SLC 500 Hardware Migration

Bulletins 1746, 1747, 1769, 5069

Reference Manual Original Instructions


SLC 500 Hardware Migration Reference Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which
may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).

2 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Table of Contents

Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Required Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter 1
Overview Product Lifecycle Status Website . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SLC 500 System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CompactLogix 5370 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CompactLogix 5380 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Compact I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compact 5000 I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SLC 500 Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
CompactLogix 5380 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Sensor Actuator Power for CompactLogix 5380 . . . . . . . . . . . . . . . . . 15
Other Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Chapter 2
Replace an SLC 500 Controller Upgrade to a CompactLogix 5370 Controller . . . . . . . . . . . . . . . . . . . . . . . 17
Upgrade to a CompactLogix 5380 Controller . . . . . . . . . . . . . . . . . . . . . . . 18

Chapter 3
Replace an SLC 500 I/O Module Upgrade an SLC I/O Installation by Replacing it with Compact I/O . . 19
Upgrade an SLC I/O Installation by Replacing it with
Compact 5000 I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SLC I/O Installation Using a Conversion Kit. . . . . . . . . . . . . . . . . . . . 25

Appendix A
Wiring Diagram Comparisons Replace an SLC 5 Processor Serial Port with a Compact
I/O Serial Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
SLC 5/03, SLC 5/04, or SLC 5/05 to 5069-SERIAL . . . . . . . . . . . . . 27
Replace an SLC 500 I/O with a Compact I/O . . . . . . . . . . . . . . . . . . . . . . . 28
1746-IA4 to 1769-IA8I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1746-IA8 to 1769-IA8I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1746-IA16 to 1769-IA16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1746-IB8 to 1769-IQ16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1746-IB16 to 1769-IQ16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1746-IG16 to 1769-IG16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1746-IM4 to 1769-IM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1746-IM8 to 1769-IM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1746-IM16 to 1769-IM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 3


Table of Contents

1746-ITB16 to 1769-IQ16F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1746-ITV16 to 1769-IQ16F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1746-IV8 to 1769-IQ16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1746-IV16 to 1769-IQ16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1746-OA8 to 1769-OA8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1746-OA16 to 1769-OA16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1746-OB8 to 1769-OB8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1746-OB16 to 1769-OB16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1746-OB16E to 1769-OB16P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1746-OBP8 to 1769-OB8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1746-OG16 to 1769-OG16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1746-OV8 to 1769-OV16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1746-OV16 to 1769-OV16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1746-OW4 to 1769-OW8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1746-OW8 to 1769-OW8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1746-OW16 to 1769-OW16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1746-IO12DC to 1769-IQ6XOW4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1746-NI4 to 1769-IF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
1746-NIO4I to 1769-IF4XOF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
1746-NIO4V to 1769-IF4XOF2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
1746-NI8 to 1769-IF8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
1746-NO4I to 1769-OF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1746-NO4V to 1769-OF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Replace an SLC 500 I/O with a Compact 5000 I/O . . . . . . . . . . . . . . . . . . 44
1746-IA16 to 5069-IA16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
1746-IM16 to 5069-IA16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
1746-IB16 to 5069-IB16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
1746-ITB16 to 5069-IB16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
1746-OA8 to 5069-OA16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
1746-OA16 to 5069-OA16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
1746-OB8 to 5069-OB8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
1746-OBP8 to 5069-OB8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
1746-OBP16 to 5069-OB16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
1746-OB16 to 5069-OB16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
1746-OB16E to 5069-OB16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
1746-OW4 to 5069-OW4I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
1746-OW8 to 5069-OW4I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
1746-OW16 to 5069-OW16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
1746-OX8 to 5069-OX4I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
1746-NI4 to 5069-IY4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
1746-NI8 to 5069-IF8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
1746-NO4I to 5069-OF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
1746-NO4V to 5069-OF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Replace an SLC 500 I/O with Combinations of Compact 5000 I/O. . . . 54
Indirect Wiring Migration for 1746-IA4 to 5069-IA16 . . . . . . . . . . . . 54
Indirect Wiring Migration for 1746-IA8 to 5069-IA16 . . . . . . . . . . . . 56
Indirect Wiring Migration for 1746-IB8 to 5069-IB16 . . . . . . . . . . . . 57
Indirect Wiring Migration for 1746-IM4 to 5069-IA16 . . . . . . . . . . . . 59
Indirect Wiring Migration for 1746-IM8 to 5069-IA16. . . . . . . . . . . . 60

4 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Table of Contents

Indirect Wiring Migration for 1746-IO4 to 5069-IA16


and 5069-OW16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Indirect Wiring Migration for 1746-IO8 to 5069-IA16
and 5069-OW16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Indirect Wiring Migration for 1746-IO12 to 5069-IA16
and 5069-OW16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Indirect Wiring Migration for 1746-NI16I to 5069-IF8 . . . . . . . . . . . 68
Indirect Wiring Migration for 1746-NI16V to 5069-IF8 . . . . . . . . . . . 69
Indirect Wiring Migration for 1746-NIO4I to 5069-OF4
and 5069-IY4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Indirect Wiring Migration for 1746-NIO4V to 5069-OF4
and 5069-IY4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Indirect Wiring Migration for 1746-NR8 to 5069-IY4 . . . . . . . . . . . . 74
Indirect Wiring Migration for 1746-OB8 to 5069-OB16 . . . . . . . . . . . 75
Indirect Wiring Migration for 1746-OBP8 to 5069-OB16 . . . . . . . . . 77
Indirect Wiring Migration for 1746-OW4 to 5069-OW16 . . . . . . . . . 78

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 5


Table of Contents

Notes:

6 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Preface

About This Publication This document serves as a guide for replacing your existing SLC™ 500 modules
with other products such as Compact I/O™ modules, or Compact 5000™ I/O
modules.

The SLC 500 Control system hardware was redesigned to be RoHS compliant.
As a result, several of the products will continue to be available for years to
come, however, some products, such as less capable controllers and lower
density I/O, have been discontinued.

The SLC™ control platform in general is in the Active Mature lifecycle state, as
the newer CompactLogix™ and Compact 5000 platforms provide greater
functionality and connectivity.

The following chapters of this document describe the many SLC,


CompactLogix, and I/O options available for active management of your
installed base of control products. You have the option of maintaining,
migrating, or replacing that installed base in a phased manner to meet your
needs.

This document focuses on hardware migration. For more detailed


information, including instructions for converting an SLC program to a Logix
program, see SLC to CompactLogix Programming Migration Guide,
publication 5069-AP001.

Audience This document is intended for users of SLC 500 controllers and I/O modules
who are familiar with the RSLogix 500® programming software.

Required Software If the replacement is an SLC 500 controller or I/O module, no additional
software is required.

If the replacement is a CompactLogix 5370 controller, CompactLogix 5380


controller, Compact I/O module, or Compact 5000 I/O module, the following
are required:
• Studio 5000 environment

The Studio 5000® environment combines elements of design into one


standard framework that optimizes productivity and reduces time to
commission.

With the Studio 5000 Applications you can:


- Build and maintain a system layout in a central place with
Studio 5000 Architect®
- Configure, program, and maintain your Logix 5000™ family of
controllers with Studio 5000 Logix Designer®
- Create intuitive, modern screens for the PanelView™ 5000 graphic
terminals with Studio 5000 View Designer®

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 7


Preface

- Create and leverage reusable libraries of content for rapid project


development with Application Code Manager

The following CompactLogix controllers are compatible with


Studio 5000 Applications:

Controllers Cat. No. Studio 5000 Logix Designer Application


5069-L306ER, 5069-L306ERM, 5069-
L310ER, 5069-L310ERM, 5069-L310ER-
NSE,
5069-L320ER, 5069-L320ERM, 5069-
L320ERMK, 5069-L330ER, 5069-
L330ERM,
5069-L330ERMK, 5069-L340ER, 5069-
L340ERM, 5069-L350ERM, 5069-
L350ERMK,
5069-L380ERM, 5069-L3100ERM
CompactLogix 5380 / 5069-L306ERS2, 5069-L306ERMS2, Version 29.00.00 or later
Compact GuardLogix 5380 5069-L310ERS2, 5069-
L310ERMS2,5069-L320ERS2,
5069-L320ERMS2, 5069-L330ERS2,
5069-L330ERMS2, 5069-L340ERS2,
5069-L340ERMS2, 5069-L350ERS2,
5069-L350ERMS2, 5069-L380ERS2,
5069-L380ERMS2, 5069-L3100ERS2,
5069-L3100ERMS2, 5069-L320ERS2K,
5069-L320ERMS2K, 5069-L330ERS2K,
5069-L330ERMS2K, 5069-L350ERS2K,
5069-L350ERMS2K
For CompactLogix 5370 controllers
using firmware revision 21.00.00 or Version 21.00.00 or later
CompactLogix 5370 later
1769-L19ER-BB1B Version 28.00.00 or later
• RSLogix 500/RSLogix Micro version 12 or RSLogix Project Migrator

The RSLogix 500/RSLogix™ Micro version 12 software includes an


integrated SLC to CompactLogix program converter tool. To convert,
simply perform a Save Program As, then select file type as *.ACD, and fill
out the menu prompts.

For older versions of RSLogix 500/RSLogix Micro, the RSLogix™ Project


Migrator tool is a free, standalone software tool for converting an
RSLogix 5 or RSLogix 500 project export file for import into Studio 5000
Logix Designer application.

The standalone converter tool is available for download at: rok.auto/pcdc.

Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.

Topic Page
Updated Recommended Compact 5000 I/O Replacement modules 23…24
Added indirect wiring solutions with combinations of Compact 5000 I/O modules 54…80

8 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Preface

Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.

Resource Description
SLC 500 Analog Input Module Installation Instructions, publication 1746-IN006 Installation instructions for the SLC 500 Analog Input Module (Cat. No. 1746-NI8).
SLC 500 RTD/Resistance Input Module Installation Instructions, publication 1746- Installation instructions for the SLC 500 RTD/Resistance Input Module (Cat. No. 1746-NR8).
IN007
SLC 500 RTD/Resistance Input Module Installation Instructions, publication 1746- Installation instructions for the SLC 500 RTD/Resistance Input Module (Cat. No. 1746-NR4).
IN012
SLC 500 Thermocouple/mV Analog Input Module Installation Instructions, publication Installation instructions for the SLC 500 Thermocouple/mV Analog Input Module.
1746-IN015
SLC 500 8-Point Analog Output Module Installation Instructions, publication 1746- Installation instructions for SLC 500 8-point analog output modules.
IN026
SLC 500 Digital I/O Modules Installation Instructions, publication 1746-IN027 Installation Instructions for SLC 500 digital I/O modules.
SLC 500 4-Channel Analog I/O Modules User Manual, publication 1746-UM005 A more detailed description on how to configure the SLC 500 analog I/O modules.
SLC 500 4-Channel Thermocouple/mV Input Module User Manual, publication 1746- A more detailed description on how to configure the SLC 500 4-Channel Thermocouple/mV Input
UM007 Module.
SLC 500 Systems Selection Guide, publication 1747-SG001 An overview of the SLC 500 family of products.
SLC to CompactLogix Programming Migration Guide, publication 5069-AP001 Provides information on converting an SLC program to a Logix program and migrating the existing SLC
I/O to an Ethernet network.
CompactLogix Controllers Specifications Technical Data, publication 1769-TD005 Provides CompactLogix controllers specifications.
Compact I/O Modules Specifications Technical Data, publication 1769-TD006 Provides Compact I/O Modules specifications.
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Provides CompactLogix, Compact GuardLogix, and CompactLogix controllers specifications.
Specifications Technical Data, publication 5069-TD002
CompactLogix 5370 Controllers User Manual, publication 1769-UM021 Describes how to install, use, and troubleshoot CompactLogix 5370 controllers.
CompactLogix 5380 Controllers User Manual, publication 5069-UM001 Describes how to install, use, and troubleshoot CompactLogix 5380 controllers and Compact
GuardLogix 5380 controllers.
Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication Provides Compact 5000 I/O and EtherNet/IP adapter specifications.
5069-TD001
Compact 5000 I/O Serial Module User Manual, publication 5069-UM003 Describes how to install, use, and troubleshoot a Compact 5000 I/O serial module.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 9


Preface

Notes:

10 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 1

Overview

Product Lifecycle Status The Rockwell Automation Product Lifecycle Status website allows you to pro-
Website actively plan and manage the transition from existing equipment to leading-
edge products and technologies. Using the search tool, you can view up-to-date
product lifecycle status and identify the most contemporary Rockwell
Automation products.

The product lifecycle status may be Active, Active Mature, End of Life, or
Discontinued.

To view the lifecycle information for a product:


1. On your web browser, open the Product Lifecycle Status website:
https://www.rockwellautomation.com/en-us/support/product/product-
compatibility-migration/product-lifecycle-status.html.
2. In the Catalog Number field, enter the catalog number of the product.

3. Click Search.
The product lifecycle data displays.

If the lifecycle status of the product is End of Life or Discontinued, you


can view the recommended replacement.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 11


Chapter 1 Overview

SLC 500 System The SLC 500 system is a small chassis-based family of programmable
controllers, discrete, analog, and specialty I/O, and peripheral devices. The SLC
500 family delivers power and flexibility with a wide range of communication
configurations, features, and memory options.

SLC 500 programmable controllers provide value with extensive capabilities to


address a broad range of applications including material handling, HVAC
control, high-speed assembly operations, small process control, simple motion
control, and SCADA. With SLC 500 Modular Hardware Style controllers, you
select the processor, power supply, and I/O modules to fit your application.
Modular style chassis are available in 4, 7, 10, and 13-slot versions.

Digital I/O modules, analog I/O modules, and specialty temperature, counting,
and process control modules are available to help you create a custom solution
for your application.

CompactLogix 5370 CompactLogix 5370 controllers provide scalable controller solutions to address
Controllers a wide variety of applications. All CompactLogix 5370 controllers provide the
following functionality:
• Two EtherNet/IP™ ports
• One USB port
• Support for local expansion modules
• Control of local and distributed I/O modules
• Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile
memory
• A battery is no longer necessary because of the internal energy-storage
solution

Some CompactLogix 5370 controllers provide the following functionality:


• Built-in power supply
• Some combination of embedded digital, analog, and high-speed counter
modules
• Support for Integrated Motion over an EtherNet/IP network
• Access to DeviceNet® networks.

CompactLogix 5380 CompactLogix 5380 controllers can operate in various applications that range
Controllers from standalone systems or in more complex systems with devices that are
connected to the controller via an EtherNet/IP network. All CompactLogix
5380 controllers provide the following functionality:
• Two EtherNet/IP ports
• One USB port
• Support for local expansion modules
• Control of local and distributed I/O modules
• Support Device Level Ring (DLR), Star, and Linear EtherNet/IP network
topologies.
• Support up to 180 EtherNet/IP nodes, depending on catalog number.
• Support Linear/DLR and Dual-IP EtherNet/IP modes.

12 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 1 Overview

• Support Generic ASCII, Modbus RTU/ASCII, and legacy DF1 and DH-485
protocols.

Some CompactLogix 5380 controllers provide the following functionality:


• Support for Integrated Motion up to 32 axes over an EtherNet/IP
network

Compact I/O Modules The Compact I/O modules can be used in the following applications:
• With a CompactLogix controller
• In an assembly with a 1769-ADN DeviceNet adapter
• In an assembly with a 1769-AENTR Ethernet adapter.

Each I/O module includes a built-in removable terminal block with fingersafe
cover for connections to I/O sensors and actuators. The terminal block is
behind a door at the front of the module. I/O wiring can be routed from
beneath the module to the I/O terminals.
• Once the modules are locked together, the system becomes a rugged
assembly.
• Upper and lower tongue-and-groove slots guide the module during
installation and secure the module within the system.
• Removable terminal blocks help ease the wiring task.
• Self-lifting, field-wire pressure plates cut installation time.
• The patented bus connector with the lock function enables consistent
system communication.
• A color bar is provided on the front of the module.
• Digital and field circuits are optically isolated.

Compact 5000 I/O Modules The Compact 5000 I/O architecture provides a wide range of input and output
modules to span many applications, from high-speed digital to process
control. The architecture uses Producer/Consumer technology that allows
input information and output status to be shared among multiple
Logix 5000 controllers.

Compact 5000 I/O systems are used as local I/O modules in


CompactLogix 5380 controller systems or as remote I/O modules with
CompactLogix 5380 controllers and some other Logix 5000 controllers. The
modules are configured with the Studio 5000 Logix Designer application.

The serial module provides two independent channels that function as


network interface using RS232C, RS422, or RS485 to serial devices
communicating on Generic ASCII, Modbus RTU/ASCII, DF1, or DH-485
protocol.

The I/O module requires a removable terminal block (RTB) to connect field-
side wiring. RTBs are not included with the I/O modules. You must order
RTBs separately.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 13


Chapter 1 Overview

Power Considerations SLC 500 Controllers


The SLC 500 controllers require an SLC power supply module on the leftmost
slot to provide power to all modules on the chassis. This powers up the
controller and the I/O modules. This also facilitates communication through
the backplane.

Though all 1746 input modules and most 1746 output modules receive the
necessary power that they need from the backplane, some 1746 output
modules, such as relay modules and AC modules, require additional power to
be supplied to the module terminal block.

CompactLogix 5380 Controllers

The CompactLogix 5380 controllers require a 24V DC source supply that is


connected to the MOD power terminal to provide power to all modules. Unlike
the SLC 500 controller, the CompactLogix 5380 controller does not require
a chassis.

Backplane connection is at the side of each module and it is necessary to cover


the side with a 5069-ECR end cap (shipped with the CompactLogix 5380
controllers and Compact 5000 EtherNet/IP adapters) to help prevent
electrical hazards.

