Fire Damper Installation
Fire Damper Installation
I1
See floor plans for location and size of
the ductwork
Duct Duct
Note:
1. Fire dampers to have breakaway joint between collars and duct.
(collars shall be integral with fire dampers frame.)
2. Fire damper shall be u.l. labeled.
3. Galvanized sleeve and frame construction shall be minimum 20 ga.
should duct be heavier than 20 gauge, provide sleeve and frame
to match duct construction.
Detail #34 - DFDdet Tab: 1 - Horizontal Fire Damper
Duct access panel 1B"X duct \
Galvanized steel blades with
width -2". For insulated ducts
provide an insulated access -=.-------' interlocking joints mounted in
a galvanized steel frame
panel
Galvanized steel
floor sleeve 1 1/2"x1 1/2"x1 /8" continuous
galvanized steel angle, bolt to
wall sleeve
Stainless steel negator - - - - -
closure spring
C>Goo•o
Blade lock
Note:
1. Fire dampers to have breakaway joint between collars and duct.
(collars shall be integral with fire dampers frame.)
2. Fire damper shall be u.l. labeled.
3. Galvanized sleeve and frame construction shall be minimum 20 ga.
should duct be heavier than 20 gauge, provide sleeve and frame
to match duct construction.