Grid feeding monitoring relay acc. VDE AR-N 4105


CM-UFD.M21

The CM-UFD.M21 is a multifunctional grid feeding


monitoring relay for three-phase mains. It provides
different monitoring functions in accordance with
VDE AR-N 4105 to detect over- and undervoltage

2CDC 251 003 S0012


(10 minutes average value, voltage increase and
decrease protection) as well as any changes in
grid frequency (frequency increase and decrease
protection). Additionally, vector shift detection is
configurable.
Characteristics
–– Monitoring of three-phase mains for grid feeding
–– Type-tested in accordance with VDE AR-N 4105
Marks
–– Two-channel measuring circuit and two processors to
a CE
ensure single-fault tolerance
–– Over- and undervoltage, 10 minutes average value as well
as over- and underfrequency monitoring
–– Two-tier threshold settings for over-/ undervoltage/
-frequency configurable according to ‘BDEW guideline for
generating plants connected to the medium voltage grid’
–– Vector shift detection configurable
–– Measured values, thresholds and settings shown on the
display
–– All threshold values adjustable as absolute values
–– Default setting according to VDE AR-N 4105
–– True RMS measuring principle
–– 2 input contacts for feedback signal of subsequent
section switch
–– Monitoring of subsequent section switch configurable
–– Tripping delay for each threshold adjustable
–– Alarm memory for up to 99 entries (incl. cause of alarm,
measured value, relative timestamp)
–– Test function
–– Simulation mode
–– Code lock and mechanical sealing possible
–– 5 digital outputs (transistor outputs) for signalling the
cause of alarm to a superior control system
–– 2 c/o (SPDT) contacts
–– 105 mm (4.13 in) width
–– LEDs for the indication of operational states

Order data

Grid feeding monitoring relay


Type Rated control supply voltage Measuring range Order code
CM-UFD.M21 24-240 V AC/DC 3 x 15-520 V AC 1SVR 510 730 R0300
Functions

Operating controls
1 2 3 4

5
6

8
9

11 10

1 Button Test 6 Indication of time

2 Indication of operational states Time: yellow LED - a time delay is displayed

Q1: red LED - overvoltage 7 Indication of device mode


Q2: red LED - undervoltage
8 Button Set / Reset ►
Q3: red LED - overfrequency
9 Button Up / Down ▲▼
Q4: red LED - underfrequency
10 Indication of operational states
Q5: red LED - error, if PR1 or PR2 activated 1)

L1: yellow LED - kind of measured value


3 D j : red LED - vector shift L2: yellow LED - kind of measured value

4 11: yellow LED - 1st c/o (SPDT) contact energized L3: yellow LED - kind of measured value

21: yellow LED - 2nd c/o (SPDT) contact energized N: yellow LED - kind of measured value

5 Display (4-digits)
11 Status indication of device locking and sealable lock button
Voltage, 10 minutes average value, frequency or vector shift value, Red LED - device is locked
alarm and error messages

1) if PR3 or PR4 activated, 2nd threshold referring to LED Q1-Q4

More details see ‘LEDs, status information and fault messages’ on page 9.

2 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Application
The CM-UFD.M21 is a monitoring relay for feeding in three-phase mains. The device is connected between the decentral
electrical energy source such as photovoltaic systems, wind turbines, block-type thermal power stations and the public
grid. In case the public grid is disconnected due to any reason, for instance during maintenance work, the CM-UFD.M21
recognizes this powerless situation. Then, in conjunction with a section switch, the CM-UFD.M21 disconnects the decentral
electrical energy source from the public grid, shows the corresponding alarm on the display and signals the cause of alarm
to a superior control system. The grid feeding monitoring relay detects over- and undervoltage (10 minutes average value,
voltage increase and decrease protection) as well as any changes in grid frequency (frequency increase and decrease
protection). Additionally, vector shift detection is configurable.

Operation
The CM-UFD.M21 can be used to monitor 3-wire as well as 4-wire AC systems. It provides 2 c/o (SPDT) contacts for
disconnection of the decentral electrical energy source from the public grid and two separate input contacts for the
feedback signal of the section switch in order to enable monitoring of the disconnection. Five transistor outputs allow
the signalling of the cause of alarm to a superior control system. The unit is adjusted by front-face setting buttons and a
display, which allows the visualization of measured values and alarms. Furthermore, the display enables the selection of
presettings as well as the precise adjustment of threshold values and delay times. To disable vector shift detection, jumper
terminals D j 1 and D j 2.
All operational states are shown on the display and signalled by the front-face LEDs. See table ‘Indication of operational
states’ on page 9.

