Research Article
Wind Tunnel Tests and Numerical Simulations of Wind-Induced
Snow Drift in an Open Stadium and Gymnasium
Received 8 March 2020; Revised 28 October 2020; Accepted 29 October 2020; Published 29 November 2020
Copyright © 2020 Xintong Jiang et al. This is an open access article distributed under the Creative Commons Attribution License,
which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
A long-span sports centre generally comprises multiple stadiums and gymnasiums, for which mutual interference effects of wind-
induced snow motion are not explicitly included in the specifications of various countries. This problem is addressed herein by
performing wind tunnel tests and numerical simulations to investigate the snow distribution and mutual interference effect on the
roofs of long-span stadiums and gymnasiums. The wind tunnel tests were used to analyse the influences of the opening direction
(0°, 90°, 180°, and 270°) and spacing (0.3 L, 0.5 L, 1 L, 1.5 L, 2 L, and 2.5 L, where L is the gymnasium span) of the stadium and
gymnasium. The wind tunnel tests and numerical simulations were used to analyse the influence of the wind direction angle (from
0° to 315°, there are a total of eight groups in 45° intervals). The following results were obtained. The stadium opening had a
significant effect on the snow distribution on the surface of the two structures. An even snow distribution was obtained when the
stadium opened directly facing the gymnasium, which corresponded to the safest condition for the structures’ surfaces. As the
spacing between the buildings increased, the interference effect between the two structures was reduced. The interference was
negligible for a spacing of 2 L. The stadium had the most significant amplification interference effect on the gymnasium for a wind
direction angle of 45°, which was extremely unfavourable to the safety of the structure. The most favourable wind direction angle
was 270°, where there were both amplification interference and blockage interference.
they can produce contradictory requirements. Some re- project is used as a case study to investigate the snow dis-
searchers (Anno [11]; Kim et al. [12]; and Kwok et al. [13]) tribution on the surface of adjacent long-span open struc-
believe that the Froude number requirements can be relaxed, tures. There are many factors that affect the snow
whereas others (Lever and Haehnel [14]) have concluded distribution on the surface, as shown in Figure 1. He et al.
that the Froude number can be neglected when the particle [26] pointed out that the wind effects around different
saltation height is much smaller than the model size. Some buildings could overlap, interact, neutralize, and offset. This
researchers have studied the factors that affect wind-induced leads to changes in the trajectory of the snow particles
snow drift. Peterka and Esterday [15] conducted a wind around the building, which affects the final snow distribu-
tunnel test on the snow distribution law of the model surface tion. The direction of the openings and the spacing between
area under different wind directions and ultimately deter- structures are both factors that affect the arrangement of
mined the roof snow load. Zhou et al. [16, 17] studied the structures, and thus, the influence of these two factors on the
snow distribution law of the surface area of flat roofs with distribution of snow cover can be studied. Additionally, the
different span-to-height ratios under different wind speeds influence of the wind direction angle on the mutual inter-
and blowing times and considered the relationship between ference effect of the two structures is studied. The obtained
the particle mass transport rate and the transport volume. results are realistic and can be used to predict the snow
Yu et al. [18] conducted wind tunnel tests on a flat three- distribution for buildings with openings.
dimensional (3D) roof and considered the effects of the
model size, wind speed, and blowing time. Qiang et al. [19] 2. Wind Tunnel Tests
conducted snow tests on flat roofs in a low-temperature
wind tunnel environment and simulated the real snowfall 2.1. Description of the Test. A small, low-speed wind tunnel
process, including during snowfall and after snowfall, and was designed and used to perform tests on wind-induced
put forward a formula to calculate the snow transport rate. snow drifts [27]. The wind tunnel had a total length of seven
Unlike wind tunnel tests, full-scale models can be metres, and the maximum airflow was 18,700 (m3 /h). The
considered in numerical simulations, which can, in turn, be wind turbine was connected to a CDI-EM60G2R2T4B
used to solve the similarity problems. Numerical simulations frequency converter to continuously adjust the wind speed.
