You are on page 1of 20

Addendum

Cat. 4875 Quick Start Guide


Version 1.2 - 061608

Current version includes the following updates:


Quick Start Guide was changed to include pictures that replace the step-by-step instructions for
quick and easy reference.

Jeron Electronic Systems, Inc. 1743-55 W. Rosehill Drive Chicago, IL 60660


(773) 275-1900 U.S.A. & Canada: (800) 621-1903 Fax: (773) 275-0283 www.jeron.com
.
For use with:

4875/76
Master
Console

Attention first time


! installers of this system!

DO NOT install field


wiring, or attempt to
program the system
before you have
completed the procedure
in the Pro-Alert 480
Quick Start Guide.

© 2008 Jeron Electronic Systems, Inc.


.

© 2008 Jeron Electronic Systems, Inc.


For use with:
4875/76
Master
Console

Pro-Alert 480 Quick Start Guide

Getting Started
Components

Cat. 4850 Main Control Cat. 4875 Master Console

Cable Serial Key Power


Supply

PC
4890 Administration
Program Software
Cat. 4882 Remote Station

Version 1.2
6/16/08 Page 1 of 16
4875/76 Master Console Quick Start

Power Down System

Disconnect Field Wiring

System Diagram

AUDIO BOARD AUX

Cat-5
65

75

Cat-5 BUS 1
REMOTE
STATION
BUS 2 65

75

BUS 3
LOGIC BOARD
4875 MASTER CONSOLE
BUS 4 10-POSITION DIPSWITCH 65

75

DATA BUS
FAULT HEARTBEAT
LEDs LED 65

75

POWER SUPPLY

Version 1.2
6/16/08 Page 2 of 16
4875/76 Master Console Quick Start

Set Dipswitches

SIDE
VIEW
Dipswitch Settings: 1111101011

TOP TOP TOP TOP TOP TOP TOP


TOP TOP TOP TOP

BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM
ON postion ON postion ON postion ON postion ON postion
ON postion OFF postion ON postion
ON postion OFF postion ON postion ON postion

1 2 3 4 5 6 7 8 9 10

SIDE
VIEW Dipswitch: 0000

TOP TOP TOP TOP

Underside of Cat. 4875


to Master Port A, subport #1 BOTTOM BOTTOM BOTTOM BOTTOM
OFF postion OFF postion OFF postion OFF postion
1 2 3 4

Version 1.2
6/16/08 Page 3 of 16
4875/76 Master Console Quick Start

Bus Address 001


.

Cat. 4882 Remote Station Back Side

SIDE Dipswitch: 1111111


VIEW

TOP TOP TOP TOP TOP TOP TOP

BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM


ON postion ON postion ON postion ON postion ON postion ON postion ON postion

1 2 3 4 5 6 7

Version 1.2
6/16/08 Page 4 of 16
4875/76 Master Console Quick Start

Connections
Set the Master Port to ‘75’

P205
1
AUX

P201
J401A
Sub-port #1

J401B
Sub-port #2

J201

J401C
Sub-port #3
65

Sub-port #4

MASTER
A
Used 75 J401D
SW1
Unused

Port switch set to ‘75’


makes this a Type
‘75’ master port for
connecting a 4875.

Cat-5 Cable from


Cat. 4875 to
Subport #1 on
Master Port ‘A’

Cat-5 Cable to RJ-45 port on Cat. 4875

Master Ports on Cat. 4850 Main Control

Version 1.2
6/16/08 Page 5 of 16
4875/76 Master Console Quick Start

Cat-5 cable from J1 of 4882 Remote


Station to J211A on Bus 1 on Main
Control

J2 J1
Cat-5 Cable to J1 on Cat. 4882 Station

Version 1.2
6/16/08 Page 6 of 16
4875/76 Master Console Quick Start

Programming
Install 4890 application as outlined in the 4890 Installation and User’s Guide before
proceeding. After you have installed the application and connected the PC to the Pro-
Alert system:

Connect Power
Supply to
105 to 132V
facility
power supply

Open Cat. 4890 Administration Program Software on PC

Connection
Port

Click OK

Version 1.2
6/16/08 Page 7 of 16
4875/76 Master Console Quick Start

Global System Data Tab

Set the last four digits to ‘Numeric’


allowing for a four-digit, numeric arch
address on the system.

Version 1.2
6/16/08 Page 8 of 16
4875/76 Master Console Quick Start

Main Control Assignment Tab

Enter 1000 for address


of Main Control A

Master Setup Tab

Be sure you are Enter 2000 for the master


working with station arch address.
master settings on
master port ‘A’.

Assign this master to sub-port #1.