Button Test
Pressing the front-face button Test de-energizes the output relays immediately in order to disconnect the decentral
electrical energy source from the public grid. If the input contacts Y0, Y1, Y2 for the feedback loop of the section switch are
connected and monitoring of the feedback signal is activated, the CM-UFD.M21 will display the disconnection time of the
system (reaction time of CM-UFD.M21 + tripping time of the section switch) until further pressing of any button.

Vector shift detection


To disable vector shift detection, jumper terminals D j 1 and D j 2.

∆ϕ1 ∆ϕ2
2CDC 252 016 F0012

To set-up vector shift detection vSr, go to menu mode and see ‘Control charts’ on page 7 for more details. The
detection can be configured to single-phase1PH, to trip in case of a vector shift in one of the three phase, or three-phase
3PH, to trip only in case of a simultaneous vector shift in all three phases. After applying control supply voltage or opening
contacts D j 1 and D j 2, the vector shift detection is suppressed for the duration of the adjusted suppression time dEon.

Display mode (backmost decimal point 6 OFF)


The CM-UFD.M21 always starts-up in display mode and shows the values (voltage, frequency, etc.) as well as alarm
messages and error codes.

Set / Reset ►
Press shortly to display the next measured value / alarm counter.
Press for > 2 s to reset, quit error message.
Press for > 4 s to display the selected program (e.g. PR1).
Press for > 10 s to display the firmware version (e.g. 0-02).

Up / Down ▲▼
Press shortly to change to menu mode, display of alarm memory (button Down) or cumulative time of alarms (button Up).
Additional pressing of button Set for > 2 s makes a reset of the stored values. Press button Up / Down for > 2 s to display
the maximum / minimum measured values (device needs to be unlocked). Additional pressing of button Set for > 2 s
deletes the stored values.

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 3


Menu mode (backmost decimal point 7 ON)
Set / Reset ►
Press shortly to change to configuration mode.
Press for > 2 s to confirm last entry and return to display mode.

Up / Down ▲▼
Press shortly to select menu item; return to display mode.
If more than 30 seconds pass before a key is pressed, the CM-UFD.M21 automatically returns to display mode.

Configuration mode (backmost decimal point 7 flashing)


The display alternates between parameter name and currently set parameter value until either button Up or button Down is
pressed to change the parameter value.
If more than 2 seconds pass before a key is pressed, the display starts to alternate again.

Set / Reset ►
Press shortly to confirm and go to next parameter.
Press for > 2 s to confirm last entry and return to display mode.

Up / Down ▲▼
Press shortly / for a long time to modify the value slowly / rapidly.
Press buttons Up and Down simultaneously to set the adjusted value to zero.
If more than 30 seconds (in simulation mode 15 minutes) pass before a key is pressed, the CM-UFD.M21 automatically
applies the last entry and returns to display mode.

Simulation mode
The simulation mode allows the simulation of measured voltage and frequency values in order to check the settings and the
correct tripping of the CM-UFD.M21. During the simulation, alarm and error messages will only be displayed via LEDs. If the
device is sealed or locked, simulation is not possible. If the input contacts Y0, Y1, Y2 for the feedback loop of the section
switch are connected and monitoring of the feedback signal is activated, the CM-UFD.M21 will display the disconnection
time of the system (reaction time of CM-UFD.M21 + tripping time of section switch) until further pressing of any button.

To start simulation:
1. Change to menu mode and select Si (button Up / Down) and press button Set.
2. The display alternates between Si and the measurement parameter.
3. Select the measurement parameter to be simulated (button Up / Down) and press button Set.
4. The value of the simulated measurement parameter can be altered by pressing button Up / Down. Once the simulated
measurement value and the adjusted threshold value coincide, the output relays de-energize.
Note: The simulation of voltage values always takes into account the last set frequency value of simulation and vice versa.

To stop simulation:
Press button Set to return to menu mode. The CM-UFD.M21 continues to monitor the adjusted threshold values.
If more than 15 minutes pass before a key is pressed, the CM-UFD.M21 automatically returns to display mode.

Hint: If a threshold higher than the adjusted 10 minutes average value needs to be simulated, monitoring of UM has to be
temporarily deactivated. The same applies to U,, when simulating U,, , and to U_ when simulating U__ in PR3…PR6.

4 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Alarm counter
The alarm counter Ac will be incremented at every alarm and logs up to 99 alarms, which allows the documentation of the
number of alarms since last resetting.
To view the alarm counter, change to display mode and see ‘Control charts’ on page 7 for more details.

