressors (1) discharge gas contains oil, which is separated in the oil separator (2). This oil is
led to the oil cooler (3) where it is cooled by a water/glycol flow. A 3-way valve (4) regulates the temperature
of the oil passed to the compressor as the capacity of the oil cooler might be too high with varying compres-
sor loads or condensing temperatures.
Refrigerant-cooled oil coolers are often referred to as ‘thermosyphon oil coolers’ as the evaporative circuit
employs the thermosyphon principle.
5 3 Liquid trap
4
The oil circuit is the same as for the brine/water-cooled oil coolers. The cooler is cooled by evaporation of
liquid from the condenser. This liquid is evaporated at condensing pressure/temperature and passed back to
the compressor’s discharge line to be re-condensed in the condenser. Alternatively, the oil cooler can return
the partly evaporated refrigerant to the receiver. However, this requires the pressure equalization line be-
tween the receiver and the compressor’s discharge line to be dimensioned to take the gas flow.
The evaporating side of these thermosyphon oil coolers requires the same considerations as a thermosyphon
evaporator. The driving force is a height difference from the liquid level in the receiver and the pressure
losses are again the pressure loss in the evaporator (oil cooler) and the wet return line. As before, the wet
return line needs to be calculated as a riser.
Note that it is necessary to provide the oil cooler with a ‘priority’. If the low-pressure system is demanding
liquid and no priority is supplied, then the oil cooler might run dry, which results in no oil cooling. No oil cool-
ing is naturally a problem for the compressor. Usually a priority volume of refrigerant liquid is calculated
from what the oil cooler evaporates in 5 to 7 minutes. The priority can be secured by having the receiver out-
let for the low-pressure system raised above the bottom of the receiver, or by adding a separate vessel that
is filled by the condenser before the receiver gets any liquid, the former method being illustrated in Figure.
Thermosyphon oil coolers are rarely seen on high-pressure float valve systems since there is no receiver to
supply liquid. It is possible to mount a priority vessel between the condenser and the expansion valve, how-
ever careful consideration needs to be made to counter the pressure loss in the condenser, since the oil
cooler needs to return the evaporated refrigerant back to the discharge line, which is at a higher pressure
(corresponding to the pressure loss in the condenser) than the liquid before the expansion valve. A drop leg
similar to the low-pressure float valve installation is necessary and, on top of that, there must be a driving
height to drive the thermosyphon function of the oil cooler.
12.3.5 De-superheaters
The primary consideration for a de-superheater is to have as little pressure loss as possible, as this increases
the compressor’s discharge pressure which results in increased power consumption.
A secondary consideration is to avoid condensation in the de-superheater. If the water/brine heated in the
de-superheater is colder than the condensing temperature, it is possible to condense some of the refrigerant
in the de-superheater. It is recommended to avoid running with such low water temperatures. If it is not pos-
sible, then the de-superheater should be designed in such a way that condensed liquid can drain from the
heat exchanger and not be built up inside. In addition, the piping from the de-superheater should slope
down towards the condenser, hindering the condensed refrigerant from settling in undesirable places.
12.3.6 Subcoolers
Similar to the de-superheater, a subcooler is not critical with regard to installation. The primary considera-
tion is to avoid having too large a pressure loss on the refrigerant side. If the pressure loss (in °C) exceeds the
subcooling (in °C) provided by the subcooler, the refrigerant will ‘flash’ causing problems for expansion
valves downstream.
12.3.7 Economizers
Economizers can be of the ‘open’ or ‘closed’ type. For both types the pressure in these are a balance be-
tween the capacity of the economizer and how much the compressor’s economizer port can absorb.
The economizer port is located physically in the screw compressor after the compression has (just) started.
As such, the pressure between the screw compressor’s rotors is higher than suction pressure and to be able
to feed additional gas in between the rotors, the pressure in the economizer port needs to be higher still. The
higher the economizer port pressure, the more gas can be absorbed by the port. On the other hand, the port
pressure equates to a saturation (evaporating) temperature in the economizer, which again with a higher
pressure means a lower capacity.
In many cases the economizer pressure is controlled by a suction pressure regulation to be above what the
economizer port dictates. It is, of course, not possible to go below what the economizer port dictates.