The 24V DC source to MOD power terminal can be from any external power
supply. You do not require additional power supply connections to each I/O
module(1) if connecting field devices are in the same operating voltage range.

For more information about MOD power and SA power considerations, see
chapter 2 of the CompactLogix 5380 and Compact GuardLogix® 5380
Controllers User Manual, 5069-UM001.

(1) Except for 5069-OB8, 5069-OB16 and 5069-OB16F.

14 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 1 Overview

Sensor Actuator Power for CompactLogix 5380

The CompactLogix 5380 I/O power system has a common sensor actuator (SA)
bus where a single power source can be shared among all attaching I/O
modules using the backplane. This helps reduce wiring effort and is
convenient if all I/O devices operate at the same operating voltage. If the SA
has two different operating voltages (see following figures), the SA power bus
can be separated with a Field Potential Distributor Module, such as the 5069-
FPD.

The CompactLogix 5380 I/O power system if sensors/actuators have a common operating voltage.

The CompactLogix 5380 I/O power system if sensors/actuators have different operating voltages.

IMPORTANT The 5069-OW16 module uses DC SA power. You must connect DC power to
the component, that is, controller, adapter, or field potential distributor, that
provides SA power to the module.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 15


Chapter 1 Overview

Other Considerations

The SLC 500 system was designed more than 30 years ago and electronic
components have evolved over time. To help avoid potential electromagnetic
interference (EMI) and transient EMI that could cause problems in your
existing system conversion, see the Industrial Automation Wiring and
Grounding Guidelines, publication 1770-IN041.

To fully migrate your SLC 500 systems you also need to convert your SLC 500
application code. For more information on software conversion, see the SLC to
CompactLogix Programming Migration Guide, publication 5069-AP001.

16 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 2

Replace an SLC 500 Controller

This chapter provides information about the recommended replacement for


your existing SLC 500 controller.

Due to the discontinuation of SLC 5/01 and SLC 5/02 controllers in


January 2017, a replacement CompactLogix controller is recommended.

You can view the lifecycle status of your SLC product on the Rockwell
Automation Product Lifecycle Status website:

https://www.rockwellautomation.com/en-us/support/product/product-
compatibility-migration/product-lifecycle-status.html.

Upgrade to a CompactLogix Table 1 lists the recommended replacement CompactLogix 5370 controller to
5370 Controller your existing SLC 500 controller. These recommendations exclude Motion and
Safety applications, consult your local sales office for more info.

Table 1 - Recommended CompactLogix 5370 Replacement Controllers


Recommended CompactLogix
Catalog Number SLC Controller Description CompactLogix 5370 Controller Description
5370 Controller Replacement (1)
1747-L511 SLC 5/01 1K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L514 SLC 5/01 4K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L524 SLC 5/02 4K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L531 SLC™ 5/03 8K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L532 SLC 5/03 16K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L533 SLC 5/03 32K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L541 SLC 5/04 16K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L542 SLC 5/04 32K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L543 SLC 5/04 64K Controller 1769-L30ER CompactLogix 5370 L3 Controller, 1 MB Memory, Dual Ethernet Port - SD Card
1747-L551 SLC 5/05 16K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L552 SLC 5/05 32K Controller 1769-L24ER-QB1B CompactLogix 5370 L2 Controller, 750 KB Memory, 16 DC Inputs, 16 DC Outputs
1747-L553 SLC 5/05 64K Controller 1769-L30ER CompactLogix 5370 L3 Controller, 1 MB Memory, Dual Ethernet Port - SD Card
(1) The general rule of thumb for memory estimation can be found under “SLC to Logix Memory Comparison” in the SLC to CompactLogix Programming Migration Guide, publication 5069-AP001.
Alternatively, you may validate the controller based on memory estimation by the code conversion tool (RSLogix Project Migrator).

For technical specifications of the recommended CompactLogix 5370


controller, see CompactLogix Controllers Specifications Technical Data,
publication 1769-TD005.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 17


Chapter 2 Replace an SLC 500 Controller

Upgrade to a CompactLogix Table 2 lists the recommended replacement CompactLogix 5380 controller to
5380 Controller your existing SLC 500 controller. These recommendations exclude Motion
applications, consult your local sales office for more information.

Table 2 - Recommended CompactLogix 5380 Replacement Controllers

Catalog Number SLC Controller Description Recommended CompactLogix CompactLogix 5380 Controller Description
5380 Controller Replacement

1747-L511 SLC 5/01 1K Controller 5069-L306ER(1)(2) CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard

1747-L514 SLC 5/01 4K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L524 SLC 5/02 4K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L531 SLC 5/03 8K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L532 SLC 5/03 16K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L533 SLC 5/03 32K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L541 SLC 5/04 16K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L542 SLC 5/04 32K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L543 SLC 5/04 64K Controller 5069-L310ER CompactLogix 5380 Controller, 1 MB, 8 I/O, 24 nodes, Standard
1747-L551 SLC 5/05 16K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L552 SLC 5/05 32K Controller 5069-L306ER CompactLogix 5380 Controller, 600 KB, 8 I/O, 16 nodes, Standard
1747-L553 SLC 5/05 64K Controller 5069-L310ER CompactLogix 5380 Controller, 1 MB, 8 I/O, 24 nodes, Standard
(1) To include safety on the control, you can upgrade any recommended CompactLogix 5380 replacement controller to Compact GuardLogix 5380 SIL 2 and Compact GuardLogix 5380 SIL 3 safety
controllers.
(2) The general rule of thumb for memory estimation can be found under “SLC to Logix Memory Comparison” in the SLC to CompactLogix Programming Migration Guide, publication 5069-AP001.
Alternatively, you can validate the controller based on memory estimation by the code conversion tool (RSLogix Project Migrator).

For technical specifications of the recommended CompactLogix 5380


controller, see CompactLogix Controllers Specifications Technical Data,
publication 5069-TD002.

18 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 3

Replace an SLC 500 I/O Module

This chapter provides information about the recommended replacement for


your existing SLC 500 I/O module.

The lifecycle status for Rockwell Automation products is maintained and


published in the Rockwell Automation Product Lifecycle Status website:
https://www.rockwellautomation.com/en-us/support/product/product-
compatibility-migration/product-lifecycle-status.html.

Upgrade an SLC I/O Table 3 lists the recommended replacement Compact I/O module to your
Installation by Replacing it existing SLC 500 I/O module.
with Compact I/O Before upgrading, take note of the following:
• When replacing an SLC I/O with a Compact I/O, a CompactLogix 5370
controller must be used.
• There might be technical differences between the SLC I/O and
Compact I/O. Verify the specifications to meet your application needs.
For wiring diagrams and technical specifications of Compact I/O
modules, see Compact I/O Modules Specifications Technical Data,
publication 1769-TD006.
Table 3 - Recommended Compact I/O Replacement
Recommended
Module Type Catalog Number (1) SLC Module Description Compact I/O Compact I/O Module Description
Replacement(2)
1746-IA4 100/120V AC, 4 120V AC input module 1769-IA8I 8 inputs, individually isolated, 100/120V AC input module
1746-IA8 100/120V AC, 8 120V AC input module 1769-IA8I 8 inputs, individually isolated, 100/120V AC input module
1746-IA16 100/120V AC, 16 120V AC input module 1769-IA16 16 inputs, 100/120V AC input module
1746-IB8 24V DC, 8 current sinking DC input module 1769-IQ16 16 inputs, 24V DC sink/source input module
1746-IB16 24V DC, 16 current sinking DC input module 1769-IQ16 16 inputs, 24V DC sink/source input module
1746-IB32 24V DC, 32 current sinking DC input module 1769-IQ32 32 inputs, 24V DC sink/source input module
1746-IC16 48V DC, 16 current sinking DC input module No replacement —
Digital input
1746-IG16 5V DC, 16 current sourcing TTL input module 1769-IG16 16 inputs, 5V DC TTL input module
1746-IH16 125V DC, 16 current sinking DC input module No replacement —
1746-IM4 200/240V AC, 4 240V AC input module 1769-IM12 12 inputs, 200/240V AC input module
1746-IM8 200/240V AC, 8 240V AC input module 1769-IM12 12 inputs, 200/240V AC input module
1746-IM16 200/240V AC, 16 240V AC input module 1769-IM12 12 inputs, 200/240V AC input module
1746-IN16 24V AC/DC, 16 24V AC/DC input module No replacement —
1746-ITB16 24V DC, 16 fast response DC sinking input module 1769-IQ16F 16 inputs, high-speed 24V DC sink/source digital input module

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 19


Chapter 3 Replace an SLC 500 I/O Module

Table 3 - Recommended Compact I/O Replacement (Continued)


Recommended
Module Type Catalog Number (1) SLC Module Description Compact I/O Compact I/O Module Description
Replacement(2)
1746-ITV16 24V DC, 16 fast response DC sourcing input module 1769-IQ16F 16 inputs, high-speed 24V DC sink/source digital input module

Digital input 1746-IV8 24V DC, 8 current sourcing DC input module 1769-IQ16 16 inputs, 24V DC sink/source input module
(cont.) 1746-IV16 24V DC, 16 current sourcing DC input module 1769-IQ16 16 inputs, 24V DC sink/source input module
1746-IV32 24V DC, 32 current sourcing DC input module 1769-IQ32 32 inputs, 24V DC sink/source input module
1746-OA8 120/240V AC, 8 120/240V AC output module 1769-OA8 8 outputs, 100/240V AC input module
1746-OA16 120/240V AC, 16 120/240V AC output module 1769-OA16 16 outputs, 100/240V AC input module
1746-OAP12 120/240V AC, 12 high current 120/240V AC output module No replacement —

1746-OB6EI 24V DC, 6 electronically protected isolated sourcing DC No replacement —


output module
1746-OB8 24V DC, 8 current sourcing DC output module 1769-OB8 8 outputs, 24V DC source output module
1746-OB16 24V DC, 16 current sourcing DC output module 1769-OB16 16 outputs, 24V DC source output module
24V DC, 16 electronically protected current sourcing DC
1746-OB16E output module 1769-OB16P 16 outputs, protected, 24V DC source output module

1746-OB32 24V DC, 32 current sourcing DC output module 1769-OB32 32 outputs, 24V DC source output module
24V DC, 32 electronically protected current sourcing DC
1746-OB32E No replacement —
output module
Digital output
1746-OBP8 24V DC, 8 high current sourcing DC output module 1769-OB8 8 outputs, 24V DC source output module
1746-OBP16 24V DC, 16 high current sourcing DC output module No replacement —
1746-OG16 5V DC, 16 current sourcing TTL output module 1769-OG16 16 outputs, 5V DC TTL output module
1746-OV8 24V DC, 8 current sinking DC output module 1769-OV16 16 outputs, 24V DC sink output module
1746-OV16 24V DC, 16 current sinking DC output module 1769-OV16 16 output, 24V DC sink output module
1746-OV32 24V DC, 32 current sinking DC output module 1769-OV32T 32 terminated outputs, 24V DC sink output module
1746-OVP16 24V DC, 16 high current sinking DC output module No replacement —
1746-OW4 AC/DC relay, 4 relay (hard contact) output module 1769-OW8 8 outputs, 5…265V AC/5…125V DC relay output module
1746-OW8 AC/DC relay, 8 relay (hard contact) output module 1769-OW8 8 outputs, 5…265V AC/5…125V DC relay output module
1746-OW16 AC/DC relay, 16 relay (hard contact) output module 1769-OW16 16 outputs, 5…265V AC/5…125V DC relay output module
1746-OX8 AC/DC relay, 8 relay (hard contact) output module No replacement —

1746-IO4 120V AC (inputs), 100/120V AC (relay contact outputs), 2-in, No replacement —


2-out combination input/output module
120V AC (inputs), 100/120V AC (relay contact outputs), 4-in,
1746-IO8 No replacement —
Digital 4-out combination input/output module
combination 120V AC (inputs), 100/120V AC (relay contact outputs), 6-in,
1746-IO12 No replacement —
6-out combination input/output module
240V DC (inputs), 100/120V AC (relay contact outputs), 6-in, 6 inputs, 4 outputs, 24V DC sink/source input AC/DC
1746-IO12DC 6-out combination input/output module 1769-IQ6XOW4 normally open, relay contact output module

20 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 3 Replace an SLC 500 I/O Module

Table 3 - Recommended Compact I/O Replacement (Continued)


Recommended
Module Type Catalog Number (1) SLC Module Description Compact I/O Compact I/O Module Description
Replacement(2)

1746-INT4 4-channel thermocouple (J, K, T, E, R, S, B, N, C, D)/mV 1769sc-IT6I Isolated thermocouple or millivolt input module
input module
4 inputs, differential or single-ended, ±10V/0…10V/0…5V/1…5V/
1746-NI4 High resolution analog input module 1769-IF4 0…20 mA/4…20 mA analog input module
8 inputs, differential or single-ended, ±10V/0…10V/0…5V/1…5V/
1746-NI8 High resolution analog input module 1769-IF8
0…20 mA/4…20 mA analog input module
1746-NI16I -20 mA…+20 mA, high resolution analog input module 1769-IF16C 16 inputs, single-ended 0…20 mA/ 4…20 mA analog input module

1746-NI16V -10V DC…+10V DC, high resolution analog input module 1769-IF16V 16 inputs, single-ended, ±10V/0…10V/0…5V/1…5V analog
input module
Analog input
6 RTD inputs, 100, 200, 500, 1000 Platinum 385/3916, 120 ohm
1746-NR4 4-channel RTD/resistance input module 1769-IR6 Nickel 618/672, 10 ohm Nickel-iron, 0…150/500/1000/3000 ohm
module
6 RTD inputs, 100, 200, 500, 1000 Platinum 385/3916, 120 ohm
1746-NR8 8-channel RTD/resistance input module 1769-IR6 Nickel 618/672, 10 ohm Nickel-iron, 0…150/500/1000/3000 ohm
module
4-channel thermocouple (J, K, T, E, R, S, B, N)/mV 6 thermocouple, thermocouple types B, C, E, J, K, N, R, S, T/±50V/
1746-NT4 1769-IT6
input module ±100V module

1746-NT8 8-channel thermocouple (J, K, T, E, R, S, B, N)/mV 1769-IT6 6 thermocouple, thermocouple types B, C, E, J, K, N, R, S, T/±50V/
input module ±100V module
High resolution, 2 analog input, 2 analog current 4 inputs, differential or single-ended, 2 outputs, single-ended
1746-NIO4I output module 1769-IF4XOF2 analog module
High resolution, 2 analog input, 2 analog voltage 4 inputs, differential or single-ended, 2 outputs, single-ended
1746-NIO4V 1769-IF4XOF2
output module analog module

1746-NO4I 0…20 mA, 4 analog current output module 1769-OF4 4 outputs, single-ended, ±10V/0…10V/0…5V/1…5V/0…20 mA/
4…20 mA analog output module
Analog output
4 outputs, single-ended, ±10V/0…10V/0…5V/1…5V/0…20 mA/
1746-NO4V -10V…+10V DC, 4 analog current output module 1769-OF4 4…20 mA analog output module
8 outputs, single-ended, 0…20 mA/4…20 mA analog
1746-NO8I 0…20 mA, 8 analog current output module 1769-OF8C
output module

1746-NO8V -10V…+10V DC, 8 analog current output module 1769-OF8V 8 outputs, single-ended, ±10V/0…10V/0…5V/1…5V analog output
module
4 inputs, differential or single-ended, 2 outputs, single-ended
1746-FIO4I 2 fast analog input, 2 analog current output module 1769-IF4XOF2 analog module
Analog
combination 4 inputs, differential or single-ended, 2 outputs, single-ended
1746-FIO4V 2 fast analog input, 2 analog voltage output module 1769-IF4XOF2
analog module

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 21


Chapter 3 Replace an SLC 500 I/O Module

Table 3 - Recommended Compact I/O Replacement (Continued)


Recommended
Module Type Catalog Number (1) SLC Module Description Compact I/O Compact I/O Module Description
Replacement(2)
1747-ACN15 ControlNet® adapter No replacement —
1747-ACNR15 ControlNet adapter, redundant No replacement —
1747-ASB SLC 500 remote I/O adapter No replacement —
1746-BAS Basic module No replacement —
1746-BAS-T High-speed basic module No replacement —
1746-BLM Blow molding module No replacement —
1746-BTM Barrel temperature module No replacement —
1746-HS IMC 110 motion module No replacement —
1746-HSCE High-speed counter encoder module No replacement —
Specialty
1746-HSCE2 Multi-channel high-speed counter encoder module 1769-HSC High-speed counter module
1746-HSTP1 1-axis stepper module No replacement —
1746-N2 Empty slot filler 1769-ARM Compact address reserve module
1746-QS Synchronized axis module No replacement —
1746-QV Open loop velocity control module No replacement —
1747-SCNR ControlNet scanner No replacement —
1747-SDN DeviceNet scanner 1769-SDN Compact I/O DeviceNet scanner
1746-SIM 16-point input simulator module No replacement —
1747-SN Remote I/O scanner No replacement —
(1) The product may be in Active Mature, End of Life, or Discontinued state. To view the most up-to-date product lifecycle status, search for the catalog number on the Product Lifecycle Status website.
(2) The recommended replacements that are indicated in this table are for reference only. There may be slight differences in specifications between the existing 1746 SLC I/O module and recommended
1769 Compact I/O module. Consult your local sales team for further assistance.

22 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 3 Replace an SLC 500 I/O Module

Upgrade an SLC I/O Table 4 lists the recommended replacement Compact 5000 I/O module to your
Installation by Replacing it existing SLC 500 I/O module.
with Compact 5000 I/O Before upgrading, take note of the following:
• When replacing an SLC I/O with a Compact 5000 I/O, a
CompactLogix 5380, CompactLogix 5480, or ControlLogix® 5580
controller must be used.
• There might be technical differences between the SLC I/O and
Compact 5000 I/O. Verify the specifications to meet your application
needs. For wiring diagrams and technical specifications of Compact
5000 I/O modules, see Compact 5000 I/O Modules Specifications
Technical Data, publication 5069-TD001.

