ALGIERS REFINERY Project N° Unit Document Code Material code Serial N° Rev.

Page

9952T 500 CN 0000 0002 D A


REHABILITATION AND ADAPTATION PROJECT
Document Class: 1

MS BLOCK - NHT UNIT

CAUSE & EFFECT CHART

H. MANE V. DEOLI
2012.06.28 11:11:05 2012.06.28 11:11:20
Neeraj Agrawal
+05'30' +05'30' 2012.06.28 14:44:10 +05'30'

D 28-JUN-2012 ISSUED FOR DESIGN H. MANE V. DEOLI N. AGRAWAL

C 21-MAY-2012 ISSUED FOR DESIGN H. MANE V. DEOLI N. AGRAWAL

B 18-APR-2012 ISSUED FOR DESIGN H. MANE V. DEOLI N. AGRAWAL

A 03-NOV-2011 ISSUED FOR REVIEW H. MANE V. DEOLI N. AGRAWAL

REV. DATE STATUS WRITTEN BY CHECKED BY APPROV./AUTHOR. BY

DOCUMENT REVISIONS
Project N° Unit Document Code Material code Serial N° Rev. Page Date
9952T 500 CN 0000 0002 D 1 28-JUN-12
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class: 1

Rev Rev
A B C D E 0 1 2 3 4 A B C D E 0 1 2 3 4
Page Page
A X X X X

1 X X X X
2 X X
3 X X
4 X
5 X
6 X X
7 X
8 X
9 X
10 X X X
11 X X
12 X X
13 X X
14 X
15 X
16 X
17 X X X
18 X X X
19 X
20 X
21 X
22 X
23 X
Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate

NOTE
C= Close
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1101
OPM = Open and in Manual

MOS : Maintenance Override Switch

Feed to NHDT Feed Surge


EFFECT
OOS : Operation Override Switch

DESCRIPTION
N/A: Not Applicable
UZ-0001

Drum
NHT Emergency Shutdown System
Case : NHDT Feed Surge Drum (500-D-001) Overfilling Protection
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

EQUIPMT
1) UZ actuated when at least 2 out of 3 are voting.

OUTPUT
TAG No

500-UZV-0001
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
(1) Feed Surge Drum Liquid Level FIELD 2oo3 3100 mm 1101 500-LZAHH-0003 1 C 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 2


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1102
MOS : Maintenance Override Switch
OOS : Operation Override Switch
N/A: Not Applicable

EFFECT

NHDT Feed Pumps


DESCRIPTION
UZ-0002
NHT Emergency Shutdown System
Case : NHDT Feed Pumps (500-P-001 A/B) Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

500-P-001 A/B
1) UZ actuated when at least 2 out of 3 are voting.

EQUIPMT
OUTPUT
TAG No
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
(1) Feed Surge Drum Liquid Level FIELD 2oo3 400 mm 1101 500-LZALL-0003 1 T 1

500-UZ-0003 NHDT Feed Surge Drum Isolation 2 T 2

500-UZ-0008 Emergency Depressurization 3 T 3

500-UZ-0005 Reactor Feed Heater Shutdown 4 T 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 3


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0002
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1101

1102
OPM = Open and in Manual

MOS : Maintenance Override Switch

NHDT Feed Pumps Shutdown


NHDT Feed Surge drum liquid
OOS : Operation Override Switch

EFFECT
N/A: Not Applicable

DESCRIPTION
UZ-0003

outlet
NHT Emergency Shutdown System
Case : NHDT Feed Surge Drum (500-D-001) Isolation GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
2) The Valve must be fully open (UZSO) before pump (500-
P-001 A/B) can start. UZ-0003 is inhibited during valve
opening. When the valve is opened (UZSO) and Pump (500
P-001 A/B) is running, if UZSO is no longer activated (Non

OUTPUT
UZSO), UZ-0003 is energized and stops the pump. If

TAG No

500-UZV-0002
UZSC, UZ-0003 is energized & stops the pump.
CAUSE
INITIATOR/FIELD

TRIP POINT OVERRIDE TAG No.


LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for NHDT Feed Surge
HWC 1101 500-UZHSC-0002A 1 C A 1
Drum Isolation
Hand Switch for NHDT Feed Surge
(1) FIELD 1101 500-UZHSC-0002B 2 C A 2
Drum Isolation
500-UZV-0002 not fully open at
(2) NHDT Feed Surge drum (500-D- FIELD 1101 500-UZLO-0002 3 C A 3
001) Outlet
500-UZV-0002 fully closed at NHDT
(2) Feed Surge drum (500-D-001) FIELD 1101 500-UZLC-0002 4 C A 4
Outlet

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0002 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 4


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate

NOTE
C= Close
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1102
OPM = Open and in Manual

MOS : Maintenance Override Switch

Naphtha Feed to Reaction


EFFECT
OOS : Operation Override Switch

Reactor Feed Heater


DESCRIPTION
N/A: Not Applicable
UZ-0004

section
NHT Emergency Shutdown System
Case : NHDT Reaction Section Shutdown
GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :

EQUIPMT
1) UZ actuated when at least 2 out of 3 are voting.

500-F-001
OUTPUT
TAG No

500-UZV-0003
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
NHDT Feed Pumps discharge 80.8
(1) FIELD 2oo3 1102 500-FZALL-0007 1 T C 1
Flow m3/hr
Recycle Compressor discharge 7847
(1) FIELD 2oo3 1109 500-FZALL-0016 2 C 2
Flow Nm3/hr

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 5


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1104

1102

1102
MOS : Maintenance Override Switch

Naphtha Feed to Reaction section


OOS : Operation Override Switch
N/A: Not Applicable

EFFECT

Reactor Feed Heater

NHT Feed Pumps


DESCRIPTION
UZ-0005
NHT Emergency Shutdown System
Case : Reactor Feed Heater Shutdown
GENERAL NOTES :

SERVICE
A.-

500-NHT
NOTES :

500-P-001 A/B
1) To be located in an enclosure at safe location.

EQUIPMT

500-F-001
2) Reactor Feed Heater (500-F-001) shutdown interlock also
to be activated by Heater internal safety system. Refer
Vendor doc.no. RB-10010-913 for details.
3) By Heater Vendor.
4) Reactor Feed Heater (500-F-001) shutdown means

OUTPUT
TAG No
closure of Main Natural Gas shutoff valves to Pilots (500-

500-UZV-0003
UZV-1204 & 1205), opening of Pilot vent valve 500-UZV-
CAUSE
1206, closure of Main Fuel Gas shutoff valves to Burners
(500-UZV-1201 & 1202), opening of FG Burner vent valve
INITIATOR/FIELD

OVERRIDE TAG No. 500-UZV-1203, closure of Main Fuel Oil shutoff valve to
TRIP POINT
LOCATION

Burners (500-UZV-1207), closure of Return Oil shutoff valve

DELAY
VOTE

OTHER 500-UZV-1208 and opening of Stack Damper 500-HV-


Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.
1209.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for Reactor Feed
HWC 1104 500-HZS-0005A 1 T T C 1
Heater Shutdown
Hand Switch for Reactor Feed
(1) (3) FIELD 1104 500-HZS-1257C 2 T T C 2
Heater Shutdown

(2) (4) Reactor Heater Package Shutdown 3 T T C 3

500-UZ-0008 Emergency Depressurization 4 T T C 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 6


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1107
MOS : Maintenance Override Switch
OOS : Operation Override Switch

NHDT Separator drum liquid


N/A: Not Applicable

EFFECT

DESCRIPTION
UZ-0006

outlet
NHT Emergency Shutdown System
Case : NHDT Separator Drum (500-D-002) Isolation
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
OUTPUT
TAG No

500-UZV-0004
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
NHDT Separator Drum Liquid
FIELD 1oo1 600 mm 1107 500-LZALL-0011 1 C 1
Level
Hand Switch for NHDT Separator
HWC 1107 500-UZHSC-0004A 2 C 2
Drum Isolation

Hand Switch for NHDT Separator


(1) FIELD 1107 500-UZHSC-0004B 3 C 3
Drum Isolation

500-UZ-0008 Emergency Depressurization 4 C 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0004 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 7


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE

(1)
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1107
MOS : Maintenance Override Switch
OOS : Operation Override Switch

Separator drum boot liquid outlet


N/A: Not Applicable

EFFECT

DESCRIPTION
UZ-0007
NHT Emergency Shutdown System
Case : NHDT Separator Drum Boot (500-D-002) Isolation
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :
1) 500-LV-0007 valve is used as Level control as well as

EQUIPMT
isolation.

