You are on page 1of 124

Ravensthorpe Joint Venture

INSTALLATION, OPERATING & MAINTENANCE


MANUAL (IOM)

FOR

Titanium & SAF Rod Valves


Tags: 25120-HV-1253, 25120-HV-1254, 25120-HV-1255, 25120-HV-1256, 25220-HV-2253, 25220-HV-
2254, 25220-HV-2255, 25220-HV-2256, 25130-HV-1339, 25230-HV-2339, 20130-HV-1365, 20130-HV-
1366, 20230-HV-2336

Purchaser: Ravensthorpe Joint Venture


Purchase Order: 314978-6J-P427

flo solutions pty ltd


Suite 4, 152 High Street
Fremantle Perth
Western Australia 61
Tel: +61 8 9430 6880 Fax: +61 8 9430 6908

IOM Volume 1 of 1
KPC CORPORATION _____________________ Ravensthorpe Nickel Project

PO 314978-6J-P427
Items:Rod Valves

25120-HV-1253 25120-HV-1254 25120-HV-1255 25120-HV-1256 25220-HV-2253


25220-HV-2254 25220-HV-2255 25220-HV-2256 25130-HV-1339 25230-HV-2339
20130-HV-1365 20130-HV-1366 20230-HV-2336

IOM INDEX
TABLE OF CONTENTS

Section C: General Description

Section D: Data Summary

Section E: Lifting & Handling

Section F: Corrosion Protection

Section G: Storage of Equipment

Section H: Drawings and Data Sheets

Section I: Spare Parts List

Section K: Lubrication

Section L: Installation

Section M: Operation Instruction

Section N: Maintenance

Section O: Sub-Supplier Manuals (Positioner & Actuator)

Purchase Order 314978-6J-P427 Client Ravensthorpe Joint Venture


Document No. 314978-00000-QP-74-004 Supplier Flo Solutions/KPC
Errata Sheet
June 2005 DVC6000 and DVC6000f Series

Errata Sheet
for
The following Instruction Manuals and Quick Start Guides

Title Form Number Date Page Number


FIELDVUER DVC6000 Series Digital Valve Controller Instruction Manual 5647 May 2005 1−5
FIELDVUER DVC6000 Series Digital Valve Controllers Quick Start Guide 5654 May 2005 4−1
FIELDVUER DVC6000f Series Digital Valve Controller Instruction Manual 5774 March 01, 2005 1−5 and 1−6
FIELDVUER DVC6000f Series Digital Valve Controllers Quick Start Guide 5778 April 2005 4−1 and 4−2

Please replace the Steady-State Air Consumption and the Maximum Ouput Capacity data found in the
Specification table of each of the documents listed above with the following, updated data. Note that the footnotes
currently associated with this data remain the same.

Steady-State Air Consumption


Standard Relay: At 1.4 bar (20 psig) supply
pressure: Less than 0.38 normal m3/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than
1.3 normal m3/hr (49 scfh)
Note
Low Bleed Relay: At 1.4 bar (20 psig) supply
pressure: Average value 0.056 normal m3/hr
(2.1 scfh) Neither EmersonR, Emerson Process
At 5.5 bar (80 psig) supply pressure: Average Management, FisherR, nor any of their
value 0.184 normal m3/hr (6.9 scfh) affiliated entities assumes
responsibility for the selection, use,
Maximum Output Capacity and maintenance of any product.
At 1.4 bar (20 psig) supply pressure: Responsibility for the selection, use,
10.0 normal m3/hr (375 scfh) and maintenance of any product
At 5.5 bar (80 psig) supply pressure: remains with the purchaser and
29.5 normal m3/hr (1100 scfh) end-user.
Note: Normal m3/hour − Normal cubic meters per hour at 0_C and 1.01325 bar,
absolute. Scfh − Standard cubic feet per hour at 60_F and 14.7 psia

www.Fisher.com
Errata Sheet
DVC6000 and DVC6000f Series June 2005

FIELDVUE and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of
Emerson Electric Co. Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property
of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.
We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and
maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.

Emerson Process Management


Fisher
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com

2
EFisher Controls International LLC 2005; All Rights Reserved Printed in USA
Quick-Start Guide
Form 5654
May 2005 DVC6000 Series
FIELDVUE DVC6000 Series
Digital Valve Controllers
Using This Guide 1
Installation 2
Basic Setup and Calibration 3
Specifications and Related Documents 4
Loop Schematics and Nameplates 5
Note
This guide provides installation, and initial
setup and calibration information for
DVC6000 Series digital valve controllers.
See the FIELDVUER DVC6000 Series Digital
Valve Controller Instruction Manual - Form
5647, available from your FisherR sales
office, for additional information, or visit
our website at www.FIELDVUE.com.
This Quick-Start Guide covers instrument
levels AC, HC, AD and PD.
When installing and setting up a DVC6000
in an SIS application it is required that you
use the FIELDVUER DVC6000 Series Digital
Valve Controller Instruction Manual - Form
5647 and the Safety Manual for DVC6000
SIS Solutions - Form 5743.

Note:  This guide applies to:


Model 375 Field
DVC6000 Series Communicator
Device Firmware Hardware Device Description
Revision Revision Revision Revision
1 2, 3, 4, 5 & 6 1 4

For details see page 1-1


D102762X012

www.Fisher.com
DVC6000 Series

THE FIELDVUER DVC6000 SERIES DIGITAL VALVE CONTROLLER IS A CORE COMPONENT OF THE
PLANTWEBR DIGITAL PLANT ARCHITECTURE. THE DIGITAL VALVE CONTROLLER POWERS PLANTWEB
BY CAPTURING AND DELIVERING VALVE DIAGNOSTIC DATA. COUPLED WITH AMS VALVELINKR
SOFTWARE, THE DVC6000 PROVIDES USERS WITH AN ACCURATE PICTURE OF VALVE PERFORMANCE,
INCLUDING ACTUAL STEM POSITION, INSTRUMENT INPUT SIGNAL AND PNEUMATIC PRESSURE TO THE
ACTUATOR. USING THIS INFORMATION, THE DIGITAL VALVE CONTROLLER DIAGNOSES NOT ONLY
ITSELF, BUT ALSO THE VALVE AND ACTUATOR TO WHICH IT IS MOUNTED.

FIELDVUE DVC6000 Series Digital Valve Controller


DVC6000 Series
nInstallation and Basic Setup Check List
Installation
Mounting
 Instrument correctly mounted on the actuator. See the appropriate mounting
procedure or installation instructions provided with the mounting kit.

 Feedback linkage properly connected. See installation instructions


provided with the mounting kit.
Pneumatic Connections and Air Supply

 Regulator correctly mounted. Perform one of the regulator mounting


procedures on page 2-6.
 Air supply connected and at proper pressure. Connect supply as described on
page 2-7. Also see specifications on page 4-1.
 Instrument output connected to the actuator. Connect instrument output as
described on page 2-8.

Wiring and Electrical Connections

 Conduit, if necessary, properly installed. Refer to local and national electrical


codes.

 Loop wiring properly connected to the LOOP + and - terminals in the terminal box.
Connect loop wiring as described on page 2-9.

 
 HART filter installed if required. Refer to the FIELDVUE DVC6000 Digital Valve
Controller Instruction Manual - Form 5647 to determine if a HART filter is required
for your system.
Basic Setup and Calibration
 Basic Setup complete. Perform Basic Setup procedure on page 3-1.
 Calibration complete. Perform Auto Calibrate Travel procedure on page 3-5.
 Final control element correctly responds to a set point change and is stable. If
necessary, perform Stabilizing or Optimizing Valve Response on page 3-6.
Final control element is ready to be placed on line.

WARNING

This product is intended for a specific range of application specifications. Incorrect


configuration of a positioning instrument could result in the malfunction of the product,
property damage or personal injury.

i
DVC6000 Series
Model 375 Field Communicator Menu Structure for FIELDVUER DVC6000
Instrument Level HC, AD and PD
Press & Actuator
Auto Setup
1 Pressure Units A
1-1-1 1 Setup Wizard 2 Max Supply Press
2 Relay Adjust 1-1-2-3 3 Actuator Style
3 Auto Calib Travel
1-1 Basic Setup 4 Stabilize/Optimize 4 Feedbck Connection
1 Auto Setup 5 Performance Tuner 5 Tvl Sensor Motion
Hot Key 2 Manual Setup 6 Valve Style
1 Instrument Mode 3 7 Zero Ctrl Signal
2 Control Mode Manual Setup
3 Protection 1 Instrument Mode
4 Stabilize/Optimize 2 Control Mode
3 Press & Actuator Tuning & Calib
1-1-2 4 Tuning & Calib
1-1-2-4 1 Tuning Set B
2 Tvl Cutoff Low
3 Relay Adjust
Mode 4 Auto Calib Travel
1 Instrument Mode
1-2-1 2 Control Mode
3 Restart Ctrl Mode
4 Restart 1-2-1-5 Burst
5 Burst 1 Burst Enable
2 Burst Command
FOLLOW THIS PATH TO 3 Select Cmd 3 Press
PERFORM BASIC SETUP C
General
1 HART Tag
2 Message
FOLLOW THIS PATH TO 1-2-3 3 Descriptor
VIEW MODEL 375 AND Detailed Setup 4 Date
DVC6000 INFORMATION 1 Mode 5 Valve Serial Num Limits & Cutoffs
2 Protection 6 Inst Serial Num 1-2-6-4 1 Tvl Limit High
1-2 3 General 7 Polling Address 2 Tvl Limit Low
4 Measured Var 3 Tvl Cutoff High
5 Actuator & Valve Measured Var 4 Tvl Cutoff Low
6 Response Control
7 Alerts
1 Analg Input Units D
2 Analog In Range Hi
8 Self Test Shutdown 3 Analog In Range Lo 1-2-6-5 Min Open/Close
Setup & Diag 1 Min Opening Time
1 Basic Setup 4 Pressure Units
1 1-2-4 2 Min Closing Time
2 Detailed Setup 5 Temp Units
3 Display
4 Calibrate Actuator & Valve
5 Stroke Valve 1 Relay Type
2 Max Supply Press Travel Alerts
1-2-7-1 1 Tvl Hi/Lo Enab
3 Actuator Style
4 Feedbck Connection 2 Tvl HH/LL Enab
1-2-5 5 Tvl Sensor Motion
6 Valve Style
3 Tvl Alert Hi Pt
4 Tvl Alert Lo Pt
E
Online
1 Setup & Diag 7 Zero Ctrl Signal Input Char 5 Tvl Alert Hi Hi Pt
2 Analog In 1-2-6-2 1 Select Input Char 6 Tvl Alert Lo Lo Pt
3 Travel Response Control 2 Define Custom 7 Tvl Alrt DB
4 Valve SP Pressures 1 Tuning Set Char
5 Drive Sgl 6 1 Output A 2 Input Char
6 Pressures 2 Output B 3 Set Pt Filter Time
7 Instrument Status 3 A-B 1-2-6 4 Limits & Cutoffs 1-2-7-2 Travel Dev Alert
4 Supply 3 5 Min Open/Close 1 Tvl Dev Alrt Enab
6 Integral Settings Integral Settings 2 Tvl Dev Alrt Pt
2
1 Enab Int Settings 3 Tvl Dev Time F
1-2-6-6 2 Integral Gain
3 Integral Dead Zone
Alerts Travel Accum Alert
Instrument Status 1 Travel Alerts 1-2-7-3 1 Tvl Acum Alrt Enab
1 Done 2 Travel Dev Alert 2 Tvl Acum Alrt Pt
1-2-7
2 Valve Alerts 3 Travel Accum Alert 3 Tvl Acum DB
3 Failure Alerts 4 Cycle Count Alert 4 Tvl Acum
7 4 Alert Record 5 Other Alerts
5 Operational Status 6 Alert Record Cycle Count Alert
1 Cycl Cnt Alrt Enab
Field Communicator
Self Test Shutdown
1-2-8 1 Done 2 Cycl Count Alrt Pt G
1 Offline 2 Flash ROM Fail 3 Cycl Count DB
Display 1-2-7-4 4 Cycl Count
2 Online 3 No Free Time
3 Frequency Device 1 Variables 4 Ref Voltage Fail
1 2 Device Information
4 Utility 5 Drive Current Fail Other Alerts
1-3 3 375 DD Rev 6 Critical NVM Fail 1 Aux Terminal Mode
7 Temp Sensor Fail 2 Aux In Alrt Enab
Calibrate 8 Press Sensor Fail 3 Aux In Alrt State
1 Analog In Calib Variables 1-2-7-5
9 Tvl Sensor Fail 4 Drive Alrt Enab
2 Auto Calib Travel 1-3-1 1 Aux Input 5 Supply Press Alrt Pt 3
3 Man Calib Travel 2 Temp
Notes: 4 Pressure Calib 3 Cycl Count H
4 Tvl Acum Alert Record
1-4 5 Restore Calib 1 Display Record
1-1-1 indicates fast-key sequence to reach menu 6 Calib Loc Man Calib Travel 5 Free Time
6 Raw Tvl Input 2 Clear Record
7 Relay Adjust 1 Analog Adjust
1 This menu is available by pressing the left 3 Inst Date & Time
8 Tvl Sensor Adjust 2 Digital Adjust 1-2-7-6
1-4-3 4 Record Group Enab
arrow key from the previous menu. 9 Performance Tuner
Device Information
2 This function not available on DVC6000 Series Stroke Valve 3 Pressure Calib 1 HART Univ Rev
with firmware revision 2. 1 Done 1 Output A Sensor 2 Device Rev
2 Ramp Open 3 Output B Sensor 3 Firmware Rev
3 Ramp Closed 4 Hardware Rev
3 Not available in the HC tier.
1-5 4 Ramp to Target
1-4-4 3 Supply Sensor
1-3-2 5 Inst Level
I
5 Step to Target 3 6 Device ID

