DC TO AC INVERTER Ower’s Manual

Inverter with ups function

Special Feature:

Fuse: Built-out
1.5 times rated power for 10s,2times for 2s(inverter)
Remote Control(Optional)
USB:5V,2.1A(Optional)
Protection: LED Indicator& Audible Alarm.
12V or 24V or 48VDC input
Input voltage range: -15% ~ +25%
Output voltage regulation: ±10%
3-Step Charger build in (Optional)
AC Auto-Transfer switch
Switchable UPS and ECO model
CE and RoHS Approved

Congratulations and thank you for purchasing ours inverter ,Carefully read,
understand and comply with all instructions before use.
Appendix III:Battery Connect
In renewable energy systems, batteries are connected to each other in one of
1. Important Safety Information............................................................ 1 three ways:
1.1 General Safety Precautions.............................................................. 1 Series (voltage increases, amperage stays the same as a single battery)
1.2 Precautions When Working With Batteries.........................................1 Parallel (voltage stays the same as a single battery, amperage increases)
2. General Information ...........................................................................2 Series/Parallel (both voltage and amperage increase)
3. Application......................................................................................... 2
4.Electrial Performance......................................................................... 3
4.1 Inverter.......................................................................................... 3
4.1.1 What is an Inverter?............................................................... 3
4.1.2 Pure Sine Wave Inverter.......................................................... 3
4.1.3 Modified Sine Wave Inverter................................................... 3
4.1.4 Soft Start function................................................................. 3
4.2 AC Charger(Option)........................................................................ 3
4.2.1 3-Step Charging.................................................................... 3
4.3 UPS Mode and ECO mode............................................................... 4
5. Mechanical Drawing.......................................................................... 4
5.1 Front Panel................................................................................... 4
5.2 Rear Panel.................................................................................... 6
6. Protection Features:.......................................................................... 6
6.1 Inverter Protection........................................................................ 6
6.1.1 Modified sine wave inverter................................................... 6
6.1.2 Pure sine wave inverter.......................................................... 7
6.2 AC charger protection(option)........................................................ 8
7. Installation........................................................................................ 8
7.1 Location....................................................................................... 8
7.2 DC Wire....................................................................................... 8
7.3 AC Wire....................................................................................... 8
7.4 Connections & Operations............................................................ 9
8.Trouble Shooting Guide...................................................................... 9
9. Specification..................................................................................... 11
9.1 Inverter with AC Auto Switch........................................................ 11
9.2 Inverter with AC Auto Switch and Charger Function....................... 13
10.Warranty ........................................................................................ 15

