You are on page 1of 8

[1] TYPE EXAMINATION CERTIFICATE

[2] Equipment or Protective System intended for use


in Potentially Explosive Atmospheres
Directive 2014/34/EU

[3] Type Examination Certificate Number: DEMKO 13 ATEX 1325026X Rev. 20

[4] Product: Programmable Controllers – 1756 Series Modules

[5] Manufacturer: Rockwell Automation

[6] Address : 1201 S 2nd St., Milwaukee, WI, 53204 USA

[7] This equipment and any acceptable variation thereto is specified in the schedule to this certificate and the documents therein referred to.

[8] UL International Demko A/S certifies that this product has been found to comply with the Essential Health and Safety Requirements relating to
the design and construction of products intended for use in potentially explosive atmospheres given in Annex II to Directive 2014/34/EU of the
European Parliament and of the Council, dated 26 February 2014.

The examination and test results are recorded in confidential report no. US/UL/ExTR14.0009/14

[9] Compliance with the Essential Health and Safety Requirements has been assured by compliance with:

EN IEC 60079-0:2018 EN 60079-15:2010

except in respect of those requirements listed at item 18 of the Schedule.

[10] If the sign "X" is placed after the certificate number, it indicates that the product is subject to the Specific Conditions of Use specified in the
schedule to this certificate.

[11] This Type examination certificate relates only to the design of the specified product, and not to specific items of product subsequently
manufactured.

[12] The marking of the product shall include the following:

II 3 G Ex nA IIC T4 Gc

This is to certify that the sample(s) of the Product described herein (“Certified Product”) has been investigated
and found in compliance with the Standard(s) indicated on this Certificate, in accordance with the ATEX Product
Certification Manager Certification Program Requirements. This certificate and test results obtained apply only to the product
sample(s) submitted by the Manufacturer. UL did not select the sample(s) or determine whether the sample(s)
Jan-Erik Storgaard provided were representative of other manufactured product. UL has not established Follow-Up Service or other
surveillance of the product. The Manufacturer is solely and fully responsible for conformity of all product to all
applicable Standards, specifications, requirements or Directives. The test results may not be used, in whole or in
part, in any other document without UL’s prior written approval.

Date of issue: 2013-08-07


Re-issued: 2021-10-28

Certification Body UL International Demko A/S, Borupvang 5A, 2750 Ballerup, Denmark
Tel. +45 44 85 65 65, info.dk@ul.com, www.ul.com

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 1 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
[15] Description of Product:
1756-A10 Series C, 1756-A13 Series C, 1756-A17 Series C, 1756-A4 Series C, 1756-A7 Series C, 1756-A7XT Series B and C, and 1756-
A10XT Series C are modular components of the Allen-Bradley ControlLogix industrial control system. It provides physical mounting,
bonding to the system protective earth equipment grounding conductor, bonding to the system functional ground conductor, limited energy
power supply distribution conductors, and digital data transfer and system interconnection conductors for all of the plug-in modules of the
system.

1756-CN2, 1756-CN2R, and 1756-CN2RXT Series C modules are modular components of the Allen-Bradley ControlLogix industrial control
system. They are utilized as data communication interfaces between the control system and other systems or devices operating on a
ControlNet communications network.

1756-DHRIOXT Series E module is a modular component of the Allen-Bradley ControlLogix industrial control system. It is utilized as a data
communications interface between the control system and other systems or devices operating on a DataHighway communications network.

1756-EN2F Series C is a modular component of the Allen-Bradley ControlLogix industrial control system. It is utilized as a data
communications interface between the control system and other systems or devices operating on a fiber optic Ethernet communications
network.

1756-EN2TR Series C, 1756-EN2TP Series A, 1756-EN3TR Series B,1756-EN2TRXT Series C and 1756-EN2TPXT Series A are modular
component of the Allen-Bradley ControlLogix industrial control system. They provide a redundant data communications interface between
the control system and other systems or devices operating on an Ethernet communications network.

1756-EN2T Series D, 1756-EN2TSC Series B, 1756-EN2TXT Series D modules are modular component of the Allen-Bradley ControlLogix
industrial control system. It is utilized as a data communications interface between the control system and other systems or devices
operating on an Ethernet communications network.

