Order data
Operating controls
1 2 3 4
5
6
8
9
11 10
4 11: yellow LED - 1st c/o (SPDT) contact energized L3: yellow LED - kind of measured value
21: yellow LED - 2nd c/o (SPDT) contact energized N: yellow LED - kind of measured value
5 Display (4-digits)
11 Status indication of device locking and sealable lock button
Voltage, 10 minutes average value, frequency or vector shift value, Red LED - device is locked
alarm and error messages
More details see ‘LEDs, status information and fault messages’ on page 9.
Operation
The CM-UFD.M21 can be used to monitor 3-wire as well as 4-wire AC systems. It provides 2 c/o (SPDT) contacts for
disconnection of the decentral electrical energy source from the public grid and two separate input contacts for the
feedback signal of the section switch in order to enable monitoring of the disconnection. Five transistor outputs allow
the signalling of the cause of alarm to a superior control system. The unit is adjusted by front-face setting buttons and a
display, which allows the visualization of measured values and alarms. Furthermore, the display enables the selection of
presettings as well as the precise adjustment of threshold values and delay times. To disable vector shift detection, jumper
terminals D j 1 and D j 2.
All operational states are shown on the display and signalled by the front-face LEDs. See table ‘Indication of operational
states’ on page 9.
Button Test
Pressing the front-face button Test de-energizes the output relays immediately in order to disconnect the decentral
electrical energy source from the public grid. If the input contacts Y0, Y1, Y2 for the feedback loop of the section switch are
connected and monitoring of the feedback signal is activated, the CM-UFD.M21 will display the disconnection time of the
system (reaction time of CM-UFD.M21 + tripping time of the section switch) until further pressing of any button.
∆ϕ1 ∆ϕ2
2CDC 252 016 F0012
To set-up vector shift detection vSr, go to menu mode and see ‘Control charts’ on page 7 for more details. The
detection can be configured to single-phase1PH, to trip in case of a vector shift in one of the three phase, or three-phase
3PH, to trip only in case of a simultaneous vector shift in all three phases. After applying control supply voltage or opening
contacts D j 1 and D j 2, the vector shift detection is suppressed for the duration of the adjusted suppression time dEon.
Set / Reset ►
Press shortly to display the next measured value / alarm counter.
Press for > 2 s to reset, quit error message.
Press for > 4 s to display the selected program (e.g. PR1).
Press for > 10 s to display the firmware version (e.g. 0-02).
Up / Down ▲▼
Press shortly to change to menu mode, display of alarm memory (button Down) or cumulative time of alarms (button Up).
Additional pressing of button Set for > 2 s makes a reset of the stored values. Press button Up / Down for > 2 s to display
the maximum / minimum measured values (device needs to be unlocked). Additional pressing of button Set for > 2 s
deletes the stored values.
Up / Down ▲▼
Press shortly to select menu item; return to display mode.
If more than 30 seconds pass before a key is pressed, the CM-UFD.M21 automatically returns to display mode.
Set / Reset ►
Press shortly to confirm and go to next parameter.
Press for > 2 s to confirm last entry and return to display mode.
Up / Down ▲▼
Press shortly / for a long time to modify the value slowly / rapidly.
Press buttons Up and Down simultaneously to set the adjusted value to zero.
If more than 30 seconds (in simulation mode 15 minutes) pass before a key is pressed, the CM-UFD.M21 automatically
applies the last entry and returns to display mode.
Simulation mode
The simulation mode allows the simulation of measured voltage and frequency values in order to check the settings and the
correct tripping of the CM-UFD.M21. During the simulation, alarm and error messages will only be displayed via LEDs. If the
device is sealed or locked, simulation is not possible. If the input contacts Y0, Y1, Y2 for the feedback loop of the section
switch are connected and monitoring of the feedback signal is activated, the CM-UFD.M21 will display the disconnection
time of the system (reaction time of CM-UFD.M21 + tripping time of section switch) until further pressing of any button.
To start simulation:
1. Change to menu mode and select Si (button Up / Down) and press button Set.
2. The display alternates between Si and the measurement parameter.
3. Select the measurement parameter to be simulated (button Up / Down) and press button Set.
4. The value of the simulated measurement parameter can be altered by pressing button Up / Down. Once the simulated
measurement value and the adjusted threshold value coincide, the output relays de-energize.