1 2 3 4 5 6
Model 375 Field Communicator Menu Structure for
ii Device Description Revision 4
DVC6000 Series
Model 375 Field Communicator Fast-Key Sequence (DVC6000 Series Instrument Levels HC, AD and PD)
Fast- Key Coordi- Fast- Key Coordi-
Function/Variable Function/Variable
Sequence nates(1) Sequence nates(1)
Actuator Style 1-2-5-3 4-E Pressure, Output A 6-1 2-F
Alert Record 1-2-7-6 4-G Pressure, Output A - Output B 6-3 2-F
Analog Input 2 1-E Pressure, Output B 6-2 2-F
Analog Input Range High 1-2-4-2 4-D Pressure, Supply(3) 6-4 2-F
Analog Input Range Low 1-2-4-3 4-D Pressure Units 1-2-4-4 4-D
Analog Input Units 1-2-4-1 4-D Protection Hot Key-3 1-B
Auto Setup 1-1-1 4-A Raw Travel Input 1-3-1-6 5-H
Auxiliary Input 1-3-1-1 5-H Relay Adjust 1-4-7 4-A
Auxiliary Input Alert Enable 1-2-7-5-2 6-H Relay Type 1-2-5-1 4-E
Auxiliary Input Alert State 1-2-7-5-3 6-H Restart 1-2-1-4 4-C
Auxiliary Terminal Mode 1-2-7-5-1 6-H Restart Control Mode 1-2-1-3 4-C
Basic Setup 1-1 3-A Self Test Shutdown 1-2-8 4-G
Burst 1-2-1-5 4-C Set Point Filter Time 1-2-6-3 4-F
Calibrate 1-4 2-E Setup Wizard 1-1-1-1 4-A
Calibrate, Analog Input 1-4-1 3-H Stabilize/Optimize Hot Key-4 1-B
Calibrate Travel (Auto) 1-4-2 3-H Stroke Valve 1-5 3-I
Calibrate, Travel (Manual) 1-4-3 3-H Supply Pressure Alert Point(3) 1-2-7-5-5 6-H
Calibrate, Pressure Sensors 1-4-4 3-H Temperature, Internal 1-3-1-2 5-H
Calibration Location 1-4-6 3-H Temperature Units 1-2-4-5 4-D
Calibration Restore 1-4-5 3-H Travel 3 1-E
Control Mode Hot Key-2 1-B Travel Accumulator 1-2-7-3-4 6-F
Cycle Count 1-2-7-4-4 5-H Travel Accumulator Alert Enable 1-2-7-3-1 6-F
Cycle Counter Alert Enable 1-2-7-4-1 6-G Travel Accumulator Alert Point 1-2-7-3-2 6-F
Cycle Counter Alert Point 1-2-7-4-2 6-G Travel Accumulator Deadband 1-2-7-3-3 6-F
Cycle Counter Deadband 1-2-7-4-3 6-G Travel Alert Hi/Lo Enable 1-2-7-1-1 6-E
Date 1-2-3-4 4-C Travel Alert High Point 1-2-7-1-3 6-E
Descriptor 1-2-3-3 4-C Travel Alert Low Point 1-2-7-1-4 6-E
Device Description Revision, Field Communicator 1-3-3 3-H Travel Alert HiHi/LoLo Enable 1-2-7-1-2 6-E
Device Information 1-3-2 5-I Travel Alert High High Point 1-2-7-1-5 6-E
Drive Alert Enable 1-2-7-5-4 6-H Travel Alert Low Low Point 1-2-7-1-6 6-E
Drive Signal 5 1-F Travel Alert Deadband 1-2-7-1-7 6-E
Feedback Connection 1-2-5-4 4-E Travel Cutoff High 1-2-6-4-3 6-D
HART Tag 1-2-3-1 4-C Travel Cutoff Low 1-2-6-4-4 6-D
Input Characteristic 1-2-6-2 4-F Travel Deviation Alert Enable 1-2-7-2-1 6-F
Instrument Level 1-3-2-5 5-I Travel Deviation Alert Point 1-2-7-2-2 6-F
Instrument Mode Hot Key-1 1-B Travel Deviation Time 1-2-7-2-3 6-F
Instrument Serial Number 1-2-3-6 4-D Travel Limit High 1-2-6-4-1 6-D
Instrument Status 7 1-F Travel Limit Low 1-2-6-4-2 6-D
Integral Settings(2) 1-2-6-6 4-F Travel Sensor Adjust 1-4-8 3-I
Manual Setup 1-1-2 4-B Travel Sensor Motion 1-2-5-5 4-E
Maximum Supply Pressure 1-2-5-2 4-E Tuning Set 1-2-6-1 4-F
Message 1-2-3-2 4-C Valve Serial Number 1-2-3-5 4-D
Minimum Closing Time 1-2-6-5-2 6-D Valve Set Point 4 1-F
Minimum Opening Time 1-2-6-5-1 6-D Valve Style 1-2-5-6 4-E
Performance Tuner(3) 1-1-1-5 4-A Zero Control Signal 1-2-5-7 4-E
Polling Address 1-2-3-7 4-D
1. Coordinates are to help locate the item on the menu structure on the previous page.
2. This function not available on DVC6000 Series with firmware revision 2.
3. Not available in the HC tier.

iii
DVC6000 Series
Model 375 Field Communicator Menu Structure for FIELDVUER DVC6000
Instrument Level AC
A

Press & Actuator


Hot Key Auto Setup
1 Pressure Units
1 Instrument Mode 1-1-1 1 Setup Wizard 2 Max Supply Press
2 Control Mode 2 Relay Adjust 1-1-2-3 3 Actuator Style
3 Protection 3 Auto Calib Travel
1-1 Basic Setup 4 Feedbck Connection
4 Stabilize/Optimize 4 Stabilize/Optimize
1 Auto Setup 5 Tvl Sensor Motion
2 Manual Setup 6 Valve Style
7 Zero Ctrl Signal
B
Manual Setup
1 Instrument Mode
2 Control Mode
3 Press & Actuator Tuning & Calib
1-1-2 4 Tuning & Calib 1 Tuning Set
1-1-2-4
2 Relay Adjust
3 Auto Calib Travel

C
1-2-1 General
1 HART Tag
2 Message
Detailed Setup 3 Descriptor
1-2 1 General 4 Date
2 Measured Var 5 Valve Serial Num
3 Response Control 6 Inst Serial Num
4 Relay Type 7 Polling Address

Measured Vars
D
1 Analg Input Units
Setup 2 Analog In Range Hi
1 Basic Setup 1-2-2 3 Analog In Range Lo
1
2 Detailed Setup
3 Calibrate

E
Online
1 Setup
2 Display
Response Control
1 Tuning Set Integral Settings
2 Select Input Char 1-2-3-3 1 Enab Int Settings
1-2-3 3 Integral Settings 2 Integral Gain
3 Integral Dead Zone
Calibrate
1 Analog In Calib
2 Auto Calib Travel
F
3 Man Calib Travel
4 Restore Calib
1-3 5 Calib Loc
6 Relay Adjust Man Calib Travel
7 Tvl Sensor Adjust 1-3-3 1 Analog Adjust

Display G
Field Communicator 1 Device Information
1 Offline 2 375 DD Rev
2
2 Online
3 Frequency Device Device Information
1
4 Utility 1 HART Univ Rev
2 Device Rev
3 Firmware Rev
Notes: 4 Hardware Rev
2-1 5 Inst Level
1-1-1 indicates fast-key sequence to reach menu 6 Device ID H
1 This menu is available by pressing the left
arrow key from the previous menu.

