Professional Documents
Culture Documents
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface
Safety Information
This manual is not a complete index of all safety measures required for operation of the
equipment (module or device). However, it comprises important information that must be followed
for personal safety, as well as to avoid material damage. Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates that property damage can result if the measures specified are
not taken.
device. Contact with hazardous voltages and currents inside this device
can cause electrical shock resulting in injury or death.
Contact with instrument terminals can cause electrical shock that can
result in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage
can result otherwise.
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
Symbols
AND Gate
OR Gate
Comparator
BI xxx
Signal input
SIG xxx
Setting input
SET xxx
Enable input
EN xxx
Timer
Timer
t
t
Timer
10ms 2ms
Timer
[Tset1] 0ms
Timer
0ms [Tset2]
Timer
[Tset1] [Tset2]
Generator
Transformer
Reactor
Motor
Capacitor
Busbar
Circuit breaker
52
Current transformer
3CT
*
Voltage transformer
3VT
Disconnector
Earth
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This manual is a comprehensive work covering the theories of protection, control, supervision,
measurement, etc. and the structure & technical data of relevant hardware. Read the sections that
pertain to your application to gain valuable information about using the PCS-978S. To concentrate
on the target sections of this manual as your job needs and responsibilities dictate. An overview of
each manual section and section topics follows.
1 Introduction
Introduces PCS-978S features, summarizes functions and applications of the device.
2 Technical Data
Lists device specifications, type tests, and ratings.
3 Protection Functions
Describes the function of various protection elements, gives detailed specifics on protection
scheme logic, provides the relevant logic diagrams.
4 Control Functions
Describes the logic for the control of disconnectors and circuit breakers.
5 Measurement
Provides information on viewing fundamental and rms metering quantities for voltages and
currents, as well as power and energy metering data.
6 Supervision
Describes self-supervision technique to help diagnose potential difficulties should these occur and
includes the list of status notification messages. Provides a troubleshooting chart for common
device operation problems.
7 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating
with the device, switching active setting group, checking relay status, reading event reports and
SER (Sequential Events Recorder) records.
8 Hardware
Describes the hardware of the PCS series device family and provides general information on the
product structure and the modules technical data.
9 Settings
Provides a list of all settings and their ranges, unit, steps, defaults. The organization of the
settings is similar to the settings organization in the device and in the PCS-Studio software.
Appendix A Glossary
Describes the abbreviations adopted in this manual.
Corresponding Version
Date Description of change
Document Software
1 Introduction
1
Table of Contents
List of Figures
1.1 Application
PCS-978S can be applied for a two-winding transformer, three-winding transformer or
auto-transformer in any voltage level. PCS-978S provides full transformer protections which are
1
configurable by user. Ancillary functions of fault diagnostic, disturbance records, event records
and communication function are integrated in the device.
HVS
3 VT
52
*
1
3 CT
51P 64
87T 49 87W 50BF 67G 67P
Alm REF
MVS * 50/
51P
* 1 CT * *
52 50/
67Q
51G
3 CT 1 CT
1 CT *
50/
51Q
1 CT
3 VT
3 CT
*
52
3 VT
LVS
1.2 Functions
1. Protection Functions
2. Control Functions
Switchgear control
Direct control
Trip statistics
U, I, P, Q, Cos, f
Max.15th harmonics
Self diagnostic
Powerful faults recording (max. buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024
supervision events, 256 control logs and 1024 device logs.
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
5. Communication Functions
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 ed1 & ed2, IEC 61850-8-1 (MMS
GOOSE), IEC 62439 Parallel Redundancy Protocol, IEC 62439 HSR Ring Redundancy
Protocol
6. User Interfaces
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment
Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
Configuration tool—PCS-Studio
7. Additional Functions
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
Cyber security
NERC CIP
IEC 62351
IEC 62443
IEEE 1686
1.3 Features
High degree of functional integration and flexible configuration modes, transformer main
protection and back-up protection can be integrated in one device, or be separated in two
devices.
The tripping output contacts can be configured by tripping matrix, which is flexible, convenient
and suitable to any mode of tripping.
The relay supports at most 6 branches differential protection. The transformer angle can be
adjusted flexibly, and any transformer angle compensation mode is supported and any side
can be chosen as the reference side of differential protection.
Reliable differential CT circuit failure supervision. The relay can detect multi-phase CT
wire-break, multi-side CT wire-break, short-circuit, and other complex situation. The
corresponding logic setting can be used to select blocking differential protection or not, in case
of CT circuit failure.
Multiple inrush current blocking options are provided. Self-adaptive inrush current blocking
criterion can ensure the relay fast operation for transformer energized on to a slight fault,
meanwhile it will avoid the unwanted operation in the case of the energization inrush current
caused by energizing transformer with no load, the recovery inrush current caused by cutting
1 off the transformer external fault, and the sympathetic inrush current.
Biased DPFC differential protection is regardless of load current and is sensitive to small
internal fault current within the transformer. Its anti CT saturation performance is also strong.
2 Technical Data
Table of Contents
Linear to 0.05In~40In
Thermal withstand
-continuously 4In
-for 1s 100In
Linear to 1V~300V
100Vac/110Vac/115Vac/120Vac
2 250Vac
Burden
Tripping/signaling contact
0.5A@48Vdc
0.35A@110Vdc
0.20A@220Vdc
0.15A@250Vdc
0.5A@48Vdc
0.35A@110Vdc
Cyclic Capacity (2.5 cycle/second,
0.30A@125Vdc
L/R=40ms)
0.20A@220Vdc
2 0.15A@250Vdc
30A@3s
Short duration current
50A@1s
10A@48V
10A@110V
Breaking capacity (L/R=40ms)
10A@125V
10A@250V
10A@48V L/R=40ms
Cyclic Capacity (4 cycles in 1 second,
10A@110V L/R=40ms
followed by 2 minutes idle for thermal
10A@125V L/R=40ms
dissipation)
10A@250V L/R=20ms
30A@3s
Short duration current
50A@1s
Device structure Plug-in modular type @ rear side, integrated front plate
Protection Class 2
Standard IEC 60529-2013
Pollution degree Ⅱ
Altitude <3000m
Max. capacity 32
Connector type LC
Type RS-232
Isolation 500Vdc
Overvoltage category Ⅲ
IEC 60255-26:2013
Frequency sweep
Radio frequency interference tests
Radiated amplitude-modulated
Spot frequency
Radiated amplitude-modulated
IEC 60255-26:2013
2 Fast transient disturbance tests Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns
IEC 60255-26:2013
IEC 60255-26:2013
IEC 61000-4-9:2016
Pulse Magnetic Field Immunity
class Ⅴ, 6.4/16μs, 1000A/m for 3s
IEC 60255-26:2013
Conducted emission 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average
IEC 60255-26:2013
peak @3m
Above 1GHz
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m)
peak @3m
IEC 60255-26:2013
2
Up to 200ms for dips to 40% of rated voltage without
Voltage dips
reset
Auxiliary power supply performance
50ms for interruption without rebooting without
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
CMMI L5
Type Resolution
2.8 Terminals
2.8.1 Ring Ferrule
2
AC current Screw terminals, 1.5~4mm lead M4 1.6~1.8 N·m
2
AC voltage Screw terminals, 0.8~4mm lead M4 1.6~1.8 N·m
2
Contact I/O Screw terminals, 0.8~4mm lead M4 0.8~1.4 N·m
p.u.——per unit value of settings and currents for current differential protection
Id——differential current
Operating time (without time delay, without 50Hz: ≤30ms (3I0d>2 times current setting)
Tolerance of time setting ≤1% of setting +30ms (3I0d>2 times current setting)
Reset ratio 1
Tolerance of operating time ≤1%×setting or 35ms (at 1.1 times voltage setting)
≤0.01Hz
2
Tolerance of pickup time ≤70ms
3 Protection Functions
Table of Contents
List of Figures
Figure 3.6-2 Operation characteristic of sensitive biased differential element ............... 3-19
Figure 3.6-3 Operation characteristic of conventional biased differential element ......... 3-20 3
Figure 3.6-4 Operation characteristic of biased/instantaneous differential elements .... 3-21
Figure 3.6-5 Operation characteristic of DPFC biased differential protection ................. 3-24
Figure 3.6-7 Logic of inrush current blocking current differential protection.................. 3-29
Figure 3.6-12 Logic diagram of DPFC biased differential element .................................... 3-37
Figure 3.7-1 Application for two-windings transformer with one CB at one side ............ 3-40
Figure 3.7-2 Application for two-windings transformer with two CBs at one side .......... 3-40
Figure 3.7-8 Logic of enabling restricted earth fault protection ........................................ 3-48
Figure 3.7-9 Pickup logic of restricted earth fault protection ............................................ 3-48
Figure 3.7-10 Logic diagram of restricted earth fault protection ....................................... 3-48
Figure 3.8-2 Winding differential protection applied to stub differential protection ....... 3-50
Figure 3.10-5 Logic of forward and reverse direction element .......................................... 3-70
Figure 3.10-7 Definite-time operating curve of phase overcurrent protection ................. 3-73
Figure 3.10-9 Definite-time dropout characteristics of phase overcurrent protection .... 3-75
Figure 3.10-10 Inverse-time dropout curve of phase overcurrent protection .................. 3-76
Figure 3.11-4 Logic of forward and reverse direction element .......................................... 3-86
Figure 3.11-6 Definite-time operating curve of earth fault protection ............................... 3-88
Figure 3.11-7 Inverse-time operating curve of earth fault protection ................................ 3-89
Figure 3.11-8 Definite-time dropout characteristics of earth fault protection .................. 3-90
Figure 3.11-9 Inverse-time dropout curve of earth fault protection ................................... 3-91
Figure 3.11-10 Inverse-time dropout characteristics of earth fault protection ................. 3-92
Figure 3.11-11 Logic diagram of earth fault overcurrent protection .................................. 3-93
Figure 3.12-4 Logic of forward and reverse direction element .......................................... 3-99
Figure 3.13-2 Logic diagram of enabling thermal overload protection (method 1) ....... 3-114
Figure 3.13-3 Pickup logic of thermal overload protection (method 1) ........................... 3-114
Figure 3.13-4 Logic diagram of thermal overload protection (method 1) ....................... 3-114
Figure 3.14-2 Logic of breaker failure initiating signal abnormality ................................ 3-119
Figure 3.15-3 Definite-time operating curve of phase overvoltage protection ............... 3-124
Figure 3.15-4 Inverse-time operating curve of phase overvoltage protection ............... 3-125
Figure 3.16-3 Definite-time operating curve of residual overvoltage protection ........... 3-132
Figure 3.17-3 Definite-time operating curve of phase undervoltage protection ............ 3-138
3 Figure 3.17-4 Inverse-time operating curve of phase undervoltage protection ............. 3-139
List of Tables
Table 3.5-1 I/O signals of three-phase current summation element .................................... 3-9
Table 3.5-2 I/O signals of three-phase current summation element .................................... 3-9 3
Table 3.6-1 Matrix of phase compensation ........................................................................... 3-14
Three-phase current element is responsible for pre-processing three phase currents and
calculating sequence components, amplitudes and phases of three phase currents, etc. All
calculated information of three-phase current element is used for protection logic calculation.
When three phase currents are engaged in the calculation of transformer differential protection,
restricted earth fault protection or winding differential protection, CT circuit failure supervision of
each protection is carried out in the corresponding protection element, which can refer to
corresponding sections for details.
When any phase current is greater than 0.04In, inputted current signals are decided valid and the
valid signal is outputted for programmable logic application.
TCUR3P
x.in_ia x.I3P
x.in_ib x.Ia_Sec
x.in_ic x.Ib_Sec
x.in_ia_smv x.Ic_Sec
x.in_ib_smv x.I1_Sec
3 x.in_ic_smv x.I2_Sec
x.3I0_Cal_Sec
x.Ang(Ia-Ib)
x.Ang(Ib-Ic)
x.Ang(Ic-Ia)
x.Ang(Ia)
x.Ang(Ib)
x.Ang(Ic)
x.Ang(3I0_Cal)
x.Alm_CTS
x.Flg_OnLoad
3.1.4 Settings
Table 3.1-3 Settings of three-phase current element
Three-phase voltage element is responsible for pre-processing three phase voltages and
calculating sequence components, amplitudes and phases of three phase voltages, etc. All
calculated information of three-phase voltage element is used for the protection logic calculation.
VT circuit failure supervision of three-phase voltage is carried out by the special VTS element,
TVOL3P
x.in_ua x.U3P
x.in_ub x.Ua_Sec
x.in_uc x.Ub_Sec
x.in_ua_smv x.Uc_Sec
3 x.in_ub_smv x.Uab_Sec
x.in_uc_smv x.Ubc_Sec
x.BI_En_VT x.Uca_Sec
x.U1_Sec
x.U2_Sec
x.3U0_Cal_Sec
x.Ang(Ua-Ub)
x.Ang(Ub-Uc)
x.Ang(Uc-Ua)
x.Ang(Ua)
x.Ang(Ub)
x.Ang(Uc)
x.Ang(3U0_Cal)
X.VTS.Alm
3.2.4 Settings
Table 3.2-3 Settings of three-phase voltage element
TCUR1P
3 x.in_ip x.I1P
x.in_ip_smv x.3I0_Ext_Sec
x.Ang(3I0_Ext)
x.Flg_OnLoad
3.3.4 Settings
Table 3.3-3 Settings of single-phase current element
TVOL1P
x.in_up x.U1P
x.in_up_smv x.U_Sec
X.BI_En_VT x.Ang(U)
3.4.4 Settings
Table 3.4-3 Settings of single-phase voltage element
Three-phase current summation element is responsible for calculating the sum of multiple current
inputs in one side of transformer. All calculated information of three-phase current summation
3 element is used for the protection logic calculation.
When any phase current is greater than 0.04In, inputted current signals are decided valid and the
valid signal is outputted for programmable logic application.
TCUR3P_3SD
x.in_i3p1 x.I3P
x.in_i3p2 x.Ia_Sec
x.in_i3p3 x.Ib_Sec
x.Ic_Sec
x.I1_Sec
x.I2_Sec 3
x.3I0_Cal_Sec
x.Ang(Ia-Ib)
x.Ang(Ib-Ic)
x.Ang(Ic-Ia)
x.Ang(Ia)
x.Ang(Ib)
x.Ang(Ic)
x.Ang(3I0_Cal)
x.Flg_OnLoad
The fault detector can initiate biased differential element, and its operation equation is as follows.
Where:
The fault detector can initiate instantaneous differential element, and its operation equation is as
follows.
Where:
The fault detector can initiate DPFC biased differential element, and its operation equation is as
follows.
I d 1.25 I dt I dth
Equation 3.6-3
I d I 1 I 2 ... I m
3
Where:
I dt is the floating threshold varied with the change of load current from time to time. The change
of load current is small and gradually under normal or even power swing condition, the adaptive
floating threshold ( I dt ) is higher than the change of current under these conditions and hence the
I 1 , I 2 , …, I m are DPFC current of each side of transformer representatively.
Regardless of direction of power flow and very sensitive, this fault detector is used to guard DPFC
biased differential protection. The setting is fixed in factory and thus site setting is not required.
During the normal operation, the magnitudes of secondary current of each side of transformer are
different due to the mismatch between the CT ratios and the power transformer ratio. The current
value difference between each side shall be eliminated before calculation for current differential
protection by amplitude compensation.
Sn
I 1bBrm Equation 3.6-4
3U 1nBrm
Where:
U1nBrm is rated primary voltage of side m (i.e., the settings [HVS.U1n_Tr], [MVS.U1n_Tr] or
[LVS.U1n_Tr]).
I 1bBrm
I 2bBrm Equation 3.6-5
CTBrm
Where:
For all differential protections, the secondary currents of each side must follow below criterion.
I 2bBr1 I 2bBr2 I
Max( , ,..., 2bBrm )
I 2nBr1 I 2nBr2 I 2nBrm
128 Equation 3.6-6
I 2bBr1 I 2bBr2 I 2bBrm
Min( , ,..., )
I 2nBr1 I 2nBr2 I 2nBrm
When selecting CT, the ratio between maximum value and minimum value
should be considered. It is recommended that the ratio is smaller than 16.
Theoretically, the ratio is preferred to be as small as it can be.
For DPFC biased differential element, the secondary currents of each side must follow Equation
3.6-7 in addition to Equation 3.6-6. Otherwise, alarm signals [ProtBrd.Fail_Settings] and
[FDBrd.Fail_Settings] are issued and the device will be blocked at the same time unless DPFC
biased differential element is disabled.
I 2bBr1 I 2bBr2 I
Max( , ,..., 2bBrm ) 0.4
I 2nBr1 I 2nBr2 I 2nBrm
Equation 3.6-7
I I I
Min( 2bBr1 , 2bBr2 ,..., 2bBrm ) 0.1
I 2nBr1 I 2nBr2 I 2nBrm
Where:
False differential current is caused by phase shift between the power transformer primary current
and secondary current for delta/wye, so phases of each side secondary current must be
compensated by this phase compensation. Δ→Y and Y→Δ transfer methods by settings can be
selected to adjust phase angle of secondary current on each side of the transformer, and Δ→Y
transfer method is recommended. Zero-sequence current is always eliminated both at Y and Δ
windings by adopting Δ→Y method.
The wiring connection of HV, MV and LV sides may be different, so it is needed to compensate
phase of each side current of transformer for calculation of current differential protection. There
are two transforming methods for phase compensation: Δ→Y and Y→Δ, and different
transforming methods will result in the difference.
2. [Clk_PhComp]: the target o'clock each side current will be shifted to for phase compensation.
For example:
The vector group of a transformer is Y0/Δ11 and the target o'clock ([Clk_PhComp]) is set to LV
1. For HV side, with reference to the set target o'clock, the o'clock of HV side is 1 (i.e. wiring
o'clock 12-target o'clock 11) clock, so the matrix of relative o'clock 1 is adopted to
compensate HV side current.
2. For LV side, with reference to the set target o'clock, the o'clock of LV side is 0 (i.e. wiring
o'clock 11- target o'clock 11), so the matrix of relative o'clock 0 is adopted to compensate LV
side current.
If an earthing transformer is connected outside the protection zone of differential protection, the
setting [HVS.En_I0Elim] (or [LVS.En_I0Elim]) could be disabled, i.e. set to 0.
3 If an earthing transformer is connected within the protection zone of differential protection, then
zero-sequence current must be eliminated and otherwise differential protection may operate
unexpectedly during an external fault. Therefore the setting [HVS.En_I0Elim] (or [LVS.En_I0Elim])
must be enabled, i.e., set to 1.
1 0 0 2 - 1 - 1
0 0 1 0 1
- 1 2 - 1
(No phase shit) 3
0 0 1 - 1 - 1 2
1 -1 0 1 -1 0
1
0 1 - 1
1
0 1 - 1
1
(Shift 30°leading) 3 3
- 1 0 1 - 1 0 1
0 -1 0 1 -2 1
2 0 0 - 1 1
1 1 - 2
(shift 60°leading) 3
- 1 0 0 - 2 1 1
0 -1 1 0 -1 1
1
1 0 - 1
1
1 0 - 1
3
(Shit 90°leading) 3 3
- 1 1 0 - 1 1 0
0 0 1 - 1 - 1 2
4 1 0 0 1
2 - 1 - 1
(Shit 120°leading) 3
0 1 0 - 1 2 - 1
- 1 0 1 - 1 0 1
1
1 - 1 0
1
1 - 1 0
5
(Shift 150°leading) 3 3
0 1 - 1 0 1 - 1
- 1 0 0 - 2 1 1
6 0 -1 0 1
1 - 2 1
(Shift 180°leading) 3
0 0 - 1 1 1 - 2
- 1 1 0 - 1 1 0
1
0 - 1 1
1
0 - 1 1
7
(Shift 150°lagging) 3 3
1 0 - 1 1 0 - 1
0 1 0 - 1 2 - 1
8 0 0 1 1
- 1 - 1 2
(Shift 120°lagging)
1 0 0
3
2 - 1 - 1 3
0 1 - 1 0 1 - 1
1
- 1 0 1
1
- 1 0 1
S9
(Shift 90°lagging) 3 3
1 - 1 0 1 - 1 0
0 0 - 1 1 1 - 2
10 - 1 0 0 1
- 2 1 1
(Shift 60°lagging) 3
0 - 1 0 1 - 2 1
1 0 - 1 1 0 - 1
1
- 1 1 0
1
- 1 1 0
11
(Shift 30°lagging) 3 3
0 - 1 1 0 - 1 1
1
I rA 2 I A1 I A2 I A3 I A4 I A5 I A6
I rB
1
2
I B1 I B 2 I B 3 I B 4 I B 5 I B 6 Equation 3.6-10
1
I rC 2 I C1 I C 2 I C 3 I C 4 I C 5 I C 6
Where:
IAm, IBm, ICm are the secondary current of branch m (m=1, 2, 3, 4, 5, 6).
I'Am, I'Bm, I'Cm are corrected secondary current of branch m (m=1, 2, 3, 4, 5, 6).
3 IdA, IdB, IdC are differential currents.
M1, M2, M3, M4, M5, M6 are matrixes of phase shifting of each branch of transformer respectively.
Its value is decided according to the vector group of transformer and please refers to “section
3.6.1.2” for details.
I2bBr1, I2bBr2, I2bBr3, I2bBr4, I2bBr5, I2bBr6 are rated secondary values of each branch of transformer
respectively.
Current compensation process is shown in the flowing figure by taken 2-winding transformer with
three-phase CT inputs for an example. In an ideal situation, the differential current (i.e.,
Id=I'_H+I'_L) should be zero during the normal operation of the transformer or an external fault
occurring.
*
*
*
I'_H I'_L
PCS-978S
Phase shift/zero sequence Phase shift/zero sequence
current elimination (*M1) current elimination (*M2)
I''_H I''_L
Where:
“I''_H” and “I''_L” are secondary corrected currents of HV and LV sides respectively.
M1 and M2 are matrixes of phase shifting and zero-sequence current elimination of HV and LV
sides respectively.
I2bBr1 and I2bBr2 are rated secondary currents at HV and LV sides respectively.
The symbol “*” represents the polarity of CT. If current flowing into the
polarity of CT, the current direction is defined as forward direction.
To clarify the situation, three important operation conditions with ideal and matched measurement 3
quantities are considered.
I'_H flows into the protected zone, I'_L leaves the protected zone, according to the definition of
signs in above figure, therefore I'_H=–I'_L.
Moreover |I'_H|=|I'_L|
Id=|I'_H+I'_L|=|I'_H-I'_H|=0
Ir=(|I'_H|+|I'_L|)/2=(|I'_H|+|I'_H|)/2=|I'_H|
Differential current (Id) is far less than restraint current (Ir), and current differential protection does
not operate.
Id=|I'_H+I'_L|=|I'_H+I'_H|=2|I'_H|
Ir=(|I'_H|+|I'_L|)/2=(|I'_H|+|I'_H|)/2=|I'_H|
Differential current (Id) is two times of restraint current (Ir), and current differential protection
operates.
Id=|I'_H+I'_L|=|I'_H+0|=|I'_H|
Ir=(|I'_H |+|I'_L|)/2=(|I'_H|+|0|)/2=|I'_H|/2
Differential current (Id) are two times of restraint current (Ir), and current differential protection
operates.