1756-ESMCAP, 1756-ESMCAPXT, and 1756--ESMNRM, 1756-ESMNRMXT, 1756-ESMNSE and 1756–ESMNSEXT Series B Energy
Storage Modules are a module component of a 1756 ControlLogix system. These modules non-battery power used with the 1756-L7x
processor family to provide non-battery power to backup program states in the event of power loss.

1756-IF8I Series A and 1756-IF8I Series B is a modular component of the Allen-Bradley ControlLogix industrial control system. It is used to
provide analog voltage and current inputs for control purposes.

1756-IRT8I Series A and 1756-IRT8I Series B are modular components of the Allen-Bradley ControlLogix industrial control system. It is
utilized device for measuring the voltages and currents of analog devices such as thermocouples or RTDs.

1756-L71, 1756-L72, 1756-L73, 1756-L73XT, 1756-L74, and 1756–L75 Series B modules are modular component of the Allen-Bradley
ControlLogix industrial control system. These modules execute programs to monitor and control processes through other modules of the
ControlLogix system

The 1756-L81E, 1756-L81ES, 1756-L82E, 1756-L82ES, 1756-L83E, 1756-L83ES, 1756-L84E, 1756-L84ES,1756-L85E, 1756-L81E-NSE,
1756-L82E-NSE, 1756-L83E-NSE, 1756-L84E-NSE, 1756-L85E-NSE, 1756-L81EP, 1756-L83EP, 1756-L85EP, 1756-L81EXT, 1756-
L82EXT, 1756-L83EXT, 1756-L84EXT, and 1756-L85EXT and 1756-L8SP Series B modules are modular component of the Allen-Bradley
ControlLogix industrial control system. These modules execute programs to monitor and control processes through other modules of the
ControlLogix system.

1756-OF8I Series A and 1756-OF8I Series B module is a modular component of the Allen-Bradley ControlLogix industrial control system. It
is used to provide analog voltage and current outputs for control purposes

1756-PB75R Series A, 1756-PBXTR Series A, 1756-PSCA2 Series A, and 1756-PSCA2XT Series A modules are modular components of
the Allen-Bradley ControlLogix industrial control system. The modules are chassis power supplies and adapters that provide redundant
power to a ControlLogix chassis. The 1756-PSCA2 or 1756-PSCA2XT provides the ability to connect two 1756-PB75R or 1756-PBXTR
supplies to a chassis to maintain one of the supplies online in the event of one supply failure.

1756-PB72 Series C, 1756-PB75 Series B, 1756-PBXT Series B, 1756-PB30XT Series A and 1756-PB50 Series A modules are a modular
component of the Allen-Bradley ControlLogix industrial control system. These modules are used to provide operating power to the chassis
and installed modules.

1756-RM2 and 1756-RM2XT Series A are modular component of the Allen-Bradley ControlLogix industrial control system. This equipment
is a modular component of the Allen-Bradley ControlLogix industrial control system. It provides a redundant data communications interface
between the control system and other systems or devices operating on a Fiber Optic Ethernet communications network.

The optical radiation output of the component with respect to explosion protection, according to Annex II clause 1.3.1 of the Directive
2014/34/EU is covered in this certificate based on Exception 1) to the scope of EN 60079-28:2015.

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 2 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
Temperature range:
The relation between ambient temperature and the assigned temperature class is as follows:

Module (see Note) Series Ambient temperature range Temperature class


1756-A10 C -25°C to +60°C T4
1756-A13 C -25°C to +60°C T4
1756-A17 C -25°C to +60°C T4
1756-A4 C -25°C to +60°C T4
1756-A7 C -25°C to +60°C T4
1756-A7XT B -25°C to +70°C T4
1756-A7XT C -25°C to +60°C T4
1756-A10XT C -25°C to +70°C T4
1756-CN2 C 0 C to +60 C T4
1756-CN2R C 0 C to +60 C T4
1756-CN2RXT C -25°C to +70°C T4
1756-DHRIOXT E -25°C to +70°C T4
1756-EN2F C 0°C to +60°C T4
1756-EN2T D 0 C to +60 C T4
1756-EN2TP A 0 C to +60 C T4
1756-EN2TR C 0 C to +60 C T4
1756-EN2TPXT A -25°C to +70°C T4
1756-EN2TRXT C -25°C to +70°C T4
1756-EN2TSC B 0 C to +60 C T4
1756-EN2TXT D -25°C to +70°C T4
1756-EN3TR B 0 C to +60 C T4
1756-ESMCAP B 0ºC to +60 ºC T4
1756-ESMCAPXT B -25°C to +70°C T4
1756-ESMNRM B 0ºC to +60 ºC T4
1756-ESMNRMXT B -25°C to +70°C T4
1756-ESMNSE B 0ºC to +60 ºC T4
1756-ESMNSEXT B -25°C to +70°C T4
1756-IF8I A, B 0 C to +60 C T4
1756-IRT8I A, B 0 C to +60 C T4
1756-L71 B 0 C to +60 C T4
1756-L72 B 0 C to +60 C T4
1756-L73 B 0 C to +60 C T4
1756-L73XT B -25°C to +70°C T4
1756-L74 B 0 C to +60 C T4
1756-L75 B 0 C to +60 C T4
1756-L81E 0°C to 50°C (Series B Chassis) or T4
B
0°C to 60°C (Series C Chassis)
1756-L81ES B 0°C to 50°C (Series B Chassis) or T4
0°C to 60°C (Series C Chassis)
1756-L82E 0°C to 50°C (Series B Chassis) or T4
B
0°C to 60°C (Series C Chassis)
1756-L82ES B 0°C to 50°C (Series B Chassis) or T4
0°C to 60°C (Series C Chassis)
1756-L83E 0°C to 50°C (Series B Chassis) or T4
B
0°C to 60°C (Series C Chassis)
1756-L83ES B 0°C to 50°C (Series B Chassis) or T4
0°C to 60°C (Series C Chassis)
1756-L84E 0°C to 50°C (Series B Chassis) or T4
B
0°C to 60°C (Series C Chassis)
1756-L84ES B 0°C to 50°C (Series B Chassis) or T4
0°C to 60°C (Series C Chassis)
1756-L85E 0°C to 50°C (Series B Chassis) or T4
B
0°C to 60°C (Series C Chassis)
1756-L8SP B 0°C to 50°C (Series B Chassis) or T4
0°C to 60°C (Series C Chassis)
1756-L81E-NSE B 0 °C to 50 °C (Series B Chassis) or T4
0 °C to 60 °C (Series C Chassis)
1756-L82E-NSE B 0 °C to 50 °C (Series B Chassis) or T4
0 °C to 60 °C (Series C Chassis)
1756-L83E-NSE B 0 °C to 50 °C (Series B Chassis) or T4
0 °C to 60 °C (Series C Chassis)
1756-L84E-NSE B 0 °C to 50 °C (Series B Chassis) or T4
0 °C to 60 °C (Series C Chassis)
1756-L85E-NSE B 0 °C to 50 °C (Series B Chassis) or T4
0 °C to 60 °C (Series C Chassis)
1756-L81EP B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 3 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
Module (see Note) Series Ambient temperature range Temperature class
1756-L83EP B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-L85EP B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-L81EXT B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-L82EXT B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-L83EXT B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-L84EXT B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-L85EXT B -25°C to 50°C (Series B Chassis) or T4
-25°C to 60°C (Series C Chassis) or
-25°C to 70°C (Series C XT Chassis)
1756-OF8I A, B 0 C to +60 C T4
1756-PB30XT A -25 C to +70 C T4
1756-PB50 A 0°C to +60°C T4
1756-PB72 C 0 C to +60 C T4
1756-PB75 B 0 C to +60 C T4
1756-PB75R A 0 C to +60 C T4
1756-PBXT B -25°C to +70°C T4
1756-PBXTR A -25°C to +70°C T4
1756-PSCA2 A 0 C to +60 C T4
1756-PSCA2XT A -25°C to +70°C T4
1756-RM2 A 0 C to +60 C T4
1756-RM2XT A -25°C to +70°C T4
Note: Catalog Numbers may be followed by a 'K' to indicate a conformal coating option