- 17-
Appendix II: DC Wire 1. Important Safety Information
For correct operation, the battery voltage should be between 0.9xVnom and 1.29x 1.1 General Safety Precautions
Vnom where Vnom is 12V, 24V or 48V depending on model, and must be able to 1.1.1 Do not expose the Inverter to rain, snow, spray, bilge or dust. To reduce
supply sufficient current to your inverter. The following table displays the risk of hazard, do not cover or obstruct the ventilation openings. Do not
recommended things(battery cable, Fuse, Battery Capacity) per inverter type : install the Inverter in a zero-clearance compartment,Overheating may
result. Allow at least 30CM of clearance around the inverter for air flow.
Make sure that the air can circulate freely around the unit. A minimum air
flow of 145CFM is required.
1.1.2 To avoid risk of fire and electronic shock, make sure that existing wiring
is in good electrical condition and that the wire is not undersized. Do not
operate the Inverter with damaged or substandard wiring.
1.1.3 This equipment contains components which may produce arcs or
sparks. To prevent fire or explosion do not install in compartments
containing batteries or flammable materials or in a location which require
ignition protected equipment. This includes any space containing
gasoline-powered machinery, fuel tanks, or joints, fittings, or other
connection between components of the fuel system.
1.1.4 Do not disassemble the Inverter. It contains no user-serviceable
20A 3 parts. Attempting to service the Inverter yourself may result in
electrical shock or fire. Internal capacitors remain charged after all power
35A 4 is disconnected.
20A 4 1.1.5 To reduce the risk of electrical shock, disconnect both AC and DC power
from the Inverter,before attempting any maintenance or cleaning.
35A 5
Turning off controls will not reduce this risk
20A 5
CAUTION: Equipment Damage
The output side of the inverter's AC wiring should at no time be connected
25A 6 to public power or a generator. This condition is far worse than a short circuit.
20A 6 If the unit survives this condition, it will shut down until corrections are made.
Installation should ensure that the inverter's AC output is at no time be connected
35A 8 to its AC input.
20A 8
1.2 Precautions When Working With Batteries
1.2.1 If battery acid contacts skin or clothing, wash immediately with soap and
35A 10
water. If acid enters eyes, immediately flood eye with running cold water
20A 10
and get medical attention immediately.
20A 10
1.2.2 Never smoke or allow a spark or flame in the vicinity of a battery or engine.
20A 10 1.2.3 Do not drop a metal tool on the battery. The resulting spark or short-circuit
on the battery may cause an explosion.
1.2.4 Remove personal metal items such as rings, bracelets, necklaces, and
-16- -1-
watches when working with a lead-acid battery. A lead-acid battery 10. Warranty
produces a short-circuit current high enough to weld a ring or the like to
metal, causing a severe burn. We warrant this product against defects in initial PCB, components and any
1.2.5 To reduce the risk of injury, charge only deep-cycle lead acid, lead manufacturing defects for one full year from date of purchase and will repair
antimony, lead calcium gel cell, absorbed mat, or NiCad/NiFe type or replace any defective inverter. This warranty is issued only at the time of
r e c h a rg e a b l e b a t t e r i e s . Other types of batteries may burst, causing original purchase; it is non-transferable. Damage caused by accident, misuse,
personal injury and damage. do-it-yourself repairs, sand, oil or water is not covered by this warranty. This
1.2.6 Sparks may result during final battery connection.Always observe proper is only warranty and the company makes no other warranties, express or
polarity as batteries are connected implied, including warranties of merchant ability and fitness for a particular
2 General Information . purpose.
Appendix I
I nverter with UPS function is a combination of an inverter,AC Auto-
Remote Control Switch
transfer switch and battery charger (Option) into one complete system with a
peak dc to ac conversion efficiency of 90%. It is packed with unique features Inverter Remote Controller Inverter Remote Controller
AC

and it is one of the most advanced system in the market today. There are two CHARGE
BATTERY LOAD
Green : Power On
Flash : Fault BATTERY
Green : Power On
LOAD Flash : Fault

model to your choose. 100%

75%
INVERTER
100%

75%
100%
INVERTER
100%

75% 75%
50% 50%
UPS model:it also called the AC priority .the AC power will be direct to 25%
BYPASS

25%
AC IN
50%
BYPASS
50%

25% 25%
AC IN
the loads through bypass ways. if have charger build in, AC power also will be
OFF ON OFF ON
used to charge the battery ; Model No KS-03 Model No KS-02

