INSTALLATION MANUAL

System air conditioner

REYQ18PY1
REYQ20PY1
REYQ22PY1
REYQ24PY1
REYQ26PY1
REYQ28PY1
REYQ30PY1
REYQ32PY1
REYQ34PY1
REYQ36PY1
REYQ38PY1
REYQ40PY1
REYQ42PY1
REYQ44PY1
REYQ46PY1
REYQ48PY1
DAIKIN INDUSTRIES, LTD.

RXYQ5PY1(E), RXYQ8PY1(E), RXYQ10PY1(E), RXYQ12PY1(E), RXYQ14PY1(E), RXYQ16PY1(E), RXYQ18PY1(E), REYP8PY1, REYP10PY1, REYP12PY1, REYP14PY1, REYP16PY1,
RXYQ20PY1(E), RXYQ22PY1(E), RXYQ24PY1(E), RXYQ26PY1(E), RXYQ28PY1(E), REYP18PY1, REYP20PY1, REYP22PY1, REYP24PY1, REYP26PY1, REYP28PY1, REYP30PY1, REYP32PY1,
RXYQ30PY1(E), RXYQ32PY1(E), RXYQ34PY1(E), RXYQ36PY1(E), RXYQ38PY1(E), REYP34PY1, REYP36PY1, REYP38PY1, REYP40PY1, REYP42PY1, REYP44PY1, REYP46PY1, REYP48PY1,
RXYQ40PY1(E), RXYQ42PY1(E), RXYQ44PY1(E), RXYQ46PY1(E), RXYQ48PY1(E), REYP8PY1B, REYP10PY1B, REYP12PY1B, REYP14PY1B, REYP16PY1B,
RXYQ50PY1(E), RXYQ52PY1(E), RXYQ54PY1(E), REMP8PY1, REMP10PY1, REMP12PY1, REMP14PY1, REMP16PY1,
BSVQ100PV1, BSVQ160PV1, BSVQ250PV1,

EN60335-2-40,

Low Voltage 2006/95/EC


Machinery Safety 98/37/EC
Electromagnetic Compatibility 89/336/EEC

DAIKIN.TCF.024

TNO

0510260101

Noboru Murata
Manager Quality Control Department Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,
1st of April 2007 Kita-ku, Osaka, 530-8323 Japan

3P177868-1B
[Q8 · 10 · 12 type]
< If installed as a single unit > < When installed in serial >
(Pattern 1) ≥300 (Pattern 1) ≥300
4 4
1 1
1 ≥10 ≥20 1 ≥10
≥10 ≥500 ≥10 ≥20 ≥500
2 3 3 2
2

≥1500

≥1000
(Pattern 2) ≥100 (Pattern 2) ≥100 3
4 4 4

≥1000
0
[Q14 · 16 type] ≥50 00
≥50 1 ≥50 1 ≥100 ≥1 ≥1500
≥500 ≥100 ≥50 ≥500
3 3 ≥1500
1 2 5 ≥1500

2 (Pattern 3) ≥300 2 (Pattern 3) ≥300 (mm)

≥200 1 ≥200 ≥400 1 ≥400

figure 1 figure 2 figure 3

1 2 3 4
2 1
2
1

2
0
≥10
0
≥10
3
3 4 0 0
1 4 ≥10 0 ≥10 0
≥10 ≥10 5
5

figure 4 figure 5 figure 6

A 1
B 1
1 6
2 4
5 6
3 2
765
765

729

631

4 5 3
2

3 3

2
1

figure 7 figure 8 figure 9 figure 10

1 3 2
2
5
4
1 6
3
4 4

figure 11 figure 12

1 2
3 4
6 7 6 7
5 8 5 8
9 15 9

9 9
14
15 16
9 19
9
10
13 17 18
11

12

figure 13
16-1
C
1 2 1
3 4
A 3
1 2
5 4
7
figure 14 D
1 5

6
1 1 4
16-2 8 16-3
B 2

figure 15 figure 16

1
1 2
5 12 12
2 8 13
4 9 11
9 10
1 3
6
2
3
4
8 8 3
4
7 7
5
6

figure 17 figure 18

1 2 2 1 2 : 8
3 4 5 1 2
11
A1P A1P F1 F2 F1 F2 F1 F2 F1 F2
A1P TO OUT/D UNIT TO IN/D UNIT 1 TO OUT/D UNIT TO IN/D UNIT 1
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT TO MULTI UNIT TO MULTI UNIT F1 F2
F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q1 Q2 9 9 F1 F2 F1 F2 F1 F2
2 2
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2
10 10
6
F1 F2 F1 F2
1 1
7

figure 19 figure 20

5
L1 L2 L3 N

1 1
(A1P)
6
4 3
1 2
4
5
4
2
2 7
3 4 6
4

8 8

figure 21 figure 22 figure 23


[In case of 8~12HP type] [In case of 14~16HP type]
13 1

11 11

10 10
1

2 12 12
9 2 9

3 8 8
3

15

4
14
6 6
5 4 7
7

figure 24

7
8 15 15 15 1
1 9 3
6
10
11
12 2
2 3
13
4
5 14
2
: 19 F17
: 20 16 ( 18 ) 1

figure 25 figure 26 figure 27

1 3 4
1 2 5 12 13 14
6 6
2 7
8
3
1 9
4 10
2 2
5 11
3 5
: 16 : 18
4 : 17 15 ( : 19 )

figure 28 figure 29 figure 30

3 20
4
5 12 13 14
6 1
7 2
8
1 9 3
10
2 4
11
: 16 : 18 9
: 17 ( : 19 ) 15

figure 31 figure 32
REYQ18PY1 REYQ26PY1 REYQ32PY1 REYQ38PY1 REYQ44PY1
REYQ20PY1 REYQ28PY1 REYQ34PY1 REYQ40PY1 REYQ46PY1 Installation
REYQ22PY1 REYQ30PY1 REYQ36PY1 REYQ42PY1 REYQ48PY1 VRVIII System air conditioner
manual
REYQ24PY1

Warning
CONTENTS • Ask your dealer or qualified personnel to carry out installation
1. FIRST OF ALL ......................................................................... 1 work. Do not try to install the machine yourself.
Improper installation may result in water leakage, electric
1-1. Safety considerations........................................................ 1
shocks or fire.
1-2. Special notice of product................................................... 2
• Perform installation work in accordance with this installation manual.
1-3. Disposal requirements ...................................................... 2
Improper installation may result in water leakage, electric shocks or fire.
2. INTRODUCTION...................................................................... 2
• When installing the unit in a small room, take measures against to
2-1. Combination ...................................................................... 2 keep refrigerant concentration from exceeding allowable safety
2-2. Standard supplied accessories ......................................... 3 limits in the event of refrigerant leakage.
2-3. Option accessory .............................................................. 3 Excessive refrigerant in a closed ambient can lead to oxygen defi-
2-4. Technical and Electrical specifications ............................. 3 ciency. Contact your dealer for more information.
2-5. Main components.............................................................. 3 • Be sure to use only the specified accessories and parts for instal-
3. SELECTION OF LOCATION ................................................... 3 lation work.
4. INSPECTING AND HANDLING THE UNIT ............................. 4 Failure to use the specified parts may result in water leakage,
5. PLACING THE UNIT................................................................ 4 electric shocks, fire or the unit falling.
6. REFRIGERANT PIPING .......................................................... 4 • Install the air conditioner on a foundation strong enough to with-
stand the weight of the unit.
6-1. Selection of piping material and Refrigerant branching kit 4 A foundation of insufficient strength may result in the unit falling
6-2. Protection against contamination when installing pipes.... 5 and causing injuries.
6-3. Pipe connection ................................................................ 5 • Carry out the specified installation work after taking into account
6-4. Connecting the refrigerant piping...................................... 5 strong winds, typhoons or earthquakes.
6-5. Example of connection...................................................... 7 Improper installation work may result in the unit falling and caus-
7. FIELD WIRING ...................................................................... 10 ing accidents.
7-1. Power circuit, safety device and cable requirements ...... 10 • Make sure that a separate power supply circuit is provided for this
7-2. Wiring Connection Example for Whole System .............. 10 unit and that all electrical work is carried out by qualified person-
7-3. Leading wire Procedure .................................................. 10 nel according to local and national regulations and this installation
7-4. Transmission Wiring Connection Procedure................... 11 manual.
7-5. Power Wiring Connection Procedure .............................. 11 An insufficient power supply capacity or improper electrical con-
7-6. Procedure for Wiring Inside Units ................................... 12 struction may lead to electric shocks or fire.
8. AIR TIGHT TEST AND VACUUM DRYING ........................... 12 • Be sure to establish an earth.
9. PIPE INSULATION ................................................................ 12 Do not earth the unit to a utility pipe, arrester or tele-
10. CHECKING OF DEVICE AND phone earth.
Incomplete earth may cause electrical shock or fire.
INSTALLATION CONDITIONS .............................................. 13
A high surge current from lightning or other sources may cause
11. ADDITIONAL REFRIGERANT CHARGE AND damage to the air conditioner.
CHECK OPERATION ............................................................ 13 • Be sure to install an earth leakage breaker.
11-1.Before working ............................................................... 13 Failure to install an earth leakage breaker may result in electric
11-2.Procedure of Adding Refrigerant charging and check shocks or fire.
operation14 • Before touching electrical parts, turn off the power.
12. ONSITE SETTINGS............................................................... 16 Failure to turn off the power may result in electric shocks.
13. TEST RUN ............................................................................. 16 • Make sure that all wiring is secured, the specified wires are used,
and no external forces act on the terminal connections or wires.
13-1.Before test run ............................................................... 16 Improper connections or installation may result in the terminals
13-2.Test Run ........................................................................ 16 overheating or fire.
13-3.Checks After Test Run................................................... 16 • When wiring the power supply and connecting the remote control-
14. CAUTION FOR REFRIGERANT LEAKS ............................... 16 ler wiring and transmission wiring, position the wires so that the
EL.COMPO.BOX lid can be securely fastened.
Improper positioning of the EL.COMPO.BOX lid may result in
1. FIRST OF ALL electric shocks or fire.
• If the refrigerant gas leaks during installation, ventilate the area
• This document is an installation manual for the Daikin REYQ-P immediately.
Series VRV Inverter. Before installing the unit, read this manual Toxic gas may be produced if the refrigerant gas comes into con-
thoroughly, and following the instructions contained in it. tact with fire.
After installation, do a test run to make sure the unit runs properly, • After completing the installation work, check that the refrigerant
and then explain how to operate and take care of the unit to the gas does not leak.
customer, using the operation manual. Toxic gas may be produced if the refrigerant gas leaks into the
Lastly, make sure the customer keeps this manual, along with the room and comes into contact with a source of fire, such as a fan
operation manual, in a safe place. heater, stove or cooker.
• Do not directly touch the refrigerant leaked from refrigerant piping
1-1 Safety considerations connections.
Please read these “Safety considerations” carefully before installing Frostbite may be caused.
• Do not allow children to mount on the outdoor unit, or avoid
air conditioning unit and be sure to install it correctly. The safety pre-
placing any object on it. Falling or tumble may result in injury.
cautions listed here are divided into two categories.
In either case, important safety information is listed which must be
read carefully. Caution
• While following the instructions in this installation manual,
Warning........Failure to observe a warning may result in death install drain piping in order to ensure proper drainage and insu-
or serious injury. late piping in order to prevent condensation.
Improper drain piping may result in water leakage and property
Caution.........Failure to observe a caution may result in injury damage.
• Install the indoor, BS and outdoor units, power supply wiring and
or damage to the unit. connecting wiring at least 1 meter away from televisions or radios
These too might lead to serious injury depend- in order to prevent image interference or noise.
ing on the circumstances. (Depending on the radio waves, a distance of 1 meter may not be
sufficient enough to eliminate the noise.)

