MV and LV components
Evolis
up to 24 kV

Catalogue

2004

Earthing switch and


cubicle components
General contents

Panorama 2

Earthing switch 4
Description and electrical characteristics 4
Optional functions 5
Dimensions 6

Cubicle components 7
Components for operation 7
Other components 9

Offer structure 10
Earthing switch 10
Cubicle components 11

Order form 13

1
Panorama MV and LV components
DE40061

Electromechanical locking

Mechanical interlocking

Electromechanical interlocking

VPIS
(Voltage Presence
Indicator System)

Earthing switch
operating crank

Open/closed
position
contacts

Mechanical locking
using keys

Power circuit unit

2
Panorama
Cubicle components
DE40062

Fixed coupling link

Busbar connection
cover

Bus section truck

DV2
(kA)
Icu
(V) 100
Ue
220/440 100
525 85
690
85kA/1s
Icw
cat.B
Icu
100%
Ics =

50/60Hz

947-2 NEMA
IEC AS
UNE
EN 60947-2
CEI
BS
VDE
UTE

Busbar earthing truck

Capacitive divider
insulation set

Door handle

Support insulator

Anticondensation
heating resistance

High resistance Circuit-breaker


plastic windows extraction table

3
Earthing switch Description and
electrical characteristics

Function
This device is used to short circuit and earth the cable ends.

Composition
DE40066

DE40065

b The earthing switch includes:


v a power circuit unit with fast acting closing mechanism independent of the operator
v an operating mechanism box to be mounted on the front face of the cubicle
v the link (rod) between the two devices. A drawing defines the installation
conditions which allow the panel builder to design the rod.

Power circuit unit 17.5 kV Power circuit unit 24 kV

Interlocking
DE40067

DE40068

b When associated with Evolis circuit-breaker and cradle, the mechanical interlock
prevents:
v to rack in the circuit-breaker if the earthing switch is closed
v to close the earthing switch if the circuit-breaker is not racked out.
b In case of installation in the NEX cubicle, the mechanical interlock with the front
and/or rear plate of the cable compartment is part of the NEX license.
b In other case the design is under the responsibility of the panel builder.
Operating mechanism box Drawing for the rods

Electrical characteristics according to


DE40071

IEC 62271-102
Mechanical interlock Phase distance mm 160 200 240 240
Rated values
voltage kV rms 7.2 12 7.2 12 17.5 7.2 12 17.5 24
DE40072

frequency fr Hz 50/60
power frequency withstand voltage(1) Ud kV rms 20 28 20 28 38 20 28 38 50
lighting impulse withstand voltage Up kV peak 60 75 60 75 95(2) 60 75 95 125
short-time withstand current 1s Ik kArms-1s 31.5 31.5 50 40 31.5 50 50 40 31.5
short-time withstand current kArms 31.5-4s 31.5-3s
peak wisthstand Ip kA peak 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
short-circuit making current 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
Endurance
mechanical endurance Ur kV rms Mo class (1000 cycles)
electrical endurance E1 class(3)

(1) 42 kV withstand for power circuit unit up to 17.5 kV.


(2) If the 95 kV impulse withstand voltage is required for 200 mm earthing switch phase distance,
it is necessary to add field deflectors on the connections (see Installation Guide for instructions).
(3) Other performances on request.

Interlocking

4
Earthing switch Optional functions

Adaptation kit for installation


DE40073

with Evolis cradle (24 kV)


b The Evolis cradle has been designed in order to allow an easy installation
of the earthing switch underneath the cradle.
Then, an adaptation kit can be supplied, including:
v the mechanical link between the operating mechanism box and
the power circuit unit
v an interface for installation of the box
v the installation notice.
Adaptation kit for Evolis cradle 24 kV
Voltage Presence Indicator System (VPIS)
DE40074

b The VPIS, combined with the capacitive divider insulators of the power circuit unit,
provides an indication by lights of the voltage presence on each phase of the main
circuit.
b The voltage presence indicator unit is installed on the front of the earthing switch
Voltage presence indicator unit operating mechanism box.
b The voltage presence indicator unit covers two voltage ranges, in accordance
with standard IEC 61958:
v 3.2 to 7.2 kV
v 10 to 24 kV.

Open/closed position contacts


DE40075

A serie of 6 auxiliary contacts indicates the open/closed position of


the earthing switch.
Characteristics
Supply Breaking capacity
V AC 250 cos ϕ = 1 16 A
cos ϕ = 0.3 6A
Open/closed position contacts V DC 48 cos ϕ = 1 2.7 A
220 cos ϕ = 1 0.3 A

Mechanical locking of the earthing switch


DE40076

DE40071

This function enables the earthing switch to be locked in its open or closed position
by adding 1 or 2 key locks.
b The option includes mechanical adaptation kit. Keylocks are not supplied
b Three configurations are available:
v locked closed by 1 key lock + locked open by 1 key lock
v locked closed by 2 key locks
v locked open by 2 key locks.
Mechanical locking of the
earthing switch using keys

Electromechanical locking of
DE40077

the earthing switch


This function is achieved using a coil which blocks switching operation when not
energised. When energised it allows operation of the earthing switch.
This system is available in several versions according to the supply voltage:
24 VDC - 48 VDC - 110 VDC - 220 VDC.