Note: The simulation of voltage values always takes into account the last set frequency value of simulation and vice versa.
To stop simulation:
Press button Set to return to menu mode. The CM-UFD.M21 continues to monitor the adjusted threshold values.
If more than 15 minutes pass before a key is pressed, the CM-UFD.M21 automatically returns to display mode.
Hint: If a threshold higher than the adjusted 10 minutes average value needs to be simulated, monitoring of UM has to be
temporarily deactivated. The same applies to U,, when simulating U,, , and to U_ when simulating U__ in PR3…PR6.
Alarm memory
The non-volatile alarm memory contains the last 99 alarms including simulated alarms. The LEDs indicate the cause of
alarm and the display alternates between tripping value and relative timestamp [hours].
To view the alarm memory, change to display mode and see ‘Control charts’ on page 7 for more details.
The alarm memory will only be reset when changing program.
Scan mode
The scan mode Scn allows the cyclic display of all measured values. The corresponding display duration dit for each
measured value is adjustable. To start scan mode, change to display mode and see ‘Control charts’ on page 7 for more
details. To change the display duration dit, go to menu mode and see ‘Control charts’ on page 7 for more details.
Code lock
The code lock can be activated to protect the adjusted parameters.
To set Pin and lock the device:
1. Change to menu mode and select CodE (button Up / Down) and press button Set
2. Enter Pin - default setting 504 (button Up / Down) and press button Set
An incorrect Pin will be notified by Err flashing three times
3. Set code lock to oFF or on (button Up / Down) and press button Set
4. Enter new Pin (button Up / Down) or go to 5.) to keep Pin unchanged
5. Press button Set to confirm
–– on flashing three times, code lock activated
–– oFF flashing three times, code lock deactivated
Sealing
The Lock button can be sealed to protected against unauthorized changes.
U <, U>, U>>, f<, f>, ϕ Y0-Y1 1st input contact for feedback signal
Connection diagram
Program setup
The suitable program must be set on the CM-UFD.M21 in accordance with the application. If the CM-UFD.M21 is sealed /
locked (red LED on), sealing has to be deactivated first.
Adjustment process:
If present, remove the seal (only authorized person)
1. Apply control supply voltage at A1-A2
2. Slightly lift the button cover and turn 180°
3. Actuate the small blue button by strong pressing on the button cover (LED starts flashing) until the flashing green LED
turns steady.
4. Press button Up 1x -> Display InFo
5. Press button Set / Reset 5x -> Display PR1
6. Set the program with the button Up / Down
7. Press button Set / Reset 1x -> Display no
8. Press button Down 1x -> Display yes
9. Press button Set / Reset
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to "default settings" (see ‘Default settings
and firmware version’ on page 11). Only change the parameters after having selected the correct program.
1) 3AC+N = 300 V
[ ] = Unit
1) 3AC+N = 300 V
[ ] = Unit
red/green LED
11-12/14, 21-22/24:
Backmost decimal
Time: yellow LED
Q1: red LED >U
N: yellow LED
Dj : red LED
Q5: red LED
yellow LED
Display
point
Function
Output relay energized V
Indication of time V
V
red: locked
Indication of device locking
green:
unlocked
Configuration mode X
AL N +
10 minutes average value (UN) V OFF OFF OFF OFF OFF OFF OFF
Measured value 2)
10 minutes average value (UN),
OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
ON-delay active
10 minutes average value (UN),
W OFF OFF OFF OFF OFF OFF V Time
OFF-delay active
AL +
Overvoltage (U>) V OFF OFF OFF OFF OFF OFF OFF
Measured value 2)
Overvoltage (U>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overvoltage (U>), OFF-delay active W OFF OFF OFF OFF OFF OFF V Time
AL +
Overvoltage (U>>) V OFF OFF OFF V OFF OFF OFF
Measured value 2)
Overvoltage (U>>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overvoltage (U>>), OFF-delay active W OFF OFF OFF W OFF OFF V Time
AL +
Undervoltage (U<) OFF V OFF OFF OFF OFF OFF OFF
Measured value 2)
Undervoltage (U<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Undervoltage (U<), OFF-delay active OFF W OFF OFF OFF OFF OFF V Time
AL +
Undervoltage (U<<) OFF V OFF OFF V OFF OFF OFF
Measured value 2)
Undervoltage (U<<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Undervoltage (U<<), OFF-delay active OFF W OFF OFF W OFF OFF V Time
AL +
Overfrequency (f>) OFF OFF V OFF OFF OFF OFF OFF
Measured value 2)
Overfrequency (f>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overfrequency (f>), OFF-delay active OFF OFF W OFF OFF OFF OFF V Time
AL +
Overfrequency (f>>) OFF OFF V OFF V OFF OFF OFF
Measured value 2)
Overfrequency (f>>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overfrequency (f>>), OFF-delay active OFF OFF W OFF W OFF OFF V Time
AL +
Underfrequency (f<) OFF OFF OFF V OFF OFF OFF OFF
Measured value 2)
Underfrequency (f<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Underfrequency (f<), OFF-delay active OFF OFF OFF W OFF OFF OFF V Time
AL +
Underfrequency (f<<) OFF OFF OFF V V OFF OFF OFF
Measured value 2)
Underfrequency (f<<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Underfrequency (f<<), OFF-delay active OFF OFF OFF W W OFF OFF V Time
AL +
Vector shift detection OFF OFF OFF OFF V OFF OFF
Measured value 2)
Vector shift detection, OFF-delay active OFF OFF OFF OFF W OFF V Time
Measured value (Voltage L1 against N) V OFF OFF V
1) In scan mode, all measured values are displayed cyclicIy. The display duration dit is adjustable.
2) The adjusted measured value is displayed.
L1
L2
L3 Low voltage grid
N
where applicable,
a transformer
m6 A
*)
A1 A2 11 21 L1 L2 L3 N
12 14 22 24 Y2 Y1 Y0
Expansion of existing installation:
in series with A
A
K1 K1
in series with B
B
K2 K2
Default settings
3 AC + N 3 AC + N 3 AC + N
3 AC 400 V 3 AC 100 V 3 AC 400V
230 V 57.7 V 230 V
Menu point Parameter Unit Pr1 * Pr2 Pr3 Pr4 Pr5 Pr6
doF: OFF-delay s - - 60 60 60 60
doF: OFF-delay s 60 60 60 60 60 60
doF: OFF-delay s 60 60 60 60 60 60
doF: OFF-delay s 60 60 60 60 60 60
3 AC + N 3 AC + N 3 AC + N
3 AC 400 V 3 AC 100 V 3 AC 400V
230 V 57.7 V 230 V
Menu point Parameter Unit Pr1 * Pr2 Pr3 Pr4 Pr5 Pr6
doF: OFF-delay s 60 60 60 60 60 60
Err9 appears in the display Configuration error Reset to factory settings, see ‚Program setup‘
on page 6
A time expires in the display If an OFF-delay dof is active, the time runs Wait until the time is complete (depending on
down in the display (the shortest one first) the setting, several times may elapse one after
the other)
Device cannot be configured / only the Code lock / Sealing activated When having problems with the code lock (Pin
threshold values can be configured forgotten), the lock can be deactivated and the
Pin can be reset to 504, by pressing the button
► until Code / off is shown in the display,
while switching on the control supply voltage.