1 2 3 4 5 6
Menu Structure for Model 375 Field Communicator
Device Description Revision 4
iv
DVC6000 Series
Model 375 Field Communicator Fast-Key Sequence (DVC6000 Series Instrument Level AC)
Fast- Key Coordi- Fast- Key Coordi-
Function/Variable Function/Variable
Sequence nates(1) Sequence nates(1)
Analog Input Range High 1-2-2-2 4-D Polling Address 1-2-1-7 4-D
Analog Input Range Low 1-2-2-3 4-D Protection Hot Key-3 1-B
Analog Input Units 1-2-2-1 4-D Relay Adjust 1-3-6 4-B
Auto Setup 1-1-1 4-B Relay Type 1-2-4 3-D
Basic Setup 1-1 3-B Setup Wizard 1-1-1-1 4-B
Calibrate, Analog Input 1-3-1 3-F Stabilize/Optimize Hot Key-4 1-B
Calibrate Travel (Auto) 1-3-2 3-F Travel Sensor Adjust 1-3-7 3-G
Calibrate, Travel (Manual) 1-3-3 3-F Travel Sensor Motion 1-1-2-3-5 5-B
Calibration Location 1-3-5 3-F Tuning Set 1-2-3-1 4-F
Calibration Restore 1-3-4 3-F Valve Serial Number 1-2-1-5 4-D
Control Mode Hot Key-2 1-B Valve Style 1-1-2-3-6 5-B
Date 1-2-1-4 4-D Zero Control Signal 1-1-2-3-7 5-B
Descriptor 1-2-1-3 4-D Instrument Level 2-1-5 5-H
Device Description Revision, Field Communicator 2-2 5-G Instrument Mode Hot Key-1 1-B
Device Information 2-1 3-G Instrument Serial Number 1-2-1-6 4-D
Feedback Connection 1-1-2-3-4 5-B Integral Settings 1-2-3-3 5-F
HART Tag 1-2-1-1 4-C Manual Setup 1-1-2 4-B
Input Characteristic 1-2-3-2 4-F Message 1-2-1-2 4-C
1. Coordinates are to help locate the item on the menu structure on the following page.

v
DVC6000 Series

vi
Using This Guide
1-1 1

W8115 / IL

Figure 1-2. Rotary Control Valve with Type DVC6020 Digital


Valve Controller
traditional function of converting an input current signal
to a pneumatic output pressure, the DVC6000 Series
W7957 / IL
digital valve controllers communicate via HART
protocol.
Figure 1-1. Type DVC6010 Digital Valve Controller Mounted
on a Sliding-Stem Valve Actuator DVC6000 Series digital valve controllers are designed
to directly replace standard pneumatic and
electro-pneumatic valve mounted positioners.

Note
No person may install, operate, or Use of this Guide
maintain a DVC6000 Series digital This guide describes how to install, setup, and
valve controller without first D being calibrate DVC6000 Series digital valve controllers.
fully trained and qualified in valve, Additional information for installing, operating, and
actuator and accessory installation, maintaining the DVC6000 Series digital valve
operation and maintenance, and D controllers can be found in the related documents
carefully reading and understanding listed on page 4-5.
the contents of this manual. If you
have any questions regarding these This guide describes instrument setup and calibration
instructions, contact your Fisher sales using a Model 375 Field Communicator. For
office before proceeding. information on using the Model 375 Field
Communicator, see the Product Manual for the Field
Communicator available from Emerson Performance
Technologies. An abbreviated description of Field
Communicator operation is also contained in the
FIELDVUE instrument instruction manual.
You can also setup and calibrate the instrument using
a personal computer and AMS ValveLink Software or
Product Description AMS Suite: Intelligent Device Manager. For
DVC6000 Series digital valve controllers (figures 1-1 information on using AMS ValveLink Software or AMS
and 1-2) are communicating, microprocessor-based Device Manager with a FIELDVUE instrument, refer to
current-to-pneumatic instruments. In addition to the the appropriate documentation or online help.

May 2005 1-1


DVC6000 Series
Displaying the Field Communicator Displaying the FIELDVUER Instrument
Device Description Revision Number Firmware Revision Number
Device Description (DD) revision identifies the version To view the instrument firmware revision, connect the
of the Fisher Device Description that resides in the Field Communicator to an instrument connected to a
Field Communicator. The device description defines source supplying a 4 to 20 mA signal. From the Online
how the Field Communicator interacts with the user menu, select Setup & Diag, Display, Device
1 and instrument. You can display the DD revision from Information, and Firmware Rev.
the Offline or Online menu.

Offline Menu—To see the Field Communicator


device description revision number from the Offline
Note
menu, select Utility, Simulation, Fisher Controls, and Neither Emerson, Emerson Process
DVC6000. Management, Fisher, nor any of their
affiliated entities assumes
responsibility for the selection, use,
Online Menu—To see the Field Communicator device and maintenance of any product.
description revision number from the Online menu, Responsibility for the selection, use,
connect the Field Communicator to an instrument and maintenance of any product
connected to a source supplying a 4 to 20 mA signal. remains with the purchaser and
From the Online menu, select Setup & Diag, Display, end-user.
375 DD Rev.

1-2 May 2005


Installation
2-2 2
Mounting Guidelines for Mounting Type DVC6010
on Sliding-Stem Actuators Up to 102 mm
(4 Inches) of Travel
WARNING
WARNING
Avoid personal injury or property
damage from sudden release of Refer to the Installation WARNING at 2
process pressure or bursting of parts. the beginning of this section.
Before proceeding with any
Installation procedures:
 Always wear protective clothing The Type DVC6010 digital valve controller mounts on
and eyewear to prevent personal sliding-stem actuators with up to 102 mm (4-inch)
injury. travel. Figure 2-1 shows a typical mounting on an
actuator with up to 51 mm (2-inch) travel. Figure 2-2
 Disconnect any operating lines shows a typical mounting on actuators with 51 to 102
providing air pressure, electric power, mm (2- to 4-inch) travel. For actuators with greater
or a control signal to the actuator. Be than 102 mm (4-inch) travel, see the guidelines for
sure the actuator cannot suddenly mounting a Type DVC6020 digital valve controller.
open or close the valve.
Refer to the following guidelines when mounting on
 Use bypass valves or completely
sliding-stem actuators with up to 4 inches of travel.
shut off the process to isolate the
valve from process pressure. Relieve 1. Attach the connector arm to the valve stem
process pressure from both sides of connector.
the valve. Drain the process media
from both sides of the valve. 2. Attach the mounting bracket to the digital valve
controller housing.
 Vent the pneumatic actuator
loading pressure and relieve any 3. If valve travel exceeds 2 inches, a feedback arm
actuator spring precompression. extension is attached to the existing 2-inch feedback
arm. Remove the existing bias spring from the 2-inch
 Use lock-out procedures to be feedback arm. Attach the feedback arm extension to
sure that the above measures stay in the feedback arm as shown in figure 2-2.
effect while you work on the
equipment. 4. Mount the digital valve controller on the actuator as
described in the mounting kit instructions.
 Check with your process or
safety engineer for any additional 5. Set the position of the feedback arm on the digital
measures that must be taken to valve controller to the no air position by inserting the
protect against process media. alignment pin through the hole on the feedback arm as
follows:

 For air-to-open actuators (i.e., the actuator


stem retracts into the actuator casing or cylinder as air
pressure to the casing or lower cylinder increases),
Mounting Standard DVC6000 Series insert the alignment pin into the hole marked ‘‘A’’. For
Digital Valve Controllers this style actuator, the feedback arm rotates
If ordered as part of a control valve assembly, the counterclockwise, from A to B, as air pressure to the
factory mounts the digital valve controller on the casing or lower cylinder increases.
actuator, makes pneumatic connections to the
actuator, sets up, and calibrates the instrument. If you  For air-to-close actuators (i.e., the actuator
purchased the digital valve controller separately, you stem extends from the actuator casing or cylinder as
will need a mounting kit to mount the digital valve air pressure to the casing or upper cylinder increases),
controller on the actuator. See the instructions that insert the alignment pin into the hole marked ‘‘B’’. For
come with the mounting kit for detailed information on this style actuator, the feedback arm rotates clockwise,
mounting the digital valve controller to a specific from B to A, as air pressure to the casing or upper
actuator model. cylinder increases.

May 2005 2-1


DVC6000 Series

CAP SCREW, FLANGED

2
MACHINE SCREW

SHIELD

ADJUSTMENT ARM
CONNECTOR ARM
CAP SCREW
PLAIN WASHER

29B1674-A / DOC

Figure 2-1. Type DVC6010 Digital Valve Controller Mounted on Sliding-Stem Actuators with up to 2 Inches Travel

CAP SCREW, FLANGED HEX NUT

FEEDBACK ARM LOCK WASHER


EXTENSION,
BIAS SPRING
ADJUSTMENT ARM
SPACER

MACHINE SCREW,
FLAT HEAD

HEX NUT, FLANGED

MACHINE SCREW
LOCK WASHER
SHIELD
MACHINE SCREW,
LOCK WASHER, PLAIN WASHER
HEX NUT

CONNECTOR ARM

Figure 2-2. Type DVC6010 Digital Valve Controller Mounted on Sliding-Stem Actuators with 2 to 4 Inches Travel

2-2 May 2005


Installation

MOUNTING ADAPTOR MACHINE SCREW

CAP SCREW, HEX SOCKET CAP SCREW,


HEX SOCKET

CAM 29B1672-A / DOC


CAM
MACHINE SCREW
29B2094-A / DOC

TYPICAL MOUNTING WITH SHORT FEEDBACK ARM TYPICAL MOUNTING WITH LONG FEEDBACK ARM
(FISHER TYPE 1052 SIZE 33 ACTUATOR SHOWN) (FISHER TYPE 1061 SIZE 30 - 68 ACTUATOR SHOWN)

Figure 2-3. Type DVC6020 Digital Valve Controller Mounted on Rotary Actuators

6. Apply lubricant to the pin of the adjustment arm. As


shown in figure 2-4, place the pin into the slot of the
feedback arm or feedback arm extension so that the
bias spring loads the pin against the side of the arm
with the valve travel markings.
7. Install the external lock washer on the adjustment
arm. Position the adjustment arm in the slot of the
connector arm and loosely install the flanged hex nut.
8. Slide the adjustment arm pin in the slot of the
connector arm until the pin is in line with the desired
valve travel marking. Tighten the flanged hex nut.
SPRING RELAXED
9. Remove the alignment pin and store it in the FEEDBACK
module base next to the I/P assembly. ARM

10. After calibrating the instrument, attach the shield


with two machine screws.

Guidelines for Mounting Type DVC6020


Sliding-Stem Actuators and Rotary
ADJUSTMENT
Actuators ARM PIN

BIAS SPRING

WARNING SPRING UNDER TENSION OF


A7209/IL ADJUSTMENT ARM PIN
Refer to the Installation WARNING at
the beginning of this section.
Figure 2-4. Locating Adjustment Arm Pin in Feedback Arm

Type DVC6020 digital valve controllers use a cam


(designed for linear response) and roller as the

May 2005 2-3


DVC6000 Series
MOUNTING
BRACKET FEEDBACK ARM

TRAVEL INDICATOR PIN

2
29B1703-A / DOC
SPACER

TRAVEL INDICATOR

19B3879- A / DOC

Figure 2-5. Mounting a Type DVC6030 Digital Valve Controller on a Rotary Actuator (Type 1032 Size 425A Shown)

feedback mechanism. Figure 2-3 shows the Type the pipe-away bracket and to transfer the feedback
DVC6020 mounted on rotary actuators. parts from the existing mounting bracket to the
pipe-away bracket.
4. Mount the Type DVC6020 on the actuator as
follows:
Note  If required, a mounting adaptor is included in the
mounting kit. Attach the adaptor to the actuator as
All cams supplied with FIELDVUE shown in figure 2-3. Then attach the digital valve
mounting kits are characterized to controller assembly to the adaptor. The roller on the
provide a linear response. digital valve controller feedback arm will contact the
actuator cam as it is being attached.
As shown in figure 2-3, two feedback arms are  If no mounting adaptor is required, attach the
available for the digital valve controller. Installations on digital valve controller assembly to the actuator or
Fisher Type 1051 size 33 and Type 1052 size 20 and mounting plate. The roller on the digital valve controller
33 actuators use the short feedback arm [54 mm (2.13 feedback arm will contact the actuator cam as it is
inches) from roller to pivot point]. Most other use the being attached.
long feedback arm. Make sure the correct feedback
arm is installed on the digital valve controller before
beginning the mounting procedure.
Guidelines for Mounting Type DVC6030
Refer to figure 2-3 for parts locations. Refer to the
following guidelines when mounting on rotary on Quarter-Turn Actuators
actuators:
1. If a cam is not already installed on the actuator, WARNING
install the cam as described in the instructions
included with the mounting kit. Refer to the Installation WARNING at
the beginning of this section.
2. If a mounting plate is required, fasten the mounting
plate to the actuator.
3. For applications that require remote venting, a Figure 2-5 shows the Type DVC6030 digital valve
pipe-away bracket kit is available. Follow the controller mounted on a quarter-turn actuator. Refer to
instructions included with the kit to replace the existing figure 2-5 for parts locations. Refer to the following
mounting bracket on the digital valve controller with guidelines when mounting on quarter-turn actuators:

2-4 May 2005


Installation
STARTING POSITION OF TRAVEL
INDICATOR ASSEMBLY (DIGITAL
VALVE CONTROLLER OUTPUT A
AT 0 PSI. )
IN THIS POSITION, THE “B” HOLE
IN THE FEEDBACK ARM WILL BE
ALIGNED WITH THE REFERENCE
HOLE IN THE DIGITAL VALVE
CONTROLLERS HOUSING.

