You are on page 1of 36

Bagan ini tidak tersedia dalam versi Excel Anda.

Mengedit bentuk ini atau menyimpan buku kerja ini ke dalam format file
yang berbeda akan merusak bagan secara permanen.

Here are 10 tips that will lower your compressed air costs.
1. Analyze air consumption

Typically, only half of generated compressed air is used for the intended process. The other
half is depleted by artificial demand, inappropriate use and leaks. Artificial demand is created
when there are extra margins on sizing compressed air systems in terms of flow or pressure
requirement. It can account for about 10% to 15% of compressed air consumption, which
translates into wasted money.

You also should check your operation for potentially inappropriate uses of compressed air such
as open blowing, personnel cooling, cabinet cooling or air motors. Some of these applications,
including cabinet cooling, liquid agitation or stirring and vacuum generation, can be served
more efficiently by a fan, blower or vacuum pump, all of which consume less energy than air
compressors. Knowing where your air goes is the first step toward developing an action plan to
reduce unnecessary compressed air consumption.

2. Inspect distribution
Inspecting your distribution means checking for leaks and assessing your pipe sizing. Both leaks
and incorrectly sized pipes can result in unwanted pressure drops, causing your compressed air
system to work harder and consume more energy. In some systems, leaks account for 20% to
30% of air consumption. Let’s take a look at some calculations and examples to understand the
impact of distribution inefficiencies.

Leaks: At 80 psig, a leak through a 1/16-inch hole consumes about 5.24 cfm. When the
pressure moves to 125 psig, that number jumps to 7.66 cfm. This 46% increase in wasted air
can compound energy costs quickly, so leaks should be identified and addressed as quickly as
possible.

While some larger leaks can be heard in a system walk, an audit is the best way to ensure all
leaks are found. Ultrasonic leak detectors are available to find minute leaks, but an ongoing
identification program involving all personnel is the most effective practice.

Pipe sizing and configuration: Pipe sizing may seem like a small factor, but it can have a big
impact on pressure. For example, suppose a plant experiencing low pressure generates 400
cfm while running at 100 psig with pipes that are two inches in diameter. To compensate for
the low pressure, the operator considers purchasing a new, larger compressor. Is this a good
solution? Probably not. Increasing the pipe size from two inches to three inches and creating a
closed-loop system reduced the pressure drop from 12 psi to 1 psi without a new compressor.
Another way to avoid air pressure drops associated with piping and configuration is to just say
no to long hoses. Minimizing the use of hoses and frequently inspecting fittings can preserve
line pressure without forcing the compressor to work harder than necessary.

3. Reduce pressure

It’s common to find systems running at a high pressure to satisfy the needs of only one point
of use. However, this can waste large volumes of compressed air, especially when the pressure
needs of different end uses are highly disparate. To avoid generating unnecessary amounts of
compressed air, try using a separate compressor or booster. That way, the rest of your system
can continue to operate at a lower pressure, reducing leakage and usage rates and ultimately
decreasing overall energy consumption.
These savings can add up. Every additional 2 psi increases energy costs by about 1%. But
before you buy a separate compressor, try a few simple checks:
Assess the validity of compressor control settings.
Look for pressure drops through dryers, filters and piping systems.
Determine if you have artificial demand.

4. Ensure air receiverus are used properly

Air receiver sizing and placement are crucial to lowering compressed air costs. Air receivers
play a vital role in the compressed air process. They store compressed air prior to end use and
serve as a buffer between the compressor and system, modulating pressure variation that may
happen during compression.

The Compressed Air and Gas Institute (CAGI) recommends four to five gallons per cfm. For
installation with multiple compressors, the air receiver should be based on the size of the trim
compressor.
Ensuring your air receiver is in the right location is another way to lower your compressed air
costs. Some operators decide to install an air receiver before the compressed air dryer. This
can be beneficial to the dryer, as the receiver may provide radiant cooling that removes some
of the condensate and entrained oil. However, the receiver will be filled with saturated air. If
there is a sudden demand that exceeds the compressor and dryer capacity rating, the dryer
can become overloaded, leading to a higher pressure dew point.

Installing the receiver after the dryer doesn’t provide the same advantages, but it does store
clean, dry air. Any sudden demand occurring in this situation will be met with dry air. The best
proactive air receiver placement is to have two receivers on the supply side: one "wet"
receiver before the dryer to provide control storage and condensate dropout and a second
"dry" air receiver to meet sudden demand. 

5. Control multiple compressor systems effectively

When designing a multiple compressor system, a good way to save money is to base load as
many compressors as possible. Multiple compressor control can optimize the running cost
because you are selecting which compressor to run at a specific load based on plant flow
demand.

It can also reduce the compressor operating pressure band (remember, 2 psi increases the
energy consumption by 1%). If you have VSD and a centrifugal compressor in the system,
multiple compressor controls will keep the VSD compressor and centrifugal compressor in an
optimum zone, minimizing compressed air blow-off.

6. Choose the right dryer and filter

The process of drying compressed air is often misunderstood, which results in inefficiently
pieced together systems that waste energy and money. We often get questions regarding
dryer and filter selection, such as:
Should I get a desiccant or refrigerant dryer?
What level of filtration do I need?
Do I need all these filters, regulators and lubricants?