Implausible voltage values Pr selected with N, but N not connected Select Pr without N or connect N
Loc appears in the display Sealing is active See ‚Program setup‘ on page 6
Code appears in the display Code lock is active See ‚Code lock‘ on page 5
Input circuits
Type CM-UFD.M21
Supply circuit A1-A2
Rated control supply voltage Us 24-240 V AC/DC
Rated control supply voltage Us tolerance -15...+20 %
Rated frequency DC and 50/60 Hz respectively
Frequency range AC 40-70 Hz
Typical current / power consumption 24 V DC 92 mA / 2.2 W
230 V AC 25 mA / 5.7 VA
Power failure buffering time 5 ms
Timing circuits
Start-up delay (prior to first grid connection) see 'adjustable OFF-delay' dof
Restart delay (after a short-term interruption <3 s) 5 s (fixed)
Tripping delay ON-and/or OFF-delay configurable
Adjustment range of the ON-delay over-/undervoltage, over-/
0.05-60.00 s, adjustable in 0.01 s steps
underfrequency dAL
Tolerance of the ON-delay 0.1 % ± 5 ms
Adjustment range of the OFF-delay over-/undervoltage, over-/
0 (>200 ms)-999 s, adjustable in 1 s steps
underfrequency doF
vector shift doF 3-240 s, adjustable in 1 s steps
Tolerance of the OFF-delay 0.1 % ± 105 ms
Delayed activation of the vector shift detection dEon 2-20 s, adjustable in 1 s steps
(Delay is effective just once after switching on or
restart)
Accuracy within the rated control supply voltage tolerance ∆t ≤ 0.01 %
Accuracy within the temperature range ∆t ≤ 0.0001 % / °C
User interface
Indication of operational states
See ‘LEDs, status information and fault messages’ on page 9
Transistor outputs
Number 5
Rated operational voltage Ue 24 V DC
Operational voltage range 4.5-27 V DC
Residual ripple 5%
Current state "0" max. 0.1 mA / output
state "1" max. 20 mA / output
Electrical isolation from the supply voltage yes
from the measuring circuit yes
from the relay outputs yes
from the inputs of the
yes
feedback contacts
Maximum fuse rating to achieve short-circuit protection 100 mA fast-acting
General data
MTBF on request
Duty time 100%
Dimensions (W x H x D) product dimensions 105 x 90 x 69 mm (4.13 x 3.54 x 2.72 in)
packaging dimensions 175 x 107 x 130 mm (6.89 x 4.21 x 5.12 in)
Weight net weight 0.225 kg (0.496 lb)
gross weight 0.343 kg (0.756 lb)
Mounting DIN rail (IEC/EN 60715) TH 35-7.5,
snap-on mounting without any tool
Mounting position any
Minimum distance to other units vertical not necessary
horizontal not necessary
Degree of protection housing / terminals IP30 / IP20
Environmental data
Ambient temperature ranges operation -20...+55 °C
storage -20…+70 °C
transport -20…+70 °C
Damp heat, cyclic (IEC 60068-2-30) 55 °C, 6 cycles
Climatic category (EN 50178) 3K3
Vibration, sinusoidal (IEC/EN 60255-21-1) Class 1
Shock (IEC/EN 60255-21-2) Class 1
Isolation data
Rated insulation voltage Ui supply/measuring/output circuits
300 V
(IEC/EN 60947-1, IEC/EN 60664-1) output circuit 1/output circuit 2
Rated impulse withstand voltage Uimp supply/measuring/output circuits
4 kV
(IEC/EN 60947-1, IEC/EN 60664-1) output circuit 1/output circuit 2
Basic insulation (IEC/EN 60664-1) supply/measuring/output circuits
300 V
output circuit 1/output circuit 2
Test voltage, routine test supply/measuring/output circuits
3820 V DC
(IEC/EN 60255-27, IEC/EN 61010-1) output circuit 1/output circuit 2
Test voltage, type test supply/measuring/output circuits
4600 V DC
(IEC/EN 60255-27) output circuit 1/output circuit 2
Protective separation supply/measuring/output circuits
300 V
(IEC/EN 61140, EN 50178) output circuit 1/output circuit 2
Pollution degree (IEC/EN 60664-1) 2
Overvoltage category (IEC/EN 60664-1) III
Standards / Directives
Product standard IEC/EN 60255
Application standards VDE-AR-N 4105, BDEW
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV / 8 kV
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (80-1000 MHz)
Level 2, 3 V/m (1400-2000 MHz)
Level 1, 1 V/m (2000-2700 MHz)
electrical fast transient / burst IEC/EN 61000-4-4 Level 4, 4 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 3, 1 kV L-L, 2kV L-earth
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3, 10 V
radio-frequency fields
Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
V V
300 300
U 200 U 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30
20 20
107
Switching cycles
106
250 V AC
resistive load
105
Contact lifetime
58 2.28”
48 1.89”
16.5 0.65”
61.8 2.43”
45 1.77”
90 3.54”
105 4.13”
Further documentation
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products ->
Electronic Relays and Controls -> Three Phase Monitors.
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.