Earthing Switch and Cubicle Components - Schneider
Earthing Switch and Cubicle Components - Schneider
MV and LV components
Evolis
up to 24 kV
Catalogue
2004
Panorama 2
Earthing switch 4
Description and electrical characteristics 4
Optional functions 5
Dimensions 6
Cubicle components 7
Components for operation 7
Other components 9
Offer structure 10
Earthing switch 10
Cubicle components 11
Order form 13
1
Panorama MV and LV components
DE40061
Electromechanical locking
Mechanical interlocking
Electromechanical interlocking
VPIS
(Voltage Presence
Indicator System)
Earthing switch
operating crank
Open/closed
position
contacts
Mechanical locking
using keys
2
Panorama
Cubicle components
DE40062
Busbar connection
cover
DV2
(kA)
Icu
(V) 100
Ue
220/440 100
525 85
690
85kA/1s
Icw
cat.B
Icu
100%
Ics =
50/60Hz
947-2 NEMA
IEC AS
UNE
EN 60947-2
CEI
BS
VDE
UTE
Capacitive divider
insulation set
Door handle
Support insulator
Anticondensation
heating resistance
3
Earthing switch Description and
electrical characteristics
Function
This device is used to short circuit and earth the cable ends.
Composition
DE40066
DE40065
Interlocking
DE40067
DE40068
b When associated with Evolis circuit-breaker and cradle, the mechanical interlock
prevents:
v to rack in the circuit-breaker if the earthing switch is closed
v to close the earthing switch if the circuit-breaker is not racked out.
b In case of installation in the NEX cubicle, the mechanical interlock with the front
and/or rear plate of the cable compartment is part of the NEX license.
b In other case the design is under the responsibility of the panel builder.
Operating mechanism box Drawing for the rods
IEC 62271-102
Mechanical interlock Phase distance mm 160 200 240 240
Rated values
voltage kV rms 7.2 12 7.2 12 17.5 7.2 12 17.5 24
DE40072
frequency fr Hz 50/60
power frequency withstand voltage(1) Ud kV rms 20 28 20 28 38 20 28 38 50
lighting impulse withstand voltage Up kV peak 60 75 60 75 95(2) 60 75 95 125
short-time withstand current 1s Ik kArms-1s 31.5 31.5 50 40 31.5 50 50 40 31.5
short-time withstand current kArms 31.5-4s 31.5-3s
peak wisthstand Ip kA peak 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
short-circuit making current 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
Endurance
mechanical endurance Ur kV rms Mo class (1000 cycles)
electrical endurance E1 class(3)
Interlocking
4
Earthing switch Optional functions
b The VPIS, combined with the capacitive divider insulators of the power circuit unit,
provides an indication by lights of the voltage presence on each phase of the main
circuit.
b The voltage presence indicator unit is installed on the front of the earthing switch
Voltage presence indicator unit operating mechanism box.
b The voltage presence indicator unit covers two voltage ranges, in accordance
with standard IEC 61958:
v 3.2 to 7.2 kV
v 10 to 24 kV.
DE40071
This function enables the earthing switch to be locked in its open or closed position
by adding 1 or 2 key locks.
b The option includes mechanical adaptation kit. Keylocks are not supplied
b Three configurations are available:
v locked closed by 1 key lock + locked open by 1 key lock
v locked closed by 2 key locks
v locked open by 2 key locks.
Mechanical locking of the
earthing switch using keys
Electromechanical locking of
DE40077
Electromechanical locking
of the earthing switch
Mechanical and electromechanical
interlockings with Evolis circuit-breaker
DE40092
DE40093
The operating mechanism box includes the function which prohibits the racking in
of the Evolis circuit-breaker, both mechanically or electromechanically.
These functions are achieved using padlocks, keylocks or electrical coil,
(please see the Installation Guide).
Mechanical Electromechanical
interlocking interlocking
Earthing switch operating crank
This is identical to the one supplied for the circuit-breaker racking truck.