The simplest form of economizer is the ‘open’ economizer, which is a vessel (3) to which the condenser (2)
liquid is flashed from condensing pressure to economizer pressure. The gas developed by this flashing is
passed to the economizer port. The liquid, at economizer temperature, is flashed once again to the low-pres-
sure side. The benefit of this type is that it is a very simple vessel, the temperature of the liquid to the low-
pressure side is the lowest possible, but the downside is that the liquid to the low-pressure side is at a lower
pressure, requiring a larger expansion valve.
Bleed line
In contrast, the ‘closed’ economizer is a heat exchanger (3) that cools the condenser (2) liquid at condensing
pressure. To perform the cooling duty, a part of the condenser liquid is flashed to economizer pressure,
evaporated and passed to the compressor’s (1) economizer port. In the below diagram, the economizer heat
exchanger is a thermosyphon evaporator, but a DX version can be used if suitable.
The benefit of the closed economizer is that the liquid to the low-pressure side is at condensing pressure and
thus the expansion devices can be smaller than with an open economizer. The downside is that the liquid
temperature cannot reach the temperatures achieved with an open economizer, since a temperature differ-
ence needs to exist in the heat exchanger. Because of this, the closed economizer is a little less efficient than
an open type.
One important thing to know about screw compressor economizer ports is that if the compressor is capacity-
regulated using slide valves, the economizer port will be exposed to the suction side very shortly after the
compressor regulates down from 100%. This has two important implications. The economizer pressure will
drop to suction pressure, which is very bad for the open economizer, since the pressure difference between
the economizer vessel and the suction side is zero. This means that no flow will pass through the expansion
devices from the economizer to the low-pressure side. The closed economizer will have an increased capac-
ity. In addition, the economizer will load the suction port, meaning that there is less flow available for actual
evaporation on the low-pressure side.
Naturally, these problems do not occur it the compressor is VFD (variable frequency drive) controlled only.
Usually economizers are fitted with valves in the economizer suction line to control the pressure, to
start/stop the economizer and to avoid the above problems. In some instances, it is not desirable to use all
the capacity available on the economizer port and thus a simple suction pressure regulation is employed.
With open economizers on slide valve-controlled systems, it is necessary to control the minimum pressure in
the economizer to ensure a minimum pressure difference for the expansion valves. This can be implementing
through a minimum pressure, assuming suction pressure does not rise above a certain value, or a pressure
difference to the suction pressure.
Finally, it can be desirable to start and stop the economizer according to the operation of the system. The
closed economizer is easily stopped with a solenoid in the economizer suction line. It is necessary to consider
the pressure loss in the heat exchanger compared to the (anticipated) subcooling from the condenser to
avoid flash gas before the expansion valve.
A simple solenoid in the economizer suction line is not appropriate for an open economizer. The entire refrig-
erant flow is flashed to the economizer vessel, and when the pressure is below condensing pressure, the gas
developed during the flashing will increase the pressure until it is at or just below the condensing pressure.
This makes it impossible for the expansion valve between the condenser and economizer to deliver enough
flow. Therefore, a separate bleed line is needed to dispense of the flash gas to the suction line. The bleed line
must contain valves that secure an appropriate economizer pressure for both expansion valves to function.
Compared to not having an economizer, the total impact of this installation on the compressor will be zero.
The amount of gas flashed to the suction line is countered by a lower temperature of the liquid passed to the
evaporators.
However, if a side load is run in parallel with the economizer, it is either not possible or ineffective to stop
the economizer. Stopping a closed economizer will stop the side load as well, while with an open econo-
mizer, stopping it will move the side load to the suction side, which is much less efficient.
The screw compressor’s rotor ‘lobes’ pass the economizer port while shifting from one ‘channel’ to another
within the compressor. This results in oscillations in the economizer pressure, which can result in undesirable
effects such as valve oscillation. To counter this, a damper can be fitted that reduces these oscillations and
thereby reduces the strain put on the economizer system. This is described in chapter 2.5 regarding econo-
mizer line pulsation damping units.
12.3.8 Superheaters
Superheaters use cooling from the condenser liquid to heat the suction gas for the compressor to provide
security of dry suction gas.
Like subcoolers and de-superheaters, the pressure loss in these heat exchangers is important with regard to
system efficiency, but apart from that the installation poses few problems.