Regardless of the question, the answer is almost always the same: it depends on your
application. However, there are a few universal tips to follow when using dryers and filters
that can help reduce compressed air costs:
Do not dry compressed air more than the application requires. This is unnecessary and wastes
money.
Consider initial drying with a refrigerant-type dryer, then dry further only to meet point-of-use
requirements.

Every filter causes a pressure drop, which costs money. Don’t filter more than necessary.

7. Remove condensate with no-loss drains

Compressors make a lot of water. You need a way to safely and efficiently remove it from your
system to avoid turning your compressed air pipes into water pipes. Manual drains should not
be used, because they rely on a maintenance team who may have other priorities.
When left open, manual drains can waste expensive amounts of compressed air.
Timer drains present a similar issue, and both types of drains may not work properly on a
humid day.

Instead, opt for drain traps that sense the presence of condensate and drain it without the loss
of compressed air. You should always inspect drain traps regularly and repair as needed.

8. Recover heat

Heat is always a byproduct of air compression. In fact, you can recover almost 90% to 95% of
heat from certain compressors. A radiator-cooled unit can provide air for space heating in a
building, and a water-cooled unit can produce hot water for plant use. Instead of directing hot
compressor outside or discarding the hot water, use these resources to power your facility to
save money.

9. Measure and monitor air use

Keeping track of your compressed air consumption can offer important insights. From
informing maintenance practices to prompting energy saving initiatives, it’s always good to
know what’s happening in your system. Doing so will not only prevent serious issues from
going unnoticed, it will also help your plant find ways to continuously improve efficiency.
There are seven important things to keep in mind regarding monitoring:
1. Establish a baseline of your system before making any changes.
2. Establish a benchmark of energy consumption against rate of production.
3. Record any system changes and resulting energy savings.
4. Record maintenance data and trends.
5. Record operating pressures at strategic points in the system, as these changes can reveal
problem areas.
6. Review the impact of new production machines.
7. Analyze low pressure at point of use; this could signal a system problem rather than a need
for a new compressor.

Mapping your system is a helpful starting point. This could be done by plant personnel or
through a compressed air audit. The latter can offer deeper insights into the system’s
functionality and reveal changes that would improve the current system. Another way to keep
an eye on your compressors is through a remote monitoring system, which can show where
compressed air is going, where pressure drops occur and how much energy the system is
using.

10. Select the right compressor

Selecting the right compressor for your operation is paramount. While there are many options,
it’s important to understand the different types of compressors and the cost advantages they
offer. Every technology has its unique advantage based on the plant demand and application.

VSD: Because it adjusts to meet demand, this compressor is good for trim applications.
Oil-free: Oil-free compressors are ideal for sensitive applications like food, beverage and
pharmaceutical processing.
Centrifugal: These dynamic compressors are large and produce high flows, making them good
base load compressors for large production industries, such as semiconductor production.
Piston: Piston compressors are frequently small and portable, making them perfect for
automotive and other shop applications.

Don’t purchase a compressor without first researching which best fits your application,
pressure and capacity needs. Examining your options up front will save you money down the
line.

These tips are just the beginning. Implementing energy and cost-saving practices takes time
and ongoing commitment. By adhering to the above practices, your facility can save significant
amounts of energy-and money.
L1 Loading Time (mnt) Usage (kWh) Total Usage (kWh)
Kitchen 47.1 1,154.0
Filling 2.24 54.9
1470 1,768.2
Cooling 14.93 365.8
Packing 7.9 193.6

L2 Loading Time (mnt) Usage (kWh) Total Usage (kWh)


Kitchen 47.1 1,154.0
Filling 2.24 54.9
1470 1,768.2
Cooling 14.93 365.8
Packing 7.9 193.6

L3 Loading Time (mnt) Usage (kWh) Total Usage (kWh)


Kitchen 25.95 635.8
Filling 1.9 46.6
1470 1,619.0
Cooling 23.55 577.0
Packing 14.68 359.7

L4 Loading Time (mnt) Usage (kWh) Total Usage (kWh)


Kitchen 25.95 635.8
Filling 2.65 64.9
1470 1,474.4
Cooling 20.15 493.7
Packing 11.43 280.0

L5 Loading Time (mnt) Usage (kWh) Total Usage (kWh)


Kitchen 27.75 679.9
Filling 2.65 64.9
1470 1,429.1
Cooling 16.15 395.7
Packing 11.78 288.6

L6 Loading Time (mnt) Usage (kWh) Total Usage (kWh)


Kitchen 177.2 4,341.4
Filling 6 147.0
Cooling 16.9 1470 414.1 5,225.4
Packing 13.18 322.9
Palletizer 3.23 79.1

Sugar dissolved Loading Time (mnt) Usage (kWh) Total Usage (kWh)
Existing motor 28.7 1470 703.2 703.2

Utility Loading Time (mnt) Usage (kWh) Total Usage (kWh)


WT 108.5 2,657.8
WWTP 80.0 1,961.1
Boiler Thermax - -
Boiler Alstom - -
Boiler TWA 70.5 1,727.3
LP Comp 282.0 6,909.0
1470 21,061.4
Abs Chiller - 1470 - 21,061.4
Chiller (aircool) 21.9 537.0
Chiller (watercool) 22.0 539.0
HVAC 116.0 2,842.0
Air Fresh 59.0 1,445.5
CT L1-L5 70.3 1,722.4
CT L6 & L7 29.4 720.3

Bagan ini tidak tersedia dalam versi Excel Anda.