Electrical data
Catalog
Number Mating Terminal
(See Note) Series Description Ratings Block
1756-A10 C CONTROLLOGIX 10 SLOT CHASSIS From system power supply / to any -
single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2V dc @ 1.5A/-
1756-A13 C CONTROLLOGIX 13 SLOT CHASSIS From system power supply / to any -
single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2V dc @ 1.5A/-
1756-A17 C CONTROLLOGIX 17 SLOT CHASSIS From system power supply / to any -
single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2V dc @ 1.5A/-
1756-A4 C CONTROLLOGIX 4 SLOT CHASSIS From system power supply / to any -
single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2V dc @ 1.5A/-
1756-A7 C CONTROLLOGIX 7 SLOT CHASSIS From system power supply / to any -
single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2V dc @ 1.5A/-

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 4 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
Catalog
Number Mating Terminal
(See Note) Series Description Ratings Block
1756-A7XT B EXTENDED TEMPERATURE From system power supply/to any -
CONTROLLOGIX 7 SLOT CHASSIS single plug-in module:
(ENHANCED) 5.1 V dc @ 10 Amps/6 Amps
24 V dc @ 2.0 Amps/2.0 Amps
3.3 V dc 4 Amps/4 Amps
1.2 V dc 1.5A/-
1756-A7XT C CONTROLOGIX 7 SLOT CHASSIS From system power supply / to any -
single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2 V dc 1.5 Amps/ -

1756-A10XT C CONTROLOGIX 10 SLOT CHASSIS From system power supply / to any -


single plug-in module:
5.1 V dc @ 15 Amps / 6 Amps
24 V dc @ 2.8 Amps / 2.8 Amps
3.3 V dc 4 Amps / 4 Amps
1.2 V dc 1.5 Amps/-
1756-CN2 C CONTROLNET MODULE Power from system backplane: -
1.1A @ 5.1 V dc
1756-CN2R C CONTROLNET 2 CHANNEL MODULE Power from system backplane: -
1.3A @ 5.1 V dc
1756-CN2RXT C EXTENDED TEMPERATURE 2 Power from system backplane: -
CHANNEL CONTROLNET MODULE 1.3A @ 5.1 V dc
1756- E EXTENDED TEMPERATURE Power from system backplane: -
DHRIOXT CONTROLLOGIX DATAHIGHWAY - 850 mA @ 5.1 V dc; 1.7 mA @ 24
REMOTE I/O COMMUNICATIONS V dc.
MODULE
1756-EN2F C CLX HI CAP EIP MOD - FBR OPTIC Power from system backplane: -
MODULE WITH DDR 5.1V dc, 1.2A
1756-EN2T D CLX HI-CAP ENET/IP MODULE - TP Power from system backplane: -
5.1 V dc, 1 A
1756-EN2TR C 2-PORT CLX HI-CAP ENET/IP MODULE Power from system backplane: -
- TP 5.1 V dc, 1A
1756-EN2TP A 2-PORT CLX HI-CAP ENET/IP MODULE Power from system backplane: -
- TP 5.1 V dc, 1A
1756- C CONTROLLOGIX XT DUAL PORT Power from system backplane: -
EN2TRXT ETHERNET/IP MODULE 5.1 V dc, 1A
1756- A 2-PORT CLX HI-CAP ENET/IP MODULE Power from system backplane: -
EN2TPXT - TP 5.1 V dc, 1A
1756-EN2TSC B CLX HI-CAP ENET/IP MODULE - TP Power from system backplane: -
5.1 V dc, 1 A
1756-EN2TXT D CLX ENET/IP MODULE - TP, X-ENVT Power from system backplane: -
5.1 V dc, 1 A
1756-EN3TR B 2-PORT CLX HI-CAP ENET/IP MODULE Power from system backplane: -
- TP Backplane:5.1 V dc, 1A
1756- B CONTROLLOGIX ENERGY STORAGE Power from system backplane: -
ESMCAP MODULE-CAP 330mA @ 5.1V dc
1756- B L7XT ENERGY STORAGE MODULE- Power from system backplane: -
ESMCAPXT CAPACITOR 330mA @ 5.1V dc
1756- B CONTROLLOGIX ENERGY STORAGE Power from system backplane: -
ESMNRM MODULE NON REMOVE 330mA @ 5.1V dc
1756- B L7XT ENERGY STORAGE MODULE- Power from system backplane: -
ESMNRMXT NON REMOVE 330mA @ 5.1V dc
1756- B CONTROLLOGIX ENERGY STORAGE Power from system backplane: -
ESMNSE MODULE NSE 300mA @ 5.1V dc
1756- B L7XT ENERGY STORAGE MODULE-NO Power from system backplane: -
ESMNSEXT ENERGY 300mA @ 5.1V dc