Cumulative time of alarms


The cumulative time of alarms tAL displays the duration of all cumulated disconnections of the decentral electrical energy
source from the public grid.
Recording only with applied control supply voltage.
To view the cumulative time of alarms, change to display mode and see ‘Control charts’ on page 7 for more details.
Press button Set / Reset for > 2 s to reset cumulative time of alarms and alarm counter.

Alarm memory
The non-volatile alarm memory contains the last 99 alarms including simulated alarms. The LEDs indicate the cause of
alarm and the display alternates between tripping value and relative timestamp [hours].
To view the alarm memory, change to display mode and see ‘Control charts’ on page 7 for more details.
The alarm memory will only be reset when changing program.

Scan mode
The scan mode Scn allows the cyclic display of all measured values. The corresponding display duration dit for each
measured value is adjustable. To start scan mode, change to display mode and see ‘Control charts’ on page 7 for more
details. To change the display duration dit, go to menu mode and see ‘Control charts’ on page 7 for more details.

Display refresh rate


To change the display refresh rate ddi, go to menu mode and see ‘Control charts’ on page 7 for more details.

Code lock
The code lock can be activated to protect the adjusted parameters.
To set Pin and lock the device:
1. Change to menu mode and select CodE (button Up / Down) and press button Set
2. Enter Pin - default setting 504 (button Up / Down) and press button Set
An incorrect Pin will be notified by Err flashing three times
3. Set code lock to oFF or on (button Up / Down) and press button Set
4. Enter new Pin (button Up / Down) or go to 5.) to keep Pin unchanged
5. Press button Set to confirm
–– on flashing three times, code lock activated
–– oFF flashing three times, code lock deactivated

Lock button (sealable)


Slightly lift the button cover and turn 180°. Actuate the Lock button by strong pressing on the button cover > 2 s (LED

starts flashing) until the CM-UFD.M21 is locked or unlocked .


In case of setting attempts Loc is displayed for 3 seconds if device has been locked.

Sealing
The Lock button can be sealed to protected against unauthorized changes.

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 5


Electrical connection

A1 A2 A2 VQ Q1 Q2 Q3 Q4 Q5 12 11 14 22 21 24 A1-A2 Control supply voltage

L1, L2, L3, N Measuring input

11-12/14 1st c/o (SPDT) contact


A1 A2 11 21
21-22/24 2nd c/o (SPDT) contact

U <, U>, U>>, f<, f>, ϕ Y0-Y1 1st input contact for feedback signal

Y0-Y2 2nd input contact for feedback signal

2CDC 252 002 F0012


L1 L2 L3 N
12 14 22 24 Dj 1-Dj 2 Vector shift detection

Jumper = vector shift detection disabled

ϕ1 ϕ2 Y0 Y1 Y2 L1 L2 L3 N VQ Supply voltage of digital outputs

Q1 Digital output for overvoltage

Q2 Digital output for undervoltage

Q3 Digital output for overfrequency

Q4 Digital output for underfrequency

Q5 Digital output for:

error, if PR1 or PR2 activated

if PR3 or PR4 activated, 2nd threshold


referring to LED Q1-Q4

Connection diagram

Configuration and settings

Program setup
The suitable program must be set on the CM-UFD.M21 in accordance with the application. If the CM-UFD.M21 is sealed /
locked (red LED on), sealing has to be deactivated first.

PR Connection Threshold values Voltage


1* 3 AC with N Low voltage 230 V
1 x overvoltage, 1 x undervoltage
2 3 AC w/o N 1 x overfrequency, 1 x underfrequency 400 V
10 min average value, 1 x vector shift
3 3 AC with N Medium voltage 57.7 V
4 3 AC w/o N 2 x overvoltage, 2 x undervoltage 100 V
5 3 AC with N 2 x overfrequency, 2 x underfrequency 230 V
6 3 AC w/o N 10 min average value, 1 x vector shift 400 V
* Default setting

Adjustment process:
If present, remove the seal (only authorized person)
1. Apply control supply voltage at A1-A2
2. Slightly lift the button cover and turn 180°
3. Actuate the small blue button by strong pressing on the button cover (LED starts flashing) until the flashing green LED
turns steady.
4. Press button Up 1x -> Display InFo
5. Press button Set / Reset 5x -> Display PR1
6. Set the program with the button Up / Down
7. Press button Set / Reset 1x -> Display no
8. Press button Down 1x -> Display yes
9. Press button Set / Reset
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to "default settings" (see ‘Default settings
and firmware version’ on page 11). Only change the parameters after having selected the correct program.