Mengedit bentuk ini atau menyimpan buku kerja ini ke dalam format file yang
berbeda akan merusak bagan secara permanen.
Loading Time
Jam Menit
KWh
24.5 1470

35,049

L1 1,768.2 4.4%
L2 1,768.2 4.4%
L3 1,619.0 4.0%
L4 1,474.4 3.7%
L5 1,429.1 3.5%
L6 5,225.4 13.0%
L7 5,225.4 13.0%
Sugar dissolved 703.2 1.7%
Utility 21,061.4 52.3%
40,274.0
LIST DATA KAPASITAS MOTOR LINE 1

Area NO. Nama Beban Jml KW / Unit Status Eff KWH Total
Hot Water Tank 1 Motor Pompa Transfer 1 4 On 1 4.0
2 Motor Agitator Premix 1 5.5 On 1 5.5
3 Motor Pump premix 1 2.2 On 1 2.2
4 Motor Agitator Mixing tank 1 11 On 1 11.0
5 Motor Pompa mixing tank 1 2.2 On 1 2.2
COOKING
6 Motor Holding tank 1 4 On 1 4.0
7 Motor Agitator Holding Tank 1 4 On 1 4.0
8 Pompa Tandon Gula 1 2.5 On 1 2.5
9 Motor Pompa Holding Tank 1 2.2 On 1 2.2
10 Motor Pompa Produk 1 4 On 1 4.0
HTST 1
11 Pompa sirkulasi Hot water 1 5.5 On 1 5.5
12 Motor Roll Sampah Seal 1 0.75 On 1 0.8
FILLING
13 Motor servo 1 1.49 On 1 1.5
14 Motor IJP Cup 1 1 0.2 On 1 0.2
15 Motor Conveyor cooling batch 1 2.98 On 1 3.0
COOLING
16 Motor Blower 1 0.75 On 1 0.8
17 Motor Cooling Batch 1 11 On 1 11.0
18 Motor extraktor 1 1 1.5 On 1 1.5
19 Motor extraktor 2 1 1.5 On 1 1.5
20 Motor Rotary packing 1 0.4 On 1 0.4
21 Motor conveyor modular 1 0.55 On 1 0.6
PACKING
22 Motor Servo Driving 1 1.5 On 1 1.5
23 Motor conveyor 1HP 1 0.75 On 1 0.8
24 Motor Carton Sealer 1 1 1.5 On 1 1.5
25 Motor IJP Dus 1 1 0.2 On 1 0.2
TOTAL KAPASITAS 25 72.17 72.2
129.00492639
SISTEM START MOTOR
On
INVERTER Off

INVERTER

INVERTER 47.1 84.19194

2.2

STAR DELTA 14.9

7.9
LIST DATA KAPASITAS MOTOR LINE 2

Area NO. Nama Beban Jml KW / Unit Status Eff KW Total


Hot Water Tank 1 Pompa Transfer 1 4 On 1 4.0
2 Agitator Premix 1 5.5 On 1 5.5
3 Pump premix 1 2.2 On 1 2.2
4 Agitator Mixing tank 1 11 On 1 11.0
5 Pompa mixing tank 1 2.2 On 1 2.2
COOKING
6 Holding tank 1 4 On 1 4.0
7 Agitator Holding Tank 1 4 On 1 4.0
8 Motor Pompa Tandon Gula 1 2.5 On 1 2.5
9 Pompa Holding Tank 1 2.2 On 1 2.2
10 Pompa Produk 1 4 On 1 4.0
HTST 1
11 Pompa sirkulasi Hot water 1 5.5 On 1 5.5
13 Motor Roll Sampah Seal 1 0.75 On 1 0.8
FILLING
14 Motor servo 1 1.49 On 1 1.5
15 Motor IJP Cup 1 1 0.2 On 1 0.2
16 Motor Conveyor cooling batch 1 2.98 On 1 3.0
COOLING
17 Motor Blower 1 0.75 On 1 0.8
18 Motor Cooling Batch 1 11 On 1 11.0
19 Motor extraktor 1 1 1.5 On 1 1.5
20 Motor extraktor 2 1 1.5 On 1 1.5
21 Motor Rotary packing 1 0.4 On 1 0.4
22 Motor conveyor modular 1 0.55 On 1 0.6
PACKING
23 Motor Servo Driving 1 1.5 On 1 1.5
24 Motor conveyor 1HP 1 0.75 On 1 0.8
25 Motor Carton Sealer 1 1 1.5 On 1 1.5
26 Motor IJP Dus 1 1 0.2 On 1 0.2
TOTAL KAPASITAS 25 72.17 72.2
129.0049
SISTEM START MOTOR
On
INVERTER Off