are inexpensive and rapid, and they do not require special Measurements showed that the wind speed was linearly
equipment. Therefore, numerical simulations have become proportional to the frequency, and the steady wind speed in
one of the most effective methods for studying wind-induced the tests was 1.5 to 10 m/s. The test section had dimensions
snow drift, although the simulation results need to be of 0.5 m × 0.5 m × 1.5 m. A simple box was placed at the
verified by field measurements or wind tunnel tests. Many outlet of the diffuser section to determine the mass
researchers have made improvements in the accuracy of transport rate. In the wind tunnel test section, the airflow
numerical simulations. Sato et al. [20] simulated 3D wind- stability did not exceed 1.5%, and the dynamic pressure
induced snow drift by considering snow saltation and field coefficient was below two percent. Taking a height of
suspension. The finite volume method was used to solve the 10 cm as the reference point, the measured wind profile and
problem and produced results that were consistent with the turbulence intensity profile at the nominal velocity of 5 m/s
measurements. Beyers and Waechter [21] used an improved are shown in Figure 2. As seen from Figure 2(a), the wind
turbulent wall function to account for the additional mo- velocity of the flow field u was strongly influenced by the
mentum from snow particle saltation motion. A simulation wall height z. The wind velocity near the wall was relatively
of the snow drift around a cubic model produced satisfactory small, and it increased with z. Within a height of 0.1 m, the
results. Zhao et al. [22] studied bidirectional coupled wind- increase of u with z was relatively large. When the wall
induced snow flow using a numerical simulation method height z was greater than 0.1 m, u increased with z steadily.
based on CFD-DEM modelling. A two-dimensional (2D) From Figure 2(b), it can be seen that the turbulence in-
numerical simulation was performed for the snow distri- tensity I decreased with z. The position that had the
bution and wind-snow coupling interference effect on a maximum value of I (approximately 5.5–6.0%) was at the
typical stepped roof. Liu et al. [23] introduced two novel bottom of the flow field. A turbulence curve was proposed
parameters, the snow residual rate and the erosion rate, in from Figure 2 to show the relationship between the wind
wind tunnel tests on flat 3D roofs. Numerical simulations velocity profile and the turbulence intensity profile. The
were used to correlate the vorticity magnitude with the fitting relationship was I � 5.886 − 0.002u4.315 , and
friction velocity around a structure. Wang et al. [24] R2 � 0.990, as shown in Figure 3. It can be seen from
combined wind tunnel tests and numerical simulations to Figure 3 that the turbulence intensity I at a height of 0.1 m
develop a probability-based half-steady Euler- decreased with an increase in the wind velocity u. This was
ian–Lagrangian method for studying the snow distribution because the higher the wind velocity was, the more particles
on roofs. Marsh et al. [25] proposed a 3D snow blowing moved. The leaping particles continuously absorb energy
model that uses a variable resolution unstructured grid for from the airflow to reduce the pulsation velocity and
spatial discretization. With a fixed-resolution grid size, turbulence intensity. The logarithm law was used to fit the
computational elements are reduced by 62%, and the total wind velocity curve, and the obtained roughness height zo
run time is reduced by 44%. was 1.4 × 10− 4 m. Roughness elements were laid at the front
In most of the current literature, only single closed of the test section to fully develop the wind. The pre-
structures have been studied. In the present study, an actual pavement method was used to simulate building the surface
Advances in Civil Engineering 3
Factors
effecting
wind-induced Structure Spacing of
snow enclosureness structures
drift
Structure type Roof type and Structure facade
and inclination roughness
arrangement
Decorations on
Blocking of
building
Occlusion buildings of the
surfaces, such
factors on same volume
as fences
structure
surface and
Ventilation for
surrounding Tree view
pedestrians and
factor
vehicles
0.5 0.6
0.5
0.4
0.4
0.3
z (m)
z (m)
0.3
0.2
0.2
0.1
0.1
0.0 0.0
2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 1 2 3 4 5 6
u (m/s) I (%)
Test results
Fitted curve
(a) (b)
Figure 2: Profiles of the mean wind and turbulence intensity. (a) Wind velocity profile. (b) Turbulence intensity profile.
4 Advances in Civil Engineering
2.2. Similarity Parameters and Particle Selection. 2.3. Test Model. The prototype building consists of a long-
Geometric similarity, motion similarity, dynamic similarity, span stadium with an open end and an oval long-span
Reynolds number similarity, and time scale similarity were gymnasium. The stadium has a 246 m long axis and a
used to ensure the accuracy of the test results. Similarity of 224 m short axis, and the highest roof elevation is 49 m.