Electromechanical locking
of the earthing switch
Mechanical and electromechanical
interlockings with Evolis circuit-breaker
DE40092

DE40093

The operating mechanism box includes the function which prohibits the racking in
of the Evolis circuit-breaker, both mechanically or electromechanically.
These functions are achieved using padlocks, keylocks or electrical coil,
(please see the Installation Guide).
Mechanical Electromechanical
interlocking interlocking
Earthing switch operating crank
This is identical to the one supplied for the circuit-breaker racking truck.
It allows the earthing switch to be operated.
It is required for operating the earthing switch.

5
Earthing switch Dimensions

Power circuit unit


357

DE40079

DE40063
357

90.2

291 322

DE40080

DE40064
C
A
A

B
B

7.2 to 17.5 kV version 24 kV version

Phase distance (mm) 160 200 240 240


Rated voltage (kV) 12 17.5 17.5 24
Dimensions (mm)
A 530 660 860 783
B 270 335 435 407
C 506 636 836 744

Operating mechanism
DE40081

207

394
DE40082

206

299
7.2 to 24 kV version

6
Cubicle components Components for operation

Voltage Presence Indicator System (VPIS)


DE40074

(in case of no earthing switch)


The VPIS system allows to control the voltage presence on each phase of the main
circuit. It can be provided as an option with the earthing switch, (see description
page 5).
Voltage presence
indicator unit
However, this system can also be installed when there is no earthing switch.
Then it includes:
b a set of three capacitive divider insulators, which:
DE40088

DE40089

v provide mechanical support and insulation up to 17.5 kV or 24 kV


v integrate capacitors able to supply a voltage signal;
b a voltage presence indicator unit with lights connected to the capacitor signal to
indicate the voltage presence on each phase. This indicator covers two voltage
ranges, in accordance with standard IEC 61958:
b 3.2 to 7.2 kV
b 10 to 24 kV.
Capacitive divider Capacitive divider The voltage presence indicator unit can be installed on the front of the cubicle.
insulator up to 17.5 kV insulator up to 24 kV

VPIS and mechanical and electromechanical


DE40092

DE40093

interlockings with the Evolis circuit-breaker


b In addition to the VPIS function above described, an interlocking feature with Evolis
circuit-breaker is available.
When these 2 functions are required, they can be installed in a specific box to be
mounted on the front of the cubicle. (This box is similar to the operating mechanism
Mechanical Electromechanical box of the earthing switch, partially equipped).
interlocking interlocking
b The interlocking is achieved using padlocks, keylocks or electrical coil (please see
the Installation Guide).

Support insulator
DE40090

DE40091

b This enables mechanical support and insulation up to 17.5 or 24 kV.


Application for busbar and cable fixing support.

Support insulator Support insulator


up to 17.5 kV up to 24 kV

7
Cubicle components Components for operation
(cont’d)

Fixed coupling link (7.2 to 17.5 kV)


DE40083

This device can be used in a busbar riser cubicle.


b This offer is exclusively available as drawings proposed in the Installation Guide.
b This unit comprises 1 bridge/phase and is easily installable by the operator on the
cradle bushing.

Electrical characteristics
rated normal current Ir A rms 1250 2500
short-time withstand current Ik/tk kA rms/3s 31.5 40

Fixed coupling link


Bus section truck
This device can be used in a busbar riser cubicle, and allows the disconnection
DE40084

between the upstream and downstream circuit of the cubicle.


It is installed in the same location as the withdrawable circuit-breaker in the cradle.
b It includes a device to lock it in the service position.

Electrical characteristics
rated voltage Ur 7.2 to 17.5 kV 24 kV*
Bus section truck phase distance mm 145 185 240 230 250
rated normal current Ir kV rms 1250 1250 2500 1250 2500
short-time withstand current Ik/tk kA rms/3s 25 31.5 40 25 31.5
making capacity kA peak 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
* available 2005

Busbar earthing truck


DE40085

This device is a safety accessory used in place of the withdrawable circuit-breaker


in order to earth the busbars.
b Possibility of locking by padlocks in the service position.

