A50 Hz overhead line has line to earth capacitance of 1 pF. It is decided to use an
earth fault neutralizer. Determine the reactance to neutralize the capacitance of entire
length of the line.
This question was previously asked in
Paper (Held on 17 Dec 2020)
View all PGCIL Diploma Trainee Papers >
1, 106192
2. 20009
3. 12619
4. 1000 Q
‘Answer (Detailed Solution Below)
Option 1: 1061Crack AE & JE -
Gates
eet ganas
Detailed Solution
Peterson coi
+ Peterson coil is an iron cored inductor used to connect the neutral of the three-phase system
to the earth. In other words, the neutral of the three-phase system is grounded through the
Peterson coil.
+ Generally, this grounding is used to minimize the capacitive charging current or earth fault
neutralizer during the fault in the lines.
+ This also eliminates the arcing ground, so it is also called an Are suppression coil.
Connection diagram of Peterson coil for LG fault:
000. A
(Peterson coi
Let's consider that LG fault has happened at phase C. Then the current flowing through the phase
Cle= la + Ie
The current through the Peterson coil |, = Vph/ w L
Where
Vpy = phase voltage of a 3 - phase system, w is the angular frequency, Lis the inductance of Peterson
coil
But the fault current lc = 3 Vph / Xc
Here, Xc is the capacitive reactance and Xe = 1/ wC
Therefore to neutralize the fault current,
Von/ w L = 3 Vph / Xe
=> Ww b= 3 wo
=> L=1/3weC
WhereC = capacitance of charging capacitor
Thus to neutralize the capacitive charging current or earth fault, the value of the inductive reactance of
the Peterson coil is equal to 1/ 36.
Calculation:
Given,
f=50Hz—= w = 2nf= 100n
C= 1pF
From the above concept, if decided to use an earth fault neutralizer then the reactance to neutralize (X,)
will be,
Tp=24= 1
X_ = 10610