ECO model : it also called the Battery Priority . the inverter will always
prefer to inverter electricity from battery first even there is a qualified AC Power ON/OFF Switch
input present .only when the battery voltage reaches the low voltage point. Power ON/OFF switch is to turn the inverter on or off.
(11Vdc for 12V battery ,22V dc for 24V battery ,44V dc for 48V battery ), the Battery Capacity/Load Voltage indicator
inverter transfer to AC input to charge the battery, and switch back to battery Load: Show the approximate connected equipment load level.
when the battery voltage from (13Vdc for 12V battery,26V dc for 24V battery, Four Levels---25%,50%,75%,100%.
52V dc for 48V battery ), Battery: Show the battery residual capacity.
Four Levels---25%,50%,75%,100%.
Note: When under the AC bypass function , if have charger build in , the AC In Indicator
charger will charge the battery. AC In: after correct connect the AC mains , the light will turn on.
Bypass: under Bypass function,the light will on .
3. Application
Charge In:Under charge function ,the light will on
Power tools–circular saws, drills, grinders, sanders, buffers, weed and
hedge trimmers, air compressors. Fault: Turns red show fault, refer to Troubleshooting of Inverter Manual.
Office equipment – computers, printers, monitors, facsimile machines, Connecting the Communications Cable
Household items – vacuum cleaners, fans, fluorescent and incandescent The communications cable is 3meters, 6-conductor cable (wired like a normal
lights, shavers, sewing machines. telephone-type cable). This cable is connected to the RJ11 jack on the rear of
Kitchen appliances – coffee makers, blenders, ice markers, toasters. the remote control and to the REMOTE port located on the rear of the inverter.
Industrial equipment – metal halide lamp, high – pressure sodium lamp. Notice:
Home entertainment electronics – television, VCRs, video games, stereos, Inverter's ON/OFF Switch and Remote control's ON/OFF Switch is in parallel.
musical instruments, satellite equipment. To use this remote control, must turn the inverter's ON/OFF Switch to OFF,and
vice versa.
-2- -15-
4. Electrical Performance
Model 4.1. Inverter
Item
KSC300M KSC500M KSC1000M KSC1500M KSC2000M 4.1.1 What is an Inverter?
Rated Power 300W 500W 1000W 1500W 2000W
Power inverter is an electronic device that convert DC(Direct Current)
O Surge Power 120%<Load<150% Rated power for 10s,150%<Load<200% Rated power for 2s
battery power to standard AC(Alternating Current) power. DC is the power
U 100V/110V/115V/120Vac or 220V/230V/240Vac
that is produced by battery while AC is the standard power needed to run
T Inverter AC Voltage AC output regulation: 10%
electrical equipment. A power inverter does the opposite of a rectifier and is
P Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
used in places and situations where AC power is not available.
U Charger DC Voltage 12V/24V/48V
T Waveform Modified Sine Wave at rated input voltage 4.1.2 Pure Sine Wave Inverter
Protection AC short circuit, Overload, Over temperature
I Bat. DC Voltage 12V/24V/48V
N Charger AC Voltage 90-120V/180-240V
P Efficiency More than 85%
U Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
T Battery Types Open & sealed lead acid battery PURE SINE WAVE(PSW) MODIFIED SINE WAVE (MSW)

Model If you want to run your equipment exactly to the manufacturer's specifications,
Item
KSC2500M KSC3000M KSC4000M KSC5000M KSC6000M choose a pure sine wave inverter. With pure sine wave, motor loads start easier
O Rated Power 2500W 3000W 4000W 5000W 6000W and run cooler. Some equipment only operate properly with pure sine wave
U 120%<Load<150% Rated power for 10s inverter, such as laser printers, variable speed motors and digital clocks.
Surge Power
T 150%<Load<200% Rated power for 2s 4.1.3 Modified Sine Wave Inverter
P 100V/110V/115V/120Vac or 220V/230V/240Vac
If your equipment can accept some voltage fluctuation , consider a modified
U AC Voltage AC output regulation: 10% sine wave inverter . These inverters provide mobile power at a more affordable
T Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
price and come in a full range of size from handheld to high performance . Do
Charger DC Voltage 12V/24V/48V
not use to power sensitive devices such as medical equipment or computers .
Waveform Modified Sine Wave at rated input voltage
Some audio equipment may perform poorly if run on Modified Sine Wave power Inverter
Protection AC short circuit, Overload, Over temperature
4.1.4 Soft Start function
I Bat. Voltage 12V/24V/48V
our inverter is engineer with Soft Start features , when the inverter is turning
N Charger AC Voltage 90-120V/180-240V on , the output voltage gradually ramp up from 0VAC to Rated Voltage in about
P Efficiency More than 85%
1 Sec, this effectively reduce high starting inrush current drawn by AC loads
U Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
such as switched mode power supplies and inductive loads .
T Battery Types Open & sealed lead acid battery
AC Out Receptacle USA, UK, Germany, France, Australia, Brazil, Italy, South Africa, etc. CAUTION: Do not parallel the AC output of the inverters to increase
Cooling Temperature and Load Controlled power capacity as they have no stacking functionality.
Operating -5°C to 40°C 4.2 AC Charger(Option)
Temperature
Environment This AC battery charger is high efficiency charger that will fully charge and
Storage Temperature -5°C to 85°C
maintain a battery at it’s proper storage voltage without the damaging effects
Relative Humidity 20% ~ 90% RH non-condensing
cased by trickle chargers .it is and ideal charger for everyday charging use or
long term storage and maintenance .
Modified Sine Wave Inverter with AC Auto Switch and Charger 4.2.1 3-Step Charging
A) Bulk Charge Stage: Current is supplied to the battery at a constant rate while