OUTPUT
TAG No

500-LV-0007
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
NHDT Separator Drum boot Liquid
FIELD 1oo1 300 mm 1107 500-LZALL-0008 1 C 1
Level

500-UZ-0008 Emergency Depressurization 2 C 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 8


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0009

500-UZ-0010
500-UZ-0002

500-UZ-0005

500-UZ-0006

500-UZ-0007

500-UZ-0011
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION

SIL
V = oVerride
CLM = Closed and in Manual

Recycle Compressors Shutdown1109, 1110

Recycle Compressors Isolation 1109, 1110


P&ID
OPM = Open and in Manual

1107

1102

1107

1107

1107

1108
MOS : Maintenance Override Switch

NHDT Feed Pump Shutdown


OOS : Operation Override Switch

Separator Drum Boot Isolation


EFFECT

H2 makeup Feed Isolation


Reactor Heater Shutdown
Depressurization Valve

Separator Drum Isolation


N/A: Not Applicable

DESCRIPTION
UZ-0008
NHT Emergency Shutdown System
Case : Emergency Depressurization GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
OUTPUT
TAG No

500-UZV-0005
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for depressurization HWC 1107 500-UZHSC-0005A 1 O A A A A A A A 1

(1) Hand Switch for depressurization FIELD 1107 500-UZHSC-0005B 2 O A A A A A A A 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0005 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 9


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0011
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1109

1110

1108
MOS : Maintenance Override Switch
OOS : Operation Override Switch
N/A: Not Applicable

EFFECT

H2 Makeup Feed Isolation


Recycle Compressor A

Recycle Compressor B
DESCRIPTION
UZ-0009
NHT Emergency Shutdown System
Case : Recycle Compressors (500-K-001 A/B) Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :
1) To be located at Safe Location.

500-K-001A

500-K-001B
EQUIPMT
2) Trip point is based on 5OC above maximum discharge
temperature.
3) Recycle Compressor (500-K-001 A/B) Shutdown interlock
also to be activated by Compressor internal safety system.
Refer vendor doc no."D412B-INST-012" for details.

OUTPUT
TAG No
4) UZ actuated when at least 2 out of 3 are voting.
CAUSE 5) Temperature Transmitter will be provided by Compressor
Vendor.
6) By Compressor vendor.
INITIATOR/FIELD

OVERRIDE TAG No.

TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for Recycle
D HWC 1109 500-HZS-0051A 1 T A 1
Compressor A Shutdown
Hand Switch for Recycle
D (6) FIELD 1109 500-HZS-1017A 2 T A 2
Compressor A Shutdown
Hand Switch for Recycle
D HWC 1110 500-HZS-0051B 3 T A 3
Compressor B Shutdown
Hand Switch for Recycle
D (6) FIELD 1110 500-HZS-1017B 4 T A 4
Compressor B Shutdown
Recycle Compressor A discharge 500-TZAHH-1002 /
(4) (5) FIELD 2oo3 (2) 107 1109 5 T A 5
Temperature 500-TZAHH-1007
Recycle Compressor B discharge 500-TZAHH-1004 /
(4) (5) FIELD 2oo3 (2) 107 1110 6 T A 6
Temperature 500-TZAHH-1096

(4) Compressor KOD liquid level FIELD 2oo3 700 mm 1108 500-LZAHH-0012 7 T T A 7

(3) Compressor Package Shutdown 8 T T A 8

500-UZ-0010 Recycle Compressor Isolation 9 T T 9

500-UZ-0008 Emergency Depressurization 10 T T 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 10


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE

(3)

(3)
O = Open
S = Start

500-UZ-0009

500-UZ-0011
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual

1109, 1110
OPM = Open and in Manual

P&ID

1109

1109

1108
MOS : Maintenance Override Switch

Recycle Compressors discharge


OOS : Operation Override Switch

Recycle Compressors Suction

Recycle Compressor Shutdown


N/A: Not Applicable

EFFECT

H2 makeup Feed Isolation


DESCRIPTION
UZ-0010

valve

valve
NHT Emergency Shutdown System
Case : Recycle Compressors (500-K-001 A/B) Isolation
GENERAL NOTES :