Electrical characteristics
rated voltage Ur kV rms 12 17.5 17.5 24* 24*
Busbar earthing truck phase distance mm 145 185 240 230 250
short-time withstand current Ik/tk kA rms/3s 25 31.5 40 25 31.5
making capacity kA peak 2.5 Ik (50 Hz) & 2.6 Ik (60 Hz)
* available 2005

Circuit-breaker extraction table


DE40086

Enables the circuit-breaker to be taken out of the cubicle and handled during
maintenance operations or during cubicle manufacturing.
b A device using screws and bolts allows the height adjustment up to 250 mm.
b A latching device is provided between the extraction table and the cradle.
The table support frame can be manufactured by the panel-builder, using a drawing
available in the Installation Guide.

Circuit-breaker extraction table

Operating shaft
DE40078

This enables all operations to be carried out on the circuit-breaker racking truck as
well as the earthing switch.

Operating shaft

8
Cubicle components Other components

Door handle
DE40094

b Enables the front panel door of the cubicle to be closed.


Several versions are available:
v with a triangular keylock
v with Ronis or Profalux type key lock.
Door handle

High resistance plastic windows


DE40095

b The high resistance plastic windows located on the panel or the door, allows you
to see inside a cubicle.
b Internal arc proof if installed according instructions of the Installation Guide.

High resistance
plastic window
Anticondensation heating resistance
b This can be used for 2 reasons:
DE40096

v heating the cubicle when the ambient temperature is too low


Anticondensation v avoiding the formation of condensation.
heating resistance b Supplied with its support without a thermostat.

Busbar connection cover


b This set of 3 insulating covers enables improved dielectric withstand at the busbar
DE40097

connections in the cubicle.


The shape must be cut locally according to the type of busbar.

Busbar connection cover

9
Offer structure Earthing switch

For cost calculation you must add b The power circuit


b The operating mechanism
b The options
Power circuit
Phase distance Ur Ith
DE40101

160 mm 12 kV 31.5 kA .4 s 59490


200 mm 7.2 kV 50 kA .1 s 59491
or 12 kV 40 kA .1 s
or 17.5 kV* 31.5 kA .4 s
240 mm 12 kV 50 kA .1 s 59492
or 17.5 kV 31.5 kA .4 s
or 17.5 kV 40 kA .1 s
24 kV 31.5 kA .4 s AAA10071
3 field deflectors 59281
DE40110

(*) mandatory if Ur = 17.5 kV - 95 kV peak


for E.S. 200 mm phase distance
Operating mechanism
operating mechanism box, (fig.1) 59496
DE40102

DE40109

operating crank, (fig.2) 59449


mandatory with the operating mechanism
(quantity: one mini per switchboard)

Fig.1 Fig.2
Options
Voltage Presence Indication System (VPIS)
voltage presence indicator unit 3.2 kV - 7.2 kV 59498
DE40087

10 kV - 24 kV 59499

Phase comparator
(one per switchboard) 59448
DE40104

Indication
open/closed positions contacts (3 NO - 3 NC) 59502
DE40107

Locking of the earthing switch


mechanical by locks, (fig.1) 1 lock O + 1 lock C 59506
DE40106

DE40108

2 locks O 59508
2 locks C 59509
electromagnetic (open/close), (fig.2) 24 Vdc 59513
48 Vdc 59514
Fig.1 Fig.2 110 Vdc 59515
220 Vdc 59516

Interlocking with Evolis circuit-breaker position


mechanical interlocking for circuit-breaker 59521
DE40078

DE40106

DE40098

in racked out position, (fig.1)


interlocking Profalux by lock 59523
(locks not supplied), (fig.2)
electromagnetic interlocking 24 Vdc 59526
Fig.1 Fig.2 Fig.3 for circuit-breaker in racked out position, (fig.3) 48 Vdc 59527
110 Vdc 59528
220 Vdc 59529

Adaptation kit for Evolis cradle 24 kV


adaptation kit for Evolis cradle 24 kV AAA10073
DE40070

10
Offer structure Cubicle components

Voltage Presence Indication System - VPIS (without earthing switch)

For cost calculation you must add b Box support VPIS


b VPIS
b 3 capacitors divider insulators with a support
b 3 field deflectors if necessary
b Options
Box support VPIS
box support interlockings with VPIS 59497
DE40103

VPIS
voltage presence indicator unit 3.2 kV - 7.2 kV 59498
DE40087

10 kV - 24 kV 59499

3 capacitors divider insulators with a support


Phase distance Ur
DE40105

160 mm 7.2 - 17.5 kV 59487


200 mm 7.2 - 17.5 kV* 59488
240 mm 7.2 - 17.5 kV 59489
240 mm 24 kV AAA10072

3 field deflectors to be fitted on insulator connections


(*) mandatory if Ur = 17.5 kV - 95 kV peak 59281
DE40110

for E.S. 200 mm phase distance

Options
phase comparator, (fig.1)
DE40104

DE40070

(one per switchboard) 59448


adaptation kit for Evolis cradle 24 kV, (fig.2) AAA10073

Fig.1 Fig.2
Other options
Interlocking with the Evolis circuit-breaker position
mechanical interlocking for circuit-breaker 59521
DE40078