1 English
• The indoor and BS unit should be installed as far away from fluo-
rescent lighting as possible. 4 1 factory refrigerant charge
Remote controller (wireless kit) transmitting distance can result of the product : see unit
shorter than expected in rooms with electronic fluorescent lamps 1 name plate (2)
(inverter or rapid start types). 2 additional refrigerant
• Do not install the air conditioner in the following locations: 2 amount charged in the field
(a) where a mineral oil mist or an oil spray or vapor is produced,
for example in a kitchen. 3 total refrigerant charge
Plastic parts may deteriorate and fall off or result in water leakage. 3 4 Contains fluorinated
(b) where corrosive gas, such as sulfurous acid gas, is produced. greenhouse gases covered
6 5 by the Kyoto Protocol
Corroding copper pipes or soldered parts may result in refrig-
erant leakage. 5 outdoor unit
(c) near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the con- 6 refrigerant cylinder and
manifold for charging
trol system and result in a malfunction of the unit.
(d) where flammable gas may leak, where there are carbon fiber (2)
In case of multiple outdoor systems, only 1 label must be adhered,
or ignitable dust suspensions in the air, or where volatile flam- mentioning the total factory refrigerant charge of all outdoor units
mables such as thinner or gasoline are handled. connected on the refrigerant system.
Operating the unit in such conditions may result in fire.
(e) Locations where small animals might build nests inside the unit. [DESIGN PRESSURE]
If small animals enter and come in contact with electrical parts, Since design pressure is 4.0MPa or 40bar (for R407C units : 3.3MPa
this can cause malfunctions, smoke, and fire. or 33bar), the wall thickness of pipes should be more carefully selected
in accordance with the relevant local and national regulations.

1-2 Special notice of product 1-3 Disposal requirements


[CLASSIFICATION] Dismantling of the unit, treatment of the refrigerant, oil and eventual
This air conditioner comes under the term “appliances not accessible other parts, should be done in accordance with the relevant local and
to the general public”. national regulations.
[EMC CHARACTERISTICS]
VRVIII System is a class A product. In a domestic environment this
product may cause radio interference in which case the user may be 2. INTRODUCTION
required to take adequate measures. • REYQ-P series are designed for outdoor installation and used for
[REFRIGERANT] cooling and heating aplications. The REYQ18-48P system is
VRVIII System use R410A refrigerant. multi outdoor unit system, which are only composed of REMQ8-
• The refrigerant R410A requires strict cautions for keeping the sys- 16P outdoor units. With a multi system combining up to three out-
tem clean, dry and tight. door units, rated cooling capacity from 50.4kW to 135kW and
Read the chapter “REFRIGERANT PIPING” carefully and follow rated heating capacity from 56.5kW to 150 kW can be achieved.
these procedures correctly. • The BS units that combined with REYQ-P system for changing
A.Clean and dry the refrigerant flow to indoor units are BSVQ100, 160, 250P type
Foreign materials (including mineral oils such as SUNISO oil or only. To combine with other type BS unit will cause malfunction.
moisture) should be prevented from getting mixed into the system. • The indoor units that combined with REYQ-P system for air con-
B.Tight ditioning are Daikin VRV series indoor units that compatible with
Take care to keep the system tight when installing. R410A. To learn which indoor units are compatible with R410A,
R410A does not contain any chlorine, does not destroy the refer to the product catalogs. To combine with other refrigerant
ozone layer, and does not reduce the earth’s protection against indoor unit will cause malfunction.
harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is 2-1 Combination
released. • The system name and that independent units are as follows.
• Since R410A is a mixed refrigerant, the required additional refrig- 〈The system name〉 〈Independent units〉
erant must be charged in its liquid state. If the refrigerant is REYP18PY1............REMQ10PY1 REMQ8PY1
charged in a state of gas, its composition changes and the system REYP20PY1............REMQ12PY1 REMQ8PY1
will not work properly. REYP22PY1............REMQ12PY1 REMQ10PY1
Limit by the total maximum refrigerant charge REYP24PY1............REMQ12PY1 REMQ12PY1
The total maximum refrigerant charge of a VRVIII system must be REYP26PY1............REMQ16PY1 REMQ10PY1
below 100kg, this to be in accordance with CE requirement REYP28PY1............REMQ16PY1 REMQ12PY1
(EN60335-2-40 standard). REYP30PY1............REMQ16PY1 REMQ14PY1
This means that in case the total maximum refrigerant charge of the REYP32PY1............REMQ16PY1 REMQ16PY1
system (factory and additional charge) is equal to or more than REYP34PY1............REMQ16PY1 REMQ10PY1 REMQ8PY1
100kg you must divide your multiple outdoor system into smaller REYP36PY1............REMQ16PY1 REMQ12PY1 REMQ8PY1
independent systems, each containing less than 100kg refrigerant REYP38PY1............REMQ16PY1 REMQ12PY1 REMQ10PY1
charge. REYP40PY1............REMQ16PY1 REMQ12PY1 REMQ12PY1
For factory charge, refer to the unit name plate. REYP42PY1............REMQ16PY1 REMQ16PY1 REMQ10PY1
Important information regarding the refrigerant used REYP44PY1............REMQ16PY1 REMQ16PY1 REMQ12PY1
This product contains fluorinated greenhouse gases covered by the REYP46PY1............REMQ16PY1 REMQ16PY1 REMQ14PY1
Kyoto Protocol. Do not vent gases into the atmosphere. REYP48PY1............REMQ16PY1 REMQ16PY1 REMQ16PY1
Refrigerant type : R410A • The indoor units can be installed in the following range.
GWP (1) value : 1975 〈Outdoor unit〉 〈Total capacity of indoor units〉
(1) REYQ18PY1 .......................... 225 ~ 585
GWP = global warming potential
REYQ20PY1 .......................... 250 ~ 650
Please fill in with indelible ink,
REYQ22PY1 .......................... 275 ~ 715
■ the factory refrigerant charge of the product,
REYQ24PY1 .......................... 300 ~ 780
■ the additional refrigerant amount charged in the field and REYQ26PY1 .......................... 325 ~ 845
■ + the total refrigerant charge on the refrigerant charge label REYQ28PY1 .......................... 350 ~ 910
supplied with the product. REYQ30PY1 .......................... 375 ~ 975
The filled out label must be adhered in the proximity of the product REYQ32PY1 .......................... 400 ~1040
charging port (e.g. onto the inside of the service cover). REYQ34PY1 .......................... 425 ~1105
REYQ36PY1 .......................... 450 ~1170
REYQ38PY1 .......................... 475 ~1235

English 2
REYQ40PY1 .......................... 500 ~1300 • Refrigerant branching kit
REYQ42PY1 .......................... 525 ~1365 for 3 piping
REYQ44PY1 .......................... 550 ~1430 REFNET header – KHRP25M33H KHRP25M72H KHRP25M73H
REYQ46PY1 .......................... 575 ~1495 REFNET joint KHRP25A22T KHRP25A33T KHRP25A72T KHRP25A73T
REYQ48PY1 .......................... 600 ~1560
for 2 piping
• For installing the 2 units multi system, Outdoor unit multi connec- REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73H
tion piping kit "BHFP26A90" are required. REFNET joint KHRP26A22T KHRP26A33T KHRP26A72T –
For installing the 3 units multi system, Outdoor unit multi connec-
• Pipe size reducer
tion piping kit "BHFP26A136" are required.
• When installing the multi system, connect the units as following for 3 piping for 2 piping
order. for REFNET header KHRP25M72HP KHRP25M73HP KHRP26M73HP
If install the system with different order, the Outdoor unit multi for REFNET joint KHRP25M72TP KHRP25M73TP –
connection piping kit may not suit and some pipe size reducer Make sure that any separately purchased accessories are designed
(field supply) may be required. for use with R410A.
Outdoor Outdoor Outdoor 2-4 Technical and Electrical specifications
Unit capacity unit A unit B unit C
A≥B≥C Refer to the Engineering Data Book for the complete list of specifications.

to indoor unit 2-5 Main components


Outdoor unit For main components and function of the main components, refer to
multi connection Outdoor unit multi the Engineering Data Book.
piping kit connection piping kit
(first branch) (second branch)

• If the total capacity of the connected indoor units exceeds the 3. SELECTION OF LOCATION
capacity of the outdoor unit, cooling and heating performance Select a location for installation that meets the following conditions
may drop when running the indoor units. See the capacity table in and get the customer’s permission.
the Engineering Data Book for details. 1. There is no danger of fire due to leakage of inflammable gas.
2-2 Standard supplied accessories 2. Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.
Confirm the following accessories are included. The storage location
of the accessories is shown in figure 1.
3. The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
Note 4. The piping length between the outdoor unit and the indoor unit
Do not throw away any of the accessories until installation is com- may not exceed the allowable piping length.
plete. They are needed for installation work. (Refer to “6. REFRIGERANT PIPING”)
Name Clamp(1) Clamp(2) Clamp(3) Manuals, etc.
5. Locations where the unit’s suction vent and outlet vent do not gen-
erally face the wind.
Quantity 8 pcs. 2 pcs. 1 pc. 1 pc. about each item
Wind blowing directly into the suction or outlet vents will interfere
• Operation manual
• Installation manual
with the unit’s operation.
• Declaration of conformity (PED) If necessary, install some kind of obstruction to block the wind.
Shape • "REQUEST FOR THE INDICATON"
label (Installation records) 6. The space around the unit is adequate for servicing and the min-
(Small) (Large) • "ADDITIONAL REF. CHARGE" label imum space for air inlet and air outlet is available.
(See the “Installation Space Examples” for the minimum space
Liquid side Liquid side Suction gas Suction gas HP / LP gas HP / LP gas
Name accessory accessory side accessory side accessory side accessory side accessory requirements.)
pipe (1) pipe (2) pipe (1) pipe (2) pipe (1) pipe (2)
Installation Space Examples
8 · 10 type 1 pc. 1 pc. 2 pcs. • The installation space requirement shown in figure 2 is a refer-
Quantity

12 type 1 pc. 1 pc. 1 pc. 1 pc. 2 pcs. ence for cooling operation when the outdoor temperature is 35°C.
14 · 16 type 1 pc. 1 pc. 1 pc. 1 pc. If the design outdoor temperature exceeds 35°C or the heat load
exceeds maximum capacity in all the outdoor unit, take an even
large space on the intake shown in figure 2.
Shape • During installation, install the units using the most appropriate of
the patterns shown in figure 2 for the location in question, taking
φ22.2 φ28.6 φ22.2 φ28.6 φ19.1 φ22.2 φ22.2
into consideration human traffic and wind.
Equalizer side Equalizer side L type L type • If the number of units installed is more than that shown in the pat-
Name accessory pipe accessory pipe accessory accessory tern in figure 2, install the units so there are no short circuits.
(1) (2) joint (1) joint (2)
• As regards space in front of the unit, consider the space needed
8 · 10 type
for the local refrigerant piping when installing the units.
Quantity

12 type 1 pc. 1 pc. 2 pcs. • If the work conditions in figure 2 do not apply, contact your dealer
14 · 16 type 1 pc. or Daikin directly.
(Refer to figure 2)
Shape 1. Front side
2. No limit to wall height
φ19.1 φ25.4 φ19.1 3. Service space of front side
4. Service space of suction side
(Refer to figure 1) For Patterns 1 and 2 in figure 2 :
1. Clamps, Manuals, etc. • Wall height for front side – no higher than 1500 mm.
2. Accessory pipes • Wall height on the suction side – no higher than 500 mm.
• Wall height for sides – no limit.
2-3 Option accessory • If the height is exceeded the above, calculate h1 and h2 shown
To install the outdoor units, the following optional parts are also required. in the figure below, and add h2/2 to the service space of front
To select an optimum kit, refer to “6. REFRIGERANT PIPING”. side and h1/2 to the service space of suction side.
• Outdoor unit multi connection piping kit
Number of outdoor units connected 2 units 3 units
Kit name BHFP26A90 BHFP26A136

3 English
5. PLACING THE UNIT
h2
<Front side> <Suction side> • Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise. (Refer to figure 6)

h1
h2 Service h1
1500

500 + space
+
2
• The base should support the unit with the extent larger than
2
or more or more hatched area in figure 7.