SERVICE
A.-

500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
2) The Valve must be fully open (UZSO) before
Compressor (500-K-001 A/B) can start. UZ-0010 is
inhibited during valve opening. When the valve is opened
(UZSO) and compressor (500-K-001 A/B) is running, if
UZSO is no longer activated (Non UZSO), UZ-0010 is

OUTPUT
TAG No
energized and stops the compressor. If UZSC, UZ-0010

500-UZV-0008

500-UZV-0009
is energized & stops the compressor.
CAUSE
3) 500-UZV-0008 and 500-UZV-0009 valves are closed
INITIATOR/FIELD after the complete stop of compressors 500-K-001 A/B. A
OVERRIDE TAG No. time delay of about 3 min. is required between the

TRIP POINT
LOCATION
shutdown of the compressors 500-K-001 A/B and the 500

DELAY
VOTE
Rev. NOTE
OTHER
DESCRIPTION SIL P&ID TAG No.
UZV-0008 and 500-UZV-0009 closure. This time delay
LOGIC shall be adjusted during pre-commisioning / commisioning

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
stage based on actual closing time of compressor.

Hand Switch for Recycle


HWC 1109 500-UZHSC-0008A 1 C A A 1
Compressors suction isolation

Hand Switch for Recycle


(1) FIELD 1109 500-UZHSC-0008B 2 C A A 2
Compressors suction isolation

500-UZV-0008 not fully open on


(2) Recycle Compressor (500-K-001 FIELD 1109 500-UZLO-0008 3 C A A 3
A/B) inlet

500-UZV-0008 fully closed on


(2) Recycle Compressor (500-K-001 FIELD 1109 500-UZLC-0008 4 C A A 4
A/B) inlet

Hand Switch for Recycle


HWC 1109 500-UZHSC-0009A 5 C A A 5
Compressors discharge isolation
Hand Switch for Recycle
(1) FIELD 1109 500-UZHSC-0009B 6 C A A 6
Compressors discharge isolation

500-UZV-0009 not fully open on


Recycle Compressor (500-K-001 FIELD 1109 500-UZLO-0009 7 C A A 7
A/B) outlet

500-UZV-0009 fully closed on


Recycle Compressor (500-K-001 FIELD 1109 500-UZLC-0009 8 C A A 8
A/B) outlet

UZ-0008 Emergency Depressurization 9 C C 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0008 1 R 1
Reset Push Button FIELD 500-UZHSR-0009 2 R 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 11


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1108
MOS : Maintenance Override Switch
OOS : Operation Override Switch

H2 makeup Isolation valve


N/A: Not Applicable

EFFECT

DESCRIPTION
UZ-0011
NHT Emergency Shutdown System
Case : H2 Makeup Feed Isolation
GENERAL NOTES :

SERVICE
A.-

500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
OUTPUT
TAG No

500-UZV-0006
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.

TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for H2 makeup valve HWC 1108 500-UZHSC-0006A 1 C 1

(1) Hand Switch for H2 makeup valve FIELD 1108 500-UZHSC-0006B 2 C 2

500-UZV-0006 not fully open at


Compressor K.O. Drum (500-D- FIELD 1108 500-UZLO-0006 3 C 3
003) inlet

500-UZV-0006 fully closed at


Compressor K.O. Drum (500-D- FIELD 1108 500-UZLC-0006 4 C 4
003) inlet

500-UZ-0008 Emergency Depressurization 5 C 5

500-UZ-0009 Recycle Compressors Shutdown 6 C 6

500-UZ-0010 Recycle Compressors Isolation 7 C 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0006 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 12


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1114

1125
MOS : Maintenance Override Switch
OOS : Operation Override Switch
N/A: Not Applicable

EFFECT

Stripper Reboiler Pumps


DESCRIPTION

Stripper Reboiler
UZ-0012
NHT Emergency Shutdown System
Case : Stripper Reboiler (500-F-002) / Pumps (500-P-005 A/B) Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

500-P-005 A/B
1) To be located at Safe Location.