E0989 / DOC

DVC6030 FEEDBACK MOVEMENT OF TRAVEL


2
ARM MOVEMENT INDICATOR ASSEMBLY WITH
INCREASING PRESSURE FROM
OUTPUT A.

ACTUATOR SHAFT MOVEMENT

STARTING POSITION OF THE ACTUATOR TRAVEL


INDICATOR ASSEMBLY IF INCREASING PRESSURE
FROM OUTPUT A DRIVES THE INDICATOR
COUNTERCLOCKWISE (THE POTENTIOMETER
SHAFT WILL ROTATE CLOCKWISE AS VIEWED 19B3879-A / DOC-1
FROM THE BACK OF THE FIELDVUE INSTRUMENT)

Figure 2-6. Explanation of Travel Indicator Starting Position and Movement, if Clockwise Orientation is Selected for
“Travel Sensor Motion” in AMS ValveLink  Software or the 375 Field Communicator

 If increasing pressure from the digital valve


controller output A rotates the potentiometer shaft
Note counterclockwise (as viewed from the back of the
instrument), mount the travel indicator assembly such
Due to NAMUR mounting limitations, do that the arrow is in the 7:30 position, as shown in
not use the heavier stainless steel Type figure 2-7.
DVC6030S in vibration service.

1. If necessary, remove the existing hub from the


actuator shaft. Note
2. If a positioner plate is required, attach the AMS ValveLink Software and the 375
positioner plate to the actuator as described in the Field Communicator use the
mounting kit instructions. convention of clockwise (figure 2-6)
3. If required, attach the spacer to the actuator shaft. and counterclockwise (figure 2-7) when
viewing the potentiometer shaft from
Refer to figures 2-6 and 2-7. The travel indicator the back of the FIELDVUE instrument.
assembly can have a starting position of 7:30 or 10:30.
Determine the desired starting position then proceed
with the next step. Considering the top of the digital
valve controller as the 12 o’clock position, in the next 4. Attach the travel indicator to the shaft connector or
step attach the travel indicator, so that the pin is spacer as described in the mounting kit instructions.
positioned as follows: 5. Attach the mounting bracket to the digital valve
controller.
 If increasing pressure from the digital valve
controller output A rotates the potentiometer shaft 6. Position the digital valve controller so that the pin
clockwise (as viewed from the back of the on the travel indicator, engages the slot in the
instrument), mount the travel indicator assembly such feedback arm and that the bias spring loads the pin as
that the arrow is in the 10:30 position, as shown in shown in figure 2-8. Attach the digital valve controller
figure 2-6. to the actuator or positioner plate.

May 2005 2-5


DVC6000 Series

MOVEMENT OF TRAVEL E0989


INDICATOR ASSEMBLY WITH

2 INCREASING PRESSURE FROM


OUTPUT A.
DVC6030 FEEDBACK
ARM MOVEMENT

19B3879-A / DOC-2

STARTING POSITION OF
TRAVEL INDICATOR ASSEMBLY ACTUATOR SHAFT MOVEMENT
(DIGITAL VALVE CONTROLLER
OUTPUT A AT 0 PSI). STARTING POSITION OF THE TRAVEL INDICATOR
IN THIS POSITION, THE “A” HOLE ASSEMBLY IF INCREASING PRESSURE FROM
IN THE FEEDBACK ARM WILL BE OUTPUT A DRIVES THE INDICATOR CLOCKWISE
ALIGNED WITH THE REFERENCE THE POTENTIOMETER SHAFT WILL ROTATE
HOLE IN THE DIGITAL VALVE COUNTERCLOCKWISE AS VIEWED FROM THE
CONTROLLERS HOUSING. BACK OF THE FIELDVUE INSTRUMENT.

Figure 2-7. Explanation of Travel Indicator Starting Position and Movement if Counterclockwise Orientation is Selected for
“Travel Sensor Motion” in AMS ValveLink  Software or the 375 Field Communicator

Mounting for Remote Mount Type


HOLE B
HOLE A
DVC6000 Instruments
Refer to the DVC6000 Series Digital Valve Controller
instruction manual, Form 5647.

Mounting the Type 67CFR Filter


Regulator
A Type 67CFR filter regulator, when used with the
DVC6000 Series digital valve controllers, can be
mounted three ways.
TRAVEL
INDICATOR PIN
FEEDBACK ARM Integral-Mounted Regulator
48B4164-B / DOC BIAS SPRING
Refer to figure 2-9. Lubricate an O-ring and insert it in
the recess around the SUPPLY connection on the
digital valve controller. Attach the Type 67CFR filter
Figure 2-8. Positioning Travel Indicator Pin in the Feedback regulator to the side of the digital valve controller.
Arm (Viewed as if Looking from the Type DVC6030 Thread a 1/4-inch socket-head pipe plug into the
toward the Actuator) unused outlet on the filter regulator. This is the
standard method of mounting the filter regulator.

Yoke-Mounted Regulator
7. If a travel indicator scale is included in the mounting Mount the filter regulator with 2 cap screws to the
kit, attach the scale as described in the mounting kit pre-drilled and tapped holes in the actuator yoke.
instructions. Thread a 1/4-inch socket-head pipe plug into the

2-6 May 2005


Installation

TYPE 67CFR

2
CAP SCREWS

O-RING 1
NOTE:
1 APPLY LUBRICANT SUPPLY CONNECTION
W8077-1 / IL

Figure 2-9. Mounting the Type 67CFR Regulator on a DVC6000 Series Digital Valve Controller

unused outlet on the filter regulator. No O-ring is


required.
Note
Casing-Mounted Regulator
Make pressure connections to the
Use the separate Type 67CFR filter regulator casing digital valve controller using tubing
mounting bracket provided with the filter regulator. with at least 10 mm (0.375 inch)
Attach the mounting bracket to the Type 67CFR and diameter.
then attach this assembly to the actuator casing.
Thread a 1/4-inch socket-head pipe plug into the
unused outlet on the filter regulator. No O-ring is
required.

Pressure Connections
Supply Connections
WARNING
Refer to the Installation WARNING at
the beginning of this section. WARNING
To avoid personal injury and property
Pressure connections are shown in figure 2-10. All damage resulting from bursting of
pressure connections on the digital valve controller are parts, do not exceed maximum supply
1/4-inch NPT female connections. Use 10 mm (0.375 pressure.
inch) tubing for all pressure connections. If remote
venting is required, refer to the vent subsection.

May 2005 2-7


DVC6000 Series
WARNING LOOP CONNECTIONS
TERMINAL BOX

Severe personal injury or property


1/2-INCH NPT
damage may occur from an CONDUIT
uncontrolled process if the instrument CONNECTIONS
(BOTH SIDES)
air supply is not clean, dry and
oil-free. While use and regular OUTPUT A
maintenance of a filter that removes CONNECTION

particles larger than 40 microns in


2 diameter will suffice in most
applications, check with a Fisher field
office and Industry Instrument air SUPPLY
CONNECTION
quality standards for use with
corrosive air or if you are unsure
about the amount of air filtration or
OUTPUT B
filter maintenance. CONNECTION

Supply pressure must be clean, dry air that meets the W7963-1 / IL
requirements of ISA Standard 7.0.01.
If you are using a Type 67CFR filter regulator, connect VALVE-MOUNTED INSTRUMENT
the supply line to the 1/4-inch NPT IN connection and NOTE:
attach tubing from the output connection on the filter PNEUMATIC CONNECTIONS APPLICABLE TO BOTH VALVE-MOUNTED
INSTRUMENTS AND TYPE DVC6005 BASE UNIT.
regulator to the SUPPLY connection on the
instrument. If you are using an integral mounted Type
67CFR filter regulator, connect the supply to the IN Figure 2-10. DVC6000 Series Digital Valve Controller
connection on the regulator. Connections

Output Connection
A factory mounted digital valve controller has its output current, OUTPUT A is at 0 pressure and OUTPUT B is
piped to the supply connection on the actuator. If at full supply pressure when the relay is properly
mounting the digital valve controller in the field, adjusted.
connect the 1/4-inch NPT digital valve controller output To have the actuator stem extend from the cylinder
connection to the pneumatic actuator input connection. with increasing input signal, connect OUTPUT A to the
upper actuator cylinder connection. Connect OUTPUT
Single-Acting Actuators B to the lower cylinder connection. Figure 2-11 shows
the digital valve controller connected to a
When connecting a single-acting direct digital valve double-acting piston actuator.
controller (relay type A) to a single-acting actuator, the
OUTPUT B connection must be plugged. Connect To have the actuator stem retract into the cylinder with
OUTPUT A to the actuator diaphragm casing. The increasing input signal, connect OUTPUT A to the
gauge for OUTPUT B is not used. It must be replaced lower actuator cylinder connection. Connect OUTPUT
with a screened vent. B to the upper cylinder connection.
When connecting a single-acting reverse digital valve
controller (relay type B) to a single-acting actuator, the
OUTPUT A connection must be plugged. Connect
OUTPUT B to the actuator diaphragm casing. The Vent
gauge for OUTPUT A is not used and can be replaced The relay output constantly bleeds a small amount of
with a pipe plug. supply air into the area under the cover. The vent
openings at the back of the housing should be left
open to prevent pressure buildup under the cover. If a
Double-Acting Actuators remote vent is required, the vent lines must be as
DVC6000 digital valve controllers on double-acting short as possible with a minimum number of bends
actuators always use relay type A. With no input and elbows.