The currents for following calculation are the products of the actual secondary current of each side
multiplying its own correction coefficient. The sensitive biased differential element with low pickup
setting and restraint slope is much more sensitive for a slight internal fault. Four blocking elements,
CT saturation, inrush current, overexcitation and CT circuit failure (optional) have also been
included for the protection in order to prevent it from the unwanted operation during an external
fault.
I d K 1 I r I Pkp(I r Knee1)
1 m
Ir Ii
2 i 1
Where:
I d and I r are respectively the differential current and the restraint current.
Differential current
K=2
[87T.I_Inst]
t
en
em
l el
6 tia
0. r en
K= ffe
di
ed
as
bi
[87T.Slope1] ve [87T.Slope3]
iti
ns
se
of
ea
ar
n
io
at
er
op
1.2 3
[87T.Slope2]
Conventional biased differential element with higher setting and restraint coefficient comparing
with sensitive biased differential element is blocked only by an inrush current detection.
Conventional biased differential element provides faster operation for severe internal faults. Its
operation criterion is:
I d 1.2 p.u(
. I r 0.8 p.u)
.
I d max(0.6,87T .Slopt 3 0.15) (I r -0.8 p.u.)(I r 0.8 p.u.) Equation 3.6-12
Conventional biased differential element can eliminate the influence of CT saturation during an
external fault and ensures reliable operation even if CT is saturated during an internal fault by
means of its biased characteristic.
The slop of conventional biased differential element takes the higher one
between “0.6” and “87T.Slope3-0.15”, and the knee point is fixed in
program.
Differential current
K=2
[87T.I_Inst]
en al
lem on
t
l e nti
tia ve
ren con
iffe of
d d area
bia ation
K=max(0.6, 87T.Slope3-0.15)
se
er
op
3
1.2
Restraint current
0.8
Instantaneous differential element for transformer is to accelerate the operation speed for
transformer's internal fault. The element has no blocking element but to guard that the setting
must be greater than the maximum inrush current. Instantaneous differential element shall
operate to clear the fault when any phase differential current is higher than its setting. Its
operation criterion is:
Where:
Differential current
F operation area of instantaneous
K=2 differential element
[87T.I_Inst]
of d
ea se
ar bia ent K=0.6
[87T.Slope1] n l
tio na elem
a
e r ti a lo ve
iti t
op ven nti e ns en
n r e s e m
co iffe of l el
d
at
n
ea ia
ar ent
io iffe
er ed d
r
[87T.Slope3]
3
E C p
o as
bi
D
1.2
[87T.Slope2]
[87T.I_Biased]
0.8 B Restraint current
A [87T.I_Knee2]
[87T.I_Knee1]
The characteristic of internal faults is a straight line with the slope 2 (63.4°) in the operation
diagram (dash-dotted line K=2)
1. Sensitive biased differential element will send tripping signal monitored by CT saturation,
overexcitation, inrush current and CT circuit failure (optional). It can ensure sensitivity and
avoid the unwanted operation when CT is saturated during an external fault. Its operation
area is the tint shadow area in the figure above.
When a slight intern fault occurs, differential current rises not greatly and the operating point
moves from A to D into the tripping area of sensitive biased differential protection.
When an external fault occurs, the short-circuit current rise strongly, causing a correspondingly
high restraint current (2 times through-flowing current) with little differential current. After CT
reaches saturation (point B), a differential quantity is produced and the restraint quantity is
reduced. In consequence, the operating point may moves into the tripping area of sensitive biased
differential protection. Because CT saturation criterion is equipped, sensitive biased differential
protection will not maloperate even the fault point moves into the operation area.
2. Conventional biased differential element will send tripping signal monitored by inrush current
only. It eliminates the influence of transient and steady saturations of CT during an external
fault and ensures reliable operation even if CT is in saturation condition during an internal
fault by means of its biased characteristic. Its operation area is the deeper shadow area in the
figure above.
When an internal fault occurs, differential current rises greatly and the operating point moves to E
in the tripping area of conventional biased differential protection. (Only the second harmonic
criterion is adapted to distinguishing inrush current for blocking conventional biased differential
protection.)
3. Unrestrained instantaneous differential protection element will send tripping signal without
any blocking if differential current of any phase reaches its setting. Its operation area is over
the above two areas with the deepest dark shadow.
3 When a severe internal fault occurs, differential current rises sharply and the operating point
moves to F in the operation area of instantaneous differential element.
DPFC biased differential protection is regardless of the load current and is sensitive to small
internal fault current within the transformer. Its performance against current transformer saturation
is also good. DPFC (Deviation of Power Frequency Component) is the power frequency
component of fault component, which is the differential value between the sampling value at this
time point and that at a cycle before.
DPFC biased differential element has the higher anti-CT saturation characteristic, the sensitivity of
which to slight inter-turn fault is maintained during normal operation of transformer. The sensitivity
of transformer differential protection is improved greatly when DPFC biased differential element is
enabled, especially in the situation inter-turn fault during heavy load operation.
200
100
-100
-200
0 20 40 60 80 100 120
Original Current
100
50
-50
-100
0 20 40 60 80 100 120
DPFC current
ΔI=I(K)-I(K-24)
I(k-24) is the value of a sampling point before a cycle, 24 is the sampling points in one cycle.
From above figures, it is concluded that DPFC can reflect the sudden change of fault current at
the initial stage of a fault and has a perfect performance of fault detection. DPFC biased
differential protection reflects variation of load condition to perform a sensitive protection for the
transformer. Lab tests show that it is more sensitive than the biased differential element under the
heavy load condition. DPFC restraint current and differential current are phase-segregated. DPFC
biased differential element can be blocked by inrush current, overexcitation and CT circuit failure.
The operation criterion is as follows:
I d 0.2 p.u.
I d 1.25 I dt I dth
I d 0.6 I r ( I r 2 p.u.) 3
Equation 3.6-14
I d 0.75 I r - 0.3 p.u.( I r 2 p.u.)
I d I 1 I 2 ... I m
m m m
I r Max I ak , I bk , I ck
k 1 k 1 k 1
Where:
I ak , I bk , I ck are DPFC current of branch k of the transformer.
I dt is the floating threshold varied with the change of load current from time to time. The change
of load current is small and gradually under normal or even power swing condition, the adaptive
floating threshold ( I dt ) is higher than the change of current under these conditions and hence the
I d and I r are DPFC differential current and DPFC restraint current respectively.
Differential current
K=m
K=0.75
1.2p.u.
3 0.2p.u.
K=0.6
Restraint current
0.333p.u. 2p.u.
The value of m is not greater than 1. For the phase with maximum restraint current, m is equal to 1,
and for other phases, m is less than 1.
DPFC biased differential element can detect a slight inter-turn fault of transformer more
sensitively than biased current differential element. During a slight inter-turn fault, fault current will
flow through transformer whether transformer is fed from one side or from both sides. Therefore,
following two typical situations (an external fault and a slight inter-turn fault) are given to show
differential and restraint current calculation.
During normal operation, Ia_HVS=1A∠0°, Ib_LVS=1A∠180°
Id=|I'a_HVS+I'b_LVS|
=|1.3A∠0°+1.1A∠180°|=0.2A
Ir=0.5x(|I'a_HVS|+|I'b_LVS|)
=0.5x(|1.3A∠0°|+|1.1A∠180°|)=1.2A
ΔId=|(I'a_HVS-Ia_HVS)+(I'b_LVS-Ib_LVS)|
=|(1.3A∠0°-1A∠0°)+(1.1A∠180°-1A∠180°)|=0.2A
ΔIr=max(|I'a_HVS-Ia_HVS|,|I'b_LVS-Ib_LVS|)
=max(|1.3A∠0°-1A∠0°|,|1.1A∠180°-1A∠180°|)=0.3A
Conclusion: DPFC biased differential element is more sensitive than biased differential element
during an internal fault.
Id=|I'a_HVS+I'b_LVS|
=|2A∠0°+2A∠180°|=0A
Ir=0.5x(|I'a_HVS|+|I'b_LVS|)
=0.5x(|2A∠0°|+|2A∠180°|)=2A
ΔId=|(I'a_HVS-Ia_HVS)+(I'b_LVS-Ib_LVS)| 3
=|(2A∠0°-1A∠0°)+(2A∠180°-1A∠180°)|=0A
ΔIr=max(|I'a_HVS-Ia_HVS|, |I'b-_LVS-Ib_LVS|)
=max(|2A∠0°-1A∠0°|,|2A∠180°-1A∠180°|)=1A
Conclusion: DPFC biased differential element does not operate during an external fault.
The device provides optional inrush current distinguished principles: harmonic principle (second
harmonic and third harmonic) and waveform symmetry principle. The logic setting
[87T.Opt_Inrush_Ident] is used to select distinguished principle, second harmonic principle or
waveform symmetry principle. The discrimination of inrush current by third harmonics is
independent criterion, and is not controlled by the setting [87T.Opt_Inrush_Ident]. When an
internal fault occurs and CT goes to stable saturation, there are great third harmonic component in
CT secondary current. Because sensitive biased differential element has too high sensitivity, the
third harmonic criterion is only used to block sensitive biased differential element to prevent it from
maloperation when both [87T.Opt_Inrush_Indent] and [En_Hm3_Inrush] are set as “1”.
The second and third harmonics of differential current can be used to distinguish inrush current.
Its criteria are:
Where:
I d _ 2 nd and I d _ 3rd are the second and third harmonics of phase differential current respectively.
The differential current is basically the fundamental sinusoidal wave during a fault. When the
transformer is energized, plentiful harmonics will appear, and the waveform will be distorted,
interrupted and unsymmetrical. Wave symmetry principle is used to distinguish inrush current.
CT saturation characteristics make waveform unsymmetrical between the first half cycle and the
second half cycle. During internal faults, current waveform is sinusoidal wave, so two half cycles
of wave are almost symmetrical after a periodic component is eliminated (calculate the differential
of differential current in fact).
3 As shown in Figure 3.6-6, arc ABC is a cycle of typical waveform of differential current with a
periodic component. Flip the arc BC of second half cycle vertically to get the arc B'C', and then
move it forward half cycle to get the arc B''C''. The degree of symmetry of current wave is shown
as
S
K sym Equation 3.6-16
S
Where:
X: arc AB
Y: arc B''C''
For a differential current waveform, the area of X is almost equal to that of Y and the value of K sym
is almost 0. For an unsymmetrical waveform, the area of X is not equal to that of Y, so the value of
Ksym is a great value. Therefore, waveform of inrush current can be distinguished from the
waveform of internal fault according to the value of K sym.
Both waveform symmetry principle and second harmonic principle are based on current distortion
due to inrush current, and the only difference is the mathematical method. The second harmonic
principle is to calculate the percentage of second harmonic in differential current, but the
waveform symmetry principle is to calculate the percentage of even harmonic to total differential
current.
There are three optional blocking modes for inrush current, self-adaptive one-phase inrush
blocking one-phase differential element mode (self-adaptive 1Pblk1P mode), two-phase inrush
blocking three-phase differential element mode (2PBlk3P mode) and one-phase inrush blocking
three-phase differential element mode (1Pblk3P mode), by the logic setting
[87T.Opt_BlkMode_Inrush]. Self-adaptive blocking mode can enhance ability of differential
protection to avoid maloperation during transformer energization effectively and ensure high
3
speed of differential protection for faults under normal operation. The self-adaptive blocking mode
is recommended to be selected in the actual application.
The device has an energizing detection element by current criterion (without additional breaker
position signal) to check whether the transformer is in the process of energization. Once the
transformer in the process of energization is detected, the following criterions are adopted to
improve the stability to avoid mal-operation caused by inrush current.
Criterion 1
The device automatically decreases the restraint coefficient values of second harmonics and
wave distortion during the initial stage of transformer energization and with the passage of time
automatically increases those values which shall be not greater than corresponding values of
settings. This feature ensures biased differential element fast operation for transformer energized
on to a fault in addition to the inrush current blocking.
Criterion 2
The device can be self-adaptive to enable “2PBlk3P” mode according to the comprehensive
characteristics of three-phase differential current. If inrush current is distinguished, then enables
“2PBlk3P” mode for short time, and then switches to phase-segregated blocking mode after a
period.
Criterion 3
If the second harmonic percent of differential current used as auxiliary criteria continues to rise,
then biased differential element is kept being blocked.
When the inrush current is detected in any two-phase current, three-phase current differential
protection will be blocked.
When the inrush current is detected in any phase current, three-phase current differential
protection will be blocked.
It is supposed that three differential currents are Ida, Idb, and Idc.
For mode 1 in case 3, when blocking criterion 1, 2 and 3 of inrush current discrimination are all
released to differential element, differential element can operate. Otherwise, differential element
will be blocked if any of three blocking criterions blocks.
Case 4 is usually an internal fault, and blocking mode 2 can ensure differential protection operate
correctly if there is an internal fault in case 4. Case 3 may be an internal fault or inrush current,
and blocking mode 1 can distinguish through its perfect criteria, hence, it is recommended to use
blocking mode 1.
The following figure shows the logic of inrush current blocking differential protection.
SET [87T.Opt_BlkMode_Inrush=0]
SIG Flag_NoInrush_Wave
&
No Inrush (Phase B)
3
SIG 87T.TrigDFR No Inrush (Phase C)
&
SIG No Inrush (Phase C)
&
>=1
&
SET [87T.Opt_BlkMode_Inrush=2]
SET [87T.Opt_BlkMode_Inrush=1]
>=1
>=1
SIG Transformer energization 100ms 0ms &
SET [87T.Opt_BlkMode_Inrush=0]
Where:
“Flag_NoInrush_Harm” is the internal signal that means no inrush current is detected by the
harmonic principle.
“Flag_NoInrush_Wave” is the internal signal that means no inrush current is detected by the
waveform symmetry principle.
“Flg_NoInrush_Hm3” is the internal signal that means no inrush current is detected by the third
harmonic principle.
There are two kinds of CT saturation, i.e. transient CT saturation and stable CT saturation. If an
3 external fault or an internal fault occurs, CT primary current increases greatly and CT secondary
current consists of fundamental component, DC component and harmonic component. The
decaying DC component results in remanent magnetism in magnetic core, and with the
accumulation of remnant magnetism, CT goes into saturation state which is called transient CT
saturation. With the time passed, the DC component decays to zero almost and CT is still
saturated caused by AC excitation, which is called stable CT saturation.
According to tests in lab, it is found that the second harmonic component is greater than the third
harmonic component at the stage of CT transient saturation and the third harmonic is greater than
the secondary harmonic at the stage of CT stable saturation. Therefore, the second and third
harmonics both can be used to detect CT saturation.
I _ 2 nd K_2nd I _1st
or Equation 3.6-17
I _ 3 rd K _3rd I _1st
Where:
I _1st is the fundamental component of one phase current, it won’t do CT saturation detection
unless the fundamental component is higher than the corresponding internal setting.
K _2nd and K _3rd are fixed coefficients of secondary and third harmonics respectively.
If any harmonic of one phase current meets the above equation, it will be considered that it is CT
saturation to cause this phase differential current and biased differential element will be blocked.
Internal faults can be distinguished from external faults by differential protection through the
asynchronous method of differential and restraint, and it is needed that the saturation free time of
CT is no less than 4ms for internal faults to ensure differential protection operate correctly with the
added CT saturation criterion.
When a transformer is overexcited, the exciting current will increase sharply which may result in
an unwanted operation of differential protection. Therefore the overexcitation shall be
discriminated to block differential protection. The third or fifth harmonic of differential current can
be selected to determinate overexcitation.
U
n Equation 3.6-19
f
Where:
The base value for calculating per unit value of voltage is rated secondary voltage value (phase
voltage) of the voltage transformer, and the base value for calculating per unit value of frequency
is rated frequency. During normal operation, n = 1.
If overexcitation factor is less than 1.4, biased differential element is blocked when the constant of
fifth or third harmonics is greater than [87T.K_Hm3/Hm5_OvExc] and this condition is judged as
overexcitation condition without damages to transformer. If overexcitation factor is greater than
1.4, biased differential element is no longer being blocked by overexcitation because transformer
is damaged in this situation.
If the differential current in any phase is continually greater than the alarm setting [87T.I_Alm] over
10s, the differential current abnormality alarm [87T.Alm_Diff] will be issued, but this alarm will not
block differential protection.
The following two cases are considered as CT circuit failure, and the device can discriminate at
which side CT circuit is failure by unbalanced currents. Differential CT secondary circuit failure
can be judged more accurately and reliably by adopting combined method of voltage and current.
First case, if none of following four conditions is satisfied after the fault detector of biased
differential current, or biased residual differential current, or biased winding differential current
picks up, it will be judged as CT circuit failure and the alarm will be issued.
1) Negative-sequence voltage at any side is greater than 2%Upp (Upp is the secondary
phase-to-phase rated voltage).
2) Any phase current at any side increases after fault detector picks up.
3 3) The maximum phase current is greater than 1.1p.u. after the fault detector picks up.
The alarm of CT circuit failure can be settable to block transformer differential protection, reactor
differential protection, restricted earth-fault protection and winding differential protection. The
alarm of CT circuit failure is latched once issued, it can be reset aumatically after the failure is
cleared (under the condition that the setting [En_AutoRecov_Alm_CTS] is set to be “1”), or it can
be reset manually when the setting [En_AutoRecov_Alm_CTS] is set to be “0”.
Transformer's DPFC biased differential element is always blocked during CT circuit failure.
Transformer's sensitive biased differential element will be blocked during CT circuit failure
when the logic setting [87T.En_CTS_Blk] set as “1”.
Biased restricted earth-fault element will be blocked during CT circuit failure when the logic
setting [64REF.En_CTS_Blk] is set as “1”.
Biased winding differential protection will be blocked during CT circuit failure when the logic
setting [87W.En_CTS_Blk] is set as “1”.
87T
87T.in_I3P1 87T.On_Inst
87T.in_I3P2 87T.On_Biased
87T.in_I3P3 87T.On_DPFC
87T.in_I3P4 .
87T.in_I3P5 .
87T.in_I3P6 . 3
87T.Enable 87T.Ib_Th
87T.Block 87T.Ic_Th
3.6.4 Logic
EN [87T.En_Inst] &
87T.On_Inst
SIG 87T.Enable
&
SIG 87T.Block >=1 87T.Blocked_Inst
SIG Fail_Device
&
87T.Valid_Inst
3
EN [87T.En_Biased] &
87T.On_Biased
SIG 87T.Enable
&
SIG 87T.Block >=1 87T.Blocked_Biased
SIG Fail_Device
&
87T.Valid_Biased
EN [87T.En_DPFC] &
87T.On_DPFC
SIG 87T.Enable
&
SIG 87T.Block >=1 87T.Blocked_DPFC
SIG Fail_Device
&
87T.Valid_DPFC
3
Figure 3.6-9 Pickup logic of transformer differential protection
SIG 87T.Pkp_Biased
>=1
SIG Sensitive 87T & 87T.Op_Biased
SIG U*/f*>1.4
SIG 87T.Pkp_Biased
SIG U*/f*>1.4
SIG 87T.Pkp_DPFC
SIG 87T.Pkp_Inst
>=1
SIG 87T.Pkp_Biased
SIG 87T.Pkp_DPFC
&
T 0ms 87T.Alm_CTS
Where:
“T” is an internal time delay parameter, and it is floating and not open for user’s configuration.
3.6.5 Settings
Table 3.6-5 Settings of transformer differential protection
REF is a kind of differential protection, so it calculates differential current and restrained current.
The differential current is a vector difference of the neutral current (i.e., current flowing in the
neutral conductor) and the residual current from the lines. For internal faults, this difference is
equal to the total earth fault current. REF operates on the fault current only, and is not dependent
on eventual load currents. This makes REF a very sensitive protection.
The difference between current differential protection and REF is that the first one is based on
adjusted phase current balance and the latter is based on balance of calculated residual current
and residual current from neutral CT.
Three groups of REF are for each side of a three-winding transformer at most. REF is not affected
by inrush current and the tap of transformer. CT Transient detection function based on the ratio of
residual current to positive current is adopted to eliminate the influence of difference of transient
characteristic to REF.
*
HV side I_H LV side
* *
3I0Cal'_H
Magnitude compensation
I'_HNP
*
3
Figure 3.7-1 Application for two-windings transformer with one CB at one side
HV side 1
* * *
I_H1
LV side
I_H2
3I0Cal'_H1 3I0Cal'_H2 * * *
HV side 2
Magnitude
compensation
REF at HV side I_HNP
Magnitude
compensation *
Magnitude
compensation
I'_HNP
Figure 3.7-2 Application for two-windings transformer with two CBs at one side
HV side
* * *
I_H
3I0Cal'_H I_M
*
MV side CW side
*
*
3I0Cal'_M
Magnitude
I_CW 3
LV side
compensation *
REF at HV side
Magnitude
compensation
I'_CW
Magnitude
compensation
Maximum 4 group of CTs and 1 neutral point CT inputs for REF, and the maximum current inputs
applied for an auto-transformer with two circuit breakers at HV and MV sides respectively.
Before REF of a side is put into service on site, polarity of neutral point CT
must have been checked by a primary injection test. Otherwise an
undesired operation may occur during an external earth fault.
Where:
If CTs used for REF have different primary rated values, the device will automatically adjust the
currents with respective correction ratio shown as below.
I1n
Klph Klb / I 2 n and K lb min(
I1n _ max
,4) Equation 3.7-2
I1n _ max I1n _ min
Where:
I1n_min is minimum primary rated value among all CTs for REF.
I1n_max is maximum primary rated value among all CTs for REF.
This calculation method is to take the minimum CT primary rated value of all calculated sides as
3 the reference side. If the multiple of maximum CT primary rated value to minimum CT primary
rated value is greater than 4, then reference side shall be taken as 4 and other sides shall be
calculated proportionally. Otherwise, the reference side shall be taken as 1, and other sides will be
calculated proportionally.
The currents used in the following analysis have been corrected, that means the currents for
following calculation are the products of the actual secondary current of each side multiplying its
own correction coefficient (K1ph).
When selecting CT, the primary currents for each side muse follow the
I1n _ max
criterion: 128 , it is recommended that the ratio is smaller than 16.
I1n _ min
I 02
I 0 d I 01 I 03
I 04
I NP
Equation 3.7-3
Where:
I01, I02, I03, I04 are secondary values of calculated residual current at each side.
I'01, I'02, I'03, I'04 are secondary values of corrected calculated residual current at each side.
K1ph1, K1ph2, K1ph3, K1ph4 are corrected coefficients of amplitude compensation at each side.
Where:
*
A
Ib
*
B
Ic
* C
I_NP
*
3I0Cal' =I'c+I'b+I'a
I'_NP REF
I_NP' flows into the protected zone from ground, 3I0Cal' leaves the protected zone, i.e. I_NP'
is negative according to the definition of signs in above figure, therefore I_NP'=-3I0Cal'.
3I0d=|3I0Cal'+I_NP'|=|3I0Cal'–3I0Cal'|=0
3I0r=Max(|3I0Cal'|, |I_NP'|)=|3I0Cal'|
No differential current, but restraint current corresponds to the through-flowing current, hence,
REF does not operate.
2. Internal short-circuit:
3I0d=|3I0Cal'+I_NP'|=2x|3I0Cal'|
Differential current are two times of restraint current and corresponding to the total fault, hence,
REF operates.