6 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Control charts
PR1 3 AC with N, PR2 3 AC w/o N, acc. to VDE-AR-N 4105

1) 3AC+N = 300 V

[ ] = Unit

Pressing buttons Up and Down


simultaneously, sets the values to the
smallest one.

Code-Reset = Press button Set 2 s while


applying control supply voltage (Pin = 504)

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 7


PR3, PR5 3 AC with N, PR4, PR6 3 AC w/o N acc. to BDEW - Technical Guideline ‘Generating Plants Connected to the
Medium-Voltage Network, Guideline for generating plants’ connection to and parallel operation with the medium-voltage
network’, June 2008 issue.

1) 3AC+N = 300 V

[ ] = Unit

Pressing buttons Up and Down


simultaneously, sets the values to the
smallest one.

Code-Reset = Press button Set 2 s while


applying control supply voltage (Pin = 504)

8 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Indication of operational states

LEDs, status information and fault messages

red/green LED
11-12/14, 21-22/24:

Backmost decimal
Time: yellow LED
Q1: red LED >U

Q2: red LED <U

Q3: red LED >F

Q4: red LED <F

L1: yellow LED

L2: yellow LED

L3: yellow LED

N: yellow LED
Dj : red LED
Q5: red LED

yellow LED

Display

point
Function
Output relay energized V

Indication of time V

V
red: locked
Indication of device locking
green:
unlocked

Display mode OFF


Menu mode V

Configuration mode X

Scan mode Measured values 1)


Error or 2nd threshold value in Pr3…6 V

AL N +
10 minutes average value (UN) V OFF OFF OFF OFF OFF OFF OFF
Measured value 2)
10 minutes average value (UN),
OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
ON-delay active
10 minutes average value (UN),
W OFF OFF OFF OFF OFF OFF V Time
OFF-delay active
AL +
Overvoltage (U>) V OFF OFF OFF OFF OFF OFF OFF
Measured value 2)
Overvoltage (U>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overvoltage (U>), OFF-delay active W OFF OFF OFF OFF OFF OFF V Time
AL +
Overvoltage (U>>) V OFF OFF OFF V OFF OFF OFF
Measured value 2)
Overvoltage (U>>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overvoltage (U>>), OFF-delay active W OFF OFF OFF W OFF OFF V Time
AL +
Undervoltage (U<) OFF V OFF OFF OFF OFF OFF OFF
Measured value 2)
Undervoltage (U<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Undervoltage (U<), OFF-delay active OFF W OFF OFF OFF OFF OFF V Time
AL +
Undervoltage (U<<) OFF V OFF OFF V OFF OFF OFF
Measured value 2)
Undervoltage (U<<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Undervoltage (U<<), OFF-delay active OFF W OFF OFF W OFF OFF V Time
AL +
Overfrequency (f>) OFF OFF V OFF OFF OFF OFF OFF
Measured value 2)
Overfrequency (f>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overfrequency (f>), OFF-delay active OFF OFF W OFF OFF OFF OFF V Time
AL +
Overfrequency (f>>) OFF OFF V OFF V OFF OFF OFF
Measured value 2)
Overfrequency (f>>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overfrequency (f>>), OFF-delay active OFF OFF W OFF W OFF OFF V Time
AL +
Underfrequency (f<) OFF OFF OFF V OFF OFF OFF OFF
Measured value 2)
Underfrequency (f<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Underfrequency (f<), OFF-delay active OFF OFF OFF W OFF OFF OFF V Time
AL +
Underfrequency (f<<) OFF OFF OFF V V OFF OFF OFF
Measured value 2)
Underfrequency (f<<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Underfrequency (f<<), OFF-delay active OFF OFF OFF W W OFF OFF V Time
AL +
Vector shift detection OFF OFF OFF OFF V OFF OFF
Measured value 2)
Vector shift detection, OFF-delay active OFF OFF OFF OFF W OFF V Time
Measured value (Voltage L1 against N) V OFF OFF V

Measured value (Voltage L2 against N) OFF V OFF V

Measured value (Voltage L3 against N) OFF OFF V V

Measured value (Voltage L1 against L2) V V OFF OFF


Measured value (Voltage L2 against L3) OFF V V OFF
Measured value (Voltage L1 against L3) V OFF V OFF
Vector shift (L1, L2, L3) X X X

1) In scan mode, all measured values are displayed cyclicIy. The display duration dit is adjustable.
2) The adjusted measured value is displayed.