2-8 May 2005


Installation
SAFETY GROUND
TALK -
TALK+

EARTH GROUND

LOOP+
38B6470-B
E0030-1 / IL LOOP -

Figure 2-12. DVC6000 Series Digital Valve Controller


Loop Connections Terminal Box

WARNING
Personal injury or property damage
W7960-2 / IL

caused by fire or explosion may occur


Figure 2-11. Type DVC6010 Digital Valve Controller Mounted if this connection is attempted in a
on Type 585C Piston Actuator potentially explosive atmosphere or in
an area that has been classified as
hazardous. Confirm that area
classification and atmosphere
conditions permit the safe removal of
the terminal box cover before
proceeding.
Wiring and Electrical Connections

WARNING
4 to 20 mA Loop Connections
Refer to the Installation WARNING at The digital valve controller is normally powered by a
the beginning of this section. control system output card. The use of shielded cable
will ensure proper operation in electrically noisy
environments.

WARNING
To avoid personal injury resulting Note
from electrical shock, do not exceed
maximum input voltage specified in Connect the digital valve controller to a
table 4-1 of this quick start guide, or 4 to 20 mA current source for operation
on the product nameplate. If the input in the point-to-point wiring mode. In
voltage specified differs, do not the point-to-point wiring mode, the
exceed the lowest specified maximum digital valve controller will not operate
input voltage. when connected to a voltage source.

May 2005 2-9


DVC6000 Series
Wire the digital valve controller as follows, refer to
figure 2-12:
NON-HART BASED DCS
1. Remove the loop connections terminal box cap
(see figure 2-10).
2. Route the field wiring into the terminal box. When
applicable, install conduit using local and national I/ I/
electrical codes which apply to the application. O O

3. Connect the control system output card positive


2
HART
wire ‘‘current output’’ to the LOOP + screw terminal in FILTER
the terminal box. Connect the control system output
card negative (or return) wire to the LOOP - screw
terminal in the terminal box. 4-20
mA
DIGITAL VALVE
4. As shown in figure 2-12, two ground terminals are CONTROLLER

available for connecting a safety ground, earth ground,


or drain wire. The safety ground is electrically identical
to the earth ground. Make connections to these T T VALVE
terminals following national and local codes and plant x x

standards.
A6188-1/IL
5. Replace and hand tighten the terminal box cap.
When the loop is ready for startup, apply power to the
Figure 2-13. HART  Filter Application
control system output card.

WARNING
HARTR Filter
Personal injury or property damage, Depending on the control system you are using, a
caused by fire or explosion, can result HART filter may be needed to allow HART
from the discharge of static electricity. communication. The HART filter is an active device
Connect a 14 AWG (2.08 mm2) ground that is inserted in field wiring from the HART loop. The
strap between the digital valve filter is normally installed near the field wiring terminals
controller and earth ground when of the control system I/O (see figure 2-13). Its purpose
flammable or hazardous gases are is to effectively isolate the control system output from
present. Refer to national and local modulated HART communication signals and raise the
codes and standards for grounding impedance of the control system to allow HART
requirements. communication. For more information on the
description and use of the HART filter, refer to the
To avoid static discharge from the
appropriate separate HART filter instruction manual.
plastic cover, do not rub or clean the
cover with solvents. Clean with a mild To determine if your system requires a filter, refer to
detergent and water only. the FIELDVUE DVC6000 Series Digital Valve
Controller instruction manual, Form 5647.

2-10 May 2005


Installation

nInstallation Check List


Mounting
 Is the instrument correctly mounted on the actuator? If not, refer to appropriate
mounting procedure and see installation instructions provided with the mounting kit.

 Is the feedback linkage properly connected? If not, see installation instructions


provided with the mounting kit. 2

Pneumatic Connections and Air Supply

 Is the regulator correctly mounted? If not, perform one of the regulator mounting procedures on
page 2-6.

 Is the air supply connected and at proper pressure? If not, connect supply as described on page
2-7. Also see specifications on page 4-1.

 Is the instrument output connected to the actuator? If not, connect instrument output as
described on page 2-8.

Wiring and Electrical Connections

 If necessary, is the conduit properly installed? If not, refer to local and national electrical
codes.

 Is the loop wiring properly connected to the LOOP + and - terminals in the terminal box? If not,
connect loop wiring as described on page 2-9.

 If necessary, is the HART filter installed on your system? To determine if a HART filter is necessary,
refer to the FIELDVUE DVC6000 Digital Valve Controller Instruction Manual - Form 5647. For
HART filter installation information, refer to the appropriate HART instruction manual.

You are ready to perform Basic Setup and Calibration in the next section.

May 2005 2-11


DVC6000 Series

2-12 May 2005


Basic Setup and Calibration
FIELD
COMMUNICATOR
CONNECTIONS
CONTROL ROOM FIELD

HF300 SERIES
HART FILTER OR LC340 FIELD INSTRUMENT 4 - 20 MA LOOP
LINE CONDITIONER CONNECTION CONNECTIONS
OR 0 - 24VDC

CONTROLLER
I/O - -
+ +
1

HART
COMMUNICATION
3
CONNECTION

NOTE:
1 NOT ALL CONTROL SYSTEMS REQUIRE A HART FILTER. IF NO HART FILTER IS PRESENT, CONNECT
FIELD COMMUNICATOR TO CONTROL SYSTEM OUTPUT TERMINALS.
2 SEE FIGURE 2-12 FOR TERMINAL BOX DETAILS.
38B6470-A / DOC
A6194-3 / IL

Figure 3-1. Connecting the Field Communicator to a FIELDVUE  Instrument

3-3 3
Connecting the Model 375 Field Basic Setup
Communicator to the Digital Valve
Controller WARNING
The Field Communicator may be connected to the 4 to Changes to the instrument setup may
20 mA loop wiring or directly to the digital valve cause changes in the output pressure
controller (see figure 3-1). or valve travel. Depending on the
application, these changes may upset
If the Field Communicator is connected directly to the process variables, which may result in
digital valve controller, attach the clip-on wires personal injury or property damage.
provided with the Field Communicator to the TALK
terminals, or the LOOP + and - terminals, in the digital
valve controller terminal box. The TALK terminals are Before beginning basic setup, be sure the instrument
the same as the LOOP + and - terminals (see figure is correctly mounted. Refer to the installation
2-12). instructions supplied with the mounting kit.

May 2005 3-1


DVC6000 Series
the instrument. If the actuator on which the instrument
is mounted is not listed by the Setup Wizard, specify
OTHER as the actuator manufacturer or actuator type
From the DVC6000 DVC6000: and refer to Non-Typical Actuators.
Online menu, select Online
1Setup & Diag
Setup & Diag. 2 Analog In 12.42 mA After entering the actuator information, the Setup
3 Travel 53.69 % Wizard prompts you to adjust the relay. For additional
4 Valve SP 53.69% information, refer to Relay Adjustment in this section.
5 Drive Sgl 58.15% After completing the relay adjustment, the next step in
basic setup is to calibrate the instrument travel. Follow
the prompts on the Field Communicator display to
automatically calibrate instrument travel. The
DVC6000:
From the Setup & Setup & Diag calibration procedure uses the valve and actuator
3 Diag Menu, select 1Basic Setup
2 Detailed Setup
stops as the 0% and 100% calibration points. For
Basic Setup. 3 Display additional information, refer to Auto Calibrate Travel in
4 Calibrate this section.
5 Stroke Valve
HOME
WARNING

DVC6000: During calibration the valve will move


From the Basic Setup full stroke. To avoid personal injury
Basic Setup 1Auto Setup and property damage caused by the
menu, select 2 Manual Setup release of pressure or process fluid,
Auto Setup. provide some temporary means of
control for the process.
HOME

DVC6000:
From the Auto Auto Setup Non-Typical Actuators
Setup menu select 1Setup Wizard If the actuator on which the instrument is mounted is
Setup Wizard and 2 Relay Adjust not listed by the Setup Wizard, specify OTHER as the
3 Auto Calib Travel
follow the on-line actuator manufacturer or actuator type. You are then
4 Stabilize/Optimize
instructions. prompted for setup parameters such as:
5 Performance Tuner
HELP HOME
 Actuator Style (spring & diaphragm, piston
double-acting without spring, piston single-acting with
INSTRUMENT LEVELS spring, piston double-acting with spring)
HC, AD AND PD
 Valve Style (rotary or sliding-stem)
Figure 3-2. Accessing the Setup Wizard on
the Model 375 Field Communicator  On Loss of Instrument Signal, Valve (opens
or closes) This identifies whether the valve is fully
open or fully closed when the input is 0%. If you are
Connect a 4-20 mA current source to the instrument. unsure how to set this parameter, disconnect the
Connect the Field Communicator to the instrument current source to the instrument. (With double-acting
and turn it on. For information on connecting the Field and single-acting direct digital valve controllers,
Communicator, see Connecting the Model 375 Field disconnecting the current source is the same as
Communicator to the Digital Valve Controller . setting the output A pressure to zero. For single-acting
reverse digital valve controllers, disconnecting the
current source is the same as setting the output B
Typical Actuators pressure to supply.)
The Setup Wizard determines the required setup
information based upon the actuator manufacturer and  Feedback Connection (Rotary - All, SStem -
model specified. Turn on the Field Communicator and Standard, SStem - Roller). For rotary valves, enter
start the Setup Wizard by proceeding through the Rotary - All. For sliding-stem valves, if the feedback
menu sequence shown in figure 3-2 or enter the linkage consists of a connector arm, adjustment arm,
fast-key sequence 1-1-1-1 on the keypad. Follow the and feedback arm (similar to figure 3-5), enter SStem -
prompts on the Field Communicator display to setup Standard. If the feedback linkage consists of a roller

3-2 May 2005


Basic Setup and Calibration

ROLLER

3
STEM
CONNECTOR CAM

29B1665-A / DOC

Figure 3-3. Feedback Connection for Typical Long-Stroke Sliding-Stem Actuator (4 to 24-inches travel)

that follows a cam (similar to figure 3-3), enter SStem Table 3-1. DVC6000 Series Factory Default Settings
- Roller. Setup Parameter(1) Default Setting
Analog Input Units mA
Analog In Range High 20.0 mA
 Travel Sensor Motion The Setup Wizard asks if Analog In Range Low 4.0 mA
it can move the valve to determine travel sensor Control Mode
motion. If you answer Yes, the instrument will stroke AC, HC, AD, PD Analog
the valve the full travel span to determine travel Restart Control Mode
sensor motion. If you answer No, then you must AC, HC, AD, PD Resume Last
specify the rotation for increasing air pressure: Self-Test Shutdown All Failures Disabled
clockwise or counterclockwise. Determine rotation by Set Point Filter Time Filter Off
viewing the end of the travel sensor shaft. Input Characteristic Linear
Travel Limit High 125%
Travel Limit Low -25%
Travel Cutoff High
AC, HC, AD, PD 99.5%
WARNING Travel Cutoff Low
AC, HC, AD, PD 0.5%
If you answer YES to the prompt for Minimum Opening Time 0 secs
permission to move the valve, the Minimum Closing Time 0 secs
Polling Address 0
instrument will move the valve
Aux Terminal Mode
through a significant portion of its AC, HC, AD, PD Aux Input Alert
travel range. To avoid personal injury
Command 3 Pressure
and property damage caused by the Double-acting actuators differential output pressure
release of pressure or process fluid, Single-acting actuators actuator pressure
provide some temporary means of 1. If the instrument level is not indicated, the default setting indicated is for all levels.
control for the process.