EQUIPMT

500-F-002
2) Stripper Reboiler (500-F-002) shutdown interlock also to
be activated by Heater internal safety system. Refer Vendor
doc.no. RB-10011-913 for details.
3) UZ actuated when at least 2 out of 3 are voting.
4) By Heater Vendor.

OUTPUT
TAG No
5) Stripper Reboiler (500-F-002) shutdown means closure of
Main Natural Gas shutoff valves to Pilots (500-UZV-1304 &
CAUSE
1305), opening of Pilot vent valve 500-UZV-1306, closure of
Main Fuel Gas shutoff valves to Burners (500-UZV-1301 &
INITIATOR/FIELD

OVERRIDE TAG No. 1302), opening of FG Burner vent valve 500-UZV-1303,


TRIP POINT
LOCATION

closure of Main Fuel Oil shutoff valve to Burners (500-UZV-

DELAY
VOTE

OTHER 1307), closure of Return Oil shutoff valve 500-UZV-1308


Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.
and opening of Stack Damper 500-HV-1309.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
15.2
(3) Stripper Overhead Pressure FIELD 2oo3 1113 500-PZAHH-0067 1 T T 1
kg/cm2g
(3) Stripper Reboiler Flow (Pass - 1) FIELD 2oo3 40 m3/hr 1114 500-FZALL-0037 2 T T 2

(3) Stripper Reboiler Flow (Pass - 2) FIELD 2oo3 40 m3/hr 1114 500-FZALL-0039 3 T T 3

(3) Stripper Reboiler Flow (Pass - 3) FIELD 2oo3 40 m3/hr 1114 500-FZALL-0041 4 T T 4

(3) Stripper Reboiler Flow (Pass - 4) FIELD 2oo3 40 m3/hr 1114 500-FZALL-0043 5 T T 5

Hand Switch for Reboiler shutdown HWC 1114 HZS-0031A 6 T T 6

(1) (4) Hand Switch for Reboiler shutdown FIELD 1114 HZS-1357C 7 T T 7

(3) Stripper Column Liquid Level FIELD 2oo3 1150 mm 1113 500-LZALL-0015 8 T T 8

500-UZ-0013 Stripper Isolation 9 T T 9

Stripper Reboiler Package


(2) (5) 10 T T 10
Shutdown

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 13


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0012
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1113

1114
OPM = Open and in Manual

MOS : Maintenance Override Switch

Stripper column bottom liquid

Stripper Reboiler / Pumps


OOS : Operation Override Switch

EFFECT
N/A: Not Applicable

DESCRIPTION

Shutdown
UZ-0013

outlet
NHT Emergency Shutdown System
Case : Stripper (500-C-001) Isolation GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
2) The Valve must be fully open (UZSO) before pump (500-
P-005 A/B) can start. UZ-0013 is inhibited during valve
opening. When the valve is opened (UZSO) and Pump (500
P-005 A/B) is running, if UZSO is no longer activated (Non

OUTPUT
UZSO), UZ-0013 is energized and stops the pump. If

TAG No

500-UZV-0010
UZSC, UZ-0013 is energized & stops the pump.
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for Stripper column
HWC 1113 500-UZHSC-0010A 1 C A 1
Isolation
Hand Switch for Stripper column
(1) FIELD 1113 500-UZHSC-0010B 2 C A 2
Isolation

500-UZV-0010 not fully open at


(2) FIELD 1113 500-UZLO-0010 3 C A 3
Stripper (500-C-001) Outlet

500-UZV-0010 fully closed at


(2) FIELD 1113 500-UZLC-0010 4 C A 4
Stripper (500-C-001) Outlet

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0010 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 14


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1118
MOS : Maintenance Override Switch
OOS : Operation Override Switch

Stripper Reflux Pumps Shutdown


N/A: Not Applicable

EFFECT

DESCRIPTION
UZ-0014
NHT Emergency Shutdown System
Case : Stripper Reflux Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

500-P-002 A/B
EQUIPMT
OUTPUT
TAG No
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Stripper Reflux drum Liquid Level FIELD 1oo1 400 mm 1115 500-LZALL-0025 1 T 1