the angle of repose was used to determine the similarity of The gymnasium has a 135 m long axis and a 116 m short
the snow particles. Many researchers have obtained satis- axis, and the highest roof elevation is 24 m. The buildings
factory results by using quartz sand in wind-snow tests are shown in Figure 4. The test model is a 1/700 scale and
(Kind [28]; Li [29]; Wang et al. [30]; and Zhou et al. [17, 31]). is made of welded 304 stainless steel with a thickness of
This medium was also used in this study. The mean diameter two millimetres. Figures 5 and 6 show two groups of 91
of the measured quartz sand was 0.14 mm, the density was and 69 measurement points on the stadium surface and
2.56 (g/cm3 ), and the angle of repose was 30.8°. Table 1 two groups of 92 and 68 measuring points on the gym-
shows that quartz sand and snow particles essentially have nasium surface, respectively. Similar variations in Cs are
similar physical properties. As wf was greater than the found using both sets of measurement points (there were a
prototype value, (wf /u∗ ) and (wf /u∗t ) were both two to few numerical differences between the Cs plots). There-
three times larger than the prototype values. The Froude fore, we select the group of 69 measurement points on the
number of the model was two orders of magnitude higher stadium surface and the group of 68 measuring points on
than that of the prototype and was inaccurately simulated. the gymnasium surface for analysis. Figure 7 shows the
Several researchers have shown that the Reynolds numbers test results for a stadium opening direction of 90°, a 0.5 L
and incompatible Froude numbers are more suitable for spacing between the two buildings, and a wind direction
wind-induced snow drift wind tunnel tests. The meteoro- angle of 90°.
logical data of the 2007 blizzard in Liaoning was used as a
case study (Li et al. [32]): the duration of this blizzard was 3. Numerical Simulations
48 h, and the force 8-9 north-easterly wind had a wind
velocity of between 17 and 24 m/s, with an average wind 3.1. Governing Equation of the Air Phase and Snow Phase.
velocity of 20.5 m/s. We adopt the test criterion proposed by Using the Reynolds average method, wind can be ap-
Iversen [10], which is based on the similarity of the mass proximated as an incompressible viscous fluid, and the
transport rate of the saltation layer, as given by equations (1) continuous equation and the momentum conservation
and (2). The test wind velocity was 5.2 m/s, and the test equation are given by the following equations,
duration was thirteen minutes. respectively:
Advances in Civil Engineering 5
16 17 15 0°
14 18 12 13 14
45 46 44 19 Opening direction
13 47 11 35 36 15
12 43 71 72 73 48 20 34 55
70 74 54 56 37 16 90°
42 69 75 49 21 10 57
11 33 53
41 76 38 17
68 50 22 9 58
10 77 52
67 32
40 51 39
78 23 59 18
9 39 66 89 8 51
88 52 31
79 24 67 68 40
8 19
38 87 65 90 53 7 50 60
80
64 25 30
7 37 86 81 91 54 61 69 41 20
63 66 49
26 6
82 29 62
6 36 62 55 48 42 21
83 27 5
5 35 61 56 28 47 63 22
34 28 4 43
4 60 84 57 64
46
33 58 29 3 27 44 23
3 32 59 85 26 45 24
2 30 2 65
1 31 1 25
(a) (b)
Figure 5: Layout of the stadium monitoring points. (a) 91 measurement points. (b) 69 measurement points.
7 8 9 10 7
11 6 8 0°
6 39 12 5 9
38 40 29
5 41 13 4 28 30 Wind direction angle
37 10
4 61 62 63 42 45
36 14 44 46
60 3 27 31 11 90°
3 64 43 15 47
35 43
59 80 65 26 59
79 81 2 60 32 12
2 34 90 44 16 42 58 66 48
78 82 66
58 65 67
33 77 89
57 91 83 67 45 17 25 41 57 61 49 33 13
1 1
76 88 92 84 68 68
32 56 50
87 85 46 18 64 85
56 86 69 24 63 34 14
75 40 55 51
74 70 47
31 55 19 52
73 72 71 54
48 39 53 35 15
30 54 20 23
53 49
29 21 38 36 16
52 51 50 22 37
28 22
21 17
27 23
26 25 24 20 19 18
(a) (b)
Figure 6: Layout of the gymnasium measuring points. (a) 92 measuring points. (b) 68 measuring points.
6 Advances in Civil Engineering
zu zv zw area per unit time qero and the amount of deposition qdep are
+ + � 0, (3) given by the following equations, respectively:
zx zy zz
qero � Aero u2∗ t − u2∗ u∗ ≥ u∗t , (7)
Dui 1 zp μ z zui
� fi − + , (4)
Dt ρ zxi ρ zxj zxj u2∗ t − u2∗
qdep � Cwf u∗ < u∗t , (8)
where u, v, and w are the velocity components in the di- u2∗ t
rections of x, y, and z, respectively, ui is the wind velocity
where Aero is a constant coefficient, which is taken as 7.0e−4,
component (m/s), t is the time component (s), fi is the
and C is the mass of snow within a unit volume, C � fρp.
component of the force acting on a unit mass of the fluid (N),
xi and xj are coordinates, p is the fluid pressure (MPa), and μ
is the air viscosity coefficient (Pa·s).