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 9


Example of application

L1
L2
L3 Low voltage grid
N
where applicable,
a transformer

m6 A

*)

A1 A2 11 21 L1 L2 L3 N

12 14 22 24 Y2 Y1 Y0
Expansion of existing installation:

in series with A
A
K1 K1

in series with B
B
K2 K2

A B Optional use of n/o contacts,

2CDC 252 013 F0212


automatic recognition
Inverter(s)
*) For example, remote disconnection Generator(s)
via ripple control receiver Power plant

10 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Default settings and firmware version
When changing program, all parameters are reset to the default settings.

Default settings

Low voltage Medium voltage

3 AC + N 3 AC + N 3 AC + N
3 AC 400 V 3 AC 100 V 3 AC 400V
230 V 57.7 V 230 V

Menu point Parameter Unit Pr1 * Pr2 Pr3 Pr4 Pr5 Pr6

U,,: Alarm on/off - - on on on on

U,,: Overvoltage V - - 66.4 115 264 458

U,, H,,: Hysteresis V - - 1.0 1.0 3.0 3.0

dAL: ON-delay s - - 0.10 0.10 0.10 0.10

doF: OFF-delay s - - 60 60 60 60

U,: Alarm on/off on on on on on on

U,: Overvoltage V 264 458 62.3 108 249 430

U, H,: Hysteresis V 5.0 5.0 1.0 1.0 3.0 3.0

dAL: ON-delay s 0.10 0.10 60.00 60.00 60.00 60.00

doF: OFF-delay s 60 60 60 60 60 60

UM: Alarm on/off on on off off off off

UM: Overvoltage V 253 438 253 438 253 438

UM HM: Hysteresis V 3.0 3.0 3.0 3.0 3.0 3.0

dAL: ON-delay s 0.10 0.10 0.10 0.10 0.10 0.10

doF: OFF-delay s 60 60 60 60 60 60

U_: Alarm on/off on on On On on on

U_: Undervoltage V 184 318 46.2 80.0 184 318

U_ H_: Hysteresis V 5.0 5.0 1.0 1.0 3.0 3.0

dAL: ON-delay s 0.10 0.10 2.70 2.70 2.70 2.70

doF: OFF-delay s 60 60 60 60 60 60

U__: Alarm on/off - - off off off off

U__: Undervoltage V - - 26.0 45.0 104 180

U__ H__: Hysteresis V - - 1.0 1.0 2.0 2.0


dAL: ON-delay s - - 0.30 0.30 0.30 0.30
doF: OFF-delay s - - 60 60 60 60
F,,: Alarm on/off - - off off off off
F,,: Overfrequency Hz - - 51.50 51.50 51.50 51.50

F,, H,,: Hysteresis Hz - - 1.45 1.45 1.45 1.45


dAL: ON-delay s - - 0.10 0.10 0.10 0.10
doF: OFF-delay s - - 60 60 60 60
F, F,: Alarm on/off on on on on on on
F,: Overfrequency Hz 51.50 51.50 51.50 51.50 51.50 51.50
H,: Hysteresis Hz 1.45 1.45 1.45 1.45 1.45 1.45
dAL: ON-delay s 0.10 0.10 0.10 0.10 0.10 0.10
doF: OFF-delay s 60 60 60 60 60 60