Version 1.2
6/16/08 Page 9 of 16
4875/76 Master Console Quick Start

Bus Station Setup Tab

At the bus station setup screen, double-click on bus


station 001. This will open the details screen and
allow you to enter settings for the bus station.

.
Enter 1001 as the arch
address for the bus station. Set audio bus to 1

Assign this bus station to report to the


4875 on sub-port #1 of master port A.

Version 1.2
6/16/08 Page 10 of 16
4875/76 Master Console Quick Start

Save configuration file in a folder on your PC. Configuration will automatically be


uploaded to the Provider system.

Operation
Place a Call

Version 1.2
6/16/08 Page 11 of 16
4875/76 Master Console Quick Start

Verify

Call Placed
LED
Illuminates

Call visually annunciated &


Routine call tone sounds at
Cat. 4875 Master

Cat. 4882 Remote Station

Answer Call

or

Lift Handset to establish audio connection or Press Enter/Talk to use panel microphone
& panel speaker

Version 1.2
6/16/08 Page 12 of 16
4875/76 Master Console Quick Start

Cancel Call

Press Cancel Replace Handset

Originating a Call to Remote Station

Enter room number 1001 Press Enter/Talk

Version 1.2
6/16/08 Page 13 of 16
4875/76 Master Console Quick Start

.
or

Lift Handset to establish audio connection or Press Enter/Talk to use panel microphone
& panel speaker

Cancel Call

Press Cancel Replace Handset

Version 1.2
6/16/08 Page 14 of 16
4875/76 Master Console Quick Start

Troubleshooting
Symptom Possible Cause Remedy
Dipswitch settings on the remote station are incorrect.
4875 display reads:
1001: FAILED Verify that the dipswitch on the remote station is set according to
page 4.
4875 display reads: You entered the Verify that the entered architectural
INVALID after an architectural address address matches the address programmed
attempt to originate a call incorrectly when using 4890 software.
to the remote station. originating the call. See page 10.
Power down the main control, set the port
Master port switch is set
4875 display reads: switch to ‘75,’ then power up the main
to ‘65’.
WAITING FOR control.
DATA 4875 is actively
No action is necessary.
receiving configuration.
Verify that you have properly
Master port is not
programmed the master port. (See page
programmed.
4875 display reads: 9.)
NOT CONFIGURED Verify that you have the dipswitches set
Dipswitches are set
properly on the main control, master
incorrectly.
console, and bus station. (See pages 3-4)
4875 master is not Verify that you have not connected the
4875 display continues to
connected to a sub-port master station to an RJ-45 port on the
read, TESTING
on the master port. audio bus.
Bus station is connected Verify that the bus station is programmed
Call displays at the master
to an audio bus other for audio bus 1 in 4890 programming,
station but there is no
than the one you then verify that the station is connected to
audio.
assigned using 4890. an RJ-45 port on audio bus 1.

Main Control
Green Heartbeat LED*
Condition Indication Action
System operating
Steadily
normally with valid No action is necessary.
flashing
configuration
Rapidly System does not have Upload valid code into the system using the 4890
flashing valid code. application.

Version 1.2
6/16/08 Page 15 of 16
4875/76 Master Console Quick Start

Green Heartbeat LED*


Condition Indication Action
The system does not have Use 4890 to upload a valid configuration to the
Steadily lit
a configuration. Pro-Alert system.
Two flashes Possible marginal Verify that the Cat-5 cable connecting the master
followed by a communications link to the main control is tested and complies with
pause between master and main. T568A standard.
Verify that the power supply is connected to a
Off No power to main control.
viable 120VAC supply.
Amber Ground Fault LED*
Condition Indication Action
Disconnect field wiring beginning with master
station, then continuing with bus stations. Observe
Steadily lit Possible ground fault. LED to see if it extinguishes when the equipment is
removed. If so, the problem is likely related to the
piece of equipment or its connective wiring.
Off Normal operation. No action necessary.
Red Data Bus Fault LEDs*
Condition Indication Action
Note which LED is lit. There are four data bus fault
LEDs labeled Faults 1–4.* They correspond to
Bus station may be wired
Buses 1–4 on the audio bus. For example, if Fault 1
incorrectly with Data
LED is lit, this indicates a problem with one of the
High (DH) and Data Low
Steadily lit stations connected to Bus 1. Verify that the station
(DL) positions switched.
wiring is correct and is consistent with wiring
details shown in on page 2.
Shorted conductors in
Verify that no cable shorts exist
Cat-5 cable
Off Normal operation. No action necessary.
* LED locations are illustrated on page 2.
.

Version 1.2
6/16/08 Page 16 of 16