INVERTER

INVERTER 47.1

2.2

STAR DELTA 14.9

7.9
LIST DATA KAPASITAS MOTOR LINE 3

BASE ON NAME PLATE UNIT


AREA NO. NAMA BEBAN
Jml KW / Unit Status Eff
1 Agitator Mixing Line 3 1 3 On 1
2 Agitator Premix Line 3 1 2 On 1
3 Agitator Holding Tank L3 1 0.55 On 1
COOKING 4 Pompa Transfer Premix L3 1 2.2 On 1
5 Pompa Tandon Gula L3 1 2.2 On 1
6 Pompa Transfer Mixing Ke HT L3 1 4 On 1
7 Pompa Transfer HT Ke HTST L3 1 4 On 1
8 Pompa HTST Inlet Filling 3 1 4 On 1
HTST
9 Pompa Hot water HTST L3 1 4 On 1
10 Conveyor mould 1 1.5 On 1
FILLING
11 Motor Transfering filling 1 0.4 On 1
12 Conveyor mould 1 2 On 1
13 Motor Transfering 1 0.4 On 1
TILTING
14 Motor Spray Mould 1 2.5 On 1
15 Pompa Sirkulasi PHE 1 2.5 On 1
16 Conveyor IJP L3 1 0.4 On 1
17 Conveyor cooling( servo) 1 4 On 1
COOLING
18 Pompa Cooling 1 11 On 1
19 Motor blower Cooling 1 0.75 On 1
20 Motor Tansfering Inlet packing 1 0.4 On 1
21 Conveyor packing L3 1 0.75 On 1
22 Motor Extractor 1 1 1.5 On 1
23 Motor Extractor 2 1 1.5 On 1
24 Motor Rotary packing 1 0.4 On 1
25 Motor conveyor modular 1 0.55 On 1
PACKING
26 Motor Gear Box Belt conveyor errector 1 0.18 On 1
27 Motor Carton sealer Errector 2 0.2 On 1
28 Motor Carton sealer Finish good 2 0.2 On 1
29 Pompa vacum screw 1 4 On 1
30 Motor Pompa Vacum elmo 1 3.5 On 1
31 Motor gear boX Row Matrial 2 0.55 On 1
TOTAL KAPASITAS 34 65.13
LINE 3

ASE ON NAME PLATE UNIT


KW Total SISTEM START MOTOR On
3.0 Off
2.0
0.6
2.2
2.2
4.0
4.0
4.0
4.0 26.0
1.5
0.4 1.9
2.0
0.4
2.5
2.5
0.4
4.0
11.0 STAR DELTA
0.8 23.6
0.4
0.8
1.5
1.5
0.4
0.6
0.2
0.4
0.4
4.0
3.5
1.1 14.7
66.1
118.119
LIST DATA KAPASITAS MOTOR LINE 4

BASE ON NAME PLATE UNIT


AREA NO. UNIT / MACHINE NAME
Jml KW / Unit Status Eff
1 Agitator Mixing Line 4 1 3 On 1
2 Agitator Premix Line 4 1 2 On 1
3 Agitator Holding Tank L4 1 0.55 On 1
COOKING 4 Pompa Transfer Premix L4 1 2.2 On 1
5 Pompa Tandon Gula L4 1 2.2 On 1
6 Pompa Transfer Mixing Ke HT L4 1 2.5 On 1
7 Pompa Transfer HT Ke HTST L4 1 4 On 1
8 Pompa HTST Inlet Filling 4 1 5.5 On 1
HTST
9 Pompa Hot water HTST L4 1 4 On 1
10 Conveyor mould 1 1.5 On 1
FILLING 11 Motor sampah seal 1 0.75 On 1
12 Motor Transfering filling 1 0.4 On 1
13 Pompa Sirkulasi PHE 1 4 On 1
14 Conveyor IJP L3 1 0.4 On 1
COOLING 15 Conveyor cooling 1 4 On 1
16 Motor Blower 1 0.75 On 1
17 Pompa Cooling Batch 1 11 On 1
18 Motor Tansfering Inlet packing 1 0.4 On 1
19 Conveyor Driving 1 1.5 On 1
20 Motor Extractor 1 1 1.5 On 1
21 Motor Extractor 2 1 1.5 On 1
22 Motor Rotary packing 1 0.4 On 1
PACKING 23 Motor conveyor modular 1 0.55 On 1
24 Motor Gear Box Belt conveyor errector 1 0.18 On 1
25 Motor Carton sealer Errector 2 0.2 On 1
26 Motor Carton sealer Finish good 2 0.2 On 1
27 Motor Pompa Vacum elmo 1 3.5 On 1
28 Motor gear boX Row Matrial 2 0.55 On 1
TOTAL KAPASITAS 31 59.23
R LINE 4

BASE ON NAME PLATE UNIT


KW Total SISTEM START MOTOR On
3.0 Off
2.0
0.6
2.2
2.2
2.5
4.0
5.5 INVERTER
4.0 26.0
1.5
0.8
0.4 2.7
4.0
0.4
4.0
0.8
11.0 STAR DELTA 20.2
0.4
1.5
1.5
1.5
0.4
0.6
0.2
0.4
0.4
3.5
1.1 11.4
60.2
107.57262672
LIST DATA KAPASITAS MOTOR LINE 5