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 11


Default settings

Low voltage Medium voltage

3 AC + N 3 AC + N 3 AC + N
3 AC 400 V 3 AC 100 V 3 AC 400V
230 V 57.7 V 230 V

Menu point Parameter Unit Pr1 * Pr2 Pr3 Pr4 Pr5 Pr6

F_: Alarm on/off on on on on on on

F_: Underfrequency Hz 47.50 47.50 47.50 47.50 47.50 47.50

H_: Hysteresis Hz 1.00 1.00 1.00 1.00 1.00 1.00


F_

dAL: ON-delay s 0.10 0.10 0.10 0.10 0.10 0.10

doF: OFF-delay s 60 60 60 60 60 60

F__: Alarm on/off - - off off off off

F__: Underfrequency Hz - - 47.50 47.50 47.50 47.50


F__
H__: Hysteresis Hz - - 1.00 1.00 1.00 1.00
dAL: ON-delay s - - 0.10 0.10 0.10 0.10
doF: OFF-delay s - - 60 60 60 60
v5r : Alarm on/off off off off off off off
vsr : Vector shift ° 10.0 10.0 10.0 10.0 10.0 10.0
v5r doF : OFF-delay s 3 3 3 3 3 3
dEon : Suppression time s 2 2 3 3 3 3
v5r : Number of phases 3ph 3ph 3ph 3ph 3ph 3ph
trEL : Switching time
rEL s 5.0 5.0 off off off off
Y1,Y2
ddi : Display refresh
s 0.5 0.5 0.5 0.5 0.5 0.5
rate
ddi
dit : Display duration
s 3.5 3.5 3.5 3.5 3.5 3.5
SCn
U : Voltage V 230 400 57.7 100 230 400
Si F : Frequency Hz 50.00 50.00 50.00 50.00 50.00 50.00
v5r : Vector shift ° 0.0 0.0 0.0 0.0 0.0 0.0
CodE pin : Pin code 504 504 504 504 504 504
fnr : Firmware version 0-02 0-02 0-02 0-02 0-02 0-02
snr : Serial number xxxxx xxxxx xxxxx xxxxx xxxxx xxxxx
Info h : Operating hours h xxxxx xxxxx xxxxx xxxxx xxxxx xxxxx
err : Error counter xxx xxx xxx xxx xxx xxx
Pr : Program 1 2 3 4 5 6
*factory preset

Protective functions, default settings according to VDE-AR-N 4105 section 6.5.2:


Voltage increase protection U>> U, 1.15 U n 100 ms
Voltage increase protection U> UM 1.1 U n 100 ms
Voltage decrease protection U< U_ 0.8 U n 100 ms
Frequency increase protection f> F, 51.5 Hz 100 ms
Frequency decrease protection f< F_ 47.5 Hz 100 ms

12 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Troubleshooting
Error Cause Remedy
EEEE or -EEE Measured voltage, frequency or the vector Consider the measuring range
appears in the display shift is too large or too small
Err4 appears in the display Too high internal measurement deviation of the Perform a reset:
two measuring channels Interrupt the conrol supply voltage for >5 s
Err5 appears in the display Error internal regulation

Err6 appears in the display Communication error internal interface


Err7 appears in the display + LED of the Error feedback contacts Feedback contacts not connected
faulty output circuit is lightning - set trEl -> off
Feedback contacts connected
- check the correct connection
- adjust the turn-on time of the section switch
under trEL.
- perform a reset:
Interrupt the conrol supply voltage for >5 s
Err8 appears in the display Hysteresis error: overlapping of the release Upper threshold value must be higher than
points the lower threshold value, check the threshold
values

Err9 appears in the display Configuration error Reset to factory settings, see ‚Program setup‘
on page 6

A time expires in the display If an OFF-delay dof is active, the time runs Wait until the time is complete (depending on
down in the display (the shortest one first) the setting, several times may elapse one after
the other)
Device cannot be configured / only the Code lock / Sealing activated When having problems with the code lock (Pin
threshold values can be configured forgotten), the lock can be deactivated and the
Pin can be reset to 504, by pressing the button
► until Code / off is shown in the display,
while switching on the control supply voltage.
Implausible voltage values Pr selected with N, but N not connected Select Pr without N or connect N
Loc appears in the display Sealing is active See ‚Program setup‘ on page 6
Code appears in the display Code lock is active See ‚Code lock‘ on page 5

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 13


Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated

Input circuits
Type CM-UFD.M21
Supply circuit A1-A2
Rated control supply voltage Us 24-240 V AC/DC
Rated control supply voltage Us tolerance -15...+20 %
Rated frequency DC and 50/60 Hz respectively
Frequency range AC 40-70 Hz
Typical current / power consumption 24 V DC 92 mA / 2.2 W
230 V AC 25 mA / 5.7 VA
Power failure buffering time 5 ms

Measuring circuit L1, L2, L3 (N)