For instruments with Relay Type A. If increasing air Note


pressure at output A causes the shaft to turn Relay adjustment may be required
clockwise, enter Clockwise. If it causes the shaft to before the Setup Wizard can determine
turn counterclockwise, enter Cntrclockwise. travel sensor motion. Follow the
For instruments with Relay Type B. If decreasing prompts on the Field Communicator
air pressure at output B causes the shaft to turn display if relay adjustment is
clockwise, enter Clockwise. If it causes the shaft to necessary.
turn counterclockwise, enter Cntrclockwise.

May 2005 3-3


DVC6000 Series

BLEED HOLES ARE


PLUGGED IN THE
LOW BLEED RELAY
OPTION
FOR SINGLE-ACTING DIRECT RELAYS:
ROTATE ADJUSTMENT DISC IN THIS
DIRECTION UNTIL IT CONTACTS THE
BEAM

FOR DOUBLE-ACTING RELAYS:


ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO DECREASE
OUTPUT PRESSURE

3
FOR DOUBLE-ACTING RELAYS:
ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO INCREASE
OUTPUT PRESSURE

ADJUSTMENT DISC

Figure 3-4. Location of Relay Adjustment (Shroud Removed for Clarity)

WARNING Factory Defaults


During basic setup, the Setup Wizard will ask you if
Changes to the tuning set may cause you want to use factory defaults. If you select YES,
the valve/actuator assembly to stroke. the Setup Wizard sets the setup parameters to the
To avoid personal injury and property values listed in table 3-1. (Yes is recommended for
damage caused by the release of initial setup). If you select NO, the setup parameters
pressure or process fluid, provide listed in the table remain at their previous settings.
some temporary means of control for
the process. Relay Adjustment
Before beginning calibration, check the relay
adjustment. To check relay adjustment, select Relay
Adjust from the Auto Setup menu. Follow the prompts
 Tuning Set There are eleven tuning sets from on the Field Communicator display. Replace the digital
which to choose. Each tuning set provides preselected valve controller cover when finished.
values for the digital valve controller gain and rate
settings. Typically, tuning set C provides the slowest
response and M provides the fastest response. For Single-Acting Actuators
smaller actuators, use tuning set C or D. For larger For single-acting direct digital valve controllers, make
actuators, use tuning set F or G. sure the adjustment disc is against the beam, as
shown in figure 3-4. For single-acting reverse digital
In addition, you can select User Adjusted or Expert, valve controllers, the relay is adjusted at the factory,
which allows you to modify tuning of the digital valve no further adjustment is necessary.
controller. With User Adjusted you can specify the
proportional gain. An algorithm in the Field
Communicator calculates the other gains. With Expert Double-Acting Actuators
you can specify not only the proportional gain but the For double-acting actuators, rotate the adjustment
velocity and minor loop feedback gain as well. disc, shown in figure 3-4, until the value displayed on
the Field Communicator is between 50 and 70% of
The tuning sets suggested by the Setup Wizard are
supply pressure.
only recommended starting points. After you finish
setting up and calibrating the instrument, run the If the low bleed relay option has been ordered
Performance Tuner or use Stabilize/Optimize Tuning stabilization may take approximately two minutes
to obtain optimum tuning. longer than the standard relay.

3-4 May 2005


Basic Setup and Calibration

ACTUATOR
STEM TRAVEL SENSOR SHAFT

FEEDBACK

3
ARM

ADJUSTMENT ARM

CONNECTOR ARM

A6536-1 / IL

Figure 3-5. Crossover Point

Auto Calibrate Travel select the method of crossover adjustment: manual,


last value, or default. Manual adjustment is
recommended for initial travel calibration.
WARNING 2. When prompted by the Field Communicator, make
the crossover adjustment by adjusting the current
During calibration the valve will move source until the feedback arm is 90° to the actuator
full stroke. To avoid personal injury stem, as shown in figure 3-5.
and property damage caused by the
release of pressure or process fluid, 3. The remainder of the auto-calibration procedure is
provide some temporary means of automatic. After completing auto travel calibration, the
control for the process. Field Communicator prompts you to place the
instrument In Service and verify that the travel
properly tracks the current source.
Follow the prompts on the Field Communicator display If the unit does not calibrate, refer to table 3-2 for error
to automatically calibrate instrument travel. The messages and possible remedies.
calibration procedure uses the valve and actuator
stops as the 0% and 100% calibration points. If after completing setup and calibration the valve
cycles or overshoots (unstable), or is unresponsive
Select Auto Calib Travel from the Auto Setup menu.
(sluggish), you can improve operation by selecting
1. If the Feedback Connection is Sliding-Stem either Performance Tuner or Stabilize/Optimize from
Standard, the Field Communicator prompts you to the Auto Setup menu.

May 2005 3-5


DVC6000 Series
Table 3-2. Auto Calibrate Travel Error Messages
Error Message Possible Problem and Remedy
Input current must exceed 3.8 mA for The analog input signal to the instrument must be greater than 3.8 mA. Adjust the current output from
calibration. the control system or the current source to provide at least 4.0 mA.
Place Out Of Service and ensure Calibrate The Instrument Mode must be Out of Service and the Protection must be None before the instrument
Protection is disabled before calib. can be calibrated.
The problem may be one or the other of the following:
1. The tuning set selected is too low and the valve does not reach an end point in the allotted time.
Calibration Aborted. An end point was not Press the Hot Key, select Stabilize/Optimize then Increase Response (selects next higher tuning set).
reached. 2. The tuning set selected is too high, valve operation is unstable and does not stay at an end point for
the allotted time. Press the Hot Key, select Stabilize/Optimize then Decrease Response (selects next
lower tuning set).
Verify proper mounting by referring to the appropriate mounting instructions.
3 Invalid travel value. Check mounting and
feedback arm adjustments, and inst supply
Verify instrument supply pressure by referring to the specifications in the appropriate actuator instruction
manual.
press. Then, repeat Auto Calib. Making the crossover adjustment with the valve positioned at either end of its travel will also cause this
message to appear.
Aborting due to response code or device The instrument may have been taken out of service by a primary master. Put the instrument into service
status. with the primary master or cycle the power off and on.

Using the Performance Tuner Stabilize/Optimize permits you to adjust valve


response by changing the digital valve controller
tuning.

If the valve is unstable, select Decrease Response to


Note stabilize valve operation. This selects the next lower
tuning set (e.g., F to E). If the valve response is
The performance tuner is not available sluggish, select Increase Response to make the valve
for instrument levels AC or HC. more responsive. This selects the next higher tuning
set (e.g., F to G).

The performance tuner is used to optimize digital valve


controller tuning. It can be used on most sliding-stem
and rotary designs, including Fisher and other
manufacturers’ products. Moreover, because the
performance tuner can detect internal instabilities
before they become apparent in the travel response, it Note
can generally optimize tuning more effectively than
manual tuning. Typically, the performance tuner takes If the tuning set is User Adjusted it will
3 to 5 minutes to tune an instrument, although tuning stay as User Adjusted during Stabilize/
instruments mounted on larger actuators may take Optimize, unless you change the
longer. damping, in which case it will become
Expert.
Access the performance tuner by selecting
Performance Tuner from the Auto Setup menu. Follow
the prompts on the Field Communicator display to
optimize digital valve controller tuning. If after selecting Decrease Response or Increase
Response the valve travel overshoot is excessive you
Stabilizing or Optimizing Valve can adjust the damping by selecting Decrease
Damping or Increase Damping. By selecting Decrease
Response Damping or Increase Damping the tuning set will
If after completing setup and calibration the valve become Expert, and allow you to select a damping
seems slightly unstable or unresponsive, you can value that is not represented in a predefined tuning
set. Select Decrease Damping to select a damping
improve operation by pressing the Hot Key and value that allows more overshoot. Select Increase
selecting Stabilize/Optimize, or select Damping to select a damping value that will decrease
Stabilize/Optimize from the Auto Setup menu. the overshoot.

3-6 May 2005


Basic Setup and Calibration

nBasic Setup and Calibration Check List


 Ispage
basic setup complete? If not, perform Basic Setup procedure on
3-1.

 Ispage
calibration complete? If not, perform Auto Calibrate Travel procedure on
3-5.

 Does the final control element correctly respond to a setpoint change and is it
stable? If not, perform Stabilizing or Optimizing Valve Response on page
3-6. 3
Final control element is ready to be placed on line.

May 2005 3-7


DVC6000 Series

3-8 May 2005


Specifications and Related Documents
4-4 4
Table 4-1. Specifications

Available Configurations 3 of the Pressure Equipment Directive (PED) 97 /


23 / EC. It was designed and manufactured in
Valve-Mounted Instrument
accordance with Sound Engineering Practice (SEP)
Type DVC6010: Sliding stem applications
and cannot bear the CE marking related to PED
Type DVC6020: Rotary and long-stroke
compliance.
sliding-stem applications
Type DVC6030: Quarter-turn rotary applications However, the product may bear the CE marking to
Remote-Mounted Instrument(1) indicate compliance with other applicable EC
DVC6005: Base unit for 2-inch pipestand or wall Directives.
mounting
DVC6015: Feedback unit for sliding-stem Supply Pressure(2,5)
applications
DVC6025: Feedback unit for rotary or long-stroke Recommended: 0.3 bar (5 psi) higher than 4
sliding-stem applications maximum actuator requirements, up to maximum
DVC6035: Feedback unit for quarter-turn rotary supply pressure
applications Maximum: 10.0 bar (145 psig) or maximum
pressure rating of the actuator, whichever is lower
DVC6000 Series digital valve controllers can be
mounted on Fisher and other manufacturers rotary
Steady-State Air Consumption(3)
and sliding-stem actuators.
Standard Relay:
Input Signal Supply Pressure: At 1.4 bar (20 psig) /
Temperature: 70F
Point-to-Point: Consumption: Less than 0.38 m3/hr (14 cfh)
Analog Input Signal: 4 to 20 mA dc, nominal
Minimum Voltage Available at instrument terminals Supply Pressure: At 5.5 bar (80 psig) /
must be 10.5 volts dc for analog control, 11 volts dc Temperature: 70F
for HART communication (see instrument Consumption: Less than 1.4 m3/hr (49 cfh)
instruction manual for details) Low Bleed Relay(6):
Minimum Control Current: 4.0 mA Supply Pressure: At 1.4 bar (20 psig) /
Minimum Current w/o Microprocessor Restart: 3.5 Temperature: 70F
mA Consumption: Average value 0.056 m3/hr
Maximum Voltage: 30 volts dc (2.1 cfh)
Overcurrent Protection: Input circuitry limits current
to prevent internal damage. Supply Pressure: At 5.5 bar (80 psig) /
Reverse Polarity Protection: No damage occurs Temperature: 70F
from reversal of loop current. Consumption: Average value 0.184 m3/hr
Multi-drop: (6.9 cfh)
Instrument Power: 11 to 30 volts dc at
approximately 8 mA Maximum Output Capacity(3)
Reverse Polarity Protection: No damage occurs Supply Pressure: At 1.4 bar (20 psig) /
from reversal of loop current. Temperature: 70F
Capacity: 10.6 m3/hr (375 cfh)
Output Signal(2) Supply Pressure: At 5.5 bar (80 psig) /
Pneumatic signal as required by the actuator, up to Temperature: 70F
full supply pressure. Capacity: 31.1 m3/hr (1100 cfh)
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig) Failure Modes
Action: Double, Single direct, and Single reverse
Refer to figure 4-1.
Declaration of SEP
Independent Linearity(2,4)
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph ±0.5% of output span
-continued-