It allows the earthing switch to be operated.
It is required for operating the earthing switch.
5
Earthing switch Dimensions
DE40079
DE40063
357
90.2
291 322
DE40080
DE40064
C
A
A
B
B
Operating mechanism
DE40081
207
394
DE40082
206
299
7.2 to 24 kV version
6
Cubicle components Components for operation
DE40089
DE40093
Support insulator
DE40090
DE40091
7
Cubicle components Components for operation
(cont’d)
Electrical characteristics
rated normal current Ir A rms 1250 2500
short-time withstand current Ik/tk kA rms/3s 31.5 40
Electrical characteristics
rated voltage Ur 7.2 to 17.5 kV 24 kV*
Bus section truck phase distance mm 145 185 240 230 250
rated normal current Ir kV rms 1250 1250 2500 1250 2500
short-time withstand current Ik/tk kA rms/3s 25 31.5 40 25 31.5
making capacity kA peak 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
* available 2005
Electrical characteristics
rated voltage Ur kV rms 12 17.5 17.5 24* 24*
Busbar earthing truck phase distance mm 145 185 240 230 250
short-time withstand current Ik/tk kA rms/3s 25 31.5 40 25 31.5
making capacity kA peak 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
* available 2005
Enables the circuit-breaker to be taken out of the cubicle and handled during
maintenance operations or during cubicle manufacturing.
b A device using screws and bolts allows the height adjustment up to 250 mm.
b A latching device is provided between the extraction table and the cradle.
The table support frame can be manufactured by the panel-builder, using a drawing
available in the Installation Guide.
Operating shaft
DE40078
This enables all operations to be carried out on the circuit-breaker racking truck as
well as the earthing switch.
Operating shaft
8
Cubicle components Other components
Door handle
DE40094
b The high resistance plastic windows located on the panel or the door, allows you
to see inside a cubicle.
b Internal arc proof if installed according instructions of the Installation Guide.
High resistance
plastic window
Anticondensation heating resistance
b This can be used for 2 reasons:
DE40096
9
Offer structure Earthing switch
DE40109
Fig.1 Fig.2
Options
Voltage Presence Indication System (VPIS)
voltage presence indicator unit 3.2 kV - 7.2 kV 59498
DE40087
10 kV - 24 kV 59499
Phase comparator
(one per switchboard) 59448
DE40104
Indication
open/closed positions contacts (3 NO - 3 NC) 59502
DE40107
DE40108
2 locks O 59508
2 locks C 59509
electromagnetic (open/close), (fig.2) 24 Vdc 59513
48 Vdc 59514
Fig.1 Fig.2 110 Vdc 59515
220 Vdc 59516
DE40106
DE40098
10
Offer structure Cubicle components
VPIS
voltage presence indicator unit 3.2 kV - 7.2 kV 59498
DE40087
10 kV - 24 kV 59499
Options
phase comparator, (fig.1)
DE40104
DE40070
Fig.1 Fig.2
Other options
Interlocking with the Evolis circuit-breaker position
mechanical interlocking for circuit-breaker 59521
DE40078
DE40106
DE40098
11
Offer structure Cubicle components
(cont’d)
Other components
Bus section truck (with screw/crank device and IEC labels)
Phase distance Ur Ir Ith
DE40111
Extraction table
upper table + 59129
DE40099
VPIS
voltage presence indicator unit 3.2 kV - 7.2 kV 59498
DE40087
10 kV - 24 kV 59499
Insulators
standard insulators 17.5 kV, (fig.1) 59431
DE40115
DE40116
DE40069
DE40100
12
Order form
Options
Operating crank
mandatory with the operating mechanism
(qty: one mini per switchboard)
Installation
Adaptation kit for installation with Evolis cradle 24 kV
Indication
Earthing switch open/closed positions 3 NO - 3 NC
Phase comparator