Table 4 - Recommended Compact 5000 I/O Replacement


Recommended
Catalog Compact 5000 I/O
Module Type SLC Module Description Compact 5000 I/O Module Description
Number (1) Replacement(2)
1746-IA4 100/120V AC, 4 120V AC input module 5069-IA16 16-point, 120/240V AC digital input module
1746-IA8 100/120V AC, 8 120V AC input module 5069-IA16 16-point, 120/240V AC digital input module
1746-IA16 100/120V AC, 16 120V AC input module 5069-IA16 16-point, 120/240V AC digital input module
1746-IB8 24V DC, 8 current sinking DC input module 5069-IB16 16-point, 24V DC sinking digital input module
1746-IB16 24V DC, 16 current sinking DC input module 5069-IB16 16-point, 24V DC sinking digital input module
1746-IB32 24V DC, 32 current sinking DC input module 5069-IB16 x 2(3) 16-point, 24V DC sinking digital input module
1746-IC16 48V DC, 16 current sinking DC input module No replacement —
1746-IG16 5V DC, 16 current sourcing TTL input module No replacement —
1746-IH16 125V DC, 16 current sinking DC input module No replacement —

Digital input 1746-IM4 200/240V AC, 4 240V AC input module 5069-IA16 16-point, 120/240V AC digital input module
1746-IM8 200/240V AC, 8 240V AC input module 5069-IA16 16-point, 120/240V AC digital input module
1746-IM16 200/240V AC, 16 240V AC input module 5069-IA16 16-point, 120/240V AC digital input module
1746-IN16 24V AC/DC, 16 24V AC/DC input module No replacement —
1746-ITB16 24V DC, 16 fast response DC sinking input module 5069-IB16 16-point, 24V DC sinking digital input module
1746-ITV16 24V DC, 16 fast response DC sourcing input module No replacement —

1746-IV8 24V DC, 8 current sourcing DC input module 5069-IV16F-SC 16-point, 24V DC sourcing digital input module
(Spectrum module)

1746-IV16 24V DC, 16 current sourcing DC input module 5069-IV16F-SC 16-point, 24V DC sourcing digital input module
(Spectrum module)

1746-IV32 24V DC, 32 current sourcing DC input module 5069-IV16F-SC x 2 16-point, 24V DC sourcing digital input module
(Spectrum module)
1746-OA8 120/240V AC, 8 120/240V AC output module 5069-OA16 16-point, 120/240V AC digital output module
1746-OA16 120/240V AC, 16 120/240V AC output module 5069-OA16 16-point, 120/240V AC digital output module
1746-OAP12 120/240V AC, 12 high current 120/240V AC output module No replacement —

1746-OB6EI 24V DC, 6 electronically protected isolated sourcing DC No replacement —


output module
1746-OB8 24V DC, 8 current sourcing DC output module 5069-OB8 8-point, 24V DC, high current digital output module
1746-OB8 x 2 24V DC, 8 current sourcing DC output module 5069-OB16 16-point, 24V DC, sourcing digital output module
Digital output 1746-OB16 24V DC, 16 current sourcing DC output module 5069-OB16 16-point, 24V DC, sourcing digital output module

1746-OB16E 24V DC, 16 electronically protected current sourcing DC 5069-OB16 16-point, 24V DC sourcing digital output module
output module
1746-OB32 24V DC, 32 current sourcing DC output module 5069-OB16 x 2(3) 16-point, 24V DC, sourcing digital output module
24V DC, 32 electronically protected current sourcing DC
1746-OB32E output module 5069-OB16 x 2(3) 16-point, 24V DC, sourcing digital output module

1746-OBP8 24V DC, 8 high current sourcing DC output module 5069-OB8 8-point, 24V DC, high current digital output module
1746-OBP8 x 2 24V DC, 8 high current sourcing DC output module 5069-OB16 16-point, 24V DC, sourcing digital output module

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 23


Chapter 3 Replace an SLC 500 I/O Module

Table 4 - Recommended Compact 5000 I/O Replacement (Continued)


Recommended
Catalog
Module Type SLC Module Description Compact 5000 I/O Compact 5000 I/O Module Description
Number (1)
Replacement(2)
1746-OBP16 24V DC, 16 high current sourcing DC output module 5069-OB8 x 2(4) 16-point, 24V DC, high current digital output module
1746-OG16 5V DC, 16 current sourcing TTL output module No replacement —
5069-OV16F-SC
1746-OV8 24V DC, 8 current sinking DC output module (Spectrum module) 16-point, 24V DC, sinking digital output module

5069-OV16F-SC
1746-OV16 24V DC, 16 current sinking DC output module 16-point, 24V DC, sinking digital output module
(Spectrum module)
5069-OV16F-SC x 2
1746-OV32 24V DC, 32 current sinking DC output module 16-point, 24V DC, sinking digital output module
Digital output (Spectrum module)
(cont.) 1746-OVP16 24V DC, 16 high current sinking DC output module No replacement —
1746-OW4 AC/DC relay, 4 relay (hard contact) output module 5069-OW4I(5)(6) 4-point, normally-open, isolated relay output module

1746-OW4 x 4 AC/DC relay, 4 relay (hard contact) output module 5069-OW16(5)(6) 16-point, non-isolated, high-density relay output module

1746-OW8 AC/DC relay, 8 relay (hard contact) output module 5069-OW16(5)(6) 16-point, non-isolated, high-density relay output module

1746-OW16 AC/DC relay, 16 relay (hard contact) output module 5069-OW16(5)(6) 16-point, non-isolated, high-density relay output module

1746-OX8 AC/DC relay, 8 relay (hard contact) output module 5069-OX4I(5)(6) 4-point, normally-open/normally-closed, isolated relay output module
120V AC (inputs), 100/120V AC (relay contact outputs), 2-in, 16-point, 120/240V AC digital input module +
1746-IO4 2-out combination input/output module 5069-IA16 + 5069-OW16 16-point, non-isolated, high-density relay output module
120V AC (inputs), 100/120V AC (relay contact outputs), 4-in, 16-point, 120/240V AC digital input module +
1746-IO8 4-out combination input/output module 5069-IA16 + 5069-OW16 16-point, non-isolated, high-density relay output module
Digital
combination 120V AC (inputs), 100/120V AC (relay contact outputs), 6-in, 16-point, 120/240V AC digital input module +
1746-IO12 6-out combination input/output module 5069-IA16 + 5069-OW16 16-point, non-isolated, high-density relay output module
240V DC (inputs), 100/120V AC (relay contact outputs), 6-
1746-IO12DC in, 6-out combination input/output module No replacement —

4-channel thermocouple (J, K, T, E, R, S, B, N, C, D)/mV


1746-INT4 input module No replacement —

1746-NI4 4 high resolution analog input module 5069-IY4 4-channel, universal analog input module, differential inputs only
1746-NI8 4 high resolution analog input module 5069-IF8 8-channel, analog input module, differential inputs only
1746-NI16I -20 mA…+20 mA, 16 high resolution analog input module 5069-IF8 8-channel, analog input module, differential inputs only
1746-NI16V -10V DC…+10V DC, 16 high resolution analog input module 5069-IF8 8-channel, analog input module, differential inputs only
Analog input
1746-NR4 4-channel RTD/resistance input module 5069-IY4 4-channel, universal analog input module, differential inputs only
1746-NR8 8-channel RTD/resistance input module 5069-IY4 4-channel, universal analog input module, differential inputs only
4-channel thermocouple (J, K, T, E, R, S, B, N)/mV
1746-NT4 input module 5069-IY4 4-channel, universal analog input module, differential inputs only

8-channel thermocouple (J, K, T, E, R, S, B, N)/mV


1746-NT8 5069-IY4 4-channel, universal analog input module, differential inputs only
input module
High resolution, 2 analog input, 2 analog current 4-channel, universal analog input module, differential inputs only +
1746-NIO4I 5069-IY4 + 5069-OF4
output module 4-channel, analog output module
High resolution, 2 analog input, 2 analog voltage 4-channel, universal analog input module, differential inputs only +
1746-NIO4V 5069-IY4 + 5069-OF4
output module 4-channel, analog output module
Analog output 1746-NO4I 0…20 mA, 4 analog current output module 5069-OF4 4-channel, analog output module
1746-NO4V -10V DC…+10V DC, 4 analog current output module 5069-OF4 4-channel, analog output module
1746-NO8I 0…20 mA, 8 analog current output module 5069-OF8 8-channel, analog output module
1746-NO8V -10V DC…+10V DC, 8 analog current output module 5069-OF8 8-channel, analog output module

Analog 1746-FIO4I 2 fast analog input, 2 analog current output module No replacement —
combination 1746-FIO4V 2 fast analog input, 2 analog voltage output module No replacement —
1747-ACN15 ControlNet adapter No replacement —
1747-ACNR15 ControlNet adapter, redundant No replacement —
Specialty
1747-ASB SLC 500 remote I/O adapter No replacement —
1746-BAS Basic module No replacement —

24 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Chapter 3 Replace an SLC 500 I/O Module

Table 4 - Recommended Compact 5000 I/O Replacement (Continued)


Recommended
Catalog
Module Type SLC Module Description Compact 5000 I/O Compact 5000 I/O Module Description
Number (1)
Replacement(2)
1746-BAS-T High-speed basic module No replacement —
1746-BLM Blow molding module No replacement —
1746-BTM Barrel temperature module No replacement —
1746-HS IMC 110 motion module No replacement —
1746-HSCE High-speed counter encoder module 5069-HSC2XOB4 High-speed counter, 2-axis, 4-point sourcing digital output module
1746-HSCE2 Multi-channel high-speed counter encoder module 5069-HSC2XOB4 High-speed counter, 2-axis, 4-point sourcing digital output module

Specialty 1746-HSTP1 1 axis stepper module No replacement —


(cont) 1746-N2 Empty slot filler 5069-ARM Address reserve module
1746-QS Synchronized axis module No replacement —
1746-QV Open loop velocity control module No replacement —
1747-SCNR ControlNet scanner No replacement —
1747-SDN DeviceNet scanner No replacement —
1746-SIM 16-point input simulator module No replacement —
1747-SN Remote I/O scanner No replacement —

(1) The product may be in Active Mature, End of Life, or Discontinued state. To view the most up-to-date product lifecycle status, search for the catalog number on the Product Lifecycle Status website.
(2) The recommended replacements that are indicated in this table are for reference only. There may be slight differences in specifications between the existing 1746 SLC I/O module and recommended
5069 Compact 5000 I/O module. Consult your local sales team for further assistance.
(3) 1746-IB32 modules can be replaced with two 5069-IB16 modules.
(4) 1746-OBP16 modules can be replaced with two 5069-OB8 modules.
(5) 5069-OW16 is a DC module.
(6) The 5069-OW16 does not come with an internal snubber, an external surge suppressor is required. For more information on selecting and adding surge suppressors, see the Industrial Automation
Wiring and Grounding Guidelines, publication 1770-4.1.

SLC I/O Installation Using a Conversion Kit


You can use a conversion system to connect the existing SLC I/O wiring to the
Compact 5000 I/O modules without disturbing the field wiring connections,
reducing labor time and eliminating downtime that could result from wiring
mistakes during the migration. With a conversion system I/O can be swapped
one rack at a time, giving you the option to run both new and old I/O networks
simultaneously.
Table 5 - SLC I/O to Compact 5000 I/O Conversion System Selection
SLC I/O Module Catalog Number Compact 5000 I/O Modules Conversion Module Catalog Conversion Module Description
(To be converted) Catalog Number (To be used) Number
1746-IA16 120VAC Input Module
5069-IA16
1746-IM16 240VAC Input Module
1492-CM1746-M01
1746-IB16 Current Sinking DC Input Module
5069-IB16
1746-ITB16 Fast Response DC Sinking Input Module
1746-OA16 5069-OA16 1492-CM1746-M02 120/240V AC Output Module
1746-OB16 Current Sourcing DC Output Module
5069-OB16 1492-CM1746-M03
1746-OB16E Current Sourcing DC Output Module
1746-OW16 5069-OW16 1492-CM1746-M04 AC/DC Relay Output Module
1746-NI8 5069-IF8 1492-CM1746-M05 High Resolution (8) Analog Input Module
1746-NI4 1492-CM1746-M06 High Resolution (4) Analog Input Module
1746-NR4 5069-IY4 1492-CM1746-M07 SLC 500 RTD/Resistance Input Module
1746-NT4 1492-CM1746-M09 4-Channel Thermocouple/mV Input Module
1746-NO4I 4 Point Analog Output Module (Current)
5069-OF4 1492-CM1746-M10
1746-NO4V 4 Point Analog Output Module (Voltage)

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 25


Chapter 3 Replace an SLC 500 I/O Module

Table 5 - SLC I/O to Compact 5000 I/O Conversion System Selection (Continued)
SLC I/O Module Catalog Number Compact 5000 I/O Modules Conversion Module Catalog Conversion Module Description
(To be converted) Catalog Number (To be used) Number
1746-NO8I 8 Point Analog Output Module (Current)
5069-OF8 1492-CM1746-M11
1746-NO8V 8 Point Analog Output Module (Voltage)
1746-IB32 5069-IB16 x 2 1492-CM1746-M12 Current Sinking DC Input Module
1746-OB32 Current Sourcing DC Output Module
5069-OB16 x 2 1492-CM1746-M13
1746-OB32E Current Sourcing DC Output Module

Table 6 - SLC to Compact 5000 Chassis Conversion System Selection


Number of Compact 5000
SLC 500 Chassis 1492 Conversion Chassis 1792 Slots max Chassis Length Usable Length I/O Cards max
1746-A4 1492-CH1746-4 4 235 mm (9.25 in.) 203 mm (8.00 in.) 4
1746-A7 1492-CH1746-7 7 339 mm (13.33 in.) 307 mm (12.08 in.) 9
1746-A10 1492-CH1746-10 10 454 mm (17.88 in.) 422 mm (16.63 in.) 14
1746-A13 1492-CH1746-13 13 559 mm (22.00 in.) 527 mm (20.75 in.) 19

For more information on choosing the appropriate conversion chassis and


conversion system for your system, see 1746 SLC I/O to Compact 5000 I/O
Conversion System Selection Guide, publication 1492-SG010.

For more information on installing the 1492 conversion system chassis, see
1746-to-5069 I/O Conversion System Instruction Sheet, publication 1492-IN132.

26 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A

Wiring Diagram Comparisons

This appendix provides wiring diagram comparisons of the recommended


replacement for your existing SLC 500 I/O module.

Topic Page
Replace an SLC 5 Processor Serial Port with a Compact I/O Serial Module 27
Replace an SLC 500 I/O with a Compact I/O 28
Replace an SLC 500 I/O with a Compact 5000 I/O 44
Replace an SLC 500 I/O with Combinations of Compact 5000 I/O 54

Replace an SLC 5 Processor See the installations instructions and technical data of the associated catalogs
Serial Port with a Compact for the detailed wiring instructions.
I/O Serial Module SLC 5/03, SLC 5/04, or SLC 5/05 to 5069-SERIAL
SLC 5/03, 5/04, 5/05 5069-SERIAL
Serial Port Serial Module

SLC 5/03 CPU

RUN FORCE
FLT DH485
BATT RS232
RUN REM PROG 1
6
7 2

3
8
4
9
5

Wiring
9-pin female 25-pin 9-pin Pin RS-232C Input (i)/Output (o)
No Handshaking Handshaking
DCD.IN 1 8 1 1 Data Carrier Detect (DCD) (i) - -
RXD.IN 2 3 2 2 Receive Data (RXD) (i) A A
3 Transmit Data (TXD) (o) A A
TXD.OUT 3 2 3
Data Terminal Ready
DTR.OUT 4 20 4 4 (DTR) (o) B B

SIG.GND 5 7 5 5 Common (COM) - A A


DSR.IN 6 6 6 6 Data Set Ready (DSR) (i) - -
7 Request To Send (RTS) (o) B A
RTS.OUT 7 4 7
8 Clear To Send (CTS) (i) - A
CTS.IN 8 5 8 9 - - - -

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 27


Appendix A Wiring Diagram Comparisons

Replace an SLC 500 I/O with See the installations instructions and technical data of the associated catalogs
a Compact I/O for the detailed wiring instructions.