500-UZ-0015 Stripper Reflux drum Isolation 2 T 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 15


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0014
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1115

1115
OPM = Open and in Manual

MOS : Maintenance Override Switch

NHDT Stripper Reflux drum


OOS : Operation Override Switch

EFFECT

Stripper Reflux Pumps


N/A: Not Applicable

DESCRIPTION

liquid outlet

Shutdown
UZ-0015
NHT Emergency Shutdown System
Case : Stripper Reflux Drum (500-D-004) Isolation GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
2) The Valve must be fully open (UZSO) before pump (500-
P-002 A/B) can start. UZ-0015 is inhibited during valve
opening. When the valve is opened (UZSO) and Pump (500
P-002 A/B) is running, if UZSO is no longer activated (Non

OUTPUT
UZSO), UZ-0015 is energized and stops the pump. If

TAG No

500-UZV-0012
UZSC, UZ-0015 is energized & stops the pump.
CAUSE
INITIATOR/FIELD

TRIP POINT OVERRIDE TAG No.


LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for NHDT Stripper
HWC 1115 500-UZHSC-0012A 1 C A 1
Reflux Drum Isolation
Hand Switch for NHDT Stripper
(1) FIELD 1115 500-UZHSC-0012B 2 C A 2
Reflux Drum Isolation
500-UZV-0012 not fully open at
(2) NHDT Stripper Reflux drum (500-D- FIELD 1115 500-UZLO-0012 3 C A 3
004) Outlet
500-UZV-0012 fully closed at NHDT
(2) Stripper Reflux drum (500-D-004) FIELD 1115 500-UZLC-0012 4 C A 4
Outlet

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0012 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 16


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate

NOTE
C= Close
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1115
OPM = Open and in Manual

Stripper Reflux drum boot liquid


MOS : Maintenance Override Switch

EFFECT
OOS : Operation Override Switch

DESCRIPTION
N/A: Not Applicable
UZ-0016

outlet
NHT Emergency Shutdown System
Case : Stripper Reflux Drum (500-D-004) Boot Isolation
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

EQUIPMT
OUTPUT
TAG No

500-UZV-0016
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Stripper Reflux drum boot liquid
FIELD 1oo1 300 mm 1115 500-LZALL-0022 1 C 1
outlet
Stripper Reflux drum boot liquid
FIELD 1001 850 mm 1115 500-LZAH-0022 2 O 2
outlet
3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 17


Rev.
ABBREVIATIONS USED IN THE MATRIX :

D
A = Activate

NOTE
C= Close
O = Open
S = Start

600-UZV-0018
530-UZV-0008

530-UZV-0008

600-UZV-0018
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION
V = oVerride

SIL
CLM = Closed and in Manual

530-1174

530-1174

600-1114

600-1114
OPM = Open and in Manual

P&ID

1119

1126
MOS : Maintenance Override Switch

CANISTER DIVERTING VALVE


OOS : Operation Override Switch

VENT GAS TO RELIEF HEATER


EFFECT

VENT GAS TO CARBON


N/A: Not Applicable

VENT GAS TO HEATER

VENT GAS TO HEATER


Splitter Reboiler Pumps

DIVERTING VALVE

DIVERTING VALVE

DIVERTING VALVE
DESCRIPTION

Splitter Reboiler
UZ-0017
NHT Emergency Shutdown System
Case : Splitter Reboiler (500-F-003) / Pumps (500-P-006 A/B) Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

530-UZV-0202 A

530-UZV-0202 B
500-P-006 A/B

600-UZV-0008

600-UZV-0007
1) To be located at Safe Location.

EQUIPMT

500-F-003
2) Splitter Reboiler (500-F-003) shutdown interlock also to
be activated by Heater internal safety system. Refer Vendor
doc.no. RB-10012-913 for details.
3) UZ actuated when at least 2 out of 3 are voting.
4) By Heater Vendor.