The governing equation of the snow phase (Zhou et al. 3.3. Calculation Model and Meshing. FLUENT software was
[16]; Uematsu et al. [33]; and Tominaga et al. [34]) is given used to perform the numerical simulations on the stadium
by the following equation: and gymnasium. Unidirectional coupling was assumed
between the air and snow particles; that is, air can drive
zρp f zρp fuj z zρp f the motion of snow particles, but the drift of snow par-
+ � μ ticles does not affect the air. The Euler-Euler method was
zt zxj zxj t zxj
(5) used. A mixture multiphase flow model was adopted for
its relative stability at a low computational cost. A full-
z
+ −ρp fuR,j , scale simulation was performed. The watershed had di-
zxj mensions of 3000 m × 1500 m × 500 m. The model was
placed in the first third of the watershed. Hybrid meshing
where f is the mass concentration of snow, uj is the wind was adopted, that is, an unstructured mesh was used to
velocity vector (m/s), μt is the turbulent kinematic viscosity, discretise the building, and a structured mesh was used to
which represents the degree of influence of air on the snow discretise the exterior space, resulting in a total number of
faces, and the speed of snow relative to the air phase uR,j is approximately 1.7 million meshes.
0.3 [35].
k � 1.5(u(z) · I)2 , literature [38] were both eroded. The erosion amount of the
roof snow in the leeward-side edge in the literature was
(10) slightly greater than the result obtained in the paper. Both in
0.090.75 · k1.5
ε� , the literature and in the paper, along the windward-side edge
l of the reticulated shell to the central part, the absolute value
− α− 0.05 of the snow erosion amount increased gradually from small
⎪
⎧
⎪ zb
⎪
⎪ 0.1 , z ≤ zb , values, reaching a maximum at the centre, and the patterns
⎪
⎪ zG
⎨ of change for the snow erosion amount were consistent. The
I �⎪ (11) absolute values of the snow erosion at the centre reported in
⎪
⎪ − α− 0.05
⎪
⎪ z the literature and obtained in the paper were the same, and
⎪ 0.1
⎩ , zb ≤ z ≤ zG ,
zG both were 0.00055. This finding proved the accuracy of the
numerical simulation used in the paper and provided a basis
⎪
⎧
⎪ z 0.5 for the simulation study of the wind-induced snow drift.
⎨ 100 , 30 m ≤ z ≤ zG ,
l �⎪ 30 (12)
⎪
⎩ 4. Test and Numerical Simulation Results
100, (z ≤ 30 m).
This is set as a II landform according to Japanese reg- 4.1. Influence of the Opening Direction. The influence of the
ulations [37], where zb is 5 (m) and zG is 350 (m). The inlet direction of the stadium opening (one open end) on the
boundary condition for the snow phase on the inflow surface snow distribution on the surface is determined for five
is working conditions, i.e., the stadium opening directions of
0°, 90°, 180°, and 270° and a closed stadium. The locations of
⎪
⎧ 0.68 the measurement points for the closed stadium are shown in
⎪
⎪
⎪ μ∗t μ2∗ − μ2∗ t , hs ≤ z,
⎪
⎪ μ p μ∗ g Figure 10, the opening angle and the measurement points for
⎪
⎨ the open stadium are shown in Figure 5(b), and the wind
f �⎪
⎪
⎪ tunnel measurements of the snow distribution on the
⎪
⎪
⎪ 0.8 exp−1.554.78μ−0.544 ∗ − z− 0.544 gymnasium surface are shown in Figure 11. For Cs ≥ 1, snow
⎪
⎩ , z ≤ hs ,
ρp was deposited on the surface of the structure, and erosion
(13) occurred for Cs < 1.