1746-IA4 to 1769-IA8I
1746-IA4 1769-IA8I L1a
100/120V AC 100/120V AC Input Module 100/120V AC
IN 0
L2a AC
COM 0
NOT L1b
USED
NOT 100/120V AC
USED
IN 1
AC
NOT L2b
USED COM 1

NOT L1c
USED
L1 100/120V AC
IN 0 IN 2
L2c AC
IN 1 COM 2

100/120V AC IN 2

IN 3 IN 3
AC
COM 3
IN 4
L2 AC COM AC
COM 4
IN 5
AC
COM 5
IN 6
AC
COM 6
AC IN 7
COM 7
NC
NC

1746-IA8 to 1769-IA8I

1746-IA8 1769-IA8I L1a

100/120V AC 100/120V AC Input Module 100/120V AC


IN 0
L2a AC
COM 0
L1 IN 0 L1b

IN 1 100/120V AC
AC IN 1
IN 2 L2b COM 1
L1c
IN 3
100/120V AC 100/120V AC
IN 4
IN 2
L2c AC
IN 5 COM 2

IN 6

IN 7 IN 3
AC
COM 3
L2 AC COM
AC IN 4
COM 4
Internally Connected AC COM
AC
IN 5

Commons COM 5
IN 6
AC
COM 6
IN 7
AC
COM 7
NC
NC

28 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-IA16 to 1769-IA16

1769-IA16
1746-IA16
100/120V AC Input Module
100/120V AC
L1 L1
IN 0
0 IN 1 IN 0
IN 2 1 IN 1
2 IN 3 IN 2
IN 4 3 IN 3
4 IN 5 IN 4
IN 6 5 IN 5
100/120V AC 6 IN 7 IN 6
IN 8 7 100/120V AC IN 7
10 IN 9 IN 8
IN 10 11 IN 9
12 IN 11 IN 10
IN 12 13 IN 11
14 IN 13 IN 12
IN 14 15 IN 13
16 IN 15 IN 14
17
L2 AC COM IN 15
AC
AC COM
L2 AC COM Commons are
Internally Connected COM connected internally.
SLC
Commons PLC

1746-IB8 to 1769-IQ16

1769-IQ16
24V DC Sink/Source Input Module
1746-IB8
24V DC Sinking +DC (sinking)
-DC (sourcing)

+DC IN 0 IN 0
IN 1
IN 1 IN 2
IN 3 24V DC
IN 2 IN 4
IN 5
IN 3 IN 6
24V DC IN 7
IN 4 DC
+DC (sinking) COM 1 +DC (sinking)
IN 5
-DC (sourcing) -DC (sourcing)

IN 6 IN 9
IN 8
IN 7 IN 11
DC COM
24V DC IN 10
-DC IN 13
IN 12
DC COM
Internally Connected IN 15
IN 14
Commons DC
+DC (sinking) COM 2
-DC (sourcing)

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 29


Appendix A Wiring Diagram Comparisons

1746-IB16 to 1769-IQ16
1769-IQ16
1746-IB16 24V DC Sink/Source Input Module
24V DC Sinking
+DC +DC (sinking)
-DC (sourcing)
IN 0
0 IN 1
IN 2 1 IN 0
2 IN 3 IN 1
IN 4 3 IN 2
4 IN 5 IN 3 24V DC
5 IN 4
IN 6
24V DC 6 IN 7 IN 5
IN 8 6 7 IN 6
10 IN 9 IN 7
11 DC
IN 10 +DC (sinking) COM 1 +DC (sinking)
12 IN 11 -DC (sourcing) -DC (sourcing)
13
IN 12
14 IN 13
15 IN 9
IN 14
16 IN 15 IN 8
17 IN 11
-DC DC COM
24V DC IN 10
DC COM
IN 13
IN 12
Internally Connected Commons SLC
IN 15
PLC IN 14
DC
+DC (sinking) COM 2
-DC (sourcing)

1746-IG16 to 1769-IG16

1746-IG16 1769-IG16
TTL Input (Low = True) 5V DC TTL Input Module

+DC +5 DC IN 0
IN 1 0
1 IN 2
IN 3 2
3 IN 4
IN 5 4
5 IN 6
IN 7 6
7 IN 8
+5V DC
IN 9 10
11 IN 10
IN 1 1 12
13 IN 12
IN 13 14
15 IN 14
IN 15 16
17
DC COM

-DC
SLC
PLC

30 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-IM4 to 1769-IM12
1769-IM12
1746-IM4
200/240V AC Input Module
200/240V AC
L1

NOT IN 0
USED IN 1
NOT
IN 2
USED IN 3
NOT
IN 4
USED IN 5
NOT IN 6
USED 200/240V AC IN 7
L1 IN 0
IN 8
IN 9
IN 1 IN 10
IN 11
200/240V AC IN 2 NC
NC
IN 3 NC
NC AC
L2 AC COM AC Commons are
L2 COM
COM connected internally.

Do not use the NC terminals as a connection.

1746-IM8 to 1769-IM12
1769-IM12
1746-IM8
200/240V AC Input Module
200/240V AC
L1

L1 IN 0
IN 0 IN 1
IN 2
IN 1 IN 3
IN 4
IN 2 IN 5
IN 6
IN 3 200/240V AC IN 7
200/240V AC IN 8
IN 4 IN 9
IN 10
IN 5 IN 11
NC
IN 6 NC
NC
IN 7
NC AC
L2 AC COM L2 AC COM Commons are
COM connected internally.
Internally Connected AC COM
Commons Do not use the NC terminals as a connection.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 31


Appendix A Wiring Diagram Comparisons

1746-IM16 to 1769-IM12
1769-IM12
1746-IM16 200/240V AC Input Module
200/240V AC
L1
L1
IN 0
IN 0
0 IN 1 IN 1
IN 2
1 IN 2
2 IN 3 IN 3
IN 4 3 IN 4
4 IN 5 IN 5
IN 6 5 IN 6
200/240V AC 6 IN 7 200/240V AC IN 7
IN 8 7 IN 8
10 IN 9 IN 9
IN 10 11
IN 11
IN 10
12
13 IN 11
IN 12
14 IN 13 NC
15 NC
IN 14
16 IN 15 NC
17 NC AC
L2 AC COM
AC COM L2 AC COM Commons are
Internally Connected COM connected internally.
SLC
Commons PLC
Do not use the NC terminals as a connection.

1746-ITB16 to 1769-IQ16F
1746 -ITB16 1769-IQ16F
24V DC Sink/Source Input Module +DC (sinking)
24V DC Sinking -DC (sourcing)
+DC
IN 0 IN 0
0 IN 1
IN 1
IN 2 1
IN 3
IN 2
2 24V DC
3 IN 3
IN 4
4 IN 5 IN 4
IN 6 5 IN 5
24V DC
6 IN 7 IN 6
7
IN 8 6 IN 7
10 IN 9 DC
11 +DC (sinking) COM 1 +DC (sinking)
IN 10 -DC (sourcing)
12 IN 1 1 -DC (sourcing)
13
IN 12
14 IN 13
IN 14
15 IN 9
16 IN 15 IN 8
DC 17 IN 11
-DC COM DC COM 24V DC IN 10
IN 13
Internally Connected Commons SLC IN 12
PLC IN 15
IN 14
DC
+DC (sinking) COM 2
-DC (sourcing)

32 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-ITV16 to 1769-IQ16F
1769-IQ16F
1746-ITV16
24V DC Sink/Source Input Module +DC (sinking)
24V DC Sourcing -DC (sourcing)
-DC
IN 0 IN 0
0 IN 1
1 IN 1
IN 2 IN 2
2 IN 3 24V DC
3 IN 3
IN 4
4 IN 5 IN 4
5 IN 5
IN 6
24V dc 6 IN 7 IN 6
IN 8 7 IN 7
IN 9 DC
10 +DC (sinking)
11 COM 1 +DC (sinking)
IN 10 -DC (sourcing) -DC (sourcing)
12 IN 1 1
IN 12 13
14 IN 13
15 IN 9
IN 14
IN 8
16 IN 15
17 IN 11
+DC VDC 24V DC IN 10
VDC IN 13
Internally SLC
IN 12
IN 15
Connected V DC PLC
IN 14
DC
+DC (sinking) COM 2
-DC (sourcing)

1746-IV8 to 1769-IQ16
1769-IQ16
1746-IV8 24V DC Sink/Source Input Module
24V DC Sourcing +DC (sinking)
-DC (sourcing)

-DC IN 0 IN 0
IN 1
IN 1 IN 2
IN 3 24V DC
IN 2 IN 4
IN 5
IN 3 IN 6
24V dc IN 7
IN 4 DC
+DC (sinking) COM 1 +DC (sinking)
-DC (sourcing) -DC (sourcing)
IN 5

IN 6 IN 9
IN 8
IN 7 IN 11
24V DC IN 10
+DC VDC IN 13
IN 12
VDC
Internally IN 15
IN 14
Connected V DC DC
+DC (sinking) COM 2
-DC (sourcing)

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 33


Appendix A Wiring Diagram Comparisons

1746-IV16 to 1769-IQ16
1769-IQ16
1746-IV16 24V DC Sink/Source Input Module
24V DC Sourcing +DC (sinking)
-DC -DC (sourcing)

IN 0
0 IN 1
1 IN 0
IN 2 IN 1
2 IN 3
IN 4 3 IN 2
4 IN 5 IN 3 24V DC
5
IN 6 IN 4
24V dc 6 IN 7 IN 5
IN 8 7
10 IN 9 IN 6
11 IN 7
IN 10 DC
12 IN 1 1
13 +DC (sinking) COM 1 +DC (sinking)
IN 12 -DC (sourcing)
14 IN 13 -DC (sourcing)
IN 14 15
16 IN 15
17 IN 9
+DC VDC IN 8
VDC
IN 11
Internally SLC 24V DC IN 10
Connected V DC PLC IN 13
IN 12
IN 15
IN 14
DC
+DC (sinking) COM 2
-DC (sourcing)

1746-OA8 to 1769-OA8
1769-OA8
1746-OA8 100/240V AC Input Module
100...240V AC Triac Output

VAC 1 L1

OUT 0 VAC 1 L1
CR OUT0
OUT 1 100…240V AC OUT1 CR
CR OUT2 100…240V AC
OUT 2
CR OUT3 CR
OUT 3 CR L2 L2
L1
L1 VAC 2
VAC 2
OUT5 CR
CR OUT4
OUT 4
OUT7 CR
100…240V AC CR OUT6
OUT 5 100…240V AC
OUT 6 CR

OUT 7 CR L2
L2

34 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-OA16 to 1769-OA16
1769-OA16
1746-OA16
100...240V AC Triac Output 100/240V AC Input Module

L1
VAC 1
OUT0
VAC 1 L1
0
CR OUT 0
OUT 1
1 OUT 2
OUT 1 CR
2 CR OUT 2
OUT 3
100…240V AC 3 OUT 4
OUT 3 CR
OUT 5 4
CR CR OUT4 100…240V AC
CR 5 OUT 6 OUT 5 CR
OUT 7 6 CR CR OUT6
CR 7 OUT 7 CR
L2 L2
VAC 2 L1 L1 VAC 2
OUT 9
11 OUT 8 OUT 9 CR
OUT 1 1 10 CR OUT 8
13 OUT 10 OUT11 CR
OUT 13 12 100…240V AC CR OUT10
CR 15 OUT 12
100…240V AC OUT 13 CR
OUT 15 14
CR
CR OUT 12
CR 17 OUT 14 OUT 15 CR
16 CR CR OUT 14
SLC
PLC
L2 L2

1746-OB8 to 1769-OB8
1769-OB8
1746-OB8 24V DC Source Output Module
10...50V DC Transistor Output-sourcing

VDC +DC
+VDC 1 DC+
OUT 0 CR OUT 0
OUT 1
OUT 1 OUT 2
OUT 3 CR
OUT 2 DC - DC COM
1
OUT 3
NC
10…50V DC NC
OUT 4 CR NC
NC
OUT 5 CR NC
NC
OUT 6 CR +VDC 2 DC+
OUT 7 CR
CR OUT 4
OUT 5 CR
DC
COM
-DC CR OUT 6
OUT 7 CR
DC COM
2
DC-

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 35


Appendix A Wiring Diagram Comparisons

1746-OB16 to 1769-OB16
1769-OB16
24V DC Source Output Module
1746-OB16
10...50V DC Transistor Output-sourcing SLC
PLC
+VDC +DC
+DC VDC
OUT 0
CR OUT 0
OUT 1
0 OUT 1 CR
1 OUT 2
CR OUT 2
2
OUT 3
3 OUT 4
OUT 3 CR
CR OUT 5
4 OUT 4
5 OUT 6 OUT 5
6
CR OUT 7
7 OUT 8
CR OUT 6
CR
10…50V DC OUT 9
10 OUT 7 CR
11 OUT 10
CR CR OUT 8 24V DC (Source)
12
OUT 11
13 OUT 12
OUT 9 CR
OUT 13 14
CR OUT 10
CR 15 OUT 14
CR
OUT 11 CR
16
CR
OUT 15 OUT 12
17
DC COM
OUT 13 CR
OUT 14
-DC OUT 15
DC COM
-DC

1746-OB16E to 1769-OB16P
1769-OB16P
1746-OB16E 24V DC Source Output Module
10...30V DC SLC
Transistor Output-sourcing PLC
+VDC +DC
+DC VDC
CR OUT 0
OUT 0
0 OUT 1 CR
OUT 1
1 OUT 2 CR OUT 2
OUT 3
2 OUT 3 CR
3 OUT 4 OUT 4
CR OUT 5
OUT 6
4 OUT 5
5
6
CR OUT 6
OUT 7
CR 7 OUT 8
CR
OUT 7 CR
10…30V DC OUT 9
11 OUT 10
10 CR OUT 8 24V DC
CR OUT 9 CR
OUT 11
13 OUT 12
12 OUT 10
OUT 13 14
CR OUT 11 CR
CR 15 OUT 14 OUT 12
CR
OUT 15 16 OUT 13 CR
CR 17 OUT 14
DC COM
OUT 15
DC COM
-DC
-DC

36 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-OBP8 to 1769-OB8
1769-OB8
1746-OBP8
24V DC Source Output Module
20.4...26.4V DC Transistor Output-sourcing

+DC VDC1
OUT 0
CR OUT 1
+VDC 1 DC+
OUT 2
CR OUT 3
CR OUT 0
20.4…26.4V DC DC OUT 1
COM1
NC OUT 2
NC OUT 3 CR
NC DC - DC COM
1
NC
NC
-DC
NC
NC NC
NC NC
NC NC
+DC VDC2
+VDC 2 DC+
OUT 4
CR
CR OUT 4
OUT 5
OUT 6 OUT 5 CR
20.4…26.4V DC CR OUT 6
CR OUT 7
DC OUT 7 CR
COM2 DC COM
-DC 2
DC-

1746-OG16 to 1769-OG16

1746-OG16 1769-OG16
TTL Output (Low = True) 5V DC TTL Output Module
+DC
VDC
OUT 0 L
OUT 1 0
L
1 OUT 2 L
2
L OUT 3
3 OUT 4 L
4
L OUT 5
5 OUT 6 L
OUT 7 6 External
+5V DC L
7 OUT 8 terminal
L
10 block
L OUT 9
11 OUT 10 5V DC
L
12
L OUT 11
13 OUT 12
L
OUT 13 14
L 15 OUT 14
16 L
OUT 15
L 17
DC COM
-DC
SLC
PLC

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 37


Appendix A Wiring Diagram Comparisons

1746-OV8 to 1769-OV16
1769-OV16
1746-OV8
24V DC Sink Output Module
10...50V DC Transistor
Output Sinking
+VDC +DC
VDC +DC CR OUT 0
OUT 0 OUT 1 CR
CR OUT 2
OUT 1 OUT 3 CR
OUT 4
OUT 2
OUT 5
OUT 3
CR OUT 6
10…50V DC OUT 7 CR
OUT 4 CR CR OUT 8 24V DC (Sink)
OUT 9 CR
OUT 5 CR OUT 10
OUT 6 OUT 11 CR
CR
OUT 12
OUT 7
CR OUT 13 CR
DC COM
OUT 14
-DC OUT 15
DC COM
-DC

1746-OV16 to 1769-OV16

1746-OV16
1769-OV16
10...50V DC Transistor 24V DC Sink Output Module
Output Sinking
+DC
+VDC +DC
VDC
OUT 0 CR OUT 0
0
OUT 1
1
OUT 1 CR
OUT 2
OUT 3 2 CR OUT 2
3 OUT 4 OUT 3 CR
CR OUT 5 4 OUT 4
10...50V DC 5 OUT 6
6 OUT 5
OUT 7
CR 7 OUT 8
CR OUT 6
CR
OUT 9 10 OUT 7 CR
11 OUT 10
CR
CR OUT 8 24V DC (Sink)
OUT 1 1 12
OUT 9 CR
13 OUT 12
OUT 13 14
CR OUT 10
CR 15 OUT 14 OUT 11 CR
16 CR
CR
OUT 15 OUT 12
17
DC COM OUT 13 CR
-DC OUT 14
SLC
PLC OUT 15
DC COM
-DC

38 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-OW4 to 1769-OW8
1769-OW8
1746-OW4
Relay Output Module
Relay Output

VAC-VDC L1 or +DC
VAC-VDC L1 or DC+
OUT 0 OUT 0 1
V AC/DC OUT 1 CR L2 or DC-
CR OUT 2
OUT 1
OUT 3 CR

OUT 2 CR
VAC-VDC
CR L2 or -DC L1 or DC+ 2
OUT 3 OUT 5 CR
L2 or DC- CR OUT 4
NOT OUT 7
USED
CR OUT 6
NOT
USED
NOT
USED
NOT
USED
OUT
NOT7
USED

1746-OW8 to 1769-OW8
1769-OW8
1746-OW8 Relay Output Module
Relay Output

VAC-VDC
1 L1 or +DC
VAC-VDC L1 or DC+
OUT 0 OUT 0 1

V AC/DC OUT 1 CR L2 or DC-


OUT 1 CR OUT 2
OUT 3 CR
CR
OUT 2

OUT 3 CR L2 or -DC L1 or DC+ VAC-VDC


2 CR
OUT 5
VAC-VDC L1 or +DC L2 or DC- CR OUT 4
2 OUT 7
OUT 4 CR OUT 6

OUT 5 V AC/DC

OUT 6 CR

OUT 7 CR L2 or -DC

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 39


Appendix A Wiring Diagram Comparisons

1746-OW16 to 1769-OW16
1769-OW16
1746-OW16
Relay Output Module
Relay Output
L1 or +DC VAC-VDC
VAC-VDC
OUT0 1 L1 or +DC
1 OUT 0
OUT 1 0 OUT 1 CR
1 OUT 2
CR OUT 2
OUT 3 2 OUT 3
V AC/DC CR
3 OUT 4 CR CR OUT 4
OUT 5 4 OUT 5
CR 5 OUT 6 OUT 6
6 CR
OUT 7 OUT 7 CR
CR 7
L2 or -DC
L2 or -DC L1 or +DC VAC-VDC
VAC-VDC L1 or +DC 2
OUT 9 2 OUT 9 CR
11 OUT 8 OUT 8
10 OUT 11 CR
OUT 11
OUT 10 CR OUT 10
13
OUT 13 12 V AC/DC OUT 13
CR CR OUT 12
15 OUT 12 CR
OUT 15 14 OUT 15 CR
CR 17 OUT 14 OUT 14
CR
SLC
16
L2 or -DC
PLC
L2 or -DC