OUTPUT
TAG No
5) Splitter Reboiler (500-F-003) shutdown means closure of
Main Natural Gas shutoff valves to Pilots (500-UZV-1404 &
CAUSE
1405), opening of Pilot vent valve 500-UZV-1406, closure of
Main Fuel Gas shutoff valves to Burners (500-UZV-1401 &
INITIATOR/FIELD

OVERRIDE TAG No. 1402), opening of FG Burner vent valve 500-UZV-1403,


TRIP POINT
LOCATION

closure of Main Fuel Oil shutoff valve to Burners (500-UZV-

DELAY
VOTE

OTHER 1407), closure of Return Oil shutoff valve 500-UZV-1408


Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.
and opening of Stack Damper 500-HV-1409.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
3.3
(3) Splitter Overhead Pressure FIELD 2oo3 1116 500-PZAHH-0095 1 T T 1
kg/cm2g
(3) Splitter Reboiler Flow (Pass - 1) FIELD 2oo3 55 m3/hr 1119 500-FZALL-0046 2 T T 2

(3) Splitter Reboiler Flow (Pass - 2) FIELD 2oo3 55 m3/hr 1119 500-FZALL-0048 3 T T 3

(3) Splitter Reboiler Flow (Pass - 3) FIELD 2oo3 55 m3/hr 1119 500-FZALL-0050 4 T T 4

(3) Splitter Reboiler Flow (Pass - 4) FIELD 2oo3 55 m3/hr 1119 500-FZALL-0052 5 T T 5

Hand Switch for Reboiler shutdown HWC 1119 HZS-0032A 6 T T 6

(1) (4) Hand Switch for Reboiler shutdown FIELD 1119 HZS-1457C 7 T T 7

(3) Splitter Column Liquid Level FIELD 2oo3 2250 mm 1113 500-LZALL-0026 8 T T 8

500-UZ-0018 Heavy Naphtha Pumps Shutdown 9 T T 9

500-UZ-0019 Splitter Isolation 10 T T 10

(2) (5) Splitter Reboiler Package Shutdown 11 T T 11

D Splitter Reboiler Shutdown 500-UZ-0017 12 C O C O 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 18


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0017
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1122

1119
MOS : Maintenance Override Switch
OOS : Operation Override Switch

Heavy Naphtha Pump Shutdown


N/A: Not Applicable

EFFECT

Splitter Reboiler / Pumps


DESCRIPTION

Shutdown
UZ-0018
NHT Emergency Shutdown System
Case : Heavy Naphtha Pumps (500-P-003 A/B) Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

500-P-003 A/B
1) UZ actuated when at least 2 out of 3 are voting.

EQUIPMT
OUTPUT
TAG No
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
(1) Splitter Column Liquid Level FIELD 2oo3 2250 mm 1116 500-LZALL-0026 1 T A 1

500-UZ-0019 Splitter Isolation 2 T 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 19


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start

500-UZ-0017

500-UZ-0018
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1116

1119

1122
OPM = Open and in Manual

MOS : Maintenance Override Switch

Heavy Naphtha Pump Shutdown


Splitter column bottom liquid

Splitter Reboiler / Pumps


OOS : Operation Override Switch

EFFECT
N/A: Not Applicable

DESCRIPTION

Shutdown
UZ-0019

outlet
NHT Emergency Shutdown System
Case : Splitter (500-C-002) Isolation GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :
1) To be located at Safe Location.

EQUIPMT
2) The Valve must be fully open (UZSO) before pump (500-
P-006 A/B) can start. UZ-0019 is inhibited during valve
opening. When the valve is opened (UZSO) and Pump (500
P-006 A/B) is running, if UZSO is no longer activated (Non

OUTPUT
UZSO), UZ-0019 is energized and stops the pump. If

TAG No

500-UZV-0013
UZSC, UZ-0019 is energized & stops the pump.
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for Splitter column
HWC 1116 500-UZHSC-0013A 1 C A A 1
Isolation
Hand Switch for Splitter column
(1) FIELD 1116 500-UZHSC-0013B 2 C A A 2
Isolation
500-UZV-0013 not fully open at
(2) FIELD 1116 500-UZLO-0013 3 C A A 3
Splitter (500-C-002) Outlet

500-UZV-0013 fully closed at


(2) FIELD 1116 500-UZLC-0013 4 C A A 4
Splitter (500-C-002) Outlet

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0013 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 20


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate
C= Close

NOTE
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
R = Reset
UNIT or EQUIPMENT LOGIC IDENTIFICATION V = oVerride

