8 Disjoncteur Diff Chint
8 Disjoncteur Diff Chint
RCBO
NB1L Residual Current
Operated Circuit Breaker
with over-current protection A
(Magnetic)
1. General
1.1 Function
Personnel and fire protection: Cable and line protection against
overload and short-circuits.
1.2 Selection
Rated residual operating current
I∆n ≤30 mA: additional protection in the case of direct
contact.
I∆n ≤300 mA: preventative fire protection in the case of
ground fault currents.
Tripping class
AC class
Tripping is ensured for sinusoidal,
alternating currents, whether they be quickly applied or
slowly increase.
A class
Tripping is ensured for sinusoidal, alternating
residual currents as well as for pulsed DC residual
currents, whether they be quickly applied or slowly
increase.
Tripping curve
B curve (3-5 In) protection and control of the circuits against
overloads and short-circuits; protection for
people and big length cables in TN and IT systems.
C curve (5-10 In) protection and control of the circuits
against overloads and short-circuits; protection for
resistive and inductive loads with low inrush current.
10000
5000
1h
t(s) B Curve t(s)
10000
5000
1h
C Curve
A
2000 2000
1000 1000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
2 2
1 1
0.5 0.5
0.2 0.2
0.1 0.1
0.05 0.05
0.02 0.02
0.01 0.01
0.005 0.005
0.002 0.002
0.001 0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In 0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In
3.2
Temperature compensation
1.20 1.15 1.10 1.05 1.00 0.95 0.90 0.85
coefficient of rated current
0
78.5 -1.2
49.5±0.31
5.5
A
34.5±0.5
45±0.31
-1.4
0
88
4P 0 0
54 -1.20 63 -1.2
49.5±0.31
NB1L
C 40 I△n 0.03A test monthly
45±0.31
45±0.31
6000 t≤0.1s
N 1
85 -1.4
35 -0.5
86 -1.4
35 -1.0
230 V~
0
IEC/EN61009-1
982418 N 2
0 0 0 0
36 -0.62 77 -1.2 54-1.2 76.5 -1.2