BASE ON NAME PLATE UNIT


AREA NO. UNIT / MACHINE NAME
Jml KW / Unit Status Eff
1 Agitator Mixing Line 5 1 3 On 1
2 Agitator Premix Line 5 1 2 On 1
3 Agitator Holding Tank L5 1 0.55 On 1
COOKING 4 Pompa Transfer Premix L5 1 2.2 On 1
5 Pompa Tandon Gula L5 1 4 On 1
6 Pompa Transfer Mixing Ke HT L5 1 2.5 On 1
7 Pompa Transfer HT Ke HTST L5 1 4 On 1
8 Pompa HTST Inlet Filling 5 1 5.5 On 1
HTST
9 Pompa Hot water HTST L5 1 4 On 1
10 Conveyor mould 1 1.5 On 1
FILLING 11 Motor sampah seal 1 0.75 On 1
12 Motor Transfering filling 1 0.4 On 1
13 Conveyor IJP L5 1 0.4 On 1
14 Conveyor cooling( servo) 1 4 On 1
COOLING
15 Motor Blower 1 0.75 On 1
16 Pompa Cooling 1 11 On 1
17 Motor Tansfering Inlet packing 1 0.4 On 1
18 Conveyor packing L4 1 0.75 On 1
19 Motor Extractor 1 1 1.5 On 1
20 Motor Extractor 2 1 1.5 On 1
21 Motor Rotary packing 1 0.4 On 1
22 Motor conveyor modular 1 0.55 On 1
PACKING
23 Motor Gear Box Belt conveyor errector 1 0.18 On 1
24 Motor Carton sealer Errector 2 0.2 On 1
25 Motor Carton sealer Finish good 2 0.2 On 1
26 Motor Pompa Vacum elmo 1 3.5 On 1
27 Motor gear boX Row Matrial 2 0.55 On 1
28 Motor gear boX Finist good 2 0.55 On 1
Kapasitas total: 32.0 56.8
E5

BASE ON NAME PLATE UNIT


KW Total SISTEM START MOTOR On
3.0 Off
2.0
0.6
2.2
4.0
2.5
4.0
5.5 INVERTER
4.0 27.8
1.5
0.8
0.4 2.7
0.4
4.0
0.8
11.0 STAR DELTA 16.2
0.4
0.8
1.5
1.5
0.4
0.6
0.2
0.4
0.4
3.5
1.1
1.1 11.8
58.3
104.2657 amp
LIST DATA KAPASITAS MOTOR LINE 6

BASE ON NAM
AREA NO. NAMA BEBAN
Jml KW / Unit
HOT WATER 1 Motor Hot Water 1 7.5
2 Pompa Hot Water CIP 1 1.5
3 Pompa Alkali 1 1.5
C.I.P
4 Pompa Acid 1 1.5
5 Pompa transfer CIP 1 5.5
6 Pompa Expantion Tank 1 7.5
HTST
7 Pompa Transfer 1 11
8 Motor Agitator Mixing 1 L6 1 18
9 Motor Agitator Mixing 2 L6 1 18
10 Agitator Holding Tank 1 L6 1 7.5
11 Agitator Holding Tank 2 L6 1 7.5
COOKING 12 Pompa transfer L6 1 11
13 Pompa Holding 1 L6 1 5.5
14 Pompa Holding 2 L6 1 5.5
15 Pompa mixing 2 L6 1 5.5
16 Pompa mixing 2 L6 1 5.5
17 Agitaror Sugar 1500 1 7.5
18 Agitator Sugar 3000 1 7.5
19 Pompa Sugar 1 L6 1 5.5
SUGAR
20 Pompa Sugar 2 L6 1 5.5
21 Pompa Dumper Sugar 1 5.5
22 Motor Agitator Sugar Tank 1 5.5
23 Agitator Jaket Nata 1 7
24 Pompa Washing Nata 1 2.2
NATA 25 Motor Sirkulasi Nata 1 1.5
26 Motor Transfer Nata 1 11
27 Pompa Return CIP 1 5.5
28 Motor ACL 1 0.75
29 Motor Elevator 1 0.75
30 Motor Servo After Elevator 1 0.75
FILLING 31 Motor Slide Cup 1 0.75
32 Motor Servo Conveyor Mould 1 1.5
33 Motor Transfering filling 1 0.75
34 Pompa Vavum ICME 1 0.75
35 Conveyor IJP L6 1 0.4
36 Motor blower 2 0.75
COOLING
37 Conveyor cooling( servo) 1 4
38 Pompa Cooling Batch 1 11
39 Pompa Vavum BECKER 1 3.4
40 Motor Tansfering Inlet packing 1 0.4
41 Conveyor packing L4( servo) 1 0.75
42 Motor Extractor 1 1 3
43 Motor Extractor 2 1 3
44 Motor Rotary packing 1 0.4
PACKING
45 Motor conveyor modular 1 0.55
46 Motor conveyor errector 1 0.18
47 Motor Belt Carton sealer Errector 2 0.12
48 Motor Stucker 2 0.18
49 Motor Carton sealer Errector 2 0.25
50 Motor Carton Glue 2 0.2
51 Motor Conv.Palletizer 1 0.37
52 Motor Metering Belt conveyor 1 0.55
53 Motor Orienting Unit 1 0.37
54 Motor Electronic Spacer 1 0.12
55 Motor elevator 1 1.1
PALLETIZER 56 Motor elevator 1 0.12
57 Motor elevator 1 0.12
58 Motor elevator 1 0.12
59 Motor elevator 1 0.12
60 Motor Conveyor C50 1 0.12
61 Motor Pallet Destracker 1 0.12
TOTAL KAPASITAS 66 222.01
OR LINE 6