SIL
CLM = Closed and in Manual
OPM = Open and in Manual

P&ID

1118
MOS : Maintenance Override Switch
OOS : Operation Override Switch

Splitter Reflux Pumps Shutdown


N/A: Not Applicable

EFFECT

DESCRIPTION
UZ-0020
NHT Emergency Shutdown System
Case : Splitter Reflux / Light Naphtha Shutdown
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

500-P-004 A/B
EQUIPMT
OUTPUT
TAG No
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Splitter Reflux drum Liquid Level FIELD 1oo1 450 mm 1118 500-LZALL-0033 1 T 1

500-UZ-0021 Splitter Reflux drum Isolation 2 T 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 21


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate

NOTE
C= Close
O = Open
S = Start

500-UZ-0020
OTHER
T = Trip

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1118

1118
OPM = Open and in Manual

MOS : Maintenance Override Switch

NHDT Splitter Reflux drum


EFFECT

Splitter Reflux Pumps


OOS : Operation Override Switch

DESCRIPTION
N/A: Not Applicable

liquid outlet

Shutdown
UZ-0021
NHT Emergency Shutdown System
Case : Splitter Reflux Drum (500-D-007) Isolation GENERAL NOTES :

SERVICE
A.-
500-NHT
NOTES :

EQUIPMT
1) To be located at Safe Location.
2) The Valve must be fully open (UZSO) before pump (500-
P-004 A/B) can start. UZ-0021 is inhibited during valve
opening. When the valve is opened (UZSO) and Pump
(500-P-004 A/B) is running, if UZLO is no longer activated

OUTPUT
TAG No
(Non UZSO), UZ-0021 is energized and stops the pump. If

500-UZV-0014
UZSC, UZ-0021 is energized & stops the pump.
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.

TRIP POINT
LOCATION

DELAY
VOTE
OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Hand Switch for NHDT Splitter
HWC 1118 500-UZHSC-0014A 1 C A 1
Reflux Drum Isolation
Hand Switch for NHDT Splitter
(1) FIELD 1118 500-UZHSC-0014B 2 C A 2
Reflux Drum Isolation
500-UZV-0014 not fully open at
(2) NHDT Splitter Reflux drum (500-D- FIELD 1118 500-UZLO-0014 3 C A 3
007) Outlet
500-UZV-0014 fully closed at
(2) NHDT Splitter Reflux drum (500-D- FIELD 1118 500-UZLC-0014 4 C A 4
007) Outlet

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
Reset Push Button FIELD 500-UZHSR-0014 1 R 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 22


Rev.
ABBREVIATIONS USED IN THE MATRIX :
A = Activate

NOTE
C= Close

(1)
O = Open
S = Start
T = Trip

OTHER

LOGIC
I = Inhibit
P = Permissive
UNIT or EQUIPMENT LOGIC IDENTIFICATION R = Reset

SIL
V = oVerride
CLM = Closed and in Manual

P&ID

1124
OPM = Open and in Manual

MOS : Maintenance Override Switch

Sour Water Degassing Drum


EFFECT
OOS : Operation Override Switch

DESCRIPTION
N/A: Not Applicable

liquid outlet
UZ-0022
NHT Emergency Shutdown System
Case : Sour Water Degassing Drum (500-D-008) Isolation
GENERAL NOTES :

SERVICE
A.- Trip point for level is from equipment bottom T/L.
500-NHT
NOTES :

EQUIPMT
1) 500-LV-0037 valve is used as Level control as well as
isolation.

OUTPUT
TAG No

500-LV-0037
CAUSE
INITIATOR/FIELD

OVERRIDE TAG No.


TRIP POINT
LOCATION

DELAY
VOTE

OTHER
Rev. NOTE
LOGIC
DESCRIPTION SIL P&ID TAG No.

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30
OOS MOS

9
Sour Water Degassing Drum
FIELD 1oo1 300 mm 1124 500-LZALL-0038 1 C 1
liquid outlet
2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 30
UNIT 500
NAPHTHA HYDROTREATING UNIT

CAUSE AND EFFECT CHART Project N° - Unit Doc. type Code Serial N° Rev. index SHEET

9952T-500 CN 0000 0002 D 23