Reyrolle

Protection
Devices

7SR45 Argus
7SR45 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay

Energy Management
7SR45 Argus
7SR45 Argus Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay
Supervision
81HBL2 Inrush Detector

Features
Password Protection
Self Monitoring
Trip Timers
Healthy shut-down below operating ranges
Remote reset (binary input based) of flag with/without
CT power and Auxiliary power
Two Settings Groups

User Interface
16 Character x 2 Line Backlit LCD
Menu Navigation Keys
9 non-programmable LEDs
Description Local Flag Indicator

The 7SR45 Argus Self Powered/Dual Powered Non-


Directional Overcurrent and Earth Fault Relay is developed
Monitoring Functions
using the latest generation of hardware technology and is
available in multiple variants depending on the Current Primary/Secondary Current Phases and Earth
Transformer (CT), binary input/binary output, power supply, Second Harmonics current (Secondary)
and communication configuration. 7SR45 is a member of Binary Input/Binary Output Status
Siemens Reyrolle® protection devices Argus product family. Time and Date
Fault Records (Trip Log)
The 7SR45 Argus Self Powered/Dual Powered Non- Event Records (Event Log)
Directional Overcurrent and Earth Fault Relay is housed
either in a 4U high, size 4 or height reduced non draw-out
case and provides protection, monitoring, instrumentation, Hardware
and metering with integrated input and output logic and
fault reports. 4 CT (1 A or 5 A) (via ordering option)
4 BI, 4 BO or 2 BI, 2 BO (via ordering option)
The relay functionality can be configured via a front USB 1 Local Flag Indication (via ordering option)
port for local PC connection or rear electrical RS485 1 Remote Flag Output (via ordering option)
(optional) port for remote connection. By using the Reydisp
1 Pulse Output
Evolution software, the user can update the settings and
9 LEDs
view the fault records (trip log) and the event records
Rear RS485 Communication Port (via ordering option)
(event log).
Auxiliary Power Input (via ordering option)
7SR45 Argus Self Powered/Dual Powered Non-Directional
Overcurrent and Earth Fault Relay supports the
IEC 60870-5-103 and Modbus communication protocols. Data Storage and
Communication
7SR45 Argus Self Powered/Dual Powered Non-Directional
Overcurrent and Earth Fault Relay can indicate the trip with Front USB port + Rear RS485 port (optional)
local and remote flag indicator. Protocols – IEC 60870-5-103, Modbus RTU
Fault Records (Trip Log)
Event Records (Event Log)
Function Overview Time Synchronism
Viewing and Changing Settings
Protection Battery Profiling
50 Instantaneous Overcurrent Protection
50N/G Instantaneous Derived/Measured Earth
Fault Protection
51 Time Delayed Overcurrent Protection
51N/G Time Delayed Derived/Measured Earth
Fault Protection
50LC/SOTF Switch-On-To-Fault

Siemens Protection Devices 2


50/51 Phase Overcurrent Fault
Application 50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent
protection, each with independent settings for pickup
current, time-multiplier (51), and time-delays. User can
7SR45 Argus Self Powered/Dual Powered Relay is a numerical
select IEC or ANSI time current characteristics.
overcurrent and earth fault protection relay primarily
intended for secondary distribution electrical networks.
The IDMT curve has a user selectable reset characteristic,
either DTL or IEC or ANSI decaying to improve the grading
The 7SR45 Argus Self Powered/Dual Powered Non-
with electromechanical protection.
Directional Overcurrent and Earth Fault Relay is designed to
operate with/without an auxiliary supply. The 7SR45 Dual
50G/51G/50N/51N Measured/Derived Earth Fault
Powered Non-Directional Overcurrent and Earth Fault relay is
powered primarily from the auxiliary voltage even though all Two earth fault measurement modes are available. One
other power sources are available. mode directly measures the earth current from an
independent CT (50G/51G) and the second mode derives
In the absence of auxiliary voltage, the relay is powered by the residual current internally from the 3 line CTs (50N/51N).
CT input.
50G/50N INST/DTL and 51G/51N IDMTL/DTL elements
The relay offers definite-time and inverse-time overcurrent provide earth fault protection, each with independent
and earth fault protection functions in accordance to IEC settings for pickup current, time-multiplier (51G/51N), and
and ANSI standards. time-delays. User can select IEC or ANSI time current
characteristics.
7SR45 Argus Self Powered/Dual Powered Non-Directional
Overcurrent and Earth Fault Relay are built in with a The IDMT curve has a user programmable reset characteristic
capacitor discharge pulse output for low-energy trip coil of either DTL or IEC or ANSI decaying to improve grading with
the circuit breaker. Changeover binary outputs are also electromechanical protection.
available for trip via an auxiliary powered shunt trip coil.
1000