1746-IO12DC to 1769-IQ6XOW4
1769-IQ6XOW4
1746-IO12DC Relay Contact Output Module
24V DC Input - Relay Output
VAC L1 or +DC
L1 or +DC CR OUT 0 VDC
VAC-VDC
OUT 0
OUT 1 CR L2 or -DC
CR OUT 2
OUT 1 CR
OUT 2 OUT 3
V AC/DC OUT 3
OUT 4 CR
CR OUT 5 NC
NOT
USED NC
L2 or -DC NC
NC
+DC NC
NOT NC
USED
IN 0 +DC (sinking)
IN 1
IN 2
-DC (sourcing)
10…30V DC IN 3 IN 0
IN 4 IN 1
IN 5 24V DC IN 2
NOT IN 3
NOT USED
IN 4
USED
-DC
DC COM +DC (sinking) DC
IN 5
-DC (sourcing) COM

40 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-NI4 to 1769-IF4
1769-IF4 Single-ended Sensor/Transmitter Inputs
1746-NI4
Analog Input Module
Sensor/ +
Transmitter - Current V in 0 +
Supply V/I in 0 -
+ Signal
+ I in 0 +
analog ANLG Com
source 0 IN 0 + V in 1 +
– 1 IN 0 – V/I in 1 -
earth
2 ANL COM Voltage
ground I in 1 +
+ ANLG Com
analog
3 IN 1 + + Ground
source 4 IN 1 – Signal V in 2 +
5 ANL COM V/I in 2 -
– earth
6 IN 2 + Voltage I in 2 +
ground
7 IN 2 – ANLG Com
Jumper unused 8 + Ground
inputs.
ANL COM Signal V in 3 +
9 IN 3 + V/I in 3 -
10 IN 3 – I in 3 +
11 ANL COM ANLG Com
+24V DC
DC NEUT

External 24V DC +
Power Supply -

1746-NIO4I to 1769-IF4XOF2

1746-NIO4I 1769-IF4XOF2 Single-ended Sensor/Transmitter Inputs


Analog Current Output Module Sensor/ +
Transmitter - Current V in 0+
Supply I in 0+
+ + Signal V/I in 0 -
analog V in 1+
source 0 IN 0 +
1 IN 0 – I in 1+

earth 2 ANL COM V/I in 1-
ground
3 IN 1 + Voltage V in 2+
Jumper unused I in 2+
inputs. 4 IN 1 – + Signal
5 ANL COM V/I in 2-
6 not used V in 3+
Load
7 OUT 0 I in 3+
8 ANL COM V/I in 3-
earth
ground 9 not used ANLG Com
Do not jumper
unused outputs. 10 OUT 1 ANLG Com
11 ANL COM V out 0+
I out 0+
V out 1+
I out 1 +

The sensor power supply must be rated Class 2.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 41


Appendix A Wiring Diagram Comparisons

1746-NIO4V to 1769-IF4XOF2

1746-NIO4V 1769-IF4XOF2 Single-ended Sensor/Transmitter Inputs


1746-NIO4V
Analog Current Output Module
Analog Voltage Output Module Sensor/ +
Transmitter - Current V in 0+
Supply I in 0+
+ Signal V/I in 0 -
+
V in 1+
Analog
source 0 IN 0 + I in 1+
– 1 IN 0 – V/I in 1-
Earth 2 ANL COM Voltage V in 2+
ground
3 IN 1 + + I in 2+
Jumper unused
4 IN 1 –
Signal
inputs. V/I in 2-
5 ANL COM V in 3+

Load 6 Not used I in 3+


7 OUT 0 V/I in 3-
8 ANL COM ANLG Com
Earth
ground
Do not jumper
9 Not used ANLG Com
unused outputs. 10 OUT 1 V out 0+
11 ANL COM
I out 0+
V out 1+
I out 1 +

The sensor power supply must be rated Class 2.

1746-NI8 to 1769-IF8

1746-NI8 1769-IF8 Single-ended Sensor/Transmitter Inputs


Analog Input Module
Power
Supply Sensor/ +
Shield
Connections Transmitter - V in 0 +
+ + + Supply Current
single-end Channel 0 V/I in 0 -
-
signal source
- + Signal
shield I in 0 +
+
single-end + ANLG Com
Channel 1
signal source V in 1 +
-
shield V/I in 1 -
+ + Voltage
single-end Channel 2 I in 1 +
signal source ANLG Com
shield
- + Ground Signal
+ V in 2 +
single-end +
Channel 3
signal source V/I in 2 -
-
shield I in 2 +
+ Voltage
+ + ANLG Com
differential
signal source -
Channel 4 + Ground Signal V in 3 +
- -
shield
+ V/I in 3 -
+ differential +
Channel 5 I in 3 +
signal source -
- - ANLG Com
shield
+ NC
+ +
differential Channel 6
signal source - NC
- -
shield
+
+
+
The sensor power supply must be rated Class 2.
differential Channel 7 Wiring for channels 4…7 are identical.
signal source -
- -
shield
Shield

42 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-NO4I to 1769-OF4
1769-OF4
1746-NO4I Analog Output Module
Analog Voltage Output Wiring

V Out 3+
0 +24V DC I Out 3+
1 DC COM V Out 2+
Voltage load I Out 2+
0 OUT 0 ANLG COM
1 ANL COM ANLG COM
Earth ground V Out 0+
2 OUT 1
I Out 0+
3 ANL COM
Current load V Out 1+
4 OUT 2 I Out 1 +
5 ANL COM
Earth ground
6 OUT 3
7 ANL COM

1746-NO4V to 1769-OF4

1769-OF4
1746-NO4V Analog Output Module
Analog Voltage Output Wiring
V Out 3+
0 +24V DC I Out 3+
1 DC COM V Out 2+
Voltage load I Out 2+
ANLG COM
0 OUT 0
ANLG COM
1 ANL COM Earth ground V Out 0+
2 OUT 1 I Out 0+
3 ANL COM V Out 1+
Current load
4 OUT 2 I Out 1 +
5 ANL COM
Earth ground
6 OUT 3
7 ANL COM

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 43


Appendix A Wiring Diagram Comparisons

Replace an SLC 500 I/O with See the installations instructions and technical data of the associated catalogs
a Compact 5000 I/O for the detailed wiring instructions.

IMPORTANT The 5069-IA16 module inputs use a shared common. The inputs have a
return through internal module circuitry to the SA(–) terminal on the SA
power RTB.
If you install modules in a Compact 5000 I/O system that use AC SA power
and DC SA power, you must install them on separate SA power buses.

1746-IA16 to 5069-IA16
1746-IA16 5069-IA16
100/120V AC 120/240V AC Input Module

L1
IN 0
0 IN 1
IN 2 1
2 IN 3
IN 4 3 Input Channel 0 (I00)
4 IN 5 Input Channel 1 (I01)
IN 6 5 Input Channel 2 (I02)
100/120V AC 6 IN 7
Input Channel 3 (I03)
7
IN 8 Input Channel 4 (I04)
10 IN 9
11
Input Channel 5 (I05)
IN 10
IN 11 Input Channel 6 (I06)
12
IN 12 13 Input Channel 7 (I07)
14 IN 13 Input Channel 8 (I08)
IN 14 15 Input Channel 9 (I09)
16 IN 15 Input Channel 10 (I10)
17
L2 AC COM Input Channel 11 (I11)
AC COM Input Channel 12 (I12)
SA+ (L1) Input Channel 13 (I13)
Internally Connected 120V/240V
SLC AC Input Channel 14 (I14)
Commons SA– (L2)
PLC Input Channel 15 (I15)
No Connect
No Connect

1746-IM16 to 5069-IA16
5069-IA16
1746-IM16 120/240V AC Input Module
200/240V AC
L1
IN 0
0 IN 1
1
IN 2
IN 3
2
3
Input Channel 0 (I00)
IN 4
IN 5
Input Channel 1 (I01)
4
5 Input Channel 2 (I02)
IN 6
200/240V AC 6 IN 7 Input Channel 3 (I03)
IN 8 7 Input Channel 4 (I04)
10 IN 9 Input Channel 5 (I05)
IN 10 11 Input Channel 6 (I06)
12 IN 11 Input Channel 7 (I07)
13
IN 12
14 IN 13
Input Channel 8 (I08)
15 Input Channel 9 (I09)
IN 14
16 IN 15 Input Channel 10 (I10)
17 Input Channel 11 (I11)
L2 AC COM
AC COM Input Channel 12 (I12)
SA+ (L1) Input Channel 13 (I13)
Internally Connected 120V/240V
SLC AC Input Channel 14 (I14)
Commons SA– (L2)
PLC Input Channel 15 (I15)
No Connect
No Connect

44 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-IB16 to 5069-IB16
5069-IB16
1746-IB16 24V DC Sinking Input Module
24V DC Sinking
+DC
IN 0
0 IN 1
IN 2 1
2 IN 3
IN 4 3 Input Channel 0 (I00)
4 IN 5 Input Channel 1 (I01)
5
IN 6 Input Channel 2 (I02)
24V DC 6 IN 7 2-wire
6 7 sensor Input Channel 3 (I03)
IN 8
10 IN 9 Input Channel 4 (I04)
IN 10 11 Input Channel 5 (I05)
DC (+) 3-wire Input Channel 6 (I06)
12 IN 11
13 DC (–) sensor
IN 12 Input Channel 7 (I07)
14 IN 13 Input Channel 8 (I08)
15
IN 14 Input Channel 9 (I09)
16 IN 15
17 Input Channel 10 (I10)
-DC DC COM Input Channel 11 (I11)
DC COM
Input Channel 12 (I12)
Input Channel 13 (I13)
Internally Connected Commons SLC
Input Channel 14 (I14)
PLC
Input Channel 15 (I15)
No Connect
No Connect

1746-ITB16 to 5069-IB16
1746 -ITB16 5069-IB16
24V DC Sinking Input Module
24V DC Sinking
+DC
IN 0
0 IN 1
IN 2 1
2 IN 3
3 Input Channel 0 (I00)
IN 4
4 IN 5 Input Channel 1 (I01)
24V DC IN 6 5 Input Channel 2 (I02)
2-wire
6 IN 7
sensor Input Channel 3 (I03)
IN 8 6
7 Input Channel 4 (I04)
10 IN 9 Input Channel 5 (I05)
IN 10 11 DC (+) 3-wire Input Channel 6 (I06)
12 IN 1 1 DC (–) sensor
13 Input Channel 7 (I07)
IN 12
IN 13 Input Channel 8 (I08)
14
15 Input Channel 9 (I09)
IN 14
16 IN 15 Input Channel 10 (I10)
DC 17 Input Channel 11 (I11)
-DC COM DC COM Input Channel 12 (I12)
Input Channel 13 (I13)
Internally Connected Commons Input Channel 14 (I14)
SLC
PLC Input Channel 15 (I15)
No Connect
No Connect

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 45


Appendix A Wiring Diagram Comparisons

1746-OA8 to 5069-OA16

IMPORTANT If the modules in the 5069 rack require more than one type of SA bus, for
example 24V DC and 240V AC, use a 5069-FPD (field potential distributor) to
separate the bus and these modules.

1746-OA8 5069-OA16
100...240V AC Triac Output 120...240V AC Output Module

VAC 1 L1

OUT 0
CR Output Channel 0 (O00)
OUT 1 100…240V AC Output Channel 1 (O01)
CR
Output Channel 2 (O02)
OUT 2 Output Channel 3 (O03)
OUT 3 CR L2 CR Output Channel 4 (O04)
Output Channel 5 (O05)
VAC 2 L1 Output Channel 6 (O06)
Output Channel 7 (O07)
OUT 4 CR Output Channel 8 (O08)
100…240V AC Output Channel 9 (O09)
OUT 5 Output Channel 10 (O10)
CR Output Channel 11 (O11)
OUT 6
CR Output Channel 12 (O12)
OUT 7 CR L2 Output Channel 13 (O13)
Output Channel 14 (O14)
Output Channel 15 (O15)
No Connect
SA– (L2) 120/240V
AC No Connect
SA+ (L1)

1746-OA16 to 5069-OA16

IMPORTANT If the modules in the 5069 rack require more than one type of SA bus,
for example 24V DC and 240V AC, use a 5069-FPD (field potential
distributor) to separate the bus and these modules.

1746-OA16 5069-OA16
100...240V AC Triac Output 120...240V AC Output Module

L1
VAC 1
OUT0
OUT 1 0
1 OUT 2
OUT 3 2
100…240V AC 3 OUT 4
Output Channel 0 (O00)
OUT 5 4
CR CR
CR 5 OUT 6 Output Channel 1 (O01)
OUT 7 6 CR Output Channel 2 (O02)
CR 7 Output Channel 3 (O03)
L2 CR Output Channel 4 (O04)
Output Channel 5 (O05)
VAC 2 L1 Output Channel 6 (O06)
OUT 9
11 OUT 8 Output Channel 7 (O07)
OUT 1 1 10 CR Output Channel 8 (O08)
13 OUT 10 Output Channel 9 (O09)
OUT 13 12 100…240V AC Output Channel 10 (O10)
CR 15 OUT 12 Output Channel 11 (O11)
CR
OUT 15 14 CR Output Channel 12 (O12)
CR 17 OUT 14
CR Output Channel 13 (O13)
16
SLC Output Channel 14 (O14)
PLC
L2 Output Channel 15 (O15)
No Connect
SA– (L2) 120/240V
No Connect
SA+ (L1) AC

46 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

IMPORTANT The 5069-OB8 and 5069-OB16 modules Local Actuator (LA+ and LA–)
connections are used to supply field-side power to the module. The module
does not draw current from the SA power bus that is internal to the system.
For the 5069-OB8 module, output channels 0…3 use LA0 +/-, and output
channels 4…7 use LA1 +/-.

1746-OB8 to 5069-OB8
1746-OB8 5069-OB8
10...50V DC Transistor Output-sourcing 24V DC Sourcing Output Module

VDC +DC
OUT 0
CR Output Channel 0 (O00)
OUT 1 Output Channel 1 (O01)
Output Channel 2 (O02)
OUT 2
Output Channel 3 (O03)
OUT 3 LA0 –
10…50V DC LA0 –
OUT 4 CR LA0 –
– LA0 –
24V DC
OUT 5 CR + LA0 +
Output Channel 4 (O04)
OUT 6 CR Output Channel 5 (005)
Output Channel 6 (006)
OUT 7 CR
Output Channel 7 (007)
DC -DC LA1 –
COM
LA1 –
LA1 –
LA1 –
LA1 +

1746-OBP8 to 5069-OB8
1746-OBP8 5069-OB8
20.4...26.4V DC Transistor Output-sourcing 24V DC Sourcing Output Module

+DC VDC1
OUT 0
CR OUT 1
OUT 2
CR OUT 3
20.4…26.4V DC DC
CR Output Channel 0 (O00)
COM1
NC Output Channel 1 (O01)
NC Output Channel 2 (O02)
NC Output Channel 3 (O03)
LA0 –
LA0 –
-DC
LA0 –
NC – LA0 –
24V DC
NC + LA0 +
NC Output Channel 4 (O04)
+DC VDC2 Output Channel 5 (005)
OUT 4 Output Channel 6 (006)
CR OUT 5 Output Channel 7 (007)
OUT 6
20.4…26.4V DC LA1 –
OUT 7
CR
DC LA1 –
COM2 LA1 –
-DC LA1 –
LA1 +

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 47


Appendix A Wiring Diagram Comparisons

1746-OBP16 to 5069-OB16
5069-OB16
1746-OBP16
24V DC Sourcing Output Module
20.4...26.4V DC SLC
Transistor Output-sourcing PLC

+DC VDC
OUT 0
0
OUT 1
1 OUT 2
2
OUT 3
3 OUT 4 Output Channel 0 (O00)
OUT 5 4 Output Channel 1 (O01)
CR
5 OUT 6 Output Channel 2 (O02)
6
CR
OUT 7
OUT 8 Output Channel 3 (O03)
7
20.4…26.4V DC (1746-OBP16) 10
CR Output Channel 4 (O04)
OUT 9
11 OUT 10 Output Channel 5 (O05)
CR
OUT 11 12 Output Channel 6 (O06)
13 OUT 12
CR Output Channel 7 (O07)
CR
OUT 13 14
Output Channel 8 (O08)
15 OUT 14
OUT 15 16 CR DC (–) Output Channel 9 (O09)
CR 17 Output Channel 10 (O10)
DC COM Output Channel 11 (O11)
Output Channel 12 (O12)
-DC Output Channel 13 (O13)
Output Channel 14 (O14)
Output Channel 15 (O15)
+ LA+
24V DC
– LA-

1746-OB16 to 5069-OB16
5069-OB16
1746-OB16
10...50V DC Transistor Output-sourcing SLC
24V DC Sourcing Output Module
PLC

+DC VDC
OUT 0
0
OUT 1
1 OUT 2
2
OUT 3
3 OUT 4
4 Output Channel 0 (O00)
CR OUT 5
5 OUT 6 Output Channel 1 (O01)
CR OUT 7
6 Output Channel 2 (O02)
7 OUT 8 CR Output Channel 3 (O03)
10…50V DC 10
OUT 9
11 OUT 10 Output Channel 4 (O04)
OUT 11 12
CR
Output Channel 5 (O05)
13 OUT 12
CR
Output Channel 6 (O06)
CR
OUT 13 14 Output Channel 7 (O07)
15 OUT 14
16 CR Output Channel 8 (O08)
OUT 15
CR 17 DC (–) Output Channel 9 (O09)
DC COM Output Channel 10 (O10)
Output Channel 11 (O11)
-DC Output Channel 12 (O12)
Output Channel 13 (O13)
Output Channel 14 (O14)
Output Channel 15 (O15)
+ LA+
24V DC
– LA-

48 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-OB16E to 5069-OB16
1746-OB16E 5069-OB16
10...30V DC SLC
24V DC Sourcing Output Module
Transistor Output-sourcing PLC

+DC VDC
OUT 0
0
OUT 1
1 OUT 2
2
OUT 3
3 OUT 4
OUT 5 4 Output Channel 0 (O00)
CR
5 OUT 6
Output Channel 1 (O01)
6
CR
OUT 7
7 OUT 8 Output Channel 2 (O02)
10…30V DC OUT 9 10
CR
Output Channel 3 (O03)
11 OUT 10
CR Output Channel 4 (O04)
OUT 11 12 Output Channel 5 (O05)
13 OUT 12
14
CR Output Channel 6 (O06)
OUT 13
CR 15 OUT 14 Output Channel 7 (O07)
CR
OUT 15 16 Output Channel 8 (O08)
CR 17
DC (–) Output Channel 9 (O09)
DC COM
Output Channel 10 (O10)
Output Channel 11 (O11)
-DC
Output Channel 12 (O12)
Output Channel 13 (O13)
Output Channel 14 (O14)
Output Channel 15 (O15)
+ LA+
24V DC
– LA-

IMPORTANT The 5069-OW4I module does not use SA power. That is, it does not draw
current from the SA power bus. The module passes it through to the next
Compact 5000 I/O module in the system.