500
If protective rubber is to be attached, attach it to the whole face of
the base.
Note • The height of the base should be at least 150mm from the floor.
1. An inverter air conditioner may cause electronic noise gener- • Secure the unit to its base using foundation bolts. (Use four com-
ated from AM broadcasting. Examine where to install the main mercially available M12-type foundation bolts, nuts, and washers.)
air conditioner and electric wires, keeping proper distances • The foundation bolts should be inserted 20 mm.
away from stereo equipment, personal computers, etc.

20
(Refer to figure 6)
Particularly for locations with weak reception, ensure there is a 1. Independent base (four corner type)
distance of at least 3 meters for indoor remote controllers, 2. Independent base (with center support type)
place power wiring and transmission wiring in conduits, and 3. Beam base (Horizontal)
ground the conduits. 4. Beam base (Vertical)
5. Center of the product
(Refer to figure 3)
1. Indoor unit (Refer to figure 7)
2. Branch switch, overcurrent breaker 1. 4-15×22.5 (Hole for foundation bolt)
3. Remote controller 2. (Depth of product)
4. COOL/HEAT selector 3. (Inner dimension of the base)
5. Personal computer or radio 4. (Outer dimension of the base)
2. When installing in a locations where there is heavy snowfall, Model A B
implement the following snow measures.
8 · 10 · 12HP type 930 792
• Ensure the base is high enough that intakes are not clogged
by snow. 14 · 16HP type 1240 1102
• Remove the rear intake grille to prevent snow from accumu-
Note
lating on the fins. • When installing central drain pan kit (optional accessory), con-
3. If condensate may drip on downstairs (or walkway) depending struct the bace by independent base (with center support type) or
on the floor condition, take a measure such as the installation of beam base (Horizontal) in figure 6.
central drain pan kit (sold separately). • There are restrictions on the refrigerant pipe connecting order
4. The refrigerant R410A itself is nontoxic, nonflammable and is between outdoor unit in the case of the multi system.
safe. If the refrigerant should leak however, its concentration See “2-1 Combination” for detail.
may exceed the allowable limit depending on room size. Due to • When installing on a roof, make sure the roof floor is strong
this it could be necessary to take measures against leakage. enough and be sure to water-proof all work.
See “14. CAUTION FOR REFRIGERANT LEAKS” for details. • Make sure the area around the machine drains properly by setting
up drainage grooves around the foundation.
Drain water is sometimes discharged from the outdoor unit when
4. INSPECTING AND HANDLING THE UNIT it is running.
• For anti-corrosion type, use nuts with resin washers. If the paint on
• At delivery, the package should be checked and any damage nut connections comes off, the anti-corrosion effect may decrease.
should be reported immediately to the carrier claims agent.
• When handling the unit, take into account the following: Resin washers

1. Fragile, handle the unit with care.


Keep the unit upright in order to avoid compressor damage.
2. Decide on the transportation route.
3. If a forklift is to be used, pass the forklift arms through the large 6. REFRIGERANT PIPING
openings on the bottom of the unit. (Refer to figure 4)
Note
4. If hanging the unit, use a cloth sling to prevent damaging the unit. • All field piping must be installed by a licensed refrigeration techni-
Keeping the following points in mind, hang the unit following the cian and must comply with relevant local and national regulations.
procedure shown in figure 5. • After piping work is complete, do not under any circumstances open
• Use a sling sufficiently strong to hold the mass of the unit. the shutoff valve until “7. FIELD WIRING” and “10. CHECKING OF
• Use 2 belts of at least 8m long. DEVICE AND INSTALLATION CONDITIONS” are complete.
• Place extra cloth or boards in the locations where the casing • Do not use flux when brazing the refrigerant piping. Use the phos-
comes in contact with the sling to prevent damage. phor copper brazing filler metal (BCuP-2 : JIS Z 3264, B-Cu93P-
• Hoist the unit making sure it is being lifted at its center of gravity. 710/795 : ISO 3677) which does not require flux.
5. After installation, remove the transportation clasp (yellow) (Flux has extremely harmful influence on refrigerant piping sys-
attached to the large openings. (Refer to figure 4) tems. For instance, if the chlorine based flux is used, it will cause
(Refer to figure 4) pipe corrosion or, in particular, if the flux contains fluorine, it will
1. Fork damage the refrigerant oil.)
2. Hole (large)
3. Transportation clasp (yellow) 6-1 Selection of piping material and Refrigerant
4. Fixed screws of transportation clasp branching kit
(Refer to figure 5) • Use only pipes which are clean inside and outside and which do
1. Belt sling not accumulate harmful sulfur, oxidants, dirt, cutting oils, mois-
2. Filler cloth or Board ture, or other contamination. (Foreign materials inside pipes
3. Hole (large) including oils for fabrication must be 30mg/10m or less.)
4. Hole (small) • Use the following items for the refrigerant piping.
Material : Jointless phosphor-deoxidized copper pipe
Note
Apply a filler cloth on a fork to prevent coating of the bottom frame from Size : See “6-5 Example of connection” to determine the
correct size.
coming off and rust from occurring when bringing the unit using a forklift.
Thickness : Select a thickness for the refrigerant piping which
complies with national and local laws.
For R410A, the design pressure is 4.0 MPa (40-bar).

English 4
The minimum thickness of piping according to Japan’s High- 4. Concave section (4 points)
Pressure Gas Safety Law (as of January 2003) is shown below. • Be sure to avoid damaging the casing
Temper grade (O type, 1/2H type) in the table indicate the • After knocking out the holes, we recommend you remove any
material types specified in JIS H 3300. burrs and paint them using the repair paint to prevent rusting.
(unit : mm) • When passing electrical wiring through the knock holes, protect the wir-
Temper grade O type ing with a conduit or bushings, making sure not to damage the wiring.
outer diameter φ6.4 φ9.5 φ12.7 φ15.9 2. Removing Pinch Piping
• When connecting refrigerant piping to an outdoor unit, remove
smallest thickness 0.80 0.80 0.80 0.99 the pinch piping using the procedure in the figure 12.
(unit : mm) (Refer to figure 12)
Temper grade 1/2H type • About handling of shutoff valves, refer to [Shutoff valve opera-
tion procedure] in “11-1 Before working”.
outer diameter φ19.1 φ22.2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
smallest thickness 0.80 0.80 0.88 0.99 1.10 1.21 1.32 1.43 Caution
• For piping work, follow the maximum tolerated length, difference After removing the gass, remove the pinch piping.
in height, and length after a branch indicated in the “6-5 Example Any gas remaining inside may blow off the pinch piping when you dis-
of connection”. solve the brazing, causing damage.
• Outdoor unit multi connection piping kit and refrigerant branching
kit (sold separately) are needed for connection of piping between (Refer to figure 12)
outdoor units (in case of multi system) and piping branches. 1. Pich piping (4 pieces)
Use only separately sold items selected specifically according to 2. Do not remove the relay piping.
the outdoor unit multi connection piping kit, the refrigerant branch- 3. Pinch piping
ing kit selection in the “6-5 Example of connection”. 4. Procedure 1 : Confirm the shutoff valve is closed.
5. Procedure 2 : Connect a charge hose to the service port
6-2 Protection against contamination of shutoff valve and remove the gas in the pinch piping.
6. Procedure 3 : After removing the gas in the pinch piping,
when installing pipes dissolve the brazing using a burner and remove the
Protect the piping to prevent moisture, dirt, dust, etc. from pinch piping.
entering the piping. 3. Connecting refrigerant piping to outdoor units
Place Installation period Protection method • Figure 13 shows the example of connecting refrigerant piping to
More than a month Pinch the pipe outdoor units.
Outdoor
Less than a month • The local interunit piping next accesorry pipes are field supplyed.
Pinch or tape the pipe
Indoor Regardless of the period • About the detail of connecting pipes between outdoor units on
outdoor unit multi system, refer to the "4. Precautions when
Note connecting piping between outdoor units" and the installation
Exercise special caution to prevent dirt or dust when passing piping manual attached to the outdoor unit multi connection piping kit.
through holes in walls and when passing pipe edges to the exterior. <In case of single system : 5-18HP type>
6-3 Pipe connection (Refer to figure 13)
• Be sure to perform nitrogen permutation or nitrogen blow when 1. When connected to the front
2. When connected at lateral side (bottom)
brazing. (Refer to figure 8)
3. Remove the shutoff valve cover to connect.
Brazing without performing nitrogen permutation or nitrogen
4. Remove the knock hole on the bottom frame and route
blow into the piping will create large quantities of oxidized film on the piping under the bottom frame.
the inside of the pipes, adversely affecting valves and compres- 5. Liquid pipe shutoff valve
sors in the refrigerating system and preventing normal operation. 6. Suction gas pipe shutoff valve
(Refer to figure 8) 7. HP/LP gas pipe shutoff valve
1. Refrigerant pipe 8. Equalizer pipe shutoff valve
2. Location to be brazed 9. Brazing
3. Nitrogen 10. Liquid side accessory pipe (1)
4. Taping 11. Suction gas side accessory pipe (1)
5. Handy valve 12. HP/LP gas side accessory pipe (1)
6. Regulator 13. Equalizer side accessory pipe (1)
14. L type accessory joint (1)
• The pressure regulator for the nitrogen released when doing
15. L type accessory joint (2)
the brazing should be set to about 0.02 MPa (0.2kg/cm2 : 16. Liquid side accessory pipe (2)
Enough to feel a slight breeze on your cheek). 17. Suction gas side accessory pipe (2)
18. In case of Q14 · 16 type : HP/LP gas side accessory pipe (2)
Note In case of Q8 ~ 12 type : HP/LP gas side accessory pipe (1)
Do not use anti-oxidants when brazing the pipe joints.
19. Equalizer side accessory pipe (2)
Residue can clog pipes and break equipment.
Note
6-4 Connecting the refrigerant piping • Equalizer pipe is only for connection between outdoor units on
1. Direction to bring out the pipes multi outdoor unit system.
That is not connect to indoor units.
The local interunit piping can be connected either forward or to
• About the connection of equalizer pipe for 3 outdoor units multi
the sides (taken out through the bottom) as shown in the figure 10.
system, refer to the installation manula of outdoor unit multi con-
When passing out through the bottom, use the knock hole in the
nection piping kit.
bottom frame.
• Make sure the onsite piping does not come into contact with other
(Refer to figure 10) piping or the bottom frame or side panels of the unit.
1. Left-side connection
2. Front connection 4. Precautions when connecting piping betweemn outdoor units
3. Right-side connection The Outdoor unit multi connection piping kit (sold separately) is
Precautions when knocking out knock holes needed to connect piping between outdoor units in multi system.
• Open knock hole (large, small) in the base frame by drilling the 4 Only proceed with piping work after considering the limitations on
concave around it with a 6mm bit. (Refer to figure 11) installation listed here and in “5. Branching the refrigerant pip-
ing”, always referring to the kit’s installation manual.
(Refer to figure 11) (1) About outdoor unit multi connection piping kit
1. Knock hole • Install the joint horizontally so that the attached warning label
(large : for liquid pipe, suction gas pipe and HP/LP gas pipe) faces strait up, and the tilt is within ±15°. (Refer to figure 16-1)
2. Knock hole (small : for equalizer pipe) Do not install vertically. (Refer to figure 16-2)
3. Drill