BASE ON NAME PLATE UNIT


Status Eff KW Total Ampere SISTEM START MOTOR
On 1 7.5 13.41 INVERTER On
On 0.3 0.5 0.80 Off
On 0.3 0.5 0.80
On 0.3 0.5 0.80
On 0.3 1.7 2.95 INVERTER
On 1 7.5 13.41 INVERTER
On 1 11.0 19.66 INVERTER
On 1 18.0 32.18 INVERTER
On 1 18.0 32.18 INVERTER
On 1 7.5 13.41 INVERTER
On 1 7.5 13.41 INVERTER
On 1 11.0 19.66 INVERTER
On 1 5.5 9.83 INVERTER
On 1 5.5 9.83 INVERTER
On 1 5.5 9.83 INVERTER CIP process
On 1 5.5 9.83 INVERTER 113.0
On 1 7.5 13.41 INVERTER
On 1 7.5 13.41 INVERTER
On 1 5.5 9.83 INVERTER
On 1 5.5 9.83 INVERTER
On 1 5.5 9.83 INVERTER
On 1 5.5 9.83 INVERTER
On 1 7.0 12.51 INVERTER
On 1 2.2 3.93
On 1 1.5 2.68
On 1 11.0 19.66 INVERTER
On 1 5.5 9.83 INVERTER 177.2
On 1 0.8 1.34
On 1 0.8 1.34
On 1 0.8 1.34
On 1 0.8 1.34
On 1 1.5 2.68
On 1 0.8 1.34
On 1 0.8 1.34 6.0
On 1 0.4 0.72
On 1 1.5 2.68
On 1 4.0 13.59
On 1 11.0 19.66 STAR DELTA 16.9
On 1 3.4 6.08
On 1 0.4 2.56
On 1 0.8 4.25
On 1 3.0 16.98
On 1 3.0 16.98
On 1 0.4 2.56
On 1 0.6 0.98
On 1 0.2 0.32
On 1 0.2 0.43
On 1 0.4 0.64
On 1 0.5 0.89
On 1 0.4 0.72 13.2
On 1 0.4 0.66
On 1 0.6 0.98
On 1 0.4 0.66
On 1 0.1 0.21
On 1 1.1 1.97
On 1 0.1 0.21
On 1 0.1 0.21
On 1 0.1 0.21
On 1 0.1 0.21
On 1 0.1 0.21
On 1 0.1 0.21 3.2
216.5 387.01
KW
Hot Water 7.5
C.I.P 3.0
HTST 18.5
COOKING 84.0
SUGAR 37.0
NATA 27.2
FILLING 6.0
COOLING 16.9
PACKING 13.2
PALLETIZER 3.2
216.5

CIP process
SUGAR DESOLVING
BASE ON NAME PLATE UNIT
AREA NO. NAMA BEBAN
Jml KW / Unit Status Eff KW Total
1 Pompa Transfer dumping 1 5.5 On 1 5.5
2 Pompa Transfer disolving 1 4 On 1 4.0
3 Pompa Transfer storage 1 5.5 On 1 5.5
SUGAR DESOLVING
4 Pompa Transfer frutcost 1 2.2 On 1 2.2
5 Agitator Disolving 1 7.5 On 1 7.5
7 Agitator Storage 1 4 On 1 4.0
Kapasitas total: 6.0 28.7 28.7
ATE UNIT
Ampere SISTEM START MOTOR
9.83 D.O.L (Direct on line ) On
7.15 Off
9.83 INVERTER
3.93
13.41 INVERTER
7.15
51.3
LIST DATA KAPASITAS MOTOR UTI