May 2005 4-1


DVC6000 Series
Table 4-1. Specifications (continued)

Electromagnetic Interference (EMI) Connections


Tested per IEC 61326-1 (Edition 1.1). Meets Supply Pressure: 1/4-inch NPT female and
emission levels for Class A equipment (industrial integral pad for mounting 67CFR regulator
locations) and Class B equipment (domestic Output Pressure: 1/4-inch NPT female
locations). Meets immunity requirements for Tubing: 3/8-inch metal, recommended
industrial locations (Table A.1 in the IEC Vent (pipe-away): 3/8-inch NPT female
specification document). Immunity performance is Electrical: 1/2-inch NPT female conduit connection
shown in table 4-2. optional—M20 female conduit connection, spring
clamp terminal connection(7)
Operating Ambient Temperature Limits(5)
-40 to 80C (-40 to 176F) for most approved Stem Travel
valve-mounted instruments DVC6010, DVC6015: 0 to 102 mm (4-inches)
4 -40 to 125C (-40 to 257F) for remote-mounted
feedback unit.
maximum travel span
0 to 9.5 mm (0.375 inches) minimum travel span
-52 to 80C (-62 to 176F) for valve-mounted DVC6020, DVC6025: 0 to 606 mm (23.875 inches)
instruments utilizing the Extreme Temperature maximum travel span
option (fluorosilicone elastomers)

See the Hazardous Area Classification bulletins for Shaft Rotation (DVC6020, DVC6025, DVC6030, and
specific ambient temperature limits of units DVC6035)
approved for operation in hazardous areas. 0 to 50 degrees minimum
0 to 90 degrees maximum
Electrical Classification
Hazardous Area: Mounting
Explosion proof, Division 2, Dust-Ignition Designed for direct actuator mounting or remote
proof, Intrinsically Safe pipestand or wall mounting. Mounting the
instrument vertically, with the vent at the bottom of
Explosion proof, Non-incendive,
the assembly, or horizontally, with the vent pointing
Dust-Ignition proof, Intrinsically Safe
APPROVED
down, is recommended to allow drainage of
ATEX Flameproof, Type n, Intrinsically Safe moisture that may be introduced via the instrument
IECEx Flameproof, Type n, Intrinsically Safe air supply.
Electrical Housing: NEMA 4X, CSA Type 4X, Weight
IEC 60529 IP66
Valve-Mounted Instruments
Refer to tables 4-3 and 4-4, and figures 5-1, 5-2,
Aluminum: 3.5 kg (7.7 lbs)
5-3, 5-4, 5-5, 5-6, 5-7, and 5-8 for specific approval
Stainless Steel: 7.7 kg (17 lbs)
information, and Hazardous Area Classification
Bulletins 9.2:001 series and 9.2:002 for additional Remote-Mounted Instruments
information. Pollution Degree 2, Overvoltage DVC6005 Base Unit: 4.1 kg (9 lbs)
Category III per ANSI/ISA-82.02.01 (IEC 61010-1 DVC6015 Feedback Unit: 1.3 kg (2.9 lbs)
Mod). DVC6025 Feedback Unit: 1.4 kg (3.1 lbs)
DVC6035 Feedback Unit: 0.9 kg (2.0 lbs)
IEC 61010 Compliance Requirements
(Valve-Mounted Instruments only) Options
Power Source: The loop current must be derived  Supply and output pressure gauges or  Tire
from a Separated Extra-Low Voltage (SELV) power valves,  Integral mounted filter regulator, 
source. Stainless steel housing, module base and terminal
Environmental Conditions: Installation Category I box (valve-mounted instruments only)
1. 3-conductor shielded cable, 22 AWG minimum wire size, is recommended for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection
and actuator has been tested to 15 meters (50 feet) maximum without performance degradation.
2. Defined in ISA Standard S51.1.
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Not applicable for Type DVC6020 digital valve controllers in long-stroke applications.
5. The pressure/temperature limits in this quick start guide and any applicable code or standard should not be exceeded.
6. The low bleed relay is offered as standard relay for DVC6000 ESD tier, used for On/Off applications
7. ATEX/IEC approvals only.

4-2 May 2005


Specifications and Related Documents
Table 4-2. Immunity Performance
Performance Criteria(1)
Port Phenomenon Basic Standard Point-to-Point
Multi-drop Mode
Mode
Electrostatic discharge (ESD) IEC 61000-4-2 A(2) A
Enclosure Radiated EM field IEC 61000-4-3 A A
Rated power frequency magnetic field IEC 61000-4-8 A A
Burst IEC 61000-4-4 A(2) A
I/O signal/control Surge IEC 61000-4-5 A(2) A
Conducted RF IEC 61000-4-6 A A
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
2. Excluding auxiliary switch function, which meets Performance Criteria B.

Table 4-3. Hazardous Area Classifications for North America


CERTIFICATION
BODY
CERTIFICATION OBTAINED ENTITY RATING
TEMPERATURE CODE ENCLOSURE
RATING
4
(Intrinsic Safety) Vmax = 30 Vdc T5(Tamb v 80C) 4X
Class/Division Imax = 226 mA
Class I,II,III Division 1 GP A,B,C,D,E,F,G Ci = 5 nF
per drawing 29B3428 Li = 0.55 mH
(Explosion Proof) T6(Tamb v 80C) 4X
CSA Class/Division - - -
Class I, Division 1 GP B,C,D
Class I Division 2 GP A,B,C,D T6(Tamb v 80C) 4X
Class II Division 1 GP E,F,G - - -
Class III Division 1
(Intrinsic Safety) Vmax = 30 Vdc T5(Tamb v 80C) 4X
Class/Division Imax = 226 mA
Class I,II,III Division 1 GP A,B,C,D,E,F,G Pi = 1.4 W
per drawing 29B3427 Ci = 5 nF
Li = 0.55 mH
FM (Explosion Proof) T6(Tamb v 80C) 4X
Class/Division - - -
Class I, Division 1 GP B,C,D
Class I Division 2 GP A,B,C,D T6(Tamb v 80C) 4X
Class II,III Division 1 GP E,F,G - - -
Class II,III Division 2 GP F,G

May 2005 4-3


DVC6000 Series
Table 4-4. Hazardous Area Classifications for Europe and Asia-Pacific
CERTIFICATE ENCLOSURE
CERTIFICATION OBTAINED ENTITY RATING TEMPERATURE CODE
(AGENCY) RATING
(Intrinsic Safety) Ui = 30 Vdc T5(Tamb v 80C) IP66
II 1 G D T6 (Tamb v75C)
Ii = 226 mA
Gas
Pi = 1.4 W
EEx ia IIC T5/T6
Dust
Ci = 5 nF
T85C (Tamb v 80C) Li = 0.55 mH
(Flameproof) T5(Tamb v 85C) IP66
II 2 G D T6 (Tamb v 75C)
ATEX Gas
- - -
(LCIE) EEx d IIB+H2 T5/T6
Dust
T90C (Tamb v 85C)
(Type n) T5(Tamb v 80C) IP66
II 3 G D T6 (Tamb v 75C)
Gas
4
- - -
EEx nCL IIC T5/T6
Dust
T85C (Tamb v 80C)
(Intrinsic Safety) Ui = 30 Vdc T5(Tamb v 80C) IP66
Gas Ii = 226 mA T6 (Tamb v 75C)
Ex ia IIC T5/T6 Pi = 1.4 W
Ci = 5 nF
Li = 0.55 mH
IECEx
(Flameproof) T5(Tamb v 80C) IP66
(CSA) Gas - - - T6 (Tamb v 75C)
Ex d IIB+H2 T5/T6
(Type n) IP66
T5(Tamb v 80C)
Gas - - -
T6 (Tamb v 75C)
Ex nC IIC T5/T6

4-4 May 2005


Specifications and Related Documents

LOSS OF
LOSS OF POWER
A PNEUMATIC SUPPLY
Instrument goes to zero Failure direction per
Single Acting Direct (Relay A) air output at port A. actuator fail mode.
Instrument goes to full supply
Double Acting (Relay A) air output at port B. A goes to Failure direction cannot
0 air output. be determined.

Single Acting Reverse (Relay B) Instrument goes to full Failure direction per
supply air output at port B. actuator fail mode.

B
4
Figure 4-1. DVC6000 Digital Valve Controller Failure Modes

Related Documents  Using the HART Tri-Loop HART-to-Analog


Signal Converter with FIELDVUE Instruments
This section lists other documents containing (PS Sheet 62.1:FIELDVUE(J))
information related to the DVC6000 Series digital
valve controllers. These documents include:  Using the FIELDVUE Instruments with the
Smart HART Loop Interface and Monitor (HIM)
 FIELDVUE  DVC6000 Series Digital Valve (PS Sheet 62.1:FIELDVUE(L))
Controllers Instruction Manual, Form 5647
 FIELDVUE  HF300 Series HART Filters
 FIELDVUE  DVC6000 Series Digital Valve Instruction Manual - Form 5715
Controller (Bulletin 62.1:DVC6000)
 Type 2530H1 HART Interchange Multiplexer
 FIELDVUE  DVC6000 Series Digital Valve Instruction Manual - Form 5407
Controllers for Safety Instrumented System (SIS) All these documents are available from your Fisher
Solutions (Bulletin 62.1:DVC6000(SIS)) sales office. Also please visit our website at
www.FIELDVUE.com.
 FIELDVUE  Instrument Split Ranging (PS Sheet
62.1:FIELDVUE(C))
Educational Services
 FIELDVUE  Instrument Status Flags on
Rosemount RS3 DCS (PS Sheet 62.1:FIELDVUE(D)) For information on available courses for the DVC6000
Series digital valve controller, as well as a variety of
other products, contact:
 Proportional Control Loop with FIELDVUE
Instruments (PS Sheet 62.1:FIELDVUE(E)) Emerson Process Management
Educational Services, Registration
P.O. Box 190; 301 S. 1st Ave.
 Using Loop Tuners with FIELDVUE Instruments Marshalltown, IA 50158-2823
(PS Sheet 62.1:FIELDVUE(F)) Phone: 800-338-8158 or
Phone: 641-754-3771
 Audio Monitor for HART Communications FAX: 641-754-3431
(PS Sheet 62.1:FIELDVUE(G)) e-mail: education@emersonprocess.com

May 2005 4-5


DVC6000 Series

4-6 May 2005


Loop Schematics and Nameplates
5-5 5

This section includes loop schematics required for


wiring of intrinsically safe installations. If you have any
questions, contact your Fisher sales office.