- 14- -3-
voltage gradually rises.
B) Absorption Charge: Voltage remains constant and current reduces as the 9.2 Inverter with AC Auto Switch and Charger Function
battery becomes charged. This ensures complete charging.
Model
C) Floating Stage: After the battery reach full charge, charging voltage is Item
KSC300P KSC500P KSC1000P KSC1500P KSC2000P
reduced to a lower level to prevent gassing and to prolong life. This stage is
Rated Power 300W 500W 1000W 1500W 2000W
often referred to as a maintenance charge. Rather than charging a battery, it Surge Power 120%<Load<150% Rated power for 10s,150%<Load<200% Rated power for 2s
O
keeps an already-charged battery from discharging while providing load U 100V/110V/115V/120Vac or 220V/230V/240Vac
current. T Inverter AC Voltage AC output regulation: 10%
Bulk Absorption Float
P Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
Vcharge

Absorb Charging: 14.6 Vdc(12V version)/ U Charger DC Voltage 12V/24V/48V


29.2Vdc(24V version) T Waveform Pure Sine Wave(THD<4%) at rated input voltage
Float Charging: 13.8Vdc(12V version)/ Protection AC short circuit, Overload, Over temperature
27.6Vdc(24V version) I Bat. DC Voltage 12V/24V/48V
Icharge

*Charging voltages can be customized N Charger AC Voltage 90-120V/180-240V


in factory. P Efficiency More than 85%

Time
U Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
T Battery Types Open & sealed lead acid battery
4.3 UPS Mode and ECO mode
Model
4 . 3 . 1 U P S M o d e : t h e AC i n p u t o f t h e i n v e r t e r i s c o n t i n u a l l y m o n i t o r e d . Item
KSC2500P KSC3000P KSC4000P KSC5000P KSC6000P
Whenever AC power falls ,the inverter automatically transfers back to
O Rated Power 2500W 3000W 4000W 5000W 6000W
the inverter mode with minimum power interruption to your appliances-
U 120%<Load<150% Rated power for 10s
as long as the inverter is turned on. The transfer time is usually fast enough Surge Power
T 150%<Load<200% Rated power for 2s
to keep your equipment (including computers) powered up. The time will P 100V/110V/115V/120Vac or 220V/230V/240Vac
be less than 16 milliseconds . U AC Voltage AC output regulation: 10%
4.3.2 ECO Mode: Battery voltage is lower than alarm point , the inverter T Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
automatically transfers back to the AC utility to the loads, the transfer 12V/24V/48V
Charger DC Voltage
time also very fast enough to keep your equipment(including computers) Waveform Pure Sine Wave(THD<4%) at rated input voltage
powered up . The time will be less than 16 milliseconds. After low battery Protection AC short circuit, Overload, Over temperature
voltage shut off, the inverter is able to restore to work after the battery I Bat. Voltage 12V/24V/48V
voltage recovers to 13V/26V/52V(With power switch still in “ON” Position). N Charger AC Voltage 90-120V/180-240V

5. Mechanical Drawing P Efficiency More than 85%


U Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
5.1 Front Panel T Battery Types Open & sealed lead acid battery
UPS Mode

ON AC Output AC Out Receptacle USA, UK, Germany, France, Australia, Brazil, Italy, South Africa, etc.
2.1A/5V