5 English
• Maintain a straight portion of 500 mm or more until the split of
the joint without wrapping any onsite piping around this area. Prohibited pattern
Over 500 mm of straight area can be maintained by connect- Unit A Unit B Unit C
Front connections
ing at least 120 mm of onsite pipe (straight) to the joint.
(Refer to figure 16-3)
to indoor unit
(Refer to figure 16)
1. Warning label
2. Horizontal surface Side (bottom) connections Unit A Unit B Unit C
3. ±15° or less
4. Ground to indoor unit
5. Onsite pipe (120mm length or more)
6. Straight part of 500mm or more Oil remains in the stopping outdoor unit.
7. C-arrow view
8. D-arrow view Change to pattern 1 or pattern 2
(2) The piping between outdoor units must be installed level
(Pattern 1) or with a rise (Pattern 2). Otherwise oil may pool Unit Unit Unit Unit Unit Unit
B C A B A B
in the pipes.
Unit Unit Unit
A C C
Pattern 1
Unit Unit Unit
Front connections A B C
to indoor unit
Level Piping between outdoor units
Oil remains in the unit B Oil remains in the unit B
Side (bottom) connections when system stops. when system stops.
Unit Unit Unit
A B C Change as shown Change as shown
in the figure below. in the figure below.
to indoor unit
Piping between outdoor units Connect straightly Connect straightly Put rising
Pattern 2 Unit Unit Unit Unit Unit Unit
B C A B A B
Front connections Unit Unit Unit
Unit Unit
Unit C C
A B C A
to indoor unit
Rise Rise Rising height :
Side (bottom) connections 200 mm or more
Unit Unit Unit
A B C
(4) If the piping length between the outdoor units exceeds 2 m,
to indoor unit create a rise of 200 mm or more in the suction gas and HP/
Rise LP gas piping under a length of 2 m from the outdoor unit
multi connection piping kit.
Change to pattern 1 or pattern 2
If less than 2m
Prohibited pattern Suction gas pipe and Unit Unit Unit
Oil remains in piping HP/LP gas pipe A B C
Front connections between outdoor units
Unit Unit Unit to indoor unit
Downward to indoor A B C less than 2m
inclination unit
If 2 m or more
Downward inclination
Suction gas pipe and Unit Rising height : Unit Rising height : Unit
200 mm or more 200 mm or more
Side (bottom) connections HP/LP gas pipe A B C
between outdoor units
Unit Unit Unit to indoor unit
A B C less than 2m less than 2m

to indoor unit
Downward inclination 5. Branching the refrigerant piping
Heed the restrictions below when installing the refrigerant branch-
(3) To avoid the risk of oil detention in the stopping unit, always ing kit and read the installation instruction manual with the kit.
connect the shutoff valve and the piping between outdoor (Improper installation could lead to malfunctioning or breakdown
units as shown A or B in the figure below. of the outdoor unit.)
<REFNET joint>
Install the REFNET joint so it splits horizontally or vertically.
(Refer to figure 14)
A
1. Horizontal
A 2. A-arrow view
B 3. Horizontal surface
B 4. ±30° or less
5. Vertical
Front connections Side (bottom) connections <REFNET header>
Install the REFNET header so it splits horizontally.
(Refer to figure 15)
1. Horizontal surface
2. B-arrow view

English 6
7
Example of connection Branch with REFNET joint Branch with REFNET joint and header Branch with REFNET header
(Connection of 8 indoor units) Outdoor unit Outdoor unit Outdoor unit
Outdoor unit Indoor unit REFNET joint (A~G)
side side
(3 pipes) (2 pipes) REFNET header
REFNET joint (A~G) REFNET header
Suction gas pipe Gas pipe a m
a
a b c d e A
HP/LP gas pipe BS b
Unit Single A B C D E B5 n p

H1
outdoor

H1
H1

f n p
Liquid pipe Liquid pipe system B b d f h j
i k c e g i
REYQ B1 B2 B3 B4 o B1 B2 B3 B4 B5 B6
r s B1 B2 B3 B4 8
F G k
6-5 Example of connection

8~16 j m o q c e g i k m n o
d f h j
Piping from outdoor unit to BS unit g
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7

H2
Suction gas pipe
(Bold):3 pipes HP/LP gas pipe 8 8
H2

H2
Liquid pipe

Piping from BS unit to indoor unit or B1 ~ B4 : BS Unit B1 ~ B5 : BS Unit B1 ~ B4 : BS Unit


Piping from Refrigerant branch kit to 1~6 : Indoor unit (Cool/Heat selection possible) 1 ~ 4 , 7 , 8 : Indoor unit (Cool/Heat selection possible) 1~6 : Indoor unit (Cool/Heat selection possible)
indoor unit used as cooling only 7, 8 : Indoor unit (Cooling only) 5, 6 : Indoor unit (Cooling only) 7, 8 : Indoor unit (Cooling only)
(Thin):2 pipes (Suction) gas pipe First outdoor unit multi connection piping kit
Liquid pipe
Outdoor unit Outdoor unit Outdoor unit

H3
H3
H3

REFNET joint (A~G)


(*1) " " Indicate the Outdoor unit multi
connection piping kit. r s t r s t REFNET header r s t
(*2) In case of multi outdoor system, re-read REFNET joint (A~G) u u REFNET header
"outdoor unit" to "the first Outdoor unit a m
multi connection piping kit" as seen from a a
b c d e A
the indoor unit. Multi b
A B C D E B5 n p

H1
H1

outdoor

H1
system f n p B b d f h j
REYQ i k c e g i
r o B1 B2 B3 B4 B5 B6
18~48 G S B1 B2 B3 B4 k 8
F m o q c e
d f h j g i k m n o
g
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7
H2

8 8
H2

H2
B1 ~ B4 : BS Unit B1 ~ B5 : BS Unit B1 ~ B4 : BS Unit
1~6 : Indoor unit (Cool/Heat selection possible) 1 ~ 4 , 7 , 8 : Indoor unit (Cool/Heat selection possible) 1~6 : Indoor unit (Cool/Heat selection possible)
7, 8 : Indoor unit (Cooling only) 5, 6 : Indoor unit (Cooling only) 7, 8 : Indoor unit (Cooling only)
Actual pipe Pipe length between outdoor unit (*2) and indoor unit ≤ 165m
length Example 8 : a + b + c + d + e + s ≤ 165m Example 6 : a + b + ≤ 165m, 8 : a + m + n + p ≤ 165m Example 8 : a + o ≤ 165m
Between outdoor unit (*2)
Equivalent Equvalent pipe length between outdoor unit (*2) and indoor unit ≤ 190m (Note 1)
Maximum and indoor unit
length (Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of BSVQ100, 160 to be 4m, that of BSVQ250 to be 6m for calculation purposes)
allowable
length Total extention length Total piping length from outdoor unit (*2) to all indoor unit ≤ 1000m
Between first outdoor unit multi Actual and Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit ≤ 10m Outdoor unit
connection piping kit and outdoor unit Equivalent Equivalent pipe length from first outdoor unit multi connection piping kit to outdoor unit ≤ 13m r ≤ 10m
(in case of multi system) pipe length (Equivalent length ≤ 13m)
u + s ≤ 10m
Allowable Between outdoor and indoor units Difference in height Difference in height between outdoor unit and indoor unit (H1) ≤ 50m (Max 40m if the outdoor unit is below) r s (Equivalent length ≤ 13m)
height Between indoor and indoor units Difference in height Difference in height between adjacent indoor units (H2) ≤ 15m t u + t ≤ 10m
difference Between outdoor and outdoor units u (Equivalent length ≤ 13m)
Difference in height Difference in height between adjacent outdoor units (H3) ≤ 5m
Actual pipe Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit ≤ 40m (Note 2)
Allowable length after the branch
length Example 8 : b + c + d + e + s ≤ 40m Example 6 : b + ≤ 40m, 8: m + n + p ≤ 40m Example 8 : o ≤ 40m

English
English
Outdoor unit multi connection piping kit and How to select the REFNET joint How to select the REFNET header
Refrigerant branch kit selection When using REFNET joint at the first branch counted from the outdoor unit side, Choose from the following table in accordance with the total capacity index of all
choose from the following table in accordance with the outdoor unit capacity type. the indoor units connected below the REFNET header.
(Example : REFNET joint A) Indoor unit of FXY ~ P280 · 450 · 560 can not be connected below the REFNET header.
• Refrigerant branch kits can only be used with R410A.
• When multi outdoor system are installed, be sure to use the Outdoor unit capacity type Refrigerant branch kit name Refrigerant branch kit name
Indoor unit total capacity index
special separately sold Outdoor unit multi connection piping 8,10HP type KHRP25A33T 3 pipes 2 pipes
kit. (BHFP26A90 · 136). 12~22HP type KHRP25A72T+KHRP25M72TP x < 200 KHRP26M22H or KHRP26M33H
KHRP25M33H
(For how to select the proper kit, follow the table at right.) 24HP type ~ KHRP25A73T+KHRP25M73TP 200 ≤ x < 290 KHRP26M33H
• Never use BHFP26M90 · 135, BHFP22M90 · 135P for M Choose the REFNET joints other than the first branch from the following table in accordance 290 ≤ x < 640 KHRP25M72H+KHRP25M72HP KHRP26M72H
type of this series or T joint (field supplyed). with the total capacity index of all the indoor units connected below the REFNET joint. 640 ≤ x KHRP25M73H+KHRP25M73HP KHRP26M73H+KHRP26M73HP
Refrigerant branch kit name How to select the outdoor unit multi connection piping kit
Indoor unit total capacity index (This is required when the system is multi outdoor unit system.)
3 pipes 2 pipes
x < 200 KHRP25A22T KHRP26A22T Choose from the following table in accordance with the number of outdoor units.
200 ≤ x < 290 KHRP25A33T KHRP26A33T Number of outdoor unit Connecting piping kit name
290 ≤ x < 640 KHRP25A72T+KHRP25M72TP KHRP26A72T 2 units BHFP26A90
640 ≤ x KHRP25A73T+KHRP25M73TP 3 units BHFP26A136
Example for indoor units Example REFNET joint B : Indoor units 7 + 8 Example REFNET header :
connected downstream Example REFNET joint C : Indoor units 5 + 6 + 7 + 8
Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6 Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Pipe size selection Piping between outdoor unit (*2) and refrigerant branch kit (part A) Piping between refrigerant branch kits
Choose from the following table in accordance with the outdoor unit system capacity type. Piping between refrigerant branch kit and BS unit
Piping between outdoor unit multi connection piping kits (part B) Piping between BS unit and refrigerant branch kit
The thickness of the pipes in the table shows Choose from the following table in accordance with the total capacity of all
the requirements of Japanease High Pressure Choose from the following table in accordance with the total capacity type of all the
the outdoor units connected upstream. (unit : mm) indoor units connected downstream.
Gas Controll low. (As of Jan. 2003)
The thickness and material shall be selected in Outdoor unit Piping size (O. D.) *1 Connection piping must not exceed the refrigerant Piping size between outdoor
accordance with local code. capacity type Suction gas pipe HP/LP gas pipe Liquid pipe unit and refrigerant branch kit (part A).
8HP type φ19.1 φ15.9
φ9.5 *2 When selecting 2 pipes line (gas pipe and liquid pipe), use Suction gas pipe
10HP type φ22.2
φ19.1 column for gas pipe and Liquid pipe column for liquid pipe.
12HP type (unit : mm)
φ12.7 Piping size (O. D.)
14,16HP type φ28.6 φ22.2 Indoor capacity index
For an outdoor unit installation, make 18HP type Suction gas pipe HP/LP gas pipe Liquid pipe
the settings in accordance with the 20,22HP type φ15.9 x < 150 φ15.9 φ12.7
following figure. 24HP type 150 ≤ x < 200 φ19.1 φ15.9 φ9.5
φ34.9 φ28.6 200 ≤ x < 290 φ22.2
Outdoor unit 26~34HP type φ19.1
36HP type φ19.1 290 ≤ x < 420 φ12.7
φ41.3 φ28.6
38~48HP type φ34.9 420 ≤ x < 640 φ15.9
640 ≤ x < 920 φ34.9 φ28.6
φ19.1
Piping between outdoor unit multi connection piping kit and outdoor unit (part C) 920 ≤ x φ41.3
Choose from the following table in accordance with the capacity type of
Equalizer pipe the outdoor unit connected. Piping between refrigerant branch kit, BS unit and indoor unit
(part D) (unit : mm)
Match to the size of the connection piping on the indoor unit. (unit : mm)
Outdoor unit Piping size (O. D.)
Piping between outdoor unit capacity type Suction gas pipe HP/LP gas pipe Liquid pipe Piping size (O. D.)
multi connection piping kit Indoor unit capacity type
8,10HP type φ22.2 φ9.5 × 0.8 gas pipe Liquid pipe
and outdoor unit (part C) φ19.1 20 · 25 · 32 · 40 · 50 type φ12.7 φ6.4
12HP type φ28.6 φ12.7
Piping between outdoor unit multi 14,16HP type φ22.2 63 · 80 · 100 · 125 type φ15.9
connection piping kits (part B) 200 type φ19.1 φ9.5
Piping between outdoor unit and 250 type φ22.2
refrigerant branch kit (part A)
Equalizer pipe (part D) (outdoor multi system only) (unit : mm)
Temper grade and wall thickness for pipes Piping size (O. D.) φ19.1
(Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.)
Copper tube O. D. φ6.4 φ9.5 φ12.7 φ15.9 φ19.1 φ22.2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
Temper grade O type 1/2H type
Wall thickness
(Min. requirement) 0.80 0.80 0.80 0.99 0.80 0.80 0.88 0.99 1.10 1.21 1.32 1.43