Figure 11 shows that Cs first decreased and, then, in-
where μp is the snow particle velocity (m/s), μp � 2.3u∗t , and creased from the windward side to the leeward side of the
the critical height of the transition and suspension layers hs gymnasium, and a large area of leeward snow was deposited.
is 0.5 (m). The peak Cs values were found at measurement points 13, 33,
The air and snow phases at the inlet were calculated using 49, 61, and 67, indicating that the greatest snow depth oc-
UDF interface programming, with fully developed outflow curred on the central axis of the leeward side. Measurement
boundary conditions at the outlet. Free-sliding wall con- points 7, 19, 29, 37, 45, 53, 59, and 63 on the central axis
ditions were applied to the top, as well as the left and right perpendicular to the downwind direction were located in the
sides of the watershed, and nonsliding wall conditions were valley, where the largest amount of snow erosion occurred.
used for the snow surface and the model wall surface. The Therefore, the variation in the snow pressure at these lo-
realisable k − ε two-equation model was selected for the cations should be considered when designing these struc-
calculations. In the iterative calculations, a dimensionless tures to prevent structural surface damage from uneven
root-mean-square residual of 10− 6 is used as the convergence snow pressure.
criterion, and a second-order discrete scheme was used for Compared with the Cs value for the closed stadium,
the solution procedure. larger Cs values were found for the 0° and 180° openings, and
smaller or equal Cs values were found for the 90° opening.
Thus, the stadium opening had a significant influence on the
3.5. Accuracy Verification. The model from literature [38] is snow distribution on the gymnasium surface. Comparing
selected for the accuracy verification of the numerical the results for the four opening conditions showed con-
simulation. In the literature, the spherical shell roof has a sistent variations in Cs for the 0° and 180° openings, which
span L1 of 60 m and the shell height h is 13.2 m, and the were greater than that for the 90° opening, which was almost
distance between the edge of the roof and the ground surface entirely below unity. At measurement point 1 on the central
H is 15 m, as shown in Figure 8. The calculated river basin is axis of the windward edge, Cs for the 90° opening was ap-
720 m × 540 m × 110 m, which is divided using an unstruc- proximately 38.18% smaller than those for the 0° and 180°
tured grid, with a total of approximately 1.35 million grids. openings and approximately 20% smaller than that for the
The boundary conditions and other parameters are shown in 270° opening. At measurement point 25 on the central axis of
detail in the literature. The snow distribution pattern of the the windward side, Cs for the 90° opening was less than those
roof using the same simulation conditions and the literature for the 0°, 180°, and 270° openings by 35.24%, 37.04%, and
simulation results are shown in Figure 9. 18.07%, respectively. At measurement point 13 on the
From Figures 9(a) and 9(b), it can be seen that the roof central axis of the leeward edge, Cs for the 90° opening was
snow simulated in the paper and the roof snow simulated in 18.4% smaller than that for the 0° opening and 20.31%
8 Advances in Civil Engineering
L1
qero/(kg·m–2·s–1) qero/(kg·m–2·s–1)
0 –0.00010
–5E – 05
–0.0001 –0.00015
Wind –0.00015 –0.00020
–0.0002
–0.00025 –0.00025
–0.0003 –0.00030
–0.00035
–0.0004 –0.00035
–0.00045 –0.00040
–0.0005
–0.00055 –0.00045
–0.0006 –0.00050
–0.00065
–0.0007 –0.00055
(a) (b)
Figure 9: Comparison of the simulation results. (a) Simulation results of this paper. (b) Simulation results in the literature.
W:windward L:leeward
1.4
w L w L w L w L w
1.3
deposition
Wind
Snow
1.2
1.1
1.0
CS
0.9
erosion
0.8
Snow
0.7
0.6 Outer circle (first circle) Second circle Third circle Fourth circle Innermost
circle
0.5
0 10 20 30 40 50 60 70
Measuring point number
0° 270°
90° Closed
180°
Figure 11: Snow distribution on the gymnasium surface for different opening directions.
deposition
1.3 1.3
Snow
Snow
Wind
1.2 1.2
1.1 1.1
Cs
Cs
1.0 1.0
0.9 0.9
erosion
erosion
Snow
0.8 0.8
Snow
0° 90°
Closed Closed
(a) (b)
W: windward L: leeward W: windward L: leeward
1.5 1.5
w L w L w L 1.4 w L w L w L w
deposition
deposition
1.4
Snow
Snow
1.3
1.3 Wind Wind
1.2
1.2
1.1 1.1
Cs
Cs
1.0 1.0
0.9 0.9
erosion
erosion
Snow
Snow
0.8 0.8
0.7 0.7
0.6 Outer circle (first circle) Second circle Innermost circle 0.6 Outer circle (first circle) Second circle Innermost circle
0.5 0.5
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Measuring point number Measuring point number
180° 270°
Closed Closed
(c) (d)
Figure 12: Comparison of the snow distribution on the surfaces of an open stadium for different opening directions and a closed stadium.