1746-OW4 to 5069-OW4I
5069-OW4I
1746-OW4
Isolated Relay Output Module
Relay Output

VAC-VDC L1 or +DC

OUT 0 Power
Supply 0A
V AC/DC 0B
OUT 1
1A
CR Load 1B
OUT 2
2A
OUT 3 CR L2 or -DC 2B
3A
NOT 3B
USED
NOT
USED
NOT
USED
NOT Terminals
USED are unused
OUT
NOT7
USED

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 49


Appendix A Wiring Diagram Comparisons

1746-OW8 to 5069-OW4I
5069-OW4I
1746-OW8
Isolated Relay Output Module
Relay Output

VAC-VDC
1 L1 or +DC

OUT 0
Power
Supply 0A
V AC/DC
OUT 1 0B
CR 1A
OUT 2
Load 1B
OUT 3 CR L2 or -DC 2A
2B
VAC-VDC L1 or +DC 3A
2
3B
OUT 4

OUT 5 V AC/DC

OUT 6 CR
Terminals
OUT 7 CR L2 or -DC are unused

1746-OW16 to 5069-OW16
1746-OW16 5069-OW16
Relay Output Digital 16-point Relay Output Module
L1 or +DC
RELAY OUTPUT
VAC-VDC
1 OUT0
OUT 1 0
1 OUT 2
OUT 3 2 5069-OW16
V AC/DC 3 OUT 4 CR
OUT 5 4
CR CR Output Channel 0
5 OUT 6
6 CR Output Channel 1
OUT 7
CR CR Output Channel 2
7
Output Channel 3
L2 or -DC L1 or +DC Output Channel 4
VAC-VDC Output Channel 5
OUT 9 2
Output Channel 6
11 OUT 8 Output Channel 7
10
OUT 11 Power Supply Common 0
OUT 10
13 Output Channel 8
OUT 13 12 V AC/DC
CR Output Channel 9
15 OUT 12 CR Output Channel 10
OUT 15 14
CR Output Channel 11
17 OUT 14
16 CR Output Channel 12
SLC
Output Channel 13
PLC
L2 or -DC Output Channel 14
Output Channel 15
Common 1

IMPORTANT The 5069-OW16 module requires an external surge suppressor for inductive
loads. For more information on adding surge suppressors, see the Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.

50 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-OX8 to 5069-OX4I
1746-OX8 5069-OX4I
Channel-to-channel Isolated Relay Output Digital 4-point Isolated Normally-open/
Normally-closed Output Module RELAY OUTPUT

VAC-VDC Power
VS0 L1 0 Supply
OUT 0 CR VS0 L2 5069-OX4I

VS1 L1 VAC-VDC
1
OUT 1 VS1 L2 Load (0 N.C.)
VS2 VDC VAC-VDC
2 (0 N.O.)
OUT 2 VS2 DC COM
VAC±VDC (O COMMON)
VS3 VDC 3 (1 N.C.)
OUT 3 Power
CR VS3 DC COM (1 N.O.)
Supply
NOT USED (1 COMMON)
NOT
USED (2 N.C.)
VAC-VDC
VS4 L1 4 (2 N.O.)
OUT 4 CR Load
VS4 L2 (2 COMMON)
VAC-VDC
VS5 L1 5 (3 N.C.)
OUT 5 VS5 L2 (3 N.O.)
VS6 VDC VAC-VDC (3 COMMON)
6
OUT 6 VS6 DC COM
VAC-VDC
VS7 VDC 7
OUT 7 CR Terminals
VS7 DC COM
are unused

1746-NI4 to 5069-IY4

IMPORTANT Channel Connections: The diagram shows devices that are connected to
channels 0, 1, 2, and 3. You are not restricted to using only this channel.
You can connect devices to any channel or combination of channels as
needed.

5069-IY4
1746-NI4 Analog Voltage Input Module
ANALOG INPUT

Analog Input Module


+
4-wire +
24V DC Differential 5069-IY4

Voltage –

+ 0

analog Shield Ground 1

source 0 IN 0 + Input 0 + 2

– 1 IN 0 – Input 0 – 3
earth ANL COM +
ground 2 RTD – 4
4-wire +
+ 3 IN 1 + 24V DC Differential
Input 1 + 5

analog Voltage – Input 1 – 6

source 4 IN 1 – – RTD – 7

5 ANL COM Shield Ground Input 2 +


– earth
8

ground 6 IN 2 + +
Input 2 – 9

7 IN 2 – 4-wire + RTD – 10

Jumper unused 8 ANL COM 24V DC Differential 11

inputs. Voltage – 12
9 IN 3 + – Input 3 + 13

10 IN 3 – Input 3 – 14

11 ANL COM RTD – 15

Shield 16

Shield 17
+
4-wire +
24V DC Differential
Voltage –

Note: 5069-IY4 modules only


support differential input.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 51


Appendix A Wiring Diagram Comparisons

IMPORTANT • This example shows separate power supplies for each device.
We recommend that you use separate power supplies to help improve the
noise immunity.
However, if you use separate power supplies, you must verify that the
common mode voltage between any two power supplies does not exceed
10V DC.
• This module has only two shield terminals. Compact 5000 I/O module RTBs
only support one wire per terminal.
If you connect more than two devices to the module, you can ground two
devices at the shield terminals. You must ground the remaining devices
somewhere else, such as, to the DIN rail via a terminal strip.

1746-NI8 to 5069-IF8

IMPORTANT Channel Connections: The diagram shows a device that is connected


to channel 0. You are not restricted to using only this channel.
You can connect devices to any channel or combination of channels as
needed.

5069-IF8
1746-NI8 Analog 8-channel Current/Voltage Input
Analog Input Module Module ANALOG INPUT
Power
Supply
Shield
Connections
+ + +
single-end Channel 0
signal source 5069-IF8
- - i
shield
+ –
single-end + 2-wire A
Channel 1 Input 0 +
signal source Transmitter
- 24V DC A Input 0 -
shield +
+ + + – Input 1 +
single-end Channel 2
signal source Input 1 -
-
shield Shield Input 2 +
+
single-end + Ground Input 2 -
Channel 3
signal source
- Input 3 +
shield
+ +
Input 3 -
+ differential Channel 4 Input 4 +
signal source - -
-
shield Input 4 -
+
+ differential + Input 5 +
Channel 5
signal source - Input 5 -
- -
shield Input 6 +
+
+ +
differential Channel 6 Input 6 -
signal source -
- - Input 7 +
shield
+
+ + Input 7 -
differential Channel 7
signal source - Shield
- -
shield Shield
Shield
Note: 5069-IF8 modules only
support differential input.

IMPORTANT Place additional loop devices, for example, strip chart recorders, at either A
location in the current loop.

52 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

1746-NO4I to 5069-OF4
5069-OF4
Analog Current/Voltage Output Module

1746-NO4I
Analog Voltage Output Wiring

0 +24V DC
1 DC COM
Differential
Voltage + Output 0 +
0 OUT 0 Receiver or – Output 0 –
Input
1 ANL COM Output 1 +
OUT 1 Output 1 –
2
3 ANL COM Output 2 +
Output 2 –
4 OUT 2 Shield Output 3 +
5 ANL COM Ground Output 3 –
6 OUT 3
7 ANL COM

Shield
Shield

1746-NO4V to 5069-OF4
5069-OF4
Analog Current/Voltage Output Module
1746-NO4V
Analog Voltage Output Wiring

0 +24V DC
1 DC COM Differential
Voltage + Output 0 +
Receiver or – Output 0 –
Input
Output 1 +
0 OUT 0 Output 1 –
1 ANL COM Output 2 +
Output 2 –
2 OUT 1 Shield Output 3 +
3 ANL COM Ground Output 3 –

4 OUT 2
5 ANL COM
6 OUT 3
7 ANL COM

Shield
Shield

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 53


Appendix A Wiring Diagram Comparisons

Replace an SLC 500 I/O with See the installations instructions and technical data of the associated catalogs
Combinations of Compact for the detailed wiring instructions.
5000 I/O Topic Page
Indirect Wiring Migration for 1746-IA4 to 5069-IA16 54
Indirect Wiring Migration for 1746-IA8 to 5069-IA16 56
Indirect Wiring Migration for 1746-IB8 to 5069-IB16 57
Indirect Wiring Migration for 1746-IM4 to 5069-IA16 59
Indirect Wiring Migration for 1746-IM8 to 5069-IA16 60
Indirect Wiring Migration for 1746-IO4 to 5069-IA16 and 5069-OW16 62
Indirect Wiring Migration for 1746-IO8 to 5069-IA16 and 5069-OW16 64
Indirect Wiring Migration for 1746-IO12 to 5069-IA16 and 5069-OW16 66
Indirect Wiring Migration for 1746-NI16I to 5069-IF8 68
Indirect Wiring Migration for 1746-NI16V to 5069-IF8 69
Indirect Wiring Migration for 1746-NIO4I to 5069-OF4 and 5069-IY4 70
Indirect Wiring Migration for 1746-NIO4V to 5069-OF4 and 5069-IY4 72
Indirect Wiring Migration for 1746-NR8 to 5069-IY4 74
Indirect Wiring Migration for 1746-OB8 to 5069-OB16 75
Indirect Wiring Migration for 1746-OBP8 to 5069-OB16 77
Indirect Wiring Migration for 1746-OW4 to 5069-OW16 78

Indirect Wiring Migration for 1746-IA4 to 5069-IA16


The solution allows for indirect wiring migration for up to four SLC 1746-IA4
modules to a single CompactLogix 5069-IA16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.

There are no uninsulated wires that could cause danger for user or installer.

54 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 1 - 1746-IA4 to 5069-IA16


1746-IA4 5069-IA16
100/120V AC 120/240V AC Input Module

NOT
USED
NOT
USED
NOT
USED
Input Channel 0 (I00)
Input Channel 1 (I01)
NOT
USED Input Channel 2 (I02)
L1 Input Channel 3 (I03)
IN 0
Input Channel 4 (I04)
IN 1 Input Channel 5 (I05)
Input Channel 6 (I06)
100/120V AC IN 2 Input Channel 7 (I07)
Input Channel 8 (I08)
IN 3
Input Channel 9 (I09)
L2 AC COM Input Channel 10 (I10)
Input Channel 11 (I11)
SA+ (L1) Input Channel 12 (I12)
120V/240V Input Channel 13 (I13)
AC
SA– (L2) Input Channel 14 (I14)
Input Channel 15 (I15)
No Connect
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module.

Wiring is transferred to the 1746-RT25R terminal block and installed on the


1492-CN1746-M01 conversion module.

Figure 2 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 2 - 4 x 1746-IA4 to 5069-IA16


1746-IA4 (1) 1746-IA4 (2) 1746-IA4 (3) 1746-IA4 (4) 1746-RT25R
5069-IA16
NOT USED NOT USED NOT USED NOT USED IN 0 (1)
IN 1 (1)
NOT USED NOT USED NOT USED NOT USED IN 2 (1)
IN 3 (1)
NOT USED NOT USED NOT USED NOT USED IN 0 (2)
IN 1 (2)
NOT USED NOT USED NOT USED NOT USED IN 2 (2)
IN 3 (2)
IN 0 IN 0 IN 0 IN 0 IN 0 (3)
IN 1 (3)
IN 1 IN 1 IN 1 IN 1 IN 2 (3)
IN 3 (3)
IN 2 IN 2 IN 2 IN 2 IN 0 (4)
IN 1 (4)
IN 3 IN 3 IN 3 IN 3 IN 2 (4)
IN 3 (4)
AC COM AC COM AC COM AC COM

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 55


Appendix A Wiring Diagram Comparisons

Figure 3 - Conversion Module - 1492-CM1746-M01

Indirect Wiring Migration for 1746-IA8 to 5069-IA16


The solution allows for indirect wiring migration for up to two SLC 1746-IA8
modules to a single CompactLogix 5069-IA16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.
Figure 4 - 1746-IA8 to 5069-IA16
5069-IA16
1746-IA8
100/120V AC 120/240V AC Input Module

L1 IN 0

IN 1
Input Channel 0 (I00)
IN 2 Input Channel 1 (I01)
Input Channel 2 (I02)
IN 3
Input Channel 3 (I03)
100/120V AC
IN 4 Input Channel 4 (I04)
Input Channel 5 (I05)
IN 5 Input Channel 6 (I06)
Input Channel 7 (I07)
IN 6 Input Channel 8 (I08)
Input Channel 9 (I09)
IN 7
Input Channel 10 (I10)
L2 AC COM Input Channel 11 (I11)
Input Channel 12 (I12)
Internally Connected SA+ (L1) Input Channel 13 (I13)
AC COM
120V/240V
Commons AC Input Channel 14 (I14)
SA– (L2)
Input Channel 15 (I15)
No Connect
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module.

56 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Wiring is transferred to the 1746-RT25R terminal block and installed on the


1492-CN1746-M01 conversion module.

Figure 5 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 5 - 2 x 1746-IA8 to 5069-IA16

1746-IA8 (1) 1746-IA8 (2) 1746-RT25R


5069-IA16

IN 0 IN 0 IN 0 (1)
IN 1 (1)
IN 1 IN 1 IN 2 (1)
IN 3 (1)
IN 2 IN 2 IN 4 (1)
IN 5 (1)
IN 3 IN 3 IN 6 (1)
IN 7 (1)
IN 4 IN 4 IN 0 (2)
IN 1 (2)
IN 5 IN 5 IN 2 (2)
IN 3 (2)
IN 6 IN 6 IN 4 (2)
IN 5 (2)
IN 7 IN 7 IN 6 (2)
IN 7 (2)
AC COM AC COM
AC COM AC COM

Figure 6 - Conversion Module - 1492-CM1746-M01

Indirect Wiring Migration for 1746-IB8 to 5069-IB16


The solution allows for indirect wiring migration for up to two SLC 1746-IB8
modules to a single CompactLogix 5069-IB16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 57


Appendix A Wiring Diagram Comparisons

Figure 7 - 1746-IB8 to 5069-IB16


5069-IB16
1746-IB8 24V DC Sinking Input Module
24V DC Sinking

+DC IN 0

IN 1

IN 2 Input Channel 0 (I00)


Input Channel 1 (I01)
IN 3 Input Channel 2 (I02)
2-wire
24V DC sensor Input Channel 3 (I03)
IN 4 Input Channel 4 (I04)
Input Channel 5 (I05)
IN 5 DC (+) 3-wire Input Channel 6 (I06)
DC (–) sensor
IN 6 Input Channel 7 (I07)
Input Channel 8 (I08)
IN 7 Input Channel 9 (I09)
Input Channel 10 (I10)
-DC DC COM
Input Channel 11 (I11)
DC COM
Input Channel 12 (I12)
Internally Connected Input Channel 13 (I13)
Input Channel 14 (I14)
Commons Input Channel 15 (I15)
No Connect
No Connect

IMPORTANT The DC COM wire is transferred to DC- of the 24V DC source.

Wiring is transferred to the 1746-RT25R terminal block and installed on the


1492-CN1746-M01 conversion module.

Figure 8 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 8 - 2 x 1746-IB8 to 5069-IB16


1746-IB8 (1) 1746-IB8 (2) 1746-RT25R
5069-IB16
IN 0 IN 0 IN 0 (1)
IN 1 (1)
IN 1 IN 1 IN 2 (1)
IN 3 (1)
IN 2 IN 2 IN 4 (1)
IN 5 (1)
IN 3 IN 3 IN 6 (1)
IN 7 (1)
IN 4 IN 4 IN 0 (2)
IN 1 (2)
IN 5 IN 5 IN 2 (2)
IN 3 (2)
IN 6 IN 6 IN 4 (2)
IN 5 (2)
IN 7 IN 7 IN 6 (2)
IN 7 (2)
DC COM DC COM
DC COM DC COM

58 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 9 - Conversion Module - 1492-CM1746-M01

Indirect Wiring Migration for 1746-IM4 to 5069-IA16

The solution allows for indirect wiring migration for up to four SLC 1746-IM4
modules to a single CompactLogix 5069-IA16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.
Figure 10 - 1746-IM4 to 5069-IA16
1746-IM4 5069-IA16
200/240V AC 120/240V AC Input Module

NOT
USED
NOT
USED
Input Channel 0 (I00)
NOT
USED Input Channel 1 (I01)
NOT Input Channel 2 (I02)
USED Input Channel 3 (I03)
L1 IN 0
Input Channel 4 (I04)
Input Channel 5 (I05)
IN 1 Input Channel 6 (I06)
Input Channel 7 (I07)
200/240V AC IN 2 Input Channel 8 (I08)
Input Channel 9 (I09)
IN 3 Input Channel 10 (I10)
Input Channel 11 (I11)
L2 AC COM
Input Channel 12 (I12)
SA+ (L1) Input Channel 13 (I13)
120V/240V
AC Input Channel 14 (I14)
SA– (L2)
Input Channel 15 (I15)
No Connect
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 59


Appendix A Wiring Diagram Comparisons

Wiring is transferred to the 1746-RT25R terminal block and installed on the


1492-CN1746-M01 conversion module.