OFF ECO Mode


Cooling Temperature and Load Controlled
AC Input

Inverter Fault

AC-IN By- Pass


Operating -5°C to 40°C
FUSE

AC Charger
Temperature
GND
Environment
Storage Temperature -5°C to 85°C
Remote
Relative Humidity 20% ~ 90% RH non-condensing

Pure Sine Wave Inverter with AC Auto Switch and Charger

With charger type


-4- -13-
Model
Item UPS Mode

KS300MT KS500MT KS1000MT KS1500MT KS2000MT ON AC Output

2.1A/5V
Rated Power 300W 500W 1000W 1500W 2000W OFF ECO Mode

O AC Input

Surge Power 120%<Load<150% Rated power for 10s,150%<Load<200% Rated power for 2s Inverter Fault

U AC-IN By- Pass


FUSE

100V/110V/115V/120Vac or 220V/230V/240Vac
T
Inverter AC Voltage AC output regulation: 10% GND

P Remote
Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
U
Waveform Modified Sine Wave at rated input voltage
T
Protection AC short circuit, Overload, Over temperature
I Bat. DC Voltage 12V/24V/48V Without charger type
N AC Voltage 90-120V/180-240V
A) ON/OFF Switch: this switch controls ON/OFF operation of the unit
P Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
B) AC Input: plug AC input cable into it and AC source
U Battery Types Open & sealed lead acid battery
T C) AC Outlet: For application demands of different geographic areas all over
Model the world, there are many different kinds of optional AC receptacle to choose
Item from.
KS2500MT KS3000MT KS4000MT KS5000MT KS6000MT
O Rated Power 2500W 3000W 4000W 5000W 6000W
U Surge Power 120%<Load<150% Rated power for 10s 150%<Load<200% Rated power for 2s
T 100V/110V/115V/120Vac or 220V/230V/240Vac
P AC Voltage AC output regulation: 10%
U Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual D) Hardwire Terminal Block: when the load current is >15A, must use Hardwire
T Charger DC Voltage 12V/24V/48V terminal connection.
Waveform Modified Sine Wave at rated input voltage
Protection AC short circuit, Overload, Over temperature
I Bat. Voltage 12V/24V/48V
N Charger AC Voltage 90-120V/180-240V
Open this cover before connecting
P Efficiency More than 85% AC OUTPUT AC INPUT

U Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
AC Input Terminal Block: a screw type terminal block for attaching AC output
T Battery Types Open & sealed lead acid battery wires. Each slot is labeled L for Lines and N for Neutral. Connect the incoming
AC Out Receptacle USA, UK, Germany, France, Australia, Brazil, Italy, South Africa, etc. Line wire to the input L slot, Connect the incoming Neutral wire to the input N
Cooling Temperature and Load Controlled slot.
Operating -5°C to 40°C
AC Output Terminal Block: a screw type terminal block for attaching AC
Temperature
Environment output wires. Each slot is labeled L for Lines and N for Neutral. Connect the
Storage Temperature -5°C to 85°C
outgoing Line wire to the output L slot, Connect the outgoing Neutral wire to
Relative Humidity 20% ~ 90% RH non-condensing
the output N slot.
Modified Sine Wave Inverter with AC Auto Switch E) Fuse breaker: under “bypass mode”, when the AC output is shorted or the
load current exceeds the rated current of the fuse breaker, the fuse breaker
will be burned to stop bypassing energy from the utility getting to present
possible danger.
F) Ventilation holes: the inverter requires suitable ventilation to work properly.
Please make sure there is good ventilation and the lifespan of the inverter
can be preserved.
-12- - 5-
G) Frame ground(FG):connect a copper wire between the grounding terminal 9. Specification
on the inverter and earth grounding system or vehicle chassis.
9.1 Inverter with AC Auto Switch
H) Communication port: for remote control purpose,the unit can be connected
a remote control panel by using the optional cable Item
Model
KS300PT KS500PT KS1000PT KS1500PT KS2000PT
I) UPS and ECO mode switch: Automatic mains priority circuit
Rated Power 300W 500W 1000W 1500W 2000W
J) Led indication: Operating status, warning O
Surge Power 120%<Load<150% Rated power for 10s,150%<Load<200% Rated power for 2s
U
Inverter: The inverter started up and output is normal. T
100V/110V/115V/120Vac or 220V/230V/240Vac