29B3428-B / DOC

Figure 5-1. CSA Schematic for Type DVC6000 and Type DVC6000S

TYPES DVC6010, DVC6020, DVC6030, DVC6010S, DVC6020S, DVC6030S

Figure 5-2. CSA Nameplate

May 2005 5-1


DVC6000 Series

29B3427-A / DOC

Figure 5-3. FM Schematic for Type DVC6000 and Type DVC6000S

TYPES DVC6010, DVC6020, DVC6030, DVC6010S, DVC6020S, DVC6030S


Figure 5-4. FM Nameplate

SPECIAL CONDITIONS FOR SAFE USE:


1. THE APPARATUS CAN ONLY BE CONNECTED TO AN INTRINSICALLY SAFE CERTIFIED EQUIPMENT AND THIS
COMBINATION MUST BE COMPATIBLE AS REGARDS THE INTRINSICALLY SAFE RULES.
2. THE ELECTRICAL PARAMETERS OF THIS EQUIPMENT MUST NOT EXCEED ANY FOLLOWING VALUES:
UOv 30 Vdc; IO v226 mA; POv 1.4 W

3. OPERATING AMBIENT TEMPERATURE: - 40_C TO + 80_C


TYPES DVC6010, DVC6020, DVC6030, DVC6010S, DVC6020S, DVC6030S
Figure 5-5. ATEX (LCIE) Nameplate; Intrinsically Safe, Dust-Tight

5-2 May 2005


Loop Schematics and Nameplates

NOTE: SPECIAL CONDITIONS FOR SAFE USE:


OPERATING AMBIENT TEMPERATURE: - 52_C or - 40_C TO +85_C

TYPES DVC6010, DVC6020, DVC6030, DVC6010S, DVC6020S, DVC6030S

Figure 5-6. ATEX (LCIE) Nameplate; Flameproof, Dust-Tight

NOTE: SPECIAL CONDITIONS FOR SAFE USE:


OPERATING AMBIENT TEMPERATURE: - 52_C or - 40_C TO +80_C

TYPES DVC6010, DVC6020, DVC6030, DVC6010S, DVC6020S, DVC6030S

Figure 5-7. ATEX (LCIE) Nameplate; Type n, Dust-Tight

CONDITIONS OF CERTIFICATION:
Ex ia / Ex d / Ex n
1. WARNING: ELECTROSTATIC CHARGE HAZARD. DO NOT RUB OR CLEAN
WITH SOLVENTS. TO DO SO COULD RESULT IN AN EXPLOSION.
Ex d / Ex n
2. DO NOT OPEN WHILE ENERGIZED.

TYPES DVC6010, DVC6020, DVC6030, DVC6010S, DVC6020S, DVC6030S

Figure 5-8. IECEx Nameplate; Intrinsically Safe, Type n, Flameproof

May 2005 5-3


DVC6000 Series

W8115

TYPE DVC6020 DIGITAL VALVE


CONTROLLER MOUNTED ON A
ROTARY CONTROL VALVE / ACTUATOR

TYPE DVC6010 DIGITAL VALVE CONTROLLER


MOUNTED ON A SLIDING STEM
CONTROL VALVE / ACTUATOR

W8373

TYPE DVC6005 BASE UNIT AND DVC6025 FEEDBACK UNIT


MOUNTED ON A ROTARY CONTROL VALVE / ACTUATOR

FIELDVUE, ValveLink, PlantWeb and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process
Management business division of Emerson Electric Co. Emerson and the Emerson logo are trademarks and service marks of Emerson Electric
Co. Tri-Loop and AMS Suite are marks owned by one of the Emerson Process Management group of companies. HART is a mark owned by the
HART Communications Foundation. All other marks are the property of their respective owners. This product may be covered under one or more
of the following patents (5,163, 463; 5,265,637; 5,381,817; 5,434,774; 5,439,021; 5,451,923; 5,502,999; 5,532,925; 5,533,544; 5,549,137;
5,558,115; 5,573,032; 5,687,098) or under pending patents.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and
maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.
Emerson Process Management
Fisher
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com
5-4

Fisher Controls International LLC 2002, 2005; All Rights Reserved Printed in USA
May 2005
MAINTENANCE MANUAL
LPS ACTUATOR

- INDEX -

I. DESCRIPTION OF THE ACTUATOR

II. INSTRUCTION TO ASSEMBLE THE ACTUATOR ONTO THE VALVE

III. START-UP

IV. REPLACEMENT OF CYLINDER SEALS

V. STORAGE

VI. PERIODIC MAINTENANCE

1/ 9
LPS ACTUATOR

I. DESCRIPTION OF THE ACTUATOR

- General description

The LP/S series are pneumatic single acting actuators, specifically designed to operate gate or
globe valve by means of coil springs.
These actuators can be fitted with an emergency manual override suitable to operate the
actuator in the event of fluid supply failure. This device can be mechanical screw or bevel gear
type, operated by means of a side or top hand wheel.
It also available for hydraulic type, with a cylinderical operated by the hand-pump.

- The main components of these units are the following:

1. The pneumatic cylinder made of “STPG”-carbon steel pipe for pressure vessel, whose walls
are fully chromium plated, in order to reduce roughness of their surface to a minimum valve
and to provide highest protection against corrosion.
The relevant piston is made of carbon steel and is sealed by o-rings and guide sliding ring in
PTFE and BRONZE.
The piston rod is chromium plated in order to prevent corrosion and to minimize the sliding
friction on the dynamic seals.

2. Die springs

3. A standard coupling in stainless mounted between the piston rod and the valve stem.

4. Mechanical visual indicator can be supplied

- The linear movement of the pneumatic cylinder operate the valve to the closing or in opening
position, by means of air or spring.
It can be operated by air to open / by spring to close or by air to close / by spring to open.

2/ 9
LPS ACTUATOR

II. INSTRUCTION TO ASSEMBLE ACTUATOR ONTO THE VALVE

The assembling position of the actuator must comply with costomer’st requirements on the each
of valves.

In order to assemble the actuator onto the valve, proceed as follows:

1. Check that the mounting dimensions of the valve flange and stem, or the relevant extension,
meet the actuator mounting dimensions.

2. Loosen the fixing screws of the valve coupling and actuator coupling.

3. Fasten the tie-rods coupling the valve and actuator on the Lw. flange.

4. Arrange the valve in the open or closed position (depending on the actuator actual position).

5. Screw the coupling adaptor after putting the valve coupling in the valve stem.

6. Lift the actuator by connecting hooks, chains or ropes suitable for the weight, to the support
points of the actuator.
If possible, place on the valve stem in the vertical position, in order to make to assembly
easier: in this case lift the actuator keeping its flange in the horizontal position.

7. Lower the actuator onto the valve mounting flange and fasten the tie-rods of actuator to the
flange by screwing the nuts.

8. Reassemble the actuator coupling, valve coupling and coupling adaptor by screwing the bolts.

3/ 9
LPS ACTUATOR

III. START-UP

- Arrangement for start-up

1. Before connecting the actuator to the pneumatic supply line, check that pipes and fitting are
according to the applicable plant specifications, in order to guarantee the required air flow for
the actuator operation and to avoid that the supply pressure drops below the minimum
allowable value.

2. Clean the inside of the pipes used for connection by washing them with suitable detergent
and by blowing air into them.
Take every precaution to remove any solid or liquid foreign matter from the pipe work to the
actuator, so as to avoid possible damages to the actuator itself or loss of performance.

3. Fasten the piping in a right way, in order not to cause loosening of threaded connections, in
case that the system undergoes strong vibrations.

4. After the completion of the pneumatic connections, operate the actuator and check that it
works correctly.
Also check that its operating times are in accordance with those specified in the test
certificate and that there are not leakage in the pneumatic connections.

- During the start-up of the actuator, it is necessary to check that;

1. The pressure of the fluid supply, as well as its quality (filtering degree, dehydration) are as
prescribed,

2. The feed voltage values of the electric components (solenoid valves coils, micro-switches,
pressure switches etc., if applicable) are as prescribed,

3. The actuator controls, such as remote control, local control, emergency control etc. (if
applicable), are properly working,

4. The required remote signals (such as valve position, fluid supply pressure, etc.) are correct,

5. The setting of the components of the actuator control unit is according to the requirements of

4/ 9
LPS ACTUATOR

the plant,

6. The pneumatic connections do not show any leakage. If necessary, tighten the nuts of the
pipe fittings,

7. The painted parts have not been damaged during the transport, assembling or storage
operations, After having removed rust, repair the damaged parts by following the applicable
painting specifications.

5/ 9
LPS ACTUATOR

IV. REPLACEMENT OF CYLINDER SEALS

When the cylinder seals must be replaced, because of a leakage or of a preventive


scheduled maintenance, proceed as described here below.

1. Arrange the valve in the closed position.

2. Disconnect the all of pneumatic and electric connection from the actuator.

3. Loosen the fixing screws of the valve coupling and actuator coupling, and disassemble the
valve coupling, actuator coupling and coupling adaptor.

4. Loosen the nuts from the tie-rods and remove the actuator from the valve.

5. Must be set the actuator on the press assembling machine or suitable jacketing device to
eliminate the force by compressed springs.

6. Unscrew the nut on the Up. flange.

7. Remove the Up. flange.

8. Remove the springs and spring guide.

9. Remove the cylinder.

10. Unscrew the fixing bolts and then remove the piston stopper from the piston.

11. Unscrew the set screws from the piston.

12. Disassemble the piston and rod.

13. Unscrew the bolt from the packing adaptor inserted in Lw. flange.

14. Take out the packing adaptor.

15. Remove the all of o-rings and packing and carefully clean the relative grooves.

6/ 9
LPS ACTUATOR

16. Replace the all of o-rings and packing after greasing, and lubricate slightly.

17. Proceed with reassembling operation by taking care not to damage the seals.

18. After reassembling, carry out a few operations with the actuator to check that its movement
is regular and that there is no leakage through the seals.

7/ 9
LPS ACTUATOR

V. STORAGE

The actuators leave the SEIL-SERES company in excellent finish and working conditions
which are guaranteed by the inspection certificate issued for each single actuator.

- In order to keep the actuators in good conditions until they are assembled on the plant, it is
recommended to follow the rules listed here below, during the storage period:

a) Check that the plugs are properly assembled on the pneumatic and electric
connections, in order to close and to protect them against the entry of foreign matters
and water during transport and storage.

b) The actuators, which are not yet assembled onto the valves, must be placed onto a
wooden pallet, in order to prevent any damage to the valve coupling flange.

- Long-term storage

In the event of a long-term storage, the following rules are also recommended:

- Protect the coupling parts (adapter and coupling joint, flange, etc.) with grease or
protective oil.

- Keep the actuators in a dry place or provide some means of protection against the
direct action of weather agents.

- If possible, we also recommended operating periodically the actuators with filtered,


dehydrated and lubricated air. After this operation, all the threaded connection must be
carefully closed.

8/ 9
LPS ACTUATOR

VI. PERIODIC MAINTENANCE

As the actuators have been designed to work for long periods in the most severe conditions,
they do not need any specific maintenance.
However, we recommend periodically checking that:

- The actuators operate the valve correctly and with the required operating time.
Carry out some opening and closing operations with all the existing controls (such as
remote control – local control – emergency control), if the working conditions of the plant
allow to do this and if the actuators is not frequently operated,

- the signals to the control board are correct,

- the fluid supply pressure value is within the required range.

- the external components of the actuator are in good conditions,


This control can be carried out visually.

- The hydraulic / pneumatic connections do not show any leakage.


If necessary, tighten the nuts of the pipe fittings,

- the painting work of the actuator has not been damaged, because it could happen that
some areas need a touch-up according to the applicable painting specifications.

9/ 9

You might also like