(a) 0°. (b) 90°. (c) 180°. (d) 270°.
formed a vortex that carried the snow on the surface away. circle (measurement points 1 to 25) were symmetric about
Therefore, Cs for the innermost circle was less than that for the measurement point 13, the Cs values for the second circle
closed stadium. The stadium opening also affected the dis- (measurement points 26 to 44) were symmetric about
tribution of snow on the stadium surface. measurement point 35, and the Cs values for the innermost
A comparison of Figure 12(a) and 12(c) showed that, for circle (measurement points 45 to 65) were symmetric about
the 0° and 180° openings, the Cs values for the outermost measurement point 55. Thus, the 0° and 180° working
10 Advances in Civil Engineering
conditions only differed in terms of the opening direction wind formed a reflux vortex between the two structures that
and produced the same surface snow distributions. Less entrapped the ground particles in the air before they landed
snow was deposited on the surface for the 90° and 270° on the roof. This resulted in a larger Cs value for the roof. As
openings than for the 0° and 180° openings. For the 270° the structure spacing increased, the energy of the vortex
opening, there was a considerable difference in Cs between decreased and caused the Cs value of the roof to decrease
the open and closed conditions for the innermost circle accordingly. When the distance was large enough, the wind
(measurement points 45 to 65), and the Cs at measurement flow changed to blow around the gymnasium. Therefore, for
points 50 and 60 for the closed stadium was approximately a sufficiently large distance between two long-span struc-
39.22% higher than that for the open stadium. In this case, tures, the mutual interference effect of the wind-induced
the opening directly faced the inflow direction, such that snow motion between the structures was negligible.
most of the wind flowed into the stadium, encountered the
inner wall, and flowed back to form a vortex. At this time, the
inner wall had no outlet to expel such a high-energy vortex, 4.3. Influence of the Wind Direction Angle. Wind tunnel tests
resulting in small Cs values for the innermost circle. In were used to study the stadium’s influence on the snow
contrast, for the closed stadium, most of the wind flowed distribution on the gymnasium surface for different wind
along the smooth wall to the leeward side, and the influence direction angles. For several wind direction angles varying
of the wind on the inner wall of the stadium was much from 0° to 360° with an interval of 45°. The wind direction
smaller than for the open stadium. The most uniform snow angle is shown in Figure 6(b). The snow distribution pattern
distribution on the gymnasium surface was obtained for the on the gymnasium surface for the eight working conditions
90° opening, and except for the outermost circle, the Cs is shown in Figure 14.
values for the other measurement points varied smoothly It can be seen from Figure 14 that compared to the two
and were concentrated between 0.9 and 1.1. The values of influencing factors, that is, the opening direction and
Cs < 1 for the measurements points on the outermost circle structure spacing, the wind direction angle had the
indicated snow erosion. Thus, the stadium surface would not greatest influence on the snow distribution on the surface
be damaged by uneven snow distribution. of the gymnasium. The snow on the surface of the
gymnasium under a wind direction angle of 270° had the
largest erosion area, which was the most structurally safe
4.2. Influence of Spacing. Tests were conducted for a gym- and beneficial. The erosion of snow under the 225° wind
nasium span of L and spacing between the stadium and the direction angle and 315° wind direction angle was also
gymnasium of 0.3 L, 0.5 L, 1 L, 1.5 L, 2 L, and 2.5 L. The snow relatively serious. The reason is that, for these three wind
distribution of the two structures was compared to the angles, the gymnasium was located upstream of the sta-
results of the single models without interference and is dium. The incoming wind blew directly on the surface of
shown in Figure 13. the gymnasium, and the stadium did not play a blocking
In Figure 13, the same variation in Cs was found for the role. The snow deposition areas at the 225° and 315° wind
gymnasium and the stadium under the seven working direction angles were not as large as the erosion area, but
conditions. All Cs values decreased with increasing distance the snow thickness at the deposition site was also ex-
(0.3 L-2 L). For the 0.3 L spacing, the Cs values of the two tremely large. This results in a significant uneven distri-
buildings were significantly higher than for 2 L. From bution of snow on the surface of the gymnasium, which
Figure 13(a), it can be seen that the measurement points 13 was detrimental to the structure. The trends in Cs for wind
and 33 of the gymnasium surface were on the transversal axis direction angles of 0° and 180° were approximately the
of the leeward side. For measurement point 13, the Cs value same. Under the 45° and 135° wind direction angles, a
at 0.3 L was approximately 19.42% higher than that at 2 L. large area of snow deposit occurred, and the Cs value was
For measurement point 33, the Cs value at 0.3 L was ap- between 1.1 and 1.3. Excessive snow can easily cause the
proximately 17.91% higher than that at 2 L. From roof to collapse. It is believed that the stadium was at the
Figure 13(b), it follows that the values of Cs were significantly upstream of the gymnasium at this time. Due to the
higher on the leeward side than those on the windward side blocking effect of the stadium, the incoming wind pro-
for the stadium measurement points for the outer circle and duced a complex turbulence, which was extremely det-
second circle. For measurement point 20, the Cs value at rimental to the safety of the gymnasium.