8
9
How to calculate the
HEAT RECOVER SYSTEM REFRIGERANT AMOUNT
additional refrigerant Total length(m) Total length(m) FOR EXCEEDING CONNECTION
R= of liquid piping of liquid piping THE AMOUNT OF
to be charged 0.37 0.26 MODEL NAME CAPACITY OF INDOOR UNIT
size at φ22.2 size at φ19.1) REFRIGERANT
REYQ18 ~ 20PY1 1.0kg MODEL NAME
INDOOR
Additional refrigerant to Total length(m) Total length(m) 1.02 REYQ22 ~ 24PY1 1.5kg CONNECTION REYQ18 REYQ34
of liquid piping 0.18 of liquid piping 0.12 REYQ26PY1 2.0kg CAPACITY ~ ~
be charged : R(kg) 32PY1 48PY1
size at φ15.9) size at φ12.7 REYQ28 ~ 30PY1 2.5kg
R should be rounded MORE THAN 100%
off in units of 0.1 kg. REYQ32 ~ 40PY1 3.0kg 0.5kg
Total length(m) Total length(m) 120% OR LESS
REYQ42PY1 3.5kg
of liquid piping 0.059 of liquid piping 0.022 MORE THAN 120%
REYQ44 ~ 46PY1 4.0kg 0.5kg 1.0kg
size at φ9.5 size at φ6.4 130% OR LESS
REYQ48PY1 4.5kg

Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : REYQ34PY1
a : φ19.1 × 30m e : φ9.5 × 10m i : φ9.5 × 10m m : φ9.5 × 20m r : φ12.7 × 3m
Total capacity of indoor unit : 116%
b : φ19.1 × 20m f : φ9.5 × 10m j : φ9.5 × 10m n : φ9.5 × 10m s : φ9.5 × 3m
c : φ9.5 × 10m g : φ9.5 × 10m k : φ9.5 × 20m o : φ6.4 × 10m t : φ9.5 × 3m
d : φ9.5 × 10m h : φ9.5 × 10m l : φ9.5 × 20m p : φ6.4 × 10m u : φ15.9 × 1m
R = ( 50 × 0.26 + 1 × 0.18 + 3 × 0.12 + 156 × 0.059 + 20 × 0.022 )×1.02 + 3.0 + 0.5
a, b u r c~n, s, t o, p REYQ34PY1 116%
= 27.148 27.1kg
Round off in units of 0.1 kg.
Note 1. System Liquid pipe
When the equivalent pipe length between outdor and indoor units is 90m or
REYQ8 ~ 10PY1 φ9.5 → φ12.7
more, the size of main pipes on the liquid side (refer to figure 9) must be
increased according to the right table. REYQ12 ~ 16PY1 φ12.7 → φ15.9
(Never increase suction gas pipe and HP/LP gas pipe.) REYQ18 ~ 24PY1 φ15.9 → φ19.1
REYQ26 ~ 48PY1 φ19.1 → φ22.2
(Refer to figure 9)
1.Outdoor unit
2.Main pipes
3.Increase only liquid pipe size
4.First refrigerant branch kit
5.BS unit
6.Indoor unit
Note 2. Allowable length after the first refrigerant branch kit to indoor units is 40m or less, however it can be extended up to 90m if all the following conditions are satisfied. (In case of "Branch with REFNET joint")

Required Conditions Example Drawings


1. It is necessary to increase the pipe size between the first branch kit 8 b + c + d + e + f + g + p ≤ 90 m Increase the pipe size as follows
and the final branch kit. (Reducers must be procured on site) increase the pipe size of b, c, d, e, f, g φ 9.5 → φ12.7 φ15.9 → φ19.1 φ22.2 → φ25.4* φ34.9 → φ38.1*
However, the pipes that are same pipe size with main pipe must not φ12.7 → φ15.9 φ19.1 → φ22.2 φ28.6 → φ31.8*
be increased.
2. For calculation of Total extension length, the actual length of a+b×2+c×2+d×2+e×2+f×2+g×2 REFNET joint (A-G)
above pipes must be doubled. (except main pipe and the pipes + h + i + j + k + l + m + n + p ≤ 1000 m Outdoor unit
that are not increased)
a b c d e f g H1
3. Indoor unit to the nearest branch kit ≤ 40 m h, i, j....... p ≤ 40 m A B C D E F G
p
4. The difference between The farthest indoor unit 8 h i j k l m n
1 2 3 4 5 6 7
[Outdoor unit to the farthest indoor unit] and [Outdoor unit The nearest indoor unit 1 8
to the nearest indoor unit] ≤ 40 m ( a + b + c + d + e + f + g + p ) - ( a + h ) ≤ 40 m Indoor units ( 1 - 8 )
*If available on the site, use this size. Otherwise it can not be increased.

English
7. FIELD WIRING • Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
Caution relevant local and national regulations.
• Specifications for local wiring are in compliance with IEC60245.
• All field wiring and components must be installed by a licensed • Use wire type H05VV when protected pipes are used.
electrician and must comply with relevant local and national Use wire type H07RN-F when protected pipes are not used.
regulations.
Phase and Minimum Recom-
• Be sure to use a dedicated power circuit. Never use a power sup- frequency
Voltage
circuit amp. mended fuses
ply shared by another appliance.
• Never install a phase advancing capacitor. As this unit is equipped REYQ18PY1 φ 3, 50Hz 380-415V 40.1A 45A
with an inverter, installing a phase advancing capacitor will not only REYQ20PY1 φ 3, 50Hz 380-415V 41.2A 50A
deteriorate power factor improvement effect, but also may cause REYQ22PY1 φ 3, 50Hz 380-415V 44.3A 50A
capacitor abnormal heating accident due to high-frequency waves. REYQ24PY1 φ 3, 50Hz 380-415V 45.4A 50A
• Only proceed with wiring work after blocking off all power. REYQ26PY1 φ 3, 50Hz 380-415V 53.1A 60A
• Always ground wires in accordance with relevant local and
REYQ28PY1 φ 3, 50Hz 380-415V 54.2A 60A
national regulations.
• This machine includes an inverter device. Connect earth and REYQ30PY1 φ 3, 50Hz 380-415V 63.0A 70A
leave charge to eliminate the impact on other devices by reducing REYQ32PY1 φ 3, 50Hz 380-415V 63.0A 70A
noise generated from the inverter device and to prevent leaked REYQ34PY1 φ 3, 50Hz 380-415V 71.6A 80A
current from being charged in the outer hull of the product. REYQ36PY1 φ 3, 50Hz 380-415V 72.7A 80A
• Do not connect the ground wire to gas pipes, sewage pipes, light- REYQ38PY1 φ 3, 50Hz 380-415V 75.8A 90A
ning rods, or telephone ground wires.
REYQ40PY1 φ 3, 50Hz 380-415V 76.9A 90A
Gas pipes : can explode or catch fire if there is a gas leak.
Sewage pipes : no grounding effect is possible if hard plastic pip- REYQ42PY1 φ 3, 50Hz 380-415V 84.6A 100A
ing is used. REYQ44PY1 φ 3, 50Hz 380-415V 85.7A 100A
Telephone ground wires and lightning rods : dangerous when REYQ46PY1 φ 3, 50Hz 380-415V 94.5A 110A
struck by lightning due to abnormal rise in electrical potential in REYQ48PY1 φ 3, 50Hz 380-415V 94.5A 110A
the grounding.
• Be sure to install an earth leakage circuit breaker. 7-2 Wiring Connection Example for Whole System
This unit uses an inverter, so install the earth leakage circuit
breaker that be capable of handling high harmonics in order to (Refer to figure 17)
prevent malfunctioning of the earth leakage circuit breaker itself. 1. Power supply
• Earth leakage circuit breaker which are especially for protecting 2. Main switch
ground-faults should be used in conjunction with main switch or 3. Earth leakage circuit breaker
fuse for use with wiring. 4. Fuse
5. Outdoor unit
Note 6. COOL/HEAT selector
• Electrical wiring must be done in accordance with the wiring dia- 7. Remote controller
grams and the description herein. 8. Indoor unit
9. BS unit
• Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may Note
be broken down.) • Make sure the weak electric wiring (i.e. for the remote controller,
• Never remove thermistor, sensor or etc. when connecting power between units, etc.) and the power wiring do not pass near each
wiring and transmission wiring. other, keeping them at least 50 mm apart.
(If operated with thermistor, sensor or etc. removed, the compres- Proximity may cause electrical interference, malfunctions, and
sor may be broken down.) breakage.
• This product have reversed phase protection detector that only • Be sure to connect the power wiring to the power wiring terminal
works when the power is turned on. If there exists black out or the block and secure it as described in “7-5 Power Wiring Connec-
power goes on and off which the product is operating, attach a tion Procedure”.
reversed phase protection circuit locally. Running the product in • Transmission wiring should be secured as described in “7-4
reversed phase may break the compressor and other parts. Transmission Wiring Connection Procedure”.
• Attach the power wire securely. Introducing power with a missing • Secure wiring with clamp such as insulation lock ties to avoid con-
N-phase or with a mistaken N-phase will break the unit. tact with piping.
• Never connect the power supply in reversed phase. • Shape the wires to prevent the structure such as the EL. COMPO.
The unit can not operate normally in reversed phase. BOX lid deforming. And close the cover firmly.
If you connect in reversed phase, replace two of the three phases. • All field wiring is to be procured on site.
• Make sure the electrical unbalance ratio is no greater than 2%. If
it is larger than this, the unit’s lifespan will be reduced. 7-3 Leading wire Procedure
If the ratio exceeds 4%, the unit will shut down and an malfunction
• The power wiring and ground wiring are passed out from the
code will be displayed on the indoor remote controller.
power wiring hole on the sides, the front (knock hole) or the bot-
• Connect the wire securely using designated wire and fix it with
tom frame (knock hole) .
attached clamp without applying external pressure on the termi-
• The transmission wiring is passed out from the wiring hole (knock
nal parts (terminal for power wiring, terminal for transmission wir-
hole) on the front of the unit or from a piping hole.
ing and earth terminal).
• If there exists the possibility of reversed phase, lose phase, (Refer to figure 18)
momentary blackout or the power goes on and off while the prod- 1. Electrical wiring diagram
uct is operating, attach a reversed phase protection circuit locally. 2. On the back of the EL .COMPO. BOX lid.
Running the product in reversed phase may break the compres- 3. Power wiring, ground wiring (inside conduit)
sor and other parts. 4. (When the wiring is routed out through the side panel.)
5. Transmission wiring
7-1 Power circuit, safety device and cable 6. Pipe opening
7. Conduit
requirements 8. For power wiring and ground wiring
• A power circuit (see the following table) must be provided for con- 9. Through cover
nection of the unit. This circuit must be protected with the required 10. Cut off the shaded zones before use.
safety devices, i.e. a main switch, a slow blow fuse on each phase 11. Burr
and an earth leakage circuit breaker. 12. Knockout hole
• When using residual current operated circuit breakers, be sure to 13. For transmission wiring
use a high-speed type (0.1 second or less) 200mA rated residual Note
operating current. • Open the knock holes with a hammer or the like.
• Use copper conductors only.