AREA NO NAMA BEBAN TYPE MOTOR JUMLAH

1 Motor sumur 1 grundfos 1


2 Motor sumur 2 grundfos 1
3 Motor sumur 3 grundfos 1
4 Motor sumur 4 grundfos 1
5 Motor sumur 5 grundfos 1
6 Motor MMF Line 1 ebara 1
7 Motor MMF Line 2 ebara 1
8 Motor MMF Line 3 ebara 1
9 Motor pump cleaning grundfos 1
10 Motor UF proses grundfos 1
11 Motor UF backwash grundfos 1
12 Motor softener RO BWT grundfos 1
13 Motor HP Pump RO BWT grundfos 2
14 Motor Proses Line 1 & Line 2 grundfos 1
15 Motor Proses Line 3,4,5 grundfos 1
16 Motor proses Line 3 & 6 ( MHO ) grundfos 1
Water Treatment 17 Motor proses RO Mix AFC grundfos 1
18 Motor proses Line 6 & 7 grundfos 1
19 Motor proses Recycle backwash mmf ebara 1
20 Motor softener line 1 ebara 1
21 Motor pump softener Line 1 ebara 1
22 Motor Pump softener effluet ebara 1
23 Motor distribusi Softener All utility ebara 1
24 Motor cooling tower line CUP ebara 1
25 Motor cooling tower line HDPE ebara 1
26 Motor backwash DMI ebara 2
27 Motor proses DMI ebara 2
28 Motor pump proses ACF LOW grundfos 2
29 Motor softener RO LOW grundfos 1
30 Motor RO LOW grundfos 1
31 Motor HP Pump RO LOW grundfos 1
32 Motor CIP RO LOW grundfos 1
33 Motor proses RO LOW grundfos 1
Total Kapasitas 37

1 Motor Blower 1
Boiler Thermax line CUP 2 Motor Feedpump 2
3 Motor Rotary burner 1
Total Kapasitas

1 Atlas Copco FO.ZT75VSD-10.4-50 1


2 Kaeser CSD 122 1
3 Sullair LS16-75 AC SULL 1
4 Sullair LS16-60 AC SULL 1
5 Ingersoll Rand V75-8 1
Air Compressor line CUP
6 Dryer Ingersoll rand 1
7 Dryer TE 112 1
8 Dryer Atlas Copco 1
9 Dryer Hankinson 1
10 Dryer Hankinson 1
Total Kapasitas

1 Motor Fan LRCH 250 1


2 Motor Fan KH 150 Line 1 1
3 Motor Fan LRCH 150 Line 2 1
4 Motor Fan KH 150 Line 3 1
Cooling Tower Line CUP 5 Motor Fan LRCH 150 Line 4 & 5 1
6 Motor cooling line transfer HTST 1
7 Motor tranfers cooling line 1 1
8 Motor transfer cooling line 2 1
9 Motor transfer cooling line 3,4,5 1
Total Kapasitas

1 ID Fan 1
2 FD Fan 1

Boiler Alstom 3,2 tph


3 Stocker drive 1
Boiler Alstom 3,2 tph 4 Rotary valve 1
5 Feed water pump 2
6 Elevator palmshell 2
7 Motor Feedpump 2
Total Kapasitas

1 Motor kompressor Bitzer 2


Chiller Aicool (Air cool) 2 Motor transfer 1
3 Motor sirkulasi 1
Total Kapasitas

1 Motor transfer ebara 1


Chiller Aicool (Water cool)
2 Motor sirkulasi ebara 1
Total Kapasitas

1 AHU Line 1 1
2 AHU Line 3 1

HVAC 3 AHU Line 4 1


4 AHU Line 5 1
5 AHU Line 2 1
6 AHU Line 6 1
Total Kapasitas

1 Line Cup positive pressure 1


2 Line Cup positive pressure 1
3 Line Cup negative pressure 2
AIR FRESH
4 Line Cup negative pressure 1
5 Air FRESH Ruangan Formula 1

Total Kapasitas

Blower first pit


1 1
Dosing pump costic
2 1
Dosing pump urea
3 1
Dosing pump TSP
4 1
Blower aeration
5 3
Filter Pump
6 1
7 Sludge Secondary pump 1
8 Agitator Primary 1
9 Agitator Secondary 1

WWTP 10 Agitator Flokulant 1


11 Agitator Coagulant 1
12 Pompa celub gutter Line 6 1
13 Pompa celub pit water Line 6 4
14 Pompa Celub sump well 1
15 Pompa celub first pit 1
16 Pompa Celub Pit 2 1
17 Pompa celub sedimentasi/Bak Klorin 1
18 Pompa celub Pit Sluge 1
19 Pompa Celub Pit A 1
20 Pompa Celub Cruser/Gilingan BS 1
Total Kapasitas

1 Pompa distribusi Abs 1


2 Pompa CWP Abs 3
Abs Chiller 3 Pompa Cooling ABS 3
4 Motor Fan Abs 2

Total Kapasitas

1 Pompa transfer HTST 1


2 Motor tunel cooling tower 1
L6 & L7 Cooling tower 3 Motor Fan cooling tower 2
4 Motor tunel cooling tower L7 2
5 Motor Fan cooling tower L7 1
Total Kapasitas

1 Motor ID Fan 1
2 Motor FD Fan 1
3 Motor Elevator 1
4 Motor Belt transfer1 1

Boiler TWA
5 Motor Incline Belt 1

Boiler TWA 6 Motor incline Boiler A 1


7 Motor feeder 1
8 Motor incline Boiler B 1
9 Motor screw 1
10 Motor water pump 1
11 Motor Lifter 1
12 Motor pompa scrubbber 1
Total Kapasitas
AS MOTOR UTILITY

