Galvanized steel wall sleeve

- - - - - - - - See architectural drawings for wall type

Galvanized steel blades with


interlocking joints mounted in - - - - - - Fire stop material with incombustible
a galvanized steel frame US gypsum fire proof mineral wool
thermofiber sating
Replaceable fusible link hook to - - - - - -
cinch

I1
See floor plans for location and size of
the ductwork
Duct Duct

Duct access panel 18"X duct - - - . J


width -2". For insulated ducts ......__ _ _ _ _ _ _ Standing 'S' slip "breakaway" connection
provide an insulated access
panel
1 1/2"x1 1/2"x1 /8" continuous
galvanized steel angle, bolt to
wall sleeve

Detail Horizontal Fire Damper Installation


No Scale

Note:
1. Fire dampers to have breakaway joint between collars and duct.
(collars shall be integral with fire dampers frame.)
2. Fire damper shall be u.l. labeled.
3. Galvanized sleeve and frame construction shall be minimum 20 ga.
should duct be heavier than 20 gauge, provide sleeve and frame
to match duct construction.
Detail #34 - DFDdet Tab: 1 - Horizontal Fire Damper
Duct access panel 1B"X duct \
Galvanized steel blades with
width -2". For insulated ducts
provide an insulated access -=.-------' interlocking joints mounted in
a galvanized steel frame
panel
Galvanized steel
floor sleeve 1 1/2"x1 1/2"x1 /8" continuous
galvanized steel angle, bolt to
wall sleeve
Stainless steel negator - - - - -
closure spring

Floor slab 0 0 <> ~ Floor Slab. See Architectural &


0 • O / Structural drawings for slab
• 0 thickness
o Cl •
0 • ()' 0

C>Goo•o

Blade lock

Standing 'S' slip Fire stop material with incombustible


"breakaway" connection US gypsum fire proof mineral wool
thermofiber sating
Replaceable fusible
link hook to cinch
Duct insulation terminate at wall sleeve
and seal ends supply ductwork only

Detail Vertical Fire Damper Installation


No Scale

Note:
1. Fire dampers to have breakaway joint between collars and duct.
(collars shall be integral with fire dampers frame.)
2. Fire damper shall be u.l. labeled.
3. Galvanized sleeve and frame construction shall be minimum 20 ga.
should duct be heavier than 20 gauge, provide sleeve and frame
to match duct construction.

Detail #34 - DFDdet Tab: 2 - Vertical Fire Damper