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 5 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
Catalog
Number Mating Terminal
(See Note) Series Description Ratings Block
1756-IF8I A, B CONTROLLOGIX 8 POINT ANALOG Power from system backplane: 1756-TBCH
INPUT 5.1V dc,200 mA, 24V dc,400 mA 1756-TBS6H

Input Voltage: -10 to +10V.


0 to 10V
0 to 5V

Input Current: 0 to 20 mA.

Output Current: 0 to 20 mA
1756-IRT8I A, B CONTROLLOGIX 8 POINT Power from system backplane: 1756-TBCH
THERMOCOUPLE/RTD INPUT 5.1V dc,200 mA 1756-TBS6H
24V dc,150 mA
Input: 1-4000 Ohms; +/-100mV
Thermocouple:
B,C,E,J,K,R,S,T,N,D,L
1756-L71 B CONTROLLOGIX 2 MB CONTROLLER Power from system backplane: -
800mA @ 5.1V dc,
5 mA @ 1.2V dc
1756-L72 B CONTROLLOGIX 4 MB CONTROLLER Power from system backplane: -
800mA @ 5.1V dc,
5 mA @ 1.2V dc
1756-L73 B CONTROLLOGIX 8 MB CONTROLLER Power from system backplane: -
800mA @ 5.1V dc,
5 mA @ 1.2V dc
1756-L73XT B CONTROLLOGIX 8MB CONTROLLER Power from system backplane: -
L7XT 800mA @ 5.1V dc,
5 mA @ 1.2V dc
1756-L74 B CONTROLLOGIX 16 MB CONTROLLER Power from system backplane: -
800mA @ 5.1V dc,
5 mA @ 1.2V dc
1756-L75 B CONTROLLOGIX 32 MB CONTROLLER Power from system backplane: -
800mA @ 5.1V dc,
5 mA @ 1.2V dc
1756-L81E B 3 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L81ES B 3 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L82E B 5 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L82ES B 5 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L83E B 8 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L83ES B 8 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L84E B 20 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L84ES B 20 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L85E B 32 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC
1756-L8SP B 32 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200mA @ 5.1V DC
5mA @ 1.2V DC

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 6 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
Catalog
Number Mating Terminal
(See Note) Series Description Ratings Block
1756-OF8I A, B CONTROLLOGIX 8 POINT ANALOG Power from system backplane: 1756-TBCH
OUTPUT 5.1V dc,200 mA 1756-TBS6H
24V dc,385 mA

Output Voltage: -10 to +10V.


0 to 10V
0 to 5V

Output Current: 0 to 20 mA.