kW / UNIT Status Eff KW TOTAL SISTEM START MOTOR

9.5 On 0.2 1.9 INVERTER On


15 On 0.2 3.0 STAR DELTA Off
9.5 On 0.2 1.9 STAR DELTA
9.5 On 0.2 1.9 INVERTER
9.5 On 0.2 1.9 INVERTER
5.5 Off 0.00 0.0 STAR DELTA
11 On 0.33 3.7 STAR DELTA
11 On 0.33 3.7 STAR DELTA
3.70 On 0.50 1.9
5.50 Off 0.00 0.0 STAR DELTA
5.50 Off 0.00 0.0 STAR DELTA
5.50 Off 0.00 0.0 STAR DELTA
30.00 Off 0.00 0.0 STAR DELTA
5.50 On 1.00 5.5 STAR DELTA
5.50 On 1.00 5.5 STAR DELTA
5.50 On 1.00 5.5 STAR DELTA
5.50 On 1.00 5.5 STAR DELTA
7.50 On 0.00 0.0 INVERTER
5.50 Off 0.00 0.0 STAR DELTA
30.00 Off 0.00 0.0 STAR DELTA
5.50 Off 0.00 0.0 STAR DELTA
5.50 On 1.00 5.5 STAR DELTA
5.50 On 1.00 5.5 STAR DELTA
5.50 Off 0.00 0.0 STAR DELTA
5.50 Off 0.00 0.0 STAR DELTA
5.50 On 1.00 11.0 STAR DELTA
5.50 On 1.00 11.0 STAR DELTA
5.50 On 1.00 11.0 STAR DELTA
2.20 On 1.00 2.2
5.50 On 1.00 5.5 STAR DELTA
15.00 On 1.00 15.0 STAR DELTA kwh
5.50 Off 0.00 0.0 2603.6
5.50 Off 0.00 0.0
262.4 108.5

11.00 Off 1.00 11.0 STAR DELTA


4.50 Off 1.00 9.0
4.50 Off 1.00 4.5
20.00 0.0

90.00 Off 0.00 0.0 INVERTER


75.00 On 1.00 75.0 STAR DELTA
56.00 On 1.00 56.0 STAR DELTA
56.00 On 1.00 56.0 STAR DELTA
75.00 On 1.00 75.0 STAR DELTA
4.30 Off 0.00 0.0
5.00 On 1.00 5.0
5.00 On 1.00 5.0
5.00 On 1.00 5.0
5.00 On 1.00 5.0
376.30 282.0

5.50 On 5.5 STAR DELTA


3.70 On 3.7
4.70 On 4.7
3.70 On 3.7
4.70 On 4.7
11.00 On 11.0 STAR DELTA
15.00 On 15.0 STAR DELTA
11.00 On 11.0 STAR DELTA

11.00 On 11.0 STAR DELTA


70.30 70.3

15.00 Off 1.00 15.0 INVERTER


5.50 Off 1.00 5.5 INVERTER
0.55 Off 1.00 0.6
0.75 Off 1.00 0.8
0.75 Off 1.00 1.5
0.75 Off 1.00 1.5
3.20 Off 1.00 6.4
26.50 0.0

7.46 On 1.00 14.9 STAR DELTA


3.50 On 1.00 3.5
3.50 On 1.00 3.5
14.46 21.9

11.00 On 1.00 11.0 STAR DELTA


11.00 On 1.00 11.0 STAR DELTA
22.00 22.0

22 On 1 22.0 INVERTER
19 On 1 19.0 INVERTER
19 On 1 19.0 INVERTER
15 On 1 15.0 STAR DELTA
22 On 1 22.0 STAR DELTA
19 On 1 19.0 INVERTER 0
116 116.0

11 On 1 11.0 STAR DELTA


11 On 1 11.0 STAR DELTA
11 On 1 22.0 STAR DELTA
7.5 On 1 7.5 STAR DELTA
7.5 On 1 7.5 STAR DELTA

48 59.0

7.5 On 1 7.5 STAR DELTA


0.115 On 1 0.1
0.115 On 1 0.1
0.115 On 1 0.1
45 On 0.4 54.0 STAR DELTA
4 On 1 4.0
0.75 On 1 0.8
0.75 On 1 0.8
0.75 On 1 0.8
1.1 On 1 1.1
1.1 On 1 1.1
1.5 Off 1 1.5
0.75 On 1 3.0
0.75 On 1 0.8
0.75 On 1 0.8
1.5 On 1 1.5
0.75 On 1 0.8
0.75 On 1 0.8
1.5 On 1 1.5 1921.08
0.75 On 1 0.8 1536.864
70.295 80.0

50 Off 1 50.0 INVERTER


15 Off 1 45.0 STAR DELTA
15 Off 1 45.0 STAR DELTA
5.5 Off 1 11.0 STAR DELTA

85.5 0.0

11 On 1 11.0 STAR DELTA


11 On 1 11.0 STAR DELTA
3.7 On 1 7.4
11 Off 1 22.0 STAR DELTA
3.7 Off 1 3.7
40.4 29.4

30 On 1 30.0 INVERTER
11 On 1 11.0 INVERTER
2.2 On 1 2.2
1.1 On 1 1.1
2.2 On 1 2.2
0.8 On 1 0.8
0.4 On 1 0.4
0.8 On 1 0.8
2.2 On 1 2.2
11 On 1 11.0 STAR DELTA
2.2 On 1 2.2
6.6 On 1 6.6 STAR DELTA
70.5 70.5
0

You might also like