English 10
• After knocking out the holes, we recommend you remove any 6. Transmission wiring
burrs and paint them using the repair paint to prevent rusting. • Transmission wiring between outdoor units in the outdoor multi sys-
(Refer to figure 18) tem must be connected to terminals Q1 and Q2 (TO MULTI UNIT).
• When passing wiring through the knock holes, remove burrs Connecting the wires to the F1, F2 (TO OUT/D UNIT) terminals
around the knock holes and protect the wiring with protective results in system malfunction.
tape. (Refer to figure 18) • Wiring to other systems should be connected to terminals F1 and
• If small animals might enter the unit, block off any gaps (hatching F2 (TO OUT/D UNIT) on the PC-board of the master unit. The out-
parts in figure 18) with material (field supply). door unit that connected transmission wiring to BS (or indoor) unit
is the master unit. The others are sub unit.
7-4 Transmission Wiring Connection Procedure
• Referring to figure 19 connect the transmission wiring between 7-5 Power Wiring Connection Procedure
outdoor unit and indoor unit, outdoor unit and outdoor unit of other • Be sure to connect the power supply wiring to the power supply
system, outdoor unit and outdoor unit of same system. terminal block and hold it in place using the included clamp as
shown in the figure 23.
(Refer to figure 19)
1. Master unit (*) • The L1, L2, L3 and N phases of the power wiring should be
2. Sub unit (*) secured separately to the hook using the included clamp (1).
3. Outdoor unit A • The ground wiring should be bound to the power wiring using the
4. Outdoor unit B included clamp (1) to prevent outside force from being applied to
5. Outdoor unit C the terminal area.
6. Never connect the power wire.
7. To outdoor unit of other system (Refer to figure 23)
8. Use duplex wires (No polarity) 1. Power supply (3N~ 380-415V 50Hz)
9. BS unit 2. Earth leakage circuit breaker
10. Indoor unit 3. Branch switch, Overcurrent breaker
11. Indoor unit (Cooling only) 4. Ground wire
(*) : The Outdoor unit that connect the transmission wiring to BS 5. Attach insulation sleeves
unit is Master unit of the multi system. 6. Power supply terminal block
And the other units are Sub unit. (In this figure, Outdoor unit 7. Ground terminal
A is the Master unit.) 8. Clamp (1) (accessory)
Check operation in installation work, Onsite settings and so Caution
on are done by operating the PC-bord (A1P) of Master unit.
• Be sure to use crimp-style terminal with insulating sleeves for
Note connections. (See the figure below.)
• Do not connect the power wiring to terminals for the transmission
wiring. Doing so would destroy the entire system. Power wire
• When connecting wires to the terminal block on the PC-board, too Crimp-style terminal
much heat or tightening could damage the PC-board. Attach with care.
See the table below for the tightening torque of the transmission wiring
terminals.
Insulating sleeve
Screw size Tightening torque (N · m)
• For wiring, use the designated power wire and connect firmly,
M3.5 (A1P) 0.80 - 0.96
then secure to prevent outside pressure being exerted on the ter-
• All transmission wiring should use sheathed vinyl cord 0.75-1.25 minal board.
mm2 or cable (duplex). • Use an appropriate screwdriver for tightening the terminal screws.
• Transmission wiring (About the symbol 1 ~ 2 , see figure 19) A screwdriver with a small head will strip the head and make
should be done within the following limitations. proper tightening impossible.
If they are exceeded, transmission problems may occur. • Over-tightening the terminal screws may break them.
See the following table for the tightening torque of the terminal
1 Between outdoor unit and BS (or indoor) unit screws.
Between BS unit and indoor unit
Between outdoor unit and outdoor unit of other systems Screw size Tightening torque (N·m)
Max. wiring length :1,000 m
M8 Power terminal, ground terminal 5.5 ~7.3
Max. total wiring length :2,000 m
Max. no. of branches :16 • When pulling the ground wire out, wire it so that it comes through
[Note] the cut out section of the cup washer. (See the figure below.) An
No branch is allowed after branch (See figure 20) improper ground connection may prevent a good ground from
Max. no. of outdoor units of other system being achieved.
that can be connected Cup washer
: 10
(Refer to figure 20)
Crimp-style terminal
1. Branch
2. Branch after branch
2 Between outdoor unit and outdoor unit of same system Cut out section
Max. wiring length : 30 m
• When two wires are connected to a single terminal, connect them
• The transmission wiring inside the EL.COMPO.BOX should be so that the rear sides of the crimp contacts face each other. Also,
secured using the clamp (1) as shown in figure 21. make sure the thinner wire is on top, securing the two wires simul-
(Refer to figure 21) taneously to the resin hook using the included clamp (1).
1. In the EL.COMPO.BOX Terminal Crip style
2. Retain to the EL.COMPO.BOX with the accessory clamp (1). block terminal Wire : narrow
• Outside the units, the transmission wiring must be finished simul- Wire : thick
taneously with the local refrigerant piping, and wound with tape
(field supply) as shown in figure 22.
(Refer to figure 22) Resin hook
1. Suction gas pipe
2. HP/LP gas pipe
3. Liquid pipe
4. Insulation material
5. Finishing tape

11 English
7-6 Procedure for Wiring Inside Units 13. Valve B
14. Valve C
• Referring to figure 27, secure and wire the power and transmis-
15. Outdoor unit
sion wiring using the included clamp (1), (2), and (3).
16. To BS (or indoor) unit
• Wire so that the ground wiring does not come into contact with the 17. Shutoff valve
compressor lead wiring. 18. Service port
If they touch, this may have an adverse effect on other devices. 19. Field piping
• The transmission wiring must be at least 50 mm away from the 20. Gas flow
power wiring.
• Make sure all wiring do not contact to the pipes (hatching parts in Note
the figure 24). • The airtightness test and vacuum drying
(Refer to figure 24) should be done using the service ports of
1. Retain with accessory clamp (3). equalizer pipe, HP/LP gas pipe, suction gas
2. Electric conduit pipe and liquid pipe shutoff valve.
3. When routing out the power/ground wires from the left side. See the [R410A] Label attached to the front
4. When routing out the transmission wiring from the open- plate of the outdoor unit for details on the
ing for piping. location of the service port (see figure at right)
5. When routing out the power/ground wires from the front. • See [Shutoff valve operation procedure] in
6. Clear over 50 mm. “11-1 Before working” for details on han- [R410A] Label
7. When routing out the transmission wiring from the dling the shutoff valve.
knockout hole. • The refrigerant charge port is connected to unit pipe.
8. Retain to the back of the column support with the acces- When shipped, the unit contains the refrigerant, so use caution
sory clamp (2). when attaching the charge hose.
9. When routing out the power/ground wires from the right side.
<Air tight test>
10. Power wiring
Pressurize the liquid pipe, suction gas pipe, HP/LP gas pipe and
11. Transmission wiring
12. Ground wire equalizer pipe from the service ports of each shutoff valve to 4.0MPa
13. Secure to the back side of the support beam using the (40bar) (do not pressurize more than 4.0MPa (40bar)). If the pres-
accessory clamp (1). sure does not drop within 24 hours, the system passes the test.
14. Retain to the back of the column support with the acces- If there is a pressure drop, check for leaks, make repairs and perform
sory clamp (2). the airtight test again.
15. When wiring, exercise sufficient caution not to detach the <Vacuum drying>
acoustic insulators from the compressor. Evacuate the system from the liquid pipe, suction gas pipe, HP/LP
gas pipe and equalizer pipe shutoff valve service ports by using a
Note vacuum pump for more than 2 hours and bring the system to
• After wiring work is completed, check to make sure there are no
–100.7kPa or less. After keeping the system under that condition
loose connections among the electrical parts in the
for more than 1 hour, check if the vacuum gauge rises or not. If it
EL.COMPO.BOX. rises, the system may either contain moisture inside or have leaks.
Note
8. AIR TIGHT TEST AND VACUUM DRYING If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work
• After finished piping work, carry out air tight test and vacuum drying. takes long enough that condensation may form on the inside of
Note the pipes, if rain might enter the pipes during work, etc.)
• Always use nitrogen gas for the airtightness test. (1) After performing the vacuum drying for two hours, pressurize to
• Absolutely do not open the shutoff valve until the main power ciruit 0.05 MPa (i.e., vacuum breakdown) with nitrogen gas, then
insulation measurement has been completed. (measuring after depressurize down to –100.7 kPa for an hour using the vacuum
the shutoff valve is opened will cause the insulation value to drop.) pump (vacuum drying).
<Needed tools> (2) If the pressure does not reach –100.7 kPa even after depressur-
izing for at least two hours, repeat the vacuum breakdown - vac-
• To prevent entry of any impurities and insure uum drying process.
sufficient pressure resistance, always use the After vacuum drying, maintain the vacuum for an hour and make sure
Gauge manifold
special tools dedicated for R410A. the pressure does not rise by monitoring with a vacuum gauge.
Charge hose
• Use charge hose that have pushing stick for
valve
connecting to service port of shutoff valves or
refrigerant charge port.
9. PIPE INSULATION
• The vacuum pump for vacuum drying should
• Insulation of pipes should be done after performing “8. AIR TIGHT
be able to lower the pressure to –100.7kPa
TEST AND VACUUM DRYING”.
Vacuum pump (5 Torr –755mm Hg).
• Always insulate the liquid piping, the HP/LP gas piping, the gas
• Take care the pump oil never flow backward
piping, the equalizer pipe (between the outdoor units for the out-
into the refrigerant pipe during the pump stops.
door multi system) and these pipe connections.
<The system for air tight test and vacuum drying> Failing to insulate the pipes may cause leaking or burns.
• Referring to figure 25, connect an nitrogen tank, refrigerant tank, Especially, be sure to insulate the HP/LP gas piping as withstand-
and a vacuum pump to the outdoor unit. ing as the suction pipe because the suction gas follows in the HP/
The refrigerant tank and the charge hose connection to refrigerant LP gas piping when the system is whole cooling mode.
charge port or the valve A in figure 25 are needed in “11. ADDI- And be sure to use the insulation which can withstand such tem-
TIONAL REFRIGERANT CHARGE AND CHECK OPERATION”. peratures of 120°C or more for the HP/LP gas piping, the equal-
(Refer to figure 25) izer pipe and the gas piping because the HP/LP gas follows in
1. Gauge manifold these pipings.
2. Nitrogen • Reinforce the insulation on the refrigerant piping according to the
3. Measuring device installation environment. Condensation might form on the surface
4. R410A tank (with siphon) of the insulation. Refer to the below.
5. Vacuum pump „ Ambient temperature : 30°C, humidity : 75% to 80% RH : min.
6. Charge hose thickness : 15mm.
7. Equalizer pipe shutoff valve „ If the ambient temperature exceeds 30°C and the humidity
8. HP/LP gas pipe shutoff valve 80% RH, then the min. thickness is 20mm.
9. Suction gas pipe shutoff valve See the Engineering data book for detail.
10. Liquid pipe shutoff valve
11. Refrigerant charge port
12. Valve A