Figure 11 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 11 - 4 x 1746-IM4 to 5069-IA16

1746-IM4 (1) 1746-IM4 (2) 1746-IM4 (3) 1746-IM4 (4) 1746-RT25R


5069-IA16

NOT USED NOT USED NOT USED NOT USED IN 0 (1)


IN 1 (1)
NOT USED NOT USED NOT USED NOT USED IN 2 (1)
IN 3 (1)
NOT USED NOT USED NOT USED NOT USED IN 0 (2)
IN 1 (2)
NOT USED NOT USED NOT USED NOT USED IN 2 (2)
IN 3 (2)
IN 0 IN 0 IN 0 IN 0 IN 0 (3)
IN 1 (3)
IN 1 IN 1 IN 1 IN 1 IN 2 (3)
IN 3 (3)
IN 2 IN 2 IN 2 IN 2 IN 0 (4)
IN 1 (4)
IN 3 IN 3 IN 3 IN 3 IN 2 (4)
IN 3 (4)
AC COM AC COM AC COM AC COM

Figure 12 - Conversion Module - 1492-CM1746-M01

Indirect Wiring Migration for 1746-IM8 to 5069-IA16

The solution allows for indirect wiring migration for up to two SLC 1746-IM8
modules to a single CompactLogix 5069-IA16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

60 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 13 - 1746-IM8 to 5069-IA16


1746-IM8 5069-IA16
200/240V AC 120/240V AC Input Module

L1
IN 0

IN 1
Input Channel 0 (I00)
IN 2 Input Channel 1 (I01)
Input Channel 2 (I02)
IN 3 Input Channel 3 (I03)
200/240V AC Input Channel 4 (I04)
IN 4 Input Channel 5 (I05)
Input Channel 6 (I06)
IN 5 Input Channel 7 (I07)
Input Channel 8 (I08)
IN 6
Input Channel 9 (I09)
IN 7
Input Channel 10 (I10)
Input Channel 11 (I11)
L2 AC COM Input Channel 12 (I12)
SA+ (L1) Input Channel 13 (I13)
120V/240V
Internally Connected AC COM AC Input Channel 14 (I14)
SA– (L2)
Commons Input Channel 15 (I15)
No Connect
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module.

Wiring is transferred to the 1746-RT25R terminal block and installed on the


1492-CN1746-M01 conversion module.

Figure 14 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 14 - 2 x 1746-IM8 to 5069-IA16

1746-IM8 (1) 1746-IM8 (2) 1746-RT25R


5069-IA16

IN 0 IN 0 IN 0 (1)
IN 1 (1)
IN 1 IN 1 IN 2 (1)
IN 3 (1)
IN 2 IN 2 IN 4 (1)
IN 5 (1)
IN 3 IN 3 IN 6 (1)
IN 7 (1)
IN 4 IN 4 IN 0 (2)
IN 1 (2)
IN 5 IN 5 IN 2 (2)
IN 3 (2)
IN 6 IN 6 IN 4 (2)
IN 5 (2)
IN 7 IN 7 IN 6 (2)
IN 7 (2)
AC COM AC COM
AC COM AC COM

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 61


Appendix A Wiring Diagram Comparisons

Figure 15 - Conversion Module - 1492-CM1746-M01

Indirect Wiring Migration for 1746-IO4 to 5069-IA16 and 5069-OW16

The solution allows for indirect wiring migration for up to eight SLC 1746-IO4
modules to a combination of CompactLogix 5069-IA16 and 5069-OW16
modules. The wiring is a manual transfer process from the SLC terminal block
to the CompactLogix conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.
Figure 16 - 1746-IO4 to 5069-IA16 and 5069-OW16
5069-IA16 5069-OW16
120/240V AC Input Module Digital 16-point Relay Output Module
1746-IO4
100/120V AC Input - Relay Output RELAY OUTPUT

V AC-V DC L1 or +DC

OUT 0 5069-OW16
V AC/DC
OUT 1 CR L2 or -DC Input Channel 0 (I00) CR Output Channel 0
Input Channel 1 (I01) Output Channel 1
NOT USED
Input Channel 2 (I02) CR Output Channel 2
NOT USED Input Channel 3 (I03) Output Channel 3
Input Channel 4 (I04) Output Channel 4
L1 IN 0 Input Channel 5 (I05) Output Channel 5
L2
Input Channel 6 (I06) Output Channel 6
IN 1
Input Channel 7 (I07) AC-type L1
Output Channel 7
Common 0
100/120V AC NOT USED Input Channel 8 (I08) Power Supply
CR Output Channel 8
Input Channel 9 (I09) Output Channel 9
NOT USED Input Channel 10 (I10) CR Output Channel 10
L2 AC COM Input Channel 11 (I11) Output Channel 11
Input Channel 12 (I12) Output Channel 12
SA+ (L1) 120V/240V Input Channel 13 (I13) -24V DC Output Channel 13
AC Input Channel 14 (I14) Output Channel 14
SA– (L2)
Input Channel 15 (I15) DC-type
Output Channel 15
No Connect Power Supply Common 1
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module. The L1
wire is transferred to SA+ and V AC - V DC on the 5069-OW16 module.

62 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

AC Input wiring is transferred to the 1746-RT25R terminal block and installed


on the 1492-CN1746-M01 conversion module.

AC Output wiring is transferred to the 1746-RT25C terminal block and installed


on the 1492-CM1746-M04 conversion module.

Figure 17 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 17 - 8 x 1746-IO4 to 5069-IA16 and 5069-OW16


1746-IO4 (1) 1746-IO4 (3) 1746-IO4 (5) 1746-IO4 (7) 1746-RT25R 1746-RT25C
1746-IO4 (2) 1746-IO4 (4) 1746-IO4 (6) 1746-IO4 (8) 5069-IA16 5069-OW16

V AC-V DC V AC-V DC V AC-V DC V AC-V DC V AC-V DC V AC-V DC V AC-V DC V AC-V DC IN 0 (1) V AC-V DC 1
IN 1 (1) OUT 0 (1)
OUT 0 OUT 0 OUT 0 OUT 0 OUT 0 OUT 0 OUT 0 OUT 0 IN 0 (2) OUT 1 (1)
IN 1 (2) OUT 0 (2)
OUT 1 OUT 1 OUT 1 OUT 1 OUT 1 OUT 1 OUT 1 OUT 1 IN 0 (3) OUT 1 (2)
IN 1 (3) OUT 0 (3)
NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED IN 0 (4) OUT 1 (3)
IN 1 (4) OUT 0 (4)
NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED IN 0 (5) OUT 1 (4)
IN 1 (5) V AC-V DC 2
IN 0 IN 0 IN 0 IN 0 IN 0 IN 0 IN 0 IN 0 IN 0 (6) OUT 1 (5)
IN 1 (6) OUT 0 (5)
IN 1 IN 1 IN 1 IN 1 IN 1 IN 1 IN 1 IN 1 IN 0 (7) OUT 1 (6)
IN 1 (7) OUT 0 (6)
NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED IN 0 (8) OUT 1 (7)
IN 1 (8) OUT 0 (7)
NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED OUT 1 (8)
AC COM AC COM AC COM AC COM AC COM AC COM AC COM AC COM OUT 0 (8)

Figure 18 - Conversion Module - 1492-CM1746-M01

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 63


Appendix A Wiring Diagram Comparisons

Figure 19 - Conversion Module - 1492-CM1746-M04

Indirect Wiring Migration for 1746-IO8 to 5069-IA16 and 5069-OW16

The solution allows for indirect wiring migration for up to four SLC 1746-IO8
modules to a combination of CompactLogix 5069-IA16 and 5069-OW16
modules. The wiring is a manual transfer process from the SLC terminal block
to the CompactLogix conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

Figure 20 - 1746-IO8 to 5069-IA16 and 5069-OW16


5069-IA16 5069-OW16
120/240V AC Input Module Digital 16-point Relay Output Module
1746-IO8
100/120V AC Input - Relay Output RELAY OUTPUT

V AC-V DC L1 or +DC

OUT 0 V AC/DC 5069-OW16

OUT 1
Input Channel 0 CR Output Channel 0
OUT 2
Input Channel 1 Output Channel 1
CR
Input Channel 2 CR Output Channel 2
OUT 3 CR L2 or -DC Input Channel 3 Output Channel 3
L1 Input Channel 4 Output Channel 4
IN 0
Input Channel 5 L2
Output Channel 5
IN 1 Input Channel 6 Output Channel 6
100/ Input Channel 7 AC-type L1
Output Channel 7
120V AC IN 2 Common 0
Input Channel 8 Power Supply
CR Output Channel 8
IN 3 Input Channel 9 Output Channel 9
Input Channel 10 CR Output Channel 10
L2 AC COM
Input Channel 11 Output Channel 11
Input Channel 12 Output Channel 12
SA+ (L1) 120V/240V Input Channel 13 -24V DC Output Channel 13
AC Input Channel 14 Output Channel 14
SA– (L2)
Input Channel 15 DC-type
Output Channel 15
No Connect Power Supply Common 1
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module. The L1
wire is transferred to SA+ and V AC - V DC on the 5069-OW16 module.

64 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

AC Input wiring is transferred to the 1746-RT25R terminal block and installed


on the 1492-CN1746-M01 conversion module.

AC Output wiring is transferred to the 1746-RT25C terminal block and installed


on the 1492-CM1746-M04 conversion module.

Figure 21 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 21 - 4 x 1746-IO8 to 5069-IA16 and 5069-OW16


1746-IO8 (1) 1746-IO8 (3) 1746-RT25R 1746-RT25C
1746-IO8 (2) 1746-IO8 (4) 5069-IA16 5069-OW16

V AC-V DC V AC-V DC V AC-V DC V AC-V DC IN 0 (1) V AC-V DC 1


IN 1 (1) OUT 0 (1)
OUT 0 OUT 0 OUT 0 OUT 0 IN 0 (2) OUT 1 (1)
IN 1 (2) OUT 0 (2)
OUT 1 OUT 1 OUT 1 OUT 1 IN 0 (3) OUT 1 (2)
IN 1 (3) OUT 0 (3)
OUT 2 OUT 2 OUT 2 OUT 3 IN 0 (4) OUT 1 (3)
IN 1 (4) OUT 0 (4)
OUT 3 OUT 3 OUT 3 OUT 4 IN 0 (5) OUT 1 (4)
IN 1 (5) V AC-V DC 2
IN 0 IN 0 IN 0 IN 0 IN 0 (6) OUT 1 (5)
IN 1 (6) OUT 0 (5)
IN 1 IN 1 IN 1 IN 1 IN 0 (7) OUT 1 (6)
IN 1 (7) OUT 0 (6)
IN 2 IN 2 IN 2 IN 2 IN 0 (8) OUT 1 (7)
IN 1 (8) OUT 0 (7)
IN 3 IN 3 IN 3 IN 3 OUT 1 (8)
OUT 0 (8)
AC COM AC COM AC COM AC COM

Figure 22 - Conversion Module - 1492-CM1746-M01

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 65


Appendix A Wiring Diagram Comparisons

Figure 23 - Conversion Module - 1492-CM1746-M04

Indirect Wiring Migration for 1746-IO12 to 5069-IA16 and 5069-OW16

The solution allows for indirect wiring migration for up to two SLC 1746-IO12
modules to a combination of CompactLogix 5069-IA16 and 5069-OW16
modules. The wiring is a manual transfer process from the SLC terminal block
to the CompactLogix conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.
Figure 24 - 1746-IO12 to 5069-IA16 and 5069-OW16
1746-IO12 5069-IA16 5069-OW16
100/120V AC Input - Relay Output 120/240V AC Input Module Digital 16-point Relay Output Module
L1 or +DC RELAY OUTPUT
VAC-VDC
OUT 0
OUT 1
OUT 2
V AC/DC OUT 3
OUT 4 CR 5069-OW16

CR OUT 5
NOT

Input Channel 0
USED
L2 or -DC CR Output Channel 0
L1 Input Channel 1 Output Channel 1
NOT
USED Input Channel 2 CR Output Channel 2
IN 0
IN 1 Input Channel 3 Output Channel 3

IN 3
IN 2 Input Channel 4 Output Channel 4
100/120V AC
IN 4 Input Channel 5 L2
Output Channel 5
IN 5
NOT
Input Channel 6 Output Channel 6
NOT
USED
USED
Input Channel 7 AC-type L1
Output Channel 7
AC COM Common 0
L2 Input Channel 8 Power Supply
CR Output Channel 8
Input Channel 9 Output Channel 9
Input Channel 10 CR Output Channel 10
Input Channel 11 Output Channel 11
Input Channel 12 Output Channel 12
SA+ (L1) 120V/240V Input Channel 13 -24V DC Output Channel 13
AC Input Channel 14 Output Channel 14
SA– (L2)
Input Channel 15 DC-type
Output Channel 15
No Connect Power Supply Common 1
No Connect

IMPORTANT You need to rewire AC POWER from the AC COM terminal to the 5069-FPD
module. The L2 wire is transferred to SA- on the 5069-FPD module. The L1
wire is transferred to SA+ and V AC - V DC on the 5069-OW16 module.

66 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

AC Input wiring is transferred to the 1746-RT25R terminal block and installed


on the 1492-CN1746-M01 conversion module.

AC Output wiring is transferred to the 1746-RT25C terminal block and installed


on the 1492-CM1746-M04 conversion module.

Figure 25 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 25 - 2 x 1746-IO12 to 5069-IA16 and 5069-OW16


1746-IO12 (1) 1746-IO12 (2) 1746-RT25R 1746-RT25C
5069-IA16 5069-OW16

V AC-V DC V AC-V DC IN 0 (1) V AC-V DC 1


OUT 0 OUT 0 IN 1 (1) OUT 0 (1)
OUT 1 OUT 1 IN 2 (1) OUT 1 (1)
OUT 2 OUT 2 IN 3 (1) OUT 2 (1)
OUT 3 OUT 3 IN 4 (1) OUT 3 (1)
OUT 4 OUT 4 IN 5 (1) OUT 4 (1)
OUT 5 OUT 5 IN 0 (2) OUT 5 (1)
NOT USED NOT USED IN 1 (2) OUT 0 (2)
NOT USED NOT USED IN 2 (2) OUT 1 (2)
IN 0 IN 0 IN 3 (2) V AC-V DC 1
IN 1 IN 1 IN 4 (2) OUT 3 (2)
IN 2 IN 2 IN 5 (2) OUT 2 (2)
IN 3 IN 3 OUT 5 (2)
IN 4 IN 4 OUT 4 (2)
IN 5 IN 5
NOT USED NOT USED
NOT USED NOT USED
AC COM AC COM

Figure 26 - Conversion Module - 1492-CM1746-M01

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 67


Appendix A Wiring Diagram Comparisons

Figure 27 - Conversion Module - 1492-CM1746-M04

Indirect Wiring Migration for 1746-NI16I to 5069-IF8

The solution allows for indirect wiring migration for a single SLC 1746-NI16I
module to a combination of two CompactLogix 5069-IF8 modules. The wiring
is a manual transfer process from the SLC terminal block to the CompactLogix
conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

Analog input wiring is transferred to the 1746-RT25B terminal block and


installed on the 1492-CN1746-M05 conversion module. The SLC module allows
for a group analog common return where the CompactLogix allows for a single
return per channel.

Figure 28 illustrates the correlating pinouts to use when moving installation


wiring.