Fault: Warning user there is some problem,need to check the system now. Inverter AC Voltage AC output regulation: 10%
P
Such as low voltage,over voltage,over load,short circuit and so on. U
Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
AC in: The status of utility is normal. T
Waveform Pure Sine Wave(THD<4%) at rated input voltage

Bypass: The unit is working under “bypass mode”, the AC electricity Protection AC short circuit, Overload, Over temperature

consumed by the loads is provided by the utility instead of the inverter. I Bat. DC Voltage 12V/24V/48V

AC charger: The built-in AC charger is charging external batteries. N AC Voltage 90-120V/180-240V


P Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
5.2.Rear Panel U Battery Types Open & sealed lead acid battery
T
Model
Item
F U S

F U S
KS2500PT KS3000PT KS4000PT KS5000PT KS6000PT
F U S

F U S O Rated Power 2500W 3000W 4000W 5000W 6000W


F U S

F U S U Surge Power 120%<Load<150% Rated power for 10s 150%<Load<200% Rated power for 2s
F U S

F U S T 100V/110V/115V/120Vac or 220V/230V/240Vac
F U S

P AC Voltage AC output regulation: 10%


U Frequency:50Hz±1%,60Hz±1%,50/60Hz(Optional),switch by manual
T Charger DC Voltage 12V/24V/48V
Waveform Pure Sine Wave(THD<4%) at rated input voltage
Protection AC short circuit, Overload, Over temperature
A) DC Battery Terminals: Connect the inverter to battery or other power sources.
I Bat. Voltage 12V/24V/48V
Negative (-) and Positive (+) DC terminals should be kept insulated to protect
N Charger AC Voltage 90-120V/180-240V
from accidental short circuits.
P Efficiency More than 85%
B) Fuse: Fuse was built-out is a very good design as you can very easy to change U Protection Battery Low Alarm, Battery Low Shutdown, Battery Polarity Reverse by Fuse
the fuse outside the inverter if your inverter fuse was blown. T Battery Types Open & sealed lead acid battery

C) Fan Operation: AC Out Receptacle USA, UK, Germany, France, Australia, Brazil, Italy, South Africa, etc.
Cooling Temperature and Load Controlled
Load and temperature multiple control the cooling fan .when loads over 20% rate
Operating -5°C to 40°C
power or inner temperature is over 45 ºC
Temperature
6. Protection Features: Environment
Storage Temperature -5°C to 85°C
6.1 INVERTER PROTECTION Relative Humidity 20% ~ 90% RH non-condensing
6.1.1 Modified sine wave inverter
A)Input Low Voltage Protection Pure Sine Wave Inverter with AC Auto Switch
When battery voltage is below 10.5V±0.5V(12V version)/21V±1.0V(24V
version)/ 42V±2.0V(48V version), a buzzer will alarm and fault light turn on

-6- - 11-
red which indicates DC power supply voltage is descending and batteries
need to recharge.