1756-PB30XT A CONTROLLOGIX EXTENDED Supply: 24V dc, 50W@70C Output: -
TEMPERATURE SLIM POWER SUPPLY 30W max. 1.25A@24V dc
(24V DC INPUT) 6.0A@5.1V dc 2.0A@3.3V dc
1.5A@1.2V dc
1756-PB50 A CONTROLLOGIX SLIM POWER Supply: 24V dc, 85W@50 C, -
SUPPLY (24V DC INPUT) 70W@60 C
Output: 60W max @ 50 C; 50W
max @ 60 C. 2.5A@24V dc
8.0A@5.1V dc 2.0A@3.3V dc
1.5A@1.2V dc
1756-PB72 C CONTROLLOGIX POWER SUPPLY Input: 24V dc, 95W -
(24V DC INPUT) Output: 10A @ 5.1V dc, 2.8A @
24V dc, 4A @ 3.3V dc, 1.5A @
1.2V dc, 75 Watts total maximum.
1756-PB75 B CONTROLLOGIX POWER SUPPLY Input: 24V dc, 95W -
(24V DC INPUT) Output: 13A @ 5.1V dc, 2.8A @
24V dc, 4A @ 3.3V dc, 1.5A @
1.2V dc, 75 Watts total maximum.
1756-PB75R A CONTROLLOGIX REDUNDANT Supply: 24 V dc, 110 Watts. -
POWER SUPPLY (DC INPUT) Output: 5.1 V dc, 13 A; 24 V dc, 2.8
A; 3.3 V dc, 4.0 A; 1.2 V dc, 1.5 A;
75 Watts total output power.
Status Contact Output: 90V
dc,50mA Resistive
1756-PBXT B CONTROLLOGIX EXTENDED Supply: 18-32V dc, 70W -
TEMPERATURE POWER SUPPLY (24V Output: 10A @ 5.1V dc, 2.1A @
DC INPUT) 24V dc, 4A @ 3.3V dc, 1.5A @
1.2V dc, 52 Watts total maximum.
1756-PBXTR A CONTROLLOGIX REDUNDANT Supply: 24 V dc, 81 Watts. -
POWER SUPPLY EXTENDED Output: 5.1 V dc, 10 A; 24 V dc, 2.1
TEMPERATURE (DC INPUT) A; 3.3 V dc, 4.0 A; 1.2 V dc, 1.5 A;
52 Watts total output power.
Status Contact Output: 90V
dc,50mA Resistive
1756-PSCA2 A REDUNDANT POWER SUPPLY Power from system backplane: -
CHASSIS ADAPTER 24 V dc, 2.8 A
5.1 V dc, 15 A
3.3 V dc, 4 A
1.2 V dc, 1.5A
1756- A REDUNDANT POWER SUPPLY Power from system backplane: -
PSCA2XT CHASSIS ADAPTER WITH 24 V dc, 2.8 A
CONFORMAL COATING 5.1 V dc, 15 A
3.3 V dc, 4 A
1.2 V dc, 1.5A
1756-RM2 A SYSTEM REDUNDANCY MODULE Power from system backplane: -
1.16 A @ 5.1 V dc; 3.4 mA @ 24 V
dc
1756-RM2XT A SYSTEM REDUNDACNY MODULE Power from system backplane: -
EXTENDED TEMPERATURE 1.16 A @ 5.1 V dc; 3.4 mA @ 24 V
dc
1756-L81E- B 3 MB LOGIX 558X CONTROLLER Power from system backplane: -
NSE 1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L82E- B 5 MB LOGIX 558X CONTROLLER Power from system backplane: -
NSE 1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 7 of 8
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 13 ATEX 1325026X Rev. 20
Catalog
Number Mating Terminal
(See Note) Series Description Ratings Block
1756-L83E- B 8 MB LOGIX 558X CONTROLLER Power from system backplane: -
NSE 1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L84E- B 20 MB LOGIX 558X CONTROLLER Power from system backplane: -
NSE 1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L85E- B 32 MB LOGIX 558X CONTROLLER Power from system backplane: -
NSE 1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L81EP B 3 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L83EP B 8 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L85EP B 32 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L81EXT B 3 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L82EXT B 5 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L83EXT B 8 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L84EXT B 20 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc
1756-L85EXT B 32 MB LOGIX 558X CONTROLLER Power from system backplane: -
1200 mA @ 5.1 V dc; 5 mA @ 1.2
V dc

Note: Models may be followed by the letter ‘K’ to indicate a conformal coating option.

Routine tests:
None required.

[16] Descriptive Documents


The scheduled drawings are listed in the report no. provided under item no. [ 8 ] on page 1 of this Type Examination Certificate.

[17] Special Conditions of Use:


This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54 (as defined
in EN60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN 60664-1) when applied in Zone 2
environments. The enclosure must be accessible only by the use of a tool.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated
voltage when applied in Zone 2 environments.
This equipment must be used only with ATEX certified Rockwell Automation backplanes.
Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.
The instruction in the user manual shall be observed.

[18] Essential Health and Safety Requirements


The Essential Health and Safety Requirements (EHSRs) covered by the standards listed at item 9.

Additional information

00-IC-F0060-1 – Issue 18.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 8 of 8