You are on page 1of 42

Ball Valve

Features and Benefits


B2...VS / VSS and B3...L
Tech.Doc -04/21- Subject to change. © Belimo Aircontrols (USA), Inc.

● 2-way and 3-way configuration ● NPT and flanged connections

● Bronze with stainless steel trim (2-way) ● Wide Cv range

● Nickel plated brass body (3-way) ● Air gap for use with hot water and steam systems

● Reduced and full port capacities ● Live load low maintenance stem packing

● Two piece construction ● 2 year warranty

● Electronic actuation

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

1
Industrial
IndustrialBallBallValves
Valves
General Information/Typical Installation
General Information / Typical Installation

FLOW PATTERN
B2..VS/VSS B3..L
Open CCW

B to A B to AB
Flow Direction Open CW Open CCW
Closed CW

NOTE: B3..L are piped differently than B3 CCV Valves.

PIPING DIAGRAMS
2-way Valve Piping Diagram B3..L Diverting & Changeover
Water (Switching) Valve Piping Diagram
VS, VSS BALL VALVES

2-way Valve Piping Diagram


Steam

W_17000- 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.
NOTE:
To avoid torque increase during off season shut down or other periods of inactivity longer than 1 month, the valve should be exercised (actuator or manually driven full
open-closed cycle) at least once per month. This is necessary to avoid any application problems after an off season shut down. This is not required for B3..L valves.

All prices are in US Dollars (USD)


PIPING/MOUNTING ORIENTATION

Assembly can be mounted horizontally or vertically for water applications. For steam applications the valve cannot be mounted vertically. When mounted
horizontally, the valve must be 0...45° off center of the pipe. Do not install with actuator below pipe.

0...90°

0...45°

Water Applications Steam Applications

800-543-9038 USA 866-805-7089


866-805-7089 CANADA 203-791-8396 LATIN
203-791-8396 LATIN AMERICA
AMERICA/CARIBBEAN
/ CARIBBEAN
12-2
2
Piping Sizing Geometry
Ball Valves

LINE SIZE
¾” 1” 1¼” 1½” 2” 2½” 3” 4”
VALVE SIZE Cv TYPE MODEL #
Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv
½” 1 2W NPT B2050VS-01 1.0 1.0 - - - - - -
½” 2 2W NPT B2050VS-02 2.0 1.9 - - - - - -
½” 4 2W NPT B2050VS-04 3.8 3.6 - - - - - -
½” 15 2W NPT B2050VS-15 8.9 7.2 - - - - - -
¾” 30 2W NPT B219VS/VSS 30.0 21.6 17.4 15.6 - - - -
¾” 51 2W NPT B220VS 51.0 26.5 19.9 17.3 - - - -
1” 43 2W NPT B224VS/VSS - 43.0 36.1 30.5 25.8 - - -
1” 68 2W NPT B225VS - 68.0 48.3 36.7 29.2 - - -
1½” 177 2W NPT B240VS - - - 177.0 102.7 77.9 67.3 -
2” 108 2W NPT B249VS/VSS - - - - 108.0 100.4 91.8 83.2
½” 6.4 3W NPT B315L 5.5 5.0 4.8 - - - - -
¾” 12.8 3W NPT B320L 12.8 11.8 11.0 10.5 - - - -
1” 11 3W NPT B325L - 11.0 10.9 10.7 10.4 - - -
1¼” 34 3W NPT B332L - - 34.0 32.8 29.9 28.2 - -
1½” 57 3W NPT B340L - - - 57.0 51.9 47.4 44.9 -
2” 87 3W NPT B350L - - - - 87.0 82.8 77.9 72.3
Tech.Doc -04/21- Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

3
Wiring Instructions
Ball Valves

GENERAL WIRING INSTRUCTIONS

WARNING The wiring technician must be trained and experienced with CAUTION It is good practice to power electronic or digital controllers
electronic circuits. Disconnect power supply before attempting any wiring from a separate power transformer than that used for actuators or
connections or changes. Make all connections in accordance with wiring other end devices. The power supply design in our actuators and other
diagrams and follow all applicable local and national codes. Provide end devices use half wave rectification. Some controllers use full wave
disconnect and overload protection as required. Use copper, twisted rectification. When these two different types of power supplies are
pair, conductors only. If using electrical conduit, the attachment to the connected to the same power transformer and the DC commons are
actuator must be made with flexible conduit. connected together, a short circuit is created across one of the diodes
in the full wave power supply, damaging the controller. Only use a single
Always read the controller manufacturer’s installation literature carefully power transformer to power the controller and actuator if you know the
before making any connections. Follow all instructions in this literature. controller power supply uses half wave rectification.
If you have any questions, contact the controller manufacturer and/or
Belimo. Multiple actuators, one transformer
Multiple actuators may be powered from one transformer provided the
Transformer(s) following rules are followed:
Typically actuators require a 24 VAC class 2 transformer and draw a 1. The TOTAL current draw of the actuators (VA rating) is less than or
maximum of 10 VA per actuator. The actuator enclosure cannot be equal to the rating of the transformer.
opened in the field, there are no parts or components to be replaced 2. Polarity on the secondary of the transformer is strictly followed. This
or repaired. means that all No. 1 wires from all actuators are connected to the
– EMC directive: 89/336/EEC common leg on the transformer and all No. 2 wires from all actuators
– Software class A: Mode of operation type 1 are connected to the hotleg. Mixing wire No. 1 & 2 on one leg of the
– Low voltage directive: 73/23/EEC transformer will result in erratic operation or failure of the actuator
and/or controls.
Typical transformer sizing
Actuator Series Voltage Max. VA Per Actuator Multiple actuators, multiple transformers
AF 24 10 Multiple actuators positioned by the same control signal may be powered
LF 24 6 from multiple transformers provided the following rules are followed:
AR 24 6 1. The transformers are properly sized.
NR 24 4 2. All No. 1 wires from all actuators are tied together and tied to the
LR 24 3 negative leg of the control signal. See wiring diagram.

Wire type and wire installation tips


For most installations, 18 or 16 Ga. cable works well with Belimo
actuators. Use code-approved wire nuts, terminal strips or solderless
connectors where wires are joined. It is good practice to run control wires
unspliced from the actuator to the controller. If splices are unavoidable,
make sure the splice can be reached for possible maintenance. Tape
and/or wire-tie the splice to reduce the possibility of the splice being

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


inadvertently pulled apart.

Wire length for actuator installation


Keep power wire runs below the lengths listed in the following tables.
If more than one actuator is powered from the same wire run, divide
the allowable wire length by the number of actuators to determine
the maximum run to any single actuator. See section 1 for specific
transformer sizing information for the actuator selected.

Example: 3 actuators, 16 Ga wire


350 Ft ÷ 3 Actuators = 117 Ft. Maximum wire run

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

4
Nomenclature
Ball Valves

B2 19 VS +NMX 24 -MFT-X1
Valve Valve Size Industrial Actuator Type Power Supply Control
B2 = 2-way 15-50 = ½...2” Construction/ Non Fail-Safe 24 = AC/DC 24 V -3-X1 = On/Off, Floating -S = Built-in
B3 = 3-way Material LMB, LMX 120 = AC 120 V Point Auxiliary
NMB, NMX UP = AC 24...240 -MFT-X1 = Multi-Func- Switch
VS = Bronze Body,
Stainless Steel Ball AMB, AMX V tion Technology
and Stem GMB, GMX or -MFT95-X1 = 0...135 Ω
VSS = Stainless Steel NRB, NRX DC 24...125
Body, Ball and Stem ARB, ARX V

L = Nickel Plated LRB, LRX


Brass Body, Chrome GRCX
Plated Brass Ball and PRB, PRX
Stem Fail-Safe
Spring Return
LF
NFB, NFX
AFB, AFX
Electronic
GKB, GKX

“X” models are customizable.


Refer to page 13-4 of the PGPL for
programming options.

Ordering Example

3 For MFT orders only - select programming code


1 Choose the valve actuator combination.
Tech.Doc -04/21- Subject to change. © Belimo Aircontrols (USA), Inc.

B219VS+NMX24-MFT-X1 NO Tagging (if needed)


4
2 Specify preference or configuration.
Does order
require
Set-Up tagging?

P-10001 (A01) Tagging:


Non Fail-Safe Models Valves may be tagged per
P-100.. (A..) Control voltage applications
NO = Normally Open customer specification.
NC = Normally Closed P-200.. (W..) Pulse width modulation ($12.00 per tag)
applications
Fail-Safe Models P-300.. (F..) Floating point applications Example:
NO/FO = Normally Open/Fail Open P-400.. (J..) On/off applications AHU-1
NO/FC = Normally Open/Fail Closed X-XXXXX Create custom MFT FCU-2
configuration code
NC/FO = Normally Closed/Fail Open Part number for tagging:
NC/FC = Normally Closed/Fail Closed X-XXXXX Create custom MFT 99981-00101
configuration in the field
Refers to valve ports A to AB. with MFT actuator PC-Tool software

5 Complete Ordering Example:B219VS+NMX24-MFT-X1


Configuration:
+NO
Programming: +A01

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

5
B2...VS Series, 2-way, Ball Valve
Bronze Body, Stainless Steel Ball and Stem

Technical Data Flow Patterns


Media chilled or hot water, glycol, 35# steam
Flow characteristic modified equal percentage • Live-load packing set
Action 90° rotation • Stainless steel ball & stem
valve open CW, valve closed CCW • Blow-out proof stem design
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”
Type of end fitting SAE NPT (female connections) Application
Materials: This valve is typically used in air handling units on heating or cooling coils, and
1 Stem packing reinforced PTFE fan coil unit heating or cooling coils. Some other common applications include
2 Stem bearing reinforced PTFE Unit Ventilators, VAV Box re-heat coils and bypass loops. This valve is suitable
3 Ball 316 stainless steel for use in a hydronic system with variable flow.
4 Seat (x2) reinforced PTFE w/ Durafill
This valve is designed with MFT functionality which facilitates the use of various
5 Retainer B16 (¾” - 1”) stainless steel
control input.
B584 (1¼” - 2”) stainless steel
6 Gland B16 brass • Up to 35 psi steam
7 Stem 316 stainless steel • ½” - 600 PSIG WOG, Cold Non-Shock.
8 Jam nut stainless steel • Federal Specification: WW-V-35C,Type II
9 Body seal PTFE (1-1/4” to 2”) Composition: BZ
10 Body B584-C84400 bronze Style: 3

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


10

Pressure rating 600 psig WOG


Media temp. range -22°F to +280°F (-30°C to +138°C)
Close-off pressure 600 psig @ 100°F
Maximum differential <600 psig
pressure (∆P)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

6
B2...VSS Series, 2-way, Ball Valve
Stainless Steel Body, Ball and Stem

Technical Data Flow Patterns


Media chilled or hot water, glycol, 50# steam
Flow characteristic modified equal percentage • Live-load packing set
Action 90° rotation • Stainless steel ball & stem
valve open CW, valve closed CCW • Blow-out proof stem design
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”
Type of end fitting SAE NPT (female connections) Application
Materials: These threaded valves are designed to provide modulating or two position control
1 Stem packing reinforced PTFE of hot or chilled water and saturated steam systems under 50 psi.
2 Stem bearing reinforced PTFE Typical applications include reheat coils, VAV terminal control, unit ventilators,
3 Ball 316 stainless steel and air handlers, especially in areas which have minimum profile requirements.
4 Seat (x2) reinforced PTFE w/ Durafill
• Up to 50 psi steam
5 Retainer B16 (¾” - 1”) stainless steel
• ½” - 2000 PSIG WOG, Cold Non-Shock.
B584 (1¼” - 2”) stainless steel
• Federal Specification: WW-V-35C,Type II,
6 Gland A276-316
Composition: SS
7 Stem 316 stainless steel
Style: 3
8 Jam nut stainless steel
9 Body seal PTFE (1¼” to 2”)
10 Body A351-CF8M 316 stainless steel
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

10

Pressure rating 2000 psig WOG (½” - 1”)


Media temp. range -22°F to +298°F (-30°C to +148°C)
Close-off pressure 600 psig @ 100°F
Maximum differential <600 psig
pressure (∆P)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

7
B3...L Series, 3-way, Ball Valve
Chrome Plated Brass Ball and Nickel Plated Stem

Technical Data
Media chilled or hot water, 60% glycol
Flow characteristic modified linear
Action 90° rotation
B to A open CW, B to AB open CCW
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”
Type of end fitting NPT female ends
Materials:
Body nickel plated brass
Ball chrome plated brass
Stem nickel plated brass
Stem seal o-ring EPDM
Valve seat PTFE
Leakage ANSI VI
Pressure rating 600 psig WOG
600 psi DN 15-25 (B3...L)
400 psi DN 32-50 (B3...L)
Media temp. range 0°F to 250°F [-18°C to +120°C]
Close-off pressure 200 psi
Maximum differential 50 psi
pressure (∆P)

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

8
Industrial Ball Valve Product Range

Valve Nominal Size Type Suitable Actuators


3-way
Cv Inches DN [mm] 2-way NPT Non Fail-Safe Fail-Safe
NPT

1 ½ 15 B2050VS-01*

LM Series

LF Series
2 ½ 15 B2050VS-02*

4 ½ 15 B2050VS-04*

15 ½ 15 B2050VS-15*

GR Series
30 ¾ 20 B219VS

Series
NM Series

NF
51 ¾ 20 B220VS
Mode of Operation
43 1 25 B224VS The control valve is operated by an electronic actuator that
25 responds to a standard voltage for on/off control, by a modulat-
68 1 B225VS

Series
ing 4…20 mA, or floating point control system. The actuator will

AM
then move the ball of the valve to the position dictated by the

AF Series
48 1¼ 32 B232VS
control signal thus changing the flow.
84 1½ 40 B239VS GM Series

PR Series
Product Features
177 1½ 40 B240VS Modified equal percentage of flow for B2. Modified linear flow
for B3.
108 2 50 B249VS B3..L valves are for diverting applications and are not rated for
steam.
15
LM

15 ½ B2050VSS-15*

LF
Actuator Specifications
GR Series

Control type on/off, floating point,


NM

20 B219VSS**

NF
30 ¾ modulating, 2...10 V
multi-function technology (MFT)
25 B224VSS**
AM

43 1
AF Series
Manual override LM, NM, GM, AM, GR, PR, AF, NF, GK
Electrical connection 3 ft. [1 m] cable with
Series

50 B249VSS** ½” conduit fitting


GM

PR

108 2

Valve Specifications
6.4 ½ 15 B315L***
Fluid chilled or hot water, (60% glycol),
LR Series

LF Series
Inc. (USA), Inc.

steam (2-way)
12.8 ¾ 20 B320L***
Flow characteristic modified equal percentage (B2),
modified linear (B3..L)
11 1 25 B325L***
Aircontrols

Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”


32 B332L*** End fitting FNPT
NR

34 1¼
© Belimo(USA),
All prices are in US Dollars (USD)

AFR Series

Materials
Body bronze (B2..VS)
AR Series

40 B340L***
Aircontrols

57 1½
stainless steel (B2..VSS)
nickel plated brass (B3..L)
87 2 50 B350L*** Ball stainless steel, bronze
change.

(B2050VSS-15)
Belimo

* For hot only or cold only applications. Not for temperature changeover applications. chrome plated brass (B3..L)
- Subject©to

** NSF/ANSI/CAN 61 Section 8, Annex G, NSF/ANSI 372 - Drinking Water System Components - Lead Content Stem stainless steel
nickel plated brass (B3..L)
to change.

*** Not for steam applications.


Seats
NOTE: Industrial ball valves (B2..VS, B2..VSS) have serviceable components. Proper maintenance of these 2-way MPTFE, RPTFE (B2050)
04/21

parts will ensure a longer in-service life for the valves. The seats of these valves will require replacement at an 3-way Teflon PTFE
- Subject

interval consistent with number of full cycles the valve has be operated, or as field condition dictates. Stem packing
W_17000-

2-way NPT MPTFE


O-rings NPT EPDM (B3..L)
Tech.Doc - 04/21

Fluid temp range


B2..VS -22...+280°F [-30...+138°C]
B2..VSS -22...+298°F [-30...+148°C]
B3..L 0...250°F [-18...+120°C]
Body pressure rating
3-way 600 psi DN 15...25 (B3..L ½...1”)
400 psi DN 32...50 (B3..L 1¼...2”)
Maximum inlet pressure
Steam 35 psi B2..VS
50 psi B2..VSS
Leakage ANSI Class VI (B2..VS, VSS)
0% (B3..L)

12-1
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

9
LF Actuators, On/Off

Dimensions with 2-Way Valve

Models
LF24 US Valve Nominal Size Dimensions (Inches)
LF24-S US w/built-in Aux. Switch
Valve Body COP Inches DN [mm] A B C D F
LF120 US
B2050VS-01 50 ½ 15 6.75 2.00 6.75 2.25 4.00
LF120-S US w/built-in Aux. Switch
B2050VS-02 50 ½ 15 6.75 2.00 6.75 2.25 4.00
B2050VS-04 50 ½ 15 6.75 2.00 6.75 2.25 4.00
Technical Data B2050VS-15 50 ½ 15 6.70 2.00 8.00 2.25 6.25
Control on/off, floating point
Power supply
LF24(-S) US 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
LF120(-S) US 120 VAC ± 10% 50/60 Hz
Power consumption
LF24(-S) US running5W
holding2.5 W
LF120(-S) US running5.5 W
holding3.5 W
Transformer sizing 7 VA, class 2 power source
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft. [1m], 18 GA appliance cable

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


Electrical protection 120V actuators double insulated
Overload protection electronic throughout rotation
Angle of rotation 95°
Spring return direction reversible with CW/CCW mounting
Position indication visual indicator 0° to 90°
Running time <40 to 75 sec. (on/off)
Valve Nominal Dimensions (mm)
spring <25 sec. @ -4°F to +122°F [-20°C to +50°C]
Size
<60 sec. @ -22°F [-30°C]
DN
Ambient temperature -22° F to +122° F [-30° C to +50° C] Valve Body COP Inches A B C
[mm]
Housing NEMA 2
B315L 50 ½ 15 2.63” [67] 1.73” [44] 1.42” [36]
Agency listings† UL 873, CSA C22.2 No. 24 certified, CE
B320L 50 ¾ 20 3.01” [78] 1.81” [46] 1.63” [42]
Quality standard ISO 9001
B325L 50 1 25 3.42” [87] 1.81” [46] 1.77” [45]
Noise level max. 62 dB(A)

LF...-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

10
WARNING
Live Electrical Components!
LF Actuators, On/Off
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams

W047
24 VAC Transformer

Line 1 Common
Volts 2 + Hot 3
1 Provide overload protection and disconnect as required.

2 CAUTION Equipment damage! LF24 US


Actuators may be connected in parallel. 2
Power consumption must be observed.
On/Off wiring for 24 VAC/DC
3 Actuator may also be powered by 24 VDC.

W049-LF-08
For end position indication, interlock control, fan startup, etc.,
4 LF24-S US and LF120-S US incorporates a built-in auxiliary switch:
1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.

1 Provide overload protection and disconnect as required.


Meets cULus or UL and CSA requirements without the Actuators may be connected in parallel. Power consumption
need of an electrical ground connection. 2 must be observed.

WARNING Live Electrical Components! 3 Actuator may also be powered by 24VDC.

During installation, testing, servicing and troubleshooting of this product, it may


be necessary to work with live electrical components. Have a qualified licensed electrician On/Off wiring for 120 VAC
or other individual who has been properly trained in handling live electrical components

W048-AUX
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

Auxiliary Switch
W047
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

11
LF24-MFT US Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

Models
LF24-MFT US
LF24-MFT-S US w/built-in Aux. Switch Valve Nominal Size Dimensions (Inches)
Valve Body COP Inches DN [mm] A B C D F
B2050VS-01 100 ½ 15 6.75 2.00 6.75 2.25 4.00
Technical Data B2050VS-02 100 ½ 15 6.75 2.00 6.75 2.25 4.00
Control MFT B2050VS-04 100 ½ 15 6.75 2.00 6.75 2.25 4.00
Control signal 2 to 10 VDC (4-20mA with 500 Ω resistor) B2050VS-15 100 ½ 15 6.70 2.00 8.00 2.25 6.25
Power consumption running 2.5 W
holding 1W
Transformer sizing 5 VA (class 2 power source) Dimensions with 3-Way Valve
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft. [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotation
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20mA
750 Ω for PWM
500 Ω for on/off and floating point
Feedback 2 to 10 VDC, 0.5 mA max
Angle of rotation 95°
Direction of rotation spring reversible with CW/CCW mounting

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


motor reversible with built-in switch
Position indication visual indicator
Running time <40 to 75 sec. (on/off)
150 sec. independent of load (proportional)
spring <25 sec. @ -4°F to +122°F [-20°C to +50°C]
<60 sec. @-22°F [-30°C]
Ambient temperature -22° F to +122° F [-30° C to +50° C]
Housing NEMA 2 Valve Nominal Dimensions (mm)
Agency listings UL 873, CSA C22.2 No. 24 certified, CE Size
Noise level max. 62 dB(A) DN
Valve Body COP Inches A B C
Quality standard ISO 9001 [mm]
B315L 200 ½ 15 2.63” [67] 1.73” [44] 1.42” [36]
LF24-MFT-S US B320L 200 ¾ 20 3.01” [78] 1.81” [46] 1.63” [42]
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed, B325L 200 1 25 3.42” [87] 1.81” [46] 1.77” [45]
adjustable 0° to 95° (double insulated)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

12
LF24-MFT US Actuators,
Wiring Multi-Function
– PWM, triac Technology
WARNING
source and s
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams

W043
24 VAC/DC Transformer

Line (1) Common


Volts
2 CAUTION Equipment damage! (2) Hot
Actuators may be connected in parallel if not mechanically mounted to a
Position (–)
the same shaft. Power consumption and input impedance must be (3) Y Input
observed. Feedback VDC (+) (5) U Output

Actuators may also be powered by 24 VDC. WARNING


3
CCW CW

Live Electrical Components! …MFT


During installation, testing, servicing and troubleshooting of this product, it maybe

4 IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155). necessary to work with live electrical components. Have a qualified licensed electrician

On/Off control
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
5 Triac A and B can also be contact closures.

W041
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or
6 Common (Sink) 24 VAC line. Line (1) Common
Volts 6
Position feedback cannot be used with Triac sink controller. (2) + Hot
7 The actuators internal common reference is not compatible. (3) Y Input
7 Position (–)
Feedback VDC (+) (5) U Output

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to CCW CW


…MFT
2 to 10 VDC, up to 2 actuators may be connected in parallel.

WARNING Live Electrical Components! PWM, triac source and sink


During installation, testing, servicing and troubleshooting of this product, it may

W302
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

...MFT
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Floating Point control

W303

Propotional 2 to 10 or 4 to 20 mA control signal

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

13
NF Actuators, On/Off

Dimensions with 2-Way Valve

B C F

A
D

Models
NFB24-X1 Valve Nominal Size Dimensions (Inches)
NFBUP-X1 Valve Body COP Inches DN [mm] A B C D F
NFBUP-S-X1 w/built-in Aux. Switch B219VS 400 ¾ 20 7.00 1.25 6.77 3.37 6.25
B220VS 400 ¾ 20 7.00 1.25 6.77 3.37 6.25
B219VSS 1000 ¾ 20 7.00 1.25 6.77 3.37 6.25
Technical Data
Control on/off
Power consumption
NFB24-X1 running 6W
holding 2.5 W
NFBUP-X1 running 6W
holding 2.5 W
Transformer sizing NFB24-X1 8.5 VA (class 2 power source)
NFBUP(-S)-X1 6 VA @ 24 VAC (class 2 powe source)
6.5 VA @ 120 VAC
9.5 VA @ 240 VAC
Electrical connection ½” conduit connector
(-S model has 2 cables) 3 ft. [1m], 18 GA appliance cables
Electrical protection 120V actuators double insulated
Overload protection electronic throughout 0° to 95°

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


rotation
Angle of rotation 95°
Position indication visual indicator
Running time control <75 seconds
spring <20 seconds
Ambient temperature -22° F to +122° F [-30° C to +50° C]
Housing NEMA 2 / IP54
Agency listings UL 873, CSA C22.2 No. 24 certified, CE
Noise level max. 45 dB(A)

NFBUP-S-X1
Auxiliary switch 2 x SPDT, 3A (0.5A inductive) @
250 V

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

14
NF Actuators, On/Off

Wiring Diagrams

W063_NFB(X)
1 24 VAC Transformer

1 Provide overload protection and disconnect as required. Line 1 Common


Volts 3
2 CAUTION Equipment damage! 2 + Hot
Actuators may be connected in parallel.
Power consumption must be observed.
3 Actuators may also be powered by 24 VDC. NFB24-X1 2
For end position indication, interlock control, fan startup, etc.,
4 NF24-S US incorporates a built-in auxiliary switch: 1 x SPDT, 7A (2.5A) On/Off wiring for NFB24-X1
@ 250 VAC, UL listed, adjustable 5° to 85°.

W066_NFB(X)UP
1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption
Meets cULus or UL and CSA requirements without the 2 must be observed.
need of an electrical ground connection.
3 Actuator may also be powered by 24VDC.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
NFBUP-X1
NFBUP-S-X1

On/Off wiring for NFBUP-X1, NFBUP-S-X1

W067_NFB(X)UP-S
Wht
Blk
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

W063

NFBUP-S-X1

Auxiliary Switch

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

15
NF Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

B C F

A
D

Models Valve Nominal Size Dimensions (Inches)


NFX24-MFT-X1
Valve Body COP Inches DN [mm] A B C D F
NFX24-MFT-S-X1
B219VS 400 ¾ 20 7.00 1.25 6.77 3.37 6.25
Technical Data B220VS 400 ¾ 20 7.00 1.25 6.77 3.37 6.25
Control MFT B219VSS 1000 ¾ 20 7.00 1.25 6.77 3.37 6.25
Control signal 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor)
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 20% / -10%
Power consumption running 6.5 W
holding 3W
Transformer sizing 9 VA, (class 2 power source)
Electrical connection ½” conduit connector
3 ft. [1m], 18 GA appliance cable
Overload protection electronic throughout 0 to 95° rotation
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for on/off and floating point
Feedback output 2 to 10 VDC, 0.5 mA max
Angle of rotation 95°
Direction of rotation spring reversible with CW/CCW mounting

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


motor reversible with built-in switch
Position indication visual indicator, 0° to 95°
Running time motor 150 seconds (default), variable (40 to 220
seconds)
spring <20 sec @ -4°F to +122°F [-20°C to +50°C];
<60 sec @ -22°F [-30°F]
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Housing NEMA 2 / IP54, Enclosure Type 2
Agency listings cULus acc. to UL60730-1A/ -2-14, CAN/
CSA E60730-1:02, CE acc. to 2004/108/EC &
2006/95/EC
Noise level <40 dB(A) motor @ 150 seconds, run time
dependent
<62 dB(A) spring return

NFX24-MFT-S-X1
Auxiliary switch 2 x SPDT, 3A (0.5A) @ 250 VAC, UL Approved
one set at +10°, one adjustable 10° to 90°

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

16
Live Electrical Components!
Live
Live Electrical
Electrical
During Components!
Components!
installation, testing, servicing and troubleshooting of this product, it may
During
During installation,
installation,
be necessary testing,
testing,
to work servicing
servicing
with live and troubleshooting
andcomponents.
electrical troubleshooting Haveof
ofathis
this product,
product,
qualified itit may
licensed may
be
be necessary
necessary
electrician to
or to work
work
other with
with live electrical
livewho
individual electrical components.
components.
has been Have
Have aa in
properly trained qualified
qualified
handlinglicensed
licensed
live
electrician
electrician or other individual
or other individual
electrical components perform who
who has been
hastasks.
these properly
been Failure trained
properlytotrained in
follow in handling
all handling live
electricallivesafety
NF Actuators, Multi-Function Technology
electrical
electrical
precautions
precautions
precautions
components
components
serious injury.
when exposed
when
perform
perform these
these
to live
to live
tasks.
tasks. Failure
electrical
electrical
Failure to
to follow
components
components
follow all
could electrical
all result
electrical
when exposed to live electrical components could result in death or
exposed could result
safety
safetyor
in death
in death or
serious 7
serious injury.
injury. 7
7
VDC/4-20 mA
VDC/4-20
VDC/4-20 mA
mA 9
Wiring Diagrams 24 VAC Transformer 4 3 5 9
9

W400_A_11
24 VAC Transformer 4 3 5
24 VAC Transformer 4 3 5
Line Blk (1) Common
Line Blk (1) Common Two
Volts
Line Blk
Red (1)
(2) Common
+ Hot
Volts 500 Ω Red (2) + Hot Two
Two
2 CAUTION Equipment damage! Volts
Control Signal
(–)
Ω 1/4
500watt
Ω 1/4
500
Ω 1/4


watt
Red (2) + Hot

Actuators may be connected in parallel if not mechanically mounted to (+)


VDC (–)
watt
4 to 20 mAControl
or 2 to 10
Signal (–) Wht (3) Y1 Input, 2 to 10V
Control Signal (+) Wht (3) Y1 Input, 2 to 10V
4 to 20 mA or 2 to 10 VDC (+) 7 Wht
the same shaft. Power consumption and input impedance must be 4 to 20 mA or 2 to 10 VDC
7
7
Pnk (3)
Pnk
(4) YY12 Input,
Input 2 to 10V
(4) Y2 Input
Pnk
observed.
W400_A_11
Grn (4)
(5) YU2Output,
Input 2 to 10V

Actuators: EFB24-MFT(-S) EFX24-MFT(-S) AFB24-MFT(-S) AFX24-MFT(-S) NFB24-MFT(-S) NFX24-MFT(-S) Grn (5) U Output, 2 to 10V
Grn
CCW (5)
CW U Output, 2 to 10V
W400_A_11

3 Actuators may also be powered by


Actuators: 24 VDC.
EFB24-MFT(-S)
LMX LRX NMX AMX EFX24-MFT(-S)
ARX GKX AFB24-MFT(-S)
NKQ ARX24-MFT-5AFX24-MFT(-S)
ARB24-MFT-5NFB24-MFT(-S)
GRX24-MFT-5 NFX24-MFT(-S)
CCW CW
CCW CW

LMX LRX NMX GRB24-MFT-S


GMX24-MFT-X1 AMX ARX GKXGRB24-MFT-5
NKQ ARX24-MFT-5 ARB24-MFT-5 GRX24-MFT-5
GRB24-MFT-7
4 IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155). Floating Point (except NKQ)
GMX24-MFT-X1 GRB24-MFT-S GRB24-MFT-5 VDC/4-20 mAPoint
GRB24-MFT-7
Floating (except NKQ) Floating Point (except NKQ)
5 Triac A and B canHazard Identification
also be contact closures. INSTALLATION NOTES
24 VAC Transformer 10 4 5

W400_A_11
10 4 5
Hazardand Identification
24 VAC Transformer 10 4 5
Warnings Cautions appear at appropriate sections throughout INSTALLATION
24 VAC Transformer
NOTES Blk Common –
Control signal may
thisbemanual.
pulsed from
Read either the Hot (Source) or
these appear
carefully.
Line (1)

6 Warnings and Cautions at appropriate sections throughout 3 Actuators mayVolts also be powered by 24 VDC.Blk
Line
Volts
Line Blk
(1) Common –
(2) Common
Red (1) Hot + –
Common (Sink) 24this VAC line. Read these carefully.
manual. Red (2) Hot +
CAUTION
Position feedback cannot be used with Triac sink controller.
Actuators with
3 Actuators
Volts
may plenum
also be ratedpowered cableAby 24 VDC.
A do not have
Red (2) Hot +
Wht (3)numbers
Y1 Input on Over
5 8 A Over
7 CAUTION
Indicates
The actuators internal
a potentially hazardous situation which, if not avoided,
common reference is not compatible.
wires; use
Actuators color
with codes
plenum instead.
rated
8
8 cable
BActuators
do not with
Wht (3)appliance
Wht (3) Y1 Input
have numbers
Y1 Input on Over
may result 5 cables are numbered. (–) B Pnk (4) Y2 Input
Indicates ainpotentially
minor or hazardous
moderate injury. It may
situation alsoifbe
which, notused to
avoided, wires; use color 2 tocodes
10 VDC instead. Actuators
B 9 with
Pnk (4)appliance
Pnk
Y2 Input
(5) YU2 Output
alert
may against
result inunsafe
minor practices.
or moderate injury. It may also be used to Control signal
cables are may
Feedback
numbered.
2
2
to 10
to 10 be
Signal
VDC
(–)
(+)
VDCpulsed
(–)
(+)
9
from9 either the
Org (4)
OrgHot
Input 2 to 10V
(5) (Source)
8 Feedback Signal
Feedback Signal (+)
U Output 2 to 10V
Org (5) U Output 2 to 10V
alert against
Equipmentunsafe practices.
damage! or Common
Control (Sink)
signal may24 be VAC
pulsed line.from either the Hot (Source)
4 Actuators may be connected in parallel if not mechanically 8 Direction of rotation switch

The ZG-R01 500 Ω resistor converts


Equipment the 4 to 20 mA control signal to
damage! or Common
For triac sink(Sink) 24 VACconnection
the Common line. from the actuator DirectionCCW
of rotation switch
DirectionCW
CCW
of rotation switch
10
CW

2 to 10 VDC, up to 24actuators
mounted to the same shaft. Power consumption and input must be connected to the Hot connection of the
the controller.
CCW CCW

may be connected in parallel.


Actuators may be connected in parallel if not mechanically For triac sink the Common connection from actuator
CCW CCW
CW CW
A B 5
CW A B 5
CW

impedance 10 Position feedback cannot be used with a triac sink controller.


mounted tomust be observed.
the same shaft.the
Power consumption and input must be connected to the Hot connection of the controller.
A B 5 A B 5

Meets cULus or UL and CSA requirements without


A B 5 A B 5

impedance must be observed. The actuator internal common reference is not


Position feedback cannot be used with a triac sink controller. compatible.
need of an electrical ground connection.
WARNING The actuator
Triac Source and Sink internal common(See
Diagrams reference
pageis21) not compatible.
Live Electrical Components!
WARNING Triac
Floating PointSource and Sink Diagrams (See page 21)
Triac Source
NKQ)and Sink Diagrams (See page 21)
WARNING Live During
Electrical Components!
installation, testing, servicing and troubleshooting of this product, it may PWM (except
(exceptAPPLICATION NOTES
Live Electrical Components! PWM
be necessary to work with live electrical PWM (except NKQ)
NKQ)
During installation, testing, servicing andtesting,
troubleshooting ofcomponents.
this product,Have ofa this
it may qualified licensed

W400_A_11
During installation, servicing and troubleshooting product, it may
be necessary to work with live electrician
beelectrical
necessary orcomponents. 
other individual
to work withHlivewho
ave has been
a qualified
electrical properly electrician
licensed
components. trained
Have ainqualified
handlinglicensed
live APPLICATION
Meets cULus requirements NOTES
24 VAC Transformer (AC only)
without(AC
24 VAC Transformer theonly)
need 4of 4 5
an electrical
5
24 VAC Transformer (AC only) 4 5
electrical
or other individual who has been components
properly trained perform
in handling these
live tasks. Failure
electrical to follow
components
electrician or other individual who has been properly trained in handling liveall electrical safety ground connection.
Meets cULus requirements
Line without the needBlkof (1)
Blk anCommon
(1) electrical
Common
precautions
perform these tasks. Failure to follow all when exposed
electrical to precautions
safety live electrical components
tasks.when exposed couldallresult
to live in death or Line 8
electrical components perform these Failure to follow electrical safety
Aground
500 Ωconnection.
Volts
Line Blk (2) Common
Red (1) + Hot
serious resistor converts the 4 to88 20 mA control
Volts Red (2)signal
electrical components could result ininjury.
precautions deathwhenor serious
exposedinjury.
to live electrical components could result in death or 7 Volts Red
+ Hot
(3) +Y Hot
Wht (2)
serious injury.
to 2 to Ω
A 500 10resistor
VDC. converts the 4 to 20 mA control
Position (–) Wht
Input
signal
Pnk (3)
Wht (4) Y Input
YY2Input
Input
VDC/4-20 mA 7 VDC (–)
Position
Feedback (3)
to 2 to 10 VDC.
Contact closures A&B
Position
Feedback VDC
(–)
also can be triacs. A &
(+)
PnkB(4)
Pnk
Org should
(4)
(5) YU2 Output
Input
Y Input
VDC/4-20 mA 9 Feedback VDC (+) Org (5) U2Output
24 VAC Transformer 4 3 5
both be closed
Contact forAtriac
closures & B source
(+)
also can and
beopen
triacs.forA triac
Org (5)sink.
U
& B should Output
9
4 (1)3 Common
5
both be closed for triac source and open for triac sink.
Line 24 VAC Transformer Blk
Volts Red Two Position
Line (1) +Common
Blk (2) Hot
Volts
500 Ω
Ω 1/4 watt Red (2) + Hot PWM Two Position
(–)
Control Signal 500 Ω 24 VAC/DC Transformer 4 3 5
4 to 20 mA or 2 to 10 VDC
(+) Ω 1/4 Wht (3) Y1 Input, 2 to 10V

W400_A_11
watt
(–)
Control Signal 7 5
4 (1)3 Common
4 to 20 mA or 2 to 10 VDC
(+) Pnk
Wht (4)
(3) YY21Input
Input, 2 to 10V Line 24 VAC/DC Transformer Blk
7 Grn
Pnk (5)
(4) UYOutput, Volts Red
2 Input
2 to 10V
Line (1) Hot
Blk (2) Common
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Grn CW
CCW (5) U Output, 2 to 10V Volts a Red (2) Hot
(–) Wht (3) Y Input
Position a
CCW CW
Pnk (4) Y2 Input
Feedback VDC (–) Wht (3) Y Input
Position (+) Org (5) U Output
Pnk (4) Y2 Input
Floating Point (except NKQ) Feedback VDC
(+) Org (5) U Output
Floating Point (except NKQ) 5
24 VAC Transformer 10 4

24 VAC Transformer 5
10 (1)4 Common
Line Blk –
Volts Red Hot +
Line Blk (2)
(1) Common –
Volts A Red (3)
Wht (2) YHot +
1 Input
Two Position
Override Control to min, mid, max, Positions
8
BA
Override Control to min, mid, max, Positions

W400_A_11
Pnk (3) Y1 Input
Wht (4) Y2 Input
(–) 8
2 to 10 VDC B9 24 VAC Transformer (AC Only) 5
Feedback Signal (+) Org (4) UY2Output
Pnk (5) Input 2 to 10V
(–) 9 24 VAC Transformer (AC Only) 5
2 to 10 VDC
Feedback Signal (+) Org (5) U Output 2 to 10V Line Blk (1) Common
Direction of rotation switch
CCW CCW
Volts
Line Red (1) +Common
Blk (2) Hot
CW CW
Direction of rotation switch
A
A
CCW
B 5 A
CCW
B 5
Volts Ω BA Red (2) + Hot
CW CW

A B 5 A B 5 (–) Ω B
Control Signal C
2-10 VDC or 4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
(–) 500 Ω
Triac Source and Sink Diagrams (See page 21) Control Signal
1/4 watt C Pnk (4) Y2 Input
Wht (3) Y Input, 2 to 10V
2-10 VDC or 4 to 20 mA (+)
7 Org (5) 1
500 Ω
Triac
PWM Source
(except NKQ) and Sink Diagrams (See page 21)
7 1/4 watt
Pnk (4) Y2 Input
Org (5)
PWM (except NKQ)
24 VAC Transformer (AC only) 4 5 Functions a b c
Min* 0%
Functions a b c
Line24 VAC Transformer (AC only) Blk 5
4 (1) Common
Mid* 50%
8 Min* 0%
Volts Red (1) +Common
Blk (2) Hot
Line Max*
Mid* 100%
50%
Volts 8 Wht Normal** Control mode acc. to Y
Red (3)
(2) Y+Input
Hot Max* 100%
Position (–) Pnk (4) Y2 Input
Feedback VDC (+) Wht (3) Y Input * Normal** Control0-100%.
Default selectable mode acc.
SeetoConfiguration
Y Data Sheet.
Position (–) Org (5) U Output ** Customizable. See Configuration Data Sheet.
Pnk (4) Y2 Input
Feedback VDC (+) * Default selectable 0-100%. See Configuration Data Sheet.
Org (5) U Output ** Customizable. See Configuration Data Sheet.
Override Control to Min, Mid, Max, Positions

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

17
AF Actuators, On/Off

Dimensions with 2-Way Valve

B C F

A
D

Models
AFB24-X1 Valve Nominal Size Dimensions (Inches)
AFBUP-X1 Valve Body COP Inches DN [mm] A B C D F
AFBUP-S-X1 w/built-in Aux. Switches B224VS 400 1 25 7.00 1.25 6.77 3.37 6.25
AFRB24-3 B225VS 200 1 25 7.00 1.25 6.77 3.62 6.25
AFRX24-3 B232VS 600 1¼ 32 7.00 1.25 6.77 3.97 6.25
*B239VS 600 1½ 40 15.00 N/A 13.54 4.37 6.25
*B240VS 600 1½ 40 15.00 N/A 13.54 4.75 6.25
Technical Data *B249VS 600 2 50 15.00 N/A 13.54 4.68 6.25
Control on/off B224VSS 1000 1 25 7.00 1.25 13.54 3.37 6.25
Power consumption *B249VSS 1000 2 50 15.00 N/A 13.54 4.68 6.25
AFBUP-X1 running 5W
holding 2.5 W Dimensions with 3-Way Valve
AFBUP-S-X1 running 7W
holding 3.5 W 9.77”
[248.2]

Transformer sizing AFB24-X1 7.5 VA (class 2 power source) 4.04”


[102.7]

AFBUP(-S)-X1 7 VA @ 24 VAC (class 2 power source)


8.5 VA @ 120 VAC

[63.5]
2.50”
18 VA @ 240 VAC
[99.9]
3.93”

Electrical connection ½” conduit connector


(-S model has 2 cables) 3 ft. [1m], 18 GA appliance cables

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


Electrical protection 120V actuators double insulated
Overload protection electronic throughout 0° to 95° rotation
Angle of rotation 95°
Position indication visual indicator
Manual override hex crank
Running time control 150 seconds independent of load
spring <20 seconds
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Housing NEMA 2 / IP54
Valve Nominal Dimensions (mm)
Agency listings UL 873, CSA C22.2 No. 24 certified, CE
Size
Noise level max. 45 dB(A)
DN
Valve Body COP Inches A B C
[mm]
AFBUP-S-X1
B332L 200 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]
Auxiliary switches 2 x SPDT, 7A (2.5A) @ 250 VAC, UL
B340L 200 1½ 40 4.80” [122] 2.44” [62] 2.61” [67]
listed, one switch is fixed at +5°, one is
B350L 200 2 50 5.60” [142] 2.67” [68] 3.11” [79]
adjustable 25° to 85° (double insulated)
* Dual Mounted Actuators

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

18
WARNING
Live Electrical Components!
AF Actuators, On/Off
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams

W194_AFB24-X1
24 VAC Transformer

Line 1 Common
Volts 2 + Hot 3
1 Provide overload protection and disconnect as required.

2 CAUTION Equipment damage! AFB24-X1 2


Actuators may be connected in parallel.
Power consumption must be observed. On/Off Wiring for AFB24-X1, AFRB24-3, AFRX24-3

3 Actuators may also be powered by 24 VDC.

W003_AFB24-X1
For end position indication, interlock control, fan startup, etc., AF24-S 24 to 240 VAC
US incorporates two built-in auxiliary switches: 2 x SPDT, 7A (2.5A) @
4 250 VAC, UL listed, one switch is fixed at +5°, one is adjustable 25° to
85°.

1 Provide overload protection and disconnect as required.


Meets cULus or UL and CSA requirements without the AFBUP-X1
AFBUP-S-X1
need of an electrical ground connection. 2
Actuators may be connected in parallel. Power consumption
must be observed.

WARNING Live Electrical Components! On/Off Wiring for AFBUP-X1, AFBUP-S-X1


3 Actuator may also be powered by 24VDC.
During installation, testing, servicing and troubleshooting of this product, it may

W195_AFBUP-S-X1
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

AFBUP-S-X1
W194
Auxiliary Switches
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

19
AF Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

B C F

A
D

Models Valve Nominal Size Dimensions (Inches)


AFX24-MFT-X1
Valve Body COP Inches DN [mm] A B C D F
AFX24-MFT-S-X1 w/built-in Aux. Switches
B224VS 400 1 25 7.00 1.25 6.77 3.37 6.25
AFX24-MFT95-X1
B225VS 200 1 25 7.00 1.25 6.77 3.62 6.25
AFRX24-MFT
B232VS 600 1¼ 32 7.00 1.25 6.77 3.97 6.25
*B239VS 600 1½ 40 15.00 N/A 13.54 4.37 6.25
Technical Data *B240VS 600 1½ 40 15.00 N/A 13.54 4.75 6.25
Control MFT *B249VS 600 2 50 15.00 N/A 13.54 4.68 6.25
Control signal 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor) B224VSS 1000 1 25 7.00 1.25 6.77 3.37 6.25
0-135 Ω (MFT95) B232VSS 1000 1¼ 32 7.00 1.25 6.77 3.97 6.25
Power supply 24 VAC ± 20% 50/60 Hz *B249VSS 1000 2 50 15.00 N/A 13.54 4.68 6.25
24 VDC ± 10%
Power consumption running 7.5 W
holding 3W
Transformer sizing 10 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S model has 2 cables) 3 ft. [1m], 18 GA appliance cable
Overload protection electronic throughout rotation Dimensions with 3-Way Valve
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
9.77”

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


[248.2]
4.04”
750 Ω for PWM [102.7]

1500 Ω for on/off and floating point


Feedback output 2 to 10 VDC, 0.5 mA max

[63.5]
2.50”
[99.9]
3.93”

Angle of rotation 95°


Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in switch
Position indication visual indicator
Manual override hex crank
Running time control 150 seconds independent of load
spring <20 seconds
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Housing NEMA 2 / IP54
Agency listings UL 873, CSA C22.2 No. 24 certified, CE Valve Nominal Dimensions (mm)
Noise level max. 45 dB(A) Size
DN
Valve Body COP Inches A B C
AFX24-MFT-S-X1 [mm]
Auxiliary switches 2 x SPDT, 7A (2.5A) @ 250 VAC, UL B332L 200 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]
listed, one switch is fixed at +5°, one is B340L 200 1½ 40 4.80” [122] 2.44” [62] 2.61” [67]
adjustable 25° to 85° (double insulated) B350L 200 2 50 5.60” [142] 2.67” [68] 3.11” [79]
* Dual Mounted Actuators

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

20
AF Actuators,
Wiring Multi-Function
– PWM, triac Technology
WARNING
source and s
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed

Wiring Diagrams
to live electrical components could result in death or serious injury.

W043
24 VAC/DC Transformer

Line (1) Common

2 CAUTION Equipment damage! Volts


(2) Hot
Actuators may be connected in parallel if not mechanically mounted to a
(–)
the same shaft. Power consumption and input impedance must be Position (3) Y Input
observed. Feedback VDC (+) (5) U Output

3 Actuators may also be powered by 24 VDC. WARNING CCW CW

Live Electrical Components! …MFT


During installation, testing, servicing and troubleshooting of this product, it maybe

4 IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155). necessary to work with live electrical components. Have a qualified licensed electrician

On/Off control
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
5 Triac A and B can also be contact closures.

W041
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or
6 Common (Sink) 24 VAC line. Line (1) Common
Volts 6
Position feedback cannot be used with Triac sink controller. (2) + Hot
7 The actuators internal common reference is not compatible. (3) Y Input
7 Position (–)
Feedback VDC (+) (5) U Output

The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to CCW CW


…MFT
2 to 10 VDC, up to 2 actuators may be connected in parallel.
Meets cULus or UL and CSA requirements without the
PWM, triac source and sink
need of an electrical ground connection.

W302_AFBX24-MFT
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

...MFT
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Floating Point control

Propotional 2 to 10 or 4 to 20 mA control signal W303


W195-AFX24-MFT-S-X1

AFX24-MFT-S-X1

Auxiliary Switches

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

21
AF Actuators, Multi-Function Technology

Actuators: AF24-MFT95-X1 GMX24-MFT95 AMX24-MFT95 NMX24-MFT95 LMX24-MFT95

High Limit Control Typical wiring diagrams for multiple actuators


INSTALLATION NOTES used with the W973, W7100 and T775 controllers

W017
24 VAC Transformer Q209A

W020
21 Minimum Position
21 24 VAC Transformer Potentiometer
21 Provide overload protection and Line Blk (1) Common
disconnect as required. Volts Red (2) + Hot Line Blk (1) Common
23 Volts Red (2) + Hot
22 Actuators and controller must have 22 Wht (3) W
23
W 24
separate transformers. Series 90 Wht (4) R
22 B R W Wht (3) W 25
R
Controller
Wht (4) R
23 Consult controller instruction data for B R W B Wht (5) B H205
Changeover W R B
Wht (5) B
more detailed information. Wht (6) ‘U5’ Output 2 to 10 VDC
Controller

Series 90 high limit control - 280 Ω


Wht (6) ‘U5’ Output 2 to 10 VDC
-MFT95-X1
24 Resistor value depends on the type of -MFT95-X1
controller and the number of 22
Wiring Multiple Actuators to a Series 90 Controller W
actuators. No resistor is used for one Shunting
Resistor
24 VAC Transformer
actuator. Honeywell® resistor kits may B

W018
Occupied
21 Contact
also be used. Line Blk (1) Common Y
Honeywell T675A
Volts Red (2) + Hot Morning Warmup
25 To reverse control rotation, use the 23 R R W
24
reversing switch. W973, W7100
W Wht (3) W 25 Controller
Shunting
Resistor R Wht (4) R
Override Wht (5) B
B
24 21
Switch A Switch B Damper Position Series 90 Wht (6) ‘U5’ Output 2 to 10 VDC
Controller Line Blk (1) Common
Damper Open -MFT95-X1 Volts Red (2) + Hot
21 23
Damper Closed
Line Blk (1) Common Wht (3) W 25
The direction of rotation switch is set so that the fail safe position and the Volts Red (2) + Hot No. of
position of the damper is closed with no signal at wire R. 23 actuators Resistance Wht (4) R
2 1300 Ω
3 910 Ω Wht (5) B
Wht (3) W 25
21 24 VAC Transformer
No. of 4 768 Ω
actuators Resistance Wht (6) ‘U5’ Output 2 to 10 VDC
Wht (4) R
W015

2 140 Ω Resistor Kit No. ZG-R06 To other


Line Blk (1) Common 3 71.5 Ω Wht (5) B actuators -MFT95-X1
Volts 4 47.5 Ω
Red (2) + Hot 5 37.5 Ω Wht (6) ‘U5’ Output 2 to 10 VDC
23 6 28 Ω Used with the W973 and W7100 controllers
A To other
-MFT95-X1
Resistor Kit No. ZG-R03 actuators
Wht (3) W 24
135 Ω Wht (4) R Wiring Multiple Actuators to a Series 90 Controller
B Honeywell Q209A
Wht (5) B using a Minimum Position Potentiometer Minimum Position
Wht (6) ‘U5’ Output 2 to 10 VDC 21 24 VAC Transformer Potentiometer

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


S963A
W019

Minimum Position
-MFT95-X1 24 VAC Transformer Potentiometer
24 VAC Transformer 21 Line Blk (1) Common
21
Line Volts Red (2) + Hot
Line Blk (1) Common 23
Blk (1) Common
Volts Red (2) + Hot 23 22
Volts Red (2) + Hot 25
23 Series 90 W R B W Wht (3) W 25
Controller 24
A R B W R Wht (4) R
B Wht (3) W R W
W Wht (3) W 24
Line Wht (4) R B Wht (5) B
Wht (4) R R
Volts
R 22 Shunting
B W Wht (5) B
Resistor
Wht (6) ‘U5’ Output 2 to 10 VDC
B Wht (5) B Shunting
Resistor W973, W7100 Honeywell
T775 T675A Morning
Wht (6) ‘U5’ Output 2 to 10 VDC -MFT95-X1
22 Controller Wht (6) ‘U5’ Output 2 to 10 VDC 23 Warmup
24
-MFT95-X1
-MFT95-X1 B R W
H205 Change- Occupied
over Controller Contact
Low Limit Control
W016

24 VAC Transformer
21
21
21
Line Blk (1) Common Line Blk (1) Common
Line Blk (1) Common
Volts Red (2) + Hot Volts Red (2) + Hot
23 Volts Red (2) + Hot 23
23
22 Wht (3) W 22 22
W W R B 24 Wht (3) W 25
Series 90
Wht (3) W 25
R Wht (4) R Wht (4) R
Controller Wht (4) R
B Wht (5) B Wht (5) B
Wht (5) B
Series 90 low limit control Wht (6) ‘U5’ Output 2 to 10 VDC Wht (6) ‘U5’ Output 2 to 10 VDC Wht (6) ‘U5’ Output 2 to 10 VDC
135 Ω for 0 to 50% control To other To other
280 Ω for 0 to 100% control -MFT95-X1 actuators -MFT95-X1 actuators -MFT95-X1

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

22
LM(B)X24-3-X1, LRX24-3 Actuators, On/Off, Floating Point

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

Models
LMB24-3-X1 D

LMX24-3-X1
Valve Nominal Size Dimensions (Inches)
LRX24-3
Valve Body COP Inches DN [mm] A B C D F H1 H2
B2050VS-01 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
Technical Data B2050VS-02 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
Control on/off, floating point B2050VS-04 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
Power supply 24 VAC ± 20% 50/60 Hz B2050VS-15 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
24 VDC ± 10%
Power consumption running 1.5 W
holding 0.2 W Dimensions with 3-Way Valve
Transformer sizing 3 VA (class 2 power source)
Electrical connection ½” conduit connector
LMB24-3-X1 3 ft., 18 GA plenum rated cables
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation 95°
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Torque 45 in-lbs [5 Nm]


Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 95 seconds, constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA type 2/IP54
Housing material UL94-5VA
Agency listings cULus acc. to UL 60730-1/-2-14,
CAN/CSA C22.2 No. 24 certified, Valve Nominal Dimensions (mm)
CE acc. to 73/23/EEC Size
Noise level <35 db(A) DN
Valve Body COP Inches A B C
Servicing maintenance free [mm]
Quality standard ISO 9001 B315L 200 ½ 15 2.63” [67] 1.73” [44] 1.42” [36]
B320L 200 ¾ 20 3.01” [78] 1.81” [46] 1.63” [42]
B325L 200 1 25 3.42” [87] 1.81” [46] 1.77” [45]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

23
LM(B)X24-3-X1, LRX24-3 Actuators, On/Off, Floating Point

Wiring Diagrams

W266-08
1 Provide overload protection and disconnect as required.

3 Actuators may also be powered by 24 VDC.

Meets cULus or UL and CSA requirements without the


need of an electrical ground connection.

WARNING Live Electrical Components! On/Off control


During installation, testing, servicing and troubleshooting of this product, it may

W267-08
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

Floating Point or On/Off control

Piping
The valve should be mounted in a weather-protected area in a location that is
within the ambient limits of the actuator. Allow sufficient room for valve with
actuator and for service. Allow 6” for cover removal and 12” for complete
actuator removal. The assembly can be mounted with the actuator vertical
or horizontal in relation to the pipe. The actuators should never be mounted
underneath the valve, as condensation can build up and result in a failure of
the actuators. Do not reverse flow direction.

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

24
LMX24-MFT-X1, LRX24-MFT Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

Models
LMX24-MFT-X1 D

LRX24-MFT
Valve Nominal Dimensions (Inches)
Size
Technical Data DN
Power supply 24 VAC ± 20% 50/60 Hz Valve Body COP Inches A B C D F H1 H2
[mm]
24 VDC ± 10% B2050VS-01 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
Power consumption 2W B2050VS-02 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
Transformer sizing 3.5 VA (class 2 power source) B2050VS-04 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
Electrical connection 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] B2050VS-15 100 ½ 15 6.75 2.00 6.75 2.25 4.00 9.75 8.50
18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout 0° to 95° rotation
Input impedance 100k Ω for 2 to 10 VDC (0.1 mA) Dimensions with 3-Way Valve
500 Ω for 4 to 20 mA
750 Ω for PWM
1500 Ω for on/off and floating point
Feedback 2 to 10 VDC, 0.5 mA max
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

VDC variable
Angle of rotation 95°
Torque 45 in-lbs [5 Nm]
Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 150 seconds (default)
variable (35 to 150 seconds)
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA type 2/IP54
Housing material UL94-5VA
Valve Nominal Dimensions (mm)
Agency listings cULus acc. to UL 60730-1/-2-14,
Size
CAN/CSA E60730-1, CSA C22.2
No. 24-93, CE acc. to 89/336/EEC DN
Valve Body COP Inches A B C
[mm]
Noise level <35 db(A)
B315L 200 ½ 15 2.63” [67] 1.73” [44] 1.42” [36]
Servicing maintenance free
B320L 200 ¾ 20 3.01” [78] 1.81” [46] 1.63” [42]
Quality standard ISO 9001
B325L 200 1 25 3.42” [87] 1.81” [46] 1.77” [45]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

25
Wht (3) Y Input
2 Position (–)
Feedback VDC (+) Org (5) U Output

Notes:
LMX24-MFT-X1, LRX24-MFT Actuators, Multi-Function Technology …MFT
1 Provide overlo
Actuators may
2 to the same sh
On/Off be observed.
Wiring Diagrams

W399
24 VAC/DC Transformer 2 3 Actuators may
1 Provide overload protection and disconnect as required. 1
Position feedb
Line Blk (1) Common 4 The actuator i
3 Actuators may also be powered by 24 VDC. Volts
Red (2) Hot Control signal
3 5
Position feedback cannot be used with Triac sink controller. or Common (S
4 The actuator internal common reference is not compatible. Position (–)
a
Wht (3) Y Input ZG-R01 may
6
Control signal may be pulsed from either the Hot (source) Feedback VDC (+) Org (5) U Output
5 or the Common (sink) 24 VAC line. 7
Contact closu
both be closed
…MFT
6 ZG-R01 may be used. 8
For triac sink
On/Off control must be conn
Contact closures A & B also VDC/4-20 mA
can be triacs. Floating Point
7 A& B should both be closed for triac source
24 VACand open for triac sink.

W399
Transformer 24 VAC Transformer
2
For triac sink the common connection
1 from the actuator 2 1
8 must be connected to the hot connection
Line of the controller. Blk (1) Common Line Blk (1) Common –
Volts Red (2) + Hot Volts Red (2) Hot +
500Ω
3 Ω 1/4 watt
(–) A
Control Signal 3 Wht (3) Y1 Input 8
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
or 5 B
2 to 10 VDC 6 Pnk (4) Y2 Input
Org (5) U Output, 2 to 10V 7
2 to 10 VDC
Org (5) U Output 2 to 10V
Feedback Signal
…MFT 4
VDC/4-20 mA …MFT Floating Point
Floating PointVDC/4-20 mA Floating24
Point
PWM 24 VAC Transformer VAC
1 24 VAC Transformer 1

W399
2 24 VAC
24 VAC Transformer (AC only) Line Blk (1) Common 1
1 1 2 Line
Volts Blk (1) +Common
Red (2) Hot Volts
Blk (1) Common Line Line
Line 500Ω
5 Volts
3 Ω 1/4 watt Red (2) + Hot Volts
Volts
Red (2) + Hot (–) 500Ω
Control
3 Signal Ω 1/4 watt 3
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
Wht (3) Y Input ControlorSignal (–) 3
2 Position (–)
24to
to10
20VDC
mA (+) 6
Org (5) U Output Wht (3) Y1 Input, 2 to 10V
Feedback VDC (+) or
2 to 10 VDC 6 Org (5) U Output, 2 to 10V
2 to 10
Notes: Org (5) U Output, 2 to 10V Feedback
2 to 10
…MFT …MFT Feedback
1 Provide overload protection and disconnect as required.
…MFTmounted
Actuators may be connected in parallel if not mechanically
2to the same shaft. Power consumption and input impedance must
On/Off VDC/4-20 mAPWM
be observed.
3PWM

W399
24 VAC/DC Transformer 2 Actuators24may also
VAC be powered(AC
Transformer by 24 VDC.
only)
1

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


1
Position feedback cannot be used with a Triac sink controller.
24 VAC Transformer (AC only)
4 The actuator internal common reference is Blk
Line Blk (1) Common 1 Line (1) Common
not compatiable.
Volts Volts 5
Red (2) Hot BlkHot(2)
Line signal may be pulsed from either the
Control Red (1) Common
+ Hot
(Source)
3 5 5
or Volts
Common (Sink) 24 VAC line.
a Red
Wht (2) + Hot
(3) Y Input
Position (–)
Wht (3) Y Input 6
2 Position
ZG-R01 (–)
may be used.
Feedback VDC (+) Wht
Org (5) Y Input
(3) U Output
Feedback VDC (+) Org (5) U Output 2 Position
Contact
(–)
closures A & B also can be triacs. A & B should
7 Feedback
both VDC
be closed (+) source and open forOrg
for triac triac U Output
(5)sink.

…MFT
Notes:
For triac sink the common connection from the actuator
8 …MFT
must be connected to the hot connection of the controller. Notes:
1 Provide overlo
PWM …MFT
Provide overlo
1 Actuators may
2 to the same sh
On/Off 2
Actuators may
be observed.
to the same sh
On/Off be observed.
Actuators may
24 VAC/DC Transformer 2 3
1 Actuators may
24 VAC/DC Transformer 2 3 Position feedb
1 Line Blk (1) Common 4 The actuator i
Position feedb
Volts Blk (2) Common 4 The actuator
Line Red (1) Hot Control signali
3 Volts 5
Red (2) Hot or Common (S
a Control signal
3 Position (–) 5
Wht (3) Y Input 6
or Common
ZG-R01 may(S
a
(–)
PositionVDC (+)
Feedback Wht (5)
Org Y Input
(3) U Output 6 ZG-R01 closu
Contact may
7
Feedback VDC (+) Org (5) U Output both be closed
Contact closu
…MFT 7
For
bothtriac sink
be closed
8
…MFT must be conn
For triac sink
8
must be conn

W399
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

26
NM(B)X24-3-X1, NRB24-3 Actuators, On/Off, Floating Point

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

Models
NMB24-3-X1
NMX24-3-X1
D
NRB24-3
Valve Nominal Dimensions (Inches)
Technical Data Size
Control on/off, floating point Valve Body COP Inches DN [mm] A B C D F H1 H2
Power supply 24 VAC ± 20% 50/60 Hz B219VS 400 ¾ 20 6.70 2.00 8.00 3.00 6.25 9.75 8.50
24 VDC ± 10% B220VS 400 ¾ 20 6.70 2.00 8.00 3.12 6.25 9.75 8.50
Power consumption running 2.0 W B2050VSS-15 1000 ½ 15 6.70 2.00 8.00 2.25 6.25 9.75 8.50
holding 0.2 W B219VSS 1000 ¾ 20 6.70 2.00 8.00 3.00 6.25 9.75 8.50
Transformer sizing 4 VA (class 2 power source)
Electrical connection 3 ft., 18 GA plenum rated cable
Dimensions with 3-Way Valve
NMB24-3-X1 ½” conduit connector
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation max 95°, adjustable with mechanical stop
Torque 90 in-lbs [10 Nm]
Direction of rotation reversible with switch
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

=CCW with decreasing control signal (10-2V)


=CW with decreasing control signal (10-2V)
Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 95 seconds, constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA type 2/IP54
Housing material UL94-5VA
Agency listings cULus acc. to UL 60730-1/-2-14,
CAN/CSA C22.2 No. 24 certified, Valve Nominal Dimensions (mm)
CE acc. to 73/23/EEC Size
Noise level <45 db(A) DN
Servicing maintenance free Valve Body COP Inches A B C
[mm]
Quality standard ISO 9001 B332L 200 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

27
NM(B)X24-3-X1, NRB24-3 Actuators, On/Off, Floating Point

Wiring Diagrams

W266-08
1 Provide overload protection and disconnect as required.

3 Actuators may also be powered by 24 VDC.

Meets cULus or UL and CSA requirements without the


need of an electrical ground connection.

WARNING Live Electrical Components! On/Off control


During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician

W267-08
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

Floating Point or On/Off control

Piping
The valve should be mounted in a weather-protected area in a location that is
within the ambient limits of the actuator. Allow sufficient room for valve with
actuator and for service. Allow 6” for cover removal and 12” for complete
actuator removal. The assembly can be mounted with the actuator vertical
or horizontal in relation to the pipe. The actuators should never be mounted
underneath the valve, as condensation can build up and result in a failure of
the actuators. Do not reverse flow direction.

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

28
NMX24-MFT-X1, NRX24-MFT Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

Models
NMX24-MFT-X1
D
NRX24-MFT
Valve Nominal Dimensions (Inches)
Technical Data Size
Power supply 24 VAC ± 20% 50/60 Hz Valve Body COP Inches DN [mm] A B C D F H1 H2
24 VDC ± 10% B219VS 400 ¾ 20 6.70 2.00 8.00 3.00 6.25 9.75 8.50
Power consumption 3.5 W (1.25 W) B220VS 400 ¾ 20 6.70 2.00 8.00 3.12 6.25 9.75 8.50
Transformer sizing 5.5 VA (class 2 power source) B2050VSS-15 1000 ½ 15 6.70 2.00 8.00 2.25 6.25 9.75 8.50
Electrical connection 3 ft. [1m], 10 ft. [3m], 16 ft. [5m] B219VSS 1000 ¾ 20 6.70 2.00 8.00 3.00 6.25 9.75 8.50
18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout 0° to 95° rotation Dimensions with 3-Way Valve
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
750 Ω for PWM
1500 Ω for on/off and floating point
Feedback 2 to 10 VDC, 0.5 mA max
VDC variable
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Angle of rotation max 95°, adjust. with mechanical stop


electronically variable
Torque 90 in-lbs [10 Nm]
Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 150 seconds (default)
Variable (45 to 170 secondss)
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA type 2/IP54 Valve Nominal Dimensions (mm)
Housing material UL94-5VA Size
Agency listings cULus acc. to UL 60730-1/-2-14, DN
Valve Body COP Inches A B C
CAN/CSA E60730-1, CSA C22.2 [mm]
No. 24-93, CE acc. to 89/336/EEC B332L 200 1¼ 32 4.13” [105] 2.00” [51] 2.19” [56]
Noise level <45 db(A)
Servicing maintenance free
Quality standard ISO 9001

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

29
Wht (3) Y Input
2 Position (–)
Feedback VDC (+) Org (5) U Output

Notes:
NMX24-MFT-X1, NRX24-MFT Actuators, Multi-Function Technology …MFT
1 Provide overlo
Actuators may
2 to the same sh
On/Off be observed.
Wiring Diagrams

W399
24 VAC/DC Transformer 2 3 Actuators may
1 Provide overload protection and disconnect as required. 1
Position feedb
Line Blk (1) Common 4 The actuator i
3 Actuators may also be powered by 24 VDC. Volts
Red (2) Hot Control signal
3 5
Position feedback cannot be used with Triac sink controller. or Common (S
4 The actuator internal common reference is not compatible. Position (–)
a
Wht (3) Y Input ZG-R01 may
6
Control signal may be pulsed from either the Hot (source) Feedback VDC (+) Org (5) U Output
5 or the Common (sink) 24 VAC line. 7
Contact closu
both be closed
…MFT
6 ZG-R01 may be used. 8
For triac sink
On/Off control must be conn
Contact closures A & B also VDC/4-20 mA
can be triacs. Floating Point
7 A& B should both be closed for triac source
24 VACand open for triac sink.

W399
Transformer 24 VAC Transformer
2
For triac sink the common connection
1 from the actuator 2 1
8 must be connected to the hot connection
Line of the controller. Blk (1) Common Line Blk (1) Common –
Volts Red (2) + Hot Volts Red (2) Hot +
500Ω
3 Ω 1/4 watt
(–) A
Control Signal 3 Wht (3) Y1 Input 8
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
or 5 B
2 to 10 VDC 6 Pnk (4) Y2 Input
Org (5) U Output, 2 to 10V 7
2 to 10 VDC
Org (5) U Output 2 to 10V
Feedback Signal
…MFT 4
VDC/4-20 mA …MFT Floating Point
Floating PointVDC/4-20 mA Floating24
Point
PWM 24 VAC Transformer VAC
1 24 VAC Transformer 1

W399
2 24 VAC
24 VAC Transformer (AC only) Line Blk (1) Common 1
1 1 2 Line
Volts Blk (1) +Common
Red (2) Hot Volts
Blk (1) Common Line Line
Line 500Ω
5 Volts
3 Ω 1/4 watt Red (2) + Hot Volts
Volts
Red (2) + Hot (–) 500Ω
Control
3 Signal Ω 1/4 watt 3
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
Wht (3) Y Input ControlorSignal (–) 3
2 Position (–)
24to
to10
20VDC
mA (+) 6
Org (5) U Output Wht (3) Y1 Input, 2 to 10V
Feedback VDC (+) or
2 to 10 VDC 6 Org (5) U Output, 2 to 10V
2 to 10
Notes: Org (5) U Output, 2 to 10V Feedback
2 to 10
…MFT …MFT Feedback
1 Provide overload protection and disconnect as required.
…MFTmounted
Actuators may be connected in parallel if not mechanically
2to the same shaft. Power consumption and input impedance must
On/Off VDC/4-20 mAPWM
be observed.
3PWM

W399
24 VAC/DC Transformer 2 Actuators24may also
VAC be powered(AC
Transformer by 24 VDC.
only)
1

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


1
Position feedback cannot be used with a Triac sink controller.
24 VAC Transformer (AC only)
4 The actuator internal common reference is Blk
Line Blk (1) Common 1 Line (1) Common
not compatiable.
Volts Volts 5
Red (2) Hot BlkHot(2)
Line signal may be pulsed from either the
Control Red (1) Common
+ Hot
(Source)
3 5 5
or Volts
Common (Sink) 24 VAC line.
a Red
Wht (2) + Hot
(3) Y Input
Position (–)
Wht (3) Y Input 6
2 Position
ZG-R01 (–)
may be used.
Feedback VDC (+) Wht
Org (5) Y Input
(3) U Output
Feedback VDC (+) Org (5) U Output 2 Position
Contact
(–)
closures A & B also can be triacs. A & B should
7 Feedback
both VDC
be closed (+) source and open forOrg
for triac triac U Output
(5)sink.

…MFT
Notes:
For triac sink the common connection from the actuator
8 …MFT
must be connected to the hot connection of the controller. Notes:
1 Provide overlo
PWM …MFT
Provide overlo
1 Actuators may
2 to the same sh
On/Off 2
Actuators may
be observed.
to the same sh
On/Off be observed.
Actuators may
24 VAC/DC Transformer 2 3
1 Actuators may
24 VAC/DC Transformer 2 3 Position feedb
1 Line Blk (1) Common 4 The actuator i
Position feedb
Volts Blk (2) Common 4 The actuator
Line Red (1) Hot Control signali
3 Volts 5
Red (2) Hot or Common (S
a Control signal
3 Position (–) 5
Wht (3) Y Input 6
or Common
ZG-R01 may(S
a
(–)
PositionVDC (+)
Feedback Wht (5)
Org Y Input
(3) U Output 6 ZG-R01 closu
Contact may
7
Feedback VDC (+) Org (5) U Output both be closed
Contact closu
…MFT 7
For
bothtriac sink
be closed
8
…MFT must be conn
For triac sink
8
must be conn

W399
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

30
AM(B)X24-3-X1, AR(B)X24-3 Actuators, On/Off, Floating Point

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

Models
AMB24-3-X1
AMX24-3-X1
D
ARX24-3
ARB24-3 Valve Nominal Dimensions (Inches)
ARB24-3-S Size
DN
Valve Body COP Inches A B C D F H1 H2
Technical Data [mm]
Control on/off, floating point B225VS 200 1 25 7.00 2.00 8.00 3.62 6.25 9.75 8.50
Power supply 24 VAC ± 20% 50/60 Hz B232VS 600 1¼ 32 7.25 2.00 8.00 3.97 6.25 9.75 8.50
24 VDC ± 10% B224VSS 1000 1 25 7.00 2.00 8.00 3.37 6.25 9.75 8.50
Power consumption running 2.5 W
holding 0.2 W
Dimensions with 3-Way Valve
Transformer sizing 5.5 VA (class 2 power source)
Electrical connection ½” conduit connector
AMB24-3-X1 3 ft., 18 GA plenum rated cable
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation max 95°, adjustable with mechanical stop
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Torque 180 in-lbs [20 Nm]


Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 95 seconds, constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA type 2/IP54
Housing material UL94-5VA
Agency listings cULus acc. to UL 60730-1/-2-14,
CAN/CSA C22.2 No. 24 certified,
CE acc. to 73/23/EEC Valve Nominal Dimensions (mm)
Noise level <45 db(A) Size
Servicing maintenance free DN
Quality standard ISO 9001 Valve Body COP Inches A B C
[mm]
B340L 200 1½ 40 4.80” [122] 2.44” [62] 2.61” [65]
B350L 200 2 50 5.60” [142] 2.67” [68] 3.11” [79]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

31
AM(B)X24-3-X1, AR(B)X24-3 Actuators, On/Off, Floating Point

Wiring Diagrams

W259-08
1 Provide overload protection and disconnect as required.

2 CAUTION Equipment damage!


Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.

5 Only connect common to neg. (–) leg of control circuits.

On/Off control

W260-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.

WARNING Live Electrical Components!


During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

Floating Point or On/Off control

Piping
The valve should be mounted in a weather-protected area in a location that is
within the ambient limits of the actuator. Allow sufficient room for valve with
actuator and for service. Allow 6” for cover removal and 12” for complete
actuator removal. The assembly can be mounted with the actuator vertical
or horizontal in relation to the pipe. The actuators should never be mounted
underneath the valve, as condensation can build up and result in a failure of
the actuators. Do not reverse flow direction.

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

32
AMX24-MFT-X1, ARX24-MFT Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

Models
AMX24-MFT-X1
AMX24-MFT95-X1
D
ARX24-MFT
Valve Nominal Dimensions (Inches)
Technical Data
Size
Power supply 24 VAC ± 20% 50/60 Hz
DN
24 VDC ± 10% Valve Body COP Inches A B C D F H1 H2
[mm]
Power consumption 4 W (1.25 W)
B225VS 200 1 25 7.00 2.00 8.00 3.62 6.25 9.75 8.50
Transformer sizing 6 VA (class 2 power source)
B232VS 600 1¼ 32 7.25 2.00 8.00 3.97 6.25 9.75 8.50
Electrical connection 3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
B224VSS 1000 1 25 7.00 2.00 8.00 3.37 6.25 9.75 8.50
18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout 0° to 95° rotation Dimensions with 3-Way Valve
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
750 Ω for PWM
1500 Ω for on/off and floating point
Feedback 2 to 10 VDC, 0.5 mA max
VDC variable
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Angle of rotation max 95°, adjust. with mechanical stop


electronically variable
Torque 180 in-lbs [20 Nm]
Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 150 seconds (default)
variable (90 to 350 seconds)
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA type 2/IP54 Valve Nominal Dimensions (mm)
Housing material UL94-5VA Size
Agency listings cULus acc. to UL 60730-1/-2-14, DN
CAN/CSA E60730-1, CSA C22.2 Valve Body COP Inches A B C
[mm]
No. 24-93, CE acc. to 89/336/EEC B340L 200 1½ 40 4.80” [122] 2.44” [62] 2.61” [65]
Noise level <45 db(A) B350L 200 2 50 5.60” [142] 2.67” [68] 3.11” [79]
Servicing maintenance free
Quality standard ISO 9001

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

33
Wht (3) Y Input
2 Position (–)
Feedback VDC (+) Org (5) U Output

Notes:
AMX24-MFT-X1, ARX24-MFT Actuators, Multi-Function Technology …MFT
1 Provide overlo
Actuators may
2 to the same sh
On/Off be observed.
Wiring Diagrams

W399
24 VAC/DC Transformer 2 3 Actuators may
1 Provide overload protection and disconnect as required. 1
Position feedb
Line Blk (1) Common 4 The actuator i
3 Actuators may also be powered by 24 VDC. Volts
Red (2) Hot Control signal
3 5
Position feedback cannot be used with Triac sink controller. or Common (S
4 The actuator internal common reference is not compatible. Position (–)
a
Wht (3) Y Input ZG-R01 may
6
Control signal may be pulsed from either the Hot (source) Feedback VDC (+) Org (5) U Output
5 or the Common (sink) 24 VAC line. 7
Contact closu
both be closed
…MFT
6 ZG-R01 may be used. 8
For triac sink
On/Off control must be conn
Contact closures A & B also VDC/4-20 mA
can be triacs. Floating Point
7 A& B should both be closed for triac source
24 VACand open for triac sink.

W399
Transformer 24 VAC Transformer
2
For triac sink the common connection
1 from the actuator 2 1
8 must be connected to the hot connection
Line of the controller. Blk (1) Common Line Blk (1) Common –
Volts Red (2) + Hot Volts Red (2) Hot +
500Ω
3 Ω 1/4 watt
(–) A
Control Signal 3 Wht (3) Y1 Input 8
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
or 5 B
2 to 10 VDC 6 Pnk (4) Y2 Input
Org (5) U Output, 2 to 10V 7
2 to 10 VDC
Org (5) U Output 2 to 10V
Feedback Signal
…MFT 4
VDC/4-20 mA …MFT Floating Point
Floating PointVDC/4-20 mA Floating24
Point
PWM 24 VAC Transformer VAC
1 24 VAC Transformer 1

W399
2 24 VAC
24 VAC Transformer (AC only) Line Blk (1) Common 1
1 1 2 Line
Volts Blk (1) +Common
Red (2) Hot Volts
Blk (1) Common Line Line
Line 500Ω
5 Volts
3 Ω 1/4 watt Red (2) + Hot Volts
Volts
Red (2) + Hot (–) 500Ω
Control
3 Signal Ω 1/4 watt 3
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
Wht (3) Y Input ControlorSignal (–) 3
2 Position (–)
24to
to10
20VDC
mA (+) 6
Org (5) U Output Wht (3) Y1 Input, 2 to 10V
Feedback VDC (+) or
2 to 10 VDC 6 Org (5) U Output, 2 to 10V
2 to 10
Notes: Org (5) U Output, 2 to 10V Feedback
2 to 10
…MFT …MFT Feedback
1 Provide overload protection and disconnect as required.
…MFTmounted
Actuators may be connected in parallel if not mechanically
2to the same shaft. Power consumption and input impedance must
On/Off VDC/4-20 mAPWM
be observed.
3PWM

W399
24 VAC/DC Transformer 2 Actuators24may also
VAC be powered(AC
Transformer by 24 VDC.
only)
1

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


1
Position feedback cannot be used with a Triac sink controller.
24 VAC Transformer (AC only)
4 The actuator internal common reference is Blk
Line Blk (1) Common 1 Line (1) Common
not compatiable.
Volts Volts 5
Red (2) Hot BlkHot(2)
Line signal may be pulsed from either the
Control Red (1) Common
+ Hot
(Source)
3 5 5
or Volts
Common (Sink) 24 VAC line.
a Red
Wht (2) + Hot
(3) Y Input
Position (–)
Wht (3) Y Input 6
2 Position
ZG-R01 (–)
may be used.
Feedback VDC (+) Wht
Org (5) Y Input
(3) U Output
Feedback VDC (+) Org (5) U Output 2 Position
Contact
(–)
closures A & B also can be triacs. A & B should
7 Feedback
both VDC
be closed (+) source and open forOrg
for triac triac U Output
(5)sink.

…MFT
Notes:
For triac sink the common connection from the actuator
8 …MFT
must be connected to the hot connection of the controller. Notes:
1 Provide overlo
PWM …MFT
Provide overlo
1 Actuators may
2 to the same sh
On/Off 2
Actuators may
be observed.
to the same sh
On/Off be observed.
Actuators may
24 VAC/DC Transformer 2 3
1 Actuators may
24 VAC/DC Transformer 2 3 Position feedb
1 Line Blk (1) Common 4 The actuator i
Position feedb
Volts Blk (2) Common 4 The actuator
Line Red (1) Hot Control signali
3 Volts 5
Red (2) Hot or Common (S
a Control signal
3 Position (–) 5
Wht (3) Y Input 6
or Common
ZG-R01 may(S
a
(–)
PositionVDC (+)
Feedback Wht (5)
Org Y Input
(3) U Output 6 ZG-R01 closu
Contact may
7
Feedback VDC (+) Org (5) U Output both be closed
Contact closu
…MFT 7
For
bothtriac sink
be closed
8
…MFT must be conn
For triac sink
8
must be conn

W399
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

34
Actuators: AF24-MFT95-X1 GMX24-MFT95 AMX24-MFT95 NMX24-MFT95 LMX24-MFT95
AMX24-MFT-X1 Actuators, Multi-Function Technology

High Limit Control Typical wiring diagrams for multiple actuators


INSTALLATION NOTES used with the W973, W7100 and T775 controllers

W017
24 VAC Transformer Q209A

W020
21 Minimum Position
21 24 VAC Transformer Potentiometer
21 Provide overload protection and Line Blk (1) Common
disconnect as required. Volts Red (2) + Hot Line Blk (1) Common
23 Volts Red (2) + Hot
22 Actuators and controller must have 22 Wht (3) W
23
W 24
separate transformers. Series 90 Wht (4) R
22 B R W Wht (3) W 25
R
Controller
Wht (4) R
23 Consult controller instruction data for B R W B Wht (5) B H205
Changeover W R B
Wht (5) B
more detailed information. Wht (6) ‘U5’ Output 2 to 10 VDC
Controller

Series 90 high limit control - 280 Ω


Wht (6) ‘U5’ Output 2 to 10 VDC
-MFT95-X1
24 Resistor value depends on the type of -MFT95-X1
controller and the number of 22
Wiring Multiple Actuators to a Series 90 Controller W
actuators. No resistor is used for one Shunting
Resistor
24 VAC Transformer
actuator. Honeywell® resistor kits may B

W018
Occupied
21 Contact
also be used. Line Blk (1) Common Y
Honeywell T675A
Volts Red (2) + Hot Morning Warmup
25 To reverse control rotation, use the 23 R R W
24
reversing switch. W973, W7100
W Wht (3) W 25 Controller
Shunting
Resistor R Wht (4) R
Override Wht (5) B
B
24 21
Switch A Switch B Damper Position Series 90 Wht (6) ‘U5’ Output 2 to 10 VDC
Controller Line Blk (1) Common
Damper Open -MFT95-X1 Volts Red (2) + Hot
21 23
Damper Closed
Line Blk (1) Common Wht (3) W 25
The direction of rotation switch is set so that the fail safe position and the Volts Red (2) + Hot No. of
position of the damper is closed with no signal at wire R. 23 actuators Resistance Wht (4) R
2 1300 Ω
3 910 Ω Wht (5) B
Wht (3) W 25
21 24 VAC Transformer
No. of 4 768 Ω
actuators Resistance Wht (6) ‘U5’ Output 2 to 10 VDC
Wht (4) R
W015

2 140 Ω Resistor Kit No. ZG-R06 To other


Line Blk (1) Common 3 71.5 Ω Wht (5) B actuators -MFT95-X1
Volts 4 47.5 Ω
Red (2) + Hot 5 37.5 Ω Wht (6) ‘U5’ Output 2 to 10 VDC
23 6 28 Ω Used with the W973 and W7100 controllers
A To other
-MFT95-X1
Resistor Kit No. ZG-R03 actuators
Wht (3) W 24
135 Ω Wht (4) R Wiring Multiple Actuators to a Series 90 Controller
B Honeywell Q209A
Wht (5) B using a Minimum Position Potentiometer Minimum Position
Wht (6) ‘U5’ Output 2 to 10 VDC S963A W019 21 24 VAC Transformer Potentiometer
Minimum Position
-MFT95-X1 24 VAC Transformer Potentiometer
21 Line Blk (1) Common
21 24 VAC Transformer
Line Volts Red (2) + Hot
Line Blk (1) Common 23
Blk (1) Common
Volts Red (2) + Hot 23 22
Volts Red (2) + Hot 25
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

23 Series 90 W R B W Wht (3) W 25


Controller 24
A R B W R Wht (4) R
B Wht (3) W R W
W Wht (3) W 24
Line Wht (4) R B Wht (5) B
Wht (4) R R
Volts
R 22 Shunting
B W Wht (5) B
Resistor
Wht (6) ‘U5’ Output 2 to 10 VDC
B Wht (5) B Shunting
Resistor W973, W7100 Honeywell
T775 T675A Morning
Wht (6) ‘U5’ Output 2 to 10 VDC -MFT95-X1
22 Controller Wht (6) ‘U5’ Output 2 to 10 VDC 23 Warmup
24
-MFT95-X1
-MFT95-X1 B R W
H205 Change- Occupied
over Controller Contact
Low Limit Control
W016

24 VAC Transformer
21
21
21
Line Blk (1) Common Line Blk (1) Common
Line Blk (1) Common
Volts Red (2) + Hot Volts Red (2) + Hot
23 Volts Red (2) + Hot 23
23
22 Wht (3) W 22 22
W W R B 24 Wht (3) W 25
Series 90
Wht (3) W 25
R Wht (4) R Wht (4) R
Controller Wht (4) R
B Wht (5) B Wht (5) B
Wht (5) B
Series 90 low limit control Wht (6) ‘U5’ Output 2 to 10 VDC Wht (6) ‘U5’ Output 2 to 10 VDC Wht (6) ‘U5’ Output 2 to 10 VDC
135 Ω for 0 to 50% control To other To other
280 Ω for 0 to 100% control -MFT95-X1 actuators -MFT95-X1 actuators -MFT95-X1

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

35
GMB24-3-X1 Actuators, On/Off, Floating Point

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

D
Models
GMB24-3-X1 Valve Nominal Dimensions (Inches)
Size
Valve Body COP Inches DN [mm] A B C D F H1 H2
Technical Data B239VS 400 1½ 40 7.50 3.00 8.00 4.37 6.25 9.75 8.50
Control on/off, floating point B240VS 400 1½ 40 7.50 3.00 8.00 4.75 6.25 9.75 8.50
Power supply 24 VAC ± 20% 50/60 Hz B249VS 400 2 50 7.50 3.00 8.00 4.68 6.25 9.75 8.50
24 VDC ± 10%
B249VSS 1000 2 50 7.50 3.00 8.00 4.68 6.25 9.75 8.50
Power consumption running 4 W
holding 2 W
Transformer sizing 6 VA (class 2 power source)
Electrical connection 3 ft. [1m]
18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout stroke
Angle of rotation 95°
Direction of rotation reversible with switch

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


Position indication reflective visual indicator (snap-on)
Running time 150 seconds, constant independent of load
Humidity 5 to 95% RH non-condensing
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Housing NEMA 2/IP54 with cable entry down
Housing material UL94-5V (flammability rating)
Agency listings cULus acc. to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE acc. to 89/336/EEC
Noise level <45 dB(A)
Quality standard ISO 9001

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

36
GMB24-3-X1 Actuators, On/Off, Floating Point

Wiring Diagrams
1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel if not mechanically mounted to
2 the same shaft. Power consumption and input impedance must be
observed.
3 Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
4 The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
5 or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
7 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
8 must be connected to the hot connection of the controller.

W259-08_GMB24-3-X1

GMB24-3-X1

On/Off control
W260-08_GMB24-3-X1
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

GMB24-3-X1

Floating Point or On/Off control

Piping
The valve should be mounted in a weather-protected area in a location that is
within the ambient limits of the actuator. Allow sufficient room for valve with
actuator and for service. Allow 6” for cover removal and 12” for complete
actuator removal. The assembly can be mounted with the actuator vertical
or horizontal in relation to the pipe. The actuators should never be mounted
underneath the valve, as condensation can build up and result in a failure of
the actuators. Do not reverse flow direction.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

37
GMX24-MFT-X1 Actuators, Multi-Function Technology

Dimensions with 2-Way Valve

PAGE7
H2

H1

B C F

D
Models
GMX24-MFT-X1 Valve Nominal Dimensions (Inches)
GMX24-MFT95-X1 Size
DN
Valve Body COP Inches A B C D F H1 H2
[mm]
Technical Data B239VS 400 1½ 40 7.50 3.00 8.00 4.37 6.25 9.75 8.50
Control on/off, floating point, 2 to 10 VDC B240VS 400 1½ 40 7.50 3.00 8.00 4.75 6.25 9.75 8.50
Power supply 24 VAC ± 20% 50/60 Hz B249VS 400 2 50 7.50 3.00 8.00 4.68 6.25 9.75 8.50
24 VDC ± 10% B249VSS 1000 2 50 7.50 3.00 8.00 4.68 6.25 9.75 8.50
Power consumption running 4.5 W
holding 3 W
Transformer sizing 7 VA (class 2 power source)
Electrical connection 3 ft. [1m]
18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout stroke
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


500 Ω for 4 to 20 mA
750 Ω for PWM
1500 Ω for on/off and floating point
Feedback 2 to 10 VDC, 0.5 mA max
VDC variable
Angle of rotation 95°
Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on)
Running time 150 seconds, constant independent of load
Humidity 5 to 95% RH non-condensing
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Housing NEMA 2/IP54 with cable entry down
Housing material UL94-5V (flammability rating)
Agency listings cULus acc. to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE acc. to 89/336/EEC
Noise level <45 dB(A)
Quality standard ISO 9001

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

38
24 VAC Transformer 24 VAC Transformer
2
1 2 1
Line Blk (1) Common Line Blk (1) Common –
Volts
GMX24-MFT-X1 Actuators, Multi-Function Technology
Red (2) + Hot Volts Red (2) Hot +
500Ω
3 Ω 1/4 watt
(–) A
Control Signal 3 Wht (3) Y1 Input 8
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
or 5 B
2 to 10 VDC 6 Pnk (4) Y2 Input
Wiring Diagrams Org (5) U Output, 2 to 10V 7
2 to 10 VDC
Org (5) U Output 2 to 10V
1 Provide overload protection and disconnect as required. Feedback Signal
…MFT 4
Actuators may be connected in parallel if not mechanically mounted to
…MFT
2 the same shaft. Power consumption and input impedance must be
observed.
PWM
3 Actuators may also be powered by 24 VDC.
24 VAC Transformer (AC only)
1
Position feedback cannot be used with Triac sink controller.
4 The actuatorLine
internal common reference
Blk (1) Common
is not compatible.
Volts 5
Control signal may be pulsed from either the HotRed
(source)
(2) + Hot
5 or the Common (sink) 24 VAC line. Wht (3) Y Input
2 Position (–)
6 ZG-R01 may be used.VDC
Feedback (+) Org (5) U Output

Contact closures A & B also can be triacs.


7 A& B should both be closed for triac source and open for triac sink.
Notes:
…MFT
For triac sink the common connection from the actuator 1 Provide overload protection and disconnect as required.
8 must be connected to the hot connection of the controller. Actuators may be connected in parallel if not mechanically mounted
2 to the same shaft. Power consumption and input impedance must
On/Off be observed.

W399
24 VAC/DC Transformer 2 3 Actuators may also be powered by 24 VDC.
1
Position feedback cannot be used with a Triac sink controller.
Line Blk (1) Common 4 The actuator internal common reference is not compatiable.
Volts
Red (2) Hot Control signal may be pulsed from either the Hot (Source)
3 5 or Common (Sink) 24 VAC line.
a
Position (–)
Wht (3) Y Input 6 ZG-R01 may be used.
Feedback VDC (+) Org (5) U Output Contact closures A & B also can be triacs. A & B should
7
both be closed for triac source and open for triac sink.
…MFT For triac sink the common connection from the actuator
8
On/Off control must be connected to the hot connection of the controller.
Floating Point
W399

24 VAC Transformer
2
1
Blk (1) Common Line Blk (1) Common –
Red (2) + Hot Volts Red (2) Hot +
A
3 Wht (3) Y1 Input 8
Wht (3) Y1 Input, 2 to 10V
5 B
Pnk (4) Y2 Input
Org (5) U Output, 2 to 10V 7
2 to 10 VDC
Org (5) U Output 2 to 10V
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Feedback Signal
…MFT 4
VDC/4-20 mA …MFT Floating Point
Floating PointVDC/4-20 mA Floating24
Point
24 VAC Transformer VAC Transformer
2
1 24 VAC Transformer 1
W399

2 24 VAC Transformer
only) Line Blk (1) Common 2 Blk (1) Common –
1 2 1
Line
Volts Blk (1) +Common
Red (2) Hot Volts
Blk (1) Common Line Line Blk (2) Common
Red (1) Hot + –
500Ω
Volts
3 Ω 1/4 watt Red (2) + Hot Volts
Red (2) + Hot A Red (2) Hot +
Control (–) 500Ω 3
3 Signal Ω 1/4 watt Wht (3) Y1 Input 8
4 to 20 mA (+) Wht (3) Y1 Input, 2 to 10V
Wht (3) Y Input (–) A
ControlorSignal 3 5 B Wht (3) Y1 Input 8
24to
to10
20VDC
mA (+) 6 Wht (3) Y1 Input, 2 to 10V Pnk (4) Y2 Input
Org (5) U Output or 5
2 to 10 VDC 6 Org (5) U Output, 2 to 10V B 7
2 to 10 VDC Pnk (4) Y2 Input
Org (5) U Output, 2 to 10V 7 Org (5) U Output 2 to 10V
Notes: Feedback Signal
2 to 10 VDC
4 Org (5) U Output 2 to 10V
…MFT
1 …MFT
Provide overload protection and disconnect as required. Feedback Signal W399
…MFTmounted 4 …MFT
Actuators may be connected in parallel if not mechanically
2
to the same shaft. Power consumption and input impedance must …MFT
VDC/4-20 mAPWM
be observed.
3PWM
W399

2 Actuators24may also
VAC be powered(AC
Transformer by 24 VDC.
only)
1
Position feedback cannot be used with a Triac sink controller.
24 VAC Transformer (AC only)
4 The actuator internal common reference is Blk
Blk (1) Common 1 Line (1) Common
not compatiable.
Volts 5
Red (2) Hot BlkHot(2)
Line signal may be pulsed from either the
Control Red (1) Common
+ Hot
(Source)
5 or Volts
Common (Sink) 24 VAC line. 5
Red + Hot
(2) Y
Wht (3) Input
Wht (3) Y Input 6
2 Position
ZG-R01 (–)
may be used.
Feedback VDC (+) Wht (5)
Org Y Input
(3) U Output
Org (5) U Output 2 Position
Contact
(–)
closures A & B also can be triacs. A & B should
7 Feedback
both VDC
be closed (+) source and open forOrg
for triac triac U Output
(5)sink.

…MFT
Notes:
For triac sink the common connection from the actuator
8 …MFT
must be connected to the hot connection of the controller. Notes:
1 Provide overload protection and disconnect as required.
PWM …MFT
Provide overload
1 Actuators may be protection
connectedand disconnect
in parallel if notas required. mounted
mechanically
2 to the same shaft. Power consumption and input impedance must
On/Off 2
Actuators may be connected in parallel if not mechanically mounted
be observed.
to the same shaft. Power consumption and input impedance must
On/Off be observed.
Actuators may also be powered by 24 VDC.
24 VAC/DC Transformer 2 3
800-543-9038
1 USA 866-805-7089 CANADA
3 Actuators may alsocannot
Position feedback be powered by203-791-8396
be used 24 VDC.
with
LATIN AMERICA / CARIBBEAN
a Triac sink controller.
24 VAC/DC Transformer 2
1 Line Blk (1) Common 4 The actuator internal common reference is not compatiable.
Volts 4
Position feedback cannot be used with a Triac sink controller. 39
Line Blk (2)
Red Common
(1) Hot The actuator
Control signalinternal
may becommon reference
pulsed from either is
thenot
Hotcompatiable.
(Source)
3 Volts 5
Valve Accessories

GK/ AF/
WEATHER SHIELDS VALVES LR NR AR GR AKR LF NF LM NM AM GM
GKR AFR
ZS-EPIV-EV-20-NF Energy Valves •
For valve sizes ½” [DN15] to ¾” [DN20] (cover
only) ePIV •

ZS-EPIV-EV-50-SCNF Energy Valves • • • •


For valve sizes 1” [DN25] to 2” [DN50] on non-
fail-safe actuator series (cover only)
For valve sizes ½” [DN15] to 2” [DN50] on elec-
tronic fail-safe actuator series (cover only) ePIV • • • •

ZS-EPIV-EV-80 Energy Valves • •


For ANSI 125, valve sizes 2½” [DN65] and 3”
[DN80] (cover only) ePIV • •

ZS-EPIV-EV-150 Energy Valves • •


For ANSI 125, valve sizes 4” [DN100], 5”
[DN125], and 6” [DN150] (cover only) ePIV • •

ZS-CCV-90* PICCV •
Kit for LF actuator series CCV •

ZS-CCV-100* PICCV • •
Kit for LR/AR actuator series CCV • •

ZS-CCV-110* PICCV •
Kit for AFR actuator series CCV •
ZS-SPBV-10
For NM, AM,GM, NF, AF, and GK • • • • • •
actuator series

ZS-SPBV-20
For dual mounted GM, AF, and GK actuator series
• • •
Ball Valves
ZS-BVVS-0002
For LM actuator series on VS/VSS models

Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.


ZS-BVVS-0003
For LF actuator series on VS/VSS models

ZTH REPLACEMENT CABLES VALVES AM GM AR GR DR GK DK SY

ZK1-GEN Ball Valves • •


Cable for use with ZTH US to connect to new
generation non-spring return actuator via diagnostic/
programming socket Butterfly Valves • • • • • • •

ZK2-GEN
Cable for use with ZTH US to connect to new
Available for all MFT Actuators
generation non-spring return actuator via diagnostic/
programming socket

Ball Valves •
ZK6-GEN
Cable for use with ZTH US to connect to SY actuator
via RJII port Butterfly Valves •

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

40
Valve Accessories

AUXILIARY SWITCHES & POTENTIOMETERS VALVES LR/LM NR/NM AR/AM GR/GM AK GK/GKR

S1A
Auxiliary switch 1x SPDT, 3A • • • • • •
(0.5A inductive) @ 250 VAC
S2A
Auxiliary switch 2x SPDT, 3A • • • • • •
(0.5A inductive) @ 250 VAC
P140A GR
Feedback potentiometer 140 Ω
• • • • • •

P500A GR
Feedback potentiometer 500 Ω
• • • • • •
Available for
P500A GR All Valves
Feedback potentiometer 500 Ω
• • • • • •

P1000A GR
Feedback potentiometer 1000 Ω
• • • • • •

P2800A GR
Feedback potentiometer 2800 Ω
• • • • • •

P5000A GR
Feedback potentiometer 5000 Ω
• • • • • •

P10000A GR
Feedback potentiometer 10000 Ω
• • • • • •

PROGRAMMING TOOLS

Near Field Communication (NFC) App


Allows fast programming, commissioning, and troubleshooting even when the Where Available on NFC Labeled Actuators Only
actuator is not powered. Available through Google Play

MFT-P
Belimo MFT confi guration software (V3.X), includes PC-Tool software
(interface cables [ZTH US] not included). Available for all MFT Actuators
Physical copy of software. Free download also available at
www.belimo.us/americas/mft.html
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

ZTH US
Handheld interface module that
Available for all MFT Actuators
allows fi eld programming. Includes ZK1-GEN, ZK2-GEN,
and ZK6-GEN cables

COVERS

ZS-T Available for all -T Model Actuators


Terminal cover for NEMA 2, -T models (except TR)

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

41
Tech.Doc - 04/21 - Subject to change. © Belimo Aircontrols (USA), Inc.

Belimo Americas
USA, Latin America, and the Caribbean: www.belimo.us
Canada: www.belimo.ca
Brazil: www.belimo.com.br

Belimo Worldwide: www.belimo.com

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

42

You might also like