Professional Documents
Culture Documents
1 Introduction.................................................................................................................3
2 Connections.................................................................................................................4
2.1 Power supply........................................................................................................................ 4
2.2 Connection to the serial interface of the PC via null-modem-cable (COM 1) .................................... 4
2.3 Ethernet PC interfacing ........................................................................................................... 4
3 Preparing the Hardware .............................................................................................6
3.1 Assigning an IP address to the Com-Server ................................................................................. 6
3.1.1 How to start and adjust the terminal programs ...................................................................... 6
3.1.2 Connection set-up ........................................................................................................... 6
3.1.3 Setting of the IP-address.................................................................................................... 8
3.1.4 Checking of the IP address allocated to the COM-Server. ....................................................... 9
3.1.4.1 Checking of the IP adress of the PC .............................................................................. 9
3.1.4.1.1 Checking the IP-adress on a Windows 98 - System ................................................... 9
3.1.4.1.2 Checking the IP-adress on a Windows 2000 System............................................... 10
3.1.4.2 Notification of the COM-Server IP-address ................................................................... 11
3.1.4.3 Test with the ping command...................................................................................... 11
3.2 Parameter assignment for the serial interface ............................................................................. 12
3.2.1 Start of the Telnet configuration ........................................................................................ 12
3.2.1.1 Start of Telnet in WIN98.......................................................................................... 12
3.2.1.2 Start of Telnet in WIN2000...................................................................................... 13
3.2.1.3 Adjustment of the serial interface ................................................................................ 13
4 Hardware Unit - Installation ....................................................................................17
4.1 Power supply...................................................................................................................... 17
4.2 Connection of the COM Server to the serial interface of the CMW ............................................... 17
4.3 Connection of the COM Server to Ethernet............................................................................... 17
5 Integration Test .........................................................................................................18
2 td_com-server-installation_rev10_07gb
1 Introduction
COM-Server
Model #58611 and Model #58631, make Wiesemann & Theis GmbH
CONCYCLE®-Wind-Inverters type CONCYCLE® is increasingly used in wind farms which have their own
infrastructure for communication purposes. The TCP/IP protocol via Ethernet is the most commonly used one for
cross-linkage within wind farms. In such wind farms where CONCYCLE®-Wind Inverters are used, a so called
COM-Server can be employed for communicating with the outside world instead of a modem.
The COM-Server is a protocol-converter which converts signals from a serial RS232 interface to an ethernet-
based TCP/IP-signal. The COM-Server is a gateway permitting to parcel data, which are sent via serial
interface, into TCP/IP and then to transfer them via an Ethernet interface and vice versa.
The COM-Server is connected to the serial interface of the CMW and transfers the data into the TCP/IP network
of the wind farm. Most TCP/IP-networks can be accessed via TCP/IP from outside. By means of the
“SEG_SerialToTCP/IPServer” users are able to login into the wind farm and then to approach the connected
Wind Energy Systems (WES) by their IP addresses.
In order to ensure a reliable operation, the COM-Server should be correctly installed/configured. This includes
setting up/allocating the IP address in the COM-Server and adjustment of the serial interface parameters of the
COM-Server. The relevant procedure is described in here step by step.
The servers need to be configured because their present default setting differs from the setting used by
Woodward SEG.
td_com-server-installation_rev10_07gb 3
2 Connections
Connecting of the PC Ethernet card to the Ethernet interface connection of the COM-Servers either:
4 td_com-server-installation_rev10_07gb
COM
Ethernet cross over patch
-
Ser-
ver
null modem cable
COM1
Windows-PC
24V-
power supply
Hub
COM
-
Ethernet Ser-
ver
null modem cable
COM1
Windows-PC
24V-
power supply
LAN segment
COM
-
Ethernet Ser-
ver
null modem cable
COM1
Windows-PC
24V-
power supply
td_com-server-installation_rev10_07gb 5
3 Preparing the Hardware
Each unit which can be approached via the TCP/IP must be given a distinct IP-address. This IP-address must be
assigned by the wind farm manufacturer.
A recommended segment for IP addresses in local networks is, for instance,
192.168.yyy.xxx.
The address setting-up procedure for the COM-Server is described in the following chapters. It is also possible to
change the IP address later on, irrespectively of the other settings.
For connecting the PC with the COM server the provided cable COM-Mita-CMW-6M or a suitable zero-modem
cable can be used.
6 td_com-server-installation_rev10_07gb
Direct connection via COM 1
O.K
Confirm by O.K.