7SR45 Argus Self Powered/Dual Powered Non-Directional


Overcurrent and Earth Fault Relay are targeted for the
following applications:
• Protection Relay for Ring Main Units (RMU)
• Back up protection relay for the medium voltage
applications 100

• Protection applications in remote locations where auxiliary


supply is not available
• Control and relay panels refurbishment of old Time
electromechanical protection relays (sec)

Functional Diagram 10
Long Time Inverse

7SR45
Normal Inverse

50LC/ 50 81
51
SOTF (x2) HBL2
IL1 1
Very Inverse
(IA )

50LC/ 50 81
51
SOTF (x2) HBL2
IL2 Extremely Inverse

(IB )

50LC/ 50 81 0.1
51 1 2 3 4 5 6 8
10 20 30 40 50 60 80
100
SOTF (x2) HBL2 Current (multiples of setting)
IL3
(IC ) Fig 2. IEC Overcurrent Curves

50 81
51N HBL2
(x2)

IL4
(IG ) 50G 81
51G
(x2) HBL2

Fig 1. Functional Diagram of 7SR45 Argus Self Powered/


Dual Powered Non-Directional Overcurrent and
Earth Fault Relay

Siemens Protection Devices 3


1000

100

Time
(sec)

10

Fig 5. Operating Time for Switch-On-To fault with Pulse


Output
Moderately Inverse
1 NOTE:
Very Inverse Multi-phase faults will result in shorter operating time.

81HBL2 Inrush Detector


Extremely Inverse Where second harmonic current is detected (i.e. during
transformer energisation) user selectable protection function
0.1
elements can be blocked.
2 3 4 5 6 8 20 30 40 50 60 80
1 10 100
Current (multiples of setting)
Sensitivity
Fig 3. ANSI Overcurrent Curves In the absence of auxiliary voltage, the sensitivity of the
relay is the minimum phase current required for the relay to
50LC/SOTF energize, detect a fault and trip as per the configuration.
SOTF functionality provides high speed tripping if a fault is
still present on the feeder after the reclosure of the circuit The sensitivity of 7SR45 Argus Self Powered/Dual Powered
breaker (Close-on-to-Fault) or if earthing clamps are left Non-Directional Overcurrent and Earth Fault Relay is 20 % of
connected after maintenance. nominal current for single phase and 10 % of nominal
current in three phases. The PROTECTION HEALTHY LED and
The following graph shows the SOTF operating time
TRIP READY LED TURN ON when the relay is TRIP ready at the
depending on the fault currents.
above mentioned current levels.

The following graphs show the sensitivity of the relay and


corresponding operating time for different start up currents.

Fig 4. Operating Time for Switch-On-To fault with Binary


Outputs

Fig 6. Sensitivity for Single Phase Fault with Binary


Output

Siemens Protection Devices 4


An internal terminating resistor is provided, which can be
connected into the circuit by adding a wire loop between the
relevant terminals.

Ext Wir e lo op to
1 Ter m
1 Inc lud e l in e
To Control 2 2 A/+ term in atin g R es
3 3 GN D
System 4 4 B/-

R ea r te rmi na ls R ea r te rmi na ls
R S 4 85 Scr ee ne d R S 4 85 Scr ee ne d
twi sted pa ir twi sted pa ir

Fig 8. Typical RS485 Connection

The rear RS485 can be user selected to be OFF,


IEC 60870-5-103 or Modbus RTU.
Fig 7. Sensitivity for Single Phase Fault with Pulse Output

NOTE:
Multi-phase current will improve the sensitivity.

Data Acquisition -
Via Communication Interface

Sequence of Event Records (Event Log)


Up to 100 events can be stored and time tagged to 1 ms
resolution. The events are stored on first-in-first-out basis.
The events are available through the communication
interface.

Fault Records (Trip Log)


The last 10 fault records are displayed on the relay fascia and
are also available through the communication interface with
time and date of trip, measured quantities, and type of fault.

Real Time Clock


The time and date can be set and is maintained while the
relay is de-energised by a coin cell battery.

Communications
The relay offers a USB port as a standard on the front of all
units. All of the relay functions can be set on a PC using
Reydisp Evolution software via the USB port. The connection
is made with a USB cable and operates with a ‘plug and play’
connection, so no pre-setting of the relay is required.