3 I 0 d [ x.64 REF .Slope] (I 0 r - [ x.64 RF .I _ Knee ]) [ x.64 REF .I _ Biased ]
Equation 3.7-5
3I 0d I01 I 02 I 03 I 04 I 0 NP
3
3 I 0 r Max( I 01 , I 02 , I 03 , I 04 , I 0 NP )
Where:
3 I 0 d and 3 I 0 r are respectively the differential current and the restraint current at side x of
transformer.
I 01 , I 02 , I 03 and I 04 are the calculated residual currents at side x of transformer.
I 0 NP is the residual current from neutral point CT at side x of transformer.
K=m
[x.64REF.Slope]
[x.64REF.I_Biased]
Restraint current
[x.64REF.I_Knee]
The value of m is defined by the branch number for REF calculation. For example, there are two
branches at HV side (wye winding with neutral point earthed), so there are three branches
In order to ensure the selectivity of restricted earth fault protection, direction criterion is also
available. The setting [x.64REF.En_Dir_Blk] is used to enable/disable the function of direction
criterion blocking REF. The direction criterion is based on the different direction characteristic of
neutral-point current 3I0_Neu and calculated residual current 3I0_Cal at an external earth fault
and an internal earth fault.
For an external earth fault, the neutral-point current 3I0_Neu and the calculated residual current
3I0_Cal have equal magnitude, but they are of approximately opposite directions.
3
For external fault
3I0_Cal
ROA (Relay Operate Angle)
3I0_Neu
ROA
For an internal earth fault, the magnitudes of the two currents 3I0_Neu and 3I0_Cal may be
different, but their relative directions are within a certain angle range. The operation angle setting
[x.64REF.ROA] is equipped in the device, it will be judged as an internal earth fault and the
direction criterion will be released when the relative angle of the two currents is lower than the
setting.
ROA
3I0_Cal
3I0_Neu
ROA
Non-identical CT characteristics can cause unbalance current. During phase-to-phase faults and
three-phase faults, the unbalance of three-phase CTs results in residual current which may lead to
maloperation of RFE. Therefore, positive-sequence current restraint blocking criterion is adopted
to prevent REF from maloperation in above mentioned conditions.
When the residual current of REF at each side is greater than 0 times positive-sequence current,
it is decided that zero-sequence current is caused by a fault and release REF. Positive-sequence
current restraint blocking criterion is showed below. This blocking criterion is ignored when neutral
point current is greater than the internal setting, whichever is greater.
3 Where:
CT saturation detection function based on 2nd and 3rd harmonics is adopted to avoid
maloperation of REF during an external fault. Please refer to Section 3.6.1.10 for details.
CT circuit supervision for REF is divided into two kinds: differential CT circuit abnormality without
the pickup of the fault detector and differential CT circuit failure with the pickup of the fault
detector.
CT Circuit Abnormality
If the following operation formula is met for 10s, CT circuit abnormality alarm of REF will be issued
without blocking the protection.
CT Circuit Failure
64REF
x.64REF.in_I3P1 x.64REF.On
x.64REF.in_I3P2 x.64REF.Blocked
x.64REF.in_I3P3 x.64REF.Valid
x.64REF.in_I3P4 x.64REF.St
x.64REF.in_I1P x.64REF.Op
x.64REF.Enable x.64REF.Alm_Diff 3
x.64REF.Block x.64REF.Alm_CTS
x.64REF.3I0d
x.64REF.3I0r
x.64REF.I0_Th
3.7.4 Logic
EN [x.64REF.En] &
x.64REF.On
SIG x.64REF.Enable
&
SIG x.64REF.Block >=1 x.64REF.Blocked
3 SIG Fail_Device
&
x.64REF.Valid
SIG I0>β0×I1
&
SIG CT saturation
EN [x.64REF.En_CTS_Blk] x.64REF.St
EN x.64REF.En_Dir_Blk
SIG x.64REF.Pkp
Where:
3.7.5 Settings
Table 3.7-3 Settings of restricted earth fault protection
Winding differential protection is based on Kirchhoff's first law and calculates differential currents
of electrical connection circuits including phase A, phase B phase C and residual differential
currents. Inrush current and tap change of the transformer have no effect on winding differential
protection. Winding differential protection has high sensitivity to internal earth faults because there
is no load current in the restraint current. Normally, winding differential protection is applied in
following two situations.
HV side
* * *
I_H
I_M
I'_H
*
MV side
*
CW side
*
I'_M
I_CW
3 Magnitude
LV side
compensation Winding
* * *
differential
Magnitude protection
compensation
Magnitude I'_CW
compensation
HV side 1
* * * I_Bush
*
I_H1
LV side
*
HV side
*
I_H2
* * *
I'_H1
I'_H2 HV side 2
Magnitude
compensation Winding differential
protection
Magnitude
compensation
Magnitude
compensation
I'_HBush
Where:
Where:
I1n
K wph K wb / I 2 n
I1n _ max
Equation 3.8-2
I1n _ max
K wb min( ,4)
I1n _ min
Where:
I1n_min is the minimum value among primary values of all CTs for winding differential protection.
I1n_max is the maximum value among primary values of all CTs for winding differential protection.
This calculation method is to take the minimum CT primary rating of all calculated CT inputs as
the reference. If the multiple of the maximum CT primary ratio to the minimum CT primary rating is
greater than 4, then reference shall be taken as 4 and others shall be calculated proportionally.
Otherwise, the reference shall be taken as 1, and others will be calculated proportionally.
The currents used in the following analysis have been corrected, which means the currents for
following calculation are the products of the actual secondary current of each side multiplying its
own correction coefficient (Kwph).
When selecting CT, the primary currents for each side muse follow the
I1n _ max
criterion: 128 , it is recommended that the ratio is smaller than 16.
I1n _ min
I wdA I A1 I A2 I A3
I I I I
3 wdB K wph1 K wph 2 K wph 3 B 3
B1 B 2
I wdC I C1 IC 2 IC 3
I wd 0 I 01 I 02 I 03
1 2 3
Equation 3.8-3
I A4 I A5
I I
K wph 4 K wph 5
B 4 B5
IC 4 IC 5
I 04 I 05
4 5
Where:
I wdA , I wdB , I wdC , I wd0 are respectively three phase and residual winding differential currents.
I wrA , I wrB , I wrC , I wr0 are secondary values of three phase restraint currents and neutral
restraint current respectively.
I Am , I B m , I C m and I 0 m are respectively secondary values of corrected three phase currents
and calculated residual current of branch m (m=1, 2, 3, 4, 5).
Kwph1, Kwph2, Kwph3, Kwph4, Kwph5 are corrected coefficients of each side for magnitude
compensation respectively.
The operation criteria of winding differential protection are as follows, and maximum 5 branches
3
are supported for the calculation.
Where:
I W 1 , I W 2 , I W 3 , I W 4 and I W 5 are currents of five branches respectively.
Differential current
K=m
3 [87W.Slope]
[87W.I_Biased]
Restraint current
[87W.I_Knee]
The value of m is defined by the branch number for winding differential protection. For example,
winding differential protection is applied for protecting an autotransformer including HV side, MV
side and common winding and m is equal to 3.
In order to prevent winding differential protection from undesired operation caused by transient or
steady state saturation of CT during an external fault, the second and third harmonics of
secondary current of individual CTs are used for the device to discriminate saturation of
three-phase CT. If CT saturation is detected, winding differential protection will be blocked.
1
I _ 2 nd K_2nd I _1st & I _ wd [ 87W.I_Biased ]
2
or Equation 3.8-7
1
I _ 3 rd K _3rd I _1st & I _ wd [ 87W.I_Biased ]
2
Where:
K _2nd and K _3rd are fixed coefficients of secondary and third harmonics respectively.
If any harmonic of one phase current meets the above equation, it will be considered that it is CT
saturation to cause this phase differential current and winding differential protection will be
blocked.
CT Circuit Abnormality
If the following operation formula is met for 10s, CT circuit abnormality alarm of winding differential
protection will be issued without blocking the protection.
3
The operation criterion is as follows:
Where:
CT Circuit Failure
87W
87W.in_I3P1 87W.On_PhSeg
87W.in_I3P2 87W.On_REF
87W.in_I3P3 87W.Blocked_PhSeg
87W.in_I3P4 .
87W.in_I3P5 .
87W.Enable .
87W.Block 87W.Ic_Th
87W.3I0_Th
3.8.4 Logic
EN [87W.En_PhSeg] &
87W.On_PhSeg
SIG 87W.Enable
&
SIG 87W.Block >=1 87W.Blocked_PhSeg
SIG Fail_Device
&
87W.Valid_PhSeg
3
EN [87T.En_REF] &
87W.On_REF
SIG 87W.Enable
&
SIG 87W.Block >=1 87W.Blocked_REF
SIG Fail_Device
&
87W.Valid_REF
SIG 87W.Flag_DIFF
& &
SIG CT Staturation [87W.t_Op] 0ms 87W.Op_PhSeg
EN [87W.En_CTS_Blk]
SIG 87W.Pkp_PhSeg
3 SIG 87W.Flag_DIFF
& &
[87W.t_Op] 0ms
SIG CT Staturation 87W.Op_REF
EN [87W.En_CTS_Blk]
SIG 87W.Pkp_REF
Where:
“87W.Flag_DIFF” means that the operation criterion of winding differential protection is satisfied.
3.8.5 Settings
Table 3.8-3 Settings of winding differential protection
During overexcitation, field current of transformer rises greatly to cause excessive heating and
severe damage. The transformer, working magnetic flux density near the knee point, is subject to
overexcitation. Frequency range for normal operation is 45~55Hz for 50Hz working frequency of
power system and 55~65Hz for 60Hz working frequency of power system.
Overexcitation protection can be configured at any side of transformer through PCS-Studio, and it
3
is recommended to be equipped at the side without OLTC.
Where:
The base value for calculating per unit value of voltage is secondary voltage corresponding to
primary voltage of one side of transformer, and the base value for calculating per unit value of
frequency is rated frequency. Hence, under normal operation, n should be equal to 1.
525
62.62V
500
3
100
This base voltage calculation is carried out in the device and users need not calculate VT ratio
when configure settings.
Several groups of setting point with independent settings can be configured for simulating the
inverse-time operation characteristics curve and this protection can satisfy overexcitation
requirements of various transformers.
3 U*/f*
n0
n1
n2
n3
n4
n5
n6
n7
n8
n9
t (s)
0 t0 t1t2 t3 t4 t5 t6 t7 t8 t9
Inverse-time characteristic curve can be specified by several overexcitation multiple settings, and
the relation among various settings of n and t are:
24DT1
24DT1.OvExc 24DT1.On
24DT1.Enable 24DT1.Blocked
24DT1.Block 24DT1.Valid
24DT1.St
24DT1.Op
3
24DT2
24DT2.OvExc 24DT2.On
24DT2.Enable 24DT2.Blocked
24DT2.Block 24DT2.Valid
24DT2.St
24DT2.Alm
24IDMT
24IDMT.OvExc 24IDMT.On
24IDMT.Enable 24IDMT.Blocked
24IDMT.Block 24IDMT.Valid
24IDMT.St
24IDMT.Op
24IDMT.Alm
24IDMT.ThermAccu
3.9.4 Logic
EN [24DT1.En] &
24DT1.On
SIG 24DT1.Enable
&
SIG 24DT1.Block >=1 24DT1.Blocked
SIG Fail_Device
&
24DT1.Valid
EN [24DT2.En] &
24DT2.On
SIG 24DT2.Enable
&
SIG 24DT2.Block >=1 24DT2.Blocked
SIG Fail_Device
&
24DT2.Valid
EN [24IDMT.En] &
24IDMT.On
SIG 24IDMT.Enable
&
SIG 24IDMT.Block >=1 24IDMT.Blocked
SIG Fail_Device
&
24IDMT.Valid
BI x.BI_En_VT
SET U*/f*>[24DT2.K_Set]
BI x.BI_En_VT
SET U*/f*>[24IDMT.Kn_Set]
BI x.BI_En_VT
24IDMT.St
SIG 24IDMT.Pkp
&
SIG U*/f*>[24IDMT.Kn_Set] & IDMT 24IDMT.Op
24IDMT.St
EN [24IDMT.En_Trp]
&
SIG U*/f*>[24IDMT.Kn_Set] & IDMT* 24IDMT.Alm
EN [24IDMT.En_Alm]
3 Where, IDMT* means that the time delay of inverse-time overexcitation protection for alarm
purpose equals to [24IDMT.K_Alm] of the time delay of inverse-time overexcitation protection for
trip purpose.
3.9.5 Settings
Table 3.9-3 Settings of overexcitation protection
3
Please input the corresponding values of selected 10 points of
overexcitation curve of transformer to the device and the values of 10
points are distributed averagely.
[24IDMT.K9_Set]<[24IDMT.K8_ Set]<…<[24IDMT.K1_Set]<[24IDMT.K0_
Set]
The device can provide 6 stages of phase overcurrent protection with independent logic by default.
Each stage can be independently set as definite-time characteristics or inverse-time
characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time
dropout or inverse-time dropout. It can be chosen whether it is blocked by voltage control element
or harmonic control element. The direction control element can be set as no direction, forward
direction and reverse direction. Phase overcurrent protection picks up when the current exceeds
the setting, and operates after a certain time delay. Once the fault disappears, phase overcurrent
Phase overcurrent protection can operate to trip or alarm and can be enabled or disabled via the
settings or the signals, for some specific applications, phase overcurrent protection needs to be
blocked by the external signal, so the device provides an input signal to be used to block phase
overcurrent protection.
EN [x.50/51Pi.En] &
x.50/51Pi.On
SIG x.50/51Pi.Enable
&
SIG x.50/51Pi.Block >=1 x.50/51Pi.Blocked 3
SIG Fail_Device
&
x.50/51Pi.Valid
SET x.Ia>0.95×[x.50/51Pi.I_Set]
>=1
SET x.Ib>0.95×[x.50/51Pi.I_Set] &
0 500ms &
SET x.Ic>0.95×[x.50/51Pi.I_Set]
x.50/51Pi.Pkp
SIG x.50/51Pi.On
SIG x.50/51Pi.Valid
&
FD.Pkp
SET [x.50/51Pi.Opt_Trp/Alm]=Alm
When a fault occurs at the remote end of a feeder, the fault current is relatively small, so the
voltage control element can be adopted to increase the sensitivity for this kind of fault. It can be
enabled or disabled via the setting [x.50/51Pi.En_Volt_Blk] (i=1~6). If VT circuit supervision is
enabled and the setting [x.50/51P.En_VTS_Blk] is set as “Enabled”, the device will issue an alarm
signal "VTS.Alm" when VT circuit fails, and voltage control element will be blocked. If voltage
control element is not enabled, phase overcurrent protection will not effected by VT circuit failure.
The corresponding relationship between each phase and voltage control element is as follows.
EN [x.50/51P.En_VTS_Blk] &
>=1
3 SIG x.VTS.Alm
>=1
SIG x.Uab, x.Ubc, x.Uca criterion
Voltage
& x.50/51P.VCE.Op
BI x.BI_En_VT
EN [x.En_VT]
Ua
[x.50/51P.DIR.phi_Min_Fwd]
Non-operating Ia
area
[x.50/51P.DIR.RCA]
Operating area in
reverse direction
[x.50/51P.DIR.phi_Max_Fwd]
[x.50/51P.DIR.phi_Min_Rev] Non-operating
area
In order to ensure the selectivity of phase overcurrent protection, direction control element is also
available. The setting [x.50/51Pi.Opt_Dir] (i=1~6) is used to select the direction characteristics for
each stage of phase overcurrent protection: no direction, forward direction and reverse direction
are selectable. Takes the phase A fault as an example, the setting
[x.50/51P.DIR.Opt_PolarizedVolt] is set as "Up", its operating characteristics is shown in Figure
3.10-4. The principle of phase B and phase C is the same. If positive-sequence voltage or
phase-to-phase voltage is used as polarized voltage, the operating characteristics are the same.
Direction criterion
Polarization Faulty Operating
Polarized voltage Angle difference
mode phase current
Phase-A Positive-sequence
Phase A Angle_A=Angle(U1)-Angle(Ia)-RCA
current Ia voltage
Positive-sequence Phase-B Positive-sequence
Phase B Angle_B=Angle(U1)-Angle(Ib)-RCA-120º
voltage polarized current Ib voltage
Phase-C Positive-sequence
Phase C Angle_C=Angle(U1)-Angle(Ic)-RCA+120º
current Ic voltage
Phase-A Phase-to-phase
Phase A Angle_A=Angle(Ubc)-Angle(Ia)-RCA+90º
current Ia voltage Ubc
Phase-to-phase Phase-B Phase-to-phase
Phase B Angle_B=Angle(Uca)-Angle(Ib)-RCA+90º
voltage polarized current Ib voltage Uca
Phase-C Phase-to-phase
Phase C Angle_C=Angle(Uab)-Angle(Ic)-RCA+90º
current Ic voltage Uab
Phase-A Phase-to-ground
Phase A Angle_A=Angle(Ua)-Angle(Ia)-RCA
current Ia voltage Ua
Phase-to-ground Phase-B Phase-to-ground
Phase B Angle_B=Angle(Ub)-Angle(Ib)-RCA
voltage polarized current Ib voltage Ub
Phase-C Phase-to-ground
Phase C Angle_C=Angle(Uc)-Angle(Ic)-RCA
current Ic voltage Uc
The calculation of direction control element needs to judge the voltage threshold and the current
threshold. The direction judgement can be executed only when both the voltage and the current
are greater than the threshold value. For different polarization mode, the selected voltage and
current, and their threshold value are also different, the specific principles are:
The memorized characteristics of direction control element can eliminate the dead zone for close
up three-phase short-circuit fault. When the polarized voltage is less than the minimum operating
voltage setting [x.50/51P.DIR.U_Min], the positive-sequence voltage before two cycles is used to
judge the direction. The polarized voltage will not be used to judge the direction until it is greater
than [x.50/51P.DIR.U_Min].The logic of forward direction element and reverse direction element
are shown in Figure 3.10-5.
EN [x.50/51P.DIR.En_VTS_Blk] &
3
>=1
SIG x.VTS.Alm
x.50/51P.DIR.FwdDir.Op
SIG Three-phase voltages
criterion
SIG Memorized U1
SET [x.50/51P.DIR.Opt_PolarizedVolt]
BI x.BI_En_VT &
EN x.En_VT
EN [x.50/51P.DIR.En_VTS_Blk] &
>=1
SIG x.VTS.Alm
x.50/51P.DIR.RevDir.Op
SIG Three-phase voltages
criterion
SIG Memorized U1
SET [x.50/51P.DIR.Opt_PolarizedVolt]
BI x.BI_En_VT &
EN x.En_VT
Where:
Memorized U1: the positive-sequence memory voltage, it refers to the positive-sequence voltage
of two cycles before the polarized voltage is less than the minimum operating voltage setting
[50/51P.DIR.U_Min], and it is calculated from the three-phase voltage.
When the transformer is energized with no-load, the inrush current may be generated, which may
cause the maloperation of phase overcurrent protection. Because secondary harmonic
component is high in the inrush current but secondary harmonic component is low in the fault
current, harmonic control element based on secondary harmonic component is added to prevent
phase overcurrent protection from maloperation due to inrush current. For harmonic control
element, the harmonic blocking mode can be selected through the setting [50/51P.HMB.Opt_Blk],
it can support phase blocking, cross blocking, and maximum phase blocking. The corresponding
relationship is shown in the following table.
3
Harmonic blocking criterion
Harmonic blocking mode
Phase A Phase B Phase C
PhaseBlk (phase Ia2/Ia1> Ib2/Ib1> Ic2/Ic1>
1
blocking) x.50/51P.HMB.K_Hm2 x.50/51P.HMB.K_Hm2 x.50/51P.HMB.K_Hm2
2 CrossBlk (cross blocking) (Ia2/Ia1) or (Ib2/Ib1) or (Ic2/Ic1)> x.50/51P.HMB.K_Hm2
MaxPhaseBlk (maximum Max(Ia2, Ib2, Ic2)/Ia1> Max(Ia2, Ib2, Ic2)/Ib1> Max(Ia2, Ib2, Ic2)/Ic1>
3
phase blocking) x.50/51P.HMB.K_Hm2 x.50/51P.HMB.K_Hm2 x.50/51P.HMB.K_Hm2
When the fundamental current is greater than the setting [x.50/51P.HMB.I_Rls], the corresponding
phase will be unblocked by harmonic control element. The logic of harmonic control element is
shown in Figure 3.10-6.
SET Imax>[x.50/51P.HMB.I_Rls]
SET [x.50/51P.HMB.Opt_Blk]
Where:
Phase overcurrent protection can operate instantaneously or with a fixed time delay. It can also
operate with inverse-time characteristics, and its characteristics curve complies with the
standards IEC 60255-3 and ANSI C37.112. Phase overcurrent protection can support
definite-time characteristics, IEC & ANSI standard inverse-time characteristics and user-defined
inverse-time characteristics, which are determined by the setting [x.50/51Pi.Opt_Curve] (i=1~6).
The relationship between the setting and the characteristics curve is shown in the table below.
Instantaneous characteristics
Definite-time characteristics
[x.50/51Pi.t_Op]
I
[x.50/51Pi.I_Set]
Inverse-time characteristics
When I>[x.50/51Pi.I_Set], phase overcurrent protection begins to accumulate, and the operating
time is affected by the applied current I. The operating time will decrease with the current
increasing, but the operating time shall not less than the setting [x.50/51Pi.tmin] (i=1~6). The
inverse-time operating characteristics equation is:
Where:
3 [x.50/51Pi.tmin]
I
[x.50/51Pi.I_Set] ID
When the applied current is not a fixed value, but changes with the time, the operating behavior of
inverse-time phase overcurrent protection is shown in the following equation.
Where:
Instantaneous characteristics
Definite-time characteristics
When I<0.95×[x.50/51Pi.I_Set], phase overcurrent protection drops out with a time delay
[x.50/51Pi.t_DropOut], and the sequence diagram of definite-time dropout characteristic among
start signal, operating signal and the counter is as shown in Figure 3.10-9.
Start time
I>[x.50/51Pi.I_Set]
x.50/51Pi.St
3
x.50/51Pi.Op
Operating counter
[x.50/51Pi.t_DropOut]
[x.50/51Pi.t_DropOut] [x.50/51Pi.t_DropOut]
Dropout time
Dropout time
Inverse-time characteristics
If I<0.95×[x.50/51Pi.I_Set], phase overcurrent protection begins to drop out, and the dropout
characteristics meets the following equations.
Where:
tr is the dropout time coefficient, it is the dropout time required when the current drops to 0 after
phase overcurrent protection operates.
tr
I
[x.50/51Pi.I_Set]
The sequence diagram of inverse-time dropout characteristics among start signal, operating
signal and the counter is shown in Figure 3.10-11.