English 12
• If there is a possibility that condensation on the shutoff valve Note
might drip down into the indoor unit through gaps in the insulation • Always use the proper refrigerant (R410A). If charged with the
and piping because the outdoor unit is located higher than the refrigerant containing an improper material, it may cause an
indoor unit, etc., this must be prevented by caulking the connec- explosion or accident.
tions, etc. (Refer to figure 26) • R410A is a mixed refrigerant, so charging it as a gas will cause
• The piping lead-out hole lid should be attached after opening a the refrigerant composition to change, which may prevent normal
knock hole. (Refer to figure 27) operation.
• If small animals and the like might enter the unit through the pip- [Shutoff valve operation procedure]
ing lead-out hole, close the hole with blocking material (procured When operating the shutoff valve, follow the procedure instructed below.
on site) after completion of “11. ADDITIONAL REFRIGERANT
CHARGE AND CHECK OPERATION”. (Refer to figure 30) Note
• Do not open the shutoff valve until “10. CHECKING OF DEVICE
(Refer to figure 26)
AND INSTALLATION CONDITIONS” are completed. If the shutoff
1. Insulation material
valve is left open without turning on the power, it may cause refrig-
2. Caulking, etc.
erant to buildup in the compressor, leading insulation degradation.
(Refer to figure 27) • Be sure to use the correct tools.
1. Piping lead-out hole lid The shutoff valve is not a back-seat type. If forced it to open, it
2. Open a knock hole at “ ”. might break the valve body.
3. Block “ ”. • When using a service port, use the charge hose.
• After tightening the cap, make sure no refrigerant gas is leaking.
Note Tightening torque
• After knocking out the holes, we recommend you remove burrs in The sizes of the shutoff valves on each model and the tightening
the knock holes (See figure 27) and paint the edges and areas torque for each size are listed in the table below.
around the edges using the repair paint.
<Size of Shutoff Valve>
8HP type 10HP type 12HP type 14HP type 16HP type
φ9.5
10. CHECKING OF DEVICE AND INSTAL- Liquid pipe The 12HP type corresponds to
φ12.7
LATION CONDITIONS shutoff valve the 12.7-diameter onsite pip-
Be sure to check the followings. ing using the accessory pipe.
φ25.4
For those doing electrical work
The 8 · 10HP type corresponds to the 22.2-diame-
1. Make sure there is no faulty transmission wiring or loosing of a nut. Suction gas
ter onsite piping using the accessory pipe
See “7-4 Transmission Wiring Connection Procedure”. shutoff valve
The 12-16 HP type corresponds to the 28.6-diam-
2. Make sure there is no faulty power wiring or loosing of a nut. eter onsite piping using the accessory pipe.
See “7-5 Power Wiring Connection Procedure”. φ19.1
3. Has the insulation of the main power circuit deteriorated? HP/LP gas
The 14 · 16 HP type corresponds to the 22.2-diam-
shutoff valve
Measure the insulation and check the insulation is above regular eter onsite piping using the accessory pipe.
value in accordance with relevant local and national regulations. Equalizer pipe
φ19.1
For those doing pipe work shutoff valve
1. Make sure piping size is correct. (Refer to figure 28)
See “6-1 Selection of piping material and Refrigerant branch- 1. Service port
ing kit”. 2. Cap
2. Make sure insulation work is done. 3. Hex holes
See “9. PIPE INSULATION”. 4. Shaft (valve body)
5. Seal section
3. Make sure there is no faulty refrigerant piping.
See “6. REFRIGERANT PIPING”. To open
1. Remove the cap and turn the shaft counterclockwise with the
hexagon wrench (JISB4648).
11. ADDITIONAL REFRIGERANT 2. Turn it until the shaft stops.
CHARGE AND CHECK OPERATION 3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
The outdoor unit is charged with refrigerant when shipped from the factory,
but depending on the size and length of the piping when installed, it may To close
require additional charging. 1. Remove the cap and turn the shaft clockwise with the hexagon
For charging the additional refrigerant, follow the procedure in this chapter. wrench (JISB4648).
And then carry out the check operation. 2. Securely tighten the valve until the shaft contacts the main body seal.
11-1 Before working 3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
[About the refrigerant tank] <Tightening torque>
Check whether the tank has a siphon pipe before charging and place
the tank so that the refrigerant is charged in liquid form. Shutoff Tightening torque N·m (Turn clockwise to close)
(See the figure below.) valve size Shaft (valve body) Cap (valve lid) Service port
With siphon pipe
φ 9.5 5.4 - 6.6 Hexagonal 13.5 - 16.5
Stand the tank upright and charge. wrench
(The siphon pipe goes all the way inside, φ 12.7 8.1 - 9.9 4 mm 18.0 - 22.0
so the tank does not need be put 11.5 - 13.9
upside-down charge in liquid form.) φ 19.1 Hexagonal
27.0 - 33.0 wrench 22.5 - 27.5
Other tanks
φ 25.4 8 mm

Stand the tank upside-down and charge.

13 English
[How to Check How Many Units are Connected]
It is possible to find out how many indoor or outdoor unit in the system are turned on by operating the push button on the PC-board (A1P) of out-
door unit (In case of multi system master unit).
Follow the procedure below to check how many indoor or outdoor units are turned on.
LED display
(LED display: h ...OFF i ...ON j ...Blinking ∗ ...Uncertain)
H1P H2P H3P H4P H5P H6P H7P
(1) Press the MODE button (BS1) once at Setting Mode 1 (H1P : off), and set the MON-
j h h h h h h
ITOR MODE (H1P : Blinking).
(2) Press the SET button (BS2) the number of times until the For checking the number of
j h h i h h h
LED display matches that at right. outdoor units : eight times
For checking the number
j h h h i h i
of indoor units : five times
(3) Press the RETURN button (BS3) and read the number of units from the display of
H2P through H7P.
[Reading Method] j ∗ ∗ ∗ ∗ ∗ ∗
The display of H2P through H7P should be read as a binary number, with j standing
for “1” and h standing for “0”.

Ex: For the LED display at right, this would be “0 1 0 1 1 0 ”,


which would mean 22 units are connected.
j h j h j j h
32 × 0 + 16 × 1 + 8 × 0 + 4 × 1 + 2 × 1 + 1 × 0 = 22 units
Note: “000000” indicates 64 units.
(4) Press the MODE button (BS1) once. This returns to Setting Mode 1 (H1P : OFF, default). h h i h h h h

Note
Press the “MODE button” (BS1) if you get confused while operating.
This returns to Setting Mode 1 (H1P : OFF, default).

• The refrigerant charge port is connected to the piping inside the unit.
11-2 Procedure of Adding Refrigerant charging When the unit is shipped from the factory, the unit’s internal piping is
and check operation already charged with refrigerant, so be careful when connecting the
charge hose.
Warning Electric Shock Warning • After adding the refrigerant, make sure to close the lid of the
refrigerant charging port.
• Make sure to close the EL. COMPO. BOX lid before turning on The tightening torque for the lid is 11.5 to 13.9 Nm.
the power. • See [Shutoff valve operation procedure] in chapter 11-1 for details
• Perform the setting on the PC-board (A1P) of the outdoor unit and on how to handle shutoff valves.
check the LED display after the power is on via the inspection
• When done or when pausing the refrigerant charging operation,
door which is in the EL. COMPO. BOX lid.
close the valve of the refrigerant tank immediately.
(Refer to figure 29) The refrigerant charge port of this product have electric expansion valve.
1. EL. COMPO. BOX The valve will be closed at end of refrigerant charging. However
2. Inspection door the valve will be opened on operation after refrigerant charging
3. EL. COMPO. BOX lid (check operation, nomal operation, etc.).
4. LED (H1~8P) If the tank is left with the valve open, the amount of refrigerant
5. Push button(BS1~5) which is properly charged may be off the point.
6. Lift the protruding part to open the inspection door. • Make sure to perform the check operation after installation. Oth-
• Use an insulated rod to operate the push buttons via the EL.
erwise, the malfunction code “U3” will be displayed and normal
COMPO. BOX’s inspection door.
operation cannot be performed.
There is a risk of electric shock if you touch any live parts, since
this operation must be performed with the power on. And the failure of “Check of miswiring” may also cause abnormal
operation. Performance may drop due to the failure of “Judgment
of piping length”.
Caution • Check operation must be performed for each refrigerant piping system.
• Make sure to use the protect tool (protective groves and gog- Checking is impossible if plural systems are being done at once.
gles) when charging the refrigerant. • The individual problems of indoor units can not be checked.
• Due to a danger of liquid hammer, the refrigerant must not be About these problems check by test run after the check operation
charged over the allowable maximum amount when charging the is completed. (See chapter 13)
refrigerant. • The check operation cannot be performed in recovery or other
• Do not perform the refrigerant charging operation under working service modes.
for the BS and indoor unit.
• When opening the front panel, make sure to take caution to the 11-2-1 Procedure of Adding Refrigerant charging
fan rotation during the working. 1. Make sure the following works are complete in accordance with
After the outdoor unit stops operating, the fan may keep rotation the installation manual.
for a while.
„ Piping work
„ Wiring work
Note
„ Air tight test
• If operation is performed within 12 minutes after the BS, indoor
„ Vacuum drying
and outdoor units are turned on, H2P will be lit on and the com-
„ Installation work for BS, indoor unit
pressor will not operate.
Check the LED display indicate as shown [Display of normal sys- 2. Calculate the “additional charging amount” using “How to calcu-
tem] in chapter 11-2-1. late the additional refrigerant to be charged” in “6-5 Example of
• In order to ensure uniform refrigerant distribution, it may take up to connection”.
around 10 minutes for the compressor to start up after the unit 3. Open the valve B (See the figure 30. The valve A,C and the liquid
starting operating. This is not a malfunction. pipe, suction gas pipe, HP/LP gas pipe, equalizer pipe shutoff valves
must be left closed), and charge the refrigerant of the “additional
charging amount” from the liquid side shutout valve service port.