DE40106

DE40098

in racked out position, (fig.1)


interlocking Profalux by lock 59523
(locks not supplied), (fig.2)
electromagnetic interlocking 24 Vdc 59526
Fig.1 Fig.2 Fig.3 for circuit-breaker in racked out position, (fig.3) 48 Vdc 59527
110 Vdc 59528
220 Vdc 59529

11
Offer structure Cubicle components
(cont’d)

Other components
Bus section truck (with screw/crank device and IEC labels)
Phase distance Ur Ir Ith
DE40111

145 mm 7.2-17.5 kV 1250 A 25 kA 59476


185 mm 7.2-17.5 kV 1250 A 31.5 kA 59477
240 mm 7.2-17.5 kV 2500 A 40 kA 59478
230 mm 24 kV 1250 A 25 kA AAA10061
250 mm 24 kV 2500 A 31.5 kA AAA10062
Busbar earthing truck (with screw/crank device and IEC labels)
Phase distance Ur Ir Ith
DE40112

145 mm 7.2-17.5 kV 1250 A 25 kA 59473


185 mm 7.2-17.5 kV 1250 A 31.5 kA 59474
240 mm 7.2-17.5 kV 2500 A 40 kA 59474
230 mm 24 kV 1250 A 25 kA AAA10063
250 mm 24 kV 2500 A 31.5 kA AAA10064

Extraction table
upper table + 59129
DE40099

complete device drawing


complete extraction table 59130

Operation crank common to earthing switch and circuit-breaker racking


operation crank 59449
DE40109

Busbar connection cover


busbar cover 59420
DE40113

VPIS
voltage presence indicator unit 3.2 kV - 7.2 kV 59498
DE40087

10 kV - 24 kV 59499

Insulators
standard insulators 17.5 kV, (fig.1) 59431
DE40115

DE40116

DE40069

DE40100

capacitor divider insulator set 17.5 kV, (fig.2) 59430


standard insulators 24 kV, (fig.3) AAA10075
capacitor divider insulator set 24 kV, (fig.4) AAA10074

fig.1 fig.2 fig.3 fig.4


Phase comparator
phase comparator 59448
DE40104

High resistance plastic windows


1 sight window (transparent screen) 59105
DE400114

Cubicle compartment handles


handle 59270
DE40017

handle with key 59271

Anticondensation heating resistance


heating resistance 59280
DE40018

12
Order form

Only one of the boxes (ticked or filled by Basic earthing switch


the needed value) have to be considered
between each horizontal line. Quantity
Blue box corresponds to none priced functions. Rated voltage Ur 24 kV
Rated voltage Ur 7.2 kV 12 kV 17.5 kV

if Ur < 24 kV fill below


Phase distance 160 mm 200 mm 240 mm
please refer to characteristic table below
3 field deflector for ES
mandatory if Ur: 17.5 kV - 95 kV peak
with 200 mm phase distance

Options
Operating crank
mandatory with the operating mechanism
(qty: one mini per switchboard)

Installation
Adaptation kit for installation with Evolis cradle 24 kV

Indication
Earthing switch open/closed positions 3 NO - 3 NC

Locking/interlocking (locks Profalux are not supplied by Schneider Electric)


Open/closed positions
mechanical by locks 1 lock O - 1 lock C 2 locks O 2 locks C
electromagnetic 24 Vdc 48 Vdc 110 Vdc 220 Vdc

Locking/interlocking for circuit-breaker fitted on E.S.


Open/closed positions
mechanical circuit-breaker withdrawable position locking
electromagnetic 24 Vdc 48 Vdc 110 Vdc 220 Vdc
interlocking Profalux by lock (locks not supplied)

Phase comparator
one phase comparator per switchboard is enough

Earthing switch characteristics table


Phase distance mm 160 200 240 240
voltage kV rms 7.2 12 7.2 12 17.5 7.2 12 17.5 24
lighting impulse withstand voltage Up kV peak 60 75 60 75 95 60 75 95 125
short-time withstand current 1s Ik kArms-1s 31.5 31.5 50 40 31.5 50 50 40 31.5

13
Note

14
Note

15
Note

16
AMTED304001EN_COUV.fm Page 1 Mardi, 6. avril 2004 9:45 09

AMTED304001EN © 2004 Schneider Electric - All rights reserved

Schneider Electric Industries SAS


Postal address As standards, specifications and designs change from time to time, please ask for confirmation of
MV department the information given in this publication.