Afterwards the Hyper-Terminal will be started and the connection will be established
td_com-server-installation_rev10_07gb 7
3.1.3 Setting of the IP-address
Enter the IP address in the standard format (xxx.xxx.xxx.xxx) and finish the input with <Enter>. If the input was
accepted this is acknowledged by the allocated IP address. If this is not the case, „FAIL“ is indicated and
followed by the last IP address.
If the connection is established successfully, this entry can be seen in the task bar. Should the Flow control:
“none” does not work, the corresponding setting has to be changed over to “hardware”.
After the assignment of the new IP-Adress the hyperterminal program could be left.
8 td_com-server-installation_rev10_07gb
3.1.4 Checking of the IP address allocated to the COM-Server.
td_com-server-installation_rev10_07gb 9
3.1.4.1.2 Checking the IP-address on a Windows 2000 System
10 td_com-server-installation_rev10_07gb
3.1.4.2 Notification of the COM-Server IP-address
Because normally unfamiliar IP addresses, that is not called the network associated IP address, are sent to a
gateway by the PC, the “unfamiliar” address has to be notified to the PC as an exception by command „route“
in the DOS-Box.
route add <ip address of COM-Server> mask 255.255.255.255 <ip address of PC>
Here:
In this example:
ping 192.168.0.10
The ping command gives back a response time of several [ms] if the connection can be established. Otherwise a
timeout occurs.
td_com-server-installation_rev10_07gb 11
3.2 Parameter assignment for the serial interface
All further COM-Server adjustments are to be carried out by the internet protocol „Telnet“.
For configuration of the COM-Server the network protocol Telnet is used. Telnet allows to access the COM
Server through a plain terminal emulation. The COM Server is allocated a valid IP address in that network and
by this the server can be addressed (see chapter „Assignment Of The IP Address“). The configuration can virtually
be carried out from any computer linked to a network and with TCP/IP-Stack. The Program telnet.exe is part of
the standard delivery scope of Windows 9x/NT/2000.
When using this version call “Run” in the start menu and click OPEN to enter “telnet”, then click O.K.
Thereafter enter the IP address of the COM-Server as hostname in submenu “Network System….” of menu
“Connection” and enter port number “1111” as connection.
12 td_com-server-installation_rev10_07gb
3.2.1.2 Start of Telnet in WIN2000
By using the following parameters call the Telnet client for selecting the configuration menu:
Aided by a simple menu, presented by the COM Server in the Telnet window, the serial interface of the COM
Server (the UART) is configured as follows:
- 19200 baud
- none parity
- 8 data bit
- 1 stop bit
- none handshake.
- FiFos off
These attitudes are to be kept absolutely, since otherwise the Login does not function.
td_com-server-installation_rev10_07gb 13
The menu entries necessary for model #58631 are shown on the following Screen-Shoots
14 td_com-server-installation_rev10_07gb
For checking or correction of the settings the following options could be used – shown in the following screen
Shots for the Model #58631.
td_com-server-installation_rev10_07gb 15
If all the settings are done, they have to be saved as shown in the following screenshot.
16 td_com-server-installation_rev10_07gb
4 Hardware Unit - Installation
For installing into the equipment the COM Server is to be placed on a top hat rail near the CMW.
4.2 Connection of the COM Server to the serial interface of the CMW
The serial interface of the COM Server (9-pole D-Sub, named „Serial Port“) is to be connected to the serial
interface of the CMWs (9-pole D-Sub, named „RS232“) by using the cable provided.
Ethernet-Hub or switch to be connected via 1:1 cable to the „Network“ RJ45 socket.
Maximum length of cable = 100m
td_com-server-installation_rev10_07gb 17
5 Integration Test
When the connection has been completed correctly and the Hub/Switch is ready to operate, the red Error-LED
does not flash.
For the test purpose it is sufficient to establish a connection between a PC with Woodward SEG Tools (customer
tool or master tool) and TCP/IP Socket Server and the CSC.
The integration can be considered successful when the connection to the CSC via the COM Server is possible.
18 td_com-server-installation_rev10_07gb
td_com-server-installation_rev10_07gb 19
This description is temporary only and is subject to updating without previous notice.
For any queries please contact us under:
Internet
Homepage http://www.woodward-seg.com
Sales
Phone: +49 (0) 21 52 145 351
Telefax: +49 (0) 21 52 145 468
Service
Phone: +49 (0) 21 52 145 397/398 ⋅ Fax: +49 (0) 21 52 145 347
e-mail: service-kempen@woodward.com
20 td_com-server-installation_rev10_07gb