Monitoring functions over-/undervoltage U,,, U, / U_, U__ yes, can be switched off
over-/underfrequency F,,, F, / F_, F__ yes, can be switched off
10 minutes average value per phase UM yes, can be switched off
vector shift v5r yes, can be switched off
Measuring ranges over-/undervoltage U,,, U, / U_, U__ 10-310 V AC (L1, L2, L3, N)
15-530 V AC (L1, L2, L3)
over-/underfrequency F,,, F, / F_, F__ 40-70 Hz
vector shift v5r 0…+45°
Threshold values over-/undervoltage, 10 minutes average value 15-300 V AC, adjustable in 0.1 V steps (< 100 V)
U,,, U, / U_, U__, UM / in 1 V steps (> 100 V) (L1, L2, L3, N)
15-520 V AC, adjustable in 0.1 V steps (< 100 V)
/ in 1 V steps (> 100 V) (L1, L2, L3)
over-/underfrequency F,,, F, / F_, F__ 45-65 Hz, adjustable in 0.01 Hz steps
vector shift v5r 2-20 °, adjustable in 0.1° steps
Hysteresis related to over-/undervoltage,
1.0-99.9 V, adjustable in 0.1 V steps
the threshold value 10 minutes average value H,,, H, / H_, H__, HM
over-/underfrequency H,,, H, / H_, H__ 0.05-10.00 Hz, adjustable in
0.05 Hz steps
Accuracy of voltage measurement L1,L2,L3,N ± 0.6 % of measured value
measurements voltage measurement L1,L2,L3 ± 0.8 % of measured value
frequency measurement ± 0.04 Hz ± 1 digit
Display accuracy > 100 V: ± 1 digit (1 V)
< 100 V: ± 1 digit (0.1 V)
Rated frequency of measuring signal 50/60 Hz
Frequency range of the measuring signal 40-70 Hz
Measuring principle True RMS
Max. reaction time (Measuring cycle CM-UFD.M21 + overvoltage U,,, U, < 65 ms
switching time of the relays) undervoltage U_, U__ < 65 ms
overfrequency F,,, F, < 65 ms
underfrequency F_, F__ < 65 ms
10 minutes average value per
depending on the voltage jump
phase UM
vector shift v5r < 50 ms
Accuracy within the rated control supply voltage tolerance ∆U ≤ 0.1 %
Accuracy within the temperature range ∆U ≤ 0.15 % / °C

14 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Feedback contacts Y0, Y1, Y2
Number 2
Kind of inputs signal source (Y0)
feedback loop section switch 1 (Y1)
feedback loop section switch 2 (Y2)
Electrical isolation from the supply voltage yes
from the measuring circuit no
from the relay outputs yes
from the transistor outputs yes
Type of triggering volt-free triggering
Max. switching current in the control circuit 4 mA
Max. cable length at the control input 5m
No-load voltage at the control inputs < 35 V DC
Feedback time section switch trEL 0.5-99.0 s, adjustable in 0.1 s steps

Control circuit vector shift detection Dj 1-Dj 2


Type of triggering volt-free triggering
Electrical isolation from the supply voltage yes
from the measuring circuit no
from the relay outputs yes
from the transistor outputs yes
Control input, control function jumpered = vector shift detection de-activated
open = vector shift detection activated (additional
configuration in the software is necessary)
Max. switching current in the control circuit 4 mA
Max. cable length at the control input 5m
No-load voltage at the control inputs < 35 V DC

Timing circuits
Start-up delay (prior to first grid connection) see 'adjustable OFF-delay' dof
Restart delay (after a short-term interruption <3 s) 5 s (fixed)
Tripping delay ON-and/or OFF-delay configurable
Adjustment range of the ON-delay over-/undervoltage, over-/
0.05-60.00 s, adjustable in 0.01 s steps
underfrequency dAL
Tolerance of the ON-delay 0.1 % ± 5 ms
Adjustment range of the OFF-delay over-/undervoltage, over-/
0 (>200 ms)-999 s, adjustable in 1 s steps
underfrequency doF
vector shift doF 3-240 s, adjustable in 1 s steps
Tolerance of the OFF-delay 0.1 % ± 105 ms
Delayed activation of the vector shift detection dEon 2-20 s, adjustable in 1 s steps
(Delay is effective just once after switching on or
restart)
Accuracy within the rated control supply voltage tolerance ∆t ≤ 0.01 %
Accuracy within the temperature range ∆t ≤ 0.0001 % / °C

User interface
Indication of operational states
See ‘LEDs, status information and fault messages’ on page 9

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 15


Output circuits
Relay outputs
Kind of outputs 11-12/14 Relay, 1st c/o (SPDT) contact
21-22/24 Relay, 2nd c/o (SPDT) contact
2 x 1 c/o (SPDT) contact
Operating principle closed-circuit principle
Contact material AgNi
Rated operational voltage Ue (IEC/EN 60947-1) 250 V AC
Minimum switching voltage / minimum switching current 12 V / 10 mA
Maximum switching voltage / maximum switching current 400 V AC / 6A
Rated operational current Ie(IEC/EN 60947-5-1) AC12 (resistive) 230 V 6A
AC15 (inductive) 230 V 1.5 A
DC12 (resistive) 24 V 6A
DC13 (inductive) 24 V 2A
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime at AC12, 230 V AC, 6 A 1 x 106 switching cycles
Maximum fuse rating to achieve short-circuit protection n/c contact 6 A, operating class gG/gL
n/o contact 6 A, operating class gG/gL
Conventional thermal current Ith (IEC/EN 60947-1) 6A