English 14
(Refer to figure 30) (*1) Lead the refrigerant charge hose etc from the pipe intake. All
1. Measuring device front panels must be closed at the procedure (3).
2. R410A tank (with siphon) (*2) • If you perform the refrigerant charging operation within the
3. Charge hose refrigerant system that have the power off unit, the operation
4. Equalizer pipe shutoff valve cannot finish properly.
5. HP/LP gas pipe shutoff valve For confirming the number of the outdoor and indoor units with
6. Suction gas shutoff valve the power on, see [How to check how many units are con-
7. Liquid pipe shutoff valve nected] in chapter 11-1. In case of a multi system, turn on the
8. Refrigerant charge port power to all outdoor units in the refrigerant system.
9. Valve A • To energize the crankcase heater, make sure to turn on for 6
10. Valve B hours before starting operation.
11. Valve C Table : Display of normal system
12. Outdoor unit A SERV. C/H SELECTOR
13. Outdoorunit B LED display TEST/ DEMA-
MONI- MODE L.N.O.P MULTI
14. Outdoor unit C (Default status TOR HWL IND MASTER SLAVE ND
15. To BS, indoor unit of shipped)
16. Field pipings HAP H1P H2P H3P H4P H5P H6P H7P H8P
17. Refrigerant flow Single system j h h i h h h h h
18. Shutoff valve j h h i h h h h i
19. Service port Multi Master unit
4. If the “additional charging amount” was charged fully, close the system Sub unit 1 j h h h h h h h j
valve B and go to step 7. (*) Sub unit 2 j h h h h h h h h
If the “additional charging amount” was not charged fully, close LED display: h...OFF, i...ON, j...Blinking
the valve B and go to step 5. (*) How to distinguish the master unit, sub unit 1, and sub unit 2 in the
5. Perform the refrigerant charging operation following [Refrigerant multi system.
charging operation procedure] as shown below, and charge the Method 1 : By the H8P (MULTI) LED display
remaining refrigerant of the “additional charging amount”. For per- i (ON) : Master unit j (Blinking) : Sub unit 1 h (OFF) : Sub unit 2
forming the refrigerant charging operation the push button on the
Method 2 : By the transmission wiring to indoor unit
PC-board (A1P) of outdoor unit (In case of multi system, master
unit) are use. (See the figure 29) In addition, the refrigerant are Transmission wiring is connected : Master unit
charged from the refrigerant charge port via the valve A. Transmission wiring is not connected : Sub unit 1 or Sub unit 2
(See the figure 31) (3) Charge the remained refrigerant by additional refrigerant charg-
For operating the push button and opening and closing the valve, ing operation of service mode.
follow the work procedure. About the method of additional refrigerant charging operation,
Note refer to the [Service Precaution] labe (lower) attached on the EL.
The refrigerant will be charged about 30kg in one hour at outdoor COMPO. BOX lid of the outdoor unit.
temp. 30°C DB (12kg at 0°C DB). (Refer to figure 32)
If you need to speedup in case of multi system, connect the refriger- 1. EL. COMPO.BOX lid
ant tanks to each outdoor unit as shown in the figure 31. 2. Inspection door
(Refer to figure 31) 3. [Service Precaution] label (upper)
1. Measuring device 4. [Service Precaution] label (lower)
2. R410A tank (with siphon)
3. Charge hose (4) Close the valve A if the “additional charging amount” of refrigerant
4. Equalizer pipe shutoff valve was charged, and push the RETURN button (BS3) once.
5. HP/LP gas pipe shutoff valve 6. After completing the additional refrigerant charging, record the
6. Suction pipe shutoff valve charging amount on the accessory “REQUEST FOR THE INDI-
7. Liquid pipe shutoff valve CATON” label (Installation records) and adhere it to the back side
8. Refrigerant charge port of the front panel. Also, record the factory charged refrigerant
9. Valve A amount, additional refrigerant amount in the field and total refrig-
10. Valve B
erant amount of the system to “ADDITIONAL REF. CHARGE”
11. Valve C
label and adhere in the proximity of the refrigerant charge port.
12. Outdoor unit A
13. Outdoor unit B About “ADDITIONAL REF. CHARGE” label, refer to [Important
14. Outdoor unit C information regarding the refrigerant used] in “1-2 Special notice
15. To BS, indoor unit of product”.
16. Field pipings 11-2-2 Procedure of check operation
17. Refrigerant flow when charging
18. Shutoff valve • Check operation perform the following work. Do the check opera-
19. Service port tion following below.
20. The refrigerant will be charged about 30kg in one hour at Otherwise, malfunction code “U3” will be displayed in the remote
outdoor temp. 30°CDB (12kg at 0°CDB). (According to controller and nomal operation can not be carried out.
outdoor temp. or the refrigerant amount in the tank, the „ Check of shutoff valve opening
charging rate may speed up). If you need to speed up in „ Check of miswiring
case of multi system, connect the refrigerant tanks to „ Judgment of piping length
each outdoor unit. „ Check of refrigerant overcharge
[Refrigerant Charging Operation Procedure]
Note
(1) Open the liquid pipe, suction gas pipe, HP/LP gas pipe and equal-
• Check operation can not carried out at outdoor temp. less than -5°C.
izer pipe shutoff valves (The valve A~C must be closed. The valve Perform the check operation at day or time that outdoor temp. is -5°C
A~C means the valves in the figure 31.)
or more.
(2) • Close the EL. COMPO. BOX lid and all front panel except on
the side of the EL. COMPO. BOX (*1) and turn the power to the [Check Operation Procedure]
outdoor unit and all connected indoor units. (*2) (1) Close the EL. COMPO. BOX lid and all front panels except as the
side of the EL. COMPO. BOX and turn on the power to the out-
• After H2P stop blinking (about 12 minutes after turning on the
door unit and all connected BS, indoor units. (Be sure to turn the
power), check LED displays as shown in Table : Display of nor-
power on at least 6 hours before operation in order to have power
mal system and the system is normal state.
running to the crank case heater.)
If H2P is blinking, check the malfunction code in the remote (2) Make the onsite settings as needed using the push button (BS1-
controller, and correct the malfunction in accordance with
BS5) on the outdoor unit PC-board (A1P) with the power on. (See
[Remote controller display malfunction code] in chapter 11-2-2.
“12 Onsite Settings”)

15 English
(3) Perform the check operation following the Check Operation Method of „ Additional refrigerant charge
the [Service Precautions] label (lower) on the EL. COMPO. BOX lid. „ Check operation
The system operation for about 40~60 minutes and automatically • Check that all work for the BS, indoor unit are finished and there
stops the check operation. are no danger to operate.
If the malfunction code is not displayed in the remote controller after
the system stop, check operation is completed. Normal operation will 13-2 Test Run
be possible after 5 minutes. If the malfunction code is displayed in the After all works are completed, operate the unit normally and check
remote controller, correct the malfunction following [Remote controller the following.
displays malfunction code] and perform the check operation again. (1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corre-
Note
For interrupting the check operation, push RETURN button (BS3). sponding outdoor unit is also operating.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
[Remote controller displays malfunction code]
(4) Push the fan direction and strength buttons on the remote control-
Malfunc- ler to see if they operate properly.
Installation error Remedial action
tion code
E3, E4 Note
The shutoff valve of the out- • Heating is not possible if the outdoor temperature is 24°C or
F3, F6 Open the shutoff valve.
door unit is left closed. higher. Refer to the Operation manual.
UF
• If a knocking sound can be heard in the liquid compression of the
The phases of the power to the Exchange two of the three phases (L1,
U1 compressor, stop the unit immediately and then energize the
outdoor unit is reversed. L2, L3) to make a proper connection.
crank case heater for a sufficient length of time before restarting
U1 No power is supplied to an out- Make sure the power source wire is prop-
the operation.
U4 door, BS or indoor unit (includ- erly connected to the outdoor, BS or
LC ing phase interruption). indoor unit and revise if necessary. • Once stopping, the compressor will not restart in about 5 minutes
even if the On/Off button of the remote controller is pushed.
There is conflict on the con- Check if the refrigerant piping line and the
UF nection of transmission wiring transmission wiring are consistent with • When the system operation is stopped by the remote controller,
in the system. each other. the outdoor units may continue operating for further 5 minutes at
maximum.
Recalculate the additional amount refrig-
E3 erant from the piping length and correct • The outdoor unit fan may rotate at low speeds if the Night-time low
F6 Refrigerant overcharge. the refrigerant charge level by recovering noise setting or the External low noise level setting is made, but
UF any excessive refrigerant with a refriger- this is not a malfunction.
ant recovery machine. • If the check operation was not performed at first istallation, the
• Check if the additional refrigerant malfunction code “U3” will be displayed in the remote controller.
charge has been finished correctly. Perform the check operation following “11-2-2 Procedure of
E4
Insufficient refrigerant. • Recalculate the additional amount Check Operation”.
F3
refrigerant from the piping length and
add the adequate amount. 13-3 Checks After Test Run
Field wiring is connected to
Perform the following checks after the test run is complete.
"TO MULTI UNIT (Q1,Q2)" ter-
U7, U4 Remove the line from the “TO MULTI • Record the contents of field setting.
minal on the outdoor unit PC-
UF, UH UNIT (Q1, Q2)” terminal. → Record them on the accessory “REQUEST FOR THE INDI-
board (A1P) when the system
is one outdoor system. CATION” label.
And attach the label on the back side of the front panel.
Note • Record the installation date.
If any malfunction codes other than the above are displayed, check → Record the installation date on the accessory “REQUEST
the service manual for how to respond. FOR THE INDICATION” label in accordance with the
IEC60335-2-40.
And attach the label on the back side of the front panel.
12. ONSITE SETTINGS
Note
Note After the test run, when handing the unit over to the customer, make
In the case of a multi system, all onsite settings should be made on sure the EL.COMPO.BOX lid, the inspection door, and the unit casing
the master unit. Settings made on sub units are invalid. are all attached.
The outdoor unit to which the indoor unit transmission wire are con-
nected is the master unit, and all other units are sub units.
14. CAUTION FOR REFRIGERANT LEAKS
Use the push button switches (BS1 through BS5) on the outdoor unit
PC-board (A1P) to make the necessary onsite settings. (Points to note in connection with refrigerant leaks)
See the “Service Precautions” label (upper) on the EL. CONPO. BOX Introduction
lid for details on the positions and operating method of the push but- The installer and system specialist shall secure safety against
ton switches and on the onsite setting. leakage according to local regulations or standards. The following
Make sure to record the setting on the accessory “REQUEST FOR standards may be applicable if local regulations are not available.
THE INDICATION” label. The VRV System, like other air conditioning systems, uses R410A as
refrigerant. R410A itself is an entirely safe non-toxic, non-combusti-
Warning Electric Shock Warning ble refrigerant. Nevertheless care must be taken to ensure that air
Use an insulated rod to operate the push buttons via the inspection conditioning facilities are installed in a room which is sufficiently large.
door of EL. COMPO. BOX lid. This assures that the maximum concentration level of refrigerant gas
There is a risk of electric shock if you touch any live parts, since is not exceeded, in the unlikely event of major leak in the system and
this operation must be performed with the power on. this in accordance to the local applicable regulations and standards.
Maximum concentration level
The maximum charge of refrigerant and the calculation of the maxi-
mum concentration of refrigerant is directly related to the humanly
13. TEST RUN occupied space in to which it could leak.
The unit of measurement of the concentration is kg/m3 ( the weight in
13-1 Before test run kg of the refrigerant gas in 1m3 volume of the occupied space).
• Make sure the following works are completed in accordance with Compliance to the local applicable regulations and standards for the
the installation manual. maximum allowable concentration level is required.
„ Piping work In Australia the maximum allowed concentration level of refrigerant to
„ Wiring work a humanly space is limited to 0.35kg/m3 for R407C and 0.44kg/m3 for
„ Air tight test R410A.
„ Vacuum drying

English 16
1

1. direction of the refrigerant flow


2. room where refrigerant leak has occurred (outflow of all
the refrigerant from the system)
Pay a special attention to the place, such as a basement, etc.
where refrigerant can stay, since refrigerant is heavier than air.
Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1
to 4 below and take whatever action is necessary to comply.
1. Calculate the amount of refrigerant (kg) charged to each system
separately.
amount of refriger- additional charging total amount
ant in a single unit + amount (amount of = of refriger-
system (amount of refrigerant added ant (kg) in
refrigerant with locally in accordance the system
which the system with the length or
is charged before diameter of the refrig-
leaving the factory) erant piping)
Note
• Where a single refrigerant facility is divided into 2 entirely inde-
pendent refrigerant systems then use the amount of refrigerant
with which each separate system is charged.
2. Calculate the smallest room volume (m3 )
Incase like the following, calculate the volume of (A), (B) as a sin-
gle room or as the smallest room.
A.Where there are no smaller room divisions

B.Where there is a room division but there is an opening


between the rooms sufficiently large to permit a free flow of
air back and forth.

1
2
1. opening between rooms
2. partition
(Where there is an opening without a door or where there are open-
ings above and below the door which are each equivalent in size to
0.15% or more of the floor area.)
3. Calculating the refrigerant density using the results of the calcu-
lations in steps 1 and 2 above.
total volume of refrigerant in the
refrigerant system
size (m3 ) of smallest room in which
≤ maximum concen-
tration level (kg/m3)
there is an indoor unit installed

If the result of the above calculation exceeds the maximum con-


centration level then make similar calculations for the second then
third smallest room and so until the result falls short of the maxi-
mum concentration.
4. Dealing with the situations where the result exceeds the maxi-
mum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be neces-
sary to revise the system. Please consult your Daikin supplier.

17 English
3P201178-5 EM06A072 (0702) FS