68 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 28 - 1746-NI16I to 2 x 5069-IF8


1746-NI16I 1746-RT25B 1746-RT25B
5069-IF8 (1) 5069-IF8 (2)
IN 0
SHIELD SHIELD
IN 1
IN 2 CH 0+ CH 8+
CH 0- CH 8-
IN 3
IN 4 CH 1+ CH 9+
CH 1- CH 9-
IN 5
IN 6 CH 2+ CH 10+
CH 2- CH 10-
IN 7
ANL COM CH 3+ CH 11+
CH 3- CH 11-
ANL COM CH 12+
IN 8 CH 4+
CH 4- CH 12-
IN 9 CH 13+
IN 10 CH 5+
CH 5- CH 13-
IN 11
IN 12 CH 6+ CH 14+
CH 6- CH 14-
IN 13
IN 14 CH 7+ CH 15+
CH 7- CH 15-
IN 15 SHIELD SHIELD

Figure 29 - Conversion Module - 1492-CM1746-M05

Indirect Wiring Migration for 1746-NI16V to 5069-IF8

The solution allows for indirect wiring migration for a single SLC 1746-NI16V
module to a combination of two CompactLogix 5069-IF8 modules. The wiring
is a manual transfer process from the SLC terminal block to the CompactLogix
conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

Analog input wiring is transferred to the 1746-RT25B terminal block and


installed on the 1492-CN1746-M05 conversion module. The SLC module allows
for a group analog common return where the CompactLogix allows for a single
return per channel.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 69


Appendix A Wiring Diagram Comparisons

Figure 30 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 30 - 1746-NI16V to 2 x 5069-IF8


1746-NI16V 1746-RT25B 1746-RT25B
5069-IF8 (1) 5069-IF8 (2)
IN 0
SHIELD SHIELD
IN 1
IN 2 CH 0+ CH 8+
CH 0- CH 8-
IN 3
IN 4 CH 1+ CH 9+
CH 1- CH 9-
IN 5
IN 6 CH 2+ CH 10+
CH 2- CH 10-
IN 7
ANL COM CH 3+ CH 11+
CH 3- CH 11-
ANL COM CH 12+
IN 8 CH 4+
CH 4- CH 12-
IN 9 CH 13+
IN 10 CH 5+
CH 5- CH 13-
IN 11
IN 12 CH 6+ CH 14+
CH 6- CH 14-
IN 13
IN 14 CH 7+ CH 15+
CH 7- CH 15-
IN 15 SHIELD SHIELD

Figure 31 - Conversion Module - 1492-CM1746-M05

Indirect Wiring Migration for 1746-NIO4I to 5069-OF4 and 5069-IY4

The solution allows for indirect wiring migration for a single SLC 1746-NIO4I
module to a combination of one CompactLogix 5069-OF4 module and one
CompactLogix 5069-IY4 module. The wiring is a manual transfer process from
the SLC terminal block to the CompactLogix conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

70 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 32 - 1746-NIO4I to 5069-OF4 and 5069-IY4

5069-OF4 5069-IY4
1746-NIO4I Analog Current/Voltage Output Module Analog Current/Voltage Output Module
Analog Current Output Module
ANALOG INPUT
i
Differential
+ ANALOG OUTPUT +
Current A
Receiver or
4-wire +
+ – A 24V DC Differential 5069-IY4
Input
analog Voltage –
source 0 IN 0 + –
– 1 IN 0 – Shield Ground 5069-OF4
0
earth 2 ANL COM
ground Shield Ground 1
3 IN 1 +
Jumper unused Output 0 + 0 Input 0 + 2
inputs. 4 IN 1 –
5 ANL COM Output 0 – 1
Input 0 – 3

i Output 1 + 2 +
6 not used RTD – 4
Load 4-wire +
7 OUT 0 Differential Output 1 – 3 Input 1 + 5
8 ANL COM + 24V DC Differential
earth Current A Output 2 + 4 Input 1 – 6
Voltage –
ground
Do not jumper
9 not used Receiver or Output 2 – –
A 5
RTD – 7
unused outputs. 10 OUT 1 Input –
Shield Ground
11 ANL COM Output 3 + 6 Input 2 + 8

Output 3 – 7 Input 2 – 9
+
8
4-wire + RTD – 10
i
9
24V DC Differential 11
Differential Voltage –
+ 10 12
Current A –
11 Input 3 + 13
Receiver or A
Input – 12 Input 3 – 14

13 RTD – 15

14 Shield 16

15 Shield 17
+
Shield 16
4-wire +
Shield 17
Differential
24V DC
Voltage –

Analog input wiring is transferred to the 1746-RT27 terminal block and


installed on the 1492-CN1746-M06 conversion module.

Analog output wiring is transferred to the 1746-RT28 terminal block and


installed on the 1492-CN1746-M10 conversion module.

Figure 33 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 33 - 2 X 1746-NIO4I to 5069-OF4 and 5069-IY4


1746-NIO4I (1) 1746-NIO4I (2) 1746-RT27 1746-RT28
5069-OF4 5069-IY4

IN 0+ IN 0+ OUT 0 (1) IN 0+ (1)

IN 01 IN 01 ANL COM (1) IN 01 (1)

ANL COM ANL COM ANL COM (1)


OUT 1 (1)
IN 1+ IN 1+ IN 1+ (1)
ANL COM (1)
IN 1- IN 1- IN 1- (1)
OUT 0 (2)
ANL COM ANL COM ANL COM (1)
ANL COM (2)
NOT USED NOT USED IN 0+ (2)

OUT 0 OUT 0 OUT 1 (2) IN 01 (2)

ANL COM ANL COM ANL COM (2) ANL COM (2)

NOT USED NOT USED IN 1+ (2)


OUT 1 OUT 1 IN 1- (2)

ANL COM ANL COM ANL COM (2)

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 71


Appendix A Wiring Diagram Comparisons

Figure 34 - Conversion Module - 1492-CM1746-M06

Figure 35 - Conversion Module - 1492-CM1746-M10

Indirect Wiring Migration for 1746-NIO4V to 5069-OF4 and 5069-IY4

The solution allows for indirect wiring migration for up to two SLC 1746-
NIO4V modules to a combination of one CompactLogix 5069-OF4 module and
one CompactLogix 5069-IY4 module. The wiring is a manual transfer process
from the SLC terminal block to the CompactLogix conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

72 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 36 - 1746-NIO4V to 5069-OF4 and 5069-IY4


5069-OF4 5069-IY4
1746-NIO4V Analog Current/Voltage Output Module Analog Current/Voltage Output Module
Analog Current Output Module ANALOG INPUT
i
Differential
+ ANALOG OUTPUT +
Current A
Receiver or
4-wire +
– A 24V DC Differential 5069-IY4
+ Input
Voltage –
Analog –
source 0 IN 0 + Shield Ground 5069-OF4
0
– 1 IN 0 –
Earth 2 ANL COM Shield Ground 1
ground
3 IN 1 + Output 0 + 0 Input 0 + 2
Jumper unused Output 0 –
inputs. 4 IN 1 – 1
Input 0 – 3
5 ANL COM i Output 1 + 2 +
RTD – 4

6 Not used Differential Output 1 – 4-wire +


Load +
3 Input 1 + 5
7 OUT 0 A 24V DC Differential
Current Output 2 + 4 Input 1 – 6
8 ANL COM Voltage –
Earth Receiver or Output 2 – –
ground 9 Not used – A 5
RTD – 7

Do not jumper Input Shield Ground


10 OUT 1 Output 3 + 6 Input 2 + 8
unused outputs.
11 ANL COM Output 3 – 7 Input 2 – 9
+
8
4-wire + RTD – 10
i
9
24V DC Differential 11
Differential Voltage –
+ 10 12
Current A –
11 Input 3 + 13
Receiver or A
Input – 12 Input 3 – 14

13 RTD – 15

14 Shield 16

15 Shield 17
+
Shield 16
4-wire +
Shield 17
Differential
24V DC
Voltage –

Analog input wiring is transferred to the 1746-RT27 terminal block and


installed on the 1492-CN1746-M06 conversion module.

Analog output wiring is transferred to the 1746-RT28 terminal block and


installed on the 1492-CN1746-M10 conversion module.

Figure 37 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 37 - 2 x 1746-NIO4V to 5069-OF4 and 5069-IY4

1746-NIO4V (1) 1746-NIO4V (2) 1746-RT27 1746-RT28


5069-OF4 5069-IY4

IN 0+ IN 0+ OUT 0 (1) IN 0+ (1)

IN 01 IN 01 IN 01 (1)
ANL COM (1)
ANL COM ANL COM ANL COM (1)
OUT 1 (1)
IN 1+ IN 1+ IN 1+ (1)
ANL COM (1)
IN 1- IN 1- IN 1- (1)
OUT 0 (2)
ANL COM ANL COM ANL COM (1)
ANL COM (2) IN 0+ (2)
NOT USED NOT USED

OUT 0 OUT 1 (2) IN 01 (2)


OUT 0

ANL COM ANL COM ANL COM (2) ANL COM (2)

NOT USED NOT USED IN 1+ (2)

OUT 1 OUT 1 IN 1- (2)

ANL COM ANL COM (2)


ANL COM

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 73


Appendix A Wiring Diagram Comparisons

Figure 38 - Conversion Module - 1492-CM1746-M06

Figure 39 - Conversion Module - 1492-CM1746-M10

Indirect Wiring Migration for 1746-NR8 to 5069-IY4

The solution allows for indirect wiring migration for a single SLC 1746-NR8
module to a combination of two CompactLogix 5069-IY4 modules. The wiring
is a manual transfer process from the SLC terminal block to the CompactLogix
conversion terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

Analog input wiring is transferred to the 1746-RT28 terminal block and


installed on the 1492-CN1746-M07 conversion module.

The 5069-IY4 module allows for each channel to be shielded on the module
itself compared to the 1746-NR8.

Figure 40 illustrates the correlating pinouts to use when moving installation


wiring.

74 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 40 - 1746-NR8 to 2 x 5069-IY4

1746-NR8 1746-RT25B 1746-RT25B


5069-IY4 (1) 5069-IY4 (2)
RTD 0
SENSE 0 SHIELD SHIELD
RETURN 0 SHIELD SHIELD
CH0 RTD CH4 RTD
RTD 1 CH1 RTD CH5 RTD
CH0 SENSE CH4 SENSE
SENSE 1
CH1 SENSE CH5 SENSE
RETURN 1 CH0 RTN CH4 RTN
RTD 2 CH1 RTN CH5 RTN
SENSE 2 SHIELD SHIELD
SHIELD SHIELD
RETURN 2 CH2 RTD CH6 RTD
RTD 3 CH3 RTD CH7 RTD
CH2 SENSE CH6 SENSE
SENSE 3
CH3 SENSE CH7 SENSE
RETURN 3 CH2 RTN CH6 RTN
RTD 4 CH3 RTN CH7 RTN
SHIELD SHIELD
SENSE 4 SHIELD SHIELD
RETURN 4
RTD 5
SENSE 5
RETURN 5
RTD 6
SENSE 6
RETURN 6
RTD 7

SENSE 7
RETURN 7

Figure 41 - Conversion Module- 1492-CM1746-M07

Indirect Wiring Migration for 1746-OB8 to 5069-OB16

The solution allows for indirect wiring migration for up to two SLC 1746-OB8
modules to a single CompactLogix 5069-OB16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 75


Appendix A Wiring Diagram Comparisons

• The conversion module is matched correctly to the specific I/O modules.


• There are no uninsulated wires that could cause danger for user or
installer.
Figure 42 - 1746-OB8 to 5069-OB16

1746-OB8 5069-OB16
10...50V DC Transistor Output-sourcing 24V DC Sourcing Output Module

VDC +DC
OUT 0
CR Output Channel 0
OUT 1
Output Channel 1
OUT 2 Output Channel 2
Output Channel 3
OUT 3
10…50V DC LA0 -
OUT 4 CR LA0 -
LA0 -
OUT 5 CR
24V DC – LA0 -
+ LA0 +
OUT 6 CR
Output Channel 4
OUT 7 CR Output Channel 5
DC Output Channel 6
-DC
COM Output Channel 7
LA1 -
LA1 -
LA1 -
LA1 -
LA1 +

Wiring is transferred to the 1746-RT25B terminal block and installed on the


1492-CN1746-M03 conversion module.

Figure 43 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 43 - 2 x 1746-OB8 to 5069-OB16


1746-OB8 (1) 1746-OB8 (2) 1746-RT25B
5069-OB16
V DC V DC
V DC
OUT 0 (1)
OUT 0 OUT 0
OUT 1 (1)
OUT 2 (1)
OUT 1 OUT 1 OUT 3 (1)
OUT 4 (1)
OUT 2 OUT 2 OUT 5 (1)
OUT 6 (1)
OUT 3 OUT 3 OUT 7 (1)
OUT 0 (2)
OUT 4 OUT 4 OUT 1 (2)
OUT 2 (2)
OUT 5 OUT 5 OUT 3 (2)

OUT 6 OUT 6 OUT 4 (2)


OUT 5 (2)
OUT 6 (2)
OUT 7 OUT 7 OUT 7 (2)
DC COM
DC COM DC COM

76 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 44 - Conversion Module - 1492-CM1746-M03

Indirect Wiring Migration for 1746-OBP8 to 5069-OB16

The solution allows for indirect wiring migration for up to two SLC 1746-OBP8
modules to a single CompactLogix 5069-OB16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.
Figure 45 - 1746-OBP8 to 5069-OB16

1746-OBP8 5069-OB16
20.4...26.4V DC Transistor Output-sourcing 24V DC Sourcing Output Module

+DC VDC1
OUT 0
CR OUT 1
OUT 2
CR OUT 3
DC
20.4…26.4V DC
NC
COM1 CR Output Channel 0
NC Output Channel 1
NC Output Channel 2
Output Channel 3
-DC LA0 -
LA0 -
NC
NC
LA0 -
NC 24V DC – LA0 -
+DC VDC2 + LA0 +
CR
OUT 4
Output Channel 4
OUT 5
OUT 6 Output Channel 5
20.4…26.4V DC
CR OUT 7 Output Channel 6
DC
COM2 Output Channel 7
-DC LA1 -
LA1 -
LA1 -
LA1 -
LA1 +

Wiring is transferred to the 1746-RT25B terminal block and installed on the


1492-CN1746-M03 conversion module.

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 77


Appendix A Wiring Diagram Comparisons

Figure 46 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 46 - 2 X 1746-OBP8 to 5069-OB16


1746-OBP8 (1) 1746-OBP8 (2) 1746-RT25B
5069-OB16
V DC1 V DC1
V DC
OUT 0 OUT 0 OUT 0 (1)
OUT 1 OUT 0
OUT 1 (1)
OUT 2 OUT 2
OUT 2 (1)
OUT 3 OUT 3 OUT 3 (1)
DC COM1 DC COM1
OUT 4 (1)
NC NC OUT 5 (1)
NC NC
NC NC OUT 6 (1)
OUT 7 (1)
NC NC
OUT 0 (2)
NC NC OUT 1 (2)
NC NC
OUT 2 (2)
V DC2 V DC2 OUT 3 (2)
OUT 4 OUT 4
OUT 5 OUT 5 OUT 4 (2)
OUT 5 (2)
OUT 6 OUT 6
OUT 6 (2)
OUT 7 OUT 7 OUT 7 (2)
DC COM2 DC
DCCOM
COM2 DC COM

Figure 47 - Conversion Module - 1492-CM1746-M03

Indirect Wiring Migration for 1746-OW4 to 5069-OW16

The solution allows for indirect wiring migration for up to four SLC 1746-OW4
modules to a single CompactLogix 5069-OW16 module. The wiring is a manual
transfer process from the SLC terminal block to the CompactLogix conversion
terminal block.

Before installation make sure that:


• The PLC system is turned off.
• The conversion module is matched correctly to the specific I/O modules.
• There are no uninsulated wires that could cause danger for user or
installer.

78 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


Appendix A Wiring Diagram Comparisons

Figure 48 - 1746-OW4 to 5069-OW16

1746-OW4 5069-OW16
Relay Output AC/DC Relay Output Module RELAY OUTPUT

VAC-VDC L1 or +DC
5069-OW16
OUT 0
V AC/DC
OUT 1 CR Output Channel 0
CR Output Channel 1
OUT 2
CR Output Channel 2
OUT 3 CR L2 or -DC Output Channel 3
NOT Output Channel 4
USED Output Channel 5
L2
NOT
USED Output Channel 6
NOT Output Channel 7
AC-type L1
USED Common 0
Power Supply
NOT CR Output Channel 8
USED
OUT Output Channel 9
NOT7
USED CR Output Channel 10
Output Channel 11
Output Channel 12
-24V DC Output Channel 13
Output Channel 14
Output Channel 15
DC-type
Power Supply Common 1

Wiring is transferred to the 1746-RT25C terminal block and installed on the


1492-CN1746-M04 conversion module.

IMPORTANT If you are using AC power as output, you must connect to SA+ and SA- on
the 5069-FPD module.

Figure 49 illustrates the correlating pinouts to use when moving installation


wiring.

Figure 49 - 4 x 1746-OW4 to 5069-OW16


1746-OW4 (1) 1746-OW4 (2) 1746-OW4 (3) 1746-OW4 (4) 1746-RT25C
5069-OW16
V AC-DC V AC-DC V AC-DC V AC-DC
V AC-DC1
OUT 0 (1)
OUT 0 OUT 0 OUT 0 OUT 0
OUT 1 (1)
OUT 1 OUT 2 (1)
OUT 1 OUT 1 OUT 1
OUT 3 (1)
OUT 2 OUT 2 OUT 0 (2)
OUT 2 OUT 2 OUT 1 (2)

OUT 3 OUT 3 OUT 3 OUT 3 OUT 6 (2)


OUT 3 (2)
V AC-DC2
NOT USED NOT USED NOT USED NOT USED OUT 1 (3)

NOT USED NOT USED NOT USED NOT USED OUT 0 (3)
OUT 3 (3)

NOT USED NOT USED NOT USED NOT USED OUT 2 (3)
OUT 1 (4)
OUT 0 (4)
NOT USED NOT USED NOT USED NOT USED OUT 3 (4)
OUT 2 (4)
NOT USED NOT USED NOT USED NOT USED

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 79


Appendix A Wiring Diagram Comparisons

Figure 50 - Conversion Module - 1492-CM1746-M04

80 Rockwell Automation Publication 1746-RM003F-EN-E - January 2022


SLC 500 Hardware Migration Reference Manual

Rockwell Automation Publication 1746-RM003F-EN-E - January 2022 81


Rockwell Automation Support
Use these resources to access support information.

Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product release rok.auto/pcdc
(PCDC) notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental information on its website at rok.auto/pec.

Allen-Bradley, Compact 5000 I/O, Compact I/O, CompactLogix, ControlLogix, expanding human possibility, FactoryTalk, GuardLogix, Logix 5000, PanelView, Rockwell Automation, RSLogix, RSLogix 500,
RSLogix Micro, SLC, SLC 5/03, SLC 500, Studio 5000, Studio 5000 Architect, Studio 5000 Logix Designer, Studio 5000 View Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur

Connect with us.

Publication 1746-RM003F-EN-E - January 2022


Supersedes Publication 1746-RM003E-EN-E - August 2020 Copyright © 2022 Rockwell Automation, Inc. All rights reserved.