Transistor outputs
Number 5
Rated operational voltage Ue 24 V DC
Operational voltage range 4.5-27 V DC
Residual ripple 5%
Current state "0" max. 0.1 mA / output
state "1" max. 20 mA / output
Electrical isolation from the supply voltage yes
from the measuring circuit yes
from the relay outputs yes
from the inputs of the
yes
feedback contacts
Maximum fuse rating to achieve short-circuit protection 100 mA fast-acting

General data

MTBF on request
Duty time 100%
Dimensions (W x H x D) product dimensions 105 x 90 x 69 mm (4.13 x 3.54 x 2.72 in)
packaging dimensions 175 x 107 x 130 mm (6.89 x 4.21 x 5.12 in)
Weight net weight 0.225 kg (0.496 lb)
gross weight 0.343 kg (0.756 lb)
Mounting DIN rail (IEC/EN 60715) TH 35-7.5,
snap-on mounting without any tool
Mounting position any
Minimum distance to other units vertical not necessary
horizontal not necessary
Degree of protection housing / terminals IP30 / IP20

16 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Electrical connection
Wire size fine-strand with(out) wire end ferrule 1 x 0.5 - 2.5 mm² (1 x 20 - 14 AWG)
rigid 1 x 0.5 - 4 mm² (1 x 20 - 12 AWG)
Stripping length 7 mm (0.28 in)
Tightening torque 0.5 Nm (4.42 lb.in)

Environmental data
Ambient temperature ranges operation -20...+55 °C
storage -20…+70 °C
transport -20…+70 °C
Damp heat, cyclic (IEC 60068-2-30) 55 °C, 6 cycles
Climatic category (EN 50178) 3K3
Vibration, sinusoidal (IEC/EN 60255-21-1) Class 1
Shock (IEC/EN 60255-21-2) Class 1

Isolation data
Rated insulation voltage Ui supply/measuring/output circuits
300 V
(IEC/EN 60947-1, IEC/EN 60664-1) output circuit 1/output circuit 2
Rated impulse withstand voltage Uimp supply/measuring/output circuits
4 kV
(IEC/EN 60947-1, IEC/EN 60664-1) output circuit 1/output circuit 2
Basic insulation (IEC/EN 60664-1) supply/measuring/output circuits
300 V
output circuit 1/output circuit 2
Test voltage, routine test supply/measuring/output circuits
3820 V DC
(IEC/EN 60255-27, IEC/EN 61010-1) output circuit 1/output circuit 2
Test voltage, type test supply/measuring/output circuits
4600 V DC
(IEC/EN 60255-27) output circuit 1/output circuit 2
Protective separation supply/measuring/output circuits
300 V
(IEC/EN 61140, EN 50178) output circuit 1/output circuit 2
Pollution degree (IEC/EN 60664-1) 2
Overvoltage category (IEC/EN 60664-1) III

Standards / Directives
Product standard IEC/EN 60255
Application standards VDE-AR-N 4105, BDEW
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC

Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV / 8 kV
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (80-1000 MHz)
Level 2, 3 V/m (1400-2000 MHz)
Level 1, 1 V/m (2000-2700 MHz)
electrical fast transient / burst IEC/EN 61000-4-4 Level 4, 4 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 3, 1 kV L-L, 2kV L-earth
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3, 10 V
radio-frequency fields
Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 17


Technical diagrams

Load limit curves

V V
300 300
U 200 U 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30
20 20

2CDC 252 010 F0212

2CDC 252 011 F0212


10 10
0.1 0.2 0.5 1 2 4 6 10 0.1 0.2 0.5 1 2 5 10
I A I A

AC load (resistive) DC load (resistive)

107

Switching cycles

106

250 V AC
resistive load

105

2CDC 252 012 F0212


104
2 4 6 8 10 12 14 16
Switching current [A]

Contact lifetime

18 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet


Dimensions
in mm and inches

58 2.28”
48 1.89”
16.5 0.65”
61.8 2.43”
45 1.77”

90 3.54”

2CDC 252 008 F0012


3 0.12”

105 4.13”

Further documentation

Document title Document type Document number


Electronic products and relays Technical catalogue 2CDC 110 004 C020x
CM-UFD.M21 Grid feeding monitoring relay Instruction sheet 1SVC 510 810 M0000

You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products ->
Electronic Relays and Controls -> Three Phase Monitors.

Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 19


Contact us

ABB STOTZ-KONTAKT GmbH

Document number 2CDC 112 193 D0201 (07.2012)


P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-mail: info.desto@de.abb.com

You can find the address of your


local sales organisation on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems

Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.

We reserve all rights in this document and in


the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole
or in parts – is forbidden without prior written
consent of ABB AG.