red light turn on --P


When input voltage is below 10V±0.5V(12V version)/20V±1.0V(24V
version)/ 40V±2.0V(48V 12V version), AC output will be automatically
shut off, a buzzer alarm and fault light turn red.
B) Input Over Voltage Protection
When input voltage reach 16V±0.5V (12V version)/32V±1.0V (12V version)/
64V±2.0V (48V version), the fault light turn red and the AC output will be shut
6 2 4
6
off automatically.
2 C) Short Circuit Protection
4 When short circuits occur, fault light turn red, output will be shut off.
6
D) Overload Protection
2 4
When overloads occur, fault light turn red, output will be shut off.
E) Reverse polarity protection
When battery terminals are reverse connected, fuse will be burned to protect
appliances.
F) Over Temperature Protection
When heat sink temperature exceeds 45ºC, the inner cooling fan will automatically
turn on to cool the inverter,When inner temperature exceeds 75ºC, AC output will
automatically shut off.
6.1.2 Pure sine wave inverter
A) Input Low Voltage Protection:
When battery voltage is below 10.5V±0.5V(12V version)/21V±1V(24V
version)/ 42V±2V(48V version), Buzzer sound 2times, which indicates
DC power supply voltage is descending and batteries need to recharge.
When input voltage is below 10V±0.5V(12V version)/20V±14V(24V
version)/ 40V±2V(48V version), Buzzer sound 3 times and red light turn
on , AC output will be automatically shut off.
B) Input Over Voltage Protection
When input voltage reach 16V±0.5V (12V version)/32V±1V (24V version)/
Red light turn on--M 64V±2V (48V version), Buzzer sound 4times and red light turn on, the AC
Buzzer sound many times and
red light turn on --P output will be shut off automatically.
C) Short Circuit Protection
When short circuits occur, buzzer sounds 11 times and red light turn on, output
will be shut off.

Notice: M—Modified sine wave inverter P---Pure sine wave inverter


- 10- - 7-
D) Overload Protection qualified electrician about the specific wire gauge required in term of wire
When overloads occur, buzzer sounds many times and red light turn on, output material and inverter power .
will be shut off. 7.4 Connections & Operations
E) Reverse polarity protection: Fuse or MOSfet Step 1 Connect the (+) and (-) cables from the battery to the respective terminals
Via Fuse: When battery terminals are reverse connected, fuse will be burned of the unit.
to protect appliances. Step 2 Plus in the AC source to real panel AC Input Socket(Hard Block Terminal)
Via MOSfet(Optional): When battery terminals are reverse connected, the Step 3 Connect the earth cable from the AC ground system to that of the unit
inverter won't work unit correct connect. Step4 To start the unit, turn on the ON/OFF switch. LED green lights on,
F) Over Temperature Protection Charger and AC power on.
Step5 Connect consumer unit to the socket in the front of the unit
When heat sink temperature exceeds 45ºC, the inner cooling fan will
automatically turn on to cool the inverter; When inner temperature exceeds Step 6 Make sure the cable is firmly connected in the socket. If the connection
is not firm enough, the plug will heat up and cause unit damage
75ºC, AC output will automatically shut off, Buzzer sound 5 times and red
Step 7 USB only supply output power source
light turn on.
6.2 AC charger protection(option) Warning: The output voltage of this unit must never be connected in it's input
A) Over charging protection AC terminal, overload or damage may result.Always switch on the inverter
B) Short circuit protection before plugging in any appliance. Damage caused by AC wiring mistakes are
C) Over Temperature protection not covered under warranty .
D) Reverse Polarity Portection .
7 INSTALLATION 8. Trouble shooting Guide
Trouble shooting contains information about how to trouble shoot possible
7.1 Location.
Please install the equipment in a location of Dry, Clean, Cool with good error conditions while using the Inverters
ventilation. The following chart is designed to help you quickly pinpoint the most common
Working temperature: -5℃ to 40℃ inverter failures.
Storage temperature: -5℃ to 70℃
Relative Humidity: 0% to 95%_non-condensing
Cooling: Forced air
7.2 DC Wire
Though your Inverter is a high-efficiency converter of electricity, its rated
output capacity is limited by the length and gauge of the cabling running from
the battery to the unit. Use the shortest length and largest diameter cabling to Low battery
fit your Inverter's DC Input terminals. Shorter and heavier gauge cabling
reduces DC voltage drop and allows for maximum transfer of current. Your
Inverters is capable of delivering peak wattage at up to 200% of its rated
continuous wattage output for brief periods of time. Heavier gauge cabling
should be used when continuously operating heavy draw equipment under
these conditions. Tighten your Inverters and battery terminals to approximately
0.8 Meter to create an efficient connection and to prevent excessive heating at
this connection. Insufficient tightening of the terminals could void your
warranty.
7.3 AC Wire
when in bypass mode the AC input power will supply both the loads and
AC charger, a thicker wire gauge for AC input is required,please consult a
- 8- -9-