You are on page 1of 1

TECHNICAL SPECIFICATION

Date: 16.11.2019
Sl. No. Description Unit Technical Data
1 Name of Manufacturer BBS Cables Ltd.
2 Size of Cable no. x mm2 4x25 4x16
3 Type of Cable A2xFGY-FR
4 Reference Standard - IEC 60228, IEC 60502-1 & IEC 60332
5 Rated Voltage of cable, Uo/U (Um) kV 0.6/1.0 (1.2)
Maximum Conductor temperature in normal
6 ⁰C 90
operation
7 Maximum short circuit temperature ⁰C 250
8 Conductor as per IEC 60228
Material - Aluminium
Shape of conductor - Stranded Circular
Class of conductor - Class-2
No. & Diameter of wire in conductor no./mm 7/2.14 7/1.71
9 Insulation as per IEC 60502-1
Material - XLPE
Nominal thickness mm 0.9 0.7
Color - Red, Yellow, Blue & Black
10 Inner Covering as per IEC 60502-1
Material - Extruded PVC
Nominal thickness mm 1.0 1.0
Color - Black
11 Armour as per IEC 60502-1
Material - Galv. Flat steel wire with steel tape binder
Dimension of each armour wire mm 4 x 0.8
Thickness of steel tape binder mm 0.3
12 Outer Sheath as per IEC 60502-1
Material - Extruded PVC-FR
Nominal thickness mm 1.8 1.8
Color - Black
13 Approximate overall diameter mm 27.0 23.8
14 Max. D.C. Resistance of conductor at 20oC Ω/km 1.20 1.91
15 Min. Insulation resistance constant ki at 20oC M.ohm-km 3670.0
16 A.C. Voltage Test for 5 minutes kV 3.5 (withstand)
17 Current rating at defined condition
In ground at 30oC Amps 94 73
In air at 35oC Amps 96 70
18
a) Minimum unaffected portion from top of the cable
mm >50
sample (After burning in flammability test machine)

b) Oxygen index of FR-PVC, minimum % >29

Mirza Abdul Malek Engr. Md. Jahangir Khan


Asst. Manager (CS & Design) AGM (QC & Lab)