Start time
I>[x.50/51Pi.I_Set]
x.50/51Pi.St
x.50/51Pi.Op
[x.50/51Pi.t_Op]
Phase overcurrent protection operating
3
Operating counter
Dropout time
Dropout time
50/51P
x.50/51Pi.in_I3P x.50/51Pi.On
x.50/51Pi.Enable x.50/51Pi.Blocked
x.50/51Pi.Block x.50/51Pi.Valid
x.50/51P.VCE.in_U3P .
x.50/51P.DIR.in_U3P .
x.50/51P.DIR.in_I3P .
x.50/51P.HMB.in_I3P x.50/51P.DIR.FwdDir.Op
x.50/51P.DIR.RevDir.Op
x.50/51P.HMB.Op
3 7 x.50/51P.HMB.in_I3P
Three-phase current data input for harmonic control element of phase
overcurrent protection
3.10.4 Logic
SET Ia>[x.50/51Pi.I_Set]
EN [x.50/51Pi.En_Volt_Blk]
SIG X.50/51P.DIR.FwdDir.Op_A
selection
Direction
SIG x.50/51P.DIR.RevDir.Op_A
EN [x.50/51Pi.En_Hm_Blk]
t
t 3
SIG x.50/51Pi.Pkp &
x.50/51Pi.Op.PhA
SET [x.50/51Pi.Opt_Trp/Alm]=Trp
&
x.50/51Pi.Alm_A
SET [x.50/51Pi.Opt_Trp/Alm]=Alm
SIG x.50/51Pi.StA
>=1
SIG x.50/51Pi.StB x.50/51Pi.St
SIG x.50/51Pi.StC
SIG x.50/51Pi.Op.PhA
>=1
SIG x.50/51Pi.Op.PhB x.50/51Pi.Op
SIG x.50/51Pi.Op.PhC
SIG x.50/51Pi.Alm_A
>=1
SIG x.50/51Pi.Alm_B x.50/51Pi.Alm
SIG x.50/51Pi.Alm_C
3.10.5 Settings
Table 3.10-3 Settings of phase overcurrent protection
3 6 x.50/51P.DIR.phi_Min_Fwd 10~90 ° 90
The minimum boundary in
forward direction of phase
overcurrent protection
The maximum boundary in
7 x.50/51P.DIR.phi_Max_Fwd 10~90 ° 90 forward direction of phase
overcurrent protection
The minimum boundary in
8 x.50/51P.DIR.phi_Min_Rev 10~90 ° 90 reverse direction of phase
overcurrent protection
The maximum boundary in
9 x.50/51P.DIR.phi_Max_Rev 10~90 ° 90 reverse direction of phase
overcurrent protection
The voltage polarization
mode of direction control
element
Upp: phase-to-phase
Upp voltage is used as polarized
10 x.50/51P.DIR.Opt_PolarizedVolt Up - Upp voltage
U1 Up: phase-to-ground voltage
is used as polarized
voltage
U1: positive-sequence
voltage is used as polarized
The minimum operating
11 x.50/51P.DIR.I_Min 0.050~1.000 In 0.05 current setting of direction
control element
The minimum operating
12 x.50/51P.DIR.U_Min 1.000~10.000 V 4 voltage setting of direction
control element
Enabling/Disabling phase
overcurrent protection with
Disabled
13 x.50/51P.DIR.En_VTS_Blk - Disabled direction control element is
Enabled
blocked by VT circuit failure
when VT circuit supervision
PhaseBlk,
blocking mode 3
PhaseBlk: phase blocking
16 x.50/51P.HMB.Opt_Blk CrossBlk, - PhaseBlk
CrossBlk: cross blocking
MaxPhaseBlk
MaxPhaseBlk: maximum
phase blocking
The current setting for stage
0.050~200.00
17 x.50/51Pi.I_Set A 15 i of phase overcurrent
0
protection (i=1~6)
The operating time delay for
0.000~100.00
18 x.50/51Pi.t_Op s 0.1 stage i of phase overcurrent
0
protection (i=1~6)
The dropout time delay for
0.000~100.00
19 x.50/51Pi.t_DropOut s 0 stage i of phase overcurrent
0
protection (i=1~6)
Enabling/Disabling stage i of
Disabled phase overcurrent protection
20 x.50/51Pi.En_Volt_Blk - Disabled
Enabled controlled by voltage control
element (i=1~6)
The option direction
NonDirectional
characteristic for stage i of
21 x.50/51Pi.Opt_Dir Forward - NonDirectional
phase overcurrent protection
Reverse
(i=1~6)
Enabling/Disabling stage i of
Disabled phase overcurrent protection
22 x.50/51Pi.En_Hm_Blk - Disabled
Enabled controlled by harmonic
control element (i=1~6)
Enabling/disabling stage i of
Disabled
23 x.50/51Pi.En - Enabled phase overcurrent protection
Enabled
(i=1~6)
Enabling/disabling stage i of
phase overcurrent protection
Trp
24 x.50/51Pi.Opt_Trp/Alm - Trp operate to trip or alarm
Alm
(i=1~6)
Trp: for tripping purpose
Earth fault protection can operate to trip or alarm and can be enabled or disabled via the settings
or the signals, for some specific applications, earth fault protection needs to be blocked by the
external signal, so the device provides an input signal to be used to block earth fault protection.
EN [x.50/51Gi.En] &
x.50/51Gi.On
SIG x.50/51Gi.Enable
&
SIG x.50/51Gi.Block >=1 x.50/51Gi.Blocked
SIG Fail_Device
&
x.50/51Gi.Valid
SET [x.50/51Gi.Opt_Trp/Alm]=Alm
-U0
[x.50/51G.DIR.phi_Min_Fwd]
Non-operating I0
area
Operating area in
[x.50/51G.DIR.phi_Max_Rev] forward direction
[x.50/51G.DIRRCA]
Operating area in
reverse direction
[x.50/51G.DIR.phi_Max_Fwd]
Non-operating
area
[x.50/51G.DIR.phi_Min_Rev]
The following table shows the relationship among the operating current, the polarized voltage and
the polarization mode.
Polarization Polarized
Operating current Angle difference
mode voltage
Calculated residual current:
- 3U0 Angle=Angle(-3U0)-Angle(3I0_Cal)-RCA
Zero-sequence 3I0_Cal
voltage polarized Measured residual current:
- 3U0 Angle=Angle(-3U0)-Angle(3I0_Ext)-RCA
3I0_Ext
The logic of forward direction element and reverse direction element are shown in Figure 3.11-4.
EN [x.50/51G.En_VTS_Blk] &
>=1
SIG x.VTS.Alm
Forward direction
& >=1
x.50/51G.DIR.FwdDir.Op
criterion
3 SIG x.3U0_Cal
BI x.BI_En_VT &
EN x.En_VT
EN [x.50/51G.En_VTS_Blk] &
>=1
SIG x.VTS.Alm
& >=1
x.50/51G.DIR.RevDir.Op
criterion
SIG x.3U0_Cal
BI x.BI_En_VT &
EN x.En_VT
Where:
Harmonic control element based on zero-sequence current can be used to prevent earth fault
protection from maloperation due to inrush current. Zero-sequence current can be calculated or
measured. When the percentage of second harmonic component to fundamental component in
residual current is greater than the setting [x.50/51G.HMB.K_Hm2], harmonic control element
operates to block earth fault protection if the corresponding setting [x.50/51Gi.En_Hm_Blk] is set
as "Enabled" (i=1~6). When the fundamental component of zero-sequence current is greater than
the setting [x.50/51G.HMB.I_Rls], earth fault protection will be unblocked by harmonic control
element. The logic of harmonic control element is shown in Figure 3.11-5.
SET x.3I0>[x.50/51G.HMB.I_Rls]
Harmonic
criterion
SET x.3I0_2nd/3I0>[x.50/51G.HMB.K_Hm2] 3
Figure 3.11-5 Logic of harmonic control element
Where:
Earth fault protection can operate instantaneously or with a fixed time delay. It can also operate
with inverse-time characteristics, and its characteristics curve complies with the standards IEC
60255-3 and ANSI C37.112. Earth fault protection can support definite-time characteristics, IEC &
ANSI standard inverse-time characteristics and user-defined inverse-time characteristics, which
are determined by the setting [x.50/51Gi.Opt_Curve] (i=1~6). The relationship between the setting
and the characteristics curve is shown in the table below.
[x.50/51Gi.Alpha] are valid, and the inverse-time operating curve is determined by the three
settings.
Instantaneous characteristics
Definite-time characteristics
t
3
[x.50/51Gi.t_Op]
I0
[x.50/51Gi.3I0_Set]
Inverse-time characteristics
When x.3I0>[x.50/51Gi.3I0_Set], earth fault protection begins to accumulate, and the operating
time is affected by the applied current x.3I0. The operating time will decrease with the current
increasing, but the operating time shall not less than the setting [x.50/51Gi.tmin] (i=1~6). The
inverse-time operating characteristics equation is:
Where:
[x.50/51Gi.tmin]
I0
[x.50/51Gi.3I0_Set] ID
When the applied residual current is not a fixed value, but changes with the time, the operating
behavior of inverse-time earth fault protection is shown in the following equation.
Where:
The supported dropout characteristics of earth fault protection include instantaneous, definite-time
and ANSI inverse-time characteristics. When the operating characteristics curve is selected as
definite-time, IEC inverse-time or user-defined inverse-time characteristics, the dropout
characteristic curve can only be selected as instantaneous or definite-time characteristics, and the
alarm signal "Fail_Settings" will be issued and the device will be blocked if ANSI inverse-time
characteristics is selected. When the operating characteristics curve is selected as ANSI
inverse-time characteristics, the dropout characteristic curve can be selected as instantaneous,
definite-time and ANSI inverse-time characteristics.
Instantaneous characteristics
Definite-time characteristics
When x.3I0<0.95×[x.50/51Gi.3I0_Set], earth fault protection drops out with a time delay
[x.50/51Gi.t_DropOut], and the sequence diagram of definite-time dropout characteristic among
start signal, operating signal and the counter is as shown in Figure 3.11-8.
Start time
x.3I0>[x.50/51Gi.3I0_Set]
3
x.50/51Gi.St
x.50/51Gi.Op
Operating counter
[x.50/51Gi.t_DropOut]
[x.50/51Gi.t_DropOut] [x.50/51Gi.t_DropOut]
Dropout time
Dropout time
Inverse-time characteristics
If x.3I0<0.95×[x.50/51Gi.3I0_Set], earth fault protection begins to drop out, and the dropout
characteristics meets the following equations.
Where:
tr is the dropout time coefficient, it is the dropout time required when the current drops to 0 after 3
earth fault protection operates.
tr
I0
[x.50/51Gi.3I0_Set]
The sequence diagram of inverse-time dropout characteristics among start signal, operating
signal and the counter is shown in Figure 3.11-10.
Start time
x.3I0>[x.50/51Gi.3I0_Set]
x.50/51Gi.St
x.50/51Gi.Op
3 [x.50/51Gi.t_Op]
Earth fault protection operating
Operating counter
Dropout time
Dropout time
50/51G
x.50/51Gi.in_I3P x.50/51Gi.On
x.50/51Gi.in_I1P x.50/51Gi.Blocked
x.50/51Gi.Enable x.50/51Gi.Valid
x.50/51Gi.Block x.50/51Gi.St
X.50/51G.DIR.in_I3P x.50/51Gi.Op
x.50/51G.DIR.in_I1P x.50/51Gi.Alm
x.50/51G.DIR.in_U3P x.50/51G.DIR.FwdDir.Op
x.50/51G.HMB.in_I3P x.50/51G.DIR.RevDir.Op
x.50/51G.HMB.in_I1P x.50/51G.HMB.Op
3.11.4 Logic
SET x.3I0>[x.50/51Gi.3I0_Set]
EN [x.50/51Gi.En_Hm_Blk]
SIG x.50/51Gi.Pkp
&
x.50/51Gi.Op
SET [x.50/51Gi.Opt_Trp/Alm]=Trp
&
x.50/51Gi.Alm
SET [x.50/51Gi.Opt_Trp/Alm]=Alm
3.11.5 Settings
3 IECE
IECST
IECLT
IECDefTime
UserDefine
The option of dropout
characteristics curve for
stage i of earth fault
protection (i=1~4
Inst
Inst: instantaneous dropout
22 x.50/51Gi.Opt_Curve_DropOut DefTime - Inst
characteristics
IDMT
DefTime: definite-time
dropout characteristics
IDMT: inverse-time dropout
characteristics
Time multiplier setting for
stage i of inverse-time
23 x.50/51Gi.TMS 0.040~20.000 - 1
earth fault protection
(i=1~4)
The minimum operating
time for stage i of
24 x.50/51Gi.tmin 0.000~10.000 s 0.02
inverse-time earth fault
protection (i=1~4
The constant “K” for stage i
of customized inverse-time
25 x.50/51Gi.K 0.0010~120.0000 - 0.14
earth fault protection
(i=1~4)
The constant “α” for stage i
of customized inverse-time
26 x.50/51Gi.Alpha 0.0100~3.0000 - 0.02
earth fault protection
(i=1~4)
The constant “C” for stage i
27 x.50/51Gi.C 0.0000~1.0000 - 0 of customized inverse-time
earth fault protection
3
The symbol ”x” represents some side of transformer defined by user
through PCS-Studio software, which may be “HVS”, “MVS”, “LVS”, “LVS2”,
by default.
Negative-sequence overcurrent protection can operate to trip or alarm and can be enabled or
disabled via the settings or the signals, for some specific applications, negative-sequence
overcurrent protection needs to be blocked by the external signal, so the device provides an input
signal to be used to block negative-sequence overcurrent protection.
EN [x.50/51Qi.En] &
x.50/51Qi.On
SIG x.50/51Qi.Enable
&
SIG x.50/51Qi.Block >=1 x.50/51Qi.Blocked
SIG Fail_Device
&
x.50/51Qi.Valid
SET [x.50/51Qi.Opt_Trp/Alm]=Alm
-U2
[x.50/51Q.DIR.phi_Min_Fwd]
Non-operating I2
area
[x.50/51Q.DIR.phi_Max_Rev]
Operating area in
forward direction
[x.50/51Q.DIR.RCA]
Operating area in
reverse direction
[x.50/51Q.DIR.phi_Max_Fwd]
Non-operating
area
[x.50/51Q.DIR.phi_Min_Rev]
The following table shows the relationship among the operating current, the polarized voltage and
the polarization mode.
Polarized
Polarization mode Operating current Angle difference
voltage
Negative-sequence
Negative-sequence current: I2 -U2 Angle=Angle(-U2)-Angle(I2)-RCA
voltage polarized
The logic of forward direction element and reverse direction element are shown in Figure 3.12-4.
EN [x.50/51Q.En_VTS_Blk] &
3
>=1
SIG x.VTS.Alm
SIG x.I2
Forward direction
& >=1
criterion
x.50/51Q.DIR.FwdDir.Op
SIG x.U2
EN x.En_VT
EN [x.50/51Q.En_VTS_Blk] &
>=1
SIG x.VTS.Alm
SIG x.I2
Reverse direction
& >=1
criterion
x.50/51Q.DIR.RevDir.Op
SIG x.U2
EN x.En_VT
Negative-sequence overcurrent protection can operate instantaneously or with a fixed time delay.
It can also operate with inverse-time characteristics, and its characteristics curve complies with
the standards IEC 60255-3 and ANSI C37.112. Negative-sequence overcurrent protection can
support definite-time characteristics, IEC & ANSI standard inverse-time characteristics and
user-defined inverse-time characteristics, which are determined by the setting
[x.50/51Qi.Opt_Curve] (i=1 or 2). The relationship between the setting and the characteristics
curve is shown in the table below.
3 ANSIE
ANSIV
ANSI Extremely inverse
ANSI Very inverse
28.2
19.61
2.0
2.0
0.1217
0.491
29.1
21.6
ANSIN ANSI Normal inverse 0.0086 0.02 0.0185 0.46
ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 4.85
ANSIDefTime ANSI Definite time - - - -
ANSILTE ANSI Long time extremely inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long time very inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long time inverse 0.086 0.02 0.185 4.6
IECN IEC Normal inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 -
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short time inverse 0.05 0.04 0 -
IECLT IEC Long time inverse 120.0 1.0 0 -
IECDefTime IEC Definite time - - - -
UserDefine Programmable
Instantaneous characteristics
Definite-time characteristics
[x.50/51Qi.t_Op]
I2
[x./51Qi.I2_Set]
Inverse-time characteristics
Where:
3 [x.50/51Qi.tmin]
I2
[x.50/51Qi.I2_Set] ID
When the applied negative-sequence current is not a fixed value, but changes with the time, the
operating behavior of inverse-time negative-sequence overcurrent protection is shown in the
following equation.
Where:
Instantaneous characteristics
Definite-time characteristics
Start time
x.I2>[x.50/51Qi.I2_Set]
x.50/51Qi.St 3
x.50/51Qi.Op
Operating counter
[x.50/51Qi.t_DropOut]
[x.50/51Qi.t_DropOut] [50/51Qi.t_DropOut]
Dropout time
Dropout time
Inverse-time characteristics
Where:
3 tr is the dropout time coefficient, it is the dropout time required when the current drops to 0 after
negative-sequence overcurrent protection operates.
tr
I2
[x.50/51Qi.I2_Set]
The sequence diagram of inverse-time dropout characteristics among start signal, operating
signal and the counter is shown in Figure 3.12-9.
Start time
x.I2>[x.50/51Qi.I2_Set]
x.50/51Qi.St
x.50/51Qi.Op
[x.50/51Qi.t_Op]
Negative-sequence overcurrent
protection operating
3
Operating counter
Dropout time
Dropout time
50/51Q
x.50/51Qi.in_I3P x.50/51Qi.On
x.50/51Qi.Enable x.50/51Qi.Blocked
x.50/51Qi.Valid
x.50/51Qi.Block
x.50/51Qi.St
x.50/51Q.DIR.in_I3P
x.50/51Qi.Op
x.50/51Q.DIR.in_U3P
x.50/51Qi.Alm
x.50/51Q.DIR.FwdDir.Op
x.50/51Q.DIR.RevDir.Op
3.12.4 Logic
SET x.I2>[x.50/51Qi.I2_Set]
x.50/51Qi.St
SIG x.50/51Q.FwdDir.Op
&
& Timer
selection
Direction
t
SIG x.50/51Q.RevDir.Op
t
SET [x.50/51Qi.Opt_Dir]
&
x.50/51Qi.Alm
SET [50/51Qx.Opt_Trp/Alm]=Alm
3.12.5 Settings
Table 3.12-3 Settings of negative-sequence overcurrent protection
3 overcurrent
protection (i=1 or 2)
The dropout time
delay for stage i of
11 x.50/51Qi.t_DropOut 0.000~100.000 s 0 negative-sequence
overcurrent
protection (i=1 or 2)
The option direction
characteristic for
NonDirectional
stage i of
12 x.50/51Qi.Opt_Dir Forward - NonDirectional
negative-sequence
Reverse
overcurrent
protection (i=1 or 2)
Enabling/disabling
stage i of
Disabled
13 x.50/51Qi.En - Enabled negative-sequence
Enabled
overcurrent
protection (i=1 or 2)
Enabling/disabling
stage i of
negative-sequence
overcurrent
protection operate to
Trp
14 x.50/51Qi.Opt_Trp/Alm - Trp trip or alarm (i=1 or
Alm
2)
Trp: for tripping
purpose
Alm: for alarm
purpose
ANSIE The option of
ANSIV operating
15 x.50/51Qi.Opt_Curve ANSIN - IECDefTime characteristics curve
ANSIM for stage i of
ANSIDefTime negative-sequence
3.13.1 Application
During overload operation of a power transformer, the generated large current may cause the
transformer temperature to rise. When the temperature is high, the internal insulation of the
transformer may be aged, thereby increasing the possibility of internal failure. Continued high
temperature can also degrade the quality of the transformer oil.
Thermal overload protection is to estimates the continuous heating content of the transformer. The
estimation is made based on the measured currents and the built thermal model of the transformer
with two time constants.
The device provide two methods to fulfill thermal overload protection, one is to calculate thermal
accumulation according the actual measured current, and the other is applied to the scenario with
oil temperature measurement, it is to calculate temperature difference between winding
temperature and oil temperature according to the measured currents and can gain winding
temperature based on the oil temperature acquired by external transducer.
1. Method 1
Two stages overload protection are available, one stage for alarm purpose and the other stage for
trip purpose. When the temperature increases to the alarm value, thermal overload protection
issues alarm signal to remind the operator for attention, and if the temperature continues to
increase to the trip value, thermal overload protection issues trip command.
There are four thermal overload protection elements at most equipped at each side of transformer.
Thermal overload protection adopts IEC 60255-8 as thermal time characteristic, and fundamental
current or 1st to 11th harmonic current is used for protection calculation.
The device provides a thermal overload model which is based on the IEC60255-8 standard.
Refer to IEC60255-8
t
3
Ip
P=—
IB
P = 0.0
P = 0.6
P = 0.8
P = 0.9
kIB I
There are two types of thermal time characteristic, cold start characteristic and hot start
characteristic. The thermal overload formulas are shown as below.
2
I eq
t ln Equation 3.13-1
2
I eq (k I B ) 2
2
I eq I 2p
t ln Equation 3.13-2
2
I eq (k I B ) 2
Where:
τ is the heating thermal time constant of the protected device, i.e. [x.49.Tau].
IP is the steady-state load current prior to the overload for a duration which would result in
constant thermal level (duration is greater than several time constant τ), which is memory current.
For cold start characteristic, it is zero.
ln is natural logarithm
The hot start characteristic is adopted in the device. The calculation is carried out at zero of IP, so
users need not to set the value of IP.
Tripping outputs of the protection is controlled by current, even if the thermal accumulation value
3 is greater than the setting for tripping, the protection drops off instantaneously when current
disappears. Alarm outputs of the protection is not controlled by current, and only if the thermal
accumulation value is greater than the setting for alarm, alarm output contacts, which can be
connected to block the auto-reclosure, will operate.
2. Method 2
The actual windings temperature can be gained by oil temperature, which is measured by external
transducer (PT100), plus temperature difference between windings temperature and oil
temperature, i.e.,
The temperature difference can be calculated according to the current, and is changed with the
current. When the current is increased from 0 to I, the temperature accumulation complies with
the following equation.
t
I
T _ Diff [ x.49.K _ T _ Diff ] ( ) ( 1 e Tau )
[ x.49.Ib _ Set ]
I
T _ Diff [ x.49.K _ T _ Diff ] ( )
[ x.49.Ib _ Set ]
Where:
t is time
According to the calculated windings temperature, the user can compare it with user-defined
temperature value, and can set stage and time delay to trip or alarm by user-defined logic.
49
X.49.in_I3P x.49.On
x.49.Enable x.49.Blocked
x.49.Block .
x.49.Clr .
.
x.49.T_Diff_B
x.49.T_Diff_C
3
3.13.5 Logic
3 EN [x.49.En_Trp] >=1
EN [x.49.En_Alm] &
x.49.On
SIG x.49.Enable
&
SIG x.49.Block >=1 x.49.Blocked
SIG Fail_Device
&
x.49.Valid
SIG x.49.in_I3P
SET [x.49.Ib_Set]
&
0 500ms &
x.49.Pkp
SIG x.49.On
FD.Pkp
SIG x.49.Valid
SIG x.49.Pkp
&
SIG x.49.in_I3P x.49.St
& Timer
SET [x.49.Ib_Set] t
x.49.Alm
t
EN [x.49.En_Alm]
& Timer
t
x.49.Op
t
EN [x.49.En_Trp]
SIG x.49.Clr
3.13.6 Settings
Table 3.13-3 Settings of thermal overload protection
5 x.49.K_T_Diff 0.000~200.000 - 30
The convertor coefficient from the current to the 3
temperature
The cooling mode of transformer, usually,
6 x.49.Alpha_Cold 1.000~2.000 - 2 natural cooling: 1.6
forced cooling: 2
Disabled Logic setting of enabling/disabling thermal overload
7 x.49.En_Trp - Disabled
Enabled protection for trip purpose
Disabled Logic setting of enabling/disabling thermal overload
8 x.49.En_Alm - Disabled
Enabled protection for alarm purpose
According to the tripping information from the device and the auxiliary information (the current and
the position) of target circuit breaker, breaker failure protection constitutes the criterion to
discriminate whether the target circuit fails to open. If the criterion is confirmed, breaker failure
protection will operate to trip the target circuit breaker with the time delay [x.50BF.t_ReTrp], trip it
again with the time delay [x.50BF.t1_Op] and trip the adjacent circuit breakers with the time delay
[x.50BF.t2_Op]. As a special backup protection, breaker failure protection can quickly isolate the
fault, reduce the affected range by the fault, keep system stability and prevent generators,
transformers and other primary equipments from seriously damaged.
For non phase-segregated tripping system, breaker failure protection provides three-phases
re-trip function. When breaker failure protection receives initiating signal of three-phases tripping
and phase overcurrent element of any phase operates, the device will issue three-phases tripping
command to re-trip the target circuit breaker with the time delay [x.50BF.t_ReTrp]. In order to
improve the sensitivity, both zero-sequence overcurrent element and negative-sequence
overcurrent element are added, which can be enabled or disabled by the settings
[x.50BF.En_3I0_3P] and [x.50BF.En_I2_3P]. In order to avoid undesired operating of breaker
failure protection and reduce the affected range, three-phases re-trip does not block AR.
As similar as three-phase re-trip, the device will operate to re-trip the target circuit breaker again
with the time delay [x.50BF.t1_Op] when the relevant operating criterion is satisfied.
As similar as three-phase re-trip, the device will operate to trip the adjacent circuit breakers with
the time delay [x.50BF.t2_Op] when the relevant operating criterion is satisfied.
Where:
= A, B or C
Where:
Where:
is negative-sequence current
For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal "x.50BF.ExTrp_WOI" is equipped to initiate breaker failure protection, once the input signal 3
is energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker
failure current check to trigger breaker failure timer. The device takes current as priority with CB
auxiliary contact " x.50BF.52b" as an option criterion for breaker failure check.
When the initiating signal of breaker failure protection is energized for longer than 10s, an alarm
signal "50BF.Alm_Init" will be issued, and will drop out with a time delay of 10s.
50BF
x.50BF.in_I3P x.50BF.On
x.50BF.Enable x.50BF.Blocked
x.50BF.Block x.50BF.Valid
x.50BF.ExTrpA x.50BF.St
x.50BF.ExTrpB x.50BF.StA
x.50BF.ExTrpC x.50BF.StB
x.50BF.ExTrp3P x.50BF.StC
x.50BF.ExTrp_WOI x.50BF.Op_ReTrpA
x.50BF.52b x.50BF.Op_ReTrpB
x.50BF.Op_ReTrpC
x.50BF.Op_ReTrp3P
x.50BF.Op_t1
x.50BF.Op_t2
x.50BF.Alm_Init
3.14.4 Logic
EN [x.50BF.En] &
x.50BF.On
SIG x.50BF.Enable
&
SIG x.50BF.Block >=1 x.50BF.Blocked
SIG Fail_Device
&
x.50BF.Valid
SIG x.50BF.Valid
SIG x.50BF.Alm_Init
EN [x.50BF.En_ReTrp]
EN [x.50BF.En_3I0_1P] >=1
SET x.3I0>[x.50BF.3I0_Set]
& &
SIG x.50BF.ExtTrpA [x.50BF.t_ReTrp] 0 x.50BF.Op_ReTrpA
& &
SIG x.50BF.ExtTrpB [x.50BF.t_ReTrp] 0 x.50BF.Op_ReTrpB
3 SET x.IB>[x.50BF.I_Set] x.50BF.StB
& &
SIG x.50BF.ExtTrpC [x.50BF.t_ReTrp] 0 x.50BF.Op_ReTrpC
SET x.IC>[x.50BF.I_Set]
>=1 x.50BF.StC
EN [x.50BF.En_Ip]
SET x.IA>[x.50BF.I_Set]
>=1
SET x.IB>[x.50BF.I_Set] &
& [x.50BF.t_ReTrp] 0 x.50BF.Op_ReTrp3P
SET x.IC>[x.50BF.I_Set]
SIG x.50BF.Op_ReTrp3P
&
EN [x.50BF.En_3I0_3P] &
>=1
SET x.3I0>[x.50BF.3I0_Set]
>=1 &
& >=1 [x.50BF.t1_Op] 0 x.50BF.Op_t1
EN [x.50BF.En_I2_3P] &
SET x.I2>[x.50BF.I2_Set]
SIG x.50BF.ExtTrp_WOI
>=1
& x.50BF.St
EN [x.50BF.En_CB_Ctrl]
SIG x.50BF.52b
EN [x.50BF.En_t1]
&
[x.50BF.t2_Op] 0 x.50BF.Op_t2
EN [x.50BF.En_t2]
3.14.5 Settings
Table 3.14-3 Settings of breaker failure protection
The device can provide two stages of phase overvoltage protection with independent logic. When
a high voltage occurs in the system, phase overvoltage protection will operate to isolate the fault
from the system after a time delay if the voltage is greater than the setting. In addition, phase
overvoltage protection also provides the alarm function to notify that there is the overvoltage in the
system and find the cause timely to prevent from further deterioration of the fault.
3 Each stage of phase overvoltage protection can be independently set as definite-time
characteristics or inverse-time characteristics. The dropout characteristics can be set as
instantaneous dropout and definite-time dropout.
Phase voltage or phase-to-phase voltage can be selected to be used by the protection calculation
via the setting [x.59P.Opt_Up/Upp]. “1-out-of-3” or “3-out-of-3” logic can be selected for the
protection criterion. (1-out-of-3 means any of three phase voltages, 3-out-of-3 means all three
phase voltages)
Phase overvoltage protection can be enabled or disabled via the settings or the signals, for some
specific applications, phase overvoltage protection needs to be blocked by the external signal, so
the device provides an input signal to be used to block phase overvoltage protection.
EN [x.59Pi.En] &
x.59Pi.On
SIG x.59Pi.Enable
&
SIG x.59Pi.Block >=1 x.59Pi.Blocked
SIG Fail_Device
&
x.59Pi.Valid
SET x.Ua>[x.59Pi.U_Set]
>=1
SET x.Ub>[x.59Pi.U_Set] &
SET x.Uc>[x.59Pi.U_Set]
SET [x.59P.Opt_1P/3P]=1P
SET x.Uc>[x.59Pi.U_Set]
&
SET x.59P.Opt_Up/Upp=Up FD.Pkp 3
SIG x.59Pi.On
SIG x.59Pi.Valid
SET [x.59Pi.Opt_Trp/Alm]=Alm
SET x.Uab>[x.59Pi.U_Set]
>=1
SET x.Ubc>[x.59Pi.U_Set] &
SET x.Uca>[x.59Pi.U_Set]
SET [x.59P.Opt_1P/3P]=1P
SET x.Uca>[x.59Pi.U_Set]
&
SET x.59P.Opt_Up/Upp=Upp FD.Pkp
SIG x.59Pi.On
SIG x.59Pi.Valid
SET [x.59Pi.Opt_Trp/Alm]=Alm
Phase overvoltage protection can operate with a fixed time delay. It can also operate with
inverse-time characteristics, and its characteristics curve complies with the standards IEC
60255-3 and ANSI C37.112. Phase overvoltage protection can support definite-time
characteristics, IEC & ANSI standard inverse-time characteristics and user-defined inverse-time
characteristics, which are determined by the setting [x.59Pi.Opt_Curve] (i=1 or 2). The
relationship between the setting and the characteristics curve is shown in the table below.
Definite-time characteristics
3 When x.U>[x.59Pi.U_Set], phase overvoltage protection operates with a time delay [x.59Pi.t_Op],
the operating characteristics curve is as shown in Figure 3.15-3.
[x.59Pi.t_Op]
U
[x.59Pi.U_Set]
Inverse-time characteristics
When x.U>[x.59Pi.U_Set], phase overvoltage protection begins to accumulate, and the operating
time is affected by the applied voltage x.U. The operating time will decrease with the voltage
increasing, but the operating time shall not less than the setting [x.59Pi.tmin] (i=1 or 2). The
inverse-time operating characteristics equation is:
Where:
[x.59Pi.tmin]
U
[x.59Pi.U_Set] UD
When the applied voltage is not a fixed value, but changes with the time, the operating behavior of
inverse-time phase overvoltage protection is shown in the following equation.
Where:
The supported dropout characteristics of phase overvoltage protection include instantaneous and
definite-time characteristics.
Instantaneous characteristics
Definite-time characteristics
Start time
x.U>[x.59Pi.U_Set]
3 x.59Pi.St
x.59Pi.Op
Operating counter
[x.59Pi.t_DropOut]
[x.59Pi.t_DropOut] [x.59Pi.t_DropOut]
Dropout time
Dropout time
59P
x.59Pi.in_U3P x.59Pi.On
x.59Pi.Enable x.59Pi.Blocked
x.59Pi.Enable x.59Pi.Valid
x.59Pi.St
x.59Pi.StA
x.59Pi.StB
3
x.59Pi.StC
x.59Pi.Op
X.59Pi.Op.PhA
x.59Pi.Op.PhB
x.59Pi.Op.PhC
x.59Pi.Alm
3.15.4 Logic
SET x.Ua>[x.59Pi.U_Set]
>=1
SET x.Ub>[x.59Pi.U_Set] &
SET x.Uc>[x.59Pi.U_Set]
SET [x.59P.Opt_1P/3P]=1P
x.59Pi.St
SET [x.59P.Opt_1P/3P]=3P >=1
& & Timer
SET x.Ua>[x.59Pi.U_Set] t
&
3 SET x.Ub>[x.59Pi.U_Set]
t
SET x.Uc>[x.59Pi.U_Set]
SET x.59P.Opt_Up/Upp=Up
SIG x.59Pi.Pkp
&
x.59Pi.Op
SET [x.59Pi.Opt_Trp/Alm]=Trp
&
x.59Pi.Alm
SET [x.59Pi.Opt_Trp/Alm]=Alm
SET x.Uab>[x.59Pi.U_Set]
>=1
SET x.Ubc>[x.59Pi.U_Set] &
SET x.Uca>[x.59Pi.U_Set]
SET [x.59P.Opt_1P/3P]=1P
x.59Pi.St
SET [x.59P.Opt_1P/3P]=3P >=1
& & Timer
SET x.Uab>[x.59Pi.U_Set] t
&
t
SET x.Ubc>[x.59Pi.U_Set]
SET x.Uca>[x.59Pi.U_Set]
SET x.59P.Opt_Up/Upp=Upp
SIG x.59Pi.Pkp
&
x.59Pi.Op
SET [x.59Pi.Opt_Trp/Alm]=Trp
&
x.59Pi.Alm
SET [x.59Pi.Opt_Trp/Alm]=Alm
3.15.5 Settings
Table 3.15-3 Settings of phase overvoltage protection
The device can provide two stages of residual overvoltage protection with independent logic.
When the residual voltage is greater than the setting, residual overvoltage protection will operate
to isolate the fault from the system after a time delay. In addition, residual overvoltage protection
also provides the alarm function to notify that there is an earth fault leading to residual voltage
generation, and find the cause timely to prevent from further deterioration of the fault.
EN [x.59Gi.En] &
x.59Gi.On
SIG x.59Gi.Enable
&
SIG x.59Gi.Block >=1 x.59Gi.Blocked
SIG Fail_Device
&
x.59Gi.Valid
SET [x.59Gi.Opt_3U0]=Ext
SIG x.59Gi.On
SIG x.59Gi.Valid
&
FD.Pkp
SET [x.59Gi.Opt_Trp/Alm]=Alm
[x.59Gi.t_Op]
U0
[x.59Gi.3U0_Set]
Instantaneous characteristics
Definite-time characteristics
Start time
x.3U0>[x.59Gi.3U0_Set]
x.59Gi.St
x.59Gi.Op
3
[x.59Gi.t_Op] Residual overvoltage
protection operating
Operating counter
[x.59Gi.t_DropOut]
[x.59Gi.t_DropOut] [x.59Gi.t_DropOut]
Dropout time
Dropout time
59G
x.59Gi.in_U3P x.59Gi.On
x.59Gi.in_U1P x.59Gi.Blocked
x.59Gi.Enable x.59Gi.Valid
x.59Gi.Block x.59Gi.St
x.59Gi.Op
x.59Gi.Alm
3.16.4 Logic
3
SET x.3U0_Cal> [x.59Gi.3U0_Set] & x.59Gi.St
&
SET [x.59G.Opt_3U0]=Cal &
[x.59Gi.t_Op] 0
SET x.3U0_Ext> [x.59Gi.3U0_Set] &
SET [x.59Gi.Opt_3U0]=Ext
&
x.59Gi.Alm
SET [x.59Gi.Opt_Trp/Alm]=Alm
3.16.5 Settings
Table 3.16-3 Settings of residual overvoltage protection
Phase voltage or phase-to-phase voltage can be selected to be used by the protection calculation
via the setting [x.27P.Opt_Up/Upp]. “1-out-of-3” or “3-out-of-3” logic can be selected for the
protection criterion. (1-out-of-3 means any of three phase voltages, 3-out-of-3 means all three
phase voltages). The circuit breaker position with/without the current condition can be as an
auxiliary criterion for phase undervoltage protection, which can be configured via the setting
[x.27P.Opt_LogicMode].
EN [x.27Pi.En] &
x.27Pi.On
SIG x.27Pi.Enable
&
SIG x.27Pi.Block >=1 x.27Pi.Blocked
SIG Fail_Device
&
x.27Pi.Valid
Phase undervoltage protection can be enabled or disabled via the settings or the signals, for
some specific applications, phase undervoltage protection needs to be blocked by the external
signal, so the device provides an input signal to be used to block phase undervoltage protection.
SET [x.27P.Opt_1P/3P]=3P
&
SET [x.27P.Opt_Up/Upp]=Upp
SET x.Uab<[x.27Pi.U_Set]
&
SET x.Ubc<[x.27Pi.U_Set]
SET x.Uca<[x.27Pi.U_Set]
>=1
&
SET [x.27P.Opt_1P/3P]=1P
SET x.Uab<[x.27Pi.U_Set]
>=1
SET x.Ubc<[x.27Pi.U_Set]
SET x.Uca<[x.27Pi.U_Set]
SET [x.27P.Opt_1P/3P]=3P
&
SET [x.27P.Opt_Up/Upp]=Up
SET x.Ua<[x.27Pi.U_Set]
&
SET x.Ub<[x.27Pi.U_Set] >=1
>=1 Voltage criterion
SET x.Uc<[x.27Pi.U_Set]
&
SET [x.27P.Opt_1P/3P]=1P
SET x.Ua<[x.27Pi.U_Set]
>=1
SET x.Ub<[x.27Pi.U_Set]
SET x.Uc<[x.27Pi.U_Set]
SET [x.27P.Opt_LogicMode]=None
>=1
&
>=1 3
SET [x.27P.Opt_LogicMode]=CurrOrCBPos
&
&
SET [x.27P.Opt_LogicMode]=CurrAndCBPos
&
EN [x.27Pi.En_VTS_Blk]
SIG x.27Pi.On
SIG x.27Pi.Valid
SET [x.27Pi.Opt_Trp/Alm]=Alm
Phase undervoltage protection can operate with a fixed time delay. It can also operate with
inverse-time characteristics, and its characteristics curve complies with the standards IEC
60255-3 and ANSI C37.112. Phase overvoltage protection can support definite-time
characteristics, IEC & ANSI standard inverse-time characteristics and user-defined inverse-time
characteristics, which are determined by the setting [x.27Pi.Opt_Curve] (i=1 or 2). The
relationship between the setting and the characteristics curve is shown in the table below.
Definite-time characteristics
When U<[x.27Pi.U_Set], phase undervoltage protection operates with a time delay [x.27Pi.t_Op],
the operating characteristics curve is as shown in Figure 3.17-3.
3 t
[x.27Pi.t_Op]
U
[x.27Pi.U_Set]
Inverse-time characteristic
Where:
[x.27Pi.tmin]
U
UD [x.27Pi.U_Set]
When the applied voltage is not a fixed value, but changes with the time, the operating behavior of
inverse-time phase undervoltage protection is shown in the following equation.
Where:
Instantaneous characteristics
Definite-time characteristics
time delay [x.27Pi.t_DropOut], and the sequence diagram of definite-time dropout characteristic
among start signal, operating signal and the counter is as shown in Figure 3.17-5.
Start time
x.U<[x.27Pi.U_Set]
x.27Pi.St
3
x.27Pi.Op
Operating counter
[x.27Pi.t_DropOut]
[x.27Pi.t_DropOut] [x.27Pi.t_DropOut]
Dropout time
Dropout time
27P
x.27Pi.in_U3P x.27Pi.On
x.27Pi.Enable x.27Pi.Blocked
x.27Pi.Block x.27Pi.Valid
x.27Pi.St
x.27Pi.StA
x.27Pi.StB 3
x.27Pi.StC
x.27Pi.Op
X.27Pi.Op.PhA
x.27Pi.Op.PhB
x.27Pi.Op.PhC
x.27Pi.Alm
3.17.4 Logic
SIG x.27Pi.On
&
3 SIG x.27Pi.Pkp
x.27Pi.Op
SET [x.27Pi.Opt_Trp/Alm]=Trp
&
x.27Pi.Alm
SET [x.27Pi.Opt_Trp/Alm]=Alm
3.17.5 Settings
Table 3.17-3 Settings of phase undervoltage protection
3 12 x.27Pi.Opt_Curve_DropOut
Inst
- Inst
undervoltage protection
(i=1 or 2)
DefTime
Inst: instantaneous
dropout characteristics
DefTime: definite-time
dropout characteristics
Time multiplier setting
for stage i of
13 x.27Pi.TMS 0.040~20.000 - 1 inverse-time phase
undervoltage protection
(i=1 or 2)
The minimum operating
time for stage i of
14 x.27Pi.tmin 0.030~10.000 s 0.03 inverse-time phase
undervoltage protection
(i=1 or 2)
The constant “K” for
stage i of customized
15 x.27Pi.K 0.0010~120.0000 - 0.14 inverse-time phase
undervoltage protection
(i=1 or 2)
The constant “α” for
stage i of customized
16 x.27Pi.Alpha 0.0100~3.0000 - 0.02 inverse-time phase
undervoltage protection
(i=1 or 2)
The constant “C” for
stage i of customized
17 x.27Px.C 0.0000~1.0000 - 0 inverse-time phase
undervoltage protection
(i=1 or 2)
Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load. The increase of frequency indicates that
the output power of the system is much larger than that of the load. When the system frequency is
greater than the predefined setting, the overfrequency protection will operate for removing some
part of active power supplies from the system.
The device can provide two stages of overfrequency protection. If the system frequency is greater
than the setting, overfrequency protection will operate to remove some part of active power
3
supplies from the system. Overfrequency protection is with independent definite-time
characteristics and with instantaneous dropout characteristics.
Overfrequency protection can be enabled or disabled by the settings and the signals. For some
specific applications, overfrequency protection needs to be blocked by the external signal, so the
device provides an input signal to be used to block overfrequency protection.
EN [81Oi.En] &
81Oi.On
SIG 81Oi.Enable
&
SIG 81Oi.Block >=1 81Oi.Blocked
SIG Fail_Device
&
81Oi.Valid
SIG 81Oi.Valid
Overfrequency protection supports definite-time characteristics complied with IEC 60255-3 and
ANSI C37.112. If the system frequency is greater than the setting [81Oi.f_Set], overfrequency
protection will operate with a time delay [81Oi.t_Op].
3 [81Oi.t_Op]
f
[81Oi.f_Set]
81O
81Oi.In_U3P 81Oi.On
81Oi.Enable 81Oi.Blocked
81Oi.Block 81Oi.Valid
81Oi.St
81Oi.Op
3.18.4 Logic
SET Upp_min>[81.Upp_Blk]
&
[81Oi.t_Op] 0 81Oi.Op
3
SIG 81Oi.Pkp
3.18.5 Settings
Table 3.18-3 Settings of overfrequency protection
Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load. The decrease of frequency indicates that
the output power of the system is much less than that of the load. When the system frequency is
less than the predefined setting, the underfrequency protection will operate for shedding some
part of loads from the system.
The device can provide four stages of underfrequency protection. If the system frequency is less
than the setting, underfrequency protection will operate to shedding some part of loads from the
system. Underfrequency protection is with independent definite-time characteristics and with
instantaneous dropout characteristics.
Underfrequency protection can be enabled or disabled by the settings and the signals. For some
specific applications, underfrequency protection needs to be blocked by the external signal, so the
device provides an input signal to be used to block underfrequency protection.
EN [81Ui.En] &
81Ui.On
SIG 81Ui.Enable
&
SIG 81Ui.Block >=1 81Ui.Blocked
SIG Fail_Device
&
3 81Ui.Valid
SIG 81Ui.Valid
Underfrequency protection supports definite-time characteristics complied with IEC 60255-3 and
ANSI C37.112. If the system frequency is greater than the setting [81Ui.f_Set], underfrequency
protection will operate with a time delay [81Ui.t_Op].
[81Ui.t_Op]
f
[81Ui.f_Set]
81U
81Ui.in_U3P 81Ui.On
81Ui.Enable 81Ui.Blocked
81Ui.Block 81Ui.Valid
81Ui.St
81Ui.Op
3.19.4 Logic
3 SET Upp_min>[81.Upp_Blk]
&
[81Ui.t_Op] 0 81Ui.Op
SIG 81Ui.Pkp
3.19.5 Settings
Table 3.19-3 Settings of underfrequency protection
VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,
poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
not be issued when the following cases happen.
1. Bus VT or bay VT is used as protection VT and the protected bus or bay is out of service.
2. Only current protection functions are enabled and VT is not connected to the device.
VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection
VT. Under normal condition, the device continuously supervises input voltage from VT, VT circuit
failure signal will be activated if residual voltage exceeds the threshold value or positive-sequence
voltage is lower than the threshold value. If the device is under pickup state due to system fault or
other abnormality, VT circuit supervision will be disabled.
Under normal conditions, the device detect residual voltage greater than the setting 3
[x.VTS.3U0_Set] to determine single-phase or two-phase VT circuit failure, and detect three times
positive-sequence voltage less than the setting [x.VTS.U1_Set] to determine three-phase VT
circuit failure. Upon detecting abnormality on VT circuit, an alarm will comes up after a time delay
of [x.VTS.t_DPU] and drop off with a time delay of [x.VTS.t_DDO] after VT circuit restored to
normal.
VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [x.VTS.MCB_VT] is energized), the device will
consider the VT circuit is not in a good condition and issues an alarm without a time delay. If the
auxiliary contact is not connected to the device, VT circuit supervision will be issued with time
delay as mentioned in previous paragraph.
When VT is not connected into the device, the alarm will be not issued if the logic setting [x.En_VT]
is set as "0". However, the alarm is still issued if the binary input [x.VTS.MCB_VT] is energized, no
matter that the logic setting [x.En_VT] is set as "0" or "1".
When neutral VT fails, third harmonic of residual voltage is comparatively large. If third harmonic
amplitude of residual voltage is larger than the setting [x.VTNS.3U0_Hm3_Set] and without
operation of fault detector element, neutral VT failure alarm signal [x.VTNS.Alm] will be issued
after a time delay of [x.VTS.t_DPU] and drop off with a time delay of [x.VTS.t_DDO] after three
phases voltage restored to normal.
VTS VTNS
x.VTS.in_U3P x.VTNS.Enable
x.VTS.in_I3P x.VTNS.Block
x.VTS.Enable
x.VTS.Block
x.VTS.MCB_VT
3 x.VTS.in_52b_a
x.VTS.in_52b_b
x.VTS.in_52b_b
3.20.4 Logic
&
SIG FD.Pkp
SET x.3U0>[x.VTS.3U0_Set]
>=1
SET x.U1<[x.VTS.U1_Set] &
>=1 If "FD.Pkp" operates, the circuit of time
SET [x.VTS.Opt_VT]=Bay & delay will be interrupted.
[x.VTS.t_DPU] [x.VTS.t_DDO]
SIG 52b (Three phases) >=1
&
SIG x.Ip > 0.04In
>=1
BI [x.BI_En_VT] >=1
3
x.VTS.Alm
EN [x.En_VT]
EN [x.VTS.En]
&
SIG x.VTS.Enable
SIG x.VTS.Block
&
SIG FD.Pkp
BI [x.BI_En_VT]
EN [x.VTNS.En]
&
SIG x.VTNS.Enable
SIG x.VTNS.Block
If fault detector element operates or automatic reclosing cycle is in progress, and VT circuit failure
signal have been detected, then the VT circuit failure signal will be maintained, only when the fault
detector element and automatic reclosing element are all drop-off, VT circuit supervision will
return to normal operation.
3.20.5 Settings
Output map controls tripping outputs of protection elements and programmable logics. Each
protection element has its corresponding tripping logic setting used to configure tripping output
contacts, and 120 tripping outputs of programmable logics are equipped for visual logic
programming.
Each protection element can control total 32 groups of tripping output contacts by tripping logic
settings. Therefore, the user can configure the tripping output contacts of each protection element
individually though the corresponding tripping logic setting. 32 groups of independent tripping
output contacts can be defined to trip HV side, MV side, and LVS side etc. Each group of tripping
contacts can correspond to certain amount of contacts on binary output plug-in modules.
Tripping logic settings are used to specify which breakers will be tripped when some protection
element operates. This logic setting comprises 32 binary bits as follows and is expressed by a
hexadecimal number of 8 digits from 00000000H to FFFFFFFFH. The tripping logic setting is
specified as follows:
“Output001” just means to drive 1st group of tripping output contacts and please refer to Chapter
“Hardware”. The tripping outputs are recorded as “Output001_OutMap ~ Output032_OutMap” by
the device when they operate, and “Outputxxx” (xxx=001, 002…032) represents “trip output xxx”
(xxx=001, 002…032). The circuit breaker corresponding with bit which is set as “1” will be tripped.
Tripping output logic settings should be set on basis of application-specific drawings.
The device provides 120 programmable trip output with I/O signals and settings for users used by
visualization programming.
For example, if it is required to set stage 1 of phase overcurrent protection at HV side of the
transformer operate to issue trip command after its operation criterion is satisfied “AND” receiving
a binary input which can be a blocking signal from other device, programmable trip output can
complete the function configuration as following steps.
2. Connect final output of programming logic to input signal of programmable trip output.
3. Set corresponding tripping logic setting of programmable trip output to complete the function
configuration.
3.21.3 Settings
3 Table 3.21-2 Settings of programmable trip output
4 Control Functions
Table of Contents
List of Figures
Figure 4.2-1 Relationship between reference and synchronous voltages ....................... 4-10
Figure 4.3-1 Voltage connection for double busbar arrangement ..................................... 4-15
4 Figure 4.3-2 Voltage connection for one and a half breakers arrangement ..................... 4-15
Figure 4.3-3 Voltage switching for double bus bar arrangement ....................................... 4-17
Figure 4.3-4 Voltage switching for 3/2 breakers arrangement (closing a bus CB) .......... 4-17
Figure 4.3-5 Voltage switching for 3/2 breakers arrangement (closing the tie CB) ......... 4-18
List of Tables
Table 4.2-1 Input signals of manual closing synchronism check ...................................... 4-11
Table 4.2-2 Output signals of manual closing synchronism check ................................... 4-12
A control command can realize various control signals such as the CB/DS/ES opening/closing. In
order to ensure the reliability of the control output, a locking circuit is added to each control object.
The operation is strictly in accordance with the selection, check and execution steps, to ensure 4
that the control operation can be safely and reliably implemented. In addition, the device has a
hardware self-checking and blocking function to prevent hardware damage from maloperation
output.
When the device is in the remote-control mode, the control command may be sent via the IEC
60870-5-103 or IEC 61850 protocol; when it is in the local control mode, the local operation may
be performed on the device LCD or panel handle.
3. If the selection is successful, the protocol module sends an execution command, otherwise it
sends a cancel command;
When the device is in the maintenance status, it can still respond to local control commands.
The switchgear control function can cooperate with functions such as synchronism check and
interlocking criteria calculation to complete the output of the corresponding operation command. It
can realize the normal control output in one bay and the interlocking and programmable logic
configuration between bays.
Module Description
CSWI Control of circuit breaker (CB), disconnector switch (DS) or earthing switch (ES)
RMTLOC Remote or local control mode
XCBR Synthesis of CB position, three-phase or phase separated
Module Description
XSWI Synthesis of DS/ES position
SXCBR/SCSWI Trip statistics of CB/DS/ES
RSYN Synchronism check for CB closing
CILO Interlocking logic for CB/DS/ES control
MCSWI Manual control of CB/DS/ES
The initiation of a control command may be sent to the device by the SCADA or the NCC through
protocol IEC 60870-5-103 or IEC 61850. It may also be the operation of the device LCD or the
manual triggering through configured signal. The command is sent by the CPU to the control
module for processing, and a control record is made on the CPU module according to the control
result.
4
SCADA/NCC IEC 60870-5-103
CPU
CSWI BO
IEC 61850
Control
Record
Local LCD
BI contact
Since the source of a control command may be SAS or NCC, or may be triggered by the device
LCD or terminal contact, it is necessary to provide a remote/local control mode switch function.
The remote/local control mode switch function determines whether the device is in the remote or
the local control permission state through the configuration of terminal contact, function key, or
binary signal. Each control object provides a remote/local input, and the control module
determines the current control authority to be remote or local according to the input value. By
default, if the input is not configured, any control operation is blocked.
A double point status (DPS), which usually indicates switchgear status, can be derived from 2
ordinary binary inputs. The signification of a DPS is shown in the following table. For switchgear
4
status, only the 2 statuses "01" and "10" indicating respectively the positions opening and closing
are valid. The other 2 statuses "00" and "11", i.e. intermediate or bad status, will cause the alarm
"DPS.Alm".
The unit also supports the DPS synthesis through switchgear opening and closing positions after
jittering processing. The synthetic DPS contains original SOE timestamp. The CB control function
supports phase-separated position inputs and can synthesize these inputs into general position.
In accordance with the control object, the DPS synthesis function is divided into 2 modules: XCBR
and XSWI. The XCBR is mainly used for CB position synthesis, including phase-separated
positions, while the XSWI is used DS or ES position synthesis.
The trip statistics function takes the opening position as input count the trip times. For CB, this
device supports phase-separated and general trip statistics. The tripping statistics function is
triggered by DPS change. The statistics result is stored in non-volatile memory for power-off
holding.
Use the clear command from the menu in local LCD or customized binary signal to reset the trip
statistics.
4.1.2.4 Interlocking
The interlocking function will influence the control operation output. When the function is enabled,
the device determines whether the control operation is permitted based on the interlocking logic
result. Each control object is equipped with an independent interlocking logic which supports
unlocking operation through a binary signal.
The interlocking function is very important for the control operation of switchgears. During the
operation of primary equipment, the positions of the relevant equipment must be correct for
operation permission. For remote control, i.e. command from SAS or NCC, this device could
judge the interlocking logic depending on the message within the command; for local control
through device LCD or terminal contact, please use the corresponding logic setting to
enable/disable the interlocking function.
The switchgear control function supports manual control function that can be configured with a
terminal contact or binary signal to trigger the control operation.
The manual control function supports the control input configuration of selection and open/close.
When the control object selection input is configured, the signal "1" indicates that the current
control object has to be selected before a control operation; if the control object selection input is
not configured, the control command can be directly issued without judgment of selection.
4 4.1.2.6 Direct Control
For applications such as signal reset and function enable/disable, the control mode is generally
direct control, i.e. execution without selection before, direct control with normal security in IEC
61850.
The direct control function provides remote/local switch and interlocking configurations. The
control command is usually issued directly by the SAS. It also supports the command triggered by
binary signal.
CSWI:XCBR CSWI:XSWI
in_Remote in_Remote
in_Local in_Local
in_Pos_NO in_Pos_NO
in_Pos_NC
in_Pos_NC
in_Pos_A_NO
in_N_Trp
in_Pos_A_NC
in_EnaOpn
in_Pos_B_NO
in_Pos_B_NC in_EnaCls
in_Pos_C_NO in_CILO_Bypass
in_Pos_C_NC in_Manual_Sel 4
in_N_Trp
in_Manual_Opn
in_N_Trp_A
in_Manual_Cls
in_N_Trp_B
in_N_Trp_C
in_Rsyn
in_EnaOpn
in_EnaCls
in_CILO_Bypass
in_Manual_Sel
in_Manual_Opn
in_Manual_Cls
4.1.5 Logics
SIG DPS_A = ON
&
DPS = ON
SIG DPS_B = ON
SIG DPS_C = ON
SET [CSWI**.DPS.En_Alm]
≥1 CSWI** interlocking
function activated
Local command from device LCD
SIG with "InterlockChk"
≥1
&
Contact triggered manual
SIG opening/closing operation
EN [CSWI**.En_Opn_Blk] ≥1
EN [CSWI**.En_Cls_Blk]
SIG in_Manual_Opn=1
≥1
SIG in_Manual_Opn=1
& Opn_Exec_Man
SIG Opn_Enabled =1
SIG in_Manual_Cls=1
≥1
SIG in_Manual_Cls=1
& Cls_Exec_Man
SIG Cls_Enabled =1
4.1.6 Settings
Table 4.1-4 Settings of control function
When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus, closing operation is
applied with the synchronism check to avoid this situation and maintain the system stability. The
synchronism check includes synchro-check and dead charge check.
The comparative relationship between the reference voltage and the synchronization voltage for
synchro-check is as follow. Furthermore, the measured three-phase voltages for synchro-check
should not exceed the overvoltage threshold [25.U_OV] or lag the undervoltage threshold
[25.U_UV].
U_Ref
U_Syn
This figure shows the characteristics of synchro-check element used for CB closing if both
4 reference and synchronous sides are live. The element operates if the voltage difference,
frequency difference, slip frequency difference and phase angle difference are all within their
setting ranges.
The difference between the reference voltage and the synchronization voltage is checked by
the following equation
The frequency difference between the reference side and the synchronization side is
checked by the following equation
|f(U_Ref)-f(U_Syn)| ≤ [25.f_Diff]
df/dt ≤ [25.df/dt]
The phase difference between the reference voltage and the synchronization voltage is
checked by the following equation
∆δ ≤ [25.phi_Diff]
The dead charge check mode checks only the synchro-check voltage. Several dead charge check
modes are supported in using the setting [25.Opt_Mode_DdChk]. The device compares the
reference side and the synchronous side voltages at both sides of circuit breaker with the settings
[25.U_LvChk] and [25.U_DdChk]. When the voltage is higher than [25.U_LvChk], the
corresponding side is regarded as live. When the voltage is lower than [25.U_DdChk], the
corresponding side is regarded as dead.
The synchronism check function is suitable for several applications. According to different
applications, user needs to configure different voltage input channel. For both the reference side
and the synchronous side, the voltage input channel may be single phase or three-phase.
While configuring through the PCS-Studio software, use the functional block MUX to synthesize a
three-phase voltage and input it for synchronism check.
MUX
In the meantime, the voltage switching logic can be adopted for the synchronism check input
channel, please refer to the following section.
4
For synchronism check voltage input channel configuration, please MAKE
SURE that the voltage source to connect to the inputs "in_ref" and
"in_syn" should be the same with that used in measurement function,
such as BayMMXU and UMMXN. Otherwise, the alarm "25.Alm_Cfg_Ch"
will be issued.
RSYN
in_ref
in_syn
in_25_Blk
in_DL_Blk
in_DB_Blk
in_SYN_Blk
in_25_Bypass
in_syn_chk
in_Dd_chk
4.2.4 Logics
SIG in_25_Blk
SIG in_SYN_Blk
SET Δf ≤ [25.f_Diff]
SET Δδ ≤ [25.phi_Diff]
SIG in_25_Blk
SIG in_DL_Blk
SIG in_DB_Blk
SET Value.[25.Opt_Mode_DdChk]
4.2.5 Settings
Table 4.2-3 Settings of synchronism check
25.Opt_Mode_DdChk
1 SynDdRefDd Dead check for both the reference and the synchronization sides
2 SynLvRefDd Live check for synchronization side and dead check for reference side
3 SynDdRefLv Dead check for synchronization side and live check for reference side
6 SynLvRefDd/SynDdRefLv Option 2 or 3
7 AnySideDd Option 1, 2 or 3
For double busbar arrangement, selection of appropriate voltage signals from Bus 1 and Bus
2 for synchronizing are required. Line VT signal is taken as reference to check synchronizing
with the voltage after voltage selection function. Selection approach is as follows.
Bus2
Bus1
DS1 DS2
UB1
UB2
DS1.DPS
CB.DPS CB
DS2.DPS
Ua
4
UL1 Ub
Line
Uc
For one and a half breakers arrangement, selection of appropriate voltage signals among
Line1 VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1
voltage signal for closing breaker at Bus 1 side.
Bus1
UB1
Bus1_CB.DPS Bus1_CB
Line 1
Ua
UL1 Ub
Uc DS1
DS1.DPS
Tie_CB.DPS Tie_CB
Line 2
UL2
DS2.DPS
DS2
Bus2_CB.DPS Bus2_CB
UB2
Bus2
Figure 4.3-2 Voltage connection for one and a half breakers arrangement
VolSwitch
in_UB1_Chn Ref_Chn
in_UB2_Chn Syn_Chn
in_UL1_Chn
in_UL2_Chn
in_Bus1_CB
in_Tie_CB
in_Bus2_CB
in_DS1
in_DS2
4.3.4 Logics
&
Alm_Invalid_Sel
UB1 U_Syn
UB2
SIG DS1.DPS=OFF
SIG Bus1_CB.DPS=ON
SIG DS2.DPS=ON
SIG DS2.DPS=OFF
SIG Bus2_CB.DPS=ON
UL1_Sel
&
UL2_Sel
&
UB2_Sel
&
Alm_Invalid_Sel
UL1 U_Ref
UL2
UB2
UB1 U_Syn
Figure 4.3-4 Voltage switching for 3/2 breakers arrangement (closing a bus CB)
UL1 Uref
UB1
UB2
&
>=1
& Alm_Invalid_Sel
Figure 4.3-5 Voltage switching for 3/2 breakers arrangement (closing the tie CB)
4.3.5 Settings
Table 4.3-3 Settings of voltage switching
contacts, carry inputs or DC measuring transducer input. The indicator supports phase-separated
inputs and discordance alarm.
The control of tap changer is treated as a special kind of binary output in this device. The binary
outputs "84.BO_StepDown", "84.BO_StepUp" and "84.BO_EmergStop" are used to descend,
raise and stop the tap changer in comply with the principle Selection Before Operation (SBO).
Additionally, during a tap changer control process, if the situation "sliding tap" occurs, the tap
changer is out of control, i.e. steps up/down continuously, the output "84.BO_Slide_Trip" is
provided to cut off the power supply of the tap changer's motor mechanism.
YLTC
in_Tap_Pos_01 Tap_Pos_01
in_Tap_Pos_02 Tap_Pos_02 4
in_Tap_Pos_03 Tap_Pos_03
in_Tap_BI_01 84.BO_Slide_Trip
in_Tap_BI_02 84.Alm_Unmatched
……
in_Tap_BI_26
4.4.4 Settings
Table 4.4-3 Settings of tap changer indicator
5 Measurement
Table of Contents
List of Figures
List of Tables
5.1 Overview
This device performs continuous measurement of the analogue input quantities. The current full
scale of relay is 40 times of rated current, and there is no effect to the performance of IED due to
overflowing of current full scale. The device samples 24 points per cycle and calculates the RMS
value in each interval and updated the LCD display in every 0.5 second. The measurement data
can be displayed on the LCD of the relay front panel or on the local/remote PC via software tool.
Navigate the menu to view the sampling value through LCD screen.
The symbol ”x” in the following measurement lists, represents some side
or bushing of transformer defined by user through PCS-Studio software, 5
which may be “HVS”, “MVS”, “LVS”, “HVS2”, “MVS2”, “LVS2”, “CWS”,
“HVB”, “MVB”, “LVB”, etc. If only one protection element is equipped, the
prefix “x.” may disappear.
1 f System frequency Hz
17 87W.Ang(Ia)_Br1-Brm Angle between phase-A currents of branch 1 and branch m (m= 2, 3, deg
5.4.8 Synchrocheck
Temperature (⁰C) 5
Tmax
P
Tmin Tp
ITransd (mA)
ip 20
O
In this example, the setting of the range for the scaled value goes from a usable range of 0mA to
+20mA. The measured value 0mA means a temperature of Tmin which is defined by the setting
[DCAI.Min_Transducer**] and the measured value 20mA signifies a temperature of Tmax which is
defined by the setting [DCAI.Max_Transducer**]. Thus, for the actual point P, the measured
transducer current ip can be converted into a value of temperature.
AnIn
in_dc01
in_dc02
in_dc03
in_dc04
in_dc05
in_dc06
in_dc07
in_dc08
5.5.4 Settings
Table 5.5-3 Settings of DC measuring transducers
6 Supervision
Table of Contents
List of Figures
List of Tables
6.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When the device is in energizing process before
the LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore,
the automatic supervision function, which checks the health of the protection system when startup
and during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.
All hardware has real-time monitoring functions, such as CPU module monitoring, communication
interface status monitoring, power supply status monitoring.
The monitoring function of CPU module also includes processor self-check, memory self-check
6
and so on. The processor self-check is checked by designing execution instructions and data
operations. Check whether the processor can execute all instructions correctly, and whether it can
correctly calculate complex data operations to determine whether it works normally. For
peripherals, it can monitor the status of the interface module, check the input and output data,
send the communication interface and receive self-loop detection. Memory self-check is used to
detect unexpected memory errors in the running process. It can effectively prevent program logic
abnormality caused by memory errors.
The status monitoring of communication interface also includes Ethernet communication interface
monitoring and differential channel communication interface monitoring. By accessing the status
register of the communication interface, the state of the corresponding interface is obtained, such
as the state of connection, the number of sending frames, the number of frames received, and the
number of wrong frames. According to the statistics of the acquired interface state, it is judged
whether the interface work is abnormal.
The hardware supervision also includes the power supply status monitoring. The voltage
monitoring chip is used by all the power supplies. The reset voltage threshold is preset to the reset
monitoring circuit. When the power supply is abnormal, the voltage monitoring chip will output the
reset signal to control CPU to be in the reset state and avoid the wrong operation.
In the process of operation, the safety allowance should always be kept and no overload
phenomenon is allowed. When the user configures logic components with PCS-Studio, the
PCS-Studio automatically calculates the time required for the theoretical execution of the
configured components. When the security limit is exceeded, the PCS-Studio will indicate that the
configuration error is not allowed to download the current configuration to the device.
During the operation of the device, there is a lot of data exchange between modules. The number
of data exchanges is related to the number of logical components configured by the user. When
the configuration is too large to cause the number of data exchange to exceed the upper limit
supported by the device, the PCS-Studio prompts the configuration error.
The initialization of the device depends on the configuration files of each module. The user
configured logical components will eventually be embodied in the configuration file, limited to the
hardware memory space. When the configuration file size is more than the upper limit, the
PCS-Studio prompts the configuration error.
The DDR3 memory chip has the function of ECC (Error Checking and Correcting) to eliminate
6 unexpected changes in memory caused by electromagnetic interference. The chip memory has
parity function. When an error occurs, the system can detect anomalies immediately, and
eliminate the logic abnormity caused by memory errors.
In addition to the above hardware memory reliability measures, the device software is also
constantly checking the memory during operation, including code, constant data, and so on. Once
the error detection, the system will automatically restart the restore operation. If they detect the
error immediately after the restart, it may be the result of a permanent fault locking device
hardware, only at the moment and not restart.
The reliability of the device is largely determined by the reliability of the export drive. By reading
the driving state of the binary output relay, the alarm signal will be generated and the device is
immediately blocked to prevent the relay from maloperation when the device is not given a
tripping order and the binary output relay driver is detected in the effective state.
The CPU chip needs to be able to ensure long-term stability under the permissible working
temperature of the specification. Therefore, it is necessary to monitor the working temperature
monitored by CPU.
The device CPU module stores the configuration check codes of other modules. In initialization
procedure, it checks whether the configuration check code of each module is consistent with the
stored code in CPU module, and if it is not consistent, this device is blocked.
2. The hardware modules and process interface versions need to be consistent with the CPU
module.
If the system is incompatible with the upgrade, it will upgrade the internal interface version. At this
moment, each hardware module and process will be upgraded synchronously, otherwise the
version of the interface will be inconsistent.
The configuration text formed by the device calibration visualization project includes checking
whether the check code is wrong or not.
4. Whether any setting is over the range, whether it needs to confirm the settings.
6
If the setting exceeds the configuration range, the device is blocked; if some settings are added, it
is necessary to confirm the new values through the LCD.
In the operation procedure, the CPU module sends a time synchronization command to other
module, each module repeats heartbeat message to the CPU module, if it does not respond or the
heartbeat is abnormal, then this device is blocked.
2. Check whether the settings of other modules are consistent with the CPU module.
The actual values of all the settings in the CPU module are initialized to send to the corresponding
slave modules. In the process of operation, the setting values stored in the CPU module and the
setting values of other modules will be checked one by one. If they are not consistent, this device
will issue the alarm signal "Fail_Settings".
The sampling circuit of this device is designed as dual-design scheme. Each analog sampling
channel is sampled by two groups of ADC. The sampling data is self checking and inter checking
in real time. If any sampling circuit is abnormal, the device reports the alarm signal "Alm_Sample",
and the protection function related to the sampling channel is disabled at the same time. When
the sampling circuit returns to normal state, the related protection is not blocked after 10s.
The secondary circuit supervision function includes current transformer supervision (CTS),
voltage transformer supervision (VTS), power supply supervision of binary inputs and
tripping/closing circuit supervision.
The purpose of the CTS is to detect whether the current transformer circuit is failed. In some
cases, if the CT is failed (broken-conductor, short-circuit), related protective element should be
blocked for preventing this device from mal-operation.
The VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit
fault, poor contact of VT circuit, VT maintenance and so on. The device can detect the failure, and
6 then issue an alarm signal and block relevant function.
All binary inputs should setup necessary debounce time to prevent the device from undesired
operation due to transient interference or mixed connection of AC system and DC system. When
the duration of binary input is less than the debounce time, the state of the binary input will be
ignored. When the duration of binary input is greater than the debounce time, the state of the
binary input will be validated and wrote into SOE.
Binary input
state
In order to meet flexible configurable requirement for different project field, all binary inputs
provided by the device are configurable. Through the configuration tool, this device provides two
parameters to setup debounce time of delayed pickup and dropout based on specific binary
signal.
1. Type 1
This type of binary inputs includes enable/disable of protection functions, AR mode selection,
“BI_RstTarg”, “BI_Maintenance”, disconnector position, settings group switch, open and close
command of circuit breaker and disconnector, enable/disable of auxiliary functions (for
example, manually trigger recording). It is on the premise of reliability, and the debounce time
of delayed pickup and delayed dropout is recommended to set as 100ms at least.
2. Type 2
Debounce time
The debounce time of delayed pickup and delayed dropout is recommended to set as
15ms, in order to prevent binary signals from maloperation due to mixed connection of
AC system and DC system.
The debounce time of delayed pickup and delayed dropout is recommended to set as
(-t1+ t2+Time delay)≥15ms, in order to prevent binary signals from maloperation due to
mixed connection of AC system and DC system. Where, “t1” is the debounce time of
delayed pickup, and “t2” is the debounce time of delayed dropout.
3. Type 4
This type of binary inputs is usually used as auxiliary input condition, and the debounce time
of delayed pickup and delayed dropout is recommended to set as 5ms.
6
When users have their own reasonable setting principles, they can set the
debounce time related settings according to their own setting principles.
[Num_Blk_Jitter] N, times threshold to block binary input status change due to jitter
[Blk_Window_Jitter] T’, blocking window of binary input status change due to jitter
For a binary input voltage variation, if the jitter processing function is enabled, its handling
principle is:
1. During the T,
a) If the actual jitter times < N, the block will not be initiated and the status change of this
binary input will be considered.
b) If the actual jitter times ≥ N, the T’ is initiated, and the status change of binary input will
be ignored during the T’.
a) If the actual jitter times < N’, the block window will expire. The final status of this binary
input will be compared to the original one before T’, so as to determine whether there is a
change or not.
b) If the actual jitter times ≥ N’, the T’ will be initiated again immediately (i.e. restart the
timer), and the status change of binary input will be ignored during the next T’.
Debounce time
(rising edge)
n=N
initiate jitter block
③ Signal after
❶ ❷ ❸ ❹ ❺ debounce & jitter
n = N’ processing
n=5<N=7 Prolong blocking
window
T’
T’ t7 t8
t5 t6
t11
6
T T T’
t1 t2 t3 t4 t9 t10 t
②Green line Blocking signal of binary input status change due to jitter
③Blue line Binary input status after debounce and jitter processing
3. T = t2 - t1
a) n = 5 < N;
b) No blocking, ② stays at 0 and ③ is tracing the voltage variation to create SOE events.
4. T = t4 - t3, at t5
a) n = 7 = N;
c) Jitter blocking, no more SOE event, ② changes its status to 1 and ③ stops the tracing.
5. T’ = t6 - t5
a) At t7, n = 5 =N’, the processing prolongs the blocking immediately due to jitter;
b) Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status.
6. T’ = t8 - t7
a) At t9, n = 5 =N’, the processing prolongs the blocking immediately due to jitter.
b) Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status.
7. T’ = t10 - t9
6 a) n = 2 < N’;
b) At t10, jitter unblocking, ② changes its status to 0 and ③ keeps its status.
8. At t11
The tripping counter statistics function supports statistics of the tripping operation, such as circuit
breakers, disconnectors and so on. For phase separation circuit breaker, when the position of
phase A, B, and C is detected from close state to open state, the total position tripping counter is
added, and the tripping counter is added once when the position of the disconnector is detected
from close state to open state.
In addition, the statistics of the number of state change of circuit breakers and disconnectors are
also provided. The state change counter will add one when the position is detected from close
state to open state or from open state to close state.
Hardware circuit and operation status of this device are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts “BO_Fail” will be given. The
protective device then cannot work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.
If the device is blocked or alarm signal is sent during operation, please do find out its reason with
the help of self-diagnostic record. If the reason cannot be found at site, please notify the factory
NR. Please do not simply press button “TARGET RESET” on the protection panel or re-energize
on the device.
7 System Functions
Table of Contents
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
When the setting [Opt_TimeSyn] is set as "Conventional", the device can automatically identify
clock synchronization signal among IRIG-B, PPS, PPM and IEC1588. If IRIG-B, PPS, PPM and
IEC1588 exist at the same time, the device selects IRIG-B in priority. If PPS, PPM and IEC1588
exist at the same time, the device selects IEEE1588 in priority.
When the setting [Opt_TimeSyn] is set as "SAS", the device can automatically identify whether
there is valid hardware clock synchronization signal. The device selects hardware clock
synchronization signal or the combination of hardware clock synchronization signal plus software
clock synchronization signal in priority.
When the device adopts SNTP to realize clock synchronization, [IP_Server_SNTP] and
[IP_StandbyServer_SNTP] shall be set correctly.
[IP_Server_SNTP] is the address of SNTP clock synchronization server which sends SNTP timing
messages to the relay or BCU. [IP_StandbyServer_SNTP] is the address of standby SNTP clock
synchronization server.
When both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are set as "0.0.0.0", the device
receives broadcast SNTP synchronization message.
7.2.1 Overview
The device can provide real-time state information, including analog quantities (such primary
measurement value, secondary measurement value, metering value and so on) and status
quantities (supervision status, input status, output status and so on). By check these state
information, operators can know operation state of the protected equipment and whether the
device is healthy.
These state information can be gained via local HMI. The menu path is:
1. Analog quantities
2. Status quantities
Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.
Device's state information can be uploaded into clients through message communication. For
differential protocols, the state information can be gained through corresponding communication
service.
The device can print the current state information, so that the operator can observe and save the
current operation condition. The access path is:
7.3.1 Overview
The device can store the latest 1024 time-stamped disturbance records, 1024 time-stamped
binary events, 1024 time-stamped supervision events, 256 time-stamped control logs and 1024
time-stamped device logs. All the records are stored in non-volatile memory, and when the
available space is exhausted, the oldest record is automatically overwritten by the latest one.
When any protection element operates or drops out, such as fault detector, distance protection
etc., they will be logged in event records. Disturbance records include signal name, its value
before and after changing, and the time precision is up to 1ms.
The device is under automatic supervision all the time. If there are any failure or abnormal
7 condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records. Supervision events include signal name, its value before and after changing, and the
time precision is up to 1ms.
When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged in event records. Binary events include signal name, its value
before and after changing, and the time precision is up to 1ms.
If an operator executes some operations on the device, such as reboot protective device, modify
setting, etc., they will be logged in event records. Device logs include signal name, its value
before and after changing, and the time precision is up to 1ms.
When an operator executes a control command via local LCD, PCS-Studio or communication
client, it will be logged in control logs. Control logs include time stamp, controlled object, control
origination, control position, operation condition, interlocking condition, control command and
operation result.
The device provides corresponding menus to view event recorders. The menu path is:
Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.
Event recorders can be uploaded into clients through corresponding communication service of the
protocol (including IEC60870-5-103, IEC61850, DNP3.0).
The device can print event recorders, so that the operator can observe and save the current
operation condition. The access path is:
Fault recorder can be used to have a better understanding of the behavior of the power network
and related primary and secondary equipment during and after a disturbance. Analysis of the
recorded data provides valuable information that can be used to improve existing equipment. This
information can also be used when planning for and designing new installations.
The fault recorder is comprised of the report and the waveform, which can be triggered by pickup
signals, trip signals and configurable binary signal [BI_TrigDFR].
The fault memory of the device is automatically updated with every recording. When the fault
memory is filled completely, the oldest records are overwritten automatically. Thus, the most
recent recordings are always stored safely. The maximum number of recordings is 32.
1. Sequence number
Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.
The date and time is recorded when a system fault is detected. The time resolution is 1ms.
An operating time (not including the operating time of output relays) is recorded in the record. The
time resolution is 1ms.
4. Fault information
The overall duration of a single fault recording comprises the total duration of the configurable
recording criterion, the pre-trigger time and the post-trigger time. With the fault recording
parameter, these components can be individually set. The pre-trigger waveform recorded duration
is configured via the setting [RecDur_PreTrigDFR]. The waveform recorded duration after the fault
disappears is configured via the setting [RecDur_PostFault]. The maximum post-trigger waveform
7 recorded duration is configured via the setting [MaxRecDur_PostTrigDFR].
4. [MaxRecDur_PostTrigDFR]
Trigger point
The pickup recording time cannot be set. It continues as long as any valid trigger condition, binary
or analog, persists (unless limited by the limit time, which is determined by the setting
[MaxRecDur_PostTrigDFR]).
The recording time begins after all activated triggers are reset. Use the setting [RecDur_PostFault]
to set this time.
Use the setting [MaxRecDur_PostTrigDFR] to set this time. If the summation of pickup recording
time and post-fault recording time is larger than maximal post-trigger recording time, the
post-trigger recording time shall be equal to the setting [MaxRecDur_PostTrigDFR].
The device provides corresponding menus to check fault recording. The menu path is:
Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.
Fault recording can be uploaded into clients through corresponding communication service of the
protocol (including IEC60870-5-103, IEC61850, DNP3.0).
The device can print fault recording, so that the operator can observe and save the current
operation condition. The access path is:
The device provides maintenance state, i.e., the binary input [BI_Maintenance] is energized,
which is convenient for maintenance work. For adopting conventional CT/VT, binary inputs and
binary outputs, maintenance state has no influence on protection logics. For binary inputs and
binary outputs by GOOSE connections. During device maintenance, the object will send GOOSE
message with Test quality attribute. The Test quality attribute indicates to the receiver device that
the object received via a GOOSE message was created under test conditions and not operating
conditions. If the Test quality attribute received is different with the object's Test quality attribute,
binary inputs and binary outputs by GOOSE connections will be affected based on different types
of binary inputs and binary outputs. For SV (Sampling Value) message, if the Test quality attribute
received is different with the object's Test quality attribute, the relevant protection functions will be
blocked.
For IEC60870-5-103 protocol, only the messages in link layer maintained, service messages in
the application layer which is uploaded automatically are blocked, and service messages in the
application layer which is issued by the client are rejected. For IEC61850 protocol, all Test quality
attribute set as "1". For DNP3.0 and ModBus protocol, they are not affected.
The device provides Test Mode to allow all protection elements, supervision events and binary
events to fulfill communication test, but to avoid the output contacts to close. During
communication test, protection functions are not affected, the signals generated by
communication test are recorded in relevant reports, and event recording and fault recording will
not stop recording disturbance information. The alarm signal "Alm_CommTest" will be issued to
indicate the operator when activating Test Mode and exiting Test Mode.
Communication test can be gained via local HMI and the virtual HMI, the corresponding content
can be viewed through the following menu paths:
Events Simulation
Forced Measurements
If no input operation is carried out within 60s, this test will exit and return to
the previous menu automatically.
Output test can be gained via the local LCD or virtual HMI of a debugging PC, the corresponding
content can be viewed through the following menu paths:
Contacts Outputs
GOOSE Outputs
The device provides target reset which can be used to reset local signals (including magnetic
latching output relays), latched LEDs, and confirm pop-up windows of reports. The function does
not affect the protection logic and communication function. There are several ways to reset.
Press the command pushbutton “ESC”+“ENT” on operation panel of the device under
main interface
Press the command pushbutton " TARGET RESET" on operation panel of the device
For different applications users can save the respective function settings in so-called settings
groups, and if necessary enable them quickly. Up to 10 different settings groups can be saved in
the device. In the process, only one settings group is active at any given time. During operation,
the operator can switch between setting groups.
The device will be temporarily blocked during switching setting groups. During temporary device
blocking, the device will loss protection functions and communication functions. Alarm signals
"Fail_Device" and "Alm_Device" will be issued. There are several ways to switch setting groups.
Press the command pushbutton “MENU” under main interface (password is required)
There are 2 appropriate input signals available for switching setting group via binary inputs.
These input signals allow selection of the settings group via a binary code. If one of two
signals changes, the signal image present will result in switching over to the appropriate
settings group. If only 2 settings groups must be switched over, only 1 binary input is required.
The following table shows the possible binary codes and applicable setting groups.
8 Hardware
Table of Contents
List of Figures
Figure 8.1-3 Typical rear view of PCS-978S with ring ferrule .................................................. 8-3
Figure 8.1-4 Typical rear view of PCS-978S with pin ferrule .................................................... 8-3 8
Figure 8.2-1 Typical hardware configuration with ring ferrule (6U, 1/1) .................................. 8-4
Figure 8.2-2 Typical hardware configuration with ring ferrule (6U, 1/2) .................................. 8-4
Figure 8.2-3 Typical wiring with ring ferrule (6U, 1/1) .............................................................. 8-5
Figure 8.2-4 Typical wiring with ring ferrule ((6U, 1/2)) ............................................................ 8-6
Figure 8.2-5 Typical hardware configuration with pin ferrule (6U, 1/1) ................................... 8-7
Figure 8.2-6 Typical hardware configuration with pin ferrule (6U, 1/2) ................................... 8-7
Figure 8.2-7 Typical wiring with pin ferrule (6U, 1/1) ................................................................ 8-8
Figure 8.2-8 Typical wiring with pin ferrule (6U, 1/2) ................................................................ 8-9
Figure 8.4-10 View of binary input module (NR6610A and NR6610B) ............................... 8-23
List of Tables
Table 8.4-1 Terminal definition and description of power supply module ............................. 8-13
Table 8.4-2 Terminal definition and description of power supply module ............................. 8-14
Table 8.4-4 Terminal definition and description of binary input module ............................... 8-22
Table 8.4-5 Terminal definition and description of binary input module ............................... 8-24
8.1 Overview
The modular design of this device allows this device to be easily upgraded or repaired by a
qualified service person. The faceplate is hinged to allow easy access to the configurable
modules, and back-plugging structure design makes it easy to repair or replace any module.
This device adopts one 32-bit ARM core in the CPU chip as control core for management and
monitoring function, and adopts another 32-bit ARM core in the CPU chip for all the protection
calculation. The parallel processing of sampled data can be realized in each sampling interval to
ensure ultrahigh reliability and safety of the device.
This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference. See Figure 8.1-1 for the hardware diagram.
External
Binary Input
Pickup
Electronic/Optic CT/VT Relay
ETHERNET
+E
LCD
Clock SYN
Power
Uaux LED ARM2
Supply
RJ45
Keypad
PRINT
The working process of the device is as shown in above figure: the currents and voltages from
conventional CT/VT are converted into small voltage signal and sent to ARM1 core after filtered
and A/D conversion for protection calculation and fault detector respectively (electronic/optic
CT/VT signals are sent to the device without A/D conversion). The ARM1 core carries out fault
detector, protection logic calculation, tripping output, and the ARM2 core performs SOE 8
(sequence of event) record, waveform recording, printing, communication between the device and
SAS and communication between HMI and CPU. When the fault detector detects a fault and picks
up, the positive power supply for output relay is provided.
The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS S series based on microcomputer
are classified into standard and optional modules.
HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.
CPU module provides functions like communication with SAS, event record, setting
management etc., and performs filtering, sampling, protection calculation and fault detector
calculation.
AC AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.
BI module provides binary inputs via opto-couplers with rating voltage among AC110V/220V
or DC24V~250V (configurable).
BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.
PCS-978S is made of a 6U height 19” chassis. Components mounted on its front include a
320×240 dot matrix LCD, a 9 button keypad, four programmable buttons, 20 LED indicators and a
multiplex RJ45 port. A monolithic micro controller is installed in the device for these functions.
Following figures show front and rear views of this device respectively.
NR6106BA NR6641-6I6U NR6641-12I Option Option Option Option Option Option Option NR6601A NR6651A NR6305A
NET 05 Ic1 Ic1n 06 05 Ic1 Ic1n 06 05 BI_05 BI_06 06 05 BO_03 06 05 BI_COM BI_03 06
CONSOLE
Ground
Figure 8.2-1 Typical hardware configuration with ring ferrule (6U, 1/1)
CONSOLE
Ground
8
Figure 8.2-2 Typical hardware configuration with ring ferrule (6U, 1/2)
0201
0202
0203
0204
0205
0206
0207
0208
0209
0210
0211
0212
0215
0216
0217
0218
0219
0220
0221
0222
0223
0224
0213
0214
Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 Ua1 Ub1 Uc1 Ua2 Ub2 Uc2
BI_01 + 1301
To SCADA
…
BI_25 + 1325
1326 -
BI_01 + P101
- P102
BI_02 + P103
- P104
BI_03 + P106
1A 0101
COM
…
To the screen of other coaxial
2A 0104
COM
Console P121
BO_05 P122
1401 P123
1402 BO_01 BO_Fail P124
1403
1404 BO_02 P125 PWR+
Power External DC power
…
Grounding Bus
Ic4 Ib4 Ia4 Ic3 Ib3 Ia3 Ic2 Ib2 Ia2 Ic1 Ib1 Ia1
8
0414
0413
0424
0423
0422
0421
0420
0419
0418
0417
0416
0415
0412
0411
0410
0409
0408
0407
0406
0405
0404
0403
0402
0401
0201
0202
0203
0204
0205
0206
0207
0208
0209
0210
0211
0212
0215
0216
0217
0218
0219
0220
0221
0222
0223
0224
0213
0214
Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 Ua1 Ub1 Uc1 Ua2 Ub2 Uc2
BI_01 + 0501
To SCADA
…
BI_25 + 0525
0526 -
BI_01 + P101
- P102
BI_02 + P103
- P104
BI_03 + P106
1A 0101
COM
…
To the screen of other coaxial
2A 0104
COM
Console P121
BO_05 P122
0601 P123
0602 BO_01 BO_Fail P124
0603
0604 BO_02 P125 PWR+
Power External DC power
…
Grounding Bus
8
Figure 8.2-4 Typical wiring with ring ferrule ((6U, 1/2))
B01 B02 & B03 B04 & B05 B06 B07 B08 B09 B10 B11 B12 B13 B14 P1
NR6106BA NR6641-6I6U NR6641-12I Option Option Option Option Option Option Option NR6610A NR6660A NR6310A
CONSOLE
BI_32 34 BO17-COM 34
35 BO17-NO 35
BI_COM
36 BO17-NC 36 Ground
Figure 8.2-5 Typical hardware configuration with pin ferrule (6U, 1/1)
BI_17
BI_18
19
20
BO10
19
20
BO_04
19
20
21
8
BI_19 21 21 BO_05
BO11 22
BI_20 22 22
BI_21 23 23 23
BO12 BO_Fail
01 1A BI_22 24 24 24
02 1B
BI_23 25 25 PWR+ 25
03 SGND BO13
04 2A
BI_24 26 26 PWR- 26
05 2B BI_25 27 27
BO14
06 SGND BI_26 28 28
07 SYN+
BI_27 29 29
08 SYN- BO15
09 SGND
BI_28 30 30
10 SYN-TTL BI_29 31 BO16-COM 31
BI_30 32 BO16-NO 32
BI_31 33 BO16-NC 33
CONSOLE
BI_32 34 BO17-COM 34
35 BO17-NO 35
BI_COM
36 BO17-NC 36 Ground
Figure 8.2-6 Typical hardware configuration with pin ferrule (6U, 1/2)
0201
0202
0203
0204
0205
0206
0207
0208
0209
0210
0211
0212
0215
0216
0217
0218
0219
0220
0221
0222
0223
0224
0213
0214
Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 Ua1 Ub1 Uc1 Ua2 Ub2 Uc2
BI_01 + 1301
BI_02 + 1302
To SCADA
…
BI_16 + 1316
1317 -
1318 -
BI_17 + 1319
BI_18 + 1320
…
BI_32 + 1334
1A 0101
COM
1B 0102 1335 -
SGND 0103 1336 -
cable with single point earthing
BI_01 + P101
To the screen of other coaxial
2A 0104
COM
2B 0105 - P102
SGND 0106
BI_02 + P103 -
SYN+ 0107
Clock SYN
1401
1402 BO_01
BI_09 + P112
1403
1404 BO_02 P105
…
P113
1417 BO_01
BO_09 P114
1418
P115
1419 BO_02 P116
BO_10
…
1420
P121
1421 BO_05
BO_11 P122
1422
P123
…
8 1431
1432 BO_16
BO_16
BO_Fail
Power
P124
P125 PWR+
External DC power
1433
Supply P126 supply
1434 PWR-
1435 BO_17
1436 BO_17
Grounding Bus
Ic4 Ib4 Ia4 Ic3 Ib3 Ia3 Ic2 Ib2 Ia2 Ic1 Ib1 Ia1
0414
0413
0424
0423
0422
0421
0420
0419
0418
0417
0416
0415
0412
0411
0410
0409
0408
0407
0406
0405
0404
0403
0402
0401
0201
0202
0203
0204
0205
0206
0207
0208
0209
0210
0211
0212
0215
0216
0217
0218
0219
0220
0221
0222
0223
0224
0213
0214
Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 Ua1 Ub1 Uc1 Ua2 Ub2 Uc2
BI_01 + 0501
To SCADA
…
BI_16 + 0516
0517 -
0518 -
BI_17 + 0519
BI_18 + 0520
…
BI_32 + 0534
1A 0101
COM
1B 0102 0535 -
SGND 0103 0536 -
cable with single point earthing
BI_01 + P101
To the screen of other coaxial
2A 0104
COM
2B 0105 - P102
SGND 0106
BI_02 + P103 -
SYN+ 0107
Clock SYN
0601
0602 BO_01
BI_09 + P112
0603
0604 BO_02 P105
…
P113
0617 BO_01
BO_09 P114
0618
P115
0619 BO_02 P116
BO_10
…
0620
8
P121
0621 BO_05
BO_11 P122
0622
P123
…
0635 BO_17
0636 BO_17
Grounding Bus
8.3 CT Requirement
1. CT Types
Generally there are three types of CT: high remanence, low remanence and no remanence.
Low remanence: TPY, PR, and the residual magnetism does not exceed 10% of the
saturation flux.
The high residual magnetism CT may have large residual magnetism. When the fault
non-periodic component and residual magnetism are in the same direction, the CT saturation
degree will be more serious. The following CT type checking calculation takes into account
the maximum residual magnetism of CT and the maximum non periodic component on the
site.
2. CT Requirement
Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn
Esl4′ = k4×Ipcf4×Isn×(Rct+Rb)/Ipn
8 k1, k2, k3, k4 are transient factors.
Maximum fault current through two bridge CB but not transformer when
Ipcf2
out-zone fault (amps)
3. K Value Requirement
While: k1=2,k3=30,k4=1.
If both CTs of double CB are low remanence type, and with the same model, then k1=2,
k2=1.5, k3=30, k4=1.
Otherwise: k1=2,k2=2,k3=30,k4=1.
4. Example
= 30×5×(1+60/25)=510V
Esl1′ = k1×Ipcf1×Isn×(Rct+Rb)/Ipn
= 2×Ipcf1 ×Isn×(Rct+(Rr+2×RL))/Ipn
= 2×40000×5×(1+(0.1+2×0.5))/2000=420V
8
Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn
=30×1500*5*(1+(0.1+2×0.5)) /2000=236.25V
The +5Vdc output provides power supply for all the electrical elements that need +5Vdc power
supply in this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device
is in cold reserve.
Three types of power supply modules are provided: NR6305A, NR6305B and NR6310A. The
NR6305B is same as the NR6305A except that the NR6105B can support at least 500ms power
supply interruption.
The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure
binary output. A 26-pin connector is fixed on the power supply module. The terminal definition of
the connector is described as below.
8.4.2.2 NR6310A
The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure
binary output. A 22-pin connector and a 4-pin connector are fixed on the power supply module.
The terminal definition of the connector is described as below.
The PWR module a grounding screw for device grounding. The grounding
screw shall be connected to grounding screw and then connected to the
earth copper bar of panel via dedicated grounding wire.
EMI, so effective grounding must be ensured before the device is put into
service.
The CPU module is the central part of this device, and contains a multi-core 32-bit powerful
processor and some necessary electronic elements. This powerful processor performs all of the
functions for this device: protection function, communication function, human-machine interface
function and so on. There are several A/D conversion circuits on this module, which are used to
convert the AC analog signals to corresponding DC signals for fulfilling the demand of the
electrical level standard. A high-accuracy clock chip is contained in this module, it provide
accurate current time for this device.
The main functional details of the CPU module are listed as below:
The CPU module can calculate protective elements (such as overcurrent element) on the
basis of the analog sampled values (voltages and currents) and binary inputs, then it does
logical judgment function and decides whether the device needs to trip or close.
Communication function
The CPU module can effectively manage all communication procedures, and reliably send
out some useful information through its various communication interfaces. These interfaces
are used to communicate with a SAS or a RTU. It also can communicate with the human
machine interface module. If an event occurs (such as SOE, protective tripping event etc.),
this module will send out the relevant event information through these interfaces, and make it
be easily observed by the user.
Auxiliary calculation
Based on the voltage and current inputs, the CPU module also can calculate out the metering
values, such as active power, reactive power and power factor etc. All these values can be
sent to a SAS or a RTU through the communication interfaces.
This module can respond the commands from the keypad of this device and show the results
on the LCD and LED indicators of this device. It also can show the operation situation and 8
event information for the users through the LCD and LED indicators.
Time synchronization
This module has a local clock chip and an interface to receive time synchronized signals from
external clock source. These signals include PPS (pulse per second) signal and IRIG-B
signal. Basing on the timing message (from SAS or RTU) and the PPS signal, or basing on
the IRIG-B signal, this module can synchronize local clock with the standard clock.
Do NOT look into the end of an optical fiber connected to an optical port.
The configuration and terminal definition of the CPU modules are listed in following table
09 SGND
TTL 10 SYN-TTL Cable
The correct connection is shown in Figure 8.4-3. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.
B 02
COM
SGND 03
cable with single point earthing
To the screen of other coaxial
04
Clock SYN
SYN- 02
SGND 03
04
Cable
RTS 05
PRINT
TXD 06
SGND 07
The 2nd RS-485 port also can be configured as a printer port through the
The analog input module is applicable for power plant or substation with conventional VT and CT,
and it can transform high AC input values to relevant low AC output value, which are suited to the
analog inputs of the CPU module. The transformers are used both to step-down the currents and
voltages to levels appropriate to the device’s electronic circuitry and to provide effective isolation
between this device and the power system. A low pass filter circuit is connected to each
transformer (CT or VT) secondary circuit for reducing the noise of each analog AC input signal.
For the analog input module, if the plug is not put in the socket, external CT circuit is closed itself.
Just shown as below.
Plug
Socket
In
Out
In
8 Out
There are two types of analog input modules. The rated current is adaptive (1A/5A). Please
declare which kind of AI module is needed before ordering. Maximum linear range of the current
converter is 40In.
6CT+6VT
12CT
NR6641-6I6U NR6641-12I
01 I1 I1n 02 01 I1 I1n 02
03 I2 I2n 04 03 I2 I2n 04
05 I3 I3n 06 05 I3 I3n 06
07 I4 I4n 08 07 I4 I4n 08
09 I5 I5n 10 09 I5 I5n 10
11 I6 I6n 12 11 I6 I6n 12
13 U1 U1n 14 13 I7 I7n 14
15 U2 U2n 16 15 I8 I8n 16
17 U3 U3n 18 17 I9 I9n 18
19 U4 U4n 20 19 I10 I10n 20
21 U5 U5n 22 21 I11 I11n 22
23 U6 U6n 24 23 I12 I12n 24
Some connection examples of the current transformers and voltage transformers which are
supported by this relay are shown in this section. If one of the analog inputs has no input in a
practical engineering, the relevant input terminals should be disconnected. 8
1. Current connections examples
A B C A B C
Ia Ia
Ian Ian
Ib Ib
Ibn Ibn
Ic Ic
Icn Icn
I01
I01n I01
(1) I01n
A B C (3)
Ia
Ian
Ib I0s
Ibn I0sn
Ic
(4)
Icn
I01 I02
I01n I02n
(2) (5)
Where:
(1) Current connections to three current transformers with a star-point connection for ground
current (zero sequence current or residual current).
(2) Current connections to three current transformers with a separate ground current
transformer (summation current transformer or core balance current transformer).
(3) Current connections to two current transformers with a separate ground current
transformer (summation current transformer or core balance current transformer), only
for ungrounded or compensated networks.
(4) Current connection to a core balance neutral current transformer for sensitive ground
8 fault detection, only for ungrounded or compensated networks.
A B C A B C
Ux
52 52 52 Ux 52 52 52
Uxn
Uxn
Ua Ua
Ub Ub
Uc Uc
Un Un
U0 U0
U0n U0n
(1) (2)
Where:
There are three kinds of BI modules available, NR6601A, NR6610A and NR6610B. The binary
input module can respectively provide 25 or 32 binary inputs, the supported rated voltages of
binary inputs are listed in Section Technical Data.
The rated voltage of binary input is optional: 24Vdc, 30Vdc, 48Vdc, 110Vdc, 8
125Vdc, 220Vdc, 110Vac or 220Vac (@50Hz), which must be specified
when placed order. It is necessary to check whether the rated voltage of
binary input module complies with site DC power supply rating before put
this device in service.
8.4.5.1 NR6601A
Each BI module is with a 26-pin connector for 25 binary inputs which share one common negative
power input and can be configurable. The pickup voltages and dropout voltages of the binary
inputs are settable by the setting [xx.U_Pickup_BI] and [xx.U_Dropoff_BI], and the range is from
50%Un to 80%Un.
01 BI_01 BI_02 02
03 BI_03 BI_04 04
05 BI_05 BI_06 06
07 BI_07 BI_08 08
09 BI_09 BI_10 10
11 BI_11 BI_12 12
13 BI_13 BI_14 14
15 BI_15 BI_16 16
17 BI_17 BI_18 18
19 BI_19 BI_20 20
21 BI_21 BI_22 22
23 BI_23 BI_24 24
25 BI_25 COM- 26
8 07
08
BI_07
BI_08
The No.7 programmable binary input
The No.8 programmable binary input
09 BI_09 The No.9 programmable binary input
10 BI_10 The No.10 programmable binary input
11 BI_11 The No.11 programmable binary input
12 BI_12 The No.12 programmable binary input
13 BI_13 The No.13 programmable binary input
14 BI_14 The No.14 programmable binary input
15 BI_15 The No.15 programmable binary input
16 BI_16 The No.16 programmable binary input
Each BI module is with two 18-pin connectors for 32 binary inputs. The first 16 binary inputs share
one common negative power input and the last 16 binary inputs share another common negative
power input. All binary inputs are configurable. The pickup voltages and dropout voltages of the
binary inputs are settable by the setting [xx.U_Pickup_BI] and [xx.U_Dropoff_BI], and the range is
from 50%Un to 80%Un. The difference between NR6610A and NR6610B is that NR6610A equips
single AD sampling and NR6610B equips dual AD sampling.
01 BI_01 19 BI_01
02 BI_02 20 BI_02
03 BI_03 21 BI_03
04 BI_04 22 BI_04
05 BI_05 23 BI_05
06 BI_06 24 BI_06
07 BI_07 25 BI_07
08 BI_08 26 BI_08
09 BI_09 27 BI_09
10 BI_10 28 BI_10
11 BI_11 29 BI_11
12 BI_12 30 BI_12
13 BI_13 31 BI_13 8
14 BI_14 32 BI_14
15 BI_15 33 BI_15
16 BI_16 34 BI_16
17 BI_COM 35 BI_COM
18 BI_COM 36 BI_COM
8 31
32
BI_29
BI_30
The No.29 programmable binary input
The No.30 programmable binary input
33 BI_31 The No.31 programmable binary input
34 BI_32 The No.32 programmable binary input
35 COM-
The common negative connection of the BI_17 to BI_32.
36 (17-32)
The binary output module consists of some necessary contact outputs, and the binary outputs are
used as tripping and closing (protection, auto-reclosing or remote control) outputs or signal
outputs. It can receive tripping commands or closing commands from the CPU module, and then
executes these commands. It also can output some alarm signals from the CPU module.
The device can provide four types of binary output modules: NR6651A, NR6651B, NR6652A and
NR6660A.
8.4.6.1 NR6651A
The NR6651A provides 13 normally open contacts (NOC) with pickup relay control.
BO_01 01 02
BO_02 03 04
BO_03 05 06
BO_04 07 08
BO_05 09 10
BO_06 11 12
BO_07 13 14
BO_08 15 16
BO_09 17 18
BO_10 19 20
BO_11 21 22
BO_12 23 24
BO_13 25 26
8.4.6.2 NR6651B
8
The NR6651B provides 11 normally open contacts (NOC, the first 11 contacts) and 2 normally
close contacts (NCC, the last 2 contacts). These binary outputs are controlled by pickup relay.
BO_01 01 02
BO_02 03 04
BO_03 05 06
BO_04 07 08
BO_05 09 10
BO_06 11 12
BO_07 13 14
BO_08 15 16
BO_09 17 18
BO_10 19 20
BO_11 21 22
BO_12 23 24
BO_13 25 26
8.4.6.3 NR6652A
The NR6652A provides 4 normally open contacts (NOC, the first 4 contacts) with heavy capacity
for controlling the circuit breaker directly, and provides 4 general normal open contacts (NOC, the
last 4 contacts). These binary outputs are controlled by pickup relay.
BO_01 01 02
03 04
BO_02 05 06
07 08
BO_03 09 10
11 12
BO_04 13 14
15 16
17 18
BO_05 19 20
BO_06 21 22
BO_07 23 24
BO_08 25 26
8.4.6.4 NR6660A
The NR6660A provides 15 normally open contacts (NOC) and 2 normally open contacts &
normally close contacts (NOC/NCC). These binary outputs are controlled by pickup relay.
BO_01 01 02
BO_02 03 04
BO_03 05 06
BO_04 07 08
18-pin
BO_05 09 10
BO_06 11 12
BO_07 13 14
BO_08 15 16
BO_09 17 18
BO_10 19 20
BO_11 21 22
BO_12 23 24
BO_13 25 26
BO_14 27 28
18-pin
BO_15 29 30
BO_16 32
31
BO_16 33
BO_17 35
34
BO_17 36
The DC analog input module can provide 0~±20mA or 0~±10V input channels. Certain type can
also provide RTD sensor input channels.
8 This device provides three types of DC analog input modules: NR6630A, NR6631A and
NR6631B.
8.4.7.1 NR6630A
The NR6630A provides 12 channels of 0~±20mA or 0~±10V inputs, and all channels can be set
as 0~±20mA or 0~±10V DC signal inputs respectively through the jumpers on the module and the
related channel type setting.
Two 18-pin connectors are fixed on this DC analog input module. The terminal definition of the
connector on the module NR6630A is listed as below.
Table 8.4-6 Terminal definition and description of DC analog input module NR6630A
16 DCAI_06+
The No.6 DC analog input channel
17 DCAI_06-
18 GND The grounding terminal
19 DCAI_07+
The No.7 DC analog input channel
20 DCAI_07-
21 GND The grounding terminal
22 DCAI_08+
The No.8 DC analog input channel
23 DCAI_08-
24 GND The grounding terminal
25 DCAI_09+
The No.9 DC analog input channel
26 DCAI_09-
27 GND The grounding terminal
28 DCAI_10+
The No.10 DC analog input channel
29 DCAI_10-
30 GND The grounding terminal
31 DCAI_11+
The No.11 DC analog input channel
32 DCAI_11-
33 GND The grounding terminal
34 DCAI_12+
The No.12 DC analog input channel
35 DCAI_12-
36 GND The grounding terminal
8.4.7.2 NR6631
The NR6631A provides 8 channels of 0~±20mA or 0~±10V inputs, and all channels can be set as
0~±20mA or 0~±10V DC signal inputs respectively through the jumpers on the module and the
related channel type setting.
The NR6631B provides 6 channels of 0~±20mA or 0~±10V inputs, and all channels can be set as
0~±20mA or 0~±10V DC signal inputs respectively through the jumpers on the module and the
related channel type setting. It also can support 3 channels of RTD sensor inputs.
The terminal definition of the connector of the module NR6631A is listed as below.
Table 8.4-7 Terminal definition and description of DC analog input module NR6631A
The terminal definition of the connector of the module NR6631B is listed as below.
Table 8.4-8 Terminal definition and description of DC analog input module NR6631B
8 17
18
RTD1_A
GND
The No.1 RTD sensor input channel
The grounding terminal
19 RTD1_B
The No.1 RTD sensor input channel
20 RTD1_C
21 RTD2_A
22 RTD2_B The No.2 RTD sensor input channel
23 RTD2_C
24 RTD3_A
25 RTD3_B The No.3 RTD sensor input channel
26 RTD3_C
The wring method of the RTD sensor to this module is shown as below.
RTDx_A RTDx_A
RTDx_B RTDx_B
RTDx_C RTDx_C
3-wire 2-wire
9 Settings
Table of Contents
List of Tables
12 MVS.En_I0Elim
Enabled,
- Enabled
zero-sequence current elimination for 9
Disabled phase compensation of MV side of
transformer.
Logic setting of enabling/disabling
Enabled, zero-sequence current elimination for
13 LVS.En_I0Elim - Enabled
Disabled phase compensation of LV side of
transformer.
Primary voltage value of VT at x side
14 x.U1n 0.000~1100.000 kV -
of transformer
15 x.U2n 1.000~200.000 V - Secondary voltage value of VT at x
9 1. [x.U1n_Plate]
They are primary rated voltage at x side of transformer or reactor stated on nameplate
The setting principle of rated phase-to-phase voltages of each side is to take the primary rated
voltage marked on the nameplate of transformer as the primary rated voltage of corresponding
side. For an on-load tap changing transformer, the voltage of transformer with tap in middle
position can be taken as the value of this setting. As to other kind of transformers, actual operation
voltage (i.e. phase-to-phase voltage) shall be taken as this setting value, otherwise the calculation
of correction coefficient may be wrong
For example, if the voltage at 220kV side is 230kV for an on-load tap changing transformer with
tap in its middle position, and then the setting is set as 230kV.
For one side not used in the device, please set the primary rated voltage
value of the corresponding side as “0”.
2. [Clk_MVS_WRT_HVS], [Clk_LVS_WRT_HVS]
They are the wiring o′clock of MV/LV side with respect to HV side, is the parameter shown on
transformer nameplate with the range of 0~11, and need not further calculation.
3. [Clk_PhComp]
It is the target o′clock each side current will be shift to for phase compensation.
For examples:
The vector group of a transformer is Y0/Δ11 and the target o′clock ([Clk_PhComp]) is set to “11”.
Therefore, the setting [Clk_LVS_WRT_HVS] should be set to “11”.
1. For HV side, the clock of HV side with reference to target o′clock is 1 (i.e. wiring o′clock
12-target o′clock 11) clock, so the matrix of relative o′clock 1 is adopted to compensate HV
side current. Zero-sequence current elimination has no effect on phase compensation in the
condition.
2. For LV side, the clock of LV side with reference to target o′clock is 0 (i.e. wiring o′clock 11-
target o′clock 11), so the matrix of relative o′clock 0 is adopted to compensate LV side current.
Then it is needed to decide whether zero-sequence current is eliminated and select the
corresponding matrix.
If an earthing transformer is connected at LV side out the protection zone of differential protection,
then matrix of relative o′clock 0 without zero-sequence current elimination can be selected.
1 0 0 2 1 1
1
0
0 1 0
1 2 1
3
0 0 1 1 1 2
1 1 0
1
1 0 1 1
3
1 0 1
0 1 0 1 2 1
2
0 0 1 1
1 1 2
3
1 0 0 2 1 1
0 1 1
1
3 1 0 1
3
1 1 0
0 0 1 1 1 2
1
4
1 0 0
2 1 1
3
0 1 0 1 2 1
1 0 1
1
5 1 1 0
3
0 1 1
1 0 0 2 1 1
6
0 1 0 1
1 2 1
3
0 0 1 1 1 2
1 1 0
1
7 0 1 1
3
1 0 1
0 1 0 1 2 1
8
0 0 1
1
1 1 2
3
1 0 0 2 1 1
9
0 1 1
1
9 1 0 1
3
1 1 0
0 0 1 1 1 2
10
1 0 0
1
2 1 1
3
0 1 0 1 2 1
1 0 1
1
11 1 1 0
3
0 1 1
4. [x.En_RevCT]
It is used to adjust the current polarity of CT at x side of transformer, and default value is 0.
When the current polarity of primary CT is different with defined forward direction by PCS-978S,
the setting can be set as “Enabled”. However, it is recommended to change external wiring of
primary CT.
Access path: MainMenu Settings Global Settings Comm Settings General Comm
Settings
18 Baud_RS485-2
19200
38400
bps 19200
Baud rate of rear RS-485
serial port 2.
9
57600
115200
Communication address
between the device and
19 Addr_RS485-1 0~255 - 100
the SCADA or RTU via
RS-485 serial port 1.
Communication address
20 Addr_RS485-2 0~255 - 100 between the device and
the SCADA or RTU via
1. [Cfg_NetPorts_Bond]
The setting is used to configure dual-networks switching, and it means that no dual-networks
switching is created when the setting is set as “0”. The device support a bond between any two
Ethernet ports, and the bond among three or above Ethernet ports is impermissible.
The devices communicate with SAS by station level network. In order to ensure reliable
communication, dual networks (i.e., network 1 and network 2) are adopted. Another special
communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the
device own the same IP address and MAC address, and network 1 and network 2 are used as hot
standby each other. When both network 1 and network 2 are normal, any of them is used to
communicate between the device and SAS. The device will automatically switch to the other
healthy network when one network is abnormal, which will not affect normal communication.
Taking a CPU module with four Ethernet ports as an example, each bit is corresponding with an
Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2,
Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2
is created, the setting [Cfg_NetPorts_Bond] is set as “3”. The specific setting is as below.
Ethernet port 1 Ethernet port 2 Ethernet port 1 Ethernet port 3 Ethernet port 1 Ethernet port 4
0 0 1 1 3 0 1 0 1 5 1 0 0 1 9
Ethernet port 2 Ethernet port 3 Ethernet port 2 Ethernet port 4 Ethernet port 3 Ethernet port 4
0 1 1 0 6 1 0 1 0 10 1 1 0 0 12
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
After the device is powered on, network 1 is selected when the link status of both network 1
and network 2 are normal.
When the link status of network 1 is abnormal, network 2 is selected if network 2 is normal.
When the link status of network 1 is abnormal, network 1 is kept to work if network 2 is also
abnormal.
When network 2 is working, network 2 is kept to work even if network 1 has been restored to
normal. The device will be switched to network 1 only if network 2 is abnormal.
Access path: MainMenu Settings Global Settings Comm Settings DNP Settings
9 client
The offline
retransmission interval
for sending the
10 t_UROfflRetry_TCP1_DNP 1~5000 s 60
unsolicited message of
the No.1 network DNP
client
The default class level
of the “Binary Input” of
11 Class_BI_TCP1_DNP 0~3 - 1
the No.1 network DNP
client
9 75 Obj32DefltVar_TCP4_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
- 1-AI32IntEvWoutT variation of the No.4
network DNP client
1-AO32Int The “OBJ40” default
76 Obj40DefltVar_TCP4_DNP 2-AO16Int - 1-AO32Int variation of the No.4
3-AO32Flt network DNP client
Access path: MainMenu Settings Global Settings Comm Settings IEC103 Settings
Access path: MainMenu Settings Global Settings Comm Settings GOOSE Settings
These settings are used to definite the label of each bay and busbar. They can be set by 6
characters at most. The label of each bay and busbar will influence the displayed contents of all
reports, settings and metering that related with each bay and busbar.
9 0.0.0.0~
The IP address of the
server when SNTP time
4 IP_Server_SNTP - 0.0.0.0
255.255.255.255 synchronization mode is
selected
The subnet mask of the
0.0.0.0~ server when SNTP time
5 Mask_Server_SNTP - 0.0.0.0
255.255.255.255 synchronization mode is
selected
The IP address of the
0.0.0.0~
6 IP_StandbyServer_SNTP - 0.0.0.0 standby server when
255.255.255.255
SNTP time
1. [Opt_TimeSyn]
There are three selections for clock synchronization of the device, each selection includes
different time clock synchronization signals shown in following table.
Item Description
IRIG-B (RS-485): IRIG-B via RS-485 differential level.
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level.
IRIG-B (Fiber): IRIG-B via optical-fibre interface.
Conventional PPS (Fiber): Pulse per second (PPS) via optical-fibre interface.
IEEE1588 (Fiber): Clock message via IEEE1588.
PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn].
PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn].
SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network.
9 SAS
SNTP(BC): Broadcast SNTP mode via Ethernet network.
IEC103: Clock messages through IEC103 protocol.
MODBUS: Clock messages through MODBUS protocol.
If time synchronization function is not needed for the device, this option can be
NoTimeSyn
selected.
When the setting [Opt_TimeSyn] is set as "SAS", if there is no conventional clock synchronization
signal, the device will not send the alarm signal "Alm_TimeSyn".
When the setting [Opt_TimeSyn] is set as "NoTimeSyn", the device will not send time
synchronization alarm signal.
The clock message via IEC103 protocol is INVALID when the device
receives the IRIG-B signal through RC-485 port.
10 x.VTNS.3U0_Hm3_Set 0.00~100.00 V 20
Zero-sequence voltage setting (third
harmonic component) of neutral VT
9
circuit supervision
Enabling/disabling resetting the CT
Disabled circuit failure alarm signal
11 En_AutoRecov_Alm_CTS - Disabled
Enabled automatically after the CT circuit
resturns to normal condition.
25.Opt_Mode_DdChk
1 SynDdRefDd Dead check for both the reference and the synchronization sides
2 SynLvRefDd Live check for synchronization side and dead check for reference side
3 SynDdRefLv Dead check for synchronization side and live check for reference side
6 SynLvRefDd/SynDdRefLv Option 2 or 3
7 AnySideDd Option 1, 2 or 3
Appendix A Glossary
The abbreviations adopted in this manual are listed as below.
FR Fault Recorder O
OOS Out-of-Step
G.703 Electrical and functional description for
digital lines used by local telephone
P
companies. Can be transported over balanced
and unbalanced lines
PD Pole Discrepancy
GIS Gas-insulated Switchgear
PDTT Permissive Direct Transfer Trip
GOOSE Generic Object-Oriented Substation
PL Programmable Logic
Event
POTT Permissive Overreaching Transfer Trip
GPS Global Positioning System
PPM Pulse Per Minute
H
PPS Pulse Per Second
HV High-voltage
R
HVDC High-voltage Direct Current
RMS Root Mean Square
I
RSTP Rapid Spanning Tree Protocol
P Phase element
G Residual/Ground element
N Neutral/Ground element
Q Negative-sequence element