0.3 L was approximately 16.67% higher than that at 2 L. For In the study of the distribution regularity of wind-in-
measurement point 40, the Cs value at 0.3 L was approxi- duced snow motion, the wind direction angles were a very
mately 19.85% higher than that at 2 L. Thus, under different important factor. However, in the wind tunnel test, it was
spacings, the wind-induced snow drift had a mutual in- impossible to quantitatively study the influence of the sta-
fluence on the adjacent long-span buildings; that is, both the dium with one open end on the snow distribution on the
blocked (gymnasium) and blocking (stadium) structures gymnasium surface and the mutual interference effect be-
were affected. For spacings of 2 L and 2.5 L, the Cs values of tween them. Therefore, a numerical simulation was adopted
both surfaces were essentially the same as without to supplement this influence factor. This method can more
interference. intuitively reflect the influence of the wind direction angle
The reason for this is that there was a large difference in on the surface snow of the gymnasium, with an interference
the heights between the stadium and gymnasium, and the coefficient, Ic:
Advances in Civil Engineering 11
1.5 1.5
W L W L W L
deposition
W L W L W L W L W
deposition
1.4 1.4
Snow
Snow
1.3 Wind 1.3 Wind
1.2 1.2
1.1 1.1
Cs
Cs
1.0 1.0
0.9 0.9
erosion
erosion
Snow
0.8 0.8
Snow
0.7 0.7
Fourth Innermost
0.6 Outer circle (first circle) Second circle Third circle circle circle 0.6 Outer circle (first circle) Second circle Innermost circle
0.5 0.5
0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70
Measuring point number Measuring point number
0.3L 2L 0.3 L 2L
0.5L 2.5L 0.5 L 2.5 L
1L No interference 1L No interference
1.5L 1.5 L
(a) (b)
Figure 13: Snow distribution on the gymnasium and stadium surfaces for different spacings between structures. (a) Gymnasium.
(b) Stadium.
1.2
1.1
pressure in regions of high negative pressure. The afore-
1.0 mentioned considerations produced the deviations between
0.9
Cs
the results of the wind tunnel test and the numerical sim-
0.8
erosion
0.7
0.6
Fourth Innermost
for the test and simulation results, indicating that the nu-
0.5 Outer circle (first circle) Second circle Third circle circle circle merical simulation was reasonably accurate.
0.4
0 10 20 30 40 50 60 70 To create a clearer analysis of the interference coefficient
Measuring point number Ic, the Ic of the gymnasium under the eight groups of wind
0° 180° direction angles are divided into groups for research. These
45° 225° groups are the working conditions of the gymnasium
90° 270° downstream of the downwind (45°, 90°, and 135°), the
135° 315° gymnasium upstream of the downwind (225°, 270°, and
Figure 14: Snow distribution on the gymnasium surface under 315°), and the wind direction perpendicular to the transverse
different wind direction angles. axis of the gymnasium (0° and 180°). The wind direction is
defined in Figure 6(b), and the obtained interference co-
efficients are compared in Figure 16.
q′ From Figure 16(a), it can be seen that when the wind
Ic � , (14)
q direction angles were 45°, 90°, and 135°, Ic > 1, indicating
that under this group of wind direction angles, the impact of
where q′ is the snow cover on the gymnasium surface and q the stadium on the gymnasium was mainly amplification
is the cover of unaffected snow. To facilitate the analysis, we interference. For the 45° and 135° wind direction angles, the
define Ic � 1 as a line of demarcation, where Ic ≤ 1 corre- peaks of Ic were on the longitudinal axis of the gymnasium.
sponds to blockage interference and Ic > 1 indicates an Attention should be given to the impact of snow on the roof.
amplification interference. A large value of |Ic − 1| implies a These points had Ic values far greater than the 90° wind
significant interference effect on the gymnasium surface. direction angle. For measurement point 7, the value of Ic at
The simulation accuracy is verified by comparing the 90° was smaller than that at 45° and 135° by 19.23% and
results of a numerical simulation for a 180° gymnasium 17.10%, respectively. For measurement point 19, these values
opening with the test results, as shown in Figure 15. were 18.24% and 16.55% smaller. For this group of wind
In Figure 15, the numerical simulation results were direction angles, the 45° and 135° wind direction angles had
larger than the test results, which is explained as follows. more significant interference effects than the 90° wind di-
First, it was difficult to accurately simulate the wind tunnel rection angle, which were more unfavourable for structural
test environment by using only the wind profile and safety.
roughness at the inlet in the numerical simulation. The Figure 16(b) shows that there was both amplification
boundary conditions also impacted the results by creating interference and blockage interference under the wind di-
vortexes and separation in the airflow around the model. rection angles of 225°, 270°, and 315°. Amplification inter-
Second, a scale model was used in the wind tunnel test, ference was in the area close to the stadium, and blockage
whereas a full-scale model was numerically simulated. Third, interference mainly occurred in the windward area of the
12 Advances in Civil Engineering
1.6 1.6
W L W L W L W L W W L W L W L
1.5 1.5
Snow deposition
Snow deposition
1.4 Wind 1.4
1.3 1.3 Wind
1.2 1.2
1.1 1.1
Cs
Cs
1.0 1.0
0.9 0.9
Snow erosion
Snow erosion
0.8 0.8
0.7 Fourth Innermost 0.7
0.6 Outer circle (first circle) Second circle Third circle circle circle 0.6 Outer circle (first circle) Second circle Innermost circle
0.5 0.5
0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70
Measuring point number Measuring point number
Results of numerical simulation Results of numerical simulation
Test results Test results
(a) (b)
Figure 15: Comparison of the results from tests and simulations. (a) Gymnasium. (b) Stadium.
1.8 1.7
1.7 1.6
1.6 1.5
Amplification
Amplification
interference
interference
1.4
1.5 1.3
1.4 1.2
1.3 1.1
Ic
Ic
1.2 1.0
1.1 0.9
interference
0.8
Blockage
1.0
interference
Blockage
1.2
1.1
Ic
1.0
interference
Blockage
Figure 16: Interference coefficients for the gymnasium surface for different wind direction angles. (a) 45°, 90°, and 135°. (b) 225°, 270°, and
315°. (c) 0° and 180°.
roof. At the 225° and 315° wind direction angles, the max- minimum value of Ic was 0.75, which was beneficial to
imum value of Ic was 1.52, and the minimum value of Ic was structural safety.
0.62. Due to the enormous difference between the Ic values From Figure 16(c), it can be seen that the trends of
under the two working conditions, the snow distribution on changes for Ic under the wind direction angles of 0° and 180°
the roof was extremely uneven and could easily cause roof were roughly the same, and Ic > 1, indicating that the impact
damage. The amplification interference effect at the 270° of the stadium on the gymnasium was mainly amplification
wind direction angle was very small. The maximum value of interference. However, the maximum value of Ic at the 0°
Ic was 1.08, and the blocking effect was obvious. The wind direction angle was 1.18, and the maximum value of Ic
Advances in Civil Engineering 13
at the 180° wind direction angle was 1.15. In summary, the For functional buildings such as stadiums and gymnasiums
amplification interference effect of the stadium on the where people are concentrated, avoiding snow disasters has
gymnasium under the wind direction angles of 0° and 180° always been a focus of research. There are many factors that
was far less than that under the wind direction angles of 45°, affect snow distribution on the surface of such large-span
90°, and 135°. Based on the abovementioned figures, it can be structures, among which are the opening direction of the
concluded that the amplification interference effect under stadium, structure spacing, wind direction angle, temperature,
the 45° wind direction angle was particularly serious, which and viscosity of the snow particle. The focus of the present
was extremely unfavourable to the roof’s stability, while the paper is on the first three factors. Concerning snow distri-
270° wind direction angle was the most beneficial to bution, the wind direction angle has the greatest effect and
structural safety. This conclusion was consistent with the spacing has the least effect. For such large-span building
results of the wind tunnel tests under different wind di- complexes, our study indicates that the designer should try to
rection angles. ensure that the lower buildings are located upstream of the
incoming wind. If there are openings in the building, they
should be oriented towards the other large-span building, and
5. Discussion the two structures should be separated far enough.