In the dual powered relays, the front port can be switched


off or set to use either the Modbus RTU or IEC 60870-5-103
protocols for testing purposes. IEC60870-5-103 protocol is a
default in the Self Powered Relays.

NOTE:
Reydisp Evolution software will work with the relay only
when the USB port is configured to the IEC 60870-5-103
protocol in the dual powered relays.

A rear RS485 electrical connection is optionally available on


the relay for system interface connections.

Siemens Protection Devices 5


Construction User Interface
The relay is housed in a non draw-out 4U high, size 4 case.

The rear connection comprises of user friendly pluggable


type terminals for pulse and flag output, binary inputs,
binary outputs, RS485 communication and auxiliary input.

The CT terminals are suitable for ring type lug connection to


provide a secure and reliable termination.

Fig 15. User Interface

The operator interface is designed to provide a user friendly


method of viewing menus, entering settings, and retrieving
data from the relay. Five buttons are provided for navigation
around the menu structure. Additionally, two buttons are
Fig 9. 7SR4501 Front view Fig 10. 7SR4501Rear view provided for battery ON/OFF and backlight ON/OFF
functionality.

LCD
A 2 line by 16 character liquid crystal display with power
save operation indicates the relay identifier, settings,
instrumentation, and fault data.

LEDs
9 non-programmable LEDs are available eliminating the
need for expensive panel mounted pilot lights and
associated wiring. Each LED shows clear indication of the
associated functions state and has a label for identification.

Flag Indicator
1 local flag indicator is provided and configured for the trip
indication.
Fig 11. 7SR4502 Front view Fig 12. 7SR4502 Rear view
Relay Information
The device is identified by the rating label on the fascia. The
user can also give the device its own identity by editing the
‘Relay Identifier’ displayed on the LCD.

Power
7SR45 Argus Self Powered/Dual Powered Non-Directional
Overcurrent and Earth Fault Relay can be powered in the
following modes and their priority is as follows:

• Auxiliary Power Supply (only for Dual Powered Relay)


• CT Power
• USB Power
• Battery Power
Fig 13. 7SR4504 Front view Fig 14. 7SR4504 Rear view

Siemens Protection Devices 6


Indication of Conformity Sensitivity
This product complies with the directive of
the Council of the European Communities on Minimum phase 20 % of nominal current in single
the harmonization of the laws of the current for relay phase
Member States relating to electromagnetic operation 10 % of nominal current in three
compatibility (EMC Directive 2014/30/EU) phases
and concerning electrical equipment for use
within specified voltage limits (Low Voltage
Mechanical Specifications
Directive 2014/35/EU) as well as restriction
on usage of hazardous substances in
electrical and electronic equipment (RoHS Design Panel mounting, Non draw-out
Directive 2011/65/EU). Polycarbonate moulded case
Enclosure IP52 (front panel)
This conformity has been proved by tests IP40 (enclosure sides)
conducted by Siemens AG in accordance of IP10 (rear side)
the Council Directive in accordance with the
Weight ~1.97 kg
product standard IEC/EN 60255-26 for the
EMC directives, and with the standard IEC/EN
60255-27 for the low-voltage directive. Installation Category

RoHS directive 2011/65/EU is met using the Installation Cate- Class III
standard EN 50581. The device has been gory (Overvoltage
designed and produced for industrial use.
Category)

Technical Data Pollution

Pollution Degree 2
For full technical data, refer to the Performance Specification
Chapter of the Technical Manual.
Recommended Terminal Lugs Specifications
Technical Data Overview
TE connectivity PIDG series
Product Family Non Directional Self Powered/ insulated tin plated crimp ring
Dual Powered Overcurrent and Current Inputs terminal, M3.5 stud size, 2.6 mm²
Earth Fault Relay to 6.6 mm², 12 AWG, Torque
Case and LEDs Non draw-out Polycarbonate case required is 1.0 Nm
(Size 4 standard, Non draw-out Insulated tin plated crimp pin
design), 9 non-programmable connector, 2.6 mm² to 6.6 mm²,
LEDs Auxiliary Supply
12 AWG to 10 AWG, Torque required
Measuring Inputs 1 A or 5 A (via ordering option), 0.5 Nm to 0.6 Nm
(Current) 50 Hz/60 Hz
Rear Communica- Pin type lug/1.5 mm2 control cable,
Auxiliary voltage 24 V to 60 V DC, tion Port Torque required 0.5 Nm to 0.6 Nm
60 V to 240 V AC/DC (via ordering
Front Communica-
option) USB, Type B
tion Port
Communication Front communication port: USB
(IEC 60870-5-103 or Modbus RTU) Insulated tin plated crimp pin
Binary Input/Binary
Rear communication port: RS485 connector, 2.6 mm² to 6.6 mm²,
Output/Pulse
(IEC 60870-5-103 or Modbus RTU) 12 AWG to 10 AWG, Torque required
Output/Flag Output
0.5 Nm to 0.6 Nm
Protection Functions 50, 50G/N, 51, 51G/N, 50LC/SOTF
Supervision 81HBL2 – (Inrush detector) Tin plated crimp ring terminal,
Functions M3 stud size, 4 mm² to 6 mm²,
Ground Terminal
12 AWG to 10 AWG, Yellow, Torque
Binary Input and 4 BI and 4 BO (via ordering option)
required 0.5 Nm to 0.6 Nm
Binary Output
Remote flag 24 V, 0.01 Ws
Local flag Mechanical Flag Indicator (via
ordering option)
• Normal – Green colour
• Trip – Red colour
Pulse output 24 V, 0.1 Ws pulse output
Altitude of operation Maximum up to 2000 m

Siemens Protection Devices 7


Binary Outputs
Inputs and Outputs
Number 2 (1 NO contact and 1 C/O contact)
Auxiliary Supply or
4 (2 NO contact and 2 C/O contact)
(via ordering option)
Rated Voltage 60 V to 240 V AC/DC,
Tolerance: -20 % to +10 % Operating Voltage Potential free
24 V to 60 V DC, Operating Mode User selectable -
Tolerance: -20 % to +10 % BO 1 and BO 2 Self or Hand/Electrical
(via ordering option) Reset
Frequency 50 Hz (Range: 45 Hz to 55 Hz) BO 3 and BO 4 Self Reset (Operated
60 Hz (Range: 54 Hz to 66 Hz) only with Auxiliary input is present)
Allowable Alter- 15 % of DC voltage Operating Time from < 20 ms
nating component energizing Binary
in DC (Ripple) Input
Typical Power <7W Disengaging time < 20 ms
consumption (DC)
BO 1 and BO 2 Output Contact Details
Typical Power < 13 VA
consumption (AC) Switching Voltage 250 V AC and 125 V DC
Max Interruption ≤ 20 ms (19.2 V DC) Contact current
time (Collapse to ≤ 20 ms (48 V DC) rating:
Zero) ≤ 500 ms (230 V AC) Continuous 5 A AC or DC

Current Inputs Short time 20 A AC or DC for 0.5 s


30 A AC or DC for 0.2 s
Quantity 3 x Phase and 1 x Earth Limiting Making
Capacity: 1000 W
Rated Current (In) 1 A or 5 A (via ordering option)
(L/R ≤ 40 ms)
Measuring Range 0.2xIn to 20xIn
Limiting Breaking Capacity:
Instrumentation ± 5 % (Typical) (≥ 0.10xIn to 2xIn) AC Resistive 1250 VA V/I = 250/5
± 3 % (> 2xIn to 20xIn)
AC Inductive 250 VA V/I = 250/1@ p.f. ≤ 0.4
Frequency 50 Hz (Range: 45 Hz to 55 Hz)
DC Resistive 75 W V/I = 48/1.5; 110/0.7
60 Hz (Range: 54 Hz to 66 Hz)
DC Inductive 30 W V/I = 48/0.7; 110/0.3
Rated CT Burden ≤ 2.5 VA per phase and ≤ 0.2 VA earth (L/R ≤ 40 ms)
[measured at for 1 A CT input
Nominal Currents Mechanical/Electrical 10000 operations
≤ 3.0 VA per phase and ≤ 0.2 VA earth Endurance
(1 A and 5 A)] for 5 A CT input
BO 3 and BO 4 Output Contact Details
Binary Inputs Switching Voltage 250 V AC and 250 V DC
Contact current
Number 2 or 4 (via ordering option) rating:
BI Threshold/ BI Voltage Continuous 5 A AC or DC
Operating Range BI Operating range
rating
Short time 20 A AC or DC for 0.5 s
19 V DC 18 V DC to 66 V DC
30 A AC or DC for 0.2 s
88 V AC/DC 86 V DC to 252 V DC
71 V AC to 252 V AC Limiting Making
Capacity: 1000 W
Maximum AC/DC
(L/R ≤ 40 ms)
current for 3.5 mA
operation Limiting Breaking Capacity:
Pick Up Delay User selectable 0 to 600 s AC Resistive 1250 VA V/I = 250/5
(up to 10 min) AC Inductive 250 VA V/I = 250/1@ p.f. ≤ 0.4
Drop Off Delay User selectable 0 to 600 s DC Resistive 75 W V/I = 48/1.5; 110/0.7;
(up to 10 min) 220/0.3
Maximum cable < 10 m DC Inductive 30 W V/I = 48/0.7; 110/0.3;
length For larger cable length, always use a (L/R ≤ 40 ms) 220/0.14
multi-core screened or twisted pair
Mechanical/Electrical 10000 operations
(screened or unscreened) cables
Endurance

Siemens Protection Devices 8


Front Communication Port AC Dielectric IEC 60255-27#
voltage 2.0 kV AC RMS for 1 min
Quantity 1 (Between any terminal and earth,
independent circuits) ^
Electrical USB, Type B 1.0 kV AC RMS for 1 min
connection (across normally open contacts)
Protocol Support Modbus RTU, IEC 60870-5-103 Slow Damped IEC 60255-26
(via ordering option) Oscillatory Wave $ Common-mode:
Test voltage: 2.5 kV peak voltage
Rear Communication Port Differential mode:
Test voltage: 1.0 kV peak voltage
Test duration: 2 s
Quantity 1 (via ordering option) Source impedance: 200 Ω
Electrical RS485, 2 wire electrical, twisted pair Voltage oscillation frequency: 1 MHz
connection Repetition frequency: 400 Hz
Protocol Support Modbus RTU, IEC 60870-5-103 Electrostatic IEC 60255-26
Discharge 8 kV air discharge
Rate Data Transfer rate: 6 kV contact discharge
1200 bps to 57600 bps Electrical Fast Zone B
Transient or Burst $ Test severity Amplitude: ± 2 kV
Data Storage Repetition frequency: 5 kHz
IEC 60255-26
Fault Record 10 records Surge Immunity * $ Test Level : Zone A
(Trip Log) Line to Line : 0.5, 1, 2 kV
Line to Earth : 0.5, 1, 2, 4 kV
Events (Event Log) 100 events (1 ms resolution) Front time/Time to half-value : 1.2/50
µs
Source Impedance : 2 Ohm
Mechanical Tests Radiated Immunity IEC 60255-26
80 MHz to 1.0 GHz and
1.4 GHz to 2.7 GHz
Test Standard
Field strength: 10 V/m (RMS)
Degree of IEC 60529, Amplitude Modulated: 80 % AM
Protection IP52 front Conducted Radio IEC 60255-26
IP10 rear Frequency 150 kHz to 80 MHz,
Interference $ 10 V (RMS), Dwell time: 0.5 s
Vibration IEC 60255-21-1, Power Frequency IEC 60255-26
Response and Endurance, Class I Magnetic Field 30 A/m applied 1 min,
Shock and Bump IEC 60255-21-2, 300 A/m applied for 3 s
Shock response and withstand, Damped Oscillatory IEC 61000-4-10
Class I Magnetic Field 0.1 and 1.0 MHz,100 A/m
Bump, Class I value
Radiated Emissions IEC 60255-26
Seismic IEC 60255-21-3, Conducted IEC 60255-26
Class I Emissions
#
Contact IEC 60255-1, Thermal Withstand IEC 60255-27
Performance (Ref: Std IEC 61810-1) Continuous withstand: 2xIn
Short time withstand:
Test duration 1 s
Electrical Tests 50 A (1 A Current input)
150 A (5 A Current input)
Test Standard Functional IEC 60255-1 and IEC 60255-151
Performance
Insulation IEC 60255-27#
Resistance Insulation resistance >100 MOhm at Maximum IEC 60255-6
500 V DC Allowable Max. temperature limit +100 °C
Test Duration: > 5 s Temperature
(Between any terminal and earth, Gradual IEC 60255-26
independent circuits) ^ shutdown/Start-up Shut down/start up ramp 60 s
Impulse Voltage IEC 60255-27# test Power off 5 min
Withstand 5 kV, 1.2/50 µs, 0.5 J Power Frequency IEC 60255-26
5 +ve, -ve pulses Immunity Test ** Common-mode:
(Between all terminals and case earth • Test voltage: 300 V
and any two independent circuits) ^ • Coupling Resistor: 220 Ω
• Coupling Capacitor: 0.47 µF

Siemens Protection Devices 9


NOTE:
* Additional 50 ms DTL pick-up delay applied to binary Product Safety Test
inputs.

NOTE: Clearances and IEC/EN 60255-27: Edition 2


# All aspect of IEC 60255-5 have been covered under Creepage Distances ≥ 4 mm
IEC 60255-27.
IP Rating IEC/EN 60255-27: Edition 2
NOTE: IP52 (Front side)
^ Flag output and Pulse output are excluded between any IP10 (Rear side)
terminals and earth.
Impulse Voltage IEC/EN 60255-27: Edition 2
NOTE: 5 kV, 5 +ve, -ve pulses
$ Not applicable for Flag output and Pulse output.
AC Dielectric IEC/EN 60255-27: Edition 2
Voltage 2.0 kV AC, 50 Hz, 1 min
NOTE:
** DC binary input ports interfacing with cables whose total Insulation IEC/EN 60255-27: Edition 2
length is more than 10 m, need to have a multi core Resistance 500 V DC, > 5 s, >100 Mohm
twisted screened cable for providing immunity against Protective Bonding IEC/EN 60255-27: Edition 2
high level of power frequency interferences. Resistance < 12 V AC/DC, 1 min, < 0.1 Ohm
Protective Bonding IEC/EN 60255-27: Edition 2
Climatic Environmental Tests Continuity
Flammability IEC/EN 60255-27: Edition 2
Single Fault IEC/EN 60255-27: Edition 2
Temperature
Condition
IEC 60068-2-1/IEC 60068-2-2/IEC 60255-1

Ambient Operating
Temperature
-10 °C to + 60 °C Performance
Permissible
Temporary 50 Instantaneous & DTL OC&EF
Operating -40 °C to + 70 °C
Temperature, Operation Non-directional
(Tested for 16 h) *
Elements Phase, Derived Earth, Measured Earth
Storage Setting Range Is 0.2, 0.3, ..... 20.0xIn
Temperature -25 °C to + 70 °C (50/50N/50G)
(Non-operational) #
Time Delay 0,0.01,....600 s
Operate Level Iop 100 % Is, ± 5 %
NOTE:
* Applicable for the following: > 0.2xIn to 0.9xIn setting: ≥ 90 % Iop
Reset level
 Self powered relay with the rated current. > 1xIn to 20xIn setting: ≥ 94 % Iop
 Dual powered relay with the rated auxiliary voltage of Basic Operate time
110 V DC and above. (with auxiliary
power/load 2xIs 25 ms, ± 15 ms,
NOTE: current): 5xIs 20 ms, ± 15 ms
# To retain the battery life during the transportation and 50, 50G, 50N
storage, it is recommended to maintain the permissible Operate time delay Tbasic+Td, ± 1 % or ± 30 ms
temperature range from -20 °C to +45 °C. Inhibited by Binary Input or Inrush detector
Disengaging time < 50 ms *
Humidity
IEC 60068-2-30/IEC 60068-2-78/IEC 60255-1
NOTE:
* With auxiliary power supply
+ 25…55 °C, RH > 93 % RH
(6 cycles)
Damp heat test,
At lower temperature, 97 %, -2 %
Cyclic
+ 3 % RH
At upper temperature, 93 %, ± 3 % RH
Damp heat test,
Steady State 10 days at 93 ± 3 % RH, + 40 °C

Siemens Protection Devices 10


51 Time Delayed OC&EF Real Time Digital Simulation Test (RTDS)

Operation Non directional Trip Response at Fault current: 1.1, 2, 3, 5, 10


Elements Phase, Derived Earth, Measured different fault currents times of set value
Earth Influence on Accuracy Influence of DC components
Setting Range Is (51) 0.2, 0.21… 2.0xIn DC content at first peak: 100 %
Decay time: 25 ms, 50 ms,
Setting Range Is (51G) 0.06, 0.07...... 0.8xIn
100 ms
Setting Range Is (51N) 0.10, 0.11...... 0.8xIn
Immunity to inrush current *
Time Multiplier 0.01, 0.02.....10 2nd harmonic content: up to
Time Delay (DTL) 0.00, 0.01... 15 s 28 %
Operate Level 110 % Is, ± 5 % or ± 2%xIn Relay behaviour at primary CT
Reset level ≥ 90 % Iop saturation
Fault currents: 10 A, 20 A, 40 A
Operate time (with
auxiliary power/ load K Trip response at Fault Current: 2 times and
top = × Tm recurring faults 5 times of set value.
current) [ ]
I α
Is −1
Delay between recurring faults:
IEC  A 
top =  P + B  × Tm 300 ms, 1 s, 2 s
 [ Is ] − 1 
I

IEEE/ANSI ± 5 % or ± 50 ms #
NOTE:
Follower Delay 0.00, 0.01... 20 s * Applicable for 7SR4501-xGA10-1AA0 variants
Reset IEC/ANSI decaying, 0, 1... 60 s
Inhibited by Binary Input or Inrush detector Inrush Response Test

NOTE:
# Add current tolerance of ± 5 % or ± 2 %xIn (whichever is Test Conditions * Simulated Inrush current with
greater) to the operating time tolerance for TMS below 15 % 2nd harmonic content
0.1 and Is below 0.1xIn. Test Result * The immunity against inrush
currents is up to 3 times of the
50LC/SOTF (Switch-On-To-Fault) peak value with 95 %
fundamental current (Iset).
Setting range 1,2,....20xIn
Operate level 100 % Is, ± 5 % NOTE:
Disengaging time < 50 ms * Applicable for 7SR4501-xGA10-1AA0 variants
Inhibited by Binary Input or Inrush detector

For more information about 50LC/SOTF, refer to SOTF.

81HBL2 Inrush Detector

81HBL2 Inrush Setting


(Ratio of 2nd Harmonic 0.10, 0.15... 0.50xI
current to fundamental Where, I = I2/I1
component current)
81HBL2 Inrush Release
0.30, 0.4,.... 20xIn
Block
Will pick-up before operation
tbasic Element basic
of any protection element due to
operate time
magnetic inrush
Will operate until drop-off of any
Reset Time protection element due to
magnetic inrush

NOTE:
For better inrush accuracy, the fundamental current should
be minimum of 0.15xIn in at least one phase.

Siemens Protection Devices 11


Case Dimensions

105
78

130
108 Current Inputs

Additional
Binary Inputs

Additional
Binary Outputs

Rear
Communication
Port
168
185

Binary Inputs,
Binary Outputs,
Flag Output,

140
165
Pulse Output

Auxiliary Power
Supply

Fig 16a. Front View Fig 16b. Front View Fig 17. Rear View (Dual Powered Full Version)
(7SR4501/7SR4502) (7SR4503/7SR4504)

4.5 - 4 Holes

156
98.5

149
4.5 - 4 Holes
10.25 78 108
4.5

4.75 98.5
9.5

15 188 30
203
30 mm clearance for
Terminal Wiring

Fig 19a. Side View (7SR4501/7SR4502)


168
159

140
159

156
146

15 188 30
203
30 mm clearance for
Terminal Wiring

Fig 18a. Panel Cut-out View Fig 18b. Panel Cut-out View Fig 19b. Side View (7SR4503/7SR4504)
(7SR4501/7SR4502) (7SR4503/7SR4504)

Siemens Protection Devices 12


7SR4501/7SR4503 Terminal/Wiring Diagram

7SR4501/7SR4503 Terminal Label


X2 X1 1A/5A
1
+ve
1
- ve BI 1
2 IL1
+ve
3
2
4
-ve BI 2
1A/5A
5 3

NO 6

COM 7 IL2
BO1
NC 8
4

9 1A/5A
BO 2 5
10

11 IL3
12
6
+ve
13 1A/5A
7
-ve PO
14

IL4
+ve
15
GND -ve FO 8
16

NOTES
Items shown in BOLD are ordering options

Figure 20 Terminal Diagram of Self Powered (7SR4501-xGB10-1AA0) and (7SR4503-xGB10-1AA0)


Non-Directional Overcurrent and Earth Fault Relay with Flag
7SR4501/7SR4503 Terminal Label
X1 X5 1A/5A
1
1
+ve
-ve BI 1
2 IL1
3
+ve
BI 2 2
4 -ve
1A/5A
3

X2
NO 1 IL2
COM 2 BO1
4
NC 3
1A/5A 5
4
BO 2
5

6 IL3

6
X3
-ve 1A/5A
1 7

2 +ve PO
IL4

8 GND

NOTES
Items shown in BOLD are ordering options
Figure 21 Terminal Diagram of Self Powered (7SR4501-xGA10-1AA0) and (7SR4503-xGA10-1AA0) Non-Directional
Overcurrent and Earth Fault Relay without Flag

Siemens Protection Devices 13


7SR4504 Terminal/Wiring Diagram

7SR4502/7SR4504 Terminal Label

X5 X2 X1 1A/5A
1
+ve 1
+ ve
1

- ve BI 3 2
-ve BI1
2 IL1
3
+ ve
3
+ve - ve BI2 2
4
-ve BI 4
4
5
1A/5A
3

X6 NO 6

NO 1 COM 7 IL2
X4 BO1
1
COM 2
BO3 NC 8
TERM 4
NC 3
2 A/+ 9
RS485

BO2 1A/5A 5
4
10
3 GND 5
BO 4
11
4 B/- IL3
12

6
X3 + ve
13
1 L - ve PO 1A/5A 7
14

2
N
IL4
3 E 15 + ve
16 - ve FO
8
GND

NOTES
Items shown in BOLD are ordering options

Figure 22 Terminal Diagram of Dual Powered (7SR4502/7SR4504) Non-Directional Overcurrent and Earth Fault
Relay with Flag

Siemens Protection Devices 14


Ordering Information – 7SR45 Argus
Product description Variants Order No.

1 2 3 4 5 6 7 - 8 9 10 11 12 - 13 14 15 16
7SR45 Argus 7 S R 4 5 0 - 0 - 1 A A 0

Non-directional Overcurrent and Earth Fault Relay

Case, I/O and fascia


Size 4 Moulded Case, 4 CT1), 2 BI/2 BO, pulse output, 9 LEDs 1 G A/B
Size 4 Moulded Case, 4 CT1), 2 BI/2 BO, pulse output, 9 LEDs 1 H/J A
Size 4 Moulded Case, 4 CT1), 4 BI/4 BO, pulse output, 9 LEDs 2 H/J B
Size 4 Moulded Case (Height Reduced), 4 CT 1), 2 BI/2 BO, pulse output, 9 LEDs 3 G A/B
Size 4 Moulded Case (Height Reduced), 4 CT1), 2 BI/2 BO, pulse output, 9 LEDs 3 H/J A
Size 4 Moulded Case (Height Reduced), 4 CT 1), 4 BI/4 BO, pulse output, 9 LEDs 4 H/J B

Measuring Input
1 A, 50 Hz/60 Hz 1
5 A, 50 Hz/60 Hz 2

Auxiliary Voltage
Self Powered (CT Powered: BI Threshold 19 V DC) G 1
Dual powered (CT Powered+Aux.Powered:24 V to 60 V DC, BI threshold 19 V DC) H 2
Dual powered (CT Powered+Aux.Powered:60 V to 240 V AC/DC, BI threshold 88 V AC/DC) J 2

Front Fascia
Standard Version A
Standard Version - with Trip Flag Indicator B

Communication Options
Front port : USB 1
Front Port : USB and Rear Port: RS-485 supporting IEC 60870-5-103 and Modbus RTU (user
selectable setting) 2

Protection Function Packages - Standard version


50 Instantaneous phase fault overcurrent
50G/50N Instantaneous earth fault
51 Time delayed phase fault overcurrent A
51G/51N Time delayed earth fault
50LC/SOTF Switch-On-To-Fault
81 HBL2 2) 2nd Harmonic block/inrush restraint

Fixed Value (Reserved for future use) 0

Fixed Value (Reserved for future use) 1

Additional functionality
A
No additional functionality

Fixed Value (Reserved for future use) 0

1) 4CT is configured as 3PF + EF


2) Not available for 7SR4501-xGA10-1AA0 MLFB variants

Use the following ordering information to order 7SR45 Argus Self Powered/Dual Powered Non-Directional Overcurrent and
Earth Fault Relay battery spares.

Variants Description
7XG1900-1AA00-0AA0 Main Battery CR123A
7XG1900-2AA00-0AA0 RTC Battery CR1632
7XG1900-3AA00-0AA0 Main Battery CR123A + RTC Battery CR1632

Siemens Protection Devices 15


Published by and copyright © 2018
Siemens Protection Devices
P.O. Box 8
North Farm Road
Hebburn
Tyne & Wear
NE31 1TZ
United Kingdom
Phone: +44 (0)191 401 7901
Fax: +44 (0)191 401 5575
E-mail: marketing.spdl.gb@siemens.com

EMEA-C10020-00-76GB
November 2018

For enquires please contact our Customer Support Center


Phone: +49 180/524 7000 (24hrs)
Fax: +49 180/524 2471
E-mail: support.energy@siemens.com
www.siemens.com/protection

Subject to change without notice, Printed in the UK.

www. siemens.com